6.4Piping diagram for refrigerant circuit .......................................... 37
7 Notes38
Installation manual
2
Heat pump (indoor unit) with integrated heat accumulator
Daikin Altherma ETS(X/H)(B)-D
008.1448499_00 – 06/2019 – EN
1General safety precautions
1.1Particular safety instructions
1 General safety precautions
WARNING
Devices that have not been set up and
installed correctly can impair the function of the device and/or cause serious
or fatal injury to the user.
▪ Work on the indoor unit (e.g. set-up,
inspection, connection and initial
commissioning) may only be carried
out by persons who are authorised
and have successfully completed
qualifying technical or vocational
training and who have taken part in
advanced training sessions recognised by the relevant responsible authorities for the specific activity.
These include, in particular, certified
heating engineers, qualified electricians and HVAC specialists
who, because of their professional
training and expert knowledge,
have experience in the professional
installation and maintenance of heating, cooling and air conditioning systems as well as hot water storage
tanks.
WARNING
Disregarding the following safety instructions may result in serious physical injury or death.
▪ This device may only be used by
children aged 8 and above and by
persons with restricted physical,
sensory or mental capabilities or with
a lack of experience and knowledge
if they are under supervision or if
they have been instructed in the safe
use of the equipment and understand the dangers arising from it.
Children must not play with the
device. Cleaning and user mainten-
ance must not be carried out by
children without supervision.
▪ Establish the power supply in ac-
cordance with IEC60335-1, via a
separate isolator which separates all
poles with a contact opening distance that provides full disconnection
in accordance with overvoltage category III.
▪ All electrical work must only be car-
ried out by electrically qualified experts and with consideration of the
local and national regulations and
the instructions in this manual.
Ensure that a suitable electrical circuit is used.
Insufficient load capacity of the electrical circuit or improperly executed
connections can result in electric
shock or fire.
▪ The customer must install a pressure
relief device with a rated over-pressure of less than 0.6MPa (6bar).
The connected drain line must have
a continuous gradient and a free outlet in a frost-free environment (see
Chap. 3.3).
▪ Water may drip out of the drain line
of the pressure relief device. The
drain opening must be left open to
atmosphere.
▪ The pressure relief device must be
operated regularly in order to remove scale deposits and to make
sure it is not blocked.
▪ The storage tank and hot water cir-
cuit can be drained. The instructions
in "Temporary decommissioning" in
the reference manual for the fitter
must be complied with.
1.1.1Observing the instructions
▪ The original documentation is written in German. All other lan-
guages are translations.
▪ Please read this manual carefully and thoroughly before proceed-
ing with the installation or modification of the heating system.
▪ The precautionary measures described in this document cover
▪ The installation of the system and all activities described in this
manual and the applicable documents for the installer must be
carried out by an approved installer.
Documentation set
This document is part of a documentation set of other applicable
documents.The complete set comprises:
▪ Installation manual for the indoor unit (format: paper – included in
the indoor unit scope of delivery)
▪ Operating instructions for the indoor unit (format: paper – included
in the indoor unit scope of delivery)
▪ Operating manual for the heat pump (format: paper – included in
the indoor unit scope of delivery)
▪ Installation manual for the outdoor unit (format: paper – included
in the outdoor unit scope of delivery)
▪ Installation instructions for optional components (format: paper –
included in the scope of delivery of the respective component)
▪ Installer reference guide of the indoor unit (format: digital)
▪ Installer reference guide of the outdoor unit (format: digital)
The reference guides contain the complete set of technical data, a
detailed description of best practices and information on maintenance, troubleshooting and decommissioning.
The digital documents and the latest editions of the supplied documentation are available on the regional Daikin website or, on request, from your dealer. The Daikin website is easy to access using
the QR code on your device.
1.1.2Meaning of warnings and symbols
Warnings in this manual are classified according to their severity and
probability of occurrence.
DANGER
Indicates an immediate danger.
Disregarding this warning can lead to serious injury or
death
WARNING
Indicates a potentially dangerous situation
Disregarding this warning may result in serious physical in-
jury or death.
CAUTION
Indicates a situation which may cause possible damage
Disregarding this warning can cause damage to property
and the environment and result in minor injuries.
