Daikin ETSH16P30D, ETSH16P50D, ETSX16P30D, ETSX16P50D, ETSHB16P30D Operation manuals

...
Page 1
Operating Instructions
RoCon+ HP
ETSH(B)16P30D ETSH(B)16P50D
ETSX(B)16P30D ETSX(B)16P50D
Operating Instructions
Daikin controller RoCon+ HP1
Betriebsanleitung
Daikin Regelung RoCon+ HP1
Manuel d'utilisation
Régulation Daikin RoCon+ HP1
Gebruiksaanwijzing
Daikin regeling RoCon+ HP1
Istruzioni per l'uso
Regolazione Daikin RoCon+ HP1
Driftsvejledning
Daikin regulering RoCon+ HP1
Instruktionsbok
Daikin reglerenhet RoCon+ HP1
Brukerveiledning
Daikin Regulering RoCon+ HP1
English
Deutsch
Nederlands
Italiano
Dansk
Svenska
Norsk
09/2019
Käyttöohje
Daikin-ohjaus RoCon+ HP1
Suomi
Page 2

List of contents

List of contents
1 General safety precaution 4
1.1 Particular safety instructions ..................................................... 4
1.1.1 Observing the instructions .......................................... 4
1.1.2 Meaning of warnings and symbols.............................. 5
1.2 Safety instructions for installation and operation....................... 5
1.2.1 General ....................................................................... 5
1.2.2 Intended use ............................................................... 5
2 Product description 6
2.1 Temporary shutdown................................................................. 6
3 Operation 7
3.1 General...................................................................................... 7
3.2 Display and operating elements ................................................ 7
3.2.1 Status display.............................................................. 7
3.2.2 Display ........................................................................ 7
3.2.3 Rotary button .............................................................. 7
3.2.4 Start screen................................................................. 7
3.3 Operating concept ..................................................................... 8
3.3.1 Navigating in the menu ............................................... 8
3.3.2 Help function............................................................... 9
3.3.3 Navigating in lists and selecting list entries................. 9
3.3.4 Setting setpoints ......................................................... 9
3.3.5 Setting the times ......................................................... 10
3.3.6 Calendar function........................................................ 10
3.3.7 Setting the time programs........................................... 10
3.3.8 External operation....................................................... 11
4 Function 12
4.1 Mode ......................................................................................... 12
4.2 User........................................................................................... 13
4.2.1 Room temperature setpoint setting............................. 13
4.2.2 Room temperature reduced setting ............................ 13
4.2.3 Room temperature absence setting............................ 13
4.2.4 Hot water temperature setpoint setting....................... 13
4.2.5 Unscheduled domestic hot water generation.............. 13
4.3 Time Program............................................................................ 13
4.3.1 Temporary time programs........................................... 13
4.3.2 Permanent time programs .......................................... 13
4.3.3 Time program reset..................................................... 14
4.4 Settings ..................................................................................... 14
4.4.1 Display settings........................................................... 15
4.4.2 System........................................................................ 15
4.4.3 Additional heat generators.......................................... 15
4.4.4 Inputs/Outputs............................................................. 15
4.4.5 Intelligent storage tank management.......................... 16
4.5 Configuration ............................................................................. 16
4.5.1 Access privileges (technician code)............................ 16
4.5.2 Sensors....................................................................... 17
4.5.3 HC configuration ......................................................... 17
4.5.4 Heating........................................................................ 17
4.5.5 Cooling........................................................................ 18
4.5.6 Domestic hot water ..................................................... 19
4.5.7 Additional program...................................................... 19
4.5.8 Configuration Wizard .................................................. 21
4.5.9 Parameter reset .......................................................... 21
4.6 Info ............................................................................................ 21
4.6.1 Current........................................................................ 21
4.6.2 Overview..................................................................... 22
4.6.3 Values......................................................................... 22
4.6.4 Water pressure ........................................................... 22
4.7 Error .......................................................................................... 22
4.8 Terminal .................................................................................... 22
4.8.1 Selecting the terminal address.................................... 23
4.8.2 Bus-Scan for terminal function.................................... 23
4.9 Statistics ..................................................................................... 24
4.9.1 Month........................................................................... 24
4.9.2 Total............................................................................. 24
5 Initial commissioning 25
5.1 Configuration Wizard.................................................................. 25
5.2 Menu navigation in the Configuration Wizard............................. 25
6 Parameter overview 26
6.1 Menu: Operating mode............................................................... 26
6.2 Menu: User................................................................................. 26
6.3 Menu: Time program .................................................................. 26
6.4 Menu: Settings ........................................................................... 26
6.5 Menu: Configuration ................................................................... 27
6.6 Menu: Information ...................................................................... 27
6.7 Menu: Error ................................................................................ 27
6.8 Menu: Terminal .......................................................................... 27
6.9 Menu: Statistics .......................................................................... 28
7 Parameter settings 29
7.1 Explanation of the parameter tables........................................... 29
7.2 Operating mode.......................................................................... 29
7.3 User............................................................................................ 30
7.3.1 Menu: Room temperature target.................................. 30
7.3.2 Menu: Reduce room temperature................................ 30
7.3.3 Menu: Room temperature absent ................................ 30
7.3.4 Menu: Hot water temperature, target........................... 30
7.3.5 Menu: 1 x hot water ..................................................... 30
7.4 Time Program............................................................................. 31
7.5 Settings ...................................................................................... 32
7.5.1 Menu: Display settings................................................. 32
7.5.2 Menu: System.............................................................. 32
7.5.3 Menu: External heat source......................................... 33
7.5.4 Menu: Inputs/Outputs................................................... 34
7.5.5 Menu: Intelligent Storage Mgmt................................... 36
7.6 Configuration .............................................................................. 37
7.6.1 Menu: Sensors............................................................. 37
7.6.2 Menu: Heating circuit config......................................... 38
7.6.3 Menu: Heating.............................................................. 38
7.6.4 Menu: Cooling.............................................................. 40
7.6.5 Menu: Hot water........................................................... 40
7.6.6 Menu: Additional programs.......................................... 42
7.7 Information ................................................................................. 43
7.7.1 Overview...................................................................... 43
7.7.2 Values.......................................................................... 44
7.7.3 Water pressure ............................................................ 44
7.8 Error ........................................................................................... 45
7.9 Terminal ..................................................................................... 45
7.10 Statistics ..................................................................................... 45
7.11 Configuration wizard................................................................... 46
8 Faults and malfunctions 47
8.1 Emergency operation ................................................................. 47
8.2 Manual Operation....................................................................... 47
8.3 Error protocol.............................................................................. 47
8.4 Error screen................................................................................ 47
8.5 Error codes................................................................................. 48
9 Mixer module 49
9.1 Mixer module start screen (terminal function) ............................ 49
9.2 Mixer valve parameter overview................................................. 49
9.3 Mixer module parameter settings ............................................... 51
10 Glossary 52 11 User-specific settings 53
11.1 Switching time program .............................................................. 53
11.2 Parameters ................................................................................. 54
11.3 Data bus addresses ................................................................... 54
12 Notes 55

Operating Instructions

2
Daikin controller RoCon+ HP1
Daikin RoCon+ HP
008.1447899_00 – 09/2019 – EN
Page 3
List of keywords 56
List of contents
Daikin RoCon+ HP Daikin controller RoCon+ HP1
008.1447899_00 – 09/2019 – EN
Operating Instructions
3
Page 4

1 General safety precaution

1 General safety precaution

1.1 Particular safety instructions

WARNING
Heating devices that are not set up and installed correctly can impair the func­tion of the heating device and/or cause serious or fatal injury to the user.
▪ Work on the heat generator (such as
set-up, servicing, connection and ini­tial commissioning) must only be carried out by persons who are au­thorised and who have successfully completed qualifying technical or vo­cational training and who have taken part in advanced training sessions recognised by the relevant respons­ible authorities for the specific activ­ity. They include, in particular, certi­fied heating engineers, qualified electricians and HVAC specialists who, because of their professional training and their expert knowledge, have experience in the professional installation and maintenance of heat­ing systems, oil and gas installations and hot water storage systems.
▪ Only operate the heat generator
when it is in perfect condition with the protective hood closed.
WARNING
Disregarding the following safety in­structions may result in serious phys­ical injury or death.
▪ This device may only be used by
children aged 8 and above and by persons with restricted physical, sensory or mental capabilities or with a lack of experience and knowledge if they are under supervision or if they have been instructed in the safe use of the equipment and under­stand the dangers arising from it. Children must not play with the device. Cleaning and user mainten­ance must not be carried out by chil­dren without supervision.
▪ Establish the power supply in ac-
cordance with IEC60335-1 via a separator device which exhibits con­tact separation in all poles with a contact opening distance that provide full disconnection in accord­ance with overvoltage category III.
▪ All electrical work must only be car-
ried out by electrically qualified ex­perts and with consideration of the local and national regulations and the instructions in this manual. Ensure that a suitable electrical cir­cuit is used. Insufficient load capacity of the elec­trical circuit or improperly executed connections can result in electric shock or fire.
Operating Instructions
4
1.1.1 Observing the instructions
▪ The original documentation is written in German. All other lan-
guages are translations.
▪ Please read this manual carefully and thoroughly before proceed-
ing with the installation or modification of the heating system.
▪ The precautionary measures described in this document cover
very important topics. Follow them meticulously.
▪ The installation of the system and all activities described in this
manual and the applicable documents for the installer must be carried out by an approved installer.
Documentation set
This document is part of a documentation set of other applicable documents.The complete set comprises:
▪ Installation instructions for the indoor unit (format: paper – in-
cluded in the indoor unit scope of delivery)
▪ Operating instructions for the indoor unit (format: paper – included
in the indoor unit scope of delivery)
Daikin RoCon+ HP
Daikin controller RoCon+ HP1
008.1447899_00 – 09/2019 – EN
Page 5
1 General safety precaution
▪ Operating manual for the heat pump (format: paper – included in
the indoor unit scope of delivery)
▪ Installation instructions for the outdoor unit (format: paper – in-
cluded in the outdoor unit scope of delivery)
▪ Installation instructions for optional components (format: paper –
included in the scope of delivery of the respective component)
▪ Reference manual for the installer of the indoor unit (format: di-
gital)
▪ Reference manual for the installer of the outdoor unit (format: di-
gital)
The reference manuals contain the complete set of technical data, a detailed description of best practices and information on mainten­ance, troubleshooting and decommissioning.
The digital documents and the latest editions of the supplied docu­mentation are available on the regional Daikin website or, on re­quest, from your dealer. The Daikin website is easy to access using the QR code on your device.
1.1.2 Meaning of warnings and symbols
Warnings in this manual are classified according to their severity and probability of occurrence.
DANGER
Indicates an immediate danger. Disregarding this warning can lead to serious injury or
death
WARNING
Indicates a potentially dangerous situation Disregarding this warning may result in serious physical in-
jury or death.
CAUTION
Indicates a situation which may cause possible damage Disregarding this warning can cause damage to property
and the environment and result in minor injuries.
Avoiding danger
The Daikin Altherma ETS(X/H) is state of the art and is built in ac­cordance with all recognised technical regulations. However, im­proper use may result in serious physical injuries or death, as well as property damage.
To avoid hazards, only operate the Daikin Altherma ETS(X/H): ▪ as stipulated and in perfect condition, ▪ with an awareness of safety and the dangers involved. This assumes knowledge and use of the contents of this manual, all
applicable documents, the relevant accident prevention regulations as well as the recognised safety-related and occupational health rules.
Display of the RoCon+ controller
Certain screen displays or menu items may deviate from those shown in these instructions depending on the national or equipment variant of the Daikin Altherma ETS(X/H) or the user status logged onto the controller.
1.2.2 Intended use
The RoCon+ HP controller must only be used in Daikin Altherma ETS(X/H) heat pumps that are approved for the regulating system. The RoCon+ HPcontroller must only be operated in accordance with the specifications in these instructions.
Any other use outside the intended use is considered as improper. The operator alone bears responsibility for any resulting damage.
For any work on the equipment that extends above and beyond the operation of the regulating system, the details provided in the sup­plementary documents must be observed, particularly with regard to safety instructions.
Documentation
The technical documentation included in the scope of supply is a constituent part of the equipment. It must be stored in such a way that it can be consulted at any time by the operator or technicians.
This symbol identifies user tips and particularly useful in­formation, but not warnings or hazards
Special warning signs
Some types of danger are represented by special symbols.
Electric current
Risk of burns or scalds
General description 1 Handling instructions are shown as a list. Actions where the se-
quential order must be adhered to are numbered.
è Results of actions are identified with an arrow. [Operating mode]: Parameters are shown in square brackets. [→Main menu]: The position of menus and functions is shown in
square brackets with →.
1.2 Safety instructions for installation
and operation
1.2.1 General
▪ For any work on the equipment, which extends above and beyond
the operation of the regulating system, the details provided in the supplementary documents must be observed, particularly with re­gard to safety instructions.
Daikin RoCon+ HP Daikin controller RoCon+ HP1
008.1447899_00 – 09/2019 – EN
Operating Instructions
5
Page 6

2 Product description

2 Product description
INFORMATION
The RoCon+ HP controller is part of the Daikin Altherma ETS(X/H).
It consists of theswitching panel PCB RoCon BM2Cto which the actuators and sensors as well as other compon­ents in the regulating system are connected and the oper­ating unit RoCon+ B1.
These operating instructions only explain the functions and possible settings of the controller. More detailed informa­tion on other device components can be found in the other applicable documents.
The electronic, digital controller is able to automatically control all heating and hot water functions for a direct heating circuit, a storage loading circuit and also further heating circuits via optionally connect­ible mixer modules, depending on the heating device.
It undertakes all safety management for the Daikin Altherma ETS(X/ H). In the event of a water shortage or undefined operating states, this executes a safety switch-off. A corresponding error message shows the operator all the information regarding fault causes.
All function settings for the Daikin Altherma ETS(X/H) and the op­tional RoCon devices that are connected via the data bus are under­taken with the control elements of the integrated RoConB1 control panel and shown on the plain text display with coloured backlighting.
The following additional, optional devices can be connected to the Daikin Altherma ETS(X/H) via the controller data bus:
▪ Room controller EHS157034 ▪ EHS157068 mixer module In addition, the RoCon+ HP controller has a frost protection function
for the direct heating circuit and the storage tank charging circuit as well as an automatic function for heating support (integration of an additional heat source such as a wood-burning boiler or solar sys­tem).
The potential-free AUX switching contact can be used to carry out different control functions in conjunction with external devices (re­quest from an external heat generator, switching to bivalent operat­ing mode, external status display, etc.).
In addition, it also has several inputs for assessing external control contacts (external operating mode switching or heat request, Smart Grid and low rate EVU functions
The optional outside temperature sensor installed on the north side of the building can be used to further optimise the weather-com­pensated feed temperature controller.
If the optional EHS157056 gateway is installed and connected to the Internet, the Daikin Altherma ETS(X/H) can be conveniently mon­itored and operated by remote control using a mobile phone (app).
Initial commissioning of the heating system is described in the in­stallation instructions for the Daikin Altherma ETS(X/H).
Certain menu items of the RoCon+ HP controller are only accessible to the heating expert. This security measure ensures that no un­desirable malfunctions arise during operation of the system through incorrect settings.
All settings for the allocated heating circuit can be carried out in the same way as the operating unit. If the terminal function is activated, all operating possibilities that are available on the integrated operat­ing unit are available with the exception of certain special functions (e.g. manual operation).
After appropriate assignment, a connected EHS157068 mixer mod­ule is also operated using the RoCon+ B1 control panel and/or the EHS157034 room station.
(1)
).

2.1 Temporary shutdown

CAUTION
A heating system that is shut down can freeze in the event of frost and may suffer damage.
▪ Drain the heating system that is shut down if there is
danger of frost.
▪ If the heating system is not drained, the power supply
must be ensured and the external main switch must re­main switched on if there is a danger of frost.
If the indoor unit is not required for a lengthy period, it can be tem­porarily decommissioned.
However, we recommend not to disconnect the system from the power supply but merely to switch it to "Standby mode" (see Control­ler operating instructions).
The system is then protected from frost. The pumps and valve pro­tection functions are active.
If it is not possible to guarantee the power supply when there is danger of frost,
▪ completely drain the indoor unit on the water side, or ▪ apply suitable antifreeze measures to the connected heating sys-
tem and hot water storage tank (e.g. draining).
INFORMATION
If there is a danger of frost for only a few days with uncer­tainly in the gas and power supply, the oes not need to be drained because the heat insulation is very good as long as the storage tank temperature is observed regularly and does not fall below + 3°C.
However, this provides no frost protection for the connec­ted heat distribution system.
(1)
The energy supply company (EVU) sends signals that are used for controlling the power mains loading and that have an influence on the cost of the power and availability.
Operating Instructions
6
Daikin controller RoCon+ HP1
Daikin RoCon+ HP
008.1447899_00 – 09/2019 – EN
Page 7

3 Operation

3 Operation

3.1 General

DANGER: RISK OF ELECTROCUTION
If electrical components come into contact with water, this can cause an electric shock as well as cause potentially fatal burns or injuries.
▪ The displays and keys of the control unit must be pro-
tected against the effects of moisture.
▪ To clean the control unit, use a dry cotton cloth. The
use of aggressive cleaning agents and other fluids can cause damage to devices or lead to an electric shock.
INFORMATION
The Daikin Altherma ETS(X/H) makes the most effective use of energy at the lowest possible return and hot water target temperatures.
If an external heat generator (e.g. the optional backup heater) is activated at feed target temperatures above 50°C, the efficiency (COP) of the Daikin Altherma ETS(X/ H) can deteriorate (depending on the outside temperature).

3.2 Display and operating elements

LED Mode Description
Flashes red Error A malfunction occurred. For fur-
ther details, see Chap. 8.
Tab.3-1 Status display
3.2.2 Display
During normal operation the display is deactivated (completely dark). The activity of the system is indicated by the status display. Each press of the rotary button (turn, press or hold) activates the display with the start screen.
If the start screen is active and no user input is made for 60seconds, the display is deactivated. If no input is made by the user at any other point in the menu for 120seconds, the system re­turns to the start screen.
3.2.3 Rotary button
CAUTION
Never operate the operating elements of the controller with a hard, pointed object. This can cause damage and can cause the controller to malfunction.
The rotary button can be used to navigate in the respective level, to select or change the setting value and to accept this change with a short key press.
Action Result
Turning Select menu, select setting, make setting
Press Confirm selection, accept setting, execute func-
tion.
Fig.3-1 RoCon+ HP display and operating elements
1 Status display 2 Display 3 Rotary button
3.2.1 Status display
The LEDs of the status indicator light up or flash to indicate the oper­ating mode of the device.
LED Mode Description
Flashes blue STANDBY The device is not in operation. Lights up blue Operation The device is in operation.
Press for 2sec. Exit menu
Tab.3-2 Function of the rotary button
3.2.4 Start screen
The start screen provides an overview of the current operating status of the system. From the start screen, any operation of the rotary switch (turn, press or hold down) leads to the Main menu.
Daikin RoCon+ HP Daikin controller RoCon+ HP1
008.1447899_00 – 09/2019 – EN
Fig.3-2 Display position on the start screen
Operating Instructions
7
Page 8
3 Operation
Item Icon Explanation
1 Date and time 2 Error message
3 Only with connected room unit: Room temperat-
ure
4 Hot water temperature
5 Floor heating feed temperature
Convector heating feed temperature
Radiator heating feed temperature
6 Outside temperature 7 Pressure in the heating circuit 8 Storage tank without heating rod
Storage tank with connected heating rod (off)
Storage tank with connected heating rod (on)
Item Icon Explanation
11 Special program: Party
Special program: Absent
Special program: Holiday
Special program: Public holiday
Special program: 1 x hot water
Special program: Screed
Special program: Ventilation
12 Quiet mode on
13 Operating mode: Heating
Operating mode: Cooling
Operating mode: Hot water
9 No outdoor unit detected
Outdoor unit present, compressor off
Outdoor unit present, compressor on
10 Operating mode: Standby
Operating mode: Reduce
Operating mode: Heating
Operating mode: Cooling
Operating mode: Summer
Operating mode: Automatic 1
Operating mode: Automatic 2
Operating mode: Emergency
Operating mode: Defrost
Operating mode: No request
14 Ext External operating mode switched (Burner block-
ing contact or Room thermostat)
Tab.3-3 Display icons on the start screen
INFORMATION
If the local control panel is used as a remote control for a mixer module, both the standard screen and the menu structure are changed (see Chap. 9).

3.3 Operating concept

The operating concept of the controller enables fast navigation in the menu, clear display of information and convenient selection of para­meters as well as the setting of setpoints and programs.
The basics of the operating concept are described in detail below us­ing a few examples. The operation of special functions follows the same principle and is described in the corresponding sections if re­quired in Chap. 4.
3.3.1 Navigating in the menu
From the start screen, any operation of the rotary switch (turn, press or hold down) leads to the main menu. The menu view consists of an upper area for the menu icons of the various submenus and the lower menu bar. The Back and Help icons are displayed in the menu bar. Use the rotary button to switch between the icons (including the icons in the menu bar). Multi-page menus are indicated by the page break arrow. Use the rotary button to switch between the menu icons on the different menu pages.
Operating Instructions
8
Daikin controller RoCon+ HP1
Daikin RoCon+ HP
008.1447899_00 – 09/2019 – EN
Page 9
3 Operation
3.3.3 Navigating in lists and selecting list entries
Lists exist as pure information lists or can be used to select a list entry. Turning the rotary button switches between the list entries. Multi-page lists are indicated by the page break arrow. Turn the rotary button to switch between the list entries of the different pages.
In the case of selection lists, the currently selected list entry is indic­ated by a tick. Click "OK" to select another list entry. The corres­ponding setting is then accepted and the list is exited.
Fig.3-3 Example: Elements in a two-page menu
1 Back icon 2 Menu bar 3 Menu icon 4 Page change arrow (for multi-page menus) 5 Help icon
Example: In the "Statistics" menu, change [→Main menu]: 1 Turn the rotary button clockwise until the "Statistics" icon (on the
second menu page) turns blue.
2 Briefly press the rotary button to confirm ("OK").
è The "Statistics" submenu is called up
3.3.2 Help function
A help text is available for each menu icon.
Fig.3-5 List with selected list entry
Example: Switch the operating mode to "Summer" [→Main menu →Operating mode]
1 Turn the rotary button clockwise until the "Summer" list entry is
displayed in blue.
2 Briefly press the rotary button to confirm ("OK").
è The box is ticked in the "Summer" list entry.
3 Turn the rotary button anticlockwise until the Back icon turns
blue.
4 Briefly press the rotary button to confirm ("OK").
è The setting is saved and the setting level is exited.
Fig.3-4 Help function
Example: Call up the help text for the "Hot water" menu and stop the help function again [→Main menu →User]:
1 Turn the rotary button clockwise until the help icon in the menu
bar turns blue.
2 Briefly press the rotary button to confirm ("OK").
è The help function becomes active, the "?" symbol is dis-
played on the last menu icon.
3 Turn the rotary button anticlockwise until the "?" symbol appears
on the "Hot water" icon.
4 Briefly press the rotary button to confirm ("OK").
è The help text for the "Hot water" is displayed.
5 Briefly press the rotary button to confirm ("OK").
è Exits the help text level.
6 Turn the rotary button clockwise until the help icon in the menu
bar turns blue.
7 Briefly press the rotary button to confirm ("OK").
è The help function is terminated.
3.3.4 Setting setpoints
The setpoint of a parameter can be changed within the displayed scale. Press "OK" to save the new value. Press and hold the rotary button to exit the setting level without saving. For some parameters there is an "Off" setting in addition to values on the scale. This set­ting can be selected by turning the rotary button anticlockwise after the minimum value of the scale has been reached.
Daikin RoCon+ HP Daikin controller RoCon+ HP1
008.1447899_00 – 09/2019 – EN
Operating Instructions
9
Page 10
3 Operation
7 Briefly press the rotary button to confirm ("OK").
è The setting is saved and the setting level is exited.
3.3.6 Calendar function
The calendar function is used to set the current date or the [Holiday] and [Public holiday] time programs. The calendar function allows the selection of a time period for the time programs.
Fig.3-6 Display of the parameter setting
1 Minimum value 2 Default value 3 Currently selected value 4 Maximum value
Example: Set [Room temperature target 1] to 22°C [→Main menu
→User →Room →Room temperature target 1]:
1 Turn the rotary button clockwise until 22°C is displayed. 2 Briefly press the rotary button to confirm ("OK").
è The setting is saved and the setting level is exited.
3.3.5 Setting the times
The clock function is used to set the current time.
Fig.3-7 Setting the times
Example: Set the time to 16:04 [→Main menu →Settings →Dis­play →Time]:
1 Turn the rotary button clockwise until the circle is displayed in
blue.
2 Briefly press the rotary button to confirm ("OK").
è The hour hand is displayed in blue.
3 Turn the rotary button clockwise until 16:00 is displayed. 4 Briefly press the rotary button to confirm ("OK").
è The minute hand is displayed in blue.
5 Turn the rotary button clockwise until 16:04 is displayed. 6 Briefly press the rotary button to confirm ("OK").
è The Confirm icon in the menu bar is displayed in blue.
Fig.3-8 Setting the period with the calendar function
Example: Set [Holiday] from 25thAugust,2018 – 2ndSeptem­ber,2018 [→Main menu → Time program →Holiday]:
1 Turn the rotary button clockwise until the month selection is
Aug2018.
2 Briefly press the rotary button to confirm ("OK").
è August 1 is shown with a blue border.
Turn the rotary button clockwise until 25th August is highlighted in blue.
3 Briefly press the rotary button to confirm ("OK").
è August 25 is shown on a grey background.
4 Turn the rotary button clockwise until 2nd September is high-
lighted in blue.
5 Briefly press the rotary button to confirm ("OK").
è The setting is saved and the setting level is exited.
When a new holiday period is set, the previously set holiday period is automatically deleted. Alternatively, the holiday setting can also be reset.
Example: Reset the holiday setting [→Main menu → Time program →Holiday]:
6 Turn the rotary button clockwise until the month selection is dis-
played in blue.
7 Briefly press the rotary button to confirm ("OK").
è The last selected day of the holiday is displayed with a blue
border.
8 Turn the rotary button anticlockwise until all days are shown in
white.
9 Briefly press the rotary button to confirm ("OK").
è The holiday setting is reset and the setting level is exited.
3.3.7 Setting the time programs
The time program function is used to set permanent time programs (see Chap. 4.3.2). This allows the daily setting of 3 switching cycles. The times can be entered separately for each individual weekday or in blocks of "Monday to Friday", "Saturday to Sunday" and "Monday to Sunday". The selected switching cycles are highlighted in grey (Fig. 3-9) in the overview level of the respective program.
Operating Instructions
10
Daikin controller RoCon+ HP1
Daikin RoCon+ HP
008.1447899_00 – 09/2019 – EN
Page 11
3 Operation
Time period Switching cycle
Single day of the week (Monday, Tuesday ...)
Working week (Monday to Fri­day)
Weekend (Saturday to Sunday) 1. 06:00 to 22:00
Entire week (Monday to Sunday) 1. 06:00 to 22:00
Tab.3-4 Structure of the permanent time programs
INFORMATION
Time settings for a switching cycle in a weekday or block program will also be accepted for other time periods as long as they are for the same weekdays.
▪ The starting time in the first switching cycle is changed
from 06:00 am to 05:00 am for the individual weekday "Monday". In the period " Monday to Friday" and "Monday to Sunday", the first switching cycle is auto­matically changed from 06:00 to 05:00.
Fig.3-9 Time program function with overview level (left) and set-
ting level (right)
Example: For the [Heating circuit auto. 1] program, set switch cycles 1 and 2 for Monday to Friday [→Main menu →Time program →HC auto 1]:
1 Turn the rotary button clockwise until the Setting icon turns blue. 2 Briefly press the rotary button to confirm ("OK").
è Display changes to setting level with blue flashing period se-
lection.
3 Turn the rotary switch clockwise until the required time period is
displayed.
4 Briefly press the rotary button to confirm ("OK").
è The display changes to the input window for the start time of
the first switching cycle.
5 Briefly press the rotary button to confirm ("OK").
è Input window for start time of the first switching cycle flashes
blue.
6 Turn the rotary button clockwise until the required start time is
displayed.
7 Briefly press the rotary button to confirm ("OK").
è The display changes to the input window for the end time of
the first switching cycle.
8 Turn the rotary button clockwise until the required end time is
displayed.
9 Briefly press the rotary button to confirm ("OK").
è The display changes to the input window for the start time of
the second switching cycle.
1. 06:00 to 22:00
2. xx:xx to xx:xx
3. xx:xx to xx:xx
1. 06:00 to 22:00
2. xx:xx to xx:xx
3. xx:xx to xx:xx
2. xx:xx to xx:xx
3. xx:xx to xx:xx
2. xx:xx to xx:xx
3. xx:xx to xx:xx
10 Briefly press the rotary button to confirm ("OK").
è Input window for the start time of the second switching cycle
flashes blue.
11 Turn the rotary button clockwise until the required start time is
displayed.
12 Briefly press the rotary button to confirm ("OK").
è The display changes to the input window for the end time of
the second switching cycle.
13 Turn the rotary button clockwise until the required end time is
displayed.
14 Briefly press the rotary button to confirm ("OK").
è The display changes to the input window for the start time of
the third switching cycle.
15 Turn the rotary button clockwise until the Confirm icon turns
blue. è The display changes to the Confirm icon.
16 Briefly press the rotary button to confirm ("OK").
è The programming is saved. è The setting level is exited. è Selected switching cycles are highlighted in grey.
17 Turn the rotary button anticlockwise until the Back icon turns
blue.
18 Briefly press the rotary button to confirm ("OK").
è The menu is exited
3.3.8 External operation
In addition to operation via the integrated RoCon+ HP controller, the system can also be adjusted and operated via external devices.
Operation via the Internet
An optional gateway (EHS157056) can be used to connect the Ro­Con+ HP controller to the Internet. This enables remote control of the RoCon+ HP by mobile phone (using an app).
Operation via the room station
It can also be operated via the optional EHS157034 room controller. For this purpose, observe the operating instructions enclosed with the device.
Daikin RoCon+ HP Daikin controller RoCon+ HP1
008.1447899_00 – 09/2019 – EN
Operating Instructions
11
Page 12

4 Function

4 Function
The system fully automatically controls the operation of the room heating, room cooling and domestic hot water preparation on the sanitary side on the basis of the specifications set in the RoCon+ HP controller. The functions that can influence system operation are de­scribed below.
Some of the functions and parameters described are restricted by access rights and can only be set by a heating specialist (see
Chap. 4.5.1).

4.1 Mode

[→Main menu →Operating mode] This menu is used to select the operating mode for operating the
device. The current operating mode is indicated by a corresponding symbol on the start screen.
Standby operating mode (Standby)
NOTICE
A heating system that is not protected against frost can freeze in the event of frost and thus be damaged.
▪ Drain the heating system on the water side if there is a
danger of frost.
▪ If the heating system is not drained, the power supply
must be ensured and the mains switch must remain switched on if there is a risk of frost.
In this operating mode, the Daikin Altherma ETS(X/H) is switched to standby mode. The frost protection function remains unchanged. In order to maintain this function, the system must not be disconnected from the mains.
All controllers integrated in the RoCon system via the CAN bus are primarily also switched to the "Standby" operating mode.
INFORMATION
In the [Standby] operating mode, the heat pump and the optionally connected backup heater are disconnected from the power supply (energy-saving mode) if the following conditions are met:
▪ the outside temperature sensor is connected and cor-
rectly parametrised in the system configuration ▪ the outside temperature is more than 8°C ▪ there is no heating request ▪ the frost protection function is not active in any connec-
ted HC and ▪ the Daikin Altherma ETS(X/H) has been switched on
for at least 5minutes.
Reduce operating mode
Reduced heating operation (lower room target temperature) accord­ing to the set reduction temperature in the [Reduce room temperat­ure] parameter (see Chap. 4.2).
Domestic hot water preparation according to the feed target temper­atures and switching cycles in the [Hot water auto. 1] hot water time program (see Chap. 4.2).
Heating operating mode
Heating, cooling mode according to the room target temperature set in the [Room temperature target 1] parameter (see Chap. 4.2).
A connected outside temperature sensor (weather-compensated feed temperature control) or a connected room controller also influ­ence the target temperature.
Domestic hot water preparation according to the feed target temper­atures and switching cycles in the [Hot water auto. 1] hot water time program (see Chap. 4.2).
Summer operating mode
Only domestic hot water preparation according to the set target tem­peratures and switching cycles is carried out in the [Hot water auto. 1] hot water time program (see Chap. 4.2).
All controllers integrated in the RoCon system via the CAN bus are also switched to the higher-level [Summer] operating mode.
Automatic 1 operating mode (time program)
Automatic heating and setback mode according to the permanent time programs (see Chap. 4.3):
▪ [Heating circuit auto. 1] ▪ [Hot water auto. 1]
Automatic 2 operating mode (time program)
Automatic heating and setback mode according to the permanent time programs (see Chap. 4.3):
▪ [Heating circuit auto. 2] ▪ [Hot water auto. 2]
INFORMATION: SWITCHING CONTACT FOR EX­TERNAL OPERATING MODE CHANGEOVER
Switching can also be performed from an external device (e.g. modem, ...) via a floating switching contact connected to terminal J8 of the Daikin Altherma ETS(X/H) to the "Ext" terminals. See Tab. 4-1.
In this case, the switching contact functionality is depend­ent on the parameter [Func. burner blocking contact]:
▪ [Func. burner blocking contact] = Resistance values
(default setting): Evaluation of the resistance values.
▪ [Func. burner blocking contact] = Burner blocking con-
tact: Evaluation as a burner blocking contact. If the switching contact is closed, the external heat generator has priority.
Operating mode Resistance Tolerance
Standby <680Ω ±5%
Heating 1200Ω Reduce 1800Ω
Summer 2700Ω Automatic 1 4700Ω Automatic 2 8200Ω
Tab.4-1 Resistance values for evaluating the EXT signal
INFORMATION
The resistances specified in Tab. 4-1 in a tolerance field of 5%. Resistances outside this tolerance field are interpreted as an open input. The heat generator switches back to the previously active operating mode.
The input is not considered for resistance values greater than the value for "Automatic 2".
If several switching contacts are connected to the Daikin Altherma ETS(X/H) (e.g. smart grid, room thermostat), the associated functions may have a higher priority than the external mode switching. The operating mode requested by the EXT switching contact is then possibly not activated or is only activated later.
Besides these operating modes, different temporary time programs (see Tab. 4-2) are available that are carried out with priority after ac­tivation.
Operating Instructions
12
Daikin controller RoCon+ HP1
Daikin RoCon+ HP
008.1447899_00 – 09/2019 – EN
Page 13
4 Function
Temporary heating
program
Party Time program Chap. 4.3
Absent
Public holiday
Holiday Screed Configuration Chap. 4.5.7
Tab.4-2 Overview of temporary time programs
INFORMATION
If a temporary heating program (Party, Absent, Public holi­day, Holiday, Screed) is started during the selected operat­ing mode, control is carried out primarily according to the settings for this time program.
Setting/activation in
the menu
Information

4.2 User

[→Main menu →User] The most important target temperatures and functions are set for the
user in this menu.
4.2.1 Room temperature setpoint setting
[→Main menu →User →Room] The room target temperatures for room heating in Heating mode are
defined in this menu. The available setpoints (1-3) belong to the re­spective cycle (1-3) of the [Heating circuit auto. 1] and [Heating cir­cuit auto. 2] time programs.
Further explanations and possible settings for this menu can be found in Chap. 7.3.
4.2.2 Room temperature reduced setting
[→Main menu →User →Reduce] The room target temperatures for room heating in Reduced mode
are defined in this menu. The reduced operation is carried out by the "Reduce" operating mode or by the [Heating circuit auto. 1] and [Heating circuit auto. 2] time programs.
Further explanations and possible settings for this menu can be found in Chap. 7.3.
4.2.3 Room temperature absence setting
[→Main menu →User →Absent] The room target temperature for room heating in Absence mode are
defined in this menu. The absence operation is carried out by the [Absent] or [Holiday] time programs.
Further explanations and possible settings for this menu can be found in Chap. 7.3.
4.2.4 Hot water temperature setpoint setting
[→Main menu →User →Hot water] The hot water target temperatures for domestic hot water prepara-
tion are defined in this menu. The available setpoints (1-3) belong to the respective cycle (1-3) of the [Hot water auto. 1] and [Hot water auto. 2] time programs.
Further explanations and possible settings for this menu can be found in Chap. 7.3.
4.2.5 Unscheduled domestic hot water generation
[→Main menu →User →1x load]
By starting this function, the hot water can be heated up to the [Hot water temperature target 1] target temperature at any time. The heating up is carried out with priority and independent of other heat­ing programs. After this temporary function has elapsed, the control unit automatically jumps back to the previously active operating mode.
Possible settings for this menu can be found in Chap. 7.3.

4.3 Time Program

[→Main menu →Time program] Various freely adjustable permanent time programs are available for
convenient and individual room and hot water temperature control. Temporary time programs are also available, which override the per­manent time programs or the currently set operating mode for the duration of their validity.
4.3.1 Temporary time programs
INFORMATION
The following temporary time programs can be cancelled at any time due to the manual changing of the operating mode.
Party
[→Main menu →Time program →Party] The program runs from activation until the end of the set period. Dur-
ing this time, the HC is controlled to the temperature set in the [Room temperature target 1] parameter. If the [Automatic 1] or [Auto­matic 2] time program is active, the heating cycle is extended or star­ted prematurely. The domestic hot water preparation is not affected.
Absent
[→Main menu →Time program →Absent] The program runs from activation until the end of the set period. Dur-
ing this time, the HC is controlled to the room target temperature in the [Room temperature absent] parameter. The domestic hot water preparation is not affected.
Holiday
[→Main menu →Time program →Holiday] A calendar function can be used to enter a time period of absence.
During this time, the HC is continuously controlled (24h per day) to the room target temperature set in the [Room temperature absent] parameter. This program is not started if the [Standby] operating mode is active on the set start date.
Public holiday
[→Main menu →Time program →Public holiday] A calendar function can be used to enter a time period of presence.
During this time, regulation is carried out exclusively according to the settings for "Sunday" in [Heating circuit auto. 1] and [Hot water auto. 1].
4.3.2 Permanent time programs
For the connected HCs and the storage tank charging circuit, time programs control the HC and hot water temperatures or the operat­ing times of the circulation pump according to the specified switching cycles. The switching cycles are saved in time blocks for which dif­ferent target temperatures can be set.
The saved time program can be changed at any time. For a better overview, it is recommended to write down and safely store the pro­grammed switching cycles (Chap. 11.1).
Daikin RoCon+ HP Daikin controller RoCon+ HP1
008.1447899_00 – 09/2019 – EN
Operating Instructions
13
Page 14
4 Function
Heating circuit auto. 1 and Heating circuit auto. 2
[→Main menu →Time program →HC auto 1/HC auto 2] The time programs for the HC can be parametrised in these menus.
Three switching cycles can be set per day, to which the [Room tem­perature target 1/2/3] parameters are assigned. Outside the switch­ing cycles, it is controlled to the [Reduce room temperature] setpoint. The entry can be made separately for each individual weekday or in week segments.
Hot water auto. 1 and Hot water auto. 2
[→Main menu →Time program →DHW auto 1/DHW auto 2] The time programs for the domestic hot water preparation can be
parametrised in these menus. Three switching cycles can be set per day, to which the [Hot water temperature, target 1/2/3] parameters are assigned.
Circulation program
[→Main menu →Time program →Circulation] A time program for an optionally connected circulation pump can be
parametrised in this menu. 3 switching cycles per day can be set.
Switching cycle 1 Switching cycle 2 Switching cycle 3
Time period On Off On Off On Off
Room heating
Temperature setting [Room temperature target 1]: 20°C [Room temperature target 2]: 20°C [Room temperature target 3]: 20°C
[Reduce room temperature]: 10°C
"Heating circuit auto. 1"
Monday – Friday 06:00 22:00 - - : - - - - : - - - - : - - - - : - -
Saturday, Sunday 07:00 23:00 - - : - - - - : - - - - : - - - - : - -
"Heating circuit auto. 2"
Monday – Friday 06:00 08:00 16:00 22:00 - - : - - - - : - -
Saturday, Sunday 07:00 23:00 - - : - - - - : - - - - : - - - - : - -
INFORMATION
Use of circulation lines not permitted in France!
Sound program
INFORMATION
During quiet mode, the output in room heating and room cooling mode decreases so that it may no longer be pos­sible to achieve pre-set target temperature values.This pro­gram can therefore only be set by the installer.
In this menu, a time program can be parametrised for various stages of the heat pump quiet mode. 3 switching cycles with a resolution of 15minutes can be set. A separate entry for each weekday is pos­sible. Format: (on) hh:mm – hh:mm (off)
Also, the cycles from Monday to Friday, Saturday to Sunday and Monday to Sunday can be parametrised.
A noise level can be assigned to each switching cycle (0 - no noise reduction; 1 - min. noise reduction; 2 - med. noise reduction; 3 ­max. noise reduction).
Factory settings
The permanent time programs are preset according to .
Domestic hot water preparation
Temperature setting [Hot water temperature target 1]:
60°C
"Hot water auto. 1"
Monday – Sunday 05:00 21:00 - - : - - - - : - - - - : - - - - : - -
"Hot water auto. 2"
Monday – Friday 05:00 21:00 - - : - - - - : - - - - : - - - - : - -
Saturday, Sunday 06:00 22:00 - - : - - - - : - - - - : - - - - : - -
"Circulation program"
Monday – Friday 05:00 21:00 - - : - - - - : - - - - : - - - - : - -
Saturday, Sunday 06:00 22:00 - - : - - - - : - - - - : - - - - : - -
Monday – Sunday - - : - - - - : - - - - : - - - - : - - - - : - - - - : - -
Tab.4-3 Factory setting of the permanent time programs
4.3.3 Time program reset
[→Main menu →Time program →TP reset] This menu can be used to reset the time programs to factory set-
tings. To do this, select the respective time programs and then con­firm the selection with the Confirm button on the second menu page.
[Hot water temperature target 2]:
60°C
"Sound program"

4.4 Settings

[→Main menu →Settings] The basic settings of the controller and the system are made in this
menu. This includes the integration of optional and external compon­ents. Depending on the access authorisation (user or expert), differ­ent parameters are available.
[Hot water temperature target 3]:
60°C
Operating Instructions
14
Daikin controller RoCon+ HP1
Daikin RoCon+ HP
008.1447899_00 – 09/2019 – EN
Page 15
4 Function
4.4.1 Display settings
[→Main menu →Settings →Display] This menu can be used to set the following parameters: Language,
date, time, LCD brightness and LCD illumination time. Further explanations and possible settings for this menu can be
found in Chap. 7.5.
INFORMATION
Increasing the brightness of the LCD display beyond the factory-set value will reduce the life of the display.
4.4.2 System
[→Main menu →Settings →System] This menu combines basic parameters of the heating system. Further explanations and possible settings for this menu can be
found in Chap. 7.5.2.
4.4.3 Additional heat generators
[→Main menu →Settings →Ext. source] This menu can be used to configure the integration of an optional ex-
ternal heat source. The heat supplied by an alternative WEZ must be fed to the unpres-
surised storage tank water in the Daikin Altherma ETS(X/H) hot wa­ter storage tank.
▪ On use of the optional EKBUxx backup heater, this is carried out
due to the design installation situation.
▪ If an alternative WEZ (e.g. gas- or oil-fired boiler) is used, this can
be hydraulically integrated ▪ unpressurised via the connections (solar feed and solar return)
of the hot water storage tank or
▪ in the case of Daikin Altherma ETS(X/H) ...B device types, via
the integrated pressurised solar system heat exchanger
The setting of the [Config. ext. heat source] parameter is used to define if any additional heat generator (WEZ) is available for do­mestic hot water preparation and heating support, and which.
▪ No external heat source ▪ Optional backup heater ▪ Ext. heat sources HW and HZU: Alternative WEZ provide do-
mestic hot water preparation and backup heating. To request the WEZ, relay K3 on PCB RTX-EHS is switched.
▪ Ext. heat source HW or HZU: Alternative WEZ 1 (optional backup
heater EKBUxx) undertakes domestic hot water preparation and alternative WEZ2 undertakes heating support. To request WEZ 1, relay K3, and to request WEZ 2, relay K1, on PCB RTX-EHS are switched respectively. Heed warning notice! The operation of an additional alternative WEZ is also influenced by the settings of the [Bivalence function] and [Bivalence temperature] parameters.
Further explanations and possible settings for this menu can be found in Chap. 7.5.3.
4.4.4 Inputs/Outputs
[→Main menu →Settings →Inputs/Outputs] This menu can be used to adjust parameter for inputs and outputs of
the controller PCB to optimise the system controller individually.
Smart grid
WARNING
There is a danger of scalds at hot water target temperat­ures over 65°C. This is possible because the utility com­pany (EVU) is entitled to control current draw optimised ac­cording to supply and demand in the definitions for Smart Grid.
Due to such forced charging, the hot water target temper­ature in the hot water storage tank can exceed 65°C.
This storage tank charging is carried out even when the [Standby] operating mode is set.
▪ Install scald protection in the hot water distribution line.
To use this function, a special electricity meter with SG receiver to which the Daikin Altherma ETS(X/H) must be connected is required.
As soon as the function is activated by the [Smart grid] parameter, the heat pump is set to an operating mode as per Tab. 4-4 depend­ing on the utility company signal.
(1)
Signal
Electricity
Effect on
costs
EVU SG Hot water Heating install-
ations
1 0 --- No operation 0 0 Normal Normal opera-
tion
0 1 low Switch-on re-
commendation, and target stor-
age tank tem-
perature value is
increased de-
pending on the
[Smart grid
mode] para-
(2)
No operation Normal opera-
Switch-on re­commendation, and target feed
temperature is
increased de-
pending on the
[Smart grid
mode] para-
meter.
(2)
tion
meter.
1 1 Very low Switch-on com-
mand and stor­age tank target
temperature is
Switch-on com-
mand for stor-
age tank char-
ging.
set to 70°C.
Tab.4-4 Use of the SG signal
AUX switching function
Setting the [AUX switching function] parameter selects the switching conditions for the potential-free AUX switching contact (toggle switch output A). This switching contact can be used to control an external heat generator, for example.
If one of the switching conditions is fulfilled, the potential-free switch­ing contact is switched after the time set in the [AUX wait time] para­meter.
AUX switching contact (toggle switch output A) is not switched if setting is deactivated.
AUX switching contact (toggle switch output A) is switched, if set­ting
▪ Storage tank temperature (T
(AUX)] parameter value.
) ≥ [Switching threshold TDHW
dhw
▪ if an error is pending. ▪ Outside temperature < [Bivalence temperature] parameter value. ▪ Heat request for domestic hot water preparation. ▪ Heat request for room heating. ▪ Heat request for room heating or domestic hot water preparation.
(1)
Switching contacts at input J8 of the RoCon BM2C PCB closed(1) or open(0).
(2)
No frost protection function
Daikin RoCon+ HP Daikin controller RoCon+ HP1
008.1447899_00 – 09/2019 – EN
Operating Instructions
15
Page 16
4 Function
Interlink function
Setting the [Interlink function] parameter = On offers the possibility that the Daikin Altherma ETS(X/H) two different feed temperature setpoints are included in the controller.
This applies to both weather-compensated control and control ac­cording to a fixed feed target temperature (see Chap. 4.5).
One possible application is, for example, the additional integration of an HP convector in a surface heating and cooling system.
Prerequisite: 2 switching contacts are connected to Daikin Altherma ETS(X/H) plug connection J16 (e.g. room thermostats).
▪ [Interlink function] parameter = Off: Deactivated ▪ [Interlink function] parameter = On: Evaluation of the heating and
cooling switching contacts at plug connection J16 on the RoCon BM2C PCB. Activation of cooling mode only by switching the op­erating mode to [Cooling] (see Chap. 4.1). Setting of the [Room thermostat] parameter is no longer evaluated.
▪ Open switching contacts: Only frost protection active ▪ [Heating] or [Automatic 1] / [Automatic 2] operating mode active
during daytime switching cycles. ▪ Closed switching contact Heating = IL1 ▪ It is controlled to the normal feed target temperature according
to the parameter settings for [Heating]. ▪ Closed switching contact Cooling = IL2 ▪ It is controlled to the increased feed target temperature (normal
feed target temperature + value of the [Interlink temperature in-
crease ] parameter). Priority if both switching contacts are
closed!
▪ [Cooling] operating mode active.
▪ Closed switching contact Heating = IL1 ▪ It is controlled to the normal feed target temperature according
to the parameter settings in level [Heating circuit config.] >
[Cooling]. ▪ Closed switching contact Cooling = IL2 ▪ The system is regulated to the reduced feed target temperature
(normal feed target temperature value of the [Interlink temperat-
ure increase ] parameter. Priority if both switching contacts are
closed!
Further explanations and possible settings for this menu can be found in Chap. 7.5.
Tdhw > T
+ 4K and Tdhw > [Hot water temperature, target] in-
HZUmin
formation parameter + 1K If the switch-on condition is fulfilled, heat is taken from the storage
tank and this is used to supply the heating system. Switch-off condition: Tdhw < T
or Tdhw < [Feed temperature, target] parameter (see
HZUmin
Chap. 4.5.3)
If the switch-off condition is fulfilled, the heating support from the hot water storage tank is set and the burner takes over the heating oper­ation.
The [Heating support power] parameter limits the maximum power that can be taken. The [Heating support max. temp.] parameter limits the maximum temperature that can enter the heating system.
Further explanations and possible settings for the parameters in this menu can be found in Chap. 7.5.5.

4.5 Configuration

[→Main menu →Configuration] This menu can be used to optimally adapt the operating characterist-
ics of the system to the system structure and the needs of the users. Additional programs facilitate commissioning. Depending on the ac­cess authorisation (user or expert), different parameters are avail­able.
4.5.1 Access privileges (technician code)
[→Main menu →Configuration →Access] Certain functions and parameters in the controller are restricted by
access rights and are not visible to the user. To gain access to it, the specialist code must be entered.
4.4.5 Intelligent storage tank management
[→Main menu →Settings →ISM] If the storage temperatures are high enough, the energy in the stor-
age tank can be used for room heating. This can either increase comfort ([Continuous heating] function) or make it possible to use energy from an external heat source, e.g. solar, when heating is re­quired ([Heating support (HZU)] function).
Continuous heating
This function enables uninterrupted heating, even when the evapor­ator is being defrosted. This enables high comfort to be guaranteed, even with rapidly reacting heating systems (e.g. convectors).
Heating support (HZU)
If the Heating support function ([Heating support (HZU)] parameter = On) is activated, the energy in the Daikin Altherma ETS(X/H)'s integ­rated storage tank is used to undertake the heating function. If the storage temperature is sufficiently high, the burner remains inactive.
The minimum value (T
) is calculated as follows: T
HZUmin
HZUmin
= cur­rently active hot water target temperature [Hot water temperature, target] + [Heating support hysteresis] parameter.
Switch-on condition:
Operating Instructions
16
Fig.4-1 Setting the access code
Example: Set code 3090 (example only, this is not a valid access code) [→Main menu →Configuration →Access]:
1 Turn the rotary button clockwise until the first input field is dis-
played in blue.
2 Briefly press the rotary button to confirm ("OK").
è The first input field flashes blue.
3 Turn the rotary button clockwise until 3 is displayed. 4 Briefly press the rotary button to confirm ("OK").
è The second input field is displayed in blue.
5 Turn the rotary button clockwise until the third input field is dis-
played in blue.
6 Briefly press the rotary button to confirm ("OK").
è The third input field flashes blue.
7 Turn the rotary button clockwise until 9 is displayed.
Daikin RoCon+ HP
Daikin controller RoCon+ HP1
008.1447899_00 – 09/2019 – EN
Page 17
4 Function
8 Briefly press the rotary button to confirm ("OK").
è The fourth input field is displayed in blue.
9 Turn the rotary button clockwise until the Confirm icon turns
blue.
10 Briefly press the rotary button to confirm ("OK").
è The code is checked and the setting level is exited.
4.5.2 Sensors
[→Main menu →Configuration →Sensors] Optional sensors are activated and configured in this menu. Pres-
sure setpoints for the water side can be defined. Further explanations and possible settings for the parameters in this
menu can be found in Chap. 7.6.1.
4.5.3 HC configuration
[→Main menu →Configuration →HC config] This menu is used to adjust the basic functionality of the heating cir-
cuit. Further explanations and possible settings for the parameters in this
menu can be found in Chap. 7.6.2.
Weather-dependent feed temperature control
If the weather-compensated feed temperature control is active, the feed temperature ([Feed temperature, target] parameter) is determ­ined automatically according to the set heating/cooling curve de­pending on the outside temperature.
This function is activated in the delivery condition. It can only be de­activated (fixed value control) or reactivated with a technician code.
If the room controller is also connected (EHS157034) to the RoCon+ HP, the target temperatures are controlled according to the weather and room temperature ([Room influence] parameter).
This function can only be configured using the technician code. Con­tact your heating expert in this regard.
This function is activated or deactivated via the [Weather-com­pensated] parameter in the "Configuration" menu.
▪ [Weather-compensated] parameter = Weather-compensated:
Weather-compensated feed temperature control
▪ [Weather-compensated] parameter = Feed temperature, fixed:
Control based on fixed target temperature ▪ For heating mode: [Feed temperature, heating mode] para-
meter or [Feed temperature, reducing mode] parameter
▪ For cooling mode: [Feed temperature, cooling mode] parameter
If the terminal function is activated, the mixer module can be oper­ated and the settings for the assigned heating circuit undertaken via the RoCon+ B1 control panel of the Daikin Altherma ETS(X/H).
In conjunction with the EHS157034 room control, the mixer module can also control the assigned heating circuit completely autonom­ously and independently of the heat generator.
Further explanations and possible settings for this menu can be found in Chap. 7.6.
Frost protection function
The integrated heating circulation pump is switched on at an external temperature below the [Frost protection temperature] parameter value in order to prevent the heating system from freezing.
In addition, the feed, storage and connected room temperature sensors are also constantly monitored. If the temperature measured by one of these sensors falls below 7°C (below 5°C at room tem­perature), the antifreeze function is also activated.
If the heating feed temperature falls below 7°C, the Daikin Altherma ETS(X/H) heats until the heating feed temperature reaches at least 12°C.
The function is ended if the external temperature rises above the set [Frost protection temperature] parameter value + 1K and also there is no other activation condition.
INFORMATION
If low rate functions are activated, [HT/NT function] parameter = Switch all off or [Smart grid] parameter = On operation of the heat pump can be shut off completely for a
limited period of time by the utility company. In these cases, regulation is not possible even in frost protection conditions and the device's internal heating circulation pump is not switched on.
These situations can be recognised if, in the [→Main menu →Information →Overview] menu in the operating data field: "Ext", the "High rate" value or "SG1" is dis­played.
4.5.4 Heating
[→Main menu →Configuration →Heating] This menu is used to configure heating times and target feed tem-
peratures for heating mode.
INFORMATION
The weather-compensated feed temperature control has no influence on the feed target temperature in the case of a hot water circuit request.
With connected Mixer module
The setting of the heating/cooling curves and the activation of the weather-compensated feed temperature control for the assigned HC are carried out in the same way as described above.
The assigned HC can be operated as a: ▪ Mixer add-on
The outside temperature of the outside temperature sensor con­nected to the Daikin Altherma ETS(X/H) external temperature
sensor is transmitted to the mixer module via the CAN bus. or as a ▪ Mixer add-on with zone control
A separate outside temperature sensor must be connected to the
mixer module. The assigned HC is controlled according to the out-
side temperature relevant for this zone.
Daikin RoCon+ HP Daikin controller RoCon+ HP1
008.1447899_00 – 09/2019 – EN
Operating Instructions
17
Page 18
4 Function
Heating curve
WARNING: FLAMMABLE MATERIAL
In the event of malfunction, the floor heating system, the screed or the floor structure could be damaged due to overheating.
▪ Prior to initial commissioning, set the maximum temper-
ature limit in the RoCon+ HP controller ([Max. feed temperature] parameter) to the maximum permitted system temperature prior to starting the emission measurement.
▪ Connect an overheating protection switch (in the build-
ing) at the "Ext" plug connection for external operating mode switch-over so that the Daikin Altherma ETS(X/ H) is switched to the "Standby" or "Summer" operating mode. If the [Room thermostat] parameter = Yesor the [Interlink function] parameter = On, the overheating protection switch must be connected so that the room thermostat's switching contact is interrupted.
▪ If the floor heating is also used for room cooling, the
connection notes in the above point also apply to the connection of a moisture protection switch in the build­ing.
The heating curve is used to adapt the feed temperature to the char­acteristics of the building independent of the respective outside tem­perature (weather-compensated feed temperature control, see
Chap. 4.5). Generally speaking, the slope of the heating curve de-
scribes the ratio of the feed temperature change to the external tem­perature change.
The heating curve is valid within the limits of the minimum and max­imum temperatures set for the respective HC. The room temperature measured in the occupied area may differ from the required room temperature; these deviations can be kept to a minimum by installing a room thermostat or a room control.
The controller is set at the factory in such a way that the heating curve does not independently adjust itself during operation.
The automatic heating curve adjustment can be activated ([Heat­ing curve adaptation] parameter) if the outside temperature sensor and the room controller (EHS157034) are connected (see
Chap. 4.5).
Start conditions for automatic heating curve adjustment: ▪ Outside temperature <8°C ▪ Operating mode is [Automatic 1] or [Automatic 2] ▪ Duration of the setback period is at least 6h If no automatic heating curve adjustment is activated, the heating
curve can be manually adjusted by adjusting the [Heating curve]
parameter).
INFORMATION: MANUALLY ADJUSTING THE HEAT­ING CURVE
Do not make any corrections to the set values for 1 – 2 days, and then only make them in small increments.
▪ Deactivate the external heat sources (e.g. stoves, dir-
ect sunlight, open windows). ▪ Fully open any radiator thermostat valves or actuators. ▪ Activate "Heating" operating mode. Approximate setting
values:
Heating element: 1.4 to 1.6.
Floor heating: 0.5 to 0.9.
Fig.4-2 Heating curves
TAOutside temperature TRRoom target temperature TVT-HS
Comfort heating
If the heat pump cannot cover the heating demand when outside temperatures are very low, heat is extracted from the storage tank and used for room heating. In rare cases (in systems with high re­quired feed temperatures and low required hot water temperatures), the required feed temperature can be higher than the storage tank target temperature. In order to avoid short-term loss of comfort in heating mode for these systems, the [Comfort heating] parameter can be set to "On". At corresponding outside temperatures, the stor­age tank temperature is raised above the storage tank temperature set for the hot water requirement.
INFORMATION
If [Comfort heating] is set to "On", the power consumption of the heat pump may increase. In the default setting, [Comfort heating] is set to "Off".
Detailed explanations and possible setting values of this function can be found in Chap. 7.6.
4.5.5 Cooling
[→Main menu →Configuration →Cooling] This menu is used to make settings for cooling mode.
CAUTION: DANGER OF CONDENSATION
In the event of malfunction or incorrect parameter settings, the floor heating, the screed or the floor structure could be damaged due to condensation.
▪ Prior to initial commissioning and activation of cooling
mode, set the minimum temperature limit to the min­imum permissible system temperature in the RoCon controller (parameter [Feed temperature lower limit]).
Prerequisites for cooling mode: ▪ Outside temperature > set value of room target temperature ▪ Outside temperature > set value of the [Start cooling outside
temp.] parameter
▪ [Cooling] operating mode activated.
▪ via menu "Operating mode" or ▪ via room thermostat function (cooling switching contact closed)
Operating Instructions
18
Daikin controller RoCon+ HP1
Daikin RoCon+ HP
008.1447899_00 – 09/2019 – EN
Page 19
4 Function
▪ No heat request active in the heating system's RoCon system.
INFORMATION
If the mean outside temperature falls below 4°C when "Cooling" operating mode is active, the operating mode automatically switches to "Heating".
Renewed automatic operating mode switching to "Cooling" only takes place:
▪ if a room thermostat is connected to plug connection
J16 (cooling) and ▪ the room thermostat's switching contact is closed and ▪ the mean outside temperature increases to over 10°C
again.
Cooling curve
[→Main menu →Configuration →Cooling →Cooling curve] The cooling curve determines the feed target temperature in cooling
mode depending on the respective outside temperature. (for weather-compensated feed temperature control, see Chap. 4.5.3). Warmer outside temperatures result in a colder feed target temperat­ure and vice versa. The cooling curve can be adapted to the condi­tion of the building by four parameters (see Fig. 4-3).
1 [Start cooling outside temp.] 2 [Max. cooling outside temp.] 3 [Target flow cooling, start] 4 [Target flow cooling, max.]
Cooling parameters
[→Main menu →Configuration →Cooling →Parameters] This menu combines further parameters to determine target feed
temperatures in cooling mode. During weather-dependent T-HS control, the user can increase or
decrease the target feed temperature by a maximum of 5K with the parameter [Cooling setpoint correction]. A temperature reduction is limited by the [Feed temperature lower limit] parameter.
INFORMATION
If optional frost protection valves are installed in the sys­tem, the [Feed temperature lower limit] parameter must not be set below 7°C.
4.5.6 Domestic hot water
[→Main menu →Configuration →DHW] The domestic hot water preparation can be individually adapted to
the behaviour and requirements of the users in this menu. This min­imises energy consumption and increases comfort.
Solar function
The [Solar function] is used to reduce the target temperature of the hot water storage tank in order to increase the yield of a connected solar system. The target value of the hot water temperature is set as a function of the outside temperature and in compliance with the safety functions. In addition, the following parameters are defined: Hot water hysteresis= 5K; Building insulation= Normal
To activate the solar function, it must be set to "On" in the menu [→Main menu →Configuration →DHW →Solar function] and the switching contact EXT (J8) must be closed.
Settings for optional circulation pump
Depending on the [Circulation pump control] parameter, an optional circulation pump can be controlled synchronously with the selected time program for domestic hot water preparation or with the time pro­gram for the circulation pump (see Chap. 4.3). During the release times of the selected time program, the circulation pump can be op­erated either continuously or cycled. This is defined with the [Circula­tion pump interval] parameter.
Anti-legionella protection
This function is used to prevent bacterial contamination in the hot water tank by thermal disinfection. To do so, the hot water tank is heated 1× daily or 1× weekly to the disinfection temperature [Anti-le­gionella temperature] depending on the [Anti-legionella day] para­meter. Disinfection starts at the specified start time [Anti-legionella start time] and is active for one hour. An optionally connected circu­lation pump is automatically switched on during this time.
Detailed explanations and possible setting values of this function can be found in Chap. 7.6.5.
4.5.7 Additional program
[→Main menu →Configuration →Addition] This menu combines programs which simplify initial commissioning
of the system.
Fig.4-3 Cooling curve parameter dependency
1 [Start cooling outside temp.] parameter 2 [Max. cooling outside temp.] parameter 3 [Target flow cooling, start] parameter 4 [Target flow cooling, max.] parameter 5 [Feed temperature lower limit] parameter 6 Room target temperature
7 Cooling mode possible TAOutside temperature TVT-HS
------- Cooling curve
- - - - Possible parallel cooling curve shift
Further explanations and possible settings for the parameters in this menu can be found in Chap. 7.6.4.
Daikin RoCon+ HP Daikin controller RoCon+ HP1
008.1447899_00 – 09/2019 – EN
Air purge function
[→Main menu →Configuration →Addition →Ventilation] By activating the ventilation function, the controller starts a fixed
defined sequence program with start/stop operation of the integrated heating circulation pump and various positions of the integrated 3­way switching valves. Existing air can escape during operation via the automatic ventilation valve.
INFORMATION
The activation of this function does not replace correct venting of the HC.
The HC must be completely full before activating this func­tion.
Relay Test
[→Main menu →Configuration →Addition →Relay test] This program allows testing of internal switching relays. This may be
necessary in the event of malfunctions, error messages or as part of annual maintenance. When the menu is opened, all relays are deac­tivated. Selecting one or more relays activates them. When the menu is exited, all relay tests are terminated.
Operating Instructions
19
Page 20
4 Function
The relay test menu is operated in the same way as list entries (see
Chap. 3.3.3). However, several relays can be activated in parallel in
the relay list for testing. To do this, select the corresponding relay with "OK". Activated relays are indicated by a tick.
Floor screed dryout
[→Main menu →Configuration →Addition →Screed] The screed drying is started in the menu according to the settings in
[Screed program]. The program is used exclusively for the pre­scribed drying of newly created screed for floor heating systems. The first day of the screed program begins after activation of the pro­gram at the change of day at 00:00.
Screed drying is a special function and is not interrupted by any other operating mode. It can only be activated by the heating expert for the direct HC and/or optionally connected mixed HCs. It must be activated separately for each HC.
INFORMATION
Before starting the screed drying, the [Room thermostat] and [Interlink function] parameters must be deactivated. During a short-term power failure, a previously activated screed drying is continued at the point of the interruption.
After activation of the screed drying, all weather-compensated con­trol functions of the respective HC are switched off. The respective HC works as a constant temperature control regardless of the oper­ating mode and switching times.
Already activated screed drying can be deactivated at any time. After ending the screed drying, the parameter is automatically set to "Off" and the HC works according to the currently set operating mode again.
Floor screed program
[→Main menu →Configuration →Addition →Program] This menu allows the individual adjustment of the factory settings for
the duration and feed target temperatures of the screed drying. Changes can only be made after entering the specialist code.
Changing the screed program
A separate feed target temperature can be set for each day for a maximum duration of 28 days. The end of the screed program is defined by the first day without a preset feed target temperature.
Day Factory setting Day Factory setting
1 – 3 25°C 10 – 19 55°C 4 – 7 55°C 20 40°C
8 25°C 21 25°C 9 40°C 22 – 26 -
Tab.4-5 Default settings of the screed program
Fig.4-4 Changing the screed program
Example: Increase the feed temperature of the 3rd day to 40°C and stop the program on the 8th day [→Main menu →Configuration →Addition →Program]:
1 Turn the rotary button clockwise until the day selection is set to
3.
2 Briefly press the rotary button to confirm ("OK").
è The temperature field is displayed in blue.
3 Turn the rotary button clockwise until the temperature selection
is 40°C.
4 Briefly press the rotary button to confirm ("OK").
è Temperature selection of the next day is shown in blue
5 Briefly press the rotary button several times until the day selec-
tion is set to 8.
6 Turn the rotary button anticlockwise until the temperature selec-
tion is set to "Off".
7 Briefly press the rotary button to confirm ("OK").
è Day 8 to day 28 are set to "Off", the Confirm icon is shown in
blue
8 Briefly press the rotary button to confirm ("OK").
è The programming is saved and the menu is exited.
Typical screed programs Function heating
The function heating serves as proof of the production of defect free work for the heating engineer. A prefabricated heating protocol relat­ing to floor heating systems can be found on the manufacturer's In­ternet portal.
In this sense, the function heating (identical with "Heating" in EN1264, section 5.2) is not considered as a heating process to achieve workability of the screed. Generally, a special screed curing heating and/or mechanical drying is required for this.
The heating of cement screeds should be carried out after 21days at the earliest and of anhydrite screeds after 7 days at the earliest in accordance with the specifications of the manufacturer. The first heating begins with a feed temperature of 25°C that must be main­tained for 3days. Afterwards, the heating is carried out with the max­imum set feed temperature for the HC (limited to max. 55°C), which must be maintained for a further 4days.
After the described heating process, it is not yet assured that the screed has reached the required moisture content for workability of the screed.
The moisture content in the screed must be checked by measure­ment prior to laying the surface covering.
Operating Instructions
20
Daikin controller RoCon+ HP1
Daikin RoCon+ HP
008.1447899_00 – 09/2019 – EN
Page 21
4 Function
INFORMATION
Procedure in accordance with EN1264 Part 4: For anhydrite and cement screeds, the HCs must be leak
tested by a water pressure test after completion. The leak­tightness must be ensured immediately before and during the laying of the screed. The height of the test pressure is at least 1.3x the maximum permitted operating pressure.
Suitable measures must be taken if there is a risk of freez­ing, e.g. use of antifreeze agents or heating the building. If antifreeze agents are no longer necessary for the intended operation of the system, the antifreeze agent must be re­moved by draining and rinsing the system with at least 3 changes of the water.
Fig.4-5 Chronological sequence of the screed program during
the function heating
t1Start temperature 25°C t2Maximum HC temperature
TVT-HS
Z Duration of the screed function in days after starting the
function
Screed curing heating
The drying process for the screed cannot be exactly predicted. If there is a high degree of humidity, sometimes it can stop completely. The drying process can be speeded up by activating the floor heat­ing (screed curing heating) or measures such as mechanical drying.
Each screed curing heating must be ordered separately by the client as an extra service in accordance with German construction contract procedures (VOB). The workability of the screed is a prerequisite for the top floor installer to start work so that he can produce defect free work.
With standard settings, the combined function and screed curing heating program can be activated to achieve the required residual moisture in the screed for workability of the screed (see Fig. 4-6). However, the residual moisture of the screed must basically be checked metrologically before the flooring can be laid.
4.5.8 Configuration Wizard
[→Main menu →Configuration →Wizard] This menu summarises the parameters queried in the Configuration
Wizard. This allows a quick adjustment of the system settings. See
Chap. 5.1.
4.5.9 Parameter reset
[→Main menu →Configuration →Parameter reset] All customer-specific parameter settings can be reset to factory set-
tings in this menu. This can be useful if the Daikin Altherma ETS(X/ H) no longer functions properly and no other causes of malfunction can be identified.

4.6 Info

[→Main menu →Information] This menu displays all system temperatures, the heat generator
type, various software information and the operating states of all sys­tem components. The number of displayed parameters depends on which components are connected. No adjustments can be made to these values.
4.6.1 Current
[→Main menu →Information →Current] This menu shows the hydraulic diagram of the system. The first and
second pages show sensors and the assigned, current values. The third page shows the compressor, pump and heating rod in white if they are inactive and blue if they are active. The current valve posi­tion is shown for both mixing valves.
Fig.4-6 Chronological sequence of the screed program during
the combined function and screed curing heating (for le­gend, see Fig. 4-5)
Detailed explanations and possible setting values of this function can be found in Chap. 7.6.
Daikin RoCon+ HP Daikin controller RoCon+ HP1
008.1447899_00 – 09/2019 – EN
Fig.4-7 Hydraulic circuit diagram – first page
Operating Instructions
21
Page 22
4 Function
Fig.4-8 Hydraulic circuit diagram – second page
Item Designation
t-AU Outside temperature sensor P Pressure V Volume flow t-R Heating return flow temperature t-V,BH Heating feed temperature, if necessary after heating
support heat exchanger t-liq Refrigerant temperature t-V Feed temperature after the plate heat exchanger T-DHW Temperature in the hot water storage tank B1 Current position of mixing valve 3UVB1 (0%:heating
network; 100%:internal bypass) DHW Current position of the mixing valve 3UV DHW
(0%:heating network; 100%:hot water tank)
Tab.4-6 Legend to the hydraulic circuit diagrams
4.6.2 Overview
[→Main menu →Information →Overview] This menu lists the current operating states of the heat pump and its
components. Further explanations of the parameters in this menu can be found in
Chap. 7.7.
4.6.3 Values
[→Main menu →Information →Values] In this menu, the current setpoint and actual values are listed. Further explanations of the parameters in this menu can be found in
Chap. 7.7.
4.6.4 Water pressure
[→Main menu →Information →Water pressure] The current water pressure is displayed in large font in this menu.
This makes it easier to read during the installation of the system.

4.7 Error

[→Main menu →Error] The error handling of the Daikin Altherma ETS(X/H) takes place in
this menu. see Chap. 8.

4.8 Terminal

[→Main menu →Terminal] This menu can also be used to operate and parametrise other
devices integrated in the RoCon system via the CAN bus (control components mixer module or heat generator), provided the respect­ive control unit has the required authorisation.
Functional IDs
The RoCon system offers a very wide range of application and ex­tension options. The individual RoCon system components commu­nicate via the CAN data bus. For this, the RoCon BM2C circuit boards and the RoCon+ B1 control units of the Daikin Altherma ETS(X/H) as well as the optional EHS157034 room station and EHS157068 mixer module are connected with each other via data bus lines if necessary. These system components must be allocated unique functional IDs, so that the data exchange and the assignment within the RoCon system functions without any problems.
The easiest way to assign the functional identifiers is to use the Con­figuration Wizard. This is carried out automatically during the first commissioning or can be started manually in case of extensions in the heating system in [→Main menu →Configuration →Wizard]. In addition, most identifiers can also be adapted to the RoCon system by parameter settings in this menu.
ID / Function System components Parameters Comments
HC ID Unique numbering of a HC in the heat-
ing system in the RoCon system. A maximum of 16 HCs can be controlled.
(1)
A maximum of 8 heat generators can be connected in the RoCon system via the CAN data bus. Several heat generators integrated in the heating installation must be regarded as a special application. If necessary, contact a service technician.
Operating Instructions
Daikin Altherma ETS(X/H)
(RoCon BM2C)
EHS157034 room station [Heating circuit assign-
EHS157068 mixer module [Heating circuit assign-
[Direct circuit configura-
tion]
See Chap. 7.11
ment]
see RoCon U1/M1 in-
structions
ment]
see RoCon U1/M1 in-
structions
Factory setting = 0 Should not normally be changed.
Factory setting = Off Adaptation required if there are different HCs
in the system and/or the [Master-RoCon] para­meter = On
Factory setting = Off Must always be adapted to the setting of the
address switch.
22
(1)
Daikin RoCon+ HP
Daikin controller RoCon+ HP1
008.1447899_00 – 09/2019 – EN
Page 23
ID / Function System components Parameters Comments
Heat generator ID Unique numbering of a heat generator
in the RoCon system.
(1)
Daikin Altherma ETS(X/H)
(RoCon BM2C)
[Bus ID heat generator]
See Chap. 7.11
EHS157068 mixer module [Boiler Assignment]
see RoCon U1/M1 in-
structions
Factory setting = 0 Should not normally be changed.
Factory setting = 0 Should not normally be changed. Defines the heat generator that supplies the
assigned HC with heat.
Terminal ID Unique numbering of a RoCon+ B1 or
EHS157034 control panel from which a heat generator and/or mixer module can be remotely controlled in the RoCon system.
The authorisation for remote control can be allocated to up to 10 control panels in the RoCon system. If remote control is to be possible in the RoCon system, the control panel must be allocated the
Daikin Altherma ETS(X/H)
(RoCon BM2C)
[Terminal address]
See Chap. 7.9
EHS157034 room station [Terminal address]
See Chap. 7.9
Factory setting = Off The value should be set to "0" if at least 1
mixer module is connected in the RoCon sys­tem and the mixer circuit is to be operated from the heat generator.
Factory setting = Off The value must be set to a unique numerical
value in the RoCon system if the room station system components are to be remotely con­trolled using a valid device ID.
ID "0". Device ID
Unique numbering of a heat generator or mixer module in the RoCon system.
Up to 16 device numbers can be alloc­ated.
These device numbers are detected during a [Bus scan] and are displayed for identification of a remotely controlled device.
Daikin Altherma ETS(X/H)
(RoCon BM2C)
[Bus ID heat generator]
See Chap. 7.11
EHS157068 mixer module [Heating circuit assign-
ment]
See Chap. 9
Identical to heat generator detection. The value must not be the same as the HC ID
of a mixer module in the RoCon system. Identical to the HC ID.
The value must not be the same as the heat generator ID of the heat generator in the Ro­Con system.
The value must be the same as the setting of the address switch.
Tab.4-7 Functional IDs in the RoCon system
4 Function
(1)
(1)
4.8.1 Selecting the terminal address
[→Main menu →Terminal →Address] Setting of the terminal ID of the control panel for system access. The
set value must be unique throughout the entire system. Confirmation of this parameter with the rotary button effects a new initialisation of the controller.
All settings except "Off", authorise the user of the control panel to activate the terminal function and thus to operate all RoCon system components with a valid device ID.
4.8.2 Bus-Scan for terminal function
[→Main menu →Terminal →Bus scan] After activating the "Bus scan", a list of detected devices (with as-
signed terminal address) is displayed in the menu [→Main menu →Terminal] for selection. After selecting and confirming an external device, the terminal function for this device is activated. The control panel is then in terminal operation.
The local control panel acts as a remote control for the external device and the corresponding start screen is shown on the display. In this case, all the control functions are performed and saved 1:1 in the same way as on the external device. The displayed values and symbols are always taken over by the selected device.
To operate the local device, switch to the start screen of the external device. Press and hold the rotary switch to return to the menu of the local device.
INFORMATION
To perform the bus scan, a valid terminal address must be assigned to the RoCon+ B1 control panel of the Daikin Altherma ETS(X/H) or the EHS157034 room station. This can only be done with a specialist code. Contact your heat­ing expert in this regard.
If the terminal function is to be used in the heating system, the terminal ID = 0 must be allocated to a control panel.
Example: Activate terminal operation for the heat generator with bus identification 2 [→Main menu →Terminal →Bus scan]:
The bus scan is carried out. An overview of all devices that are found is displayed.
1 Turn the rotary switch clockwise until the BM1/BE1 #2 controller
is displayed in blue.
2 Briefly press the rotary button to confirm ("OK").
è The local control panel acts as a remote control for the heat
generator with bus ID 2.
To end terminal operation and switch back to the operation of the as­signed device, switch to the start screen of the external device. Press and hold the rotary switch to return to the menu of the local device.
INFORMATION
If the local control panel is used as a remote control for a mixer module, both the standard screen and the menu structure are changed (see Chap. 9).
(1)
A maximum of 8 heat generators can be connected in the RoCon system via the CAN data bus. Several heat generators integrated in the heating installation must be regarded as a special application. If necessary, contact a service technician.
Daikin RoCon+ HP Daikin controller RoCon+ HP1
008.1447899_00 – 09/2019 – EN
Operating Instructions
23
Page 24
4 Function

4.9 Statistics

INFORMATION
The values listed in this menu are approximate values. In particular if glycol is present in the system, there may be greater deviations from real performance data.
[→Main menu →Statistics] This menu can be used to access the values for the power output
and run times of the heat pump and its components. The [Electr. en­ergy total] parameter describes the total electrical power consump­tion of the heat pump and its components. All other values refer to the energy provided by the heat pump or the run time of various components.
4.9.1 Month
[→Main menu →Statistics →Month] This menu can be used to call up summed values for the power out-
put and power consumption over the month. The displayed value is assigned to the month shown in blue on the diagram. The various values can be displayed by turning the rotary switch.
4.9.2 Total
[→Main menu →Statistics →Total] This menu can be used to call up summed values for the power out-
put and power consumption of the heat pump since commissioning (or since the last reset by a specialist).
Operating Instructions
24
Daikin controller RoCon+ HP1
Daikin RoCon+ HP
008.1447899_00 – 09/2019 – EN
Page 25

5 Initial commissioning

5 Initial commissioning
INFORMATION
In addition to the commissioning instructions listed in this chapter, the specific commissioning instructions listed in the respective installation instructions for the Daikin Altherma ETS(X/H) must be observed.

5.1 Configuration Wizard

The Configuration Wizard simplifies system configuration during in­stallation. It appears automatically during initial commissioning and guides the user through defined selection pages. As long as the en­tire system setting is not confirmed, the Configuration Wizard is called up again each time it is switched on. Only after confirmation of the system setting can the heat generator switch to normal opera­tion. In normal operation, the parameters of the Configuration Wizard can be called up and set in the menu [→Main menu →Configura­tion →Wizard].
The different selection pages of the Configuration Wizard are oper­ated according to the screens described in Chap. 3.3. Confirming a selection with "OK" or the Confirm icon leads directly to the next se­lection page. The modified parameter is applied directly.

5.2 Menu navigation in the Configuration Wizard

→ Language 1 Select the desired language. 2 Confirm the selection with the Confirm icon.
→ Standard configuration If no optional RoCon system components are connected: 1 Briefly press the rotary button to confirm ("Yes").
When optional RoCon system components such as EHS157034 and/or EHS157068 are connected:
1 Turn the rotary button clockwise until "No" is displayed in blue. 2 Briefly press the rotary button to confirm ("OK"). 3 Select and set the following list elements as required:
▪ Direct circuit configuration (see Chap. 4.8) ▪ Bus ID heat generator (see Chap. 4.8) ▪ Time master (see Chap. 7.11)
4 If all settings have been made as required, confirm by clicking on
the Confirm icon.
→ Time 1 Setting the current time (see Chap. 3.3.5).
→ Date 1 Setting the current date (see Chap. 3.3.6).
→ System parameters
The following parameters can be set:
▪ [Room thermostat] present? (see Chap. 7.5.4) ▪ [Heating support (HZU)] required? (see Chap. 7.5.5) ▪ [Continuous heating] required? (see Chap. 7.5.5)
→ Heating limit
The following parameters can be set:
▪ [Heat limit, heating mode] (see Chap. 7.5.3) ▪ [Heat limit, reducing mode] (see Chap. 7.5.3)
→ Weather-compensated
Weather-compensated control is required: 1 Confirm the "Weather-compensated" selection with the Confirm
icon.
The following parameters can be set:
▪ [Room temperature target 1] setting (see Chap. 7.5.1) ▪ [Heating curve] setting (see Chap. 4.5.4) ▪ Only with reversible device type: Setting of the cooling curve
(see Chap. 4.5.5)
Weather-compensated control is not required:
1 Select the "Feed temperature, fixed" setting. 2 Confirm the selection with the Confirm icon.
The following parameters can be set:
▪ [Feed temperature, heating mode] setting (see Chap. 7.6.3) ▪ Only with reversible device type: Setting [Feed temperature,
cooling mode] (see Chap. 7.6.4)
→ Hot water
The following parameters can be set:
▪ [Hot water temperature target 1] (see Chap. 7.3.4) ▪ [Hot water hysteresis] (see Chap. 7.6.5)
→ Device selection
The following parameters can be set:
▪ [Outdoor unit] ▪ [Indoor unit]
→ External heat generator
No external heat generator available:
1 Select the "No external heat generator" setting. 2 Confirm the selection with the Confirm icon.
Optional backup heater available: 1 Confirm the "Backup heater BUH" selection with the Confirm
icon.
2 Select and set the following list elements as required:
▪ [External power hot water] (see Chap. 7.5.3) ▪ [External power stage 1] (see Chap. 7.5.3) ▪ [External power stage 2] (see Chap. 7.5.3) ▪ Emergency (see Chap. 8.1)
3 If all settings have been made as required, confirm by clicking on
the Confirm icon. Alternative external heat generator available: 1 Select the "DHW + heating support" or "Two external heat gen-
erators" setting (see Chap. 7.5.3).
2 Confirm the selection with the Confirm icon. 3 Select and set the following list elements as required:
▪ [External power hot water] (see Chap. 7.5.3) ▪ [External power stage 1] (see Chap. 7.5.3) ▪ Emergency (see Chap. 8.1)
4 If all settings have been made as required, confirm by clicking on
the Confirm icon.
→ Heating system 1 The [Heating system] parameter can be set (see Chap. 7.5.2).
Daikin RoCon+ HP Daikin controller RoCon+ HP1
008.1447899_00 – 09/2019 – EN
Operating Instructions
25
Page 26

6 Parameter overview

Standby
Reduce
Heating
Automatic 2
Automatic 1
Summer
Cooling
Room temperature target 1
Room temperature target 2
Room temperature target 3
Hot water temperature target 1
Hot water temperature target 2
Hot water temperature target 3
Room
Reduce
Absent
Hot water
1x load
Reduce room temperature
Room temperature absent
1 x hot water
Party
Absent
Holiday
Public holiday
HC auto 1
Heating circuit auto. 1
HC auto 2
Heating circuit auto. 2
TP reset
Time program reset
DHW auto 1
Hot water auto. 1
DHW auto 2
Hot water auto. 2
Circulation
Circulation program
Sound program
Display
System
Ext. source
Inputs/Outputs
ISM
Glycol
Language
Time
Date
LCD brightness
LCD illumination duration
Outdoor unit
Indoor unit
Heating system
Pump dT heating
Pump dT cooling
Config. ext. heat source
External power hot water
External power stage 1
External power stage 2
Bivalence function
Bivalence function
Smart grid
Smart grid mode
HT/NT function
HT/NT contact
Room thermostat
Interlink function
Programmable output (230V)
Func. burner blocking contact
AUX switching function
AUX wait time
Switching threshold TDHW (AUX)
Continuous heating
Heating support (HZU)
Heating support power
Heating support hysteresis
Heating support max. temp.
Min. pump power
Max. pump power
HP Power limitation
Pump limit
6 Parameter overview

6.1 Menu: Operating mode

Fig.6-1 Parameter in menu: "Operating mode"

6.2 Menu: User

6.4 Menu: Settings

Fig.6-2 Parameter in menu: "User"

6.3 Menu: Time program

Fig.6-3 Parameter in menu: "Time program"
Fig.6-4 Parameter in menu: "Settings"
Operating Instructions
26
Daikin controller RoCon+ HP1
Daikin RoCon+ HP
008.1447899_00 – 09/2019 – EN
Page 27
6 Parameter overview
Hot water sensor
Water pressure sensor
Heat limit, reducing mode
Heating curve
Feed temperature, heating mode
Feed temperature, reducing mode
Min. feed temperature
Room sensor adaptation
Feed temperature lower limit
Cooling setpoint correction
Interlink temperature reduction
Max. hot water loading time
Hot water blocking time
Outside temperature correction
Water pressure, min.
Water pressure, max.
Water pressure, target
Maximum pressure loss
Weather-compensated
Frost protection temperature
Building insulation
Heat limit, heating mode
Max. feed temperature
Room influence
Heating curve adaptation
Interlink temperature increase
Feed temperature, cooling mode
Circulation pump control
Circulation pump interval
Anti-legionella day
Anti-legionella start time
Anti-legionella temperature
Addition
Sensors
Access
DHW
HC config
Heating
Cooling curve
Cooling
Parameters
Wizard
Reset
Feed temperature, overshoot
Comfort heating
Outside temperature sensor
Switch temp. heating circuit
Hot water hysteresis
Wait time ext. heat generator
Target flow cooling, start
Start cooling outside temp.
Max. cooling outside temp.
Target flow cooling, max.
Relay test
Ventilation
Ventilation function
Screed
Screed drying
Program
Screed program
Parameter reset
Solar function
Hot water temperature, current
Hot water temperature, target
Return flow temperature
Feed temperature HC target
Feed temperature BUH
Outdoor temperature (optional)
Refrigerant temperature
Volume flow
Feed temperature, current
Feed temperature, target
Feed temperature PHX
Average outside temperature
Feed temperature HC current
Current
Overview
Values
Pressure
Mode
External request
Room thermostat/Interlink
Quiet mode
Status, heat circulation pump
PWM pump
BUH current output
3UVB1 position
3UVDHW position
Heat generator type
Software no. B1/U1
Software no. controller
Glycol
Water pressure
Heating support
Water pressure
Emergency
Manual operation
Protocol
Screen
Manual operation status
Temperature, manual operation
Error screen
Mixer #X
Address
Bus scan
Controller BM1/BE1 #X
Terminal address

6.5 Menu: Configuration

6.6 Menu: Information

Fig.6-5 Parameter in menu: "Configuration"
Daikin RoCon+ HP Daikin controller RoCon+ HP1
008.1447899_00 – 09/2019 – EN
Fig.6-6 Parameter in menu: "Information"

6.7 Menu: Error

Fig.6-7 Parameter in menu: "Error"

6.8 Menu: Terminal

Fig.6-8 Parameter in menu: "Terminal"
Operating Instructions
27
Page 28
6 Parameter overview
Month
Total
Energy HP, cooling
Energy HP, heating
Energy, hot water
Energy HP total
Electr. energy total
Reset
Ext. energy source, hot water
Ext. energy source, heating
Energy HP, cooling
Energy HP, heating
Energy, hot water
Energy HP total
Electr. energy total
Runtime, compressor
Runtime, pump
INFORMATION
If the local control panel is used as a remote control for a mixer module, both the standard screen and the menu structure are changed (see Chap. 9).

6.9 Menu: Statistics

Fig.6-9 Parameter in menu: "Statistics"
Operating Instructions
28
Daikin controller RoCon+ HP1
Daikin RoCon+ HP
008.1447899_00 – 09/2019 – EN
Page 29

7 Parameter settings

7 Parameter settings

7.1 Explanation of the parameter tables

The parameter tables listed in Chap. 7.2 to Chap. 7.10 contain com­pact information on all parameters that are available in the respect­ive menus and submenus of the controller (1st menu level, 2nd menu level).
In addition to the parameter designations, the tables contain informa­tion on setting ranges, factory settings, setting options or adjustment steps and brief explanations of the function.
In addition, they provide an explanation of the access rights for oper­ation of the controller. The following abbreviations are used for cor­responding labelling:

7.2 Operating mode

[→Main menu →Operating mode]
BE Access right for the operator HF Access right with technician code
If different entries are made in the BE and HF columns, the technician must be logged in before selecting the parameter level in order to obtain the status entered in the HF column (see Chap. 4.5.1)
Status:
N Not visible E Visible and configurable S Visible
INFORMATION
Changing some parameters requires a restart of the device. This takes a few minutes. No further settings can be made during this time. The restart can be delayed by 5minutes in response to the prompt "Restart required. Per­form now?" by selecting "later".
Parameters that require a restart are marked with (*) in the following tables
Parameters Setting range
Min / Max
Standby In this operating mode all internal functions are switched off. Frost protec-
tion remains active and a blocking protection for the pump is guaranteed. All controllers integrated in the RoCon system via the CAN bus are primar-
ily also switched to the operating mode if this setting is selected. Outputs are not always completely free of voltage.
Reduce The internal HC continuously regulates to the required reduced feed tem-
perature according to the [Heating curve] or [Feed temperature, reducing mode] parameters or to the room temperature [Reduce room temperature] if the room thermostat is connected. Domestic hot water preparation is car­ried out according to [Hot water auto. 1].
Heating The internal HC continuously regulates to the required feed temperature
according to the [Heating curve] or [Feed temperature, heating mode] parameters or to the room temperature [Room temperature target 1] if the room thermostat is connected. Domestic hot water preparation is carried out according to [Hot water auto. 1].
Summer The internal HC is switched off. Frost protection remains active and a
blocking protection for the pump is guaranteed. Domestic hot water prepar­ation is carried out according to [Hot water auto. 1].
All controllers integrated in the RoCon system via the CAN bus are primar­ily also switched to the operating mode if this setting is selected.
Automatic 1 The internal heating circuits are controlled according to the set [Heating cir-
cuit auto. 1] time program with the respective room target temperatures. Domestic hot water preparation is carried out according to [Hot water auto. 1].
Automatic 2 The internal heating circuits are controlled according to the set [Heating cir-
cuit auto. 2] time program with the respective room target temperatures. Domestic hot water preparation is carried out according to [Hot water auto. 2].
Cooling The internal heating circuit continuously regulates to the required feed tem-
perature according to the parameters in the menu [→Main menu →Con­figuration →Cooling] or to the [Room temperature target 1] room temperat­ure if the room thermostat is connected. Domestic hot water preparation is carried out according to [Hot water auto. 1]. Frost protection remains active and a blocking protection for the pump is guaranteed.
Tab.7-1 Parameter in the "Operating mode" menu
Description Factory
setting
Incre-
ment
BE HF
- E E
- E E
- E E
- E E
- E E
- E E
- E E
Access
Daikin RoCon+ HP Daikin controller RoCon+ HP1
008.1447899_00 – 09/2019 – EN
Operating Instructions
29
Page 30
7 Parameter settings

7.3 User

[→Main menu →User]
7.3.1 Menu: Room temperature target
[→Main menu →User →Room]
Parameters Setting range
Min / Max
Room temper­ature target 1
Room temper­ature target 2
Room temper­ature target 3
Tab.7-2 Parameter in the "Room temperature target" menu
5 – 40°C Target value of the room temperature in °C, which is valid for the 1st
switching time cycle of the [Automatic 1] and [Automatic 2] time programs.
5 – 40°C Target value of the room temperature in °C, which is valid for the 2nd
switching time cycle of the [Automatic 1] and [Automatic 2] time programs.
5 – 40°C Target value of the room temperature in °C, which is valid for the 3rd
switching time cycle of the [Automatic 1] and [Automatic 2] time programs.
7.3.2 Menu: Reduce room temperature
[→Main menu →User →Reduce]
Parameters Setting range
Min / Max
Reduce room temperature
Tab.7-3 Parameter in the "Reduce room temperature" menu
5 – 40°C Target value of the reduced room temperature in °C, which is valid for the
[Automatic 1] and [Automatic 2] time programs.
7.3.3 Menu: Room temperature absent
[→Main menu →User →Absent]
Parameters Setting range
Min / Max
Room temper­ature absent
Tab.7-4 Parameter in the "Room temperature absent" menu
5 – 40°C Target value of the reduced room temperature in °C, which is valid for the
[Absent] + [Holiday] time programs.
Description Factory
setting
20°C 0.5°C E E
20°C 0.5°C E E
20°C 0.5°C E E
Description Factory
setting
15°C 0.5°C E E
Description Factory
setting
15°C 0.5°C E E
Incre-
ment
Incre-
ment
Incre-
ment
Access BE HF
Access BE HF
Access BE HF
7.3.4 Menu: Hot water temperature, target
[→Main menu →User →Hot water]
Parameters Setting range
Min / Max
Hot water tem­perature target 1
Hot water tem­perature target 2
Hot water tem­perature target 3
Tab.7-5 Parameter in the "Hot water temperature, target" menu
35 – 70°C Target value of the hot water temperature in °C, which is valid for the 1st
switching time cycle of the [Automatic 1] and [Automatic 2] time programs.
35 – 70°C Target value of the hot water temperature in °C, which is valid for the 2nd
switching time cycle of the [Automatic 1] and [Automatic 2] time programs.
35 – 70°C Target value of the hot water temperature in °C, which is valid for the 3rd
switching time cycle of the [Automatic 1] and [Automatic 2] time programs.
Description Factory
7.3.5 Menu: 1 x hot water
[→Main menu →User →1x load]
Parameters Setting range
Min / Max
1 x hot water Off Start of one-time domestic hot water preparation to the set target value
On
Tab.7-6 Parameter in the "1 x hot water" menu
[Hot water temperature target 1] without time limit, independent of the heat­ing programs.
Description Factory
Incre-
setting
48°C 0.5°C E E
48°C 0.5°C E E
48°C 0.5°C E E
setting
ment
Incre-
ment
Access BE HF
Access BE HF
- E E
Operating Instructions
30
Daikin controller RoCon+ HP1
Daikin RoCon+ HP
008.1447899_00 – 09/2019 – EN
Page 31

7.4 Time Program

[→Main menu →Time program]
7 Parameter settings
Parameters Setting range
Min / Max
Party 0 – 360min This operating mode can be used to set a unique time for temporarily ex-
tending the heating time of the internal heating circuit.
Absent 0 – 360min This operating mode can be used to set a one-off time for temporary regu-
lation to the parametrised absence temperature.
Holiday Date 1st day
-
Date last day
Public holiday Date 1st day
-
Date last day
Heating circuit auto. 1
Heating circuit auto. 2
Hot water auto. 1
Hot water auto. 2
Circulation program
Sound pro­gram
See Chap. 4.3 In this menu, the 1st time program can be parametrised for the internal HC.
See Chap. 4.3 In this menu, the 2nd time program for the internal HC can be paramet-
See Chap. 4.3 This menu can be used to parametrise the 1st time program for domestic
See Chap. 4.3 This menu can be used to parametrise the 2nd time program for domestic
See Chap. 4.3 This menu can be used to parametrise a timer program for the circulation
See Chap. 4.3
0 – 3
The internal heating circuit provides continuous (24h per day) regulation to the parametrised absence temperature ([Reduce room temperature] para­meter).
A calendar function can be used to enter a time period of absence. A calendar function can be used to enter a time period of presence.
During this period of time, regulation is carried out exclusively according to the settings for "Sunday" in the [Heating circuit auto. 1] and [Hot water auto. 1] time programs.
3 switching cycles with a resolution of 15minutes can be set. A separate entry for each weekday is possible. Format: (on) hh:mm – hh:mm (off)
Also, the cycles from Monday to Friday, Saturday to Sunday and Monday to Sunday can be parametrised.
rised. 3 switching cycles with a resolution of 15minutes can be set. A sep­arate entry for each weekday is possible. Format: (on) hh:mm – hh:mm (off)
Also, the cycles from Monday to Friday, Saturday to Sunday and Monday to Sunday can be parametrised.
hot water preparation. 3 switching cycles with a resolution of 15minutes can be set. A separate entry for each weekday is possible. Format: (on) hh:mm – hh:mm (off)
Also, the cycles from Monday to Friday, Saturday to Sunday and Monday to Sunday can be parametrised.
hot water preparation. 3 switching cycles with a resolution of 15minutes can be set. A separate entry for each weekday is possible. Format: (on) hh:mm – hh:mm (off)
Also, the cycles from Monday to Friday, Saturday to Sunday and Monday to Sunday can be parametrised.
pump. 3 switching cycles with a resolution of 15minutes can be set. A sep­arate entry for each weekday is possible. Format: (on) hh:mm – hh:mm (off)
Also, the cycles from Monday to Friday, Saturday to Sunday and Monday to Sunday can be parametrised.
In this menu, a time program can be parametrised for various stages of the heat pump quiet mode. 3 switching cycles with a resolution of 15minutes can be set. A separate entry for each weekday is possible. Format: (on) hh:mm – hh:mm (off)
Also, the cycles from Monday to Friday, Saturday to Sunday and Monday to Sunday can be parametrised.
A noise level can be assigned to each switching cycle (0: no noise reduc­tion, 1: Min. noise reduction, 2: Med. noise reduction , 3: Max. noise reduc­tion).
Note: This program can therefore only be set by the installer.
Description Factory
Incre-
setting
0min 15min E E
0min 15min E E
- 1 day E E
- 1 day E E
See
Tab. 4-3
See
Tab. 4-3
See
Tab. 4-3
See
Tab. 4-3
See
Tab. 4-3
0 15min N E
ment
15min E E
15min E E
15min E E
15min E E
15min E E
Access
BE HF
Daikin RoCon+ HP Daikin controller RoCon+ HP1
008.1447899_00 – 09/2019 – EN
Operating Instructions
31
Page 32
7 Parameter settings
Parameters Setting range
Min / Max
Time program reset
Tab.7-7 Parameter in menu: "Time program"
Party This menu can be used to reset the time programs to factory settings. To Absent Holiday Public holiday Heating circuit
auto. 1 Heating circuit
auto. 2 Hot water auto.
1 Hot water auto.
2 Circulation pro-
gram Sound program
do this, select the respective time programs and then confirm the selection with the Confirm icon.

7.5 Settings

[→Main menu →Settings]
7.5.1 Menu: Display settings
[→Main menu →Settings →Display]
Description Factory
setting
- - E E
Incre-
ment
Access BE HF
Parameters Setting range
Min / Max
Language Deutsch National language of the display texts on the control panel - E E
English
Français
Nederlands
Español
Italiano
Português
Lietuvos
Time Time in hours/minutes format. E E Date Current date in day/month/year format. The current day of the week is cal-
culated automatically from the date.
LCD bright­ness
LCD illumina­tion duration
Tab.7-8 Parameter in the "Display settings" menu
10 – 100% Brightness of the display 80% 10% E E
1 – 60s Lighting duration of the display 30s 1s E E
Description Factory
setting
Incre-
ment
Access BE HF
E E
7.5.2 Menu: System
[→Main menu →Settings →System]
Parameters Setting range
Min / Max
Outdoor unit No selection Heat pump outdoor unit type - - N E
14kW 16kW 18kW
Description Factory
setting
Incre-
ment
Access BE HF
Operating Instructions
32
Daikin controller RoCon+ HP1
Daikin RoCon+ HP
008.1447899_00 – 09/2019 – EN
Page 33
7 Parameter settings
Parameters Setting range
Min / Max
Indoor unit No selection Heat pump interior unit type.
ETS(H/X)
(B)16P30D
ETS(H/X)
(B)16P50D
Heating sys­tem (*)
Pump dT heat­ing (*)
Pump dT cool­ing (*)
Glycol (*) No glycol added Adding glycol to the water circuit is recommended to guarantee frost pro-
HP Power lim­itation
Pump limit This parameter defines the maximum pump speed. Under normal condi-
Tab.7-9 Parameter in the "System" menu
Floor heating Heat exchanger type in the heating system.
Convector
Radiator
3 – 10 Required temperature difference between return and feed temperature. If a
3 – 10 Required temperature difference between return and feed temperature. If a
Glycol added
20 – 50A The permanent power limitation is useful to ensure maximum power con-
0 No limit
1 – 4 Limitation of pump speed independent of the operating status. This setting
5 – 8 Limitation of the pump speed if there is no heating or cooling requirement.
Adaptation of the set value important, as the device types have different defrosting logics.
If "Radiator" is selected and high feed temperatures are desired, it may make sense to increase the [Max. feed temperature] parameter to 65°C ([→Main menu →Configuration →Heating]).
minimum temperature difference is required for good heat distribution sys­tem operation in heating mode.
minimum temperature difference is required for good heat distribution sys­tem operation in cooling mode.
tection in the event of a power failure. If glycol has been added to the sys­tem, the RoCon+ controller setting must be adapted accordingly.
sumption of the system. In some countries, legislation limits the maximum power consumption for room heating and domestic hot water.
tions, the default setting should NOT be changed. The limitation of the pump speed is skipped if the flow rate is in the range of the minimum flow rate. The water flow resulting at limited pump speed can be taken from the pump characteristic curve (see Installation and maintenance instructions Daikin Altherma ETS(X/H))
cannot guarantee heating comfort. The maximum pump speed depends on the setting as follows: 1:90%, 2:75%, 3:65%,4:55%
The maximum pump speed depends on the setting as follows: 5:90%, 6:75%, 7:65%, 8:55%
Description Factory
Incre-
setting
- - N E
5 1 N E
5 1 N E
50A N E
6 1 N E
ment
Access
BE HF
- N E
- N E
7.5.3 Menu: External heat source
[→Main menu →Settings →Ext. source]
Parameters Setting range
Min / Max
Config. ext. heat source
External power hot water
External power stage 1 (*)
External power stage 2 (*)
No external heat generator
Backup heater BUH
DHW + heating support
Two external heat generators
1 – 40kW Heat output of the electric heater booster for domestic hot water prepara-
1 – 40kW Heat output of the electric heater booster for heating support stage 1
1 – 40kW Heat output of the electric heater booster for heating support stage 2
Setting of whether there is an additional external heat generator for do­mestic hot water preparation (DHW) and/or heating support (HZU).
The heat pump is the only heat source
Optional heating rod (3N~) installed in the storage tank
An alternative heat generator (e.g. backup heater 1N~) provides domestic hot water preparation and backup heating
Two external heat generators: Alternative WEZ 1 (e.g. backup heater 1N~) takes over domestic hot water preparation and alternative WEZ 2 takes over heating support
tion
See operating instructions for heating element EKBUxx.
See operating instructions for heating element EKBUxx.
Description Factory
setting
3kW 1kW N E
3kW 1kW N E
3kW 1kW N E
Incre-
ment
BE HF
- N E
Access
Daikin RoCon+ HP Daikin controller RoCon+ HP1
008.1447899_00 – 09/2019 – EN
Operating Instructions
33
Page 34
7 Parameter settings
Parameters Setting range
Min / Max
Bivalence function (*)
Aux. heating al-
ways possible
Aux. heating T-
biv. dependent
Bivalence tem­perature
Tab.7-10 Parameter in the "External heat source" menu
-15°C – +35°C Setting influences the effect of the potential-free AUX switching contact
The bivalence function is only relevant to operation of the optional heater booster due to a backup request (room heating mode).
Operation of the backup heater is always possible.
Backup heater is only released if the temperature set in the [Bivalence temperature] parameter is undercut.
(toggle switch output A) defined in the [AUX switching function] parameter. Only if [Bivalence function] parameter = heating up T-bivalence: Outside temperature as of which the optional heater booster is activated to
support room heating. The bivalence temperature is relevant to operation of the optional heater booster due to a backup request (room heating mode). The temperature of the temperature sensor (information value TemperatureA) integrated in the heat pump outdoor unit is used for this.
Description Factory
setting
0°C 1°C N E
Incre-
ment
- N E
Access BE HF
7.5.4 Menu: Inputs/Outputs
[→Main menu →Settings →Inputs/Outputs]
Parameters Setting range
Min / Max
Smart grid Evaluation of the SG signal (see Chap. 4.4). - N E
Off Smart Grid function not active, SG signal is not evaluated.
On Depending on the utility company signal, the heat pump is shut off (no frost
protection function) or operated at higher temperatures.
Smart grid mode
Comfort Increase of the hot water target temperature by 5K
Standard Increase of the feed target temperature by 2K and increase of the hot wa-
Eco Increase of the feed target temperature by 5K and increase of the hot wa-
HT/NT func­tion
Inactive Deactivated (no effect)
Switch off com-
pressor
Switch off com­pressor + BUH
Switch all off Everything is switched off (no frost protection function, see Chap. 4.5.3)
HT/NT contact Definition of whether the HT/NT input is evaluated as a normally closed
Normally open
contact
Normally closed
contact
Only if [Smart grid] parameter = On: Is used for a possible target temperature increase with a Smart Grid
switch-on command.
ter target temperature by 5K
ter target temperature by 7K Setting of which heat sources are switched off if the high rate signal output
by the utility company (EVU) is received in the case of a low rate mains connection.
Refrigerant compressor is switched off
Refrigerant compressor and backup heater are switched off
contact or a normally open contact. Switching contact closed during high rate.
Switching contact closed during low rate.
Description Factory
setting
Incre-
ment
BE HF
- N E
- N E
- N E
Access
Operating Instructions
34
Daikin controller RoCon+ HP1
Daikin RoCon+ HP
008.1447899_00 – 09/2019 – EN
Page 35
7 Parameter settings
Parameters Setting range
Min / Max
Room thermo­stat
No Deactivated
Yes Only if [Interlink function] parameter = Off:
Interlink func­tion
Off Deactivated
On Evaluation of the heating nd cooling switching contacts at plug connection
Programmable output (230V)
Func. burner blocking con­tact
Inactive The output has no function.
Heating circuit
request
Circulation re-
quest
Direct heating circuit request
Resistance val-
ues
Burner blocking
contact
Description Factory
setting
Configuration of a room thermostat with potential-free contacts connected to Daikin Altherma ETS(X/H) connection J16.
Evaluation of the heating and cooling switching contacts at plug connection J16 on the RoCon BM2C PCB (only if none of the "Standby", "Reduce", "Summer", "Holiday", "Public holiday" or "Screed" is active):
▪ Closed heating switching contact: Operating mode is switched to "Heat-
ing". Priority if both switching contacts are closed.
▪ Closed cooling switching contact: Operating mode is switched to "Cool-
ing". Open contacts: Only frost protection active. Configuration for systems that are operated with 2 different feed target
temperatures (see Chap. 4.4.4). One possible application is, for example, the additional integration of an
HP convector in a surface heating and cooling system. Prerequisite: 2 room thermostats are connected to Daikin Altherma ETS(X/
H) plug connection J16.
J16 on the RoCon BM2C PCB. Activation of cooling mode only by switching the operating mode to "Cool-
ing" (see Chap. 4.1). Setting of the [Room thermostat] parameter is no longer evaluated. ▪ Open switching contacts: Only frost protection active ▪ "Heating" and "Automatic 1" / "Automatic 2" operating mode active dur-
ing the switching cycles in day mode.
▪ Closed heating switching contact = IL1:
▪ It is regulated to the normal feed target temperature in accordance
with the parameter settings in [→Main menu →Configuration
→Heating]. ▪ Closed cooling switching contact = IL2: ▪ The system is regulated to the increased feed target temperature (nor-
mal feed target temperature + value of the [Interlink temperature in-
crease ] parameter. Priority if both switching contacts are closed!
▪ "Cooling" operating mode active.
▪ Closed heating switching contact = IL1: ▪ It is regulated to the normal feed target temperature in accordance
with the parameter settings in [→Main menu →Configuration
→Heating]. ▪ Closed cooling switching contact = IL2:
The system is regulated to the reduced feed target temperature (normal feed target temperature value of the [Interlink temperature reduction] para­meter. Priority if both switching contacts are closed
Configuration of the multi-function output (230V, J14 connection): - N E
Header pump – The output becomes active as soon as any heating circuit (e.g. mixer circuit) of the system reports a heat request to the heat gener­ator.
Circulation pump – The output is activated either after the time program of the circulation pump or after the time program of the domestic hot water preparation, depending on the parametrisation (see Chap. 4.3).
Feeder pump – The output becomes active as soon as a heat requirement is pending for the direct heating circuit of the heat generator.
Selection of the functionality of the EXT switching contact (J8) (see
Chap. 4.1)
Incre-
ment
Access
BE HF
- N E
- N E
- N E
Daikin RoCon+ HP Daikin controller RoCon+ HP1
008.1447899_00 – 09/2019 – EN
Operating Instructions
35
Page 36
7 Parameter settings
Parameters Setting range
Min / Max
AUX switching function
Inactive Function deactivated.
Switching
threshold TDHW
(AUX)
Heating/cooling
request
BUH request If a hot water request to the backup heater (EKBUxx) is present or the con-
Error If an error is pending
TVBH >60°C If the sensor value (TVBH) is >60°C.
Outside temper-
ature
Outside temp. +
DHW/heating
DHW request If a hot water request is present.
Outside temper-
ature + heating
Multi-oil If the outside temperature is < [Bivalence temperature] parameter value +
Cooling mode If the heat pump is in the "Cooling" operating mode.
AUX wait time 0 – 600s AUX switching contact(A) only switches after a delay if the switching con-
Switching threshold TDHW (AUX)
Tab.7-11 Parameter in the "Inputs/Outputs" menu
20 – 85°C Storage tank temperature (Tdhw) switching threshold for AUX switching
Setting assigns the switching conditions for the potential-free AUX switch­ing contact (toggle switch output A, see Chap. 4.4.4).
AUX switching contact switches:
If storage tank temperature (Tdhw) ≥ value of [Switching threshold TDHW (AUX)] parameter.
If a cooling request or heating request is present.
figured backup heater is requested for heating support.
If the outside temperature is < [Bivalence temperature] parameter value. (heat pump continues to operate = parallel equilibrium mode)
If the outside temperature is < [Bivalence temperature] parameter value + a heating request or a hot water request is present. (heat pump does not continue to operate = alternative equilibrium mode)
If the outside temperature is < [Bivalence temperature] parameter value + "room heating" heat request (not for hot water request). Heat pump no longer operates in room heating mode below the value set in the [Bi­valence temperature] parameter – only in hot water mode.
Application: Alternative room heating bi-valence mode if the boiler is hy­draulically integrated so that it directly heats the unpressurised storage tank water of the Daikin Altherma ETS(X/H) (connection via solar connec­tions).
"room heating" heat request (not for hot water request). Heat pump no longer operates in room heating mode below the value set in the [Bi­valence temperature] parameter – only in hot water mode.
Application: Alternative room heating equilibrium mode if the boiler is hy­draulically integrated in the heat pump feed. For this application type, the frost protection function must be deactivated on the Daikin Altherma ETS(X/H) ([Frost protection temperature] parameter = Off).
dition (see [AUX switching function] parameter) is present for longer than the set time.
contact (see [AUX switching function] parameter).
Description Factory
Incre-
setting
120s 5s N E
50°C 1°C N E
ment
Access
BE HF
- N E
7.5.5 Menu: Intelligent Storage Mgmt
[→Main menu →Settings →ISM]
Parameters Setting range
Min / Max
Continuous heating
Off No uninterrupted heating On Uninterrupted heating. When the evaporator is being defrosted, heat for
Heating sup­port (HZU)
Off No heating support On Heating support function active
Operating Instructions
This function enables uninterrupted heating, even when the evaporator is being defrosted. This enables high comfort to be guaranteed, even with rapidly reacting heating systems (e.g. convectors).
heating is taken from the storage tank. Heating support from hot water storage tank if minimum temperature is ex-
ceeded (see Chap. 4.4 and [Heating support hysteresis] parameter).
36
Description Factory
setting
Daikin controller RoCon+ HP1
008.1447899_00 – 09/2019 – EN
Incre-
ment
Access BE HF
- N E
- N E
Daikin RoCon+ HP
Page 37
7 Parameter settings
Parameters Setting range
Min / Max
Heating sup­port power
Heating sup­port hysteresis
Heating sup­port max. temp.
Min. pump power
Max. pump power
Tab.7-12 Parameter in the "Intelligent Storage Mgmt" menu
3 – 40kW The setting limits the heating support output. 15kW 1kW N E
2 – 15 Only if [Heating support (HZU)] parameter = On.
Heating support is activated if Tdhw > THZUmin + 4K and Tdhw > [Feed temperature, target] + 1K. Heating support is deactivated if Tdhw < THZUmin or Tdhw < [Feed temperature, target]. THZUmin = currently active hot water target temperature [Feed temperat-
ure, target] + set [Heating support hysteresis] parameter value. Tdhw = current hot water storage tank temperature [Feed temperature, target] = currently active feed target temperature (see
Chap. 4.5)
5 – 85°C The setting limits the target feed temperature (measured against t
when the heating support function is active.
40 – 80% Lower limit for pump operation. Only used when heating support is active
or heat is generated by an external heat source. During normal operation, the pump is controlled according to the [Pump limit] parameter, see
Chap. 7.5.2.
60 – 80% Upper limit for pump operation. Only used when heating support is active
or heat is generated by an external heat source. During normal operation, the pump is controlled according to the [Pump limit] parameter, see
Chap. 7.5.2.
Description Factory
setting
5 1 N E
V, BH
)
60°C 1°C N E
50% 1% N E
80% 1% N E
Incre-
ment
Access
BE HF

7.6 Configuration

[→Main menu →Configuration]
7.6.1 Menu: Sensors
[→Main menu →Configuration →Sensors]
Parameters Setting range
Min / Max
Outside tem­perature sensor (*)
Hot water sensor
Water pres­sure sensor
Outside tem­perature cor­rection
Water pres­sure, min.
Integrated
sensor
Optional sensor
Inactive No function for domestic hot water preparation.
Sensor Function for domestic hot water preparation is activated. A storage temper-
Thermostat Function for domestic hot water preparation is activated. A thermostatic
Off No sensor evaluation On Sensor evaluation activated (if no pressure sensor is connected, an error
-5.0 – +5.0K Individual adjustment for the measured value of the outside temperature
0.1 – 5.0bar Defines the minimum water pressure.
Selection of whether the sensor integrated in the outdoor unit or an op­tional outside temperature sensor is used to determine the target feed tem­peratures
Configuration of the domestic hot water preparation: - N E
ature sensor is evaluated for domestic hot water preparation (if no storage temperature sensor is connected, an error message is generated).
switch (ON/OFF) is evaluated for domestic hot water preparation where an "open terminal" is evaluated as "not required".
Configuration of the sensor for detecting the water pressure of the system. - N E
message is generated.)
relevant for the controller.
Pressure monitor function (only with activated pressure sensor, [Water pressure sensor]= On): If the measured value falls below the set value, the Daikin Altherma ETS(X/H) is switched off and an error message gener­ated.
Description Factory
setting
0.0K 0.1K N E
0.5bar 0.1bar N E
Incre-
ment
BE HF
- N E
Access
Daikin RoCon+ HP Daikin controller RoCon+ HP1
008.1447899_00 – 09/2019 – EN
Operating Instructions
37
Page 38
7 Parameter settings
Parameters Setting range
Min / Max
Water pres­sure, max.
Water pres­sure, target
Maximum pressure loss
Tab.7-13 Parameter in the "Sensors" menu
0.1 – 5.0bar Defines the maximum water pressure. Pressure monitoring function (only with activated pressure sensor, [Water
pressure sensor] = On): If the measured value exceeds the set value, a warning message is generated.
0.1 – 5.0bar Defines the target water pressure. Pressure monitoring function (only with activated pressure sensor, [Water
pressure sensor] = On): If the measured value falls below the set value by more than the value set in the [Maximum pressure loss] parameter, a warning message is generated.
0.1 – 5.0bar Defines the maximum acceptable pressure loss in the heating system. Pressure monitoring function (only with activated pressure sensor, [Water
pressure sensor] = On): If the measured value falls below the set value by more than the value set in the [Water pressure, target] parameter, a warn­ing message is generated.
7.6.2 Menu: Heating circuit config.
[→Main menu →Configuration →HC config]
Parameters Setting range
Min / Max
Weather-com­pensated
Frost protec­tion temperat­ure
Building insu­lation
Switch temp. heating circuit
Tab.7-14 Parameter in the "Heating circuit config." menu
Feed temperat-
ure, fixed
Weather-com-
pensated
Off No frost protection of the HC 0°C 1°C E E
-15 – 5°C If the outside temperature drops below the set value, the system switches
Off Setting the building insulation standard. This influences the averaged out-
low
Normal
Good
Very good
Off Deactivated
10 – 40°C If the outside temperature exceeds the set value, the system is switched to
Selection of the method for determining the target feed temperature. - N E Feed temperature, fixed: Control to a fixed flow value (depending on oper-
ating mode) Weather-compensated: Weather-compensated control based on the heat-
ing curve
to frost protection operation (the pumps are switched on). The function is ended if the outside temperature rises above the set value +1K.
side temperature and the automatic adaptations of the heating curve and the heating times.
Automatic activation of cooling mode. 1°C N E
the "Cooling" operating mode. If the outside temperature falls 2K below the set value, the system automatically switches back to the previously ac­tivated operating mode
Description Factory
setting
3.0bar 0.1bar N E
0.9bar 0.1bar N E
0.5bar 0.1bar N E
Description Factory
setting
Incre-
ment
Incre-
ment
- E E
Access BE HF
Access BE HF
7.6.3 Menu: Heating
[→Main menu →Configuration →Heating]
Parameters Setting range
Min / Max
Heat limit, heating mode
Heat limit, re­ducing mode
Heating curve 0.0 – 3.0 Only if [Weather-compensated] parameter = Weather-compensated:
Operating Instructions
Off Setting of the automatic summer switch-off of the heating operation. If the
10 – 40°C
Off Setting the heating limit for the "switch-off" of the heating circuit during the
10 – 40°C
outside temperature measured and averaged by the controller exceeds the set value by 1K, the HC is switched off. The heating is released again if the outside temperature undercuts the set heating limit.
setback time (functioning as in [Heat limit, heating mode] parameter).
Setting of the heating curve. The heating curve reflects the dependence of the target feed temperature of the HC on the outside temperature (see
Chap. 4.5).
Description Factory
38
Incre-
setting
19°C 1K E E
10°C 1K E E
0.5 0.1 E E
008.1447899_00 – 09/2019 – EN
ment
Daikin controller RoCon+ HP1
Access BE HF
Daikin RoCon+ HP
Page 39
7 Parameter settings
Parameters Setting range
Min / Max
Feed temper­ature, over­shoot (*)
Feed temper­ature, heating mode
Feed temper­ature, reducing mode
Max. feed tem­perature
Min. feed tem­perature
Room influ­ence
Room sensor adaptation
Heating curve adaptation
Interlink tem­perature in­crease
0 – 4 This function defines how far the water temperature may exceed the feed
20 – 90°C Only if [Weather-compensated] parameter = Weather-compensated:
10 – 90°C Only if [Weather-compensated] parameter = Weather-compensated:
20 – 90°C The setting limits the feed temperature (measured at tV2) with active heat-
10 – 90°C The determined flow target temperature of the heating circuit is limited to
Off Purely weather-compensated feed temperature control
0K Purely weather-compensated feed temperature control, but internal circula-
1 – 20K Causes a correction of the target feed temperature (parallel shift of the
-5 – +5K Only with room control connected and assigned to the HC.
Off Deactivated
On Activated = start of a one-time automatic heating curve adaptation.
1 – 50K Only if [Interlink function] parameter = On:
Description Factory
target temperature before the compressor is stopped. The compressor re­sumes operation when the feed temperature falls below the target feed temperature. This function ONLY applies to heating mode.
Setting of the target feed temperature for the heating circuit during the heating time in operating mode: "Automatic 1", "Automatic 2", "Heating".
Setting the target feed temperature for the heating circuit during the set­back time for the operating mode: "Automatic 1", "Automatic 2", "Heating".
ing support function. The determined target feed temperature of the HC is limited to the max-
imum value set here. If an optionally connected mixed HC requests a higher temperature of the
heat generator, this is taken into account. This means the internal circula­tion pump of the heat generator always runs if the generator is switched on. If the direct HC supplies the floor heating, a mechanical temperature limiter must be installed to prevent any overheating of the screed.
the minimum value set here. Only with the room control connected and assigned to the HC:
The setting of what influence the deviation of the room temperature meas­ured by EHS157034 from the current target value (see Chap. 4.2) has on the feed temperature.
tion pump continues running until the next heating cycle after a heat re­quirement during the setback cycle.
heating curve) by the set factor. If the measured temperature lies 2K be­low the target value, the target feed temperature is increased by 2x the set value.
Individual adjustment of the room temperature relevant to the controller. If a systematic deviation of the room temperature measured by the
EHS157034 to the actual temperature in the occupied area of this room is determined, the measured value can be corrected by the set value.
The function can only be carried out with a room controller connected and assigned to the HC:
Prerequisites: ▪ Outside temperature <8°C ▪ Setting of the operating mode: "Automatic 1" or "Automatic 2" ▪ Duration of the setback period is at least 6hours Function: At the start of the setback time, the current room temperature is
set as the target value for the following 4 hours. The heating curve that is required to maintain this room temperature is determined from the target feed temperature by the controller.
If the automatic heating curve adaptation is interrupted, the function pauses until the adaptation is successfully carried out or ended the next day (setting the parameter to "Off" or changing the current operating mode).
Domestic hot water preparation and heating optimisation is locked during the automatic heating curve adaptation.
Feed target temperature is increased by the set value when the cooling RT switching contact is closed. Request, e.g. by HP convector.
Incre-
setting
3 1 N E
40°C 1°C E E
10°C 1°C E E
80°C 1°C N E
10°C 1°C N E
0.0K 1K E E
5K 1K N E
ment
Access
BE HF
1K E E
- N E
Daikin RoCon+ HP Daikin controller RoCon+ HP1
008.1447899_00 – 09/2019 – EN
Operating Instructions
39
Page 40
7 Parameter settings
Parameters Setting range
Min / Max
Comfort heat­ing
Off Only if the heating demand is not covered is the storage tank temperature
On At corresponding outside temperatures, the storage tank temperature is al-
Tab.7-15 Parameter in the "Heating" menu
If the heat pump cannot cover the heating demand when outside temperat­ures are very low, heat is extracted from the storage tank and used for room heating (see Chap. 4.5.4)
raised. During the time it takes to raise the temperature, there may be a slight loss of comfort.
ways raised above the storage tank temperature set for the hot water re­quirement. The power consumption of the heat pump may increase.
7.6.4 Menu: Cooling
[→Main menu →Configuration →Cooling]
Parameters Setting range
Min / Max
Target flow cooling, start
Target flow cooling, max.
Start cooling outside temp.
Max. cooling outside temp.
Feed temper­ature lower limit
Feed temper­ature, cooling mode
Cooling set­point correc­tion
Interlink tem­perature re­duction
Tab.7-16 Parameter in the "Cooling" menu
5 – 25°C Only if [Weather-compensated] parameter = Weather-compensated:
Setting of the cooling feed target temperature at the start of cooling mode (outside temperature = [Start cooling outside temp.] parameter)
5 – 25°C Only if [Weather-compensated] parameter = Weather-compensated:
Setting of the minimum cooling feed target temperature. This is held con­stant as of the outside temperature ([Max. cooling outside temp.] para­meter).
15 – 45°C Only if [Weather-compensated] parameter = Weather-compensated:
Setting as of which outside temperature cooling mode starts with the highest cooling feed target temperature [Target flow cooling, start] (setting condition: "Cooling" operating mode).
20 – 45°C Only if [Weather-compensated] parameter = Weather-compensated:
Setting of the outside temperature at which the lowest cooling feed target temperature [Target flow cooling, max.] is specified (setting condition: "Cooling" operating mode).
5 – 25°C Setting of the absolute lower limit of the cooling feed target temperature.
Limitation acts if a lower cooling feed target temperature is determined from other parameter settings.
If optional frost protection valves are installed in the system, the [Feed tem­perature lower limit] parameter must not be set below 7°C.
8 – 30°C Only if [Weather-compensated] parameter = Feed temperature, fixed:
Setting of the cooling feed target temperature (fixed value) for active cool­ing mode.
-5.0 – +5.0K Parallel shift of the cooling characteristic curve by the set value. 0.0K 1K N E
1 – 50K Only if [Interlink function] parameter = On:
When the RT switching contact cooling is closed, the cooling feed target temperature is reduced by the set value (see [Interlink function] para­meter). Request, e.g. by HP convector.
Description Factory
setting
Description Factory
setting
18°C 1°C E E
8°C 1°C E E
24°C 1°C E E
35°C 1°C E E
18°C 1°C N E
18°C 1°C E E
5K 1K N E
Incre-
ment
Incre-
ment
Access BE HF
N E
Access BE HF
7.6.5 Menu: Hot water
[→Main menu →Configuration →DHW]
Parameters Setting range
Min / Max
Max. hot water loading time
Operating Instructions
10 – 240min Setting of the maximum duration of a domestic hot water preparation cycle.
Then cancellation of domestic hot water preparation if the current hot water temperature does not reach the set target value in the [Hot water temperat­ure target 1] parameter.
40
Description Factory
setting
60min 10min N E
Daikin controller RoCon+ HP1
008.1447899_00 – 09/2019 – EN
Incre-
ment
Access BE HF
Daikin RoCon+ HP
Page 41
7 Parameter settings
Parameters Setting range
Min / Max
Hot water blocking time
Hot water hys­teresis
Wait time ext. heat generator
Solar function Used to reduce the target temperature of the hot water storage tank in or-
Circulation pump control
Circulation pump interval
Anti-legionella day
Anti-legionella start time
Anti-legionella temperature
Tab.7-17 Parameter in the "Hot water" menu
0 – 180min Setting of the blocking time after completion or cancellation of a domestic
hot water preparation cycle. The repeat request for domestic hot water pre­paration is operated after this blocking time has elapsed at the earliest.
2 – 20K Hot water charging switching threshold
Setting of the temperature difference by which the temperature in the hot water storage tank may fall in comparison with the currently valid hot water target temperature [Hot water temperature, target] before the heat pump for hot water charging is to be activated.
20 – 95min Delay time as of which the additional heat generator may support the heat
pump in hot water charging (see Chap. 4.5).
der to increase the yield of a connected solar system. The target value of the hot water temperature is set as a function of the outside temperature and in compliance with the safety functions. The following parameters are also defined: Hot water hysteresis = 5K; building insulation = Normal
Off Deactivated
On Activated if the switching contact EXT (J8) is also closed.
Setting for the control of a circulation pump. Use in France not permitted! - E E
Off Optional circulation pump is synchronously controlled to the active switch-
ing time program for domestic hot water preparation.
On Optional circulation pump is controlled according to the [Circulation pro-
gram] switching time program. Setting of the interval control for an optional circulation pump. Use in
France not permitted!
Off Deactivated. The circulation pump runs permanently during the release
times of the assigned switching time program ([Circulation pump control] parameter).
1 – 15min The circulation pump runs clocked (clock cycle ratio: pump runtime = set-
ting value each 15min). Setting of the day for thermal disinfection of the hot water storage tank. Off - E E
Off No thermal disinfection
Monday
...
Sunday
Daily Daily thermal disinfection
00:00 – 23:45 Setting of the start time for thermal disinfection of the hot water storage
60 – 70°C Setting of the hot water target temperature during thermal disinfection of
Day of thermal disinfection
tank (format hh:mm).
the hot water storage tank.
Description Factory
Incre-
setting
30min 10min N E
7K 1K E E
50min 1min E E
Off 1min E E
03:30 15min N E
65°C 1°C N E
ment
Access
BE HF
- E E
Daikin RoCon+ HP Daikin controller RoCon+ HP1
008.1447899_00 – 09/2019 – EN
Operating Instructions
41
Page 42
7 Parameter settings
7.6.6 Menu: Additional programs
[→Main menu →Configuration →Addition]
Parameters Setting range
Min / Max
Relay test Manual control of individual relays for test purposes. After confirmation of
this parameter with the rotary button, the list of relays 1 – 9 is displayed with a checkbox on the display. For selection and confirmation of a relay with the rotary button, a tick is placed in the checkbox and the respective relay is activated. Multiple selection is possible.
Output J1 Output J1 (internal heating circulation pump), output pump
Output J14 Output J14 (circulation pump), mixer "Open"
Output J2 con-
tact A
Output J2 con-
tact B
Output J12 3UV
DHW open
Output J12 3UV
DHW closed
Connection J3
N/O contact B
Connec. J3 changeover
contact A
Output J10 Output J10 (A1P power supply)
Output J17 relayK2Output J17 (pin 3) – relay K2 (RTX-EHS) output XBUH1 T2
Contact A on output J2 (switching valve 3UVB1), mixer "Closed"
Contact B on output J2 (switching valve 3UVB1)
Output J12, switching valve 3UV DHW "Closed"
Output J12, switching valve 3UV DHW "Open"
Connection J3 (potential-free relay: normally open B-B1) – AUX
Connection J3 (potential-free relay: Changer A-A1/A-A2) – AUX
Description Factory
Incre-
setting
- - N E
ment
Access BE HF
Output J17 relayK1Output J17 (pin 2) – relay K1 (RTX-EHS) output XBUH1 T3
Output J17 relayK3Output J17 (pin 4) – relay K3 (RTX-EHS) output XBUH1 T1
Ventilation function
Off Deactivated
On Start of the ventilation function
Screed Function for screed drying - N E
Off Deactivated
On The feed target temperature is regulated according to the set [Screed pro-
Screed pro­gram
Tab.7-18 Parameter in the "Additional programs" menu
10 – 70°C per
heating day
Activation of automatic ventilation of the Daikin Altherma ETS(X/H) and the connected HC.
gram]. The day on which the screed function is activated is not included in the running time of the screed program. The first day starts when the day changes at 00:00 am. On the day of activation, heating is carried out for the remaining time with the feed target temperature of the program of the first day (see Chap. 4.5.7).
Setting of the sequence program of the screed heating. An individual feed target temperature can be set for each day for a maximum duration of 28 days. The end of the screed program is defined by the 1st day with the tar­get value setting "Off" (see Chap. 4.5.7).
See
Chap. 4.5.7
- N E
1°C N E
Operating Instructions
42
Daikin controller RoCon+ HP1
Daikin RoCon+ HP
008.1447899_00 – 09/2019 – EN
Page 43

7.7 Information

[→Main menu →Information]
7.7.1 Overview
[→Main menu →Information →Overview]
7 Parameter settings
Parameters Setting range
Min / Max
Mode No request Current mode of the heating pump. - - S S
Heating Cooling
Domestic hot
water prepara-
tion
Defrost
External re­quest
Room thermo­stat/Interlink
Quiet mode Status of the Quiet mode - - S S Heating sup-
port
Status, heat circulation pump
PWM pump 25 – 100% Output of the internal heating circulation pump - - S S BUH current
output 3UVB1 posi-
tion 3UVDHW pos-
ition Heat generator
type Software no.
B1/U1 Software no.
controller Glycol No glycol added No glycol present in the heating circuit
Tab.7-19 Parameter in the "Overview" menu
No external
mode
Low rate EVU function HT/NT active and low rate.
High rate EVU function HT/NT active and high rate.
SGN EVU function Smart grid active, normal operation.
SG1 EVU function Smart grid active, discharge: No heat pump operation, no
SG2 EVU function Smart grid active, switch-on recommendation, operation at
SG3 EVU function Smart grid active, switch-on command and storage tank
Off If [Interlink function] = On: frost protection only; otherwise: Off
Request If [Room thermostat] = Yes
No heat request If [Room thermostat] = Yes
IL1 If [Interlink function] = On: Normal feed target temperature IL2 If [Interlink function] = On: In heating mode increased feed target temperat-
Off Status of the heating support - - S S On Off Output of the internal heating circulation pump (on/off) - - S S On
- Current output of the optional backup heater in kW - - S S
- The current position of the 3-way mixer valve 3UVB1 is displayed in %. - 1% S S
- The current position of the 3-way mixer valve 3UV DHW is displayed in %. - 1% S S
- The configured type of the heat generator is displayed. - - S S
- The software and version of the operating unit are displayed. - - S S
- The software number and version of the controller PCB are displayed. - - S S
Glycol added Glycol present in the heating circuit
External request: - - S S Heat pump operates in normal operation.
frost protection function.
higher target temperatures, inexpensive electricity.
charging to 70°C, inexpensive electricity Room thermostat/Interlink: - - S S
ure, in cooling mode reduced feed target temperature
Description Factory
setting
Incre-
ment
Access
BE HF
Daikin RoCon+ HP Daikin controller RoCon+ HP1
008.1447899_00 – 09/2019 – EN
Operating Instructions
43
Page 44
7 Parameter settings
7.7.2 Values
[→Main menu →Information →Values]
Parameters Unit Description Factory
setting
Feed temper­ature, current
Feed temper­ature, target
Average out­side temperat­ure
Hot water tem­perature, cur­rent
Hot water tem­perature, tar­get
Return flow temperature
Feed temper­ature HC cur­rent
Feed temper­ature HC tar­get
Feed temper­ature PHX
Feed temper­ature BUH
Outdoor tem­perature (op­tional)
Refrigerant temperature
Volume flow l/h The filtered value of the current water-side volume flow is displayed.
Water pres­sure
Tab.7-20 Parameter in the "Values" menu
INFORMATION
Depending on the device type, the system configuration and the status of the device software, individual listed in­formation parameters cannot be displayed or can be dis­played at a different parameter level.
°C The current feed temperature of the heat generator (tV1) is displayed in °C. - 1°C S S
°C The current target temperature of the heat generator is displayed in °C. - 0.1°C S S
°C The current outside temperature is displayed in °C. 0.1°C S S
°C The current temperature of the hot water storage tank is displayed in °C. If
no hot water function is activated, "----" is displayed.
°C The current target temperature for domestic hot water preparation is dis-
played in °C. If no hot water function is activated, "----" is displayed. Here, the current target value is always the maximum value of all requests relev­ant for this hot water circuit.
°C The current return flow temperature of the heat generator is displayed in
°C. If no respective sensor is connected to the heat generator, "----" is dis­played.
°C The temperature of the direct HC (tV2 is displayed with active heating sup-
port, otherwise tV1) in °C.
°C The (feed) target temperature of the direct HC is displayed in °C. - 0.1°C S S
°C The current feed temperature of the heat generator in the outdoor unit is
displayed.
°C The current feed temperature of the heat generator after the optional
backup heater is displayed.
°C The current outdoor temperature measured by the optional outdoor tem-
perature sensor is displayed.
°C The current refrigerant temperature of the outdoor unit (liquid) is displayed. - 0.1°C S S
If glycol is added and the internal flow switch is active, 0l/h is displayed.
bar The current water pressure is displayed. - 0.1bar S S
Incre-
ment
- 0.1°C S S
- 0.1°C S S
- 0.1°C S S
- 0.1°C S S
- 0.1°C S S
- 0.1°C S S
- 0.1°C S S
- 1l/h S S
Access BE HF
7.7.3 Water pressure
[→Main menu →Information →Pressure]
Parameters Unit Description Factory
setting
Water pres­sure
Tab.7-21 Parameter in the "Water pressure" menu
Operating Instructions
bar The current water pressure is displayed in bar. - 0.1bar S S
44
Incre-
ment
Daikin controller RoCon+ HP1
008.1447899_00 – 09/2019 – EN
Access BE HF
Daikin RoCon+ HP
Page 45

7.8 Error

[→Main menu →Error]
7 Parameter settings
Parameters Setting range
Min / Max
Emergency Emergency heating by backup heater or another external heat generator. - E E
Yes In the event of an error, emergency operation is automatically activated.
No In the event of an error, emergency operation by manual activation only.
Manual opera­tion status
Temperature, manual opera­tion
Tab.7-22 Parameter in the "Error" menu
Inactive Activation of the fixed feed temperature control (for diagnostic purposes). - E E
Active
20 – 80°C Required feed temperature for manual operation. 50°C - E E
Description Factory
setting
Incre-
ment
Access
BE HF

7.9 Terminal

[→Main menu →Terminal]
Parameters Setting range
Min / Max
Terminal ad­dress
Bus scan Off No function Off - E E
Controller BM1/BE1 #X
Mixer #X With a detected device only: Activation switches to the mixer module with
Tab.7-23 Parameter in the "Terminal" menu
Off Setting of the terminal ID of the control panel for system access. The set
0 – 9
On Controller checks which RoCon devices are connected in the system via
value must be unique throughout the entire system. Confirmation of this parameter with the rotary button effects a new initialisation of the controller.
All settings except "Off" authorise the user of the control panel to activate the terminal function and thus to operate all RoCon system components with a valid device ID.
CAN bus lines. Detected devices are displayed in the menu [→Main menu →Terminal] with type and data bus ID (e.g. MM#8 = mixer module with bus ID8).
With a detected device only: Activation switches to the heat generator with the bus ID X (see Chap. 4.8, [Bus ID heat generator] parameter).
the bus ID X (see Chap. 4.8, [Heating circuit assignment] parameter).
Description Factory
setting
Off 1 N E
Incre-
ment
BE HF
-
- E E
Access

7.10 Statistics

[→Main menu →Statistics]
Parameters Setting range
Min / Max
Energy HP, cooling
Energy HP, heating
Energy, hot water
Energy HP total
Electr. energy total
Ext. energy source, hot water
Daikin RoCon+ HP Daikin controller RoCon+ HP1
008.1447899_00 – 09/2019 – EN
- The amount of heat delivered by the heat pump for cooling operation is dis-
- The amount of heat delivered by the heat pump for heating operation is
- The amount of heat delivered by the heat pump for domestic hot water pre-
- The total amount of heat delivered by the heat pump is displayed in kWh
- The total electrical power consumed is displayed in kWh (per month).
- The volume of heat of the additional heat generator for domestic hot water
Description Factory
played in kWh (per month).
displayed in kWh (per month).
paration is displayed in kWh (per month).
(per month).
preparation in kWh is displayed.
Incre-
setting
- kWh S S
- kWh S S
- kWh
- kWh S S
ment
Operating Instructions
Access
BE HF
45
Page 46
7 Parameter settings
Parameters Setting range
Min / Max
Ext. energy source, heat­ing
Runtime, com­pressor
Runtime, pump
Reset - All parameters listed in the Statistics menu are reset to "0". (Specialist
Tab.7-24 Parameter in the "Statistics" menu
INFORMATION
Depending on the device type, the system configuration and the status of the device software, individual listed in­formation parameters cannot be displayed or can be dis­played at a different parameter level.
- The volume of heat of the additional heat generator for heating mode in kWh is displayed.
- The running time of the refrigerant compressor in h is displayed. - 1h S S
- The runtime of the internal heating circulation pump is displayed in h. - 1h S S
code required).
Description Factory

7.11 Configuration wizard

Only after hardware reset.
Parameters Setting range
Min / Max
Direct circuit configuration
Bus ID heat generator
Time master No Activation of a system-wide time master. The time master synchronises all
Tab.7-25 Parameter in the "Configuration Wizard" menu
0 – 15 Setting of the heating circuit ID for the direct heating circuit of the Daikin
Altherma ETS(X/H). The heating circuit ID must be unique throughout the entire RoCon system. There must be no overlap with the HC IDs of op­tional mixer circuits.
0 – 7 The setting must not be changed if more than 1 heat generator is integ-
rated in the RoCon system. Several heat generators integrated in the heat­ing system must be regarded as a special application. If necessary, contact a service technician.
Yes
controllers in the RoCon system with the time and date set on the time master. For all other control panels in the system, it is no longer possible to enter the time and date. There must only be one time master in the entire system. The parameter is not available if the time master parameter is ac­tivated on another controller in the RoCon system.
Description Factory
Incre-
setting
- kWh S S
- -
setting
0 1 N E
0 1 N E
ment
Incre-
ment
- N E
Access BE HF
Access BE HF
Operating Instructions
46
Daikin controller RoCon+ HP1
Daikin RoCon+ HP
008.1447899_00 – 09/2019 – EN
Page 47

8 Faults and malfunctions

8 Faults and malfunctions
DANGER: RISK OF ELECTROCUTION
Electrostatic charges can lead to voltage arcing that can destroy the electronic components.
▪ Ensure potential equalisation prior to touching the
switching panel PCB (e.g. by touching the switching panel holder).
The electronics of the Daikin Altherma ETS(X/H) indicate an error by red illumination of the status display, the appearance of the error screen on the display (see Chap. 8.4) and the appearance of the er­ror symbol on the start screen. An integrated error memory stores up to 15 error messages (see Chap. 8.3).
INFORMATION
A list of all error codes can be found in the Daikin Altherma ETS(X/H) installation and maintenance instructions, chapter "Errors, malfunctions, messages".
Troubleshooting: Error code E90XX
An error reset can be performed. This can be started from the cur­rently displayed error screen. If the error screen has been exited, it can be recalled via [→Main menu →Error →Screen].
If the same error is displayed again shortly, the cause of the error must be found and rectified by a specialist. In the meantime, emer­gency operation may be maintained. Emergency operation can be permitted via [→Main menu →Error →Emergency], see Chap. 8.1. If emergency operation has not been permitted, it can be started from the current error screen.
Troubleshooting: Other error codes
The cause of the error must be found and rectified by a specialist. In the meantime, emergency operation may be maintained. Emergency operation can be permitted via [→Main menu →Error →Emer­gency], see Chap. 8.1. If emergency operation has not been permit­ted, it can be started from the current error screen.
INFORMATION
To ensure that the error has not been caused by incorrect settings, set all the parameters back to the factory settings before possible replacement of components (see
Chap. 4.5.9).
If it is not possible to determine the cause of the fault, please consult a service technician.
Please have the essential device data ready for this: Type and manufacturer number of the Daikin Altherma
ETS(X/H) (see heat pump nameplate) as well as the soft­ware versions of:
a: Control panel RoCon+ B1 [→Main menu →Information →Values →Software no. B1/U1]
b: PCB RoCon BM2C [→Main menu →Information →Values →Software no. controller]
On optional RoCon system components: EHS157034 [Software no. B1/U1] EHS157068 [Mixer software number]

8.1 Emergency operation

[→Main menu →Error →Emergency] If the heat pump fails, the backup heater or another external heat
generator can be used as an emergency heater. If [Emergency] is set to "Yes", emergency operation is automatically activated in the event of an error. Otherwise, emergency operation can only be star­ted in the event of an error via the error screen.
If emergency operation is started via the error screen, the [Emer­gency] parameter remains set to "Yes", i.e. emergency operation is also started automatically in the event of future errors. If this is not desired, the [Emergency] parameter must be reset to "No" after the error has been corrected.

8.2 Manual Operation

[→Main menu →Error →Manual operation] In manual operation, the heat pump is controlled to a fixed feed tem-
perature. Manual operation should only be used for diagnostic pur­poses. Manual operation is started by setting the [Manual operation status] parameter to "Active". The desired feed temperature is set by [Temperature, manual operation] parameter.
With hydraulically controlled priority operation for domestic hot water preparation, it must be ensured that the feed target temperature set in manual operation is sufficient to achieve the stored hot water tar­get temperature ([Hot water temperature target 1] parameter).

8.3 Error protocol

[→Main menu →Error →Protocol] The error protocol can be read in this menu. The most recent error
message comes first. All previous messages are moved backwards with each new entry in the position. The 16th error message is de­leted if a new error message arrives. The error protocol can only be deleted by Service.
The protocol lists ▪ the error code, ▪ the PCB associated with the error (A1P or BM2, see Daikin
Altherma ETS(X/H) Installation and maintenance instructions)
▪ Date and time when the error occurred.

8.4 Error screen

[→Main menu →Error →Screen]
Fig.8-1 Error screen
If an error occurs, the error screen is displayed. This displays the er­ror code, an explanatory text and the date and time when the error occurred. Depending on the type of error, a reset can be carried out in the error screen by selecting the corresponding icons and/or emergency operation can be started (see Chap. 8.1). Selecting the Back icon closes the error screen and the display returns to the start screen.
If an error has occurred, the error screen can be called up manually via [→Main menu →Error →Screen].
Daikin RoCon+ HP Daikin controller RoCon+ HP1
008.1447899_00 – 09/2019 – EN
Operating Instructions
47
Page 48
8 Faults and malfunctions

8.5 Error codes

See Daikin Altherma ETS(X/H) Reference manual for the installer, chapter "Errors, malfunctions, messages".
Operating Instructions
48
Daikin controller RoCon+ HP1
Daikin RoCon+ HP
008.1447899_00 – 09/2019 – EN
Page 49

9 Mixer module

Room temperature target 1
Room temperature target 2
Room temperature target 3
Room
Reduce
Reduce
Reduce room temperature
Room temperature absent
Party
Absent
Holiday
Public holiday
HC auto 1
Heating circuit auto. 1
HC auto 2
Heating circuit auto. 2
9 Mixer module
In addition to the direct HC, the heating system can be extended by additional HCs using EHS157068 mixer modules. These additional HCs can be configured independently of the direct HC. The configur­ation is similar to the configuration of the direct HC (see Chap. 4). Only a limited selection of parameters and functions is available (see
Chap. 9.2).
The optional EHS157068 mixer module does not have its own con­trol unit. For configuration and operation, it must be connected via a CAN bus line to the RoCon+ controller installed in the heat generator or a EHS157034 room station. The mixer module can be operated in terminal mode from both operating units (see Chap. 4.8).
A unique device ID (≥ 1) must be set on the address switch of the mixer module (see Fig. 9-1) for the HC to be controlled by this mixer module, which must be synchronised with the [Heating circuit as­signment] parameter of the mixer module (see Tab. 4-7]).
Fig.9-1 Setting the device ID for the EHS157068 mixer module
The current operating status can be determined directly on the EHS157068 mixer module (see Fig. 9-2).

9.1 Mixer module start screen (terminal function)

Fig.9-3 Mixer module start screen
The start screen for the mixer module (Fig. 9-3) is a reduced version of the RoCon+ HP start screen. The meaning of the icons is the same Tab. 3-3, but the mixer temperature is the only system temper­ature displayed (Fig. 9-3, item1).
The start screen for the mixer module is displayed in the menu [→Main menu →Terminal →Mixer #X]. Briefly pressing the rotary switch switches to the mixer menu. A long press of the rotary switch switches to the menu of the local control panel.
Fig.9-2 Explanation of symbols for EHS157068 status displays
Item LED Description
1 Red Flashing: Internal error
(The error code is communicated to the relevant control unit via the CAN bus)
On: Undervoltage of the internal clock after a power failure (>10h)
2 Green On: Display during operation, mixer module
switched on 3 Green On: CAN communication 4 Green On: Mixer circuit pump switched on 5 Green On: Mixer valve "Open" is activated 6 Green On: Mixer valve "Closed" is activated
Tab.9-1

9.2 Mixer valve parameter overview

Menu: Operating mode
see Chap. 6.1.
Menu: User
Fig.9-4 Parameter in menu: "User"
Menu: Time program
Daikin RoCon+ HP Daikin controller RoCon+ HP1
008.1447899_00 – 09/2019 – EN
Fig.9-5 Parameter in menu: "Time program"
Operating Instructions
49
Page 50
9 Mixer module
SystemMin. mixer valve pump
Max. mixer valve pump
Outside temperature sensor
Outside temperature correction
Weather-compensated
Frost protection temperature
Building insulation
Heat limit, heating mode
Heat limit, reducing mode
Heating curve
Feed temperature, heating mode
Feed temperature, reducing mode
Max. feed temperature
Min. feed temperature
Room influence
Room sensor adaptation
Heating curve adaptation
SlopeOffset
Cooling curve
Target flow cooling, start
Target flow cooling, max.
Start cooling outside temp.
Max. cooling outside temp.
Cooling parameters
Feed temperature lower limit
Feed temperature, cooling mode
Cooling setpoint correction
Relay test
Screed
Program
Screed drying
Screed program
Software no. B1/U1
Average outside temperature
Values
Mixer temperature, current
Mixer software number
Mixer temperature, target
Mixer pump status
PWM mixer pump
Mixer valve status
Menu: Access
Menu: System
Fig.9-6 Parameter in menu: "System"
Menu: Sensors
Fig.9-7 Parameter in menu: "Sensors"
Menu: HC config
Fig.9-8 Parameter in menu: "HC config"
Menu: Heating
Menu: Information
Fig.9-12 Parameter in menu: "Information"
Fig.9-9 Parameter in menu: "Heating"
Menu: Cooling
Fig.9-10 Parameter in menu: "Cooling"
Menu: Special
Fig.9-11 Parameter in menu: "Special"
Operating Instructions
50
Daikin controller RoCon+ HP1
Daikin RoCon+ HP
008.1447899_00 – 09/2019 – EN
Page 51

9.3 Mixer module parameter settings

The parameters available for the mixer module are largely identical to the parameter described in Chap. 7. Tab. 9-2 lists the additional parameters available for the mixer module.
9 Mixer module
Parameters Setting range
Min / Max
Min. mixer valve pump
Max. mixer valve pump
SlopeOffset 0 – 50K [→Main menu →Heating]
Mixer temper­ature, current
Mixer temper­ature, target
Mixer pump status
PWM mixer pump
Mixer valve status
Tab.9-2 Parameters of the mixer module
10 – 100% [→Main menu →System]
Minimum power of the pump in the mixer circuit.
20 – 100% [→Main menu →System]
Maximum power of the pump in the mixer circuit.
Setting of the slope offset of the feed target temperature on the Daikin Altherma ETS(X/H) in comparison with the feed target temperature determ­ined for the mixer circuit.
0 – 100°C [→Main menu →Information →Values]
Current feed temperature in the mixer circuit
0 – 90°C [→Main menu →Information →Values]
Current target feed temperature in the mixer circuit On [→Main menu →Information →Values] Off
0 – 100% [→Main menu →Information →Values]
Neutral [→Main menu →Information →Values]
Close Open
Current status of the mixer pump
Current modulation of the mixer pump
Current status of the mixer valve
Description Factory
setting
30% 1% N E
100% 1% N E
5K 1K N E
- - S S
- - S S
- - S S
- - S S
- - S S
Incre-
ment
Access
BE HF
Daikin RoCon+ HP Daikin controller RoCon+ HP1
008.1447899_00 – 09/2019 – EN
Operating Instructions
51
Page 52

10 Glossary

10 Glossary
Mode Request by the user or the control unit for the function of the heat generator (e.g. room heating, domestic hot
water generation, standby, etc.)
Backup requirement Operating situation in which the required feed temperature cannot be reached efficiently or at all using the heat
pump process. A heater booster (e.g. a backup heater) is therefore integrated to support the Daikin Altherma
ETS(X/H) in generating heat. Backup heater Optional electric heater booster for general support of the Daikin Altherma ETS(X/H) during heat generation. Heating curve Mathematical relationship between the external temperature and the feed temperature setpoint in order to
achieve the required room temperature at all external temperatures. Refrigerant A substance used for heat transfer in the heat pump process. At low temperature and low pressure, heat is ab-
sorbed and at high temperature and a high pressure, heat is emitted. Anti-legionella system Periodic heating of the storage water to >60°C for the preventative elimination of pathogenic bacteria (so-
called legionella) in the hot water circuit. Off-peak mains connection
(HT/NT) Parameters A value that influences the execution of programs or processes or defines specific states. Control unit Device electronics that are used to control the processes for the heat generation and heat distribution of the
Return flow Part of the hydraulic circuit that directs the cooled water from the radiators in the rooms back to the heat gen-
Switching time program Program for setting the times on the control unit in order to determine the regular heating, reducing and hot
Smart Grid (SG) Intelligent use of energy for inexpensive heating. By using a special electricity meter, it is possible to receive a
Flow Part of the hydraulic circuit that diverts the heated water from the heat generator to the heating surfaces. Domestic hot water circuit This is the water circuit in which cold water is heated and diverted to the hot water tap. Domestic hot water generation Operating status of the heat generator in which heat with elevated temperatures is generated and fed to the
Heat pump process In a closed-loop refrigerant circuit, the refrigerant absorbs the heat from the ambient air. By means of com-
Heat exchanger A component that transfers thermal energy from one circuit to another. The two circuits are hydraulically sep-
Weather-dependent feed tem­perature control
Circulation pump The circulation pump is an additional electrical circulation pump that permanently circulates the hot water in
Heater booster Additional heat generator (e.g. backup heater or external boiler) integrated in the heating system to achieve
A special mains connection to the energy supplier, which offers various cheaper rates during so-called low-
load periods for electrical current (day-, night-, heat pump current, etc.).
heating system. The control unit consists of a number of electronic components. The most important compon-
ent for the operator is the control panel in the front area of the heat generator, which includes program selec-
tion keys, rotary buttons and display.
erator via the piping system.
water cycles.
"Smart Grid signal" from the utility company.
Depending on the signal, the heat pump is shut off or operated as normal or at higher temperatures.
hot water circuit, e.g. loading of the hot water storage tank.
pression, the refrigerant achieves a higher temperature that is transferred to the heating system (thermody-
namic cycle).
arated from one another by a wall in the heat exchanger.
A suitable feed temperature is determined from the measured value for the external temperature and a defined
heating curve; this temperature is used as the target value for temperature control in the heating unit.
the hot water lines, thus providing it immediately at every tap. This circulation is especially useful in extensive
pipeline networks. In systems without a circulation line, first the water cooled in the sampling line escapes dur-
ing the sampling process until the sampling line has been sufficiently heated by the inflowing hot water.
the required feed temperature setpoint in the case of an inadequate or inefficient heat pump process.
Operating Instructions
52
Daikin controller RoCon+ HP1
Daikin RoCon+ HP
008.1447899_00 – 09/2019 – EN
Page 53

11 User-specific settings

11 User-specific settings
Switching cycle 1 Switching cycle 2 Switching cycle 3
Temperature setting
Time period On Off On Off On Off
Heating circuit auto. 1
Heating circuit auto. 2
Tab.11-1 Individual settings in the heating timer programs
Monday Tuesday Wednesday Thursday Friday Saturday Sunday Monday Tuesday Wednesday Thursday Friday Saturday Sunday
[Room temperature target 1]:
____ °C

11.1 Switching time program

The factory settings of the timer programs are indicated in Chap. 4.3. Enter your timer settings in the table below.
[Room temperature target 2]:
____ °C
[Room temperature target 3]:
____ °C
Switching cycle 1 Switching cycle 2 Switching cycle 3
Temperature setting
Time period On Off On Off On Off
Hot water auto.1Monday
Tuesday Wednesday Thursday Friday Saturday Sunday
Hot water auto.2Monday
Tuesday Wednesday Thursday Friday Saturday Sunday
Tab.11-2 Individual settings in the hot water timer programs
Time period On Off On Off On Off
Circulation pro­gram
Tab.11-3 Individual settings of the switching time program of the circulation pump
Monday Tuesday Wednesday Thursday Friday Saturday Sunday
[Hot water temperature target 1]:
____ °C
Switching cycle 1 Switching cycle 2 Switching cycle 3
[Hot water temperature target 2]:
____ °C
[Hot water temperature target 3]:
____ °C
Daikin RoCon+ HP Daikin controller RoCon+ HP1
008.1447899_00 – 09/2019 – EN
Operating Instructions
53
Page 54
11 User-specific settings
Switching cycle 1 Switching cycle 2 Switching cycle 3
Time period On Off Stage On Off Stage On Off Stage
Sound program Monday
Tuesday Wednesday Thursday Friday Saturday Sunday
Tab.11-4 Individual settings of the sound program

11.2 Parameters

Enter the parameter changes that were made in the table below and in the operating manual of the heat generator.
Menu path Parameters Old value New value Date Comments
Tab.11-5 Individual parameter changes

11.3 Data bus addresses

RoCon device Terminal address Comments
Tab.11-6 Data bus addresses in the RoCon system
Operating Instructions
54
Daikin controller RoCon+ HP1
Daikin RoCon+ HP
008.1447899_00 – 09/2019 – EN
Page 55
12 Notes

12 Notes

Daikin RoCon+ HP Daikin controller RoCon+ HP1
008.1447899_00 – 09/2019 – EN
Operating Instructions
55
Page 56

List of keywords

List of keywords
A
Anti-legionella protection .........................19, 52
C
Calendar ..................................................................10
Circulation pump..................................................19
Comfort heating....................................................18
Configuration .........................................................16
Configuration Wizard.........................................25
D
Device ID.................................................................23
Display.........................................................................7
Documentation set ................................................4
E
External operation...............................................11
F
Factory setting ......................................................29
G
Glossary...................................................................52
H
HC ID.........................................................................22
Heat generator ID................................................23
Heating curve ........................................................18
Heating support function..................................16
Help function ............................................................9
Status display...........................................................7
Switching function...............................................15
T
Technician code...................................................29
Temperature setting
Hot water operation ...................................13
Reduced..........................................................13
Room temperature absent......................13
Room temperature target........................13
Terminal function.................................................22
Terminal ID.............................................................23
Time program................................................10, 13
Permanent programs ................................13
Temporary programs ................................13
U
Unscheduled domestic hot water prepara-
tion......................................................................13
V
Ventilation function .............................................19
Z
Zone control...........................................................17
I
Intended use.............................................................5
M
Mixer module.................................................17, 49
N
Navigating in lists...................................................9
Navigating in the menu .......................................8
O
Operating elements...............................................6
Rotary button...................................................7
Operating mode ...................................................12
Operating modes
Automatic 1....................................................12
Automatic 2....................................................12
Heating, Cooling..........................................12
Reduce.............................................................12
Standby............................................................12
Summer...........................................................12
Operation via the Internet................................11
Operation via the room station .....................11
P
Parameter reset ...................................................21
Parameter table....................................................29
Parameters.............................................................52
S
Safety switch-off .....................................................6
Screed program
Function heating..........................................20
Screed curing heating...............................21
Sensor test..............................................................19
Setting setpoints.....................................................9
Setting the times..................................................10
Settings ....................................................................14
Smart Grid...............................................................15
Start screen...............................................................7
Daikin RoCon+ HP Daikin controller RoCon+ HP1
008.1447899_00 – 09/2019 – EN
Operating Instructions
56
Page 57
Daikin RoCon+ HP Daikin controller RoCon+ HP1
008.1447899_00 – 09/2019 – EN
Operating Instructions
57
Page 58

Inhaltsverzeichnis

Inhaltsverzeichnis
1 Allgemeine Sicherheitsvorkehrung 60
1.1 Besondere Sicherheitsanweisungen ......................................... 60
1.1.1 Anweisungen beachten............................................... 60
1.1.2 Bedeutung der Warnhinweise und Symbole ............... 61
1.2 Sicherheitsanweisungen für die Montage und den Betrieb ....... 61
1.2.1 Allgemein .................................................................... 61
1.2.2 Bestimmungsgemäße Verwendung ............................ 61
2 Produktbeschreibung 62
2.1 Vorübergehende Stilllegung ...................................................... 62
3 Bedienung 63
3.1 Allgemeines............................................................................... 63
3.2 Anzeige- und Bedienelemente .................................................. 63
3.2.1 Statusanzeige ............................................................. 63
3.2.2 Display ........................................................................ 63
3.2.3 Drehtaster ................................................................... 63
3.2.4 Startbildschirm ............................................................ 63
3.3 Bedienkonzept........................................................................... 65
3.3.1 Im Menü navigieren .................................................... 65
3.3.2 Hilfe-Funktion .............................................................. 65
3.3.3 In Listen navigieren und Listeneinträge auswählen .... 65
3.3.4 Sollwerte einstellen ..................................................... 66
3.3.5 Uhrzeiten einstellen .................................................... 66
3.3.6 Kalender-Funktion....................................................... 66
3.3.7 Zeitprogramme einstellen ........................................... 67
3.3.8 Externe Bedienung ..................................................... 68
4 Funktion 69
4.1 Betriebsart ................................................................................. 69
4.2 Benutzer .................................................................................... 70
4.2.1 Einstellung Raumtemperatur Soll ............................... 70
4.2.2 Einstellung Raumtemperatur Absenken ..................... 70
4.2.3 Einstellung Raumtemperatur Abwesend..................... 70
4.2.4 Einstellung Warmwassertemperatur Soll .................... 70
4.2.5 Außerplanmäßige Warmwasserbereitung .................. 70
4.3 Zeitprogramm ............................................................................ 70
4.3.1 Temporäre Zeitprogramme ......................................... 70
4.3.2 Permanente Zeitprogramme ....................................... 70
4.3.3 Zeitprogramm Reset ................................................... 71
4.4 Einstellungen............................................................................. 71
4.4.1 Anzeigeeinstellungen .................................................. 72
4.4.2 System ........................................................................ 72
4.4.3 Externe Wärmequellen ............................................... 72
4.4.4 Ein-/Ausgänge ............................................................ 72
4.4.5 Intelligentes Speicher Management............................ 73
4.5 Konfiguration ............................................................................. 73
4.5.1 Zugriffsrechte (Fachmanncode) .................................. 73
4.5.2 Sensoren..................................................................... 74
4.5.3 Heizkreis Konfiguration ............................................... 74
4.5.4 Heizen ......................................................................... 74
4.5.5 Kühlen ......................................................................... 75
4.5.6 Warmwasser ............................................................... 76
4.5.7 Zusatzprogramm ......................................................... 76
4.5.8 Configuration Wizard .................................................. 78
4.5.9 Parameter Reset ......................................................... 78
4.6 Info ............................................................................................ 78
4.6.1 Aktuell ......................................................................... 78
4.6.2 Übersicht ..................................................................... 79
4.6.3 Werte .......................................................................... 79
4.6.4 Wasserdruck ............................................................... 79
4.7 Fehler ........................................................................................ 79
4.8 Terminal .................................................................................... 79
4.8.1 Terminaladresse auswählen ....................................... 80
4.8.2 Bus-Scan für Terminalfunktion.................................... 80
4.9 Statistik....................................................................................... 81
4.9.1 Monat ........................................................................... 81
4.9.2 Gesamt ........................................................................ 81
5 Erste Inbetriebnahme 82
5.1 Configuration Wizard.................................................................. 82
5.2 Menüführung im Configuration Wizard....................................... 82
6 Parameterübersicht 84
6.1 Menü: Betriebsart ....................................................................... 84
6.2 Menü: Benutzer .......................................................................... 84
6.3 Menü: Zeitprogramm .................................................................. 84
6.4 Menü: Einstellungen................................................................... 84
6.5 Menü: Konfiguration ................................................................... 85
6.6 Menü: Info .................................................................................. 85
6.7 Menü: Fehler .............................................................................. 85
6.8 Menü: Terminal .......................................................................... 85
6.9 Menü: Statistik............................................................................ 86
7 Parametereinstellungen 87
7.1 Erläuterung zu den Parametertabellen....................................... 87
7.2 Betriebsart .................................................................................. 87
7.3 Benutzer ..................................................................................... 88
7.3.1 Menü: Raumtemperatur Soll ........................................ 88
7.3.2 Menü: Raumtemperatur Absenken .............................. 88
7.3.3 Menü: Raumtemperatur Abwesend ............................. 88
7.3.4 Menü: Warmwassertemperatur Soll............................. 88
7.3.5 Menü: 1x Warmwasser ................................................ 89
7.4 Zeitprogramm ............................................................................. 89
7.5 Einstellungen.............................................................................. 90
7.5.1 Menü: Anzeigeeinstellungen ........................................ 90
7.5.2 Menü: System .............................................................. 91
7.5.3 Menü: Externe Wärmequelle ....................................... 92
7.5.4 Menü: Ein-/Ausgänge .................................................. 92
7.5.5 Menü: Intelligentes Speicher Management.................. 96
7.6 Konfiguration .............................................................................. 96
7.6.1 Menü: Sensoren........................................................... 96
7.6.2 Menü: Heizkreis Konfiguration ..................................... 97
7.6.3 Menü: Heizen ............................................................... 98
7.6.4 Menü: Kühlen ............................................................... 99
7.6.5 Menü: Warmwasser .....................................................100
7.6.6 Menü: Zusatzprogramme .............................................101
7.7 Info .............................................................................................102
7.7.1 Übersicht ......................................................................102
7.7.2 Werte ...........................................................................103
7.7.3 Wasserdruck ................................................................103
7.8 Fehler .........................................................................................104
7.9 Terminal .....................................................................................104
7.10 Statistik .......................................................................................104
7.11 Configuration Wizard ..................................................................105
8 Fehler und Störungen 106
8.1 Notbetrieb...................................................................................106
8.2 Handbetrieb................................................................................106
8.3 Fehlerprotokoll............................................................................ 106
8.4 Fehlerbildschirm .........................................................................106
8.5 Fehlercodes................................................................................ 107
9 Mischermodul 108
9.1 Startbildschirm Mischermodul (Terminalfunktion) ......................108
9.2 Parameterübersicht Mischer ......................................................108
9.3 Parametereinstellungen Mischermodul ......................................110
10 Glossar 111 11 Benutzerspezifische Einstellungen 112
11.1 Schaltzeitprogramme ................................................................. 112
11.2 Parameter...................................................................................113
11.3 Datenbusadressen .....................................................................113
12 Notizen 114

Betriebsanleitung

58
Daikin Regelung RoCon+ HP1
Daikin RoCon+ HP
008.1447899_00 – 09/2019 – DE
Page 59
Stichwortverzeichnis 115
Inhaltsverzeichnis
Daikin RoCon+ HP Daikin Regelung RoCon+ HP1
008.1447899_00 – 09/2019 – DE
Betriebsanleitung
59
Page 60

1 Allgemeine Sicherheitsvorkehrung

1 Allgemeine
Sicherheitsvorkehrung

1.1 Besondere Sicherheitsanweisungen

WARNUNG
Heizgeräte, die nicht ordnungsgemäß eingerichtet und installiert werden, kön­nen die Funktion des Heizgeräts beein­trächtigen und/oder ernsthafte oder tödliche Verletzungen des Benutzers verursachen.
▪ Arbeiten am Wärmeerzeuger (wie
z.B. Einrichtung, Inspektion, An­schluss und erste Inbetriebnahme) dürfen nur von Personen durchge­führt werden, die autorisiert sind und zu der jeweiligen Tätigkeit eine befä­higende technische oder handwerkli­che Ausbildung erfolgreich absol­viert, sowie an fachlichen, von der jeweils zuständigen Behörde aner­kannten Fortbildungsveranstaltun­gen teilgenommen haben. Hierzu zählen insbesondere Heizungsfach­kräfte, Elektrofachkräfte und Kälte­Klima-Fachkräfte, die aufgrund ihrer fachlichen Ausbildung und ihrer Sachkenntnis Erfahrungen mit der fachgerechten Installation und War­tung von Heizungsanlagen, Öl- und Gasinstallation sowie Warmwasser­speichern haben.
▪ Den Wärmeerzeuger nur in einwand-
freiem Zustand mit geschlossener Abdeckhaube betreiben.
WARNUNG
Die Missachtung folgender Sicherheits­anweisungen kann zu schwerer Kör­perverletzung oder Tod führen.
▪ Dieses Gerät darf von Kindern ab ei-
nem Alter von 8 Jahren und darüber sowie von Personen mit einge­schränkten physischen, sensori­schen oder mentalen Fähigkeiten oder einem Mangel an Erfahrung und Wissen nur dann benutzt wer­den, wenn sie beaufsichtigt oder be­züglich des sicheren Gebrauchs des Geräts unterwiesen wurden und die daraus resultierenden Gefahren ver­stehen. Kinder dürfen nicht mit dem Gerät spielen. Reinigung und Benut­zerwartung dürfen nicht von Kindern ohne Beaufsichtigung durchgeführt werden.
▪ Der Netzanschluss muss gemäß
IEC60335-1 über eine Trennvorrich­tung hergestellt werden, welche eine Trennung jedes Pols mit einer Kon­taktöffnungsweite entsprechend den Bedingungen der Überspannungska­tegorie III für volle Trennung auf­weist.
▪ Sämtliche elektrotechnischen Arbei-
ten dürfen nur durch elektrotech­nisch qualifiziertes Fachpersonal und unter Beachtung der örtlichen und nationalen Vorschriften sowie der Anweisungen in dieser Anleitung ausgeführt werden. Sicherstellen, dass ein geeigneter Stromkreis verwendet wird. Nicht ausreichende Belastbarkeit des Stromkreises oder unsachge­mäß ausgeführte Anschlüsse kön­nen Stromschlag oder Feuer verur­sachen.
Betriebsanleitung
60
1.1.1 Anweisungen beachten
▪ Die Originaldokumentation ist in deutscher Sprache verfasst. Alle
anderen Sprachen sind Übersetzungen.
▪ Bitte lesen Sie diese Anleitung aufmerksam durch, bevor Sie mit
der Installation beginnen oder Eingriffe in der Heizungsanlage vor­nehmen.
▪ Die in diesem Dokument beschriebenen Vorsichtsmaßnahmen
decken sehr wichtige Themen ab. Halten Sie sie sorgfältig ein.
Daikin RoCon+ HP
Daikin Regelung RoCon+ HP1
008.1447899_00 – 09/2019 – DE
Page 61
1 Allgemeine Sicherheitsvorkehrung
▪ Die Installation des Systems und alle in dieser Anleitung und den
mitgeltenden Dokumenten für den Monteur beschriebenen Arbei­ten müssen von einem zugelassenen Monteur durchgeführt wer­den.
Dokumentationssatz
Dieses Dokument ist Teil eines Dokumenationssatzes aus mitgelten­den Dokumenten. Der vollständige Satz besteht aus:
▪ Installationsanleitung für das Innengerät (Format: Papier - im Lie-
ferumfang des Innengeräts enthalten)
▪ Betriebssanleitung für das Innengerät (Format: Papier - im Liefer-
umfang des Innengeräts enthalten)
▪ Betriebshandbuch Wärmepumpe (Format: Papier - im Lieferum-
fang des Innengeräts enthalten)
▪ Installationsanleitung für das Außengerät (Format: Papier - im Lie-
ferumfang des Außengeräts enthalten)
▪ Installationsanleitungen für optionale Komponenten (Format: Pa-
pier - im Lieferumfang der jeweiligen Komponente enthalten)
▪ Referenzhandbuch für den Monteur für das Innengerät (Format:
Digital)
▪ Referenzhandbuch für den Monteur für das Außengerät (Format:
Digital)
Die Referenzhandbücher enthalten den vollständigen Satz Techni­scher Daten, die detaillierte Beschreibung bewährter Verfahren, so­wie Informationen zu Wartung, Fehlerbehebung und Außerbetrieb­nahme.
Die digitalen Dokumente sowie neueste Ausgaben der mitgelieferten Dokumentation sind auf der regionalen Daikin-Webseite oder auf Anfrage bei Ihrem Händler verfügbar. Die Daikin-Webseite ist kom­fortabel über den QR-Code an Ihrem Gerät erreichbar.
1.1.2 Bedeutung der Warnhinweise und Symbole
In dieser Anleitung sind die Warnhinweise entsprechend der Schwe­re der Gefahr und der Wahrscheinlichkeit ihres Auftretens systemati­siert.
GEFAHR
Weist auf eine unmittelbare Gefahr hin. Die Missachtung des Warnhinweises führt zu schwerer
Körperverletzung oder Tod
WARNUNG
Weist auf eine möglicherweise gefährliche Situation hin Die Missachtung des Warnhinweises kann zu schwerer
Körperverletzung oder Tod führen.
ACHTUNG
Weist auf eine möglicherweise schädliche Situation hin Die Missachtung des Warnhinweises kann zu Sach- und
Umweltschäden und leichten Verletzungen führen.
Dieses Symbol kennzeichnet Anwendertipps und beson­ders nützliche Informationen, jedoch keine Warnungen vor Gefährdungen
Spezielle Warnsymbole
Einige Gefahrenarten werden durch spezielle Symbole dargestellt.
Elektrischer Strom
Allgemeine Darstellung 1 Handlungsanweisungen werden als Liste dargestellt. Handlun-
gen, bei denen zwingend die Reihenfolge einzuhalten ist, wer­den nummeriert dargestellt.
è Resultate von Handlungen werden mit einem Pfeil gekenn-
zeichnet. [Betriebsart]: Parameter werden in eckigen Klammern dargestellt. [→Hauptmenü]: Die Position von Menüs und Funktionen wird in
eckigen Klammern mit → dargestellt.
1.2 Sicherheitsanweisungen für die
Montage und den Betrieb
1.2.1 Allgemein
▪ Zu jeglichen Arbeiten an den Geräten, die über die Bedienung des
Regelungssystems hinausgehen, sind die Angaben in den mitgel­tenden Dokumenten, insbesondere die Sicherheitshinweise zu be­achten.
Gefahren vermeiden
Die Daikin Altherma ETS(X/H) ist nach dem Stand der Technik und den anerkannten technischen Regeln gebaut. Dennoch können bei unsachgemäßer Verwendung Gefahren für Leib und Leben von Per­sonen sowie Sachbeschädigungen entstehen.
Zur Vermeidung von Gefahren, die Daikin Altherma ETS(X/H) nur betreiben:
▪ bestimmungsgemäß und in einwandfreiem Zustand, ▪ sicherheits- und gefahrenbewusst. Dies setzt die Kenntnis und Anwendung des Inhalts dieser Anlei-
tung, aller mitgeltenden Dokumente, der einschlägigen Unfallverhü­tungsvorschriften sowie der anerkannten sicherheitstechnischen und arbeitsmedizinischen Regeln voraus.
Anzeigedarstellung der RoCon+-Regelung
Bestimmte Bildschirmanzeigen oder Menüpunkte können in Abhän­gigkeit der Länder- oder Ausstattungsvariante der Daikin Altherma ETS(X/H) bzw. dem an der Regelung angemeldeten Benutzerstatus, von gezeigten Darstellungen dieser Anleitung abweichen.
1.2.2 Bestimmungsgemäße Verwendung
Die Regelung RoCon+ HP darf ausschließlich in Daikin Altherma ETS(X/H) Wärmepumpen verwendet werden, die für das Regelungs­system freigegeben sind. Die Regelung RoCon+ HP darf nur gemäß den Angaben dieser Anleitung betrieben werden.
Jede andere oder darüber hinausgehende Verwendung gilt als nicht bestimmungsgemäß. Für hieraus entstehende Schäden trägt das Ri­siko allein der Betreiber.
Zu jeglichen Arbeiten an den Geräten, die über die Bedienung des Regelungssystems hinausgehen, sind die Angaben in den mitgelten­den Dokumenten, insbesondere die Sicherheitshinweise zu beach­ten.
Dokumentation
Die im Lieferumfang enthaltene technische Dokumentation ist Teil des Geräts. Sie muss so abgelegt werden, dass sie jederzeit vom Betreiber oder dem Fachpersonal eingesehen werden kann.
Verbrennungsgefahr oder Verbrühungsgefahr
Daikin RoCon+ HP Daikin Regelung RoCon+ HP1
008.1447899_00 – 09/2019 – DE
Betriebsanleitung
61
Page 62

2 Produktbeschreibung

2 Produktbeschreibung
INFORMATION
Die Regelung RoCon+ HP ist Bestandteil der Daikin Alther­ma ETS(X/H).
Sie besteht aus der Schaltfeldplatine RoCon BM2C, an die Aktoren und Sensoren sowie weitere Komponenten des Regelungssystems angeschlossen werden und dem Be­dienteil RoCon+ B1.
In dieser Anleitung werden nur die Funktionen und Einstell­möglichkeiten der Regelung erläutert. Nähere Informatio­nen zu sonstigen Gerätekomponenten finden Sie in den mitgeltenden Dokumenten.
Die elektronische, digitale Regelung regelt, je nach Heizgerät, auto­matisch alle Heiz- und Warmwasserfunktionen für einen direkten Heizkreis, einen Speicherladekreis und über optional anschließbare Mischermodule auch weitere Heizkreise.
Sie übernimmt das gesamte Sicherheitsmanagement der Daikin Alt­herma ETS(X/H). So wird z.B. bei Wassermangel, nicht zulässigen oder undefinierten Betriebszuständen eine Sicherheitsabschaltung durchgeführt. Eine entsprechende Fehlermeldung zeigt dem Betrei­ber alle Informationen zur Störungsursache an.
Alle Funktionseinstellungen für die Daikin Altherma ETS(X/H) und die über den Datenbus angeschlossenen optionalen RoCon-Geräte werden mit den Bedienelementen des integrierten Bedienteils Ro­ConB1 vorgenommen und im farbig hinterleuchtetem Klartextdis­play angezeigt.
An der Daikin Altherma ETS(X/H) können über den Regelungsda­tenbus folgende zusätzliche, optionale Geräte angeschlossen wer­den:
▪ Raumregler EHS157034 ▪ Mischermodul EHS157068 Des Weiteren besitzt die Regelung RoCon+ HP eine Frostschutz-
funktion für den direkten Heizkreis und den Speicherladekreis sowie eine automatische Funktion zur Heizungsunterstützung (Einbindung einer zusätzlichen Wärmequelle wie z.B. Holzkessel, Solaranlage).
Über den potenzialfreien AUX-Schaltkontakt können verschiedene Steuerfunktionen in Verbindung mit externen Geräten realisiert wer­den (Anforderung eines externen Wärmeerzeugers, Umschaltung bi­valenter Betrieb, externe Statusanzeige, etc.).
Außerdem stehen mehrere Eingänge zur Auswertung externer Steu­erkontakte zur Verfügung (externe Betriebsartenumschaltung oder Wärmeanforderung, Smart Grid- und Niedertarif EVU-Funktionen
Mit dem optionalen Außentemperaturfühler, welcher an der Nordsei­te des Gebäudes installiert wird, kann die witterungsgeführte Vor­lauftemperaturregelung noch optimiert werden.
Ist das optionale Gateway EHS157056 installiert und mit dem Inter­net verbunden, kann die Daikin Altherma ETS(X/H) bequem per Fernsteuerung mit Mobiltelefonen (App) überwacht und bedient wer­den.
Die Erstinbetriebnahme der Heizungsanlage ist in der Installations­anleitung der Daikin Altherma ETS(X/H) beschrieben.
Bestimmte Menüpunkte der Regelung RoCon+ HP sind nur für den Heizungsfachmann zugänglich. Diese Sicherheitsmaßnahme ge­währleistet, dass es im Anlagenbetrieb nicht zu unerwünschten Fehl­funktionen durch falsche Einstellungen kommt.
Alle Einstellungen für den zugeordneten Heizkreis können in glei­cher Weise vorgenommen werden, wie am Bedienteil. Bei aktivierter Terminalfunktion stehen mit Ausnahme weniger Sonderfunktionen (z.B. Handbetrieb) alle Bedienmöglichkeiten wie am integrierten Be­dienteil zur Verfügung.
(1)
Ein angeschlossenes Mischermodul EHS157068 wird nach entspre­chender Zuordnung ebenfalls über das Bedienteil RoCon+ B1 und/ oder die Raumstation EHS157034 bedient.

2.1 Vorübergehende Stilllegung

ACHTUNG
Stillgelegte Heizungsanlage kann bei Frost einfrieren und dadurch beschädigt werden.
▪ Stillgelegte Heizungsanlage bei Frostgefahr entleeren. ▪ Bei nicht entleerter Heizungsanlage muss bei Frostge-
fahr die Stromversorgung sichergestellt und der exter­ne Hauptschalter eingeschaltet bleiben.
Wenn das Innengerät für längere Zeit nicht benötigt wird, kann es vorübergehend stillgelegt werden.
Wir empfehlen jedoch, die Anlage nicht von der Stromversorgung zu trennen, sondern lediglich in den "Stand-By-Betrieb" zu versetzen (siehe Betriebsanleitung der Regelung).
Die Anlage ist dann frostgeschützt, die Pumpen- und Ventilschutz­funktionen sind aktiv.
Wenn bei Frostgefahr die Stromversorgung nicht gewährleistet wer­den kann, muss
▪ das Innengerät wasserseitig, vollständig entleert werden oder ▪ geeignete Frostschutzmaßnahmen für die angeschlossene Hei-
zungsanlage und den Warmwasserspeicher getroffen werden (z.B. Entleerung).
INFORMATION
Besteht die Frostgefahr bei unsicherer Gas- und Stromver­sorgung nur wenige Tage, kann aufgrund der sehr guten Wärmedämmung auf das Entleeren des Innengeräts ver­zichtet werden, wenn die Speichertemperatur regelmäßig beobachtet wird und nicht unter +3°C sinkt.
Ein Frostschutz für das angeschlossene Wärmevertei­lungssystem besteht dadurch allerdings nicht!
).
Betriebsanleitung
62
(1)
Energieversorgungsunternehmen (EVU) sendet Signale aus, die zur Steuerung der Stromnetzauslastung genutzt werden und Einfluss auf den Strompreis und die Verfügbarkeit haben.
Daikin Regelung RoCon+ HP1
008.1447899_00 – 09/2019 – DE
Daikin RoCon+ HP
Page 63

3 Bedienung

3 Bedienung

3.1 Allgemeines

GEFAHR: STROMSCHLAGGEFAHR
Durch Kontakt von Wasser mit elektrischen Bauteilen kann es zu einem Stromschlag, sowie zu lebensgefährlichen Verletzungen und Verbrennungen kommen.
▪ Die Anzeigen und die Tasten der Regelung vor Einwir-
kung von Nässe schützen.
▪ Zum Reinigen der Regelung ein trockenes Baumwoll-
tuch verwenden. Das Verwenden von aggressiven Rei­nigungsmitteln und anderen Flüssigkeiten kann zu Ge­räteschäden oder Stromschlag führen.
INFORMATION
Die effektivste Energienutzung erreicht die Daikin Altherma ETS(X/H) bei möglichst niedrigen Rücklauf- und Warm­wasser-Solltemperaturen.
Wird bei Vorlauf-Solltemperaturen über 50°C ein externer Wärmeerzeuger (z.B. der optionale Backup-Heater) zuge­schaltet, kann sich (abhängig von der Außentemperatur) der Wirkungsgrad (COP) der Daikin Altherma ETS(X/H) verschlechtern.

3.2 Anzeige- und Bedienelemente

3.2.1 Statusanzeige
Die LEDs der Statusanzeige leuchten oder blinken und zeigen so den Betriebsmodus des Geräts.
LED Modus Beschreibung
Blinkt blau Standby Das Gerät ist nicht in Betrieb. Leuchtet blau Betrieb Das Gerät ist in Betrieb. Blinkt rot Fehler Es ist ein Fehler aufgetreten.
Weitere Einzelheiten siehe
Kap. 8.
Tab.16-1 Statusanzeige
3.2.2 Display
Im Normalbetrieb ist das Display deaktiviert (vollkommen dunkel). Die Aktivität der Anlage wird durch die Statusanzeige angezeigt. Jegliches Betätigen des Drehtasters (drehen, drücken oder lange drücken) aktiviert das Display mit dem Startbildschirm.
Ist der Startbildschirm aktiv, und es erfolgt für 60 Sekunden keine Eingabe durch den Benutzer, wird das Display deaktiviert. Erfolgt an jeder anderen Stelle im Menü für 120 Sekunden keine Eingabe durch den Benutzer, wird zurück auf den Startbildschirm gewechselt.
3.2.3 Drehtaster
ACHTUNG
Die Bedienelemente der Regelung niemals mit einem har­ten, spitzen Gegenstand betätigen. Dies kann zur Beschä­digung und zu Fehlfunktionen der Regelung führen.
Mit dem Drehtaster kann in den jeweiligen Ebenen navigiert, der Ein­stellwert angewählt, verändert und mit kurzem Tastendruck diese Änderung übernommen werden.
Aktion Resultat
Drehen Menü auswählen, Einstellung auswählen, Ein-
stellung vornehmen
Antippen Auswahl bestätigen, Einstellung übernehmen,
Funktion ausführen.
Bild16-1 RoCon+ HP Anzeige- und Bedienelemente
1 Statusanzeige 2 Display 3 Drehtaster
2 Sek. drücken Menü verlassen
Tab.16-2 Funktion des Drehtasters
3.2.4 Startbildschirm
Der Startbildschirm gibt einen Überblick über den aktuellen Betriebs­zustand der Anlage. Vom Startbildschirm führt jegliches Betätigen des Drehtasters (drehen, drücken oder lange drücken) zum Haupt­menü.
Daikin RoCon+ HP Daikin Regelung RoCon+ HP1
008.1447899_00 – 09/2019 – DE
Betriebsanleitung
63
Page 64
3 Bedienung
Pos. Symbol Erklärung
10 Betriebsart: Bereitschaft
Betriebsart: Absenken
Betriebsart: Heizen
Betriebsart: Kühlen
Betriebsart: Sommer
Betriebsart: Automatik 1
Betriebsart: Automatik 2
Betriebsart: Notbetrieb
Bild16-2 Anzeigeposition auf dem Startbildschirm
Pos. Symbol Erklärung
1 Datum und Uhrzeit 2 Fehlermeldung
3 Nur bei angeschlossenem Raumgerät: Raum-
Temperatur
4 Warmwasser-Temperatur
5 Vorlauftemperatur Fußbodenheizung
Vorlauftemperatur Konvektorheizung
Vorlauftemperatur Radiatorheizung
6 Außentemperatur 7 Druck im Heizkreis 8 Speicherbehälter ohne Heizstab
Speicherbehälter mit angeschlossenem Heizstab (aus)
Speicherbehälter mit angeschlossenem Heizstab (an)
11 Sonderprogramm: Party
Sonderprogramm: Abwesend
Sonderprogramm: Urlaub
Sonderprogramm: Feiertag
Sonderprogramm: 1 x Warmwasser
Sonderprogramm: Estrich
Sonderprogramm: Entlüftung
12 Flüsterbetrieb ein
13 Modus: Heizen
Modus: Kühlen
Modus: Warmwasser
Modus: Defrost
9 Kein Außengerät erkannt
Außengerät vorhanden, Verdichter aus
Außengerät vorhanden, Verdichter an
Betriebsanleitung
64
Modus: Keine Anforderung
14 Ext Betriebsart extern umgeschaltet (Brennersperr-
kontakt oder Raumthermostat)
Tab.16-3 Display-Symbole auf dem Startbildschirm
INFORMATION
Wird das lokale Bedienteil als Fernbedienung für ein Mi­schermodul genutzt, ist sowohl der Standardbildschirm als auch die Menüstruktur geändert (siehe Kap. 9).
Daikin RoCon+ HP
Daikin Regelung RoCon+ HP1
008.1447899_00 – 09/2019 – DE
Page 65

3.3 Bedienkonzept

Das Bedienkonzept der Regelung ermöglicht ein schnelles Navigie­ren im Menü, die übersichtliche Anzeige von Informationen und die komfortable Auswahl von Parametern und Einstellung von Sollwer­ten und Programmen.
Die Grundlagen des Bedienkonzepts werden im Folgenden anhand einiger Beispiele detailliert dargestellt. Die Bedienung von Sonder­funktionen folgt dem gleichen Prinzip und wird bei Bedarf in den ent­sprechenden Abschnitten in Kap. 4 beschrieben.
3.3.1 Im Menü navigieren
Vom Startbildschirm führt jegliches Betätigen des Drehtasters (dre­hen, drücken oder lange drücken) zum Hauptmenü. Die Menüan­sicht besteht aus einem oberen Bereich für die Menü-Icons der ver­schiedenen Untermenüs sowie der unteren Menüleiste. In der Menü­leiste wird das Zurück- und das Hilfe-Icon dargestellt. Durch Drehen des Drehtasters kann man zwischen den Icons (inklusive den Icons in der Menüleiste) wechseln. Mehrseitige Menüs sind durch den Sei­tenwechsel-Pfeil erkennbar. Durch Drehen des Drehtasters wird zwi­schen den Menü-Icons auf den verschiedenen Menüseiten gewech­selt.
Bild16-3 Beispiel: Elemente in zweiseitigem Menü
1 Zurück-Icon 2 Menüleiste 3 Menü-Icon 4 Seitenwechsel-Pfeil (bei mehrseitigen Menüs) 5 Hilfe-Icon
Beispiel: In das Menü "Statistik" wechseln [→Hauptmenü]: 1 Drehtaster im Uhrzeigersinn drehen, bis das Icon "Statistik" (auf
der zweiten Menüseite) blau dargestellt wird.
2 Drehtaster kurz antippen zum Bestätigen ("OK").
è Untermenü "Statistik" wird aufgerufen
3.3.2 Hilfe-Funktion
Für jedes Menü-Icon steht ein Hilfetext zur Verfügung.
3 Bedienung
Bild16-4 Hilfe-Funktion
Beispiel: Hilfetext für das Menü "Warmwasser" aufrufen und Hilfe­Funktion wieder beenden [→Hauptmenü→Benutzer]:
1 Drehtaster im Uhrzeigersinn drehen, bis das Hilfe-Icon in der
Menüleiste blau dargestellt wird.
2 Drehtaster kurz antippen zum Bestätigen ("OK").
è Hilfe-Funktion wird aktiv, das "?"-Symbol wird am letzten
Menü-Icon eingeblendet. 3 Drehtaster gegen den Uhrzeigersinn drehen, bis das "?"-Symbol
am Icon "Warmwasser" erscheint.
4 Drehtaster kurz antippen zum Bestätigen ("OK").
è Hilfetext für das Menü "Warmwasser" wird angezeigt.
5 Drehtaster kurz antippen zum Bestätigen ("OK").
è Hilfetext-Ebene wird verlassen.
6 Drehtaster im Uhrzeigersinn drehen, bis das Hilfe-Icon in der
Menüleiste blau dargestellt wird.
7 Drehtaster kurz antippen zum Bestätigen ("OK").
è Hilfe-Funktion wird beendet.
3.3.3 In Listen navigieren und Listeneinträge
auswählen
Listen existieren als reine Informationslisten oder dienen zur Wahl eines Listeneintrags. Drehen des Drehtasters wechselt zwischen den Listeneinträgen. Mehrseitige Listen sind durch den Seitenwech­sel-Pfeil erkennbar. Durch Drehen des Drehtasters wird zwischen den Listeneinträgen der verschiedenen Seiten gewechselt.
Bei Auswahl-Listen wird der aktuell gewählte Listeneintrag durch einen Haken angezeigt. Durch "OK" kann ein anderer Listeneintrag gewählt werden. Die entsprechende Einstellung wird dann übernom­men und die Liste verlassen.
Daikin RoCon+ HP Daikin Regelung RoCon+ HP1
008.1447899_00 – 09/2019 – DE
Betriebsanleitung
65
Page 66
3 Bedienung
Bild16-5 Liste mit gewähltem Listeneintrag
Beispiel: Betriebsart auf "Sommer" umstellen [→Hauptmenü →Be­triebsart]
1 Drehtaster im Uhrzeigersinn drehen, bis Listeneintrag "Sommer"
blau dargestellt wird.
2 Drehtaster kurz antippen zum Bestätigen ("OK").
è Haken wird bei Listeneintrag "Sommer" gesetzt.
3 Drehtaster gegen den Uhrzeigersinn drehen, bis das Zurück-
Icon blau dargestellt wird.
4 Drehtaster kurz antippen zum Bestätigen ("OK").
è Einstellung wird gespeichert und Einstellebene verlassen.
3.3.4 Sollwerte einstellen
Der Sollwert eines Parameters kann innerhalb der dargestellten Ska­la geändert werden. Durch "OK" wird der neue Wert gespeichert. Durch langes Drücken des Drehtasters wird die Einstellebene ohne Speichern verlassen. Für manche Parameter existiert neben Werten auf der Skala auch die Einstellung "Aus". Diese Einstellung ist durch Drehen des Drehtasters gegen den Uhrzeigersinn wählbar, nach­dem der minimale Wert der Skala erreicht wurde.
2 Drehtaster kurz antippen zum Bestätigen ("OK").
è Einstellung wird gespeichert und Einstellebene verlassen.
3.3.5 Uhrzeiten einstellen
Um die aktuelle Uhrzeit einzustellen, wird die Uhr-Funktion genutzt.
Bild16-7 Uhrzeiten einstellen
Beispiel: Uhrzeit auf 16:04 Uhr einstellen [→Hauptmenü →Einstel­lungen →Anzeige →Uhrzeit]:
1 Drehtaster im Uhrzeigersinn drehen, bis der Kreis blau darge-
stellt wird.
2 Drehtaster kurz antippen zum Bestätigen ("OK").
è Stundenzeiger wird blau dargestellt.
3 Drehtaster im Uhrzeigersinn drehen, bis 16:00 dargestellt wird. 4 Drehtaster kurz antippen zum Bestätigen ("OK").
è Minutenzeiger wird blau dargestellt.
5 Drehtaster im Uhrzeigersinn drehen, bis 16:04 dargestellt wird. 6 Drehtaster kurz antippen zum Bestätigen ("OK").
è Bestätigen-Icon in Menüleiste wird blau dargestellt.
7 Drehtaster kurz antippen zum Bestätigen ("OK").
è Einstellung wird gespeichert und Einstellebene verlassen.
Bild16-6 Darstellung der Parametereinstellung
1 Minimalwert 2 Standardwert 3 Aktuell gewählter Wert 4 Maximalwert
Beispiel: [Raumtemperatur Soll 1] auf 22°C einstellen [→Haupt-
menü→Benutzer →Raum →Raumtemperatur Soll 1]: 1 Drehtaster im Uhrzeigersinn drehen, bis 22°C angezeigt wird.
Betriebsanleitung
66
3.3.6 Kalender-Funktion
Um das aktuelle Datum oder die Zeitprogramme [Urlaub] und [Feier­tag] einzustellen, wird die Kalender-Funktion genutzt. Für die Zeit­programme erlaubt die Kalenderfunktion die Auswahl eines Zeit­raums.
Bild16-8 Zeitraum einstellen mit der Kalender-Funktion
Daikin RoCon+ HP
Daikin Regelung RoCon+ HP1
008.1447899_00 – 09/2019 – DE
Page 67
3 Bedienung
Beispiel: [Urlaub] vom 25.August2018 - 02.September2018 ein-
stellen [→Hauptmenü → Zeitprogramm →Urlaub]: 1 Drehtaster im Uhrzeigersinn drehen, bis die Monatsauswahl auf
Aug2018 steht.
2 Drehtaster kurz antippen zum Bestätigen ("OK").
è 1.August wird blau umrandet dargestellt.
Drehtaster im Uhrzeigersinn drehen, bis der 25.August blau umran­det dargestellt wird.
3 Drehtaster kurz antippen zum Bestätigen ("OK").
è 25.August wird grau hinterlegt dargestellt.
4 Drehtaster im Uhrzeigersinn drehen, bis der 2.September blau
umrandet dargestellt wird.
5 Drehtaster kurz antippen zum Bestätigen ("OK").
è Einstellung wird gespeichert und Einstellebene verlassen.
Bei Einstellung eines neuen Urlaubszeitraums wird der zuvor einge­stellte Urlaubszeitraum automatisch gelöscht. Alternativ kann die Ur­laubseinstellung auch zurückgesetzt werden.
Beispiel: Urlaubseinstellung zurücksetzen [→Hauptmenü →Zeit­programm →Urlaub]:
6 Drehtaster im Uhrzeigersinn drehen, bis die Monatsauswahl blau
dargestellt wird.
7 Drehtaster kurz antippen zum Bestätigen ("OK").
è Letzter ausgewählter Urlaubstag wird blau umrandet darge-
stellt.
8 Drehtaster gegen den Uhrzeigersinn drehen, bis alle Tage weiß
dargestellt sind.
9 Drehtaster kurz antippen zum Bestätigen ("OK").
è Urlaubseinstellung wird zurückgesetzt und Einstellebene
verlassen.
3.3.7 Zeitprogramme einstellen
Um permanente Zeitprogramme (siehe Kap. 4.3.2) einzustellen, wird die Zeitprogramm-Funktion genutzt. Diese erlaubt die tageweise Ein­stellung von 3 Schaltzyklen. Die Eingabe ist für jeden einzelnen Wo­chentag separat möglich oder in Blöcken von "Montag bis Freitag", "Samstag bis Sonntag" und "Montag bis Sonntag". Die ausgewähl­ten Schaltzyklen werden in der Übersichtsebene des jeweiligen Pro­gramms grau unterlegt dargestellt (Bild 16-9).
Zeitraum Schaltzyklus
Einzelner Wochentag (Mon­tag,Dienstag…)
Arbeitswoche (MontagbisFrei­tag)
Wochenende (Sams­tagbisSonntag)
Gesamte Woche (Mon­tagbisSonntag)
Tab.16-4 Struktur der permanenten Zeitprogramme
Daikin RoCon+ HP Daikin Regelung RoCon+ HP1
008.1447899_00 – 09/2019 – DE
1. 06:00 bis 22:00
2. xx:xx bis xx:xx
3. xx:xx bis xx:xx
1. 06:00 bis 22:00
2. xx:xx bis xx:xx
3. xx:xx bis xx:xx
1. 06:00 bis 22:00
2. xx:xx bis xx:xx
3. xx:xx bis xx:xx
1. 06:00 bis 22:00
2. xx:xx bis xx:xx
3. xx:xx bis xx:xx
INFORMATION
Zeiteinstellungen für einen Schaltzyklus in einem Wochen­tag- oder Blockprogramm werden auch für andere Zeiträu­me übernommen, sofern diese die gleichen Wochentage betreffen.
▪ Für den einzelnen Wochentag "Montag" wird die An-
fangszeit im ersten Schaltzyklus von 06:00 auf 05:00 Uhr geändert. Im Zeitraum "Montag bis Freitag" und "Montag bis Sonntag" wird automatisch der erste Schaltzyklus von 06:00 auf 05:00 Uhr mit geändert.
Bild16-9 Zeitprogramm-Funktion mit Übersichtsebene (links) und
Einstellebene (rechts)
Beispiel: Für das Programm [Heizkreis Automatik 1] die Schaltzy­klen 1 und 2 für Montag bis Freitag einstellen [→Hauptmenü →Zeitprogramm →HK Auto 1]:
1 Drehtaster im Uhrzeigersinn drehen, bis das Einstellung-Icon
blau dargestellt wird.
2 Drehtaster kurz antippen zum Bestätigen ("OK").
è Anzeige wechselt auf Einstellebene mit blau blinkender Zeit-
raum-Auswahl. 3 Drehtaster im Uhrzeigersinn drehen, bis gewünschter Zeitraum
dargestellt wird.
4 Drehtaster kurz antippen zum Bestätigen ("OK").
è Anzeige wechselt auf Eingabefenster für Startzeit des ersten
Schaltzyklus. 5 Drehtaster kurz antippen zum Bestätigen ("OK").
è Eingabefenster für Startzeit des ersten Schaltzyklus blinkt
blau. 6 Drehtaster im Uhrzeigersinn drehen, bis gewünschte Startzeit
dargestellt wird.
7 Drehtaster kurz antippen zum Bestätigen ("OK").
è Anzeige wechselt auf Eingabefenster für Endzeit des ersten
Schaltzyklus. 8 Drehtaster im Uhrzeigersinn drehen, bis gewünschte Endzeit
dargestellt wird.
9 Drehtaster kurz antippen zum Bestätigen ("OK").
è Anzeige wechselt auf Eingabefenster für Startzeit des zwei-
ten Schaltzyklus. 10 Drehtaster kurz antippen zum Bestätigen ("OK").
è Eingabefenster für Startzeit des zweiten Schaltzyklus blinkt
blau. 11 Drehtaster im Uhrzeigersinn drehen, bis gewünschte Startzeit
dargestellt wird.
12 Drehtaster kurz antippen zum Bestätigen ("OK").
è Anzeige wechselt auf Eingabefenster für Endzeit des zwei-
ten Schaltzyklus. 13 Drehtaster im Uhrzeigersinn drehen, bis gewünschte Endzeit
dargestellt wird.
14 Drehtaster kurz antippen zum Bestätigen ("OK").
è Anzeige wechselt auf Eingabefenster für Startzeit des dritten
Schaltzyklus. 15 Drehtaster im Uhrzeigersinn drehen, bis Bestätigen-Icon blau
dargestellt wird. è Anzeige wechselt auf das Bestätigen-Icon.
Betriebsanleitung
67
Page 68
3 Bedienung
16 Drehtaster kurz antippen zum Bestätigen ("OK").
è Programmierung wird gespeichert. è Einstellebene wird verlassen. è Gewählte Schaltzyklen werden grau unterlegt dargestellt.
17 Drehtaster gegen den Uhrzeigersinn drehen, bis Zurück-Icon
blau dargestellt wird.
18 Drehtaster kurz antippen zum Bestätigen ("OK").
è Menü wird verlassen
3.3.8 Externe Bedienung
Neben der Bedienung durch die integrierte RoCon+ HP Regelung kann die Anlage auch über externe Geräte eingestellt und bedient werden.
Bedienung über das Internet
Über ein optionales Gateway (EHS157056) kann die Regelung Ro­Con+ HP mit dem Internet verbunden werden. Damit ist eine Fern­steuerung der RoCon+ HP über Mobiltelefone (per App) möglich.
Bedienung über die Raumstation
Die Bedienung kann auch über den optionalen Raumregler EHS157034 erfolgen. Dazu dem Gerät beiliegende Bedienungsan­leitung beachten.
Betriebsanleitung
68
Daikin Regelung RoCon+ HP1
Daikin RoCon+ HP
008.1447899_00 – 09/2019 – DE
Page 69

4 Funktion

4 Funktion
Die Anlage regelt vollautomatisch anhand der in der Regelung Ro­Con+ HP eingestellten Vorgaben den Betrieb der Raumheizung, Raumkühlung und die sanitärseitige Warmwasserbereitung. Im Fol­genden werden die Funktionen beschrieben, welche den Anlagenbe­trieb beeinflussen können.
Manche der beschriebenen Funktionen und Parameter sind durch Zugriffsrechte beschränkt und können nur vom Heizungsfachmann eingestellt werden (siehe Kap. 4.5.1).

4.1 Betriebsart

[→Hauptmenü →Betriebsart] In diesem Menü erfolgt die Auswahl der Betriebsart, mit welcher das
Gerät arbeiten soll. Die aktuelle Betriebsart wird durch ein entspre­chendes Symbol im Startbildschirm gekennzeichnet.
Betriebsart Bereitschaft (Stand-by)
HINWEIS
Eine nicht frostgesicherte Heizungsanlage kann bei Frost einfrieren und dadurch beschädigt werden.
▪ Die Heizungsanlage bei Frostgefahr wasserseitig ent-
leeren.
▪ Bei nicht entleerter Heizungsanlage, muss bei Frostge-
fahr die Stromversorgung sichergestellt und der Netz­schalter eingeschaltet bleiben.
In dieser Betriebsart wird die Daikin Altherma ETS(X/H) in den Stand-by-Betrieb versetzt. Die Frostschutzfunktion bleibt dabei er­halten. Zur Erhaltung dieser Funktion darf die Anlage nicht vom Netz genommen werden!
Alle im RoCon-System über den CAN-Bus integrierten Regler wer­den übergeordnet ebenfalls in die Betriebsart "Bereitschaft" geschal­tet.
INFORMATION
In der Betriebsart [Bereitschaft] wird die Wärmepumpe und ggf. der optional angeschlossene Backup-Heater von der Spannungsversorgung getrennt (Energiesparmodus), wenn folgende Bedingungen erfüllt sind:
▪ der Außentemperaturfühler ist angeschlossen und rich-
tig in der Anlagenkonfiguration parametriert, ▪ die Außentemperatur liegt über 8°C, ▪ es liegt keine Heizungsanforderung vor, ▪ in keinem angeschlossenem Heizkreis ist die Frost-
schutzfunktion aktiv und ▪ die Daikin Altherma ETS(X/H) ist seit mindestens 5min
eingeschaltet.
Betriebsart Absenken
Reduzierter Heizbetrieb (niedrigere Raumsolltemperatur) nach der im Parameter [Raumtemperatur Absenken] eingestellten Absenk­temperatur (siehe Kap. 4.2).
Warmwasserbereitung nach den eingestellten Solltemperaturen und Schaltzyklen im Warmwasser-Zeitprogramm [Warmwasser Automa­tik 1] (siehe Kap. 4.2).
Betriebsart Heizen
Heiz-, Kühlbetrieb nach der im Parameter [Raumtemperatur Soll 1] eingestellten Raum-Solltemperatur (siehe Kap. 4.2).
Ein angeschlossener Außentemperaturfühler (witterungsgeführte Vorlauftemperaturregelung) oder ein angeschlossener Raumregler beeinflussen ebenfalls die Vorlauf-Solltemperatur.
Warmwasserbereitung nach den eingestellten Solltemperaturen und Schaltzyklen im Warmwasser-Zeitprogramm [Warmwasser Automa­tik 1] (siehe Kap. 4.2).
Betriebsart Sommer
Es erfolgt nur eine Warmwasserbereitung nach den eingestellten Solltemperaturen und Schaltzyklen im Warmwasser-Zeitprogramm [Warmwasser Automatik 1] (siehe Kap. 4.2).
Alle im RoCon-System über den CAN-Bus integrierten Regler wer­den übergeordnet ebenfalls in die Betriebsart [Sommer] geschaltet.
Betriebsart Automatik 1 (Zeitprogramm)
Automatischer Heiz- und Absenkbetrieb nach den permanenten Zeit­programmen (siehe Kap. 4.3):
▪ [Heizkreis Automatik 1] ▪ [Warmwasser Automatik 1]
Betriebsart Automatik 2 (Zeitprogramm)
Automatischer Heiz- und Absenkbetrieb nach den permanenten Zeit­programmen (siehe Kap. 4.3):
▪ [Heizkreis Automatik 2] ▪ [Warmwasser Automatik 2]
INFORMATION: SCHALTKONTAKT FÜR EXTERNE BE­TRIEBSARTENUMSCHALTUNG
Über einen am Anschluss J8 der Daikin Altherma ETS(X/ H) an den Klemmen "Ext" angeschlossenen und mit einem Widerstand beschalteten potenzialfreien Schaltkontakt kann von einem externen Gerät (z. B. Modem, …) eben­falls eine Umschaltung erfolgen. Siehe Tab. 17-1.
Die Funktionalität des Schaltkontakts ist dabei abhängig von dem Parameter [Funktion Brennersperrkontakt]:
▪ [Funktion Brennersperrkontakt] = Widerstandswerte
(Standardeinstellung): Auswertung der Widerstands­werte.
▪ [Funktion Brennersperrkontakt] = Brennersperrkontakt:
Auswertung als Brennersperrkontakt. Bei geschlosse­nem Schaltkontakt wird dem externen Wärmeerzeuger Vorrang eingeräumt.
Betriebsart Widerstand Toleranz
Bereitschaft <680Ω ±5%
Heizen 1200Ω
Absenken 1800Ω
Sommer 2700Ω Automatik 1 4700Ω Automatik 2 8200Ω
Tab.17-1 Widerstandswerte zur Auswertung des EXT-Signals
INFORMATION
Die in Tab. 17-1 angegebenen Widerstände funktionieren in einem Toleranzfeld von 5%. Außerhalb dieser Toleranz­felder liegende Widerstände werden als offener Eingang interpretiert. Der Wärmeerzeuger schaltet in die zuvor akti­ve Betriebsart zurück.
Bei Widerstandswerten größer dem Wert für "Automatik 2", wird der Eingang nicht berücksichtigt.
Sollten mehrere Schaltkontakte an die Daikin Altherma ETS(X/H) angeschlossen sein (z. B. Smart Grid, Raum­thermostat), können die damit verbundenen Funktionen ei­ne höhere Priorität als die externe Betriebsartenumschal­tung haben. Die durch den EXT-Schaltkontakt angeforder­te Betriebsart wird dann eventuell nicht oder erst später ak­tiviert.
Daikin RoCon+ HP Daikin Regelung RoCon+ HP1
008.1447899_00 – 09/2019 – DE
Betriebsanleitung
69
Page 70
4 Funktion
Neben diesen Betriebsarten stehen verschiedene temporäre Zeitpro­gramme (siehe Tab. 17-2) zur Verfügung, die nach Aktivierung mit Vorrang ablaufen.
Temporäres Heizpro-
gramm
Party Zeitprogramm Kap. 4.3
Abwesend
Feiertag
Urlaub Estrich Konfiguration Kap. 4.5.7
Tab.17-2 Übersicht temporäre Zeitprogramme
INFORMATION
Wird ein temporäres Heizprogramm (Party, Abwesend, Feiertag, Urlaub, Estrich) während der gewählten Betriebs­art gestartet, so wird vorrangig nach den Einstellungen für dieses Zeitprogramm geregelt.
Einstellung / Aktivie-
rung in Menü
Hinweis

4.2 Benutzer

[→Hauptmenü →Benutzer] In diesem Menü werden für den Benutzer die wichtigsten Solltempe-
raturen und Funktionen eingestellt.
4.2.1 Einstellung Raumtemperatur Soll
[→Hauptmenü →Benutzer →Raum] In diesem Menü werden die Raum-Solltemperaturen im Heizbetrieb
für die Raumheizung festgelegt. Die verfügbaren Sollwerte (1-3) ge­hören zum jeweiligen Zyklus (1-3) der Zeitprogramme [Heizkreis Au­tomatik 1] und [Heizkreis Automatik 2].
Weiterführende Erklärungen und mögliche Einstellwerte zu diesem Menü finden Sie in Kap. 7.3.
4.2.2 Einstellung Raumtemperatur Absenken
[→Hauptmenü →Benutzer →Absenken] In diesem Menü wird die Raum-Solltemperatur im Absenkbetrieb für
die Raumheizung festgelegt. Der Absenkbetrieb erfolgt durch die Betriebsart "Absenken" oder durch die Zeitprogramme [Heizkreis Automatik 1] und [Heizkreis Automatik 2].
Weiterführende Erklärungen und mögliche Einstellwerte zu diesem Menü finden Sie in Kap. 7.3.
4.2.3 Einstellung Raumtemperatur Abwesend
[→Hauptmenü →Benutzer →Abwesend] In diesem Menü wird die Raum-Solltemperatur im Abwesenheitsbe-
trieb für die Raumheizung festgelegt. Der Abwesenheitsbetrieb er­folgt durch die Zeitprogramme [Abwesend] oder [Urlaub].
Weiterführende Erklärungen und mögliche Einstellwerte zu diesem Menü finden Sie in Kap. 7.3.
4.2.4 Einstellung Warmwassertemperatur Soll
[→Hauptmenü →Benutzer →Warmwasser] In diesem Menü werden die Warmwasser-Solltemperaturen für die
Warmwasserbereitung festgelegt. Die verfügbaren Sollwerte (1-3) gehören zum jeweiligen Zyklus (1-3) der Zeitprogramme [Warmwas­ser Automatik 1] und [Warmwasser Automatik 2].
Weiterführende Erklärungen und mögliche Einstellwerte zu diesem Menü finden Sie in Kap. 7.3.
4.2.5 Außerplanmäßige Warmwasserbereitung
[→Hauptmenü →Benutzer →1x Laden] Durch Starten dieser Funktion kann das Warmwasser zu einem be-
liebigen Zeitpunkt auf die Solltemperatur [Warmwassertemperatur Soll 1] aufgeheizt werden. Die Aufheizung erfolgt vorrangig und un­abhängig von anderen Heizprogrammen. Nach Ablauf dieser tempo­rären Funktion springt die Regelung automatisch auf die zuvor aktive Betriebsart zurück.
Mögliche Einstellwerte zu diesem Menü finden Sie in Kap. 7.3.

4.3 Zeitprogramm

[→Hauptmenü →Zeitprogramm] Für eine komfortable und individuelle Raum- und Warmwassertem-
perierung stehen verschiedene frei einstellbare permanente Zeitpro­gramme zur Auswahl. Zudem stehen temporäre Zeitprogramme zur Verfügung, welche die permanenten Zeitprogramme bzw. die aktuell eingestellte Betriebsart für die Dauer ihrer Gültigkeit außer Kraft set­zen.
4.3.1 Temporäre Zeitprogramme
INFORMATION
Die folgenden temporären Zeitprogramme können jeder­zeit durch das manuelle Verändern der Betriebsart abge­brochen werden.
Party
[→Hauptmenü →Zeitprogramm →Party] Das Programm läuft ab Aktivierung bis zum Ablauf des eingestellten
Zeitraums. Der Heizkreis wird in dieser Zeit auf die im Parameter [Raumtemperatur Soll 1] eingestellte Temperatur geregelt. Sind die Zeitprogramme [Automatik 1] oder [Automatik 2] aktiv, wird der Heiz­zyklus verlängert oder vorzeitig gestartet. Die Warmwasserbereitung wird nicht beeinflusst.
Abwesend
[→Hauptmenü →Zeitprogramm →Abwesend] Das Programm läuft ab Aktivierung bis zum Ablauf des eingestellten
Zeitraums. Der Heizkreis wird in dieser Zeit auf die im Parameter [Raumtemperatur Abwesend] eingestellte Raum-Solltemperatur ge­regelt. Die Warmwasserbereitung wird nicht beeinflusst.
Urlaub
[→Hauptmenü →Zeitprogramm →Urlaub] Mit dieser Kalenderfunktion kann ein Zeitraum der Abwesenheit ein-
gegeben werden. In dieser Zeit wird der Heizkreis dauerhaft (24h pro Tag) auf die im Parameter [Raumtemperatur Abwesend] einge­stellte Raum-Solltemperatur geregelt. Dieses Programm wird nicht gestartet, wenn zum eingestellten Startdatum die Betriebsart [Bereit­schaft] aktiv ist.
Feiertag
[→Hauptmenü →Zeitprogramm →Feiertag] Mit dieser Kalenderfunktion kann ein Zeitraum der Anwesenheit ein-
gegeben werden. In dieser Zeit wird ausschließlich nach den Einstel­lungen für "Sonntag" in [Heizkreis Automatik 1] und [Warmwasser Automatik 1] geregelt.
4.3.2 Permanente Zeitprogramme
Für die angeschlossenen Heizkreise und den Speicherladekreis re­geln Zeitprogramme die Heizkreis- und Warmwassertemperaturen bzw. die Betriebszeiten der Zirkulationspumpe nach den vorgegebe­nen Schaltzyklen. Die Schaltzyklen sind in Zeitblöcken abgespei­chert, für welche unterschiedliche Solltemperaturen einstellbar sind.
Betriebsanleitung
70
Daikin Regelung RoCon+ HP1
Daikin RoCon+ HP
008.1447899_00 – 09/2019 – DE
Page 71
4 Funktion
Gespeicherte Zeitprogramm können jederzeit geändert werden. Zur besseren Übersicht wird empfohlen, die programmierten Schaltzy­klen aufzuschreiben und sicher aufzubewahren (siehe Kap. 11.1).
Heizkreis Automatik 1 und Heizkreis Automatik 2
[→Hauptmenü →Zeitprogramm →HK Auto 1/HK Auto 2] In diesen Menüs können die Zeitprogramme für den Heizkreis para-
metriert werden. Pro Tag können 3 Schaltzyklen eingestellt werden, denen die Parameter [Raumtemperatur Soll 1/2/3] zugeordnet sind. Außerhalb der Schaltzyklen wird auf den Sollwert [Raumtemperatur Absenken] geregelt. Die Eingabe ist für jeden einzelnen Wochentag separat oder in Wochenabschnitten möglich.
Warmwasser Automatik 1 und Warmwasser Automatik 2
[→Hauptmenü →Zeitprogramm →WW Auto 1/WW Auto 2] In diesen Menüs können die Zeitprogramme für die Warmwasserbe-
reitung parametriert werden. Pro Tag können 3 Schaltzyklen einge­stellt werden, denen die Parameter [Warmwassertemperatur Soll 1/2/3] zugeordnet sind.
Zirkulationsprogramm
[→Hauptmenü →Zeitprogramm →Zirkulation] In diesem Menü kann ein Zeitprogramm für eine optional ange-
schlossene Zirkulationspumpe parametrisiert werden. Es können 3 Schaltzyklen pro Tag eingestellt werden.
Schaltzyklus1 Schaltzyklus2 Schaltzyklus3
Zeitraum Ein Aus Ein Aus Ein Aus
Raumheizung
Temperatureinstellung [Raumtemperatur Soll 1]: 20°C [Raumtemperatur Soll 2]: 20°C [Raumtemperatur Soll 3]: 20°C
[Raumtemperatur Absenken]: 10°C
"Heizkreis Automatik 1"
Montag - Freitag 06:00 22:00 - - : - - - - : - - - - : - - - - : - -
Samstag, Sonntag 07:00 23:00 - - : - - - - : - - - - : - - - - : - -
"Heizkreis Automatik 2"
Montag - Freitag 06:00 08:00 16:00 22:00 - - : - - - - : - -
Samstag, Sonntag 07:00 23:00 - - : - - - - : - - - - : - - - - : - -
INFORMATION
Verwendung von Zirkulationsleitungen in Frankreich nicht zulässig!
Sound Programm
INFORMATION
Bei geräuscharmem Betrieb nimmt die Leistung im Raum­heiz- und Raumkühlbetrieb so ab, dass ggf. voreingestellte Temperatursollwerte nicht mehr erreicht werden können. Daher kann dieses Programm nur vom Installateur einge­stellt werden.
In diesem Menü kann ein Zeitprogramm für verschiedene Stufen des geräuscharmen Betriebs der Wärmepumpe parametriert werden. Es können 3 Schaltzyklen mit einer Auflösung von 15 Minuten einge­stellt werden. Die Eingabe ist für jeden einzelnen Wochentag sepa­rat möglich. Format: (Ein) hh:mm - hh:mm (Aus)
Ebenfalls können die Zyklen von Montag bis Freitag, Samstag bis Sonntag und Montag bis Sonntag parametriert werden.
Jedem Schaltzyklus kann eine Geräuschstufe zugeordnet werden (0
- keine Geräuschreduktion; 1 – Min. Geräuschreduktion; 2 – Med. Geräuschreduktion; 3 – Max. Geräuschreduktion).
Werkseinstellungen
Die permanenten Zeitprogramme sind entsprechend Werkseinstel­lung voreingestellt.
Warmwasserbereitung
Temperatureinstellung [Warmwassertemperatur Soll 1]:
60°C
"Warmwasser Automatik 1"
Montag - Sonntag 05:00 21:00 - - : - - - - : - - - - : - - - - : - -
"Warmwasser Automatik 2"
Montag - Freitag 05:00 21:00 - - : - - - - : - - - - : - - - - : - -
Samstag, Sonntag 06:00 22:00 - - : - - - - : - - - - : - - - - : - -
"Zirkulationsprogramm"
Montag - Freitag 05:00 21:00 - - : - - - - : - - - - : - - - - : - -
Samstag, Sonntag 06:00 22:00 - - : - - - - : - - - - : - - - - : - -
"Sound Programm"
Montag - Sonntag - - : - - - - : - - - - : - - - - : - - - - : - - - - : - -
Tab.17-3 Werkseinstellung der permanenten Zeitprogramme
4.3.3 Zeitprogramm Reset
[→Hauptmenü →Zeitprogramm →ZP Reset] In diesem Menü können die Zeitprogramme auf Werkseinstellungen
zurückgesetzt werden. Hierzu die jeweiligen Zeitprogramme aus­wählen und anschließend die Auswahl mit dem Bestätigen-Button auf der zweiten Menü-Seite bestätigen.
[Warmwassertemperatur Soll 2]:
60°C
[Warmwassertemperatur Soll 3]:

4.4 Einstellungen

[→Hauptmenü →Einstellungen] In diesem Menü wird die Grundeinstellung der Regelung und des
Systems vorgenommen. Dazu gehört die Einbindung optionaler und externer Komponenten. Je nach Zugangsberechtigung (Benutzer oder Fachmann) sind verschiedene Parameter verfügbar.
60°C
Daikin RoCon+ HP Daikin Regelung RoCon+ HP1
008.1447899_00 – 09/2019 – DE
Betriebsanleitung
71
Page 72
4 Funktion
4.4.1 Anzeigeeinstellungen
[→Hauptmenü →Einstellungen →Anzeige] In diesem Menü kann Sprache, Datum, Uhrzeit, LCD Helligkeit und
LCD Beleuchtungsdauer eingestellt werden. Weiterführende Erklärungen und mögliche Einstellwerte zu diesem
Menü finden Sie in Kap. 7.5.
INFORMATION
Die Erhöhung der Helligkeit des LCD-Displays über den werkseingestellten Wert hinaus verringert die Lebensdauer des Displays.
4.4.2 System
[→Hauptmenü →Einstellungen →System] In diesem Menü sind grundlegende Parameter der Heizanlage zu-
sammengefasst. Weiterführende Erklärungen und mögliche Einstellwerte zu diesem
Menü finden Sie in Kap. 7.5.2.
4.4.3 Externe Wärmequellen
[→Hauptmenü →Einstellungen →Ext. Quelle] In diesem Menü kann die Einbindung einer optionalen externen Wär-
mequelle konfiguriert werden. Die von einem alternativen WEZ gelieferte Wärme, muss dem druck-
losen Speicherwasser im Warmwasserspeicher der Daikin Altherma ETS(X/H) zugeführt werden.
▪ Bei Verwendung des optionalen Backup-Heaters EKBUxx, erfolgt
dies bedingt durch die konstruktive Einbausituation.
▪ Bei Verwendung eines alternativen WEZ (z. B. Gas- oder Ölheiz-
kessel) kann dieser hydraulisch ▪ drucklos über die Anschlüsse (Solar-Vorlauf und Solar-Rück-
lauf) des Warmwasserspeichers oder
▪ bei Gerätetypen Daikin Altherma ETS(X/H) …B über den inte-
griertem Drucksolar-Wärmetauscher eingebunden werden. Mit der Einstellung des Parameters [Konfig. externe Wärmequelle]
wird festgelegt, ob und welcher zusätzliche Wärmeerzeuger (WEZ) für die Warmwasserbereitung und die Heizungsunterstützung vor­handen ist.
▪ Keine externe Wärmequelle ▪ Optionaler Backup-Heater ▪ Externe Wärmequelle WW und HZU: Alternativer WEZ übernimmt
Warmwasserbereitung und Heizungsunterstützung. Zur Anforde­rung des WEZ wird das Relais K3 auf der Schaltplatine RTX-EHS geschaltet.
▪ Externe Wärmequelle WW oder HZU: Alternativer WEZ 1 (optio-
naler Backup-Heater EKBUxx) übernimmt Warmwasserbereitung und alternativer WEZ 2 übernimmt Heizungsunterstützung. Zur Anforderung des WEZ 1 wird das Relais K3 und zur Anforderung des WEZ 2 das Relais K1 auf der Schaltplatine RTX-EHS ge­schaltet. Warnhinweis beachten! Die Funktionsweise eines zu­sätzlichen alternativen WEZ wird auch durch die Einstellungen der Parameter [Bivalenzfunktion] und [Bivalenztemperatur] beein­flusst.
Weiterführende Erklärungen und mögliche Einstellwerte zu diesem Menü finden Sie in Kap. 7.5.3.
(1)
Schaltkontakte am Eingang J8 der Schaltplatine RoCon BM2C geschlossen (1) oder geöffnet (0).
(2)
Keine Frostschutzfunktion
4.4.4 Ein-/Ausgänge
[→Hauptmenü →Einstellungen →Ein-/Ausgänge] In diesem Menü können Parameter für Ein- und Ausgänge der Re-
gelungsplatine konfiguriert werden, um die Anlagenregelung indivi­duell zu optimieren.
Smart Grid
WARNUNG
Bei Warmwasser-Solltemperaturen über 65°C besteht Verbrühungsgefahr. Dies ist möglich, da das Energiever­sorgungsunternehmen (EVU) in den Festlegungen für Smart Grid berechtigt ist, die Stromabnahme optimiert nach Angebot und Nachfrage zu steuern.
Durch eine solche erzwungene Ladung kann die Warm­wasser-Solltemperatur im Warmwasserspeicher über 65°C erreichen.
Diese Speicherladung erfolgt selbst dann, wenn die Be­triebsart [Bereitschaft] eingestellt ist.
▪ Verbrühschutz in die Warmwasser-Verteilleitung ein-
bauen.
Für die Nutzung dieser Funktion ist ein spezieller Stromzähler mit SG-Empfänger notwendig, an welchem die Daikin Altherma ETS(X/ H) angeschlossen werden muss.
Sobald die Funktion durch den Parameter [Smart Grid] aktiviert ist, wird abhängig vom Signal des Energieversorgungsunternehmens die Wärmepumpe in eine Betriebsweise gemäß Tab. 17-4 versetzt.
(1)
Signal
EVU SG Warmwasser Heizung
1 0 --- Kein Betrieb 0 0 Normal Normaler Be-
0 1 Gering Einschaltemp-
1 1 Sehr gering Einschaltbefehl
Tab.17-4 Nutzung des SG-Signals
AUX-Schaltfunktion
Durch Einstellen des Parameters [AUX-Schaltfunktion] werden die Schaltbedingungen für den potenzialfreien AUX-Schaltkontakt (Wechselschaltausgang A) gewählt. Über diesen Schaltkontakt kann beispielsweise ein externer Wärmeerzeuger angesteuert werden.
Ist eine der Schaltbedingungen erfüllt, so wird der potenzialfreie Schaltkontakt nach Ablauf der im Parameter [AUX-Wartezeit] einge­stellten Zeit geschaltet.
AUX-Schaltkontakt (Wechselschaltausgang A) wird nicht geschal­tet, wenn Einstellung deaktiviert.
AUX-Schaltkontakt (Wechselschaltausgang A) wird geschaltet,
wenn Einstellung ▪ Speichertemperatur (T
HW (AUX)].
▪ wenn ein Fehler anliegt.
Stromkosten Auswirkung auf
(2)
Kein Betrieb
Normaler Be-
trieb
Einschaltemp-
fehlung und
Sollwert Spei-
chertemperatur
wird abhängig
von Parameter
[Modus Smart
Grid] erhöht.
fehlung und Vor-
lauf-Solltempe-
ratur wird ab-
hängig von Pa-
rameter [Modus
Smart Grid] er-
höht.
Einschaltbefehl
und Sollwert
Speichertempe-
für Speicherla-
dung.
ratur wird auf
70°C gesetzt.
) ≥ Wert Parameter [Schaltschwelle TD-
dhw
(2)
trieb
Betriebsanleitung
72
Daikin Regelung RoCon+ HP1
Daikin RoCon+ HP
008.1447899_00 – 09/2019 – DE
Page 73
4 Funktion
▪ Außentemperatur < Parameterwert [Bivalenztemperatur].
▪ Wärmeanforderung Warmwasserbereitung.
▪ Wärmeanforderung Raumheizung.
▪ Wärmeanforderung Raumheizung oder Warmwasserbereitung.
Interlinkfunktion
Die Einstellung des Parameters [Interlinkfunktion] = Ein bietet die
Möglichkeit, dass die Daikin Altherma ETS(X/H) zwei verschiedene
Vorlauf-Solltemperaturwerte in die Regelung einbezieht.
Dies gilt sowohl für eine witterungsgeführte Regelung als auch bei
der Regelung nach einer festen Vorlauf-Solltemperatur (siehe
Kap. 4.5).
Eine mögliche Anwendung ist z. B. die zusätzliche Einbindung eines
HP convector in ein Flächenheiz- und Kühlsystem.
Voraussetzung: Am Steckeranschluss J16 der Daikin Altherma
ETS(X/H) sind 2 Schaltkontakte (z. B. Raumthermostate) ange-
schlossen.
▪ Parameter [Interlinkfunktion] = Aus: Deaktiviert
▪ Parameter [Interlinkfunktion] = Ein: Auswertung der Schaltkontak-
te Heizen und Kühlen am Steckeranschluss J16 auf der Schaltpla­tine RoCon BM2C. Aktivieren des Kühlbetriebs nur durch Umstel­len der Betriebsart auf [Kühlen] (siehe Kap. 4.1). Einstellung des Parameters [Raumthermostat] wird nicht mehr ausgewertet.
▪ Offene Schaltkontakte: nur Frostschutz aktiv ▪ Betriebsart [Heizen] oder [Automatik 1] / [Automatik 2] während
der Schaltzyklen im Tagbetrieb aktiv. ▪ Geschlossener Schaltkontakt Heizen = IL1 ▪ Es wird auf die normale Vorlauf-Solltemperatur gemäß den Pa-
rametereinstellungen für [Heizen] geregelt. ▪ Geschlossener Schaltkontakt Kühlen = IL2 ▪ Es wird auf die erhöhte Vorlauf-Solltemperatur geregelt (norma-
le Vorlauf-Solltemperatur + Wert des Parameters [Interlink Tem-
peraturerhöhung ]). Priorität, falls beide Schaltkontakte ge-
schlossen sind!
▪ Betriebsart [Kühlen] aktiv.
▪ Geschlossener Schaltkontakt Heizen= IL1 ▪ Es wird auf die normale Vorlauf-Solltemperatur gemäß den Pa-
rametereinstellungen in Ebene [Heizkreis Konfiguration] > [Küh-
len] geregelt. ▪ Geschlossener Schaltkontakt Kühlen = IL2 ▪ Es wird auf die abgesenkte Vorlauf-Solltemperatur geregelt
(normale Vorlauf-Solltemperatur - Wert des Parameters [Inter-
link Temperaturerhöhung ]. Priorität, falls beide Schaltkontakte
geschlossen sind!
Weiterführende Erklärungen und mögliche Einstellwerte zu diesem Menü finden Sie in Kap. 7.5.
Heizungsunterstützung (HZU)
Wird die Heizungsunterstützungsfunktion (Parameter [Heizungsun­terstützung (HZU)] = Ein) aktiviert, so wird die Energie im integrier­ten Speicherbehälter der Daikin Altherma ETS(X/H) genutzt, um die Heizungsfunktion zu übernehmen. Bei ausreichend hoher Speicher­temperatur bleibt der Brenner außer Betrieb.
Der Mindestwert (T
) errechnet sich wie folgt: T
HZUmin
HZUmin
= Gerade aktive Warmwasser-Solltemperatur [Warmwassertemperatur Soll] + Parameter [HZU Hysterese].
Einschaltbedingung: Tdhw > T
+ 4K und Tdhw > Info-Parameter [Warmwassertem-
HZUmin
peratur Soll] + 1K Ist die Einschaltbedingung erfüllt, so wird dem Speicherbehälter
Wärme entnommen und damit die Heizungsanlage versorgt. Ausschaltbedingung: Tdhw < T
oder Tdhw < Parameter [Vorlauftemperatur Soll] (sie-
HZUmin
he Kap. 4.5.3) Ist die Ausschaltbedingung erfüllt, so wird die Heizungsunterstüt-
zung aus dem Warmwasserspeicher eingestellt und der Brenner übernimmt den Heizbetrieb.
Der Parameter [Leistung BIV] begrenzt die Leistung, die maximal entnommen werden darf. Der Parameter [HZU Max. Temperatur] be­grenzt die maximale Temperatur, welche in die Heizungsanlage ge­langen darf.
Weiterführende Erklärungen und mögliche Einstellwerte zu den Pa­rametern in diesem Menü finden Sie in Kap. 7.5.5.

4.5 Konfiguration

[→Hauptmenü →Konfiguration] In diesem Menü kann die Betriebscharakteristik der Anlage optimal
an den Systemaufbau und den Bedarf der Nutzer angepasst wer­den. Zusatzprogramme erleichtern die Inbetriebnahme. Je nach Zu­gangsberechtigung (Benutzer oder Fachmann) sind verschiedene Parameter verfügbar.
4.5.1 Zugriffsrechte (Fachmanncode)
[→Hauptmenü →Konfiguration →Zugriff] Bestimmte Funktionen und Parameter in der Regelung sind durch
Zugriffsrechte beschränkt und für den Benutzer nicht sichtbar. Um Zugriff darauf zu erhalten, muss der Fachmanncode eingegeben werden.
4.4.5 Intelligentes Speicher Management
[→Hauptmenü →Einstellungen →ISM] Bei ausreichend hohen Speichertemperaturen kann die Energie im
Speicherbehälter für die Raumheizung genutzt werden. Dies kann entweder den Komfort erhöhen (Funktion [Continuous heating]) oder es ermöglichen, Energie aus einer externen Wärmequelle wie z.B. Solar dann zu nutzen, wenn Heizbedarf besteht (Funktion [Hei­zungsunterstützung (HZU)]).
Continuous heating
Die Funktion erlaubt das ununterbrochene Heizen auch während dem Abtauen des Verdampfers. Damit kann ein hoher Komfort auch bei schnell reagierenden Heizsystemen (z.B. Konvektoren) gewähr­leistet werden.
Daikin RoCon+ HP Daikin Regelung RoCon+ HP1
008.1447899_00 – 09/2019 – DE
Bild17-1 Zugriffscode einstellen
Beispiel: Code 3090 einstellen (nur exemplarisch, dies ist kein gülti­ger Zugriffscode) [→Hauptmenü →Konfiguration →Zugriff]:
Betriebsanleitung
73
Page 74
4 Funktion
1 Drehtaster im Uhrzeigersinn drehen, bis erstes Eingabefeld blau
dargestellt wird.
2 Drehtaster kurz antippen zum Bestätigen ("OK").
è Erstes Eingabefeld blinkt blau.
3 Drehtaster im Uhrzeigersinn drehen, bis 3 dargestellt wird. 4 Drehtaster kurz antippen zum Bestätigen ("OK").
è Zweites Eingabefeld wird blau dargestellt.
5 Drehtaster im Uhrzeigersinn drehen, bis drittes Eingabefeld blau
dargestellt wird.
6 Drehtaster kurz antippen zum Bestätigen ("OK").
è Drittes Eingabefeld blinkt blau.
7 Drehtaster im Uhrzeigersinn drehen, bis 9 dargestellt wird. 8 Drehtaster kurz antippen zum Bestätigen ("OK").
è Viertes Eingabefeld wird blau dargestellt.
9 Drehtaster im Uhrzeigersinn drehen, bis Bestätigen-Icon blau
dargestellt wird.
10 Drehtaster kurz antippen zum Bestätigen ("OK").
è Code wird geprüft und Einstellebene verlassen.
4.5.2 Sensoren
[→Hauptmenü →Konfiguration →Sensoren] In diesem Menü werden (optionale) Sensoren aktiviert und konfigu-
riert. Druck-Sollwerte für die Wasserseite können festgelegt werden. Weiterführende Erklärungen und mögliche Einstellwerte zu den Pa-
rametern in diesem Menü finden Sie in Kap. 7.6.1.
4.5.3 Heizkreis Konfiguration
[→Hauptmenü →Konfiguration →HK-Konfig] In diesem Menü wird die grundlegende Funktionalität des Heizkrei-
ses eingestellt. Weiterführende Erklärungen und mögliche Einstellwerte zu den Pa-
rametern in diesem Menü finden Sie in Kap. 7.6.2.
Witterungsgeführte Vorlauftemperaturregelung
Wenn die witterungsgeführte Vorlauftemperaturregelung aktiv ist, wird die Vorlauftemperatur (Parameter [Vorlauftemperatur Soll]) au­tomatisch, abhängig von der Außentemperatur nach der eingestell­ten Heiz-/Kühlkurve bestimmt.
Im Auslieferungszustand ist diese Funktion aktiviert. Sie kann nur mit Fachmanncode deaktiviert (Festwertregelung) oder wieder akti­viert werden.
Ist zusätzlich der Raumregler (EHS157034) an die RoCon+ HP an­geschlossen, werden die Solltemperaturen witterungs- und raum­temperaturgeführt (Parameter [Raumeinfluss]) geregelt.
Die Einstellung dieser Funktion kann nur mit Fachmanncode vorge­nommen werden. Kontaktieren Sie hierzu Ihren Heizungsfachmann.
Die Aktivierung bzw. Deaktivierung dieser Funktion erfolgt über den Parameter [Witterungsgeführt] im Menü "Konfiguration".
▪ Parameter [Witterungsgeführt] = Witterungsgeführt: Witterungsge-
führte Vorlauftemperaturregelung
▪ Parameter [Witterungsgeführt] = Vorlauftemperatur fix: Regelung
nach fester Solltemperatur ▪ Bei Heizbetrieb: Parameter [Vorlauftemperatur Heizbetrieb]
oder Parameter [Vorlauftemperatur Absenkbetrieb]
▪ Bei Kühlbetrieb: Parameter [Vorlauftemperatur Kühlbetrieb]
INFORMATION
Die witterungsgeführte Vorlauftemperaturregelung hat kei­nen Einfluss auf die Vorlauf-Solltemperatur bei einer Anfor­derung des Warmwasserkreises.
Bei angeschlossenen Mischermodul
Die Einstellung der Heiz-/Kühlkurve und die Aktivierung der witte­rungsgeführten Vorlauftemperaturregelung für den zugeordneten Heizkreis erfolgen in gleicher Weise, wie zuvor beschrieben.
Es besteht die Möglichkeit den zugeordneten Heizkreis zu betreiben als
▪ Mischererweiterung
Dem Mischermodul wird die Außentemperatur des an der Daikin Altherma ETS(X/H) angeschlossenen Außentemperaturfühlers
über den CAN-Bus übermittelt. oder als ▪ Mischererweiterung mit Zonenregelung
Am Mischermodul muss ein separater Außentemperaturfühler an-
geschlossen werden. Der zugeordnete Heizkreis wird nach der,
für diese Zone relevanten Außentemperatur geregelt. Mit aktivierter Terminalfunktion kann das Mischermodul über das Be-
dienteil RoCon+ B1 der Daikin Altherma ETS(X/H) bedient und die Einstellungen für den zugeordneten Heizkreis vorgenommen wer­den.
In Verbindung mit dem Raumregler EHS157034 kann das Mischer­modul den zugeordneten Heizkreis auch völlig selbstständig und un­abhängig vom Wärmeerzeuger regeln.
Weiterführende Erklärungen und mögliche Einstellwerte zu diesem Menü finden Sie in Kap. 7.6.
Frostschutzfunktion
Bei einer Außentemperatur unterhalb des Parameterwerts [Frost­schutztemperatur], wird die integrierte Heizungsumwälzpumpe ein­geschaltet, um ein Einfrieren der Heizungsanlage zu verhindern.
Außerdem werden auch die Vorlauf-, Speicher- und angeschlossene Raumtemperatursensoren ständig überwacht. Sinkt an einem dieser Sensoren die gemessene Temperatur unter 7°C (bei Raumtempera­tur unter 5°C), wird die Frostschutzfunktion ebenfalls aktiviert.
Sinkt die Temperatur Heizung Vorlauf unter 7°C, heizt die Daikin Alt­herma ETS(X/H) so lange, bis die Temperatur Heizung Vorlauf min­destens 12°C erreicht.
Die Funktion wird beendet, wenn die Außentemperatur über den ein­gestellten Parameterwert [Frostschutztemperatur] + 1K steigt und auch keine andere Aktivierungsbedingung vorliegt.
INFORMATION
Sind Niedertarif-Funktionen aktiviert; Parameter [HT/NT Funktion] = Alles ausschalten oder Parameter [Smart Grid] = Ein kann der Betrieb der Wärmepumpe vom Energieversor-
gungsunternehmen für einen begrenzten Zeitraum kom­plett abgeschaltet werden. In diesen Fällen kann auch bei Frostschutzbedingungen nicht nachgeheizt werden und die geräteinterne Heizungsumwälzpumpe wird nicht einge­schaltet.
Diese Situationen sind erkennbar, wenn im Menü [→Hauptmenü →Info →Übersicht] beim Betriebsdaten­feld: "Ext" der Wert "Hochtarif" oder "SG1" angezeigt wird.
4.5.4 Heizen
[→Hauptmenü →Konfiguration →Heizen] In diesem Menü werden Heizzeiten und Soll-Vorlauftemperaturen für
den Heizbetrieb konfiguriert.
Betriebsanleitung
74
Daikin Regelung RoCon+ HP1
Daikin RoCon+ HP
008.1447899_00 – 09/2019 – DE
Page 75
Heizkurve
WARNUNG: ENTFLAMMBARES MATERIAL
Im Störfall könnte durch Überhitzung die Fußbodenhei­zungsanlage, der Estrich bzw. der Fußbodenaufbau be­schädigt werden.
▪ Vor Erstinbetriebnahme die Maximaltemperaturbegren-
zung in der Regelung RoCon+ HP (Parameter [Max. Vorlauftemperatur]) vor Beginn der Emissionsmessung auf die maximal zulässige Anlagentemperatur einstel­len.
▪ Überhitzungsschutzschalter (bauseits) an den Stecker-
anschluss "Ext" zur externen Betriebsartenumschaltung so anschließen, dass die Daikin Altherma ETS(X/H) in die Betriebsart "Bereitschaft" oder "Sommer" geschaltet wird. Bei Parameter [Raumthermostat] = Ja oder Para­meter [Interlinkfunktion] = Ein muss der Überhitzungs­schutzschalter so angeschlossen werden, dass der Schaltkontakt des Raumthermostats unterbrochen wird.
▪ Wird die Fußbodenheizung auch zur Raumkühlung ver-
wendet, gelten die Anschlusshinweise im vorher aufge­führten Punkt auch für den Anschluss eines bauseiti­gen Feuchteschutzschalters.
Mit der Heizkurve wird die Vorlauftemperatur abhängig von der je­weiligen Außentemperatur an die Gebäudebeschaffenheit angepasst (witterungsgeführte Vorlauftemperaturregelung siehe Kap. 4.5). Die Steilheit der Heizkurve beschreibt allgemein das Verhältnis von Vor­lauftemperaturänderung zu Außentemperaturänderung.
Die Heizkurve gilt innerhalb der Grenzen für Minimal- und Maximal­temperatur, die für den jeweiligen Heizkreis eingestellt wurden. Zwi­schen der gemessenen Raumtemperatur im Aufenthaltsbereich und der jeweils gewünschten Raumtemperatur können Abweichungen auftreten, die sich durch den Einbau eines Raumthermostats oder eines Raumreglers minimieren lassen.
Die Regelung ist werksseitig so eingestellt, dass sich die Heizkur- ve beim Betrieb nicht selbstständig anpasst.
Die automatische Heizkurvenanpassung kann aktiviert werden (Parameter [Heizkurvenadaption]), wenn der Außentemperaturfüh- ler und der Raumregler (EHS157034) angeschlossenen sind (sie­he Kap. 4.5).
Startbedingungen für die automatische Heizkurvenanpassung: ▪ Außentemperatur <8°C ▪ Betriebsart ist [Automatik 1] oder [Automatik 2] ▪ Dauer der Absenkphase mindestens 6h Ist keine automatische Heizkurvenanpassung aktiviert, kann die
Heizkurve manuell durch Verstellen des Parameters [Heizkurve] eingestellt werden.
INFORMATION: HEIZKURVE MANUELL ANPASSEN
Nehmen Sie Korrekturen der eingestellten Werte erst nach 1-2 Tagen und nur in kleineren Schritten vor.
▪ Fremdwärmequellen deaktivieren (z.B. Kaminöfen, di-
rekte Sonneneinstrahlung, geöffnete Fenster).
▪ Vorhandene Heizkörperthermostatventile oder Stellan-
triebe vollständig öffnen.
▪ Betriebsart "Heizen" aktivieren. Anhaltswerte für die
Einstellung sind:
Heizkörper: 1,4 bis 1,6.
Fußbodenheizung: 0,5 bis 0,9.
4 Funktion
Bild17-2 Heizkurven
TAAußentemperatur TRRaumtemperatur-Sollwert
TVVorlauftemperatur
Comfort Heating
Kann die Wärmepumpe den Heizbedarf bei sehr niedrigen Außen­temperaturen nicht decken, wird Wärme aus dem Speicher entnom­men und für die Raumheizung genutzt. In seltenen Fällen (in Syste­men mit hohen benötigten Vorlauftemperaturen und niedrigen benö­tigten Warmwassertemperaturen) kann die erforderliche Vorlauftem­peratur höher sein als die eingestellte Speichertemperatur. Um für diese Systeme kurzfristige Komforteinbußen im Heizbetrieb zu ver­meiden, kann der Parameter [Comfort Heating] auf "Ein" gestellt werden. Bei entsprechenden Außentemperaturen wird die Speicher­temperatur über die für den Warmwasserbedarf eingestellte Spei­chertemperatur angehoben.
INFORMATION
Wird [Comfort Heating] auf "Ein" gesetzt, erhöht sich gege­benenfalls der Stromverbrauch der Wärmepumpe. In der Standardeinstellung ist [Comfort Heating] auf "Aus" ge­setzt.
Weiterführende Erklärungen und mögliche Einstellwerte zu dieser Funktion finden Sie in Kap. 7.6.
4.5.5 Kühlen
[→Hauptmenü →Konfiguration →Kühlen] In diesem Menü werden Einstellungen für den Kühlbetrieb vorge-
nommen.
ACHTUNG: KONDENSATIONSGEFAHR
Im Störfall oder bei falscher Einstellung der Parameter könnte durch Kondensation die Fußbodenheizung, der Estrich bzw. der Fußbodenaufbau beschädigt werden.
▪ Vor Erstinbetriebnahme und Aktivierung des Kühlbe-
triebes, die Minimaltemperaturbegrenzung in der Rege­lung RoCon (Parameter [Untergrenze Vorlauftempera­tur]) auf die minimal zulässige Anlagentemperatur ein­stellen.
Voraussetzungen für den Kühlbetrieb: ▪ Außentemperatur > Einstellwert der Raum-Solltemperatur ▪ Außentemperatur > Einstellwert des Parameters [Start Kühlen A-
Temp]
Daikin RoCon+ HP Daikin Regelung RoCon+ HP1
008.1447899_00 – 09/2019 – DE
Betriebsanleitung
75
Page 76
4 Funktion
▪ Betriebsart [Kühlen] aktiviert.
▪ über Menü "Betriebsart" oder ▪ über Raumthermostat-Funktion (Schaltkontakt Kühlen ge-
schlossen)
▪ Keine Wärmeanforderung im RoCon-System der Heizungsanlage
aktiv
INFORMATION
Sinkt die mittlere Außentemperatur bei aktiver Betriebsart "Kühlen" unter 4°C, schaltet die Betriebsart automatisch auf "Heizen" um.
Eine erneute automatische Umschaltung der Betriebsart auf "Kühlen" erfolgt nur dann:
▪ wenn ein Raumthermostat am Steckeranschluss J16
(Kühlen) angeschlossen ist und
▪ der Schaltkontakt des Raumthermostats geschlossen
ist und
▪ die mittlere Außentemperatur wieder über 10°C steigt.
Kühlkurve
[→Hauptmenü →Konfiguration →Kühlen→Kühlkurve] Die Kühlkurve bestimmt die Vorlauf-Solltemperatur im Kühlbetrieb
abhängig von der jeweiligen Außentemperatur. (Witterungsgeführte Vorlauftemperaturregelung, siehe Kap. 4.5.3). Wärmere Außentem­peraturen resultieren in einer kälteren Vorlauf-Solltemperatur und umgekehrt. Die Kühlkurve kann durch vier Parameter an die Gebäu­debeschaffenheit angepasst werden (Siehe Bild 17-3).
1 [Start Kühlen A-Temp] 2 [Max. Kühlen A-Temp] 3 [VL-Soll Start Kühlen] 4 [VL-Soll Max Kühlen]
Kühlparameter
[→Hauptmenü →Konfiguration →Kühlen→Parameter] Dieses Menü beinhaltet weitere Parameter zur Anpassung der Vor-
lauf-Solltemperatur im Kühlbetrieb. Während der witterungsgeführten Vorlauftemperaturregelung kann
der Benutzer die Vorlauf-Solltemperatur durch den Parameter [Kühl­sollwert Korrektur] maximal um 5K nach oben oder unten verstellen. Nach unten ist die Temperatur durch den Parameter [Untergrenze Vorlauftemperatur] begrenzt.
INFORMATION
Sind im System optionale Frostschutz-Ventile verbaut, darf der Parameter [Untergrenze Vorlauftemperatur] nicht unter 7°C eingestellt werden.
TVVorlauftemperatur
------- Kühlkurve
- - - - mögliche Parallelverschiebung der Kühlkurve
Weiterführende Erklärungen und mögliche Einstellwerte zu den Pa­rametern in diesem Menü finden Sie in Kap. 7.6.4.
4.5.6 Warmwasser
[→Hauptmenü →Konfiguration →WW] In diesem Menü kann die Warmwasserbereitung individuell an Ver-
halten und Bedarf der Nutzer angepasst werden. Damit kann der Energieverbrauch minimiert und der Komfort erhöht werden.
Solarfunktion
Die [Solar Funktion] dient zum Herabsetzen der Solltemperatur des Warmwasserspeichers, um den Ertrag einer angeschlossenen So­laranlage zu erhöhen. Der Sollwert der Warmwassertemperatur wird hierbei in Abhängigkeit der Außentemperatur und unter Einhaltung der Sicherheitsfunktionen eingestellt. Zudem werden folgende Para­meter festgelegt: Warmwasser Hysterese = 5K; Gebäudedämmung = Normal
Um die Solarfunktion zu aktivieren, muss diese im Menü [→Haupt­menü →Konfiguration →WW →Solar Funktion] auf "Ein" gestellt werden und der Schaltkontakt EXT (J8) geschlossen sein.
Einstellungen für optionale Zirkulationspumpe
Abhängig vom Parameter [Zirkulationspumpe Ansteuerung] kann ei­ne optionale Zirkulationspumpe synchron mit dem gewählten Zeit­programm für die Warmwasserbereitung oder mit dem Zeitpro­gramm für die Zirkulationspumpe angesteuert werden (Siehe
Kap. 4.3). Während der Freigabezeiten des gewählten Zeitpro-
gramms kann die Zirkulationspumpe entweder kontinuierlich oder getaktet betrieben werden. Dies wird mit dem Parameter [Zirkulati­onspumpe Intervall] festgelegt.
Legionellenschutz
Diese Funktion dient zur Vorbeugung einer bakteriellen Verkeimung im Warmwasserspeicher durch thermische Desinfektion. Dazu wird der Warmwasserspeicher abhängig vom Parameter [Antilegionellen Tag] 1× täglich oder 1× wöchentlich auf die Desinfektionstemperatur [Antilegionellen Temperatur] aufgeheizt. Die Desinfektion beginnt zur festgelegten Startzeit [Antilegionellen Startzeit] und ist für eine Stun­de aktiv. Eine optional angeschlossene Zirkulationspumpe wird wäh­rend dieser Zeit automatisch mit eingeschaltet.
Weiterführende Erklärungen und mögliche Einstellwerte zu dieser Funktion finden Sie in Kap. 7.6.5.
4.5.7 Zusatzprogramm
[→Hauptmenü →Konfiguration →Zusatz] In diesem Menü finden sich Programme, welche die Inbetriebnahme
der Anlage erleichtern.
Bild17-3 Parameterabhängigkeit Kühlkurve
1 Parameter [Start Kühlen A-Temp] 2 Parameter [Max. Kühlen A-Temp] 3 Parameter [VL-Soll Start Kühlen] 4 Parameter [VL-Soll Max Kühlen] 5 Parameter [Untergrenze Vorlauftemperatur] 6 Raum-Solltemperatur 7 Kühlbetrieb möglich
TAAußentemperatur
Betriebsanleitung
76
Entlüftungsfunktion
[→Hauptmenü →Konfiguration →Zusatz →Entlüftung] Durch Aktivieren der Entlüftungsfunktion startet die Regelung ein
fest definiertes Ablaufprogramm mit Start-Stopp-Betrieb der inte­grierten Heizungsumwälzpumpe sowie verschiedenen Stellungen der integrierten 3-Wege-Umschaltventile. Vorhandene Luft kann während der Funktion über das automatische Entlüftungsventil aus­treten.
Daikin RoCon+ HP
Daikin Regelung RoCon+ HP1
008.1447899_00 – 09/2019 – DE
Page 77
4 Funktion
INFORMATION
Die Aktivierung dieser Funktion ersetzt nicht das korrekte Entlüften des Heizkreislaufs.
Vor Aktivierung dieser Funktion muss der Heizkreislauf vollständig befüllt sein.
Relaistest
[→Hauptmenü →Konfiguration →Zusatz →Relaistest] Dieses Programm erlaubt es, interne Schaltrelais zu prüfen. Dies
kann bei Störungen, Fehlermeldungen oder im Rahmen der jährli­chen Wartung erforderlich sein. Wird das Menü geöffnet, werden alle Relais deaktiviert. Durch die Auswahl einzelner oder mehrerer Re­lais werden diese aktiviert. Bei Verlassen des Menüs werden alle Relaistests beendet.
Die Bedienung des Relaistest-Menüs erfolgt analog zur Auswahl von Listeneinträgen (Siehe Kap. 3.3.3). Allerdings können in der Relais­Liste mehrere Relais parallel zum Testen aktiviert werden. Dazu wird das entsprechende Relais mit "OK" gewählt. Aktivierte Relais wer­den durch einen Haken angezeigt.
Estrichtrocknung
[→Hauptmenü →Konfiguration →Zusatz →Estrich] In diesem Menü wird die Estrichtrocknung entsprechend den Einstel-
lungen im [Estrichprogramm] gestartet. Das Programm dient aus­schließlich zur vorgeschriebenen Trocknung von neu erstelltem Estrich bei Fußbodenheizungen. Der erste Tag des Estrichpro­gramms beginnt nach Aktivierung des Programms am Tageswech­sel um 00:00 Uhr.
Die Estrichtrocknung ist eine Sonderfunktion und wird durch keine andere Betriebsart unterbrochen. Es ist nur vom Heizungsfachmann für den Direktheizkreis und/oder optional angeschlossene gemischte Heizkreise aktivierbar. Es muss für jeden Heizkreis separat aktiviert werden.
INFORMATION
Vor Start der Estrichtrocknung müssen die Parameter [Raumthermostat] und [Interlinkfunktion] deaktiviert sein. Bei kurzzeitigem Stromausfall wird eine zuvor aktivierte Estrichtrocknung an der Stelle des Abbruchs fortgesetzt.
Nach der Aktivierung der Estrichtrocknung werden sämtliche witte­rungsgeführten Regelfunktionen des entsprechenden Heizkreises ausgeschaltet. Der entsprechende Heizkreis arbeitet unabhängig von Betriebsart und Schaltzeiten als Konstanttemperaturregler.
Eine bereits gestartete Estrichtrocknung lässt sich jederzeit deakti­vieren. Nach Beenden der Estrichtrocknung wird der Parameter au­tomatisch auf "Aus" gestellt und der Heizkreis arbeitet wieder nach der aktuell eingestellten Betriebsart.
Estrichprogramm
[→Hauptmenü →Konfiguration →Zusatz →Programm] Dieses Menü erlaubt die individuelle Anpassung der werkseitigen
Einstellungen für Dauer und Vorlauf-Solltemperaturen der Estricht­rocknung. Änderungen können nur nach Eingabe des Fachmannco­des durchgeführt werden.
Estrichprogramm ändern
Für eine Dauer von maximal 28 Tagen kann für jeden Tag eine eige­ne Vorlauf-Solltemperatur eingestellt werden. Das Ende des Estrich­programms wird durch den 1. Tag ohne vorgegebene Vorlauf-Soll­temperatur definiert.
Tag Werkseinstellung Tag Werkseinstellung
1 - 3 25°C 10 - 19 55°C 4 - 7 55°C 20 40°C
8 25°C 21 25°C 9 40°C 22 - 26 -
Tab.17-5 Voreinstellungen Estrichprogramm
Bild17-4 Estrichprogramm ändern
Beispiel: Vorlauftemperatur des 3. Tages auf 40°C erhöhen und Programm am 8. Tag beenden [→Hauptmenü →Konfiguration →Zusatz →Programm]:
1 Drehtaster im Uhrzeigersinn drehen, bis die Tagesauswahl auf
3. steht.
2 Drehtaster kurz antippen zum Bestätigen ("OK").
è Temperaturfeld wird blau dargestellt
3 Drehtaster im Uhrzeigersinn drehen, bis die Temperaturauswahl
auf 40°C steht
4 Drehtaster kurz antippen zum Bestätigen ("OK").
è Temperaturauswahl des nächsten Tages wird blau darge-
stellt
5 Drehtaster mehrmals kurz antippen, bis die Tagesauswahl auf 8.
steht.
6 Drehtaster gegen den Uhrzeigersinn drehen, bis die Tempera-
turauswahl auf "Aus" steht.
7 Drehtaster kurz antippen zum Bestätigen ("OK").
è Tag 8 bis Tag 28 sind auf "Aus" gestellt, Bestätigen-Icon
wird blau dargestellt
8 Drehtaster kurz antippen zum Bestätigen ("OK").
è Programmierung wird gespeichert und Menü verlassen.
Typische Estrichprogramme Funktionsheizen
Das Funktionsheizen dient als Nachweis der Erstellung eines man­gelfreien Werks für den Heizungsbauer. Ein vorgefertigtes, auf Fuß­bodenheizungen bezogenes Aufheizprotokoll finden Sie im Internet­portal vom Hersteller.
Das Funktionsheizen (identisch mit "Aufheizen" in EN1264, Ab­schnitt5.2) gilt in diesem Sinne nicht als Aufheizvorgang zum Errei­chen der Belegreife. Dazu ist üblicherweise ein gesondertes Bele­greifheizen und/oder eine mechanische Trocknung erforderlich.
Das Aufheizen bei Zementestrichen sollte frühestens nach 21 Tagen und bei Anhydritestrichen nach Angaben des Herstellers frühestens nach 7 Tagen erfolgen. Das erste Aufheizen beginnt mit einer Vor­lauftemperatur von 25°C, die 3 Tage zu halten ist. Danach wird mit der für den Heizkreis eingestellten, maximalen Vorlauftemperatur (auf max. 55°C begrenzt) geheizt, welche weitere 4 Tage gehalten wird.
Daikin RoCon+ HP Daikin Regelung RoCon+ HP1
008.1447899_00 – 09/2019 – DE
Betriebsanleitung
77
Page 78
4 Funktion
Nach dem beschriebenen Aufheizvorgang ist noch nicht sicherge­stellt, dass der Estrich den für die Belegreife erforderlichen Feuchtig­keitsgehalt erreicht hat.
Der Feuchtigkeitsgehalt im Estrich muss vor dem Verlegen des Oberbelags durch Messung überprüft werden.
INFORMATION
Verfahrensweise gemäß EN1264 Teil4: Die Heizkreise sind nach Fertigstellung bei Anhydrit- und
Zementestrichen durch eine Wasserdruckprobe auf ihre Dichtheit zu prüfen. Die Dichtheit muss unmittelbar vor und während der Estrichverlegung sichergestellt sein. Die Hö­he des Prüfdrucks beträgt mindestens das 1,3-Fache des maximal zulässigen Betriebsdrucks.
Bei Einfriergefahr sind geeignete Maßnahmen zu treffen, z.B. Verwendung von Frostschutzmitteln oder Temperie­ren des Gebäudes. Sofern für den bestimmungsgemäßen Betrieb der Anlage kein Frostschutzmittel mehr erforderlich ist, ist das Frostschutzmittel durch Entleeren und Spülen der Anlage mit mindestens 3-fachem Wasserwechsel zu entfernen.
Weiterführende Erklärungen und mögliche Einstellwerte zu dieser Funktion finden Sie in Kap. 7.6.
4.5.8 Configuration Wizard
[→Hauptmenü →Konfiguration →Wizard] In diesem Menü sind die im Configuration Wizard abgefragten Para-
meter zusammengefasst. Dies erlaubt eine schnelle Anpassung der Systemeinstellung. Siehe Kap. 5.1.
4.5.9 Parameter Reset
[→Hauptmenü →Konfiguration →Parameter Reset] In diesem Menü können alle kundenspezifischen Parametereinstel-
lungen auf Werkseinstellung zurückgesetzt werden. Dies kann zweckdienlich sein, wenn die Daikin Altherma ETS(X/H) nicht mehr ordnungsgemäß funktioniert und keine anderen Ursachen für das Fehlverhalten feststellbar sind.

4.6 Info

[→Hauptmenü →Info] In diesem Menü werden alle Anlagentemperaturen, der Wärmeer-
zeugertyp, diverse Softwareinformationen sowie die Betriebszustän­de aller Anlagenkomponenten angezeigt. Die Anzahl der angezeig­ten Parameter ist abhängig von den angeschlossenen Komponen­ten. Es können keine Einstellungen an diesen Werten vorgenommen werden.
Bild17-5 Zeitlicher Ablauf des Estrichprogramms beim Funktions-
heizen
t1Starttemperatur 25°C t2Maximale Heizkreistemperatur
TVVorlauftemperatur
Z Dauer der Estrichfunktion in Tagen nach Funktionsstart
Belegreifheizen
Der Austrocknungsverlauf für den Estrich ist nicht genau vorherzu­sagen. Bei hoher Luftfeuchtigkeit kommt er unter Umständen ganz zum Erliegen. Eine Beschleunigung des Austrocknungsvorgangs kann durch den Betrieb der Fußbodenheizung (Belegreifheizen) oder Maßnahmen wie das mechanische Trocknen erreicht werden.
Jedes Belegreifheizen ist als extra Leistung nach VOB, gesondert durch den Bauherrn zu beauftragen. Die Belegreife ist Vorausset­zung für den Beginn der Arbeiten des Oberbodenlegers, damit er ein mangelfreies Werk erstellen kann.
Mit Standardeinstellungen kann das kombinierte Funktions- und Be­legreifheizprogramm aktiviert werden, um eine für die Belegreife er­forderliche Restfeuchtigkeit des Estrichs zu erreichen (siehe
Bild 17-6). Die Restfeuchte des Estrichs ist jedoch grundsätzlich
messtechnisch zu überprüfen, bevor ein Bodenbelag verlegt wird.
4.6.1 Aktuell
[→Hauptmenü →Info →Aktuell] Dieses Menü zeigt das Hydraulikschema des Systems. Auf der ers-
ten und zweiten Seite sind Sensoren und die zugeordneten, aktuel­len Werte dargestellt. Auf der dritten Seite sind Verdichter, Pumpe und Heizstab weiß dargestellt, wenn sie inaktiv sind, und blau, wenn sie aktiv sind. Für die beiden Mischventile wird die aktuelle Ventil­stellung gezeigt.
Bild17-7 Hydraulikschaltbild - Erste Seite
Bild17-6 Zeitlicher Ablauf des Estrichprogramms beim kombinier-
ten Funktions- und Belegreifheizen (Legende siehe
Bild 17-5)
Betriebsanleitung
78
Daikin Regelung RoCon+ HP1
Daikin RoCon+ HP
008.1447899_00 – 09/2019 – DE
Page 79
Bild17-8 Hydraulikschaltbild - Zweite Seite
Pos. Bezeichnung
t-AU Außentemperaturfühler P Druck V Volumenstrom t-R Temperatur Heizung Rücklauf t-V,BH Temperatur Heizung Vorlauf ggf. nach Heizungsunter-
stützungswärmetauscher t-liq Kältemitteltemperatur t-V Vorlauftemperatur nach dem Plattenwärmetauscher t-DHW Temperatur im Warmwasserspeicher B1 Aktuelle Stellung der Mischventils 3UVB1 (0%:Heiz-
netz; 100%:Interner Bypass) DHW Aktuelle Stellung des Mischventils 3UV DHW (0%:Heiz-
netz; 100%:Warmwasserspeicher)
Tab.17-6 Legende zu den Hydraulikschaltbildern
4.6.2 Übersicht
[→Hauptmenü →Info →Übersicht] In diesem Menü werden aktuelle Betriebszustände der Wärmepum-
pe und ihrer Komponenten aufgelistet. Weiterführende Erklärungen zu den Parametern in diesem Menü fin-
den Sie in Kap. 7.7.
4 Funktion
4.6.3 Werte
[→Hauptmenü →Info →Werte] In diesem Menü werden aktuelle Soll- und Ist-Werte aufgelistet. Weiterführende Erklärungen zu den Parametern in diesem Menü fin-
den Sie in Kap. 7.7.
4.6.4 Wasserdruck
[→Hauptmenü →Info →Wasserdruck] In diesem Menü wird der aktuelle Wasserdruck in großer Schrift dar-
gestellt. Dies erleichtert das Ablesen während der Installation der Anlage.

4.7 Fehler

[→Hauptmenü →Fehler] In diesem Menü findet die Fehlerbehandlung der Daikin Altherma
ETS(X/H) statt. Siehe Kap. 8.

4.8 Terminal

[→Hauptmenü →Terminal] In diesem Menü können auch andere, im RoCon-System über den
CAN-Bus integrierte Geräte (Regelungskomponenten Mischermodul oder Wärmeerzeuger) bedient und parametriert werden, sofern das jeweilige Bedienteil die erforderliche Berechtigung besitzt.
Funktionelle Kennungen
Das RoCon-System bietet sehr viele Anwendungs- und Erweite­rungsmöglichkeiten. Die einzelnen RoCon-Systemkomponenten kommunizieren über den CAN-Datenbus miteinander. Dazu sind die Schaltplatinen RoCon BM2C und die Bedienteile RoCon+ B1 der Daikin Altherma ETS(X/H), sowie ggf. die optionalen Systemkompo­nenten Raumstation EHS157034 und Mischermodul EHS157068 über Datenbusleitungen miteinander verbunden. Diesen System­komponenten müssen eindeutige funktionelle Kennungen zugewie­sen werden, damit der Datenaustausch und die Zuordnung innerhalb des RoCon-Systems reibungslos funktionieren.
Die Zuordnung der funktionellen Kennungen erfolgt am einfachsten über den Configuration Wizard. Dieser wird bei der ersten Inbetrieb­nahme automatisch ausgeführt, oder kann bei Erweiterungen in der Heizungsanlage in [→Hauptmenü →Konfiguration →Wizard] ma­nuell gestartet werden. Zusätzlich können die meisten Kennungen auch durch Parametereinstellungen in diesem Menü an das RoCon­System angepasst werden.
Kennung / Funktion Systemkomponente Parameter Bemerkungen
Heizkreiskennung Eindeutige Nummerierung eines Heiz-
kreises der Heizungsanlage im RoCon­System. Maximal 16 Heizkreise können geregelt werden.
(1)
Maximal 8 Wärmeerzeuger können im RoCon-System über den CAN-Datenbus verbunden sein. Mehrere in die Heizungsanlage eingebundene Wärmeerzeuger sind als Sonderanwendung zu betrachten. Ggf. Servicefachmann kontaktieren.
Daikin RoCon+ HP Daikin Regelung RoCon+ HP1
008.1447899_00 – 09/2019 – DE
Daikin Altherma ETS(X/H)
(RoCon BM2C)
Raumstation EHS157034 [Heizkreis Zuordnung]
Mischermodul EHS157068 [Heizkreis Zuordnung]
[KonfigDirekt-Kreis]
siehe Kap. 7.11
siehe Anleitung RoCon
U1/M1
siehe Anleitung RoCon
U1/M1
Werkseinstellung = 0 Sollte normalerweise nicht verändert werden.
(1)
Werkseinstellung = Aus Anpassung erforderlich, wenn unterschiedli-
che Heizkreise im System sind und / oder der Parameter [Master-RoCon] = Ein
Werkseinstellung = Aus Muss grundsätzlich auf die Einstellung des
Adressschalters angepasst werden.
Betriebsanleitung
79
Page 80
4 Funktion
Kennung / Funktion Systemkomponente Parameter Bemerkungen
Wärmeerzeugerkennung Eindeutige Nummerierung eines Wär-
meerzeugers im RoCon-System.
(1)
Terminalkennung Eindeutige Nummerierung eines Be-
dienteils RoCon+ B1 oder EHS157034, von dem aus ein Wärmeerzeuger und / oder ein Mischermodul im RoCon-Sys­tem fernbedient werden kann.
Bis zu 10 Bedienteilen im RoCon-Sys­tem kann die Berechtigung zur Fernbe­dienung vergeben werden. Soll eine Fernbedienung im RoCon-System mög­lich sein, muss einem Bedienteil die Kennung "0" zugewiesen sein.
Gerätekennung Eindeutige Nummerierung eines Wär-
meerzeugers oder Mischermoduls im RoCon-System.
Bis zu 16 Gerätenummern können ver­geben werden.
Diese Gerätenummern werden bei ei­nem [Bus-Scan] erkannt und zu Identifi­kation eines fernbedienten Geräts ange­zeigt.
Tab.17-7 Funktionelle Kennungen im RoCon-System
Daikin Altherma ETS(X/H)
(RoCon BM2C)
[Buskennung-WEZ]
siehe Kap. 7.11
Mischermodul EHS157068 [WE Zuordnung]
siehe Anleitung RoCon
U1/M1
Daikin Altherma ETS(X/H)
(RoCon BM2C)
[Terminaladresse]
siehe Kap. 7.9
Raumstation EHS157034 [Terminaladresse]
siehe Kap. 7.9
Daikin Altherma ETS(X/H)
(RoCon BM2C)
[Buskennung-WEZ]
siehe Kap. 7.11
Mischermodul EHS157068 [Heizkreis Zuordnung]
siehe Kap. 9
Werkseinstellung = 0 Sollte normalerweise nicht verändert werden.
(1)
Werkseinstellung = 0 Sollte normalerweise nicht verändert werden.
(1)
Definiert den Wärmeerzeuger, der den zuge­ordneten Heizkreis mit Wärme versorgt.
Werkseinstellung = Aus Wert sollte auf "0" eingestellt werden, wenn
mindestens 1 Mischermodul im RoCon-Sys­tem angeschlossen ist und der Mischerkreis vom Wärmeerzeuger aus bedienbar sein soll.
Werkseinstellung = Aus Wert muss auf einen im RoCon-System ein-
deutigen numerischen Wert eingestellt wer­den, wenn mit der Raumstation Systemkom­ponenten mit einer gültigen Gerätekennung fernbedienbar sein sollen.
Identisch mit Wärmeerzeugerkennung. Wert darf nicht gleich sein wie die Heizkreis-
kennung eines Mischermoduls im RoCon-Sys­tem.
Identisch mit Heizkreiskennung. Wert darf nicht gleich sein wie die Wärmeer-
zeugerkennung eines Wärmeerzeugers im RoCon-System.
Wert muss gleich sein wie die Einstellung des Adressschalters.
4.8.1 Terminaladresse auswählen
[→Hauptmenü →Terminal →Adresse] Einstellen der Terminalkennung des Bedienteils für den Systemzu-
griff. Der eingestellte Wert muss im gesamten System eindeutig sein. Eine Bestätigung dieses Parameters mit dem Drehtaster be­wirkt eine neue Initialisierung der Regelung.
Alle Einstellungen, außer "Aus", ermächtigen den Benutzer des Be­dienteils, die Terminalfunktion zu aktivieren und damit alle RoCon­Systemkomponenten mit einer gültigen Gerätekennung zu bedienen.
4.8.2 Bus-Scan für Terminalfunktion
[→Hauptmenü →Terminal →Bus-Scan] Nach Aktivierung des "Bus-Scan" wird im Menü [→Hauptmenü
→Terminal] eine Liste der erkannten Geräte (mit zugewiesener Ter­minaladresse) zur Auswahl angezeigt. Nach Auswahl und Bestäti­gung eines externen Geräts wird die Terminalfunktion für dieses Ge­rät aktiviert. Das Bedienteil befindet sich dann im Terminalbetrieb.
Das lokale Bedienteil wirkt als Fernbedienung für das externe Gerät und im Display wird der zugehörige Startbildschirm dargestellt. Da­bei werden alle Bedienfunktionen 1:1, wie am externen Gerät ausge­führt und abgespeichert. Die angezeigten Werte und Symbole wer­den immer vom ausgewählten Gerät übernommen.
Zur Bedienung des lokalen Geräts muss auf den Startbildschirm des externen Geräts gewechselt werden. Durch langes Drücken des Drehtasters kann dann zurück in das Menü des lokalen Geräts ge­wechselt werden.
INFORMATION
Um den Bus-Scan durchzuführen, muss dem Bedienteil RoCon+ B1 der Daikin Altherma ETS(X/H) oder der Raum­station EHS157034 eine gültige Terminaladresse zugewie­sen werden. Dies kann nur mit Fachmanncode vorgenom­men werden. Kontaktieren Sie hierzu Ihren Heizungsfach­mann.
Wenn die Terminalfunktion in der Heizungsanlage genutzt werden soll, muss einem Bedienteil die Terminalkennung = 0 zugewiesen werden.
Beispiel: Terminalbetrieb für den Wärmeerzeuger mit Buskennung 2 aktivieren [→Hauptmenü →Terminal →Bus-Scan]:
Bus - Scan wird durchgeführt. Die Übersicht aller gefundenen Gerä­te wird angezeigt.
1 Drehtaster im Uhrzeigersinn drehen, bis Regler BM1/BE1 #2
blau dargestellt wird.
2 Drehtaster kurz antippen zum Bestätigen ("OK").
è Das lokale Bedienteil wirkt als Fernbedienung für den Wär-
meerzeuger mit Buskennung 2.
Um den Terminalbetrieb zu beenden und das Bedienteil wieder zur Bedienung des zugeordneten Geräts umzuschalten, muss auf den Startbildschirm des externen Geräts gewechselt werden. Durch lan­ges Drücken des Drehtasters kann dann zurück in das Menü des lo­kalen Geräts gewechselt werden.
Betriebsanleitung
80
(1)
Maximal 8 Wärmeerzeuger können im RoCon-System über den CAN-Datenbus verbunden sein. Mehrere in die Heizungsanlage
eingebundene Wärmeerzeuger sind als Sonderanwendung zu betrachten. Ggf. Servicefachmann kontaktieren.
Daikin Regelung RoCon+ HP1
008.1447899_00 – 09/2019 – DE
Daikin RoCon+ HP
Page 81
INFORMATION
Wird das lokale Bedienteil als Fernbedienung für ein Mi­schermodul genutzt, ist sowohl der Standardbildschirm als auch die Menüstruktur geändert (siehe Kap. 9).

4.9 Statistik

INFORMATION
Bei den in diesem Menü aufgeführten Angaben handelt es sich um Näherungswerte. Insbesondere, wenn Glykol im System enthalten ist, kann es zu stärkeren Abweichungen gegenüber realen Leistungsdaten kommen.
[→Hauptmenü →Statistik] In diesem Menü können Werte zur Leistungsabgabe und Laufzeiten
der Wärmepumpe und ihrer Komponenten abgerufen werden. Der Parameter [Elektr. Energie gesamt] beschreibt die gesamte elektri­sche Leistungsaufnahme der Wärmepumpe und ihrer Komponenten. Alle anderen Werte beziehen sich auf die von der Wärmepumpe zur Verfügung gestellte Energie bzw. die Laufzeit verschiedener Kompo­nenten.
4.9.1 Monat
[→Hauptmenü →Statistik →Monat] In diesem Menü können über den Monat aufsummierte Werte zur
Leistungsabgabe und Leistungsaufnahme abgerufen werden. Der angezeigte Wert ist dem im Diagramm blau dargestellten Monat zu­geordnet. Die verschiedenen Werte können durch Drehen des Drehtasters angezeigt werden.
4 Funktion
4.9.2 Gesamt
[→Hauptmenü →Statistik →Gesamt] In diesem Menü können aufsummierte Werte zur Leistungsabgabe
und Leistungsaufnahme der Wärmepumpe seit Inbetriebnahme (oder seit dem letzten Reset durch den Fachmann) abgerufen wer­den.
Daikin RoCon+ HP Daikin Regelung RoCon+ HP1
008.1447899_00 – 09/2019 – DE
Betriebsanleitung
81
Page 82

5 Erste Inbetriebnahme

5 Erste Inbetriebnahme
INFORMATION
Zusätzlich zu den in diesem Kapitel aufgeführten Inbetrieb­nahmeerklärungen sind die spezifischen Anweisungen zur Inbetriebnahme der Daikin Altherma ETS(X/H) in der je­weils dazugehörigen Installationsanleitung mit zu beach­ten.

5.1 Configuration Wizard

Der Configuration Wizard erleichtert die Systemeinstellung während der Installation. Er erscheint automatisch bei Erstinbetriebnahme und führt durch festgelegte Auswahl-Seiten. Solange nicht die ge­samte Systemeinstellung bestätigt wird, wird der Configuration Wi­zard bei jedem Einschalten erneut aufgerufen. Erst nach Bestäti­gung der Systemeinstellung kann der Wärmeerzeuger in den Nor­malbetrieb wechseln. Im Normalbetrieb können die Parameter des Configuration Wizard im Menü [→Hauptmenü →Konfiguration → Wizard] aufgerufen und eingestellt werden.
Die Bedienung der unterschiedlichen Auswahl-Seiten des Configura­tion Wizards erfolgt entsprechend den in Kap. 3.3 beschriebenen Masken. Bei Bestätigen einer Auswahl mit "OK" oder dem Bestäti­gen-Icon wird direkt zur nächsten Auswahl-Seite gewechselt. Der modifizierte Parameter wird direkt übernommen.

5.2 Menüführung im Configuration Wizard

→ Sprache 1 Gewünschte Sprache auswählen. 2 Mit Bestätigen-Icon die Auswahl bestätigen.
→ Standard-Konfiguration
Wenn keine optionalen RoCon-Systemkomponenten angeschlos­sen sind:
1 Drehtaster kurz antippen zum Bestätigen ("Ja"). Wenn optionale RoCon-Systemkomponenten wie EHS157034
und / oder EHS157068 angeschlossen sind:
1 Drehtaster im Uhrzeigersinn drehen, bis "Nein" blau dargestellt
wird.
2 Drehtaster kurz antippen zum Bestätigen ("OK"). 3 Bei Bedarf folgende Listenelemente auswählen und einstellen:
▪ KonfigDirekt-Kreis (siehe Kap. 4.8) ▪ Buskennung-WEZ (siehe Kap. 4.8) ▪ Zeitmaster (siehe Kap. 7.11)
4 Wenn alle Einstellungen nach Bedarf erfolgt sind mit Bestätigen-
Icon bestätigen.
→ Uhrzeit 1 Einstellung der aktuellen Uhrzeit (siehe Kap. 3.3.5).
→ Datum 1 Einstellung des aktuellen Datums (siehe Kap. 3.3.6).
→ Systemparameter
Folgende Parameter können eingestellt werden:
▪ [Raumthermostat] vorhanden? (siehe Kap. 7.5.4) ▪ [Heizungsunterstützung (HZU)] erwünscht? (siehe Kap. 7.5.5) ▪ [Continuous heating] erwünscht? (siehe Kap. 7.5.5)
→ Heizgrenze
Folgende Parameter können eingestellt werden:
▪ [Heizgrenze Heizbetrieb] (siehe Kap. 7.5.3) ▪ [Heizgrenze Absenkbetrieb] (siehe Kap. 7.5.3)
→ Witterungsgeführt
Witterungsgeführte Regelung ist erwünscht: 1 Mit Bestätigen-Icon die Auswahl "Witterungsgeführt" bestätigen. Folgende Parameter können eingestellt werden:
▪ Einstellung [Raumtemperatur Soll 1] (siehe Kap. 7.5.1) ▪ Einstellung [Heizkurve] (siehe Kap. 4.5.4) ▪ Nur bei reversiblem Gerätetyp: Einstellung der Kühlkurve (siehe
Kap. 4.5.5)
Witterungsgeführte Regelung ist nicht erwünscht:
1 Einstellung "Vorlauftemperatur fix" auswählen. 2 Mit Bestätigen-Icon die Auswahl bestätigen.
Folgende Parameter können eingestellt werden:
▪ Einstellung [Vorlauftemperatur Heizbetrieb] (siehe Kap. 7.6.3) ▪ Nur bei reversiblem Gerätetyp: Einstellung [Vorlauftemperatur
Kühlbetrieb] (siehe Kap. 7.6.4)
→ Warmwasser
Folgende Parameter können eingestellt werden:
▪ [Warmwassertemperatur Soll 1] (siehe Kap. 7.3.4) ▪ [Warmwasser Hysterese] (siehe Kap. 7.6.5)
→ Geräteauswahl
Folgende Parameter können eingestellt werden:
▪ [Aussengerät] ▪ [Innengerät]
→ Externer Wärmeerzeuger
Kein externer Wärmeerzeuger vorhanden:
1 Einstellung "Kein externer Wärmeerzeuger" auswählen. 2 Mit Bestätigen-Icon die Auswahl bestätigen.
Optionaler Backup-Heater vorhanden: 1 Mit Bestätigen-Icon die Auswahl "Backup-Heater BUH" bestäti-
gen.
2 Bei Bedarf folgende Listenelemente auswählen und einstellen:
▪ [Ext. Leistung Warmwasser] (siehe Kap. 7.5.3) ▪ [Ext. Leistung Stufe 1] (siehe Kap. 7.5.3) ▪ [Ext. Leistung Stufe 2] (siehe Kap. 7.5.3) ▪ Notbetrieb (siehe Kap. 8.1)
3 Wenn alle Einstellungen nach Bedarf erfolgt sind mit Bestätigen-
Icon bestätigen. Alternativer externer Wärmeerzeuger vorhanden:
1 Einstellung "WW + Heiz-Unterstützung" oder "Zwei externe Wär-
meerzeuger" auswählen (siehe Kap. 7.5.3).
2 Mit Bestätigen-Icon die Auswahl bestätigen. 3 Bei Bedarf folgende Listenelemente auswählen und einstellen:
▪ [Ext. Leistung Warmwasser] (siehe Kap. 7.5.3) ▪ [Ext. Leistung Stufe 1] (siehe Kap. 7.5.3) ▪ Notbetrieb (siehe Kap. 8.1)
4 Wenn alle Einstellungen nach Bedarf erfolgt sind mit Bestätigen-
Icon bestätigen.
Betriebsanleitung
82
Daikin Regelung RoCon+ HP1
008.1447899_00 – 09/2019 – DE
Daikin RoCon+ HP
Page 83
→Heizsystem 1 Der Parameter [Heizsystem] kann eingestellt werden (siehe
Kap. 7.5.2).
5 Erste Inbetriebnahme
Daikin RoCon+ HP Daikin Regelung RoCon+ HP1
008.1447899_00 – 09/2019 – DE
Betriebsanleitung
83
Page 84

6 Parameterübersicht

Bereitschaft
Absenken
Heizen
Automatik 2
Automatik 1
Sommer
Kühlen
Raumtemperatur Soll 1
Raumtemperatur Soll 2
Raumtemperatur Soll 3
Warmwassertemperatur Soll 1
Warmwassertemperatur Soll 2
Warmwassertemperatur Soll 3
Raum
Absenken
Abwesend
Warmwasser
1x Laden
Raumtemperatur Absenken
Raumtemperatur Abwesend
1 x Warmwasser
Party
Abwesend
Urlaub
Feiertag
HK Auto 1
Heizkreis Automatik 1
HK Auto 2
Heizkreis Automatik 2
ZP Reset
Zeitprogramm Reset
WW Auto 1
Warmwasser Automatik 1
WW Auto 2
Warmwasser Automatik 2
Zirkulation
Zirkulationsprogramm
Sound Programm
Anzeige
System
Ext. Quelle
Ein-/Ausgänge
ISM
Glykol
Sprache
Uhrzeit
Datum
LCD Helligkeit
LCD Beleuchtungsdauer
Aussengerät
Innengerät
Heizsystem
Pumpe dT Heizen
Pumpe dT Kühlen
Konfig. externe Wärmequelle
Ext. Leistung Warmwasser
Ext. Leistung Stufe 1
Ext. Leistung Stufe 2
Bivalenzfunktion
Bivalenzfunktion
Smart Grid
Modus Smart Grid
HT/NT Funktion
HT/NT Anschluss
Raumthermostat
Interlinkfunktion
Programmierbarer Ausgang (230V)
Funktion Brennersperrkontakt
AUX-Schaltfunktion
AUX-Wartezeit
Schaltschwelle TDHW (AUX)
Continuous heating
Heizungsunterstützung (HZU)
Leistung BIV
HZU Hysterese
HZU Max. Temperatur
Min. Leistung Pumpe
Max. Leistung Pumpe
Leistungsbegrenzung Wärmepumpe
Pumpenlimit
6 Parameterübersicht

6.1 Menü: Betriebsart

Bild19-1 Parameter im Menü: "Betriebsart"

6.2 Menü: Benutzer

6.4 Menü: Einstellungen

Bild19-2 Parameter im Menü: „Benutzer“

6.3 Menü: Zeitprogramm

Bild19-3 Parameter im Menü: "Zeitprogramm"
Bild19-4 Parameter im Menü: "Einstellungen"
Betriebsanleitung
84
Daikin Regelung RoCon+ HP1
Daikin RoCon+ HP
008.1447899_00 – 09/2019 – DE
Page 85
6 Parameterübersicht
Warmwasserfühler
Wasserdrucksensor
Heizgrenze Absenkbetrieb
Heizkurve
Vorlauftemperatur Heizbetrieb
Vorlauftemperatur Absenkbetrieb
Min. Vorlauftemperatur
Raumsensor Anpassung
Untergrenze Vorlauftemperatur
Kühlsollwert Korrektur
Interlink Temperaturreduktion
Max. Warmwasser Ladezeit
Warmwasser Sperrzeit
Außenfühlerkorrektur
Wasserdruck Min.
Wasserdruck Max.
Wasserdruck Soll
Max. Druckverlust
Witterungsgeführt
Frostschutztemperatur
Gebäudedämmung
Heizgrenze Heizbetrieb
Max. Vorlauftemperatur
Raumeinfluss
Heizkurvenadaption
Interlink Temperaturerhöhung
Vorlauftemperatur Kühlbetrieb
Zirkulationspumpe Ansteuerung
Zirkulationspumpe Intervall
Antilegionellen Tag
Antilegionellen Startzeit
Antilegionellen Temperatur
Zusatz
Sensoren
ZugriffWWHK-Konfig
Heizen
Kühlkurve
Kühlen
Parameter
Wizard
Reset
Vorlauftemperatur Überhöhung
Comfort Heating
Außentemperaturfühler
Umschalttemperatur Heizkreis
Warmwasser Hysterese
Wartezeit ext. Wärmeerzeuger
VL-Soll Start Kühlen
Start Kühlen A-Temp
Max. Kühlen A-Temp
VL-Soll Max Kühlen
Relaistest
Entlüftung
Entlüftungsfunktion
Estrich
Estrichtrocknung
Programm
Estrichprogramm
Parameter Reset
Solar Funktion
Warmwassertemperatur Aktuell
Warmwassertemperatur Soll
Rücklauftemperatur
Vorlauftemp. HK Soll
Vorlauftemp. BUH
Außentemperatur (optional)
Kältemitteltemp.
Volumenstrom
Vorlauftemperatur Aktuell
Vorlauftemperatur Soll
Vorlauftemp. PWT
Außentemperatur gemittelt
Vorlauftemp. HK Aktuell
Aktuell
Übersicht
Werte
Druck
Modus
Externe Anforderung
RT / Interlink
Flüsterbetrieb
Status Heizungsumwälzpumpe
PWM Pumpe
BUH Leistungsaufnahme
3UVB1 Position
3UVDHW Position
Wärmeerzeugertyp
Software Nr B1/U1
Software Nr Regler
Glykol
Wasserdruck
HZU
Wasserdruck
Notbetrieb
Handbetrieb
Protokoll
Bildschirm
Status Handbetrieb
Temperatur Handbetrieb
Fehlerbildschirm
Mischer #X
Adresse
Bus-Scan
Regler BM1/BE1 #X
Terminaladresse

6.5 Menü: Konfiguration

6.6 Menü: Info

Bild19-5 Parameter im Menü: "Konfiguration"
Daikin RoCon+ HP Daikin Regelung RoCon+ HP1
008.1447899_00 – 09/2019 – DE
Bild19-6 Parameter im Menü: "Info"

6.7 Menü: Fehler

Bild19-7 Parameter im Menü: "Fehler"

6.8 Menü: Terminal

Bild19-8 Parameter im Menü: "Terminal"
Betriebsanleitung
85
Page 86
6 Parameterübersicht
Monat
Gesamt
Energie WP Kühlung
Energie WP Heizung
Energie Warmwasser
Energie WP gesamt
Elektr. Energie gesamt
Reset
Energie ext. Quelle Warmwasser
Energie ext. Quelle Heizung
Energie WP Kühlung
Energie WP Heizung
Energie Warmwasser
Energie WP gesamt
Elektr. Energie gesamt
Laufzeit Kompressor
Laufzeit Pumpe
INFORMATION
Wird das lokale Bedienteil als Fernbedienung für ein Mi­schermodul genutzt, ist sowohl der Standardbildschirm als auch die Menüstruktur geändert (siehe Kap. 9).

6.9 Menü: Statistik

Bild19-9 Parameter im Menü: "Statistik"
Betriebsanleitung
86
Daikin Regelung RoCon+ HP1
Daikin RoCon+ HP
008.1447899_00 – 09/2019 – DE
Page 87

7 Parametereinstellungen

7 Parametereinstellungen

7.1 Erläuterung zu den Parametertabellen

Die in Kap. 7.2 bis Kap. 7.10 aufgeführten Parametertabellen enthal­ten kompakte Informationen zu allen Parametern, die in den jeweili­gen Menüs und Untermenüs an der Regelung (1.Menüebene,
2.Menüebene) verfügbar sind.
Neben den Parameterbezeichnungen enthalten die Tabellen Anga­ben zu Einstellbereichen, Werkseinstellungen, Einstelloptionen bzw. Verstellschrittweiten und kurze Erläuterungen zur Funktion.
Außerdem geben sie Aufschluss über die Zugangsberechtigungen für die Bedienung an der Regelung. Zur entsprechenden Kennzeich­nung werden folgende Kurzbezeichnungen verwendet:

7.2 Betriebsart

[→Hauptmenü →Betriebsart]
BE Zugriffsberechtigung für den Betreiber HF Zugriffsberechtigung mit Fachmanncode
Bei unterschiedlichen Angaben in den Spalten BE und HF muss vor Anwahl der Parameterebene die Anmeldung als Fachmann erfolgt sein, um den in Spalte HF eingetragenen Status zu erhalten (siehe Kap. 4.5.1).
Status:
N Nicht sichtbar E Sichtbar und einstellbar S Sichtbar
INFORMATION
Die Änderung mancher Parameter erfordert einen Neustart des Geräts. Dieser dauert einige Minuten. In dieser Zeit können keine weiteren Einstellungen vorgenommen wer­den. Der Neustart kann um 5Minuten verzögert werden, indem bei der Abfrage "Neustart erforderlich. Jetzt durch­führen?" die Auswahl "später" getroffen wird.
Parameter, die einen Neustart erfordern, sind in den fol­genden Tabellen mit (*) gekennzeichnet
Parameter Einstellbereich
Min / Max
Bereitschaft In dieser Betriebsart sind alle internen Funktionen abgeschaltet. Frost-
schutz ist weiterhin aktiv und ein Blockierschutz der Pumpe bleibt gewähr­leistet.
Alle im RoCon-System über den CAN-Bus integrierten Regler werden bei Auswahl dieser Einstellung übergeordnet ebenfalls in diese Betriebsart ge­schaltet.
Ausgänge sind nicht ständig spannungsfrei.
Absenken Der interne Heizkreis regelt kontinuierlich auf die erforderliche Absenk-Vor-
lauftemperatur entsprechend den Parametern [Heizkurve] oder [Vorlauf­temperatur Absenkbetrieb] oder bei angeschlossenem Raumthermostat auf die Raumtemperatur [Raumtemperatur Absenken]. Die Warmwasser­bereitung erfolgt nach [Warmwasser Automatik 1].
Heizen Der interne Heizkreis regelt kontinuierlich auf die erforderliche Vorlauftem-
peratur entsprechend den Parametern [Heizkurve] oder [Vorlauftemperatur Heizbetrieb] oder bei angeschlossenem Raumthermostat auf die Raum­temperatur [Raumtemperatur Soll 1]. Die Warmwasserbereitung erfolgt nach [Warmwasser Automatik 1].
Sommer Der interne Heizkreis ist abgeschaltet. Frostschutz ist weiterhin aktiv und
ein Blockierschutz der Pumpe bleibt gewährleistet. Die Warmwasserberei­tung erfolgt nach [Warmwasser Automatik 1].
Alle im RoCon-System über den CAN-Bus integrierten Regler werden bei Auswahl dieser Einstellung übergeordnet ebenfalls in diese Betriebsart ge­schaltet.
Automatik 1 Der interne Heizkreise regelt nach dem eingestellten Zeitprogramm [Heiz-
kreis Automatik 1] mit den jeweiligen Raumsolltemperaturen. Die Warm­wasserbereitung erfolgt nach [Warmwasser Automatik 1].
Automatik 2 Der interne Heizkreise regelt nach dem eingestellten Zeitprogramm [Heiz-
kreis Automatik 2] mit den jeweiligen Raumsolltemperaturen. Die Warm­wasserbereitung erfolgt nach [Warmwasser Automatik 2].
Beschreibung Werks-
einstellung
Schritt-
weite
- E E
- E E
- E E
- E E
- E E
- E E
Zugriff
BE HF
Daikin RoCon+ HP Daikin Regelung RoCon+ HP1
008.1447899_00 – 09/2019 – DE
Betriebsanleitung
87
Page 88
7 Parametereinstellungen
Parameter Einstellbereich
Min / Max
Kühlen Der interne Heizkreis regelt kontinuierlich auf die erforderliche Vorlauftem-
peratur entsprechend den Parametern im Menü [→Hauptmenü→Konfigu­ration→Kühlen] oder bei angeschlossenem Raumthermostat auf die Raumtemperatur [Raumtemperatur Soll 1]. Die Warmwasserbereitung er­folgt nach [Warmwasser Automatik 1]. Frostschutz ist weiterhin aktiv und ein Blockierschutz der Pumpe bleibt gewährleistet.
Tab.20-1 Parameter in Menü "Betriebsart"
Beschreibung Werks-

7.3 Benutzer

[→Hauptmenü →Benutzer]
7.3.1 Menü: Raumtemperatur Soll
[→Hauptmenü →Benutzer →Raum]
Parameter Einstellbereich
Min / Max
Raumtempera­tur Soll 1
Raumtempera­tur Soll 2
Raumtempera­tur Soll 3
Tab.20-2 Parameter in Menü "Raumtemperatur Soll"
5 – 40°C Sollwert der Raumtemperatur in °C, welche für den 1. Schaltzeitzyklus der
Zeitprogramme [Automatik 1] und [Automatik 2] gilt.
5 – 40°C Sollwert der Raumtemperatur in °C, welche für den 2. Schaltzeitzyklus der
Zeitprogramme [Automatik 1] und [Automatik 2] gilt.
5 – 40°C Sollwert der Raumtemperatur in °C, welche für den 3. Schaltzeitzyklus der
Zeitprogramme [Automatik 1] und [Automatik 2] gilt.
Beschreibung Werks-
Schritt-
einstellung
einstellung
20°C 0,5°C E E
20°C 0,5°C E E
20°C 0,5°C E E
weite
- E E
Schritt-
weite
Zugriff
BE HF
Zugriff
BE HF
7.3.2 Menü: Raumtemperatur Absenken
[→Hauptmenü →Benutzer →Absenken]
Parameter Einstellbereich
Min / Max
Raumtempera­tur Absenken
Tab.20-3 Parameter in Menü "Raumtemperatur Absenken"
5 – 40°C Sollwert der Absenk-Raumtemperatur in °C, welche für die Zeitprogramme
[Automatik 1] und [Automatik 2] gilt.
7.3.3 Menü: Raumtemperatur Abwesend
[→Hauptmenü →Benutzer →Abwesend]
Parameter Einstellbereich
Min / Max
Raumtempera­tur Abwesend
Tab.20-4 Parameter in Menü "Raumtemperatur Abwesend"
5 – 40°C Sollwert der Absenk-Raumtemperatur in °C, welche für die Zeitprogramme
[Abwesend] + [Urlaub] gilt.
7.3.4 Menü: Warmwassertemperatur Soll
[→Hauptmenü →Benutzer →Warmwasser]
Parameter Einstellbereich
Min / Max
Warmwasser­temperatur Soll 1
Warmwasser­temperatur Soll 2
Warmwasser­temperatur Soll 3
Tab.20-5 Parameter in Menü "Warmwassertemperatur Soll"
35 – 70°C Sollwert der Warmwassertemperatur in °C, welche für den 1. Schaltzeitzy-
klus der Zeitprogramme [Automatik 1] und [Automatik 2] gilt.
35 – 70°C Sollwert der Warmwassertemperatur in °C, welche für den 2. Schaltzeitzy-
klus der Zeitprogramme [Automatik 1] und [Automatik 2] gilt.
35 – 70°C Sollwert der Warmwassertemperatur in °C, welche für den 3. Schaltzeitzy-
klus der Zeitprogramme [Automatik 1] und [Automatik 2] gilt.
Beschreibung Werks-
einstellung
15°C 0,5°C E E
Beschreibung Werks-
einstellung
15°C 0,5°C E E
Beschreibung Werks-
einstellung
48°C 0,5°C E E
48°C 0,5°C E E
48°C 0,5°C E E
Schritt-
weite
Schritt-
weite
Schritt-
weite
Zugriff
BE HF
Zugriff
BE HF
Zugriff
BE HF
Betriebsanleitung
88
Daikin Regelung RoCon+ HP1
Daikin RoCon+ HP
008.1447899_00 – 09/2019 – DE
Page 89
7.3.5 Menü: 1x Warmwasser
[→Hauptmenü →Benutzer →1x Laden]
7 Parametereinstellungen
Parameter Einstellbereich
Min / Max
1 x Warmwas­ser
Tab.20-6 Parameter in Menü "1 x Warmwasser"
Aus Start einer einmaligen Warmwasserbereitung auf den eingestellten Soll-
Ein
wert [Warmwassertemperatur Soll 1] ohne Zeitbegrenzung, unabhängig von den Heizprogrammen.
Beschreibung Werks-

7.4 Zeitprogramm

[→Hauptmenü →Zeitprogramm]
Parameter Einstellbereich
Min / Max
Party 0 – 360min Mit dieser Betriebsart kann eine einmalige Zeit für die vorübergehende
Heizzeitverlängerung des internen Heizkreises eingestellt werden.
Abwesend 0 – 360min Mit dieser Betriebsart kann eine einmalige Zeit für die vorübergehende Re-
gelung auf die eingestellte Abwesenheitstemperatur eingestellt werden.
Urlaub Datum 1.Tag
-
Datum letzter
Tag
Feiertag Datum 1.Tag
-
Datum letzter
Tag
Heizkreis Au­tomatik 1
Heizkreis Au­tomatik 2
Warmwasser Automatik 1
Warmwasser Automatik 2
Zirkulations­programm
siehe Kap. 4.3 In diesem Menü kann das 1. Zeitprogramm für den internen Heizkreis pa-
siehe Kap. 4.3 In diesem Menü kann das 2. Zeitprogramm für den internen Heizkreis pa-
siehe Kap. 4.3 In diesem Menü kann das 1. Zeitprogramm für die Warmwasserbereitung
siehe Kap. 4.3 In diesem Menü kann das 2. Zeitprogramm für die Warmwasserbereitung
siehe Kap. 4.3 In diesem Menü kann ein Zeitprogramm für die Zirkulationspumpe parame-
Der interne Heizkreis regelt dauerhaft (24h pro Tag) auf die eingestellte Abwesenheitstemperatur (Parameter [Raumtemperatur Absenken]).
Über eine Kalenderfunktion kann ein Zeitraum der Abwesenheit eingege­ben werden.
Über eine Kalenderfunktion kann ein Zeitraum der Anwesenheit eingege­ben werden.
In diesem Zeitraum wird ausschließlich nach den Einstellungen für "Sonn­tag" in den Zeitprogrammen [Heizkreis Automatik 1] und [Warmwasser Au­tomatik 1] geregelt.
rametriert werden. Es können 3 Schaltzyklen mit einer Auflösung von 15 Minuten eingestellt werden. Die Eingabe ist für jeden einzelnen Wochentag separat möglich. Format: (Ein) hh:mm - hh:mm (Aus)
Ebenfalls können die Zyklen von Montag bis Freitag, Samstag bis Sonntag und Montag bis Sonntag parametriert werden.
rametriert werden. Es können 3 Schaltzyklen mit einer Auflösung von 15 Minuten eingestellt werden. Die Eingabe ist für jeden einzelnen Wochentag separat möglich. Format: (Ein) hh:mm - hh:mm (Aus)
Ebenfalls können die Zyklen von Montag bis Freitag, Samstag bis Sonntag und Montag bis Sonntag parametriert werden.
parametriert werden. Es können 3 Schaltzyklen mit einer Auflösung von 15 Minuten eingestellt werden. Die Eingabe ist für jeden einzelnen Wochentag separat möglich. Format: (Ein) hh:mm - hh:mm (Aus)
Ebenfalls können die Zyklen von Montag bis Freitag, Samstag bis Sonntag und Montag bis Sonntag parametriert werden.
parametriert werden. Es können 3 Schaltzyklen mit einer Auflösung von 15 Minuten eingestellt werden. Die Eingabe ist für jeden einzelnen Wochentag separat möglich. Format: (Ein) hh:mm - hh:mm (Aus)
Ebenfalls können die Zyklen von Montag bis Freitag, Samstag bis Sonntag und Montag bis Sonntag parametriert werden.
triert werden. Es können 3 Schaltzyklen mit einer Auflösung von 15 Minu­ten eingestellt werden. Die Eingabe ist für jeden einzelnen Wochentag se­parat möglich. Format: (Ein) hh:mm - hh:mm (Aus)
Ebenfalls können die Zyklen von Montag bis Freitag, Samstag bis Sonntag und Montag bis Sonntag parametriert werden.
Beschreibung Werks-
Schritt-
einstellung
einstellung
0min 15min E E
0min 15min E E
- 1 Tag E E
- 1 Tag E E
siehe
Tab. 17-3
siehe
Tab. 17-3
siehe
Tab. 17-3
siehe
Tab. 17-3
siehe
Tab. 17-3
weite
- E E
Schritt-
weite
15min E E
15min E E
15min E E
15min E E
15min E E
Zugriff
BE HF
Zugriff
BE HF
Daikin RoCon+ HP Daikin Regelung RoCon+ HP1
008.1447899_00 – 09/2019 – DE
Betriebsanleitung
89
Page 90
7 Parametereinstellungen
Parameter Einstellbereich
Min / Max
Sound Pro­gramm
Zeitprogramm Reset
Tab.20-7 Parameter in Menü „Zeitprogramm“
siehe Kap. 4.3
0 – 3
Party In diesem Menü können die Zeitprogramme auf Werkseinstellungen zu­Abwesend Urlaub Feiertag Heizkreis Auto-
matik 1 Heizkreis Auto-
matik 2 Warmwasser
Automatik 1 Warmwasser
Automatik 2 Zirkulationspro-
gramm Sound Pro-
gramm
In diesem Menü kann ein Zeitprogramm für verschiedene Stufen des ge­räuscharmen Betriebs der Wärmepumpe parametriert werden. Es können 3 Schaltzyklen mit einer Auflösung von 15 Minuten eingestellt werden. Die Eingabe ist für jeden einzelnen Wochentag separat möglich. Format: (Ein) hh:mm - hh:mm (Aus)
Ebenfalls können die Zyklen von Montag bis Freitag, Samstag bis Sonntag und Montag bis Sonntag parametriert werden.
Jedem Schaltzyklus kann eine Geräuschstufe zugeordnet werden (0: keine Geräuschreduktion, 1: Min. Geräuschreduktion, 2: Med. Geräuschredukti­on , 3: Max. Geräuschreduktion).
Hinweis: Dieses Programm kann nur vom Installateur eingestellt werden.
rückgesetzt werden. Hierzu die jeweiligen Zeitprogramme auswählen und anschließend die Auswahl mit dem Bestätigen-Icon bestätigen.
Beschreibung Werks-
einstellung
0 15min N E
- - E E
Schritt-
weite
Zugriff
BE HF

7.5 Einstellungen

[→Hauptmenü→Einstellungen]
7.5.1 Menü: Anzeigeeinstellungen
[→Hauptmenü →Einstellungen →Anzeige]
Parameter Einstellbereich
Min / Max
Sprache Deutsch Landessprache der Anzeigetexte an der Bedieneinheit - E E
English
Français
Nederlands
Español
Italiano
Português
Lietuvos
Uhrzeit Uhrzeit im Format Stunden / Minuten. E E Datum Aktuelles Datum im Format Tag / Monat / Jahr. Der aktuelle Wochentag
wird anhand des Datums automatisch berechnet. LCD Helligkeit 10 – 100% Helligkeit des Displays 80% 10% E E LCD Beleuch-
tungsdauer
Tab.20-8 Parameter in Menü "Anzeigeeinstellungen"
1 - 60s Beleuchtungsdauer des Displays 30s 1s E E
Beschreibung Werks-
einstellung
Schritt-
weite
Zugriff
BE HF
E E
Betriebsanleitung
90
Daikin Regelung RoCon+ HP1
Daikin RoCon+ HP
008.1447899_00 – 09/2019 – DE
Page 91
7.5.2 Menü: System
[→Hauptmenü →Einstellungen →System]
7 Parametereinstellungen
Parameter Einstellbereich
Min / Max
Aussengerät keine Auswahl Typ Wärmepumpenaußengerät - - N E
14 kW 16 kW 18 kW
Innengerät keine Auswahl Typ Wärmepumpeninnengerät.
ETS(H/X)
(B)16P30D
ETS(H/X)
(B)16P50D
Heizsystem (*) Fussbodenhei-
zung
Konvektor
Radiator
Pumpe dT Heizen (*)
Pumpe dT Kühlen (*)
Glykol (*) Kein Glykol zu-
Leistungsbe­grenzung Wär­mepumpe
Pumpenlimit Der Parameter legt die maximale Pumpendrehzahl fest. Unter normalen
Tab.20-9 Parameter in Menü "System"
3 - 10 Erforderlicher Temperaturunterschied zwischen Rücklauf- und Vorlauftem-
3 - 10 Erforderlicher Temperaturunterschied zwischen Rücklauf- und Vorlauftem-
gefügt
Glykol zugefügt
20-50A Die permanente Leistungsbegrenzung ist nützlich, um eine maximale
0 Keine Begrenzung
1 – 4 Begrenzung der Pumpendrehzahl unabhängig vom Betriebszustand. Mit
5 - 8 Begrenzung der Pumpendrehzahl, wenn keine Heiz- oder Kühlanforderung
Anpassung des Einstellwerts wichtig, da die Gerätetypen unterschiedliche Abtaulogiken beinhalten.
Wärmeübertragertyp im Heizsystem. Wird "Radiator" gewählt und hohe Vorlauftemperaturen sind erwünscht,
kann es sinnvoll sein, den Parameter [Max. Vorlauftemperatur] auf 65°C zu erhöhen ([→Hauptmenü →Konfiguration →Heizen]).
peratur. Falls ein minimaler Temperaturunterschied für einen guten Betrieb der Heizverteilsysteme im Heizmodus erforderlich ist.
peratur. Falls ein minimaler Temperaturunterschied für einen guten Betrieb der Heizverteilsysteme im Kühlmodus erforderlich ist.
Es wird empfohlen, Glykol zum Wasserkreislauf hinzuzufügen, um Frost­schutz bei Stromausfall zu gewährleisten. Wurde dem System Glykol hin­zugefügt, muss die Einstellung der Regelung RoCon+ entsprechend ange­passt werden.
Stromaufnahme des Systems zu gewährleisten. In einigen Ländern be­grenzt die Gesetzgebung den maximalen Stromverbrauch für die Raum­heizung und die Brauchwasserbereitung.
Bedingungen sollte die Standardeinstellung NICHT geändert werden. Die Begrenzung der Pumpendrehzahl wird übergangen, wenn sich die Durch­flussmenge im Bereich des minimalen Durchflusses befindet. Der bei be­grenzter Pumpendrehzahl resultierende Wasserdurchfluss ist der Pumpen­kennlinie zu entnehmen (siehe Installations- und Wartungsanleitung Daikin Altherma ETS(X/H))
dieser Einstellung kann der Heizkomfort nicht garantiert werden. Die maxi­male Pumpendrehzahl ist abhängig von der Einstellung wie folgt: 1:90%, 2:75%, 3:65%,4:55%
vorliegt. Die maximale Pumpendrehzahl ist abhängig von der Einstellung wie folgt: 5:90%, 6:75%, 7:65%, 8:55%
Beschreibung Werks-
einstellung
- - N E
5 1 N E
5 1 N E
50A N E
6 1 N E
Schritt-
weite
- N E
- N E
Zugriff
BE HF
Daikin RoCon+ HP Daikin Regelung RoCon+ HP1
008.1447899_00 – 09/2019 – DE
Betriebsanleitung
91
Page 92
7 Parametereinstellungen
7.5.3 Menü: Externe Wärmequelle
[→Hauptmenü →Einstellungen →Ext. Quelle]
Parameter Einstellbereich
Min / Max
Konfig. exter­ne Wärme­quelle
Ext. Leistung Warmwasser
Ext. Leistung Stufe 1 (*)
Ext. Leistung Stufe 2 (*)
Bivalenzfunkti­on (*)
Bivalenztem­peratur
Tab.20-10 Parameter in Menü "Externe Wärmequelle"
Kein externer Wärmeerzeuger
Backup-Heater BUH
WW + Heiz-Un­terstützung
Zwei externe Wärmeerzeuger
1 – 40 kW Wärmeleistung des elektrischen Zuheizers für Warmwasserbereitung 3 kW 1 kW N E
1 – 40 kW Wärmeleistung des elektrischen Zuheizers bei Heizungsunterstützung Stu-
1 – 40 kW Wärmeleistung des elektrischen Zuheizers bei Heizungsunterstützung Stu-
Zuheizen immer
möglich
Zuheizen T-Bi-
valenz abhängig
-15°C - +35°C Einstellung beeinflusst die im Parameter [AUX-Schaltfunktion] definierte
Einstellung, ob zusätzlicher externer Wärmeerzeuger für Warmwasserbe-
reitung (WW) und/oder Heizungsunterstützung (HZU) vorhanden ist.
Wärmepumpe ist einzige Wärmequelle
Optionaler Heizstab (3N~) in Speicherbehälter verbaut
Ein alternativer Wärmeerzeuger (z. B. Backup-Heater 1N~) übernimmt
Warmwasserbereitung und Heizungsunterstützung
Zwei externe Wärmeerzeuger: Alternativer WEZ 1 (z. B. Backup-Heater
1N~) übernimmt Warmwasserbereitung und alternativer WEZ 2 übernimmt
Heizungsunterstützung
fe 1
siehe Betriebsanleitung des Heizstabes EKBUxx.
fe 2
siehe Betriebsanleitung des Heizstabes EKBUxx.
Die Bivalenzfunktion ist für den Betrieb des optionalen Zuheizers aufgrund
einer Backup-Anforderung (Raumheizbetrieb) relevant.
Betrieb des Backup-Heaters ist immer möglich.
Backup-Heater wird erst freigeben, wenn die im Parameter [Bivalenztem-
peratur] eingestellte Temperatur unterschritten wird.
Wirkungsweise des potenzialfreien AUX-Schaltkontakts (Wechselschalt-
ausgang A).
Nur wenn Parameter [Bivalenzfunktion] = Zuheizen T-Bivalenz:
Außentemperatur, ab welcher der optionale Zuheizer zur Unterstützung
der Raumheizung aktiviert wird. Die Bivalenztemperatur ist für den Betrieb
des optionalen Zuheizers aufgrund einer Backup-Anforderung (Raumheiz-
betrieb) relevant. Hierfür wird die Temperatur des im Wärmepumpenau-
ßengerät integrierten Temperatursensors (Infowert TA) verwendet.
Beschreibung Werks-
einstellung
3 kW 1 kW N E
3 kW 1 kW N E
0°C 1°C N E
Schritt-
weite
- N E
- N E
Zugriff
BE HF
7.5.4 Menü: Ein-/Ausgänge
[→Hauptmenü →Einstellungen →Ein-/Ausgänge]
Parameter Einstellbereich
Min / Max
Smart Grid Auswertung des SG-Signals (siehe Kap. 4.4). - N E
Aus Funktion Smart Grid nicht aktiv, SG-Signal wird nicht ausgewertet.
Ein Je nach Signal des Energieversorgungsunternehmens wird die Wärme-
pumpe abgeschaltet (keine Frostschutzfunktion) oder auf höheren Tempe-
raturen betrieben. Modus Smart
Grid
Komfort Anhebung der Warmwasser-Solltemperatur um 5K
Standard Anhebung der Vorlauf-Solltemperatur um 2K und Warmwasser-Solltempe-
Eco Anhebung der Vorlauf-Solltemperatur um 5K und Warmwasser-Solltempe-
Betriebsanleitung
Nur wenn Parameter [Smart Grid] = Ein:
Dient zu einer möglichen Soll-Temperaturerhöhung bei einem Smart Grid-
Einschaltbefehl.
ratur um 5K
ratur um 7K
92
Beschreibung Werks-
einstellung
Daikin Regelung RoCon+ HP1
008.1447899_00 – 09/2019 – DE
Schritt-
weite
BE HF
- N E
Daikin RoCon+ HP
Zugriff
Page 93
7 Parametereinstellungen
Parameter Einstellbereich
Min / Max
HT/NT Funkti­on
Inaktiv Deaktiviert (keine Auswirkung)
Verdichter aus-
schalten
Verdichter +
BUH ausschal-
ten
Alles ausschal-
ten
HT/NT An­schluss
Schließerkon-
takt
Öffnerkontakt Schaltkontakt geschlossen bei Niedertarif.
Raumthermo­stat
Nein Deaktiviert
Ja Nur wenn Parameter [Interlinkfunktion] = Aus
Beschreibung Werks-
Einstellung, welche Wärmequellen ausgeschaltet werden, wenn bei einem Niedertarif-Netzanschluss das vom Energieversorgungsunternehmen (EVU) ausgegebene Signal für Hochtarif empfangen wird.
Kältemittelverdichter wird ausgeschaltet
Kältemittelverdichter und Reserveheizung werden ausgeschaltet
Alles wird ausgeschaltet (keine Frostschutzfunktion - siehe Kap. 4.5.3)
Festlegung, ob der HT-/NT-Eingang als Öffner- oder Schließerkontakt aus­gewertet wird.
Schaltkontakt geschlossen bei Hochtarif.
Konfiguration eines am Anschluss J16 der Daikin Altherma ETS(X/H) an­geschlossenen Raumthermostats mit potenzialfreien Kontakten.
Auswertung der Schaltkontakte Heizen und Kühlen am Steckeranschluss J16 auf der Schaltplatine RoCon BM2C (nur, wenn keine der Betriebsarten "Bereitschaft", "Absenken", "Sommer", "Urlaub", "Feiertag" oder "Estrich" aktiv ist):
▪ Geschlossener Schaltkontakt Heizen : Betriebsart wird auf "Heizen" ge-
schaltet. Priorität, falls beide Schaltkontakte geschlossen sind.
▪ Geschlossener Schaltkontakt Kühlen : Betriebsart wird auf "Kühlen" ge-
schaltet.
Offene Kontakte: Nur Frostschutz aktiv.
einstellung
Schritt-
weite
- N E
- N E
- N E
Zugriff
BE HF
Daikin RoCon+ HP Daikin Regelung RoCon+ HP1
008.1447899_00 – 09/2019 – DE
Betriebsanleitung
93
Page 94
7 Parametereinstellungen
Parameter Einstellbereich
Min / Max
Interlinkfunkti­on
Aus Deaktiviert
Ein Auswertung der Schaltkontakte Heizen und Kühlen am Steckeranschluss
Programmier­barer Ausgang (230V)
Funktion Bren­nersperrkon­takt
Inaktiv Der Ausgang ist ohne Funktion.
Anforderung
Heizkreis
Anforderung Zir-
kulation
Anforderung di-
rekter Heizkreis
Widerstands-
werte
Brennersperr-
kontakt
Beschreibung Werks-
einstellung
Konfiguration für Anlagen, die mit 2 verschiedenen Vorlauf-Solltemperatu-
ren betrieben werden (siehe Kap. 4.4.4).
Eine mögliche Anwendung ist z. B. die zusätzliche Einbindung eines HP
convector in ein Flächenheiz- und Kühlsystem.
Voraussetzung: Am Steckeranschluss J16 der Daikin Altherma ETS(X/H)
sind 2 Raumthermostate angeschlossen.
J16 auf der Schaltplatine RoCon BM2C.
Aktivieren des Kühlbetriebs nur durch Umstellen der Betriebsart auf "Küh-
len" (siehe Kap. 4.1).
Einstellung des Parameters [Raumthermostat] wird nicht mehr ausgewer-
tet.
▪ Offene Schaltkontakte: nur Frostschutz aktiv
▪ Betriebsart "Heizen" und "Automatik 1" / "Automatik 2" während der
Schaltzyklen im Tagbetrieb aktiv. ▪ Geschlossener Schaltkontakt Heizen = IL1: ▪ Es wird auf die normale Vorlauf-Solltemperatur gemäß den Parame-
tereinstellungen in [→Hauptmenü →Konfiguration →Heizen] gere-
gelt. ▪ Geschlossener Schaltkontakt Kühlen = IL2: ▪ Es wird auf die erhöhte Vorlauf-Solltemperatur geregelt (normale Vor-
lauf-Solltemperatur + Wert des Parameters [Interlink Temperaturerhö-
hung ]. Priorität, falls beide Schaltkontakte geschlossen sind!
▪ Betriebsart "Kühlen" aktiv.
▪ Geschlossener Schaltkontakt Heizen = IL1: ▪ Es wird auf die normale Vorlauf-Solltemperatur gemäß den Parame-
tereinstellungen in [→Hauptmenü →Konfiguration →Heizen] gere-
gelt. ▪ Geschlossener Schaltkontakt Kühlen = IL2:
Es wird auf die abgesenkte Vorlauf-Solltemperatur geregelt (normale Vor­lauf-Solltemperatur - Wert des Parameters [Interlink Temperaturreduktion]. Priorität, falls beide Schaltkontakte geschlossen sind
Konfigurieren des Multifunktionsausgangs (230V, Anschluss J14): - N E
Sammlerpumpe – Der Ausgang wird aktiv, sobald ein beliebiger Heizkreis (z.B. Mischerkreis) des Systems eine Wärmeanforderung zum Wärmeer­zeuger meldet.
Zirkulationspumpe – Der Ausgang wird je nach Parametrierung entweder nach dem Zeitprogramm der Zirkulationspumpe oder nach dem Zeitpro­gramm der Warmwasserbereitung aktiviert (siehe Kap. 4.3).
Zubringerpumpe – Der Ausgang wird aktiv, sobald für den direkten Heiz­kreis des Wärmeerzeugers eine Wärmeanforderung ansteht.
Wahl der Funktionalität des Schaltkontakts EXT (J8) (siehe Kap. 4.1) - N E
Schritt-
weite
- N E
Zugriff
BE HF
Betriebsanleitung
94
Daikin Regelung RoCon+ HP1
Daikin RoCon+ HP
008.1447899_00 – 09/2019 – DE
Page 95
7 Parametereinstellungen
Parameter Einstellbereich
Min / Max
AUX-Schalt­funktion
Inaktiv Funktion deaktiviert.
Schaltschwelle
TDHW (AUX)
Anforderung
Heizen/Kühlen
Anforderung
BUH
Fehler Wenn ein Fehler anliegt
TVBH > 60 °C Wenn der Fühlerwert (TVBH) >60°C ist.
Außentempera-
tur
Außentempera-
tur + WW/Hei-
zen
AnforderungWWWenn eine Warmwasseranforderung besteht.
Außentempera-
tur + Heizen
Multi-Oil Wenn Außentemperatur < Parameterwert [Bivalenztemperatur] + Wärme-
Betriebsart Küh-
len
AUX-Wartezeit 0-600s AUX-Schaltkontakt (A) schaltet erst verzögert, wenn die Schaltbedingung
Schaltschwelle TDHW (AUX)
Tab.20-11 Parameter in Menü "Ein-/Ausgänge"
20 – 85°C Schaltschwelle Speichertemperatur (Tdhw) für AUX-Schaltkontakt (siehe
Einstellung weist die Schaltbedingungen für den potenzialfreien AUX-
Schaltkontakt zu (Wechsel Schaltausgang A, siehe Kap. 4.4.4).
AUX-Schaltkontakt schaltet:
Wenn Speichertemperatur (Tdhw) ≥ Wert Parameter [Schaltschwelle TD-
HW (AUX)] ist.
Wenn eine Kühlanforderung oder Heizanforderung vorliegt.
Wenn eine Warmwasseranforderung an den Backup-Heater (EKBUxx) vor-
liegt oder der konfigurierte Backup-Heater zur Heizungsunterstützung an-
gefordert wird.
Wenn die Außentemperatur < Parameterwert [Bivalenztemperatur] ist.
(Wärmepumpe arbeitet weiter = paralleler Bivalenzbetrieb)
Wenn die Außentemperatur < Parameterwert [Bivalenztemperatur] ist + ei-
ne Anforderung Heizen oder eine Warmwasseranforderung vorliegt. (Wär-
mepumpe arbeitet nicht weiter = alternativer Bivalenzbetrieb)
Wenn Außentemperatur < Parameterwert [Bivalenztemperatur] + Wärme-
anforderung "Raumheizung" (nicht für Warmwasseranforderung). Wärme-
pumpe arbeitet unterhalb dem im Parameter [Bivalenztemperatur] einge-
stellten Wert nicht mehr im Raumheizbetrieb - nur noch im Warmwasser-
betrieb.
Anwendung: Alternativer Bivalenzbetrieb Raumheizung, wenn Heizkessel
hydraulisch so eingebunden ist, dass er das druckloses Speicherwasser
der Daikin Altherma ETS(X/H) direkt erwärmt (Anschluss über Solaran-
schlüsse).
anforderung "Raumheizung" (nicht für Warmwasseranforderung). Wärme-
pumpe arbeitet unterhalb dem im Parameter [Bivalenztemperatur] einge-
stellten Wert nicht mehr im Raumheizbetrieb - nur noch im Warmwasser-
betrieb.
Anwendung: Alternativer Bivalenzbetrieb Raumheizung, wenn Heizkessel
hydraulisch im Vorlauf der Wärmepumpe eingebunden ist. Für diese An-
wendungsart muss die Frostschutzfunktion an der Daikin Altherma ETS(X/
H) deaktiviert werden (Parameter [Frostschutztemperatur] = Aus).
Wenn sich die Wärmepumpe in der Betriebsart "Kühlen" befindet.
(siehe Parameter [AUX-Schaltfunktion]) länger als die eingestellte Zeit an-
steht.
Parameter [AUX-Schaltfunktion]).
Beschreibung Werks-
Schritt-
einstellung
120s 5s N E
50°C 1°C N E
weite
- N E
Zugriff
BE HF
Daikin RoCon+ HP Daikin Regelung RoCon+ HP1
008.1447899_00 – 09/2019 – DE
Betriebsanleitung
95
Page 96
7 Parametereinstellungen
7.5.5 Menü: Intelligentes Speicher Management
[→Hauptmenü →Einstellungen →ISM]
Parameter Einstellbereich
Min / Max
Continuous heating
Aus Kein ununterbrochenes Heizen
Ein Ununterbrochenes Heizen. Heizwärme wird während dem Abtauen des
Heizungsun­terstützung (HZU)
Leistung BIV 3 – 40kW Einstellung begrenzt Leistung der Heizungsunterstützung. 15kW 1kW N E HZU Hystere-
se
HZU Max. Temperatur
Min. Leistung Pumpe
Max. Leistung Pumpe
Tab.20-12 Parameter in Menü "Intelligentes Speicher Manag."
Aus Keine Heizungsunterstützung
Ein Heizungsunterstützungsfunktion aktiv
2 - 15 Nur wenn Parameter [Heizungsunterstützung (HZU)] = Ein.
5 - 85°C Einstellung begrenzt die Vorlauf-Solltemperatur (gemessen an t
40 - 80% Untergrenze für den Pumpenbetrieb. Wird nur angewendet, wenn Hei-
60 - 80% Obergrenze für den Pumpenbetrieb. Wird nur angewendet, wenn Hei-
Die Funktion erlaubt das ununterbrochene Heizen auch während dem Ab­tauen des Verdampfers. Damit kann ein hoher Komfort auch bei schnell reagierenden Heizsystemen (z.B. Konvektoren) gewährleistet werden.
Verdampfers aus dem Speicher entnommen. Heizungsunterstützung aus Warmwasserspeicher, wenn Mindesttempera-
tur überschritten ist (siehe Kap. 4.4 und Parameter [HZU Hysterese]).
Heizungsunterstützung wird aktiviert, wenn Tdhw > THZUmin + 4K und Tdhw > [Vorlauftemperatur Soll] + 1 K. Die Heizungsunterstützung wird deaktiviert, wenn Tdhw < THZUmin oder Tdhw < [Vorlauftemperatur Soll]. THZUmin = Gerade aktive Warmwasser-Solltemperatur [Vorlauftemperatur
Soll] + eingestellter Parameterwert [HZU Hysterese]. Tdhw = aktuelle Warmwasserspeichertemperatur [Vorlauftemperatur Soll] = gerade aktive Vorlauf-Solltemperatur (siehe
Kap. 4.5)
tiver Heizungsunterstützungsfunktion.
zungsunterstützung aktiv ist oder Wärme durch eine externe Wärmequelle erzeugt wird. Im normalen Betrieb wird die Pumpe nach dem Parameter [Pumpenlimit] geregelt, siehe Kap. 7.5.2.
zungsunterstützung aktiv ist oder Wärme durch eine externe Wärmequelle erzeugt wird. Im normalen Betrieb wird die Pumpe nach dem Parameter [Pumpenlimit] geregelt, siehe Kap. 7.5.2.
Beschreibung Werks-
einstellung
5 1 N E
V,BH
) bei ak-
60°C 1°C N E
50% 1% N E
80% 1% N E
Schritt-
weite
- N E
- N E
Zugriff
BE HF

7.6 Konfiguration

[→Hauptmenü →Konfiguration]
7.6.1 Menü: Sensoren
[→Hauptmenü →Konfiguration →Sensoren]
Parameter Einstellbereich
Min / Max
Außentempe­raturfühler (*)
Warmwasser­fühler
Betriebsanleitung
Integrierter Sen-
sor
Optionaler Sen-
sor
Inaktiv Keine Funktion zur Warmwasserbereitung.
Sensor Funktion zur Warmwasserbereitung ist aktiviert. Für die Warmwasserberei-
Thermostat Funktion zur Warmwasserbereitung ist aktiviert. Für die Warmwasserberei-
Auswahl, ob der im Außengerät integrierte Sensor oder ein optionaler Au­ßentemperaturfühler genutzt wird, um Soll-Vorlauftemperaturen zu ermit­teln
Konfiguration der Warmwasserbereitung: - N E
tung wird ein Speichertemperaturfühler ausgewertet (Ist kein Speichertem­peraturfühler angeschlossen, wird eine Fehlermeldung erzeugt).
tung wird ein Thermostatschalter (Ein / Aus) ausgewertet, wobei "offene Klemmen" als "Kein Bedarf" ausgewertet wird.
96
Beschreibung Werks-
einstellung
Daikin Regelung RoCon+ HP1
008.1447899_00 – 09/2019 – DE
Schritt-
weite
BE HF
- N E
Daikin RoCon+ HP
Zugriff
Page 97
7 Parametereinstellungen
Parameter Einstellbereich
Min / Max
Wasserdruck­sensor
Außenfühler­korrektur
Wasserdruck Min.
Wasserdruck Max.
Wasserdruck Soll
Max. Druck­verlust
Tab.20-13 Parameter in Menü "Sensoren"
Aus Keine Fühlerauswertung
Ein Fühlerauswertung aktiviert (Ist kein Drucksensor angeschlossen, wird eine
-5,0 – +5,0K Individuelle Anpassung für den Messwert der für die Regelung relevanten
0,1 - 5,0bar Definiert den minimalen Wasserdruck.
0,1 - 5,0bar Definiert den maximalen Wasserdruck.
0,1 - 5,0bar Definiert den Soll-Wasserdruck.
0,1 - 5,0bar Definiert den maximal akzeptablen Druckverlust in der Heizungsanlage.
Konfiguration des Sensors zur Erfassung des Wasserdrucks der Anlage. - N E
Fehlermeldung generiert.)
Außentemperatur.
Druckwächterfunktion (nur bei aktiviertem Drucksensor, [Wasserdrucksen-
sor] = Ein): Unterschreitet der Messwert den eingestellten Wert, wird die
Daikin Altherma ETS(X/H) abgeschaltet und eine Fehlermeldung generiert.
Druckwächterfunktion (nur bei aktiviertem Drucksensor, [Wasserdrucksen-
sor] = Ein): Überschreitet der Messwert den eingestellten Wert, wird eine
Warnmeldung generiert.
Druckwächterfunktion (nur bei aktiviertem Drucksensor, [Wasserdrucksen-
sor] = Ein): Unterschreitet der Messwert den eingestellten Wert um mehr
als den im Parameter [Max. Druckverlust] eingestellten Wert, wird eine
Warnmeldung generiert.
Druckwächterfunktion (nur bei aktiviertem Drucksensor, [Wasserdrucksen-
sor] = Ein): Unterschreitet der Messwert den im Parameter [Wasserdruck
Soll] eingestellten Wert um mehr als den eingestellten Wert, wird eine
Warnmeldung generiert.
Beschreibung Werks-
einstellung
0,0K 0,1K N E
0,5bar 0,1bar N E
3,0bar 0,1bar N E
0,9bar 0,1bar N E
0,5bar 0,1bar N E
Schritt-
weite
Zugriff
BE HF
7.6.2 Menü: Heizkreis Konfiguration
[→Hauptmenü →Konfiguration →HK-Konfig]
Parameter Einstellbereich
Min / Max
Witterungsge­führt
Frostschutz­temperatur
Gebäudedäm­mung
Umschalttem­peratur Heiz­kreis
Tab.20-14 Parameter in Menü "Heizkreis Konfiguration"
Vorlauftempera-
tur fix
Witterungsge-
führt
Aus Kein Frostschutz des Heizkreises 0°C 1°C E E
-15 – 5°C Wenn die Außentemperatur unter den eingestellten Wert sinkt, schaltet die
Aus Einstellung des Gebäudedämmstandards. Dadurch werden die gemittelte
Gering
Normal
Gut
Sehr gut
Aus Deaktiviert
10 - 40°C Überschreitet die Außentemperatur den eingestellten Wert, wird auf die
Auswahl der Methode zur Ermittlung der Soll-Vorlauftemperatur. - N E
Vorlauftemperatur fix: Regelung auf einen festen Vorlaufwert (je nach Be-
triebsweise)
Witterungsgeführt: Witterungsgeführte Regelung anhand der Heizkurve.
Anlage in den Frostschutzbetrieb (Einschalten der Pumpen). Die Funktion
wird beendet, wenn die Außentemperatur über den eingestellten Wert +1K
steigt.
Außentemperatur und die automatischen Anpassungen der Heizkurve und
der Heizzeiten beeinflusst.
Automatische Aktivierung des Kühlbetriebs. 1°C N E
Betriebsart "Kühlen" gestellt. Sinkt die Außentemperatur um 2K unter den
eingestellten Wert, wird automatisch auf die zuvor aktivierte Betriebsart zu-
rückgeschaltet
Beschreibung Werks-
einstellung
Schritt-
weite
- E E
Zugriff
BE HF
Daikin RoCon+ HP Daikin Regelung RoCon+ HP1
008.1447899_00 – 09/2019 – DE
Betriebsanleitung
97
Page 98
7 Parametereinstellungen
7.6.3 Menü: Heizen
[→Hauptmenü →Konfiguration →Heizen]
Parameter Einstellbereich
Min / Max
Heizgrenze Heizbetrieb
Heizgrenze Absenkbetrieb
Heizkurve 0,0 - 3,0 Nur wenn Parameter [Witterungsgeführt] = Witterungsgeführt:
Vorlauftempe­ratur Überhö­hung (*)
Vorlauftempe­ratur Heizbe­trieb
Vorlauftempe­ratur Absenk­betrieb
Max. Vorlauf­temperatur
Min. Vorlauf­temperatur
Raumeinfluss Nur bei angeschlossenem und dem Heizkreis zugeordnetem Raumregler:
Raumsensor Anpassung
Aus Einstellen der automatischen Sommerabschaltung des Heizbetriebs. Über-
10 – 40°C
Aus Einstellen der Heizgrenze zur "Abschaltung" des Heizkreises während der
10 – 40°C
0 - 4 Diese Funktion legt fest, wie hoch die Wassertemperatur über die Soll-Vor-
20 – 90°C Nur wenn Parameter [Witterungsgeführt] = Witterungsgeführt
10 – 90°C Nur wenn Parameter [Witterungsgeführt] = Witterungsgeführt
20 – 90°C Einstellung begrenzt die Vorlauftemperatur (gemessen an tV2) bei aktiver
10 – 90°C Die ermittelte Vorlaufsolltemperatur des Heizkreises wird auf den hier ein-
Aus Rein witterungsgeführte Vorlauftemperaturregelung
0K Rein witterungsgeführte Vorlauftemperaturregelung, aber interne Umwälz-
1 – 20K Bewirkt eine Korrektur der Vorlaufsolltemperatur (Parallelverschiebung der
-5 - +5K Nur bei angeschlossenem und dem Heizkreis zugeordnetem Raumregler.
steigt die durch den Regler gemessene und gemittelte Außentemperatur den eingestellten Wert um 1K, so wird der Heizkreis abgeschaltet. Die Be­heizung wird wieder freigegeben, wenn die Außentemperatur die einge­stellte Heizgrenze unterschreitet.
Absenkzeit (Funktionsweise wie Parameter [Heizgrenze Heizbetrieb]).
Einstellung der Heizkurve. Die Heizkurve gibt die Abhängigkeit der Vorlauf­solltemperatur des Heizkreises von der Außentemperatur wieder (siehe
Kap. 4.5).
lauftemperatur steigen darf, bevor der Verdichter gestoppt wird. Der Ver­dichter nimmt den Betrieb wieder auf, wenn die Vorlauftemperatur unter die Soll-Vorlauftemperatur fällt. Diese Funktion gilt NUR für den Heizmo­dus.
Einstellung der Vorlaufsolltemperatur für den Heizkreis während der Heiz­zeit bei Betriebsart: "Automatik 1", "Automatik 2", "Heizen".
Einstellung der Vorlaufsolltemperatur für den Heizkreis während der Ab­senkzeit bei Betriebsart: "Automatik 1", "Automatik 2", "Heizen".
Heizungsunterstützungsfunktion. Die ermittelte Vorlaufsolltemperatur des Heizkreises wird auf den hier ein-
gestellten Maximalwert begrenzt. Fordert ein optional angeschlossener, gemischter Heizkreis eine höhere
Temperatur des Wärmeerzeugers an, so wird diese berücksichtigt. Somit läuft die interne Umwälzpumpe des Wärmeerzeugers immer, wenn dieser eingeschaltet ist. Wenn der direkte Heizkreis eine Fußbodenheizung ver­sorgt, ist daher ein mechanischer Temperaturbegrenzer einzubauen, um ein Überhitzen des Estrichs zu verhindern.
gestellten Minimalwert begrenzt.
Einstellung, welchen Einfluss die Abweichung der vom EHS157034 ge­messenen Raumtemperatur vom aktuellen Sollwert (siehe Kap. 4.2) auf die Vorlauftemperatur hat.
pumpe läuft nach einer Wärmeanforderung während der Absenkzeit bis zum nächsten Heizzyklus weiter.
Heizkurve) um den eingestellten Faktor. Wenn die gemessene Temperatur 2K unter dem Sollwert liegt, wird die Vorlaufsolltemperatur um das 2-Fa­che des eingestellten Werts angehoben.
Individuelle Anpassung der für die Regelung relevanten Raumtemperatur. Sollte eine systematische Abweichung der vom EHS157034 gemessenen
Raumtemperatur zu der im Aufenthaltsbereich dieses Raumes tatsächli­chen Temperatur festgestellt werden, kann der Messwert um den einge­stellten Wert korrigiert werden.
Beschreibung Werks-
Schritt-
einstellung
19°C 1K E E
10°C 1K E E
0,5 0,1 E E
3 1 N E
40°C 1°C E E
10°C 1°C E E
80°C 1°C N E
10°C 1°C N E
0,0K 1K E E
weite
1K E E
Zugriff
BE HF
Betriebsanleitung
98
Daikin Regelung RoCon+ HP1
Daikin RoCon+ HP
008.1447899_00 – 09/2019 – DE
Page 99
7 Parametereinstellungen
Parameter Einstellbereich
Min / Max
Heizkurvenad­aption
Aus Deaktiviert
Ein Aktiviert = Start einer einmaligen automatischen Heizkurvenadaption.
Interlink Tem­peraturerhö­hung
Comfort Hea­ting
Tab.20-15 Parameter in Menü "Heizen"
1 – 50K Nur wenn Parameter [Interlinkfunktion] = Ein:
Aus Erst bei nicht gedecktem Heizbedarf wird die Speichertemperatur angeho-
Ein Bei entsprechenden Außentemperaturen wird die Speichertemperatur im-
Funktion kann nur bei angeschlossenem und dem Heizkreis zugeordnetem
Raumregler ausgeführt werden:
Voraussetzungen:
▪ Außentemperatur <8°C
▪ Einstellung der Betriebsart: "Automatik 1" oder "Automatik 2"
▪ Dauer der Absenkphase mindestens 6 Stunden
Funktion: Zu Beginn der Absenkzeit wird die aktuelle Raumtemperatur als
Sollwert für die folgenden 4 Stunden gesetzt. Die Heizkurve wird von der
Regelung aus den Vorlaufsolltemperaturen ermittelt, die zum Halten dieser
Raumtemperatur erforderlich sind.
Wird die automatische Heizkurvenadaption unterbrochen, so pausiert die
Funktion, bis sie am nächsten Tag erfolgreich durchgeführt oder beendet
wird (Einstellen des Parameters auf "Aus" oder Ändern der aktuellen Be-
triebsart).
Während der automatischen Heizkurvenadaption sind die Warmwasserbe-
reitung und die Aufheizoptimierung gesperrt.
Vorlauf-Solltemperatur wird bei geschlossenem RT-Schaltkontakt Kühlen
um den eingestellten Wert erhöht. Anforderung z. B. durch HP convector.
Kann die Wärmepumpe den Heizbedarf bei sehr niedrigen Außentempera-
turen nicht decken, wird Wärme aus dem Speicher entnommen und für die
Raumheizung genutzt (Siehe Kap. 4.5.4)
ben. In der Zeit, die zur Temperaturanhebung benötigt wird, kann es zu ge-
ringen Komforteinbußen kommen.
mer über die für den Warmwasserbedarf eingestellte Speichertemperatur
angehoben. Es erhöht sich gegebenenfalls der Stromverbrauch der Wär-
mepumpe.
Beschreibung Werks-
einstellung
5K 1K N E
Schritt-
weite
- N E
Zugriff
BE HF
N E
7.6.4 Menü: Kühlen
[→Hauptmenü →Konfiguration →Kühlen]
Parameter Einstellbereich
Min / Max
VL-Soll Start Kühlen
VL-Soll Max Kühlen
Start Kühlen A-Temp
Max. Kühlen A-Temp
Untergrenze Vorlauftempe­ratur
5 - 25°C Nur wenn Parameter [Witterungsgeführt] = Witterungsgeführt:
Einstellung der Kühlvorlauf-Solltemperatur beim Start des Kühlbetriebs
(Außentemperatur = Parameter [Start Kühlen A-Temp])
5 - 25°C Nur wenn Parameter [Witterungsgeführt] = Witterungsgeführt:
Einstellung der minimalen Kühlvorlauf-Solltemperatur. Diese wird ab der
Außentemperatur (Parameter [Max. Kühlen A-Temp]) konstant gehalten.
15 - 45°C Nur wenn Parameter [Witterungsgeführt] = Witterungsgeführt:
Einstellung, ab welcher Außentemperatur der Kühlbetrieb mit der höchsten
Kühlvorlauf-Solltemperatur [VL-Soll Start Kühlen] startet (Einstellbedin-
gung: Betriebsart "Kühlen").
20 - 45°C Nur wenn Parameter [Witterungsgeführt] = Witterungsgeführt:
Einstellung, bei welcher Außentemperatur die niedrigste Kühlvorlauf-Soll-
temperatur [VL-Soll Max Kühlen] vorgegeben wird (Einstellbedingung: Be-
triebsart "Kühlen").
5 - 25°C Einstellung der absoluten Untergrenze der Kühlvorlauf-Solltemperatur. Be-
grenzung wirkt, falls aus anderen Parametereinstellungen eine niedrigere
Kühlvorlauf-Solltemperatur ermittelt würde.
Sind im System optionale Frostschutz-Ventile verbaut, darf der Parameter
[Untergrenze Vorlauftemperatur] nicht unter 7°C eingestellt werden.
Beschreibung Werks-
einstellung
18°C 1°C E E
8°C 1°C E E
24°C 1°C E E
35°C 1°C E E
18°C 1°C N E
Schritt-
weite
Zugriff
BE HF
Daikin RoCon+ HP Daikin Regelung RoCon+ HP1
008.1447899_00 – 09/2019 – DE
Betriebsanleitung
99
Page 100
7 Parametereinstellungen
Parameter Einstellbereich
Min / Max
Vorlauftempe­ratur Kühlbe­trieb
Kühlsollwert Korrektur
Interlink Tem­peraturredukti­on
Tab.20-16 Parameter in Menü "Kühlen"
8 - 30°C Nur wenn Parameter [Witterungsgeführt] = Vorlauftemperatur fix:
Einstellung der Kühlvorlauf-Solltemperatur (Festwert) bei aktivem Kühlbe­trieb.
-5,0 - +5,0K Parallelverschiebung der Kühl-Kennlinie um den eingestellten Wert. 0,0K 1K N E
1 - 50K Nur wenn Parameter [Interlinkfunktion] = Ein:
Kühlvorlauf-Solltemperatur wird bei geschlossenem RT-Schaltkontakt Küh­len um den eingestellten Wert reduziert (siehe Parameter [Interlinkfunkti­on]). Anforderung z. B. durch HP convector.
Beschreibung Werks-
7.6.5 Menü: Warmwasser
[→Hauptmenü →Konfiguration →WW]
Parameter Einstellbereich
Min / Max
Max. Warm­wasser Lade­zeit
Warmwasser Sperrzeit
Warmwasser Hysterese
Wartezeit ext. Wärmeerzeu­ger
Solar Funktion Dient zum Herabsetzen der Solltemperatur des Warmwasserspeichers, um
Zirkulations­pumpe An­steuerung
Zirkulations­pumpe Inter­vall
Antilegionellen Tag
10 – 240min Einstellung der maximalen Dauer eines Warmwasserbereitungszyklus. Da-
nach Abbruch der Warmwasserbereitung, wenn die aktuelle Warmwasser­temperatur nicht den eingestellten Sollwert in Parameter [Warmwasser­temperatur Soll 1] erreicht.
0 – 180min Einstellung der Sperrzeit nach Abschluss oder Abbruch eines Warmwas-
serbereitungszyklus. Die erneute Anforderung einer Warmwasserbereitung wird frühestens nach Ablauf dieser Sperrzeit bedient.
2 - 20K Schaltschwelle Warmwasserladung
Einstellung der Temperaturdifferenz, um die die Temperatur im Warmwas­serspeicher gegenüber der gerade gültigen Warmwasser-Solltemperatur [Warmwassertemperatur Soll] absinken darf, bevor die Wärmepumpe für die Warmwasserladung angeschaltet werden soll.
20 - 95min Verzögerungszeit, ab wann der zusätzliche Wärmeerzeuger die Wärme-
pumpe bei einer Warmwasserladung unterstützen darf (siehe Kap. 4.5).
den Ertrag einer angeschlossenen Solaranlage zu erhöhen. Der Sollwert der Warmwassertemperatur wird hierbei in Abhängigkeit der Außentempe­ratur und unter Einhaltung der Sicherheitsfunktionen eingestellt. Zudem werden folgende Parameter festgelegt: Warmwasser Hysterese = 5K; Ge­bäudedämmung = Normal
Aus Deaktiviert
Ein Aktiviert, wenn zusätzlich der Schaltkontakt EXT (J8) geschlossen ist
Einstellung zur Ansteuerung einer Zirkulationspumpe. Verwendung in Frankreich nicht zulässig!
Aus Optionale Zirkulationspumpe wird synchron zum aktiven Schaltzeitpro-
gramm zur Warmwasserbereitung angesteuert.
Ein Optionale Zirkulationspumpe wird nach dem Schaltzeitprogramm [Zirkulati-
onsprogramm] angesteuert. Einstellung der Intervallsteuerung für optionale Zirkulationspumpe. Ver-
wendung in Frankreich nicht zulässig!
Aus Deaktiviert. Die Zirkulationspumpe läuft während der Freigabezeiten des
zugewiesenen Schaltzeitprogramms (Parameter [Zirkulationspumpe An­steuerung]) permanent durch.
1 – 15min Die Zirkulationspumpe läuft getaktet (Taktverhältnis: Pumpenlaufzeit = Ein-
stellwert pro 15min). Einstellung des Tages zur thermischen Desinfektion des Warmwasserspei-
chers.
Aus Keine thermische Desinfektion
Montag
...
Sonntag
Täglich Tägliche thermische Desinfektion
Tag der thermischen Desinfektion
Beschreibung Werks-
Schritt-
einstellung
18°C 1°C E E
5K 1K N E
einstellung
60min 10min N E
30min 10min N E
7K 1K E E
50min 1min E E
Aus 1min E E
Aus - E E
weite
Schritt-
weite
- E E
- E E
Zugriff
BE HF
Zugriff
BE HF
Betriebsanleitung
100
Daikin Regelung RoCon+ HP1
Daikin RoCon+ HP
008.1447899_00 – 09/2019 – DE
Loading...