This symbol identifies user tips and particularly useful information, but not warnings or hazards
Special warning signs
Some types of danger are represented by special symbols.
Electric current
Danger of explosion
Risk of burns or scalds
Risk of poisoning
Validity
Some information in this manual has limited validity. The validity is
highlighted by a symbol.
Heat pump outdoor unit
Heat pump indoor unit
FWXV-ATV3
Observe the specified tightening torque
Only applies to devices with unpressurised solar system
connection (DrainBack).
Only applies to devices with a bivalent solar system connection (Biv).
Only applies to indoor units with cooling function
Handling instructions
1 Handling instructions are shown as a list. Actions where the se-
quential order must be adhered to are numbered.
è
Results of actions are identified with an arrow.
1.2Safety instructions for installation
and operation
1.2.1General
WARNING
Devices that have not been set up and installed correctly
can impair the function of the device and/or cause serious
or fatal injury to the user.
▪ Work on the indoor unit (e.g. set-up, inspection, con-
nection and initial commissioning) may only be carried
out by persons who are authorised and have successfully completed qualifying technical or vocationaltraining and who have taken part in advanced training
sessions recognised by the relevant responsible authorities for the specific activity. These include, in particular, certified heating engineers, qualified electri-
cians and HVAC specialists who, because of their
professional training and expert knowledge, have
experience in the professional installation and maintenance of heating, cooling and air conditioning systems
as well as hot water storage tanks.
▪ Before starting any work on the indoor unit, switch off
the external main switch and secure it against unintentional switch-on.
▪ Do not leave any tools or other objects below the hood
of the device after finishing installation or maintenance
work.
Avoiding danger
The indoor unit conforms to the state of the art and meets all recognised technical requirements. However, improper use may result in
serious physical injuries or death, as well as property damage. To
prevent such risks, only install and operate the devices:
▪ as stipulated and in perfect condition,
▪ with an awareness of safety and the hazards involved.
This assumes knowledge and use of the contents of this manual, of
the relevant accident prevention regulations as well as the recognised safety-related and occupational health rules.
Before working on the hydraulic system
▪ Work on the system (such as installation, connection and initial
commissioning, for example) must only be carried out by persons
who are authorised, who have successfully completed qualifying
technical or vocational training for the respective activity and who
have taken part in advanced training sessions recognised by the
relevant responsible authority.
▪ When carrying out any work on the system, switch off the main
switch and secure against being switched on inadvertently.
Installation manual
4
Heat pump (indoor unit) with integrated heat accumulator
Daikin Altherma ETS(X/H)(B)-D
008.1448499_00 – 06/2019 – EN
1 General safety precautions
▪ Seals must not be damaged or removed.
▪ Make sure that the safety valves comply with the requirements of
EN12828 when connecting on the heating side, and with the requirements of EN12897 when connecting on the domestic water
side.
1.2.2Intended use
The indoor unit may only be used for domestic hot water preparation, as a room heating system and, depending on its design, as a
room cooling system.
The indoor unit must only be installed, connected and operated according to the indications in these instructions.
Only the use of a suitable outdoor unit approved by the manufacturer
is permitted.
ETSH16P30D
ETSHB16P30D
ETSX16P30D
ETSXB16P30D
ETSH16P50D
ETSHB16P50D
ETSX16P50D
ETSXB16P50D
EPRA14DAV3P
EPRA16DAV3P
EPRA18DAV3P
EPRA14DAW1P
EPRA16DAW1P
EPRA18DAW1P
Tab.1-1Permissible combinations
Any other use outside the intended use is considered as improper.
The operator alone shall bear responsibility for any resulting damage.
Intended use also includes compliance with the maintenance and inspection conditions. Replacement parts must at least satisfy the
technical requirements defined by the manufacturer. This is the
case, for example, with original spare parts.
1.2.3Device installation room
WARNING
The plastic wall of the storage tank on the indoor unit can
melt under the effects of external heat (>80 °C) and, in the
extreme case, can catch fire.
▪ Only install the indoor unit at a minimum clearance of
1m from other heat sources (>80°C) (e.g. electrical
heater, oil heater, chimney) and combustible materials.
CAUTION
▪ Only install the indoor unit if sufficient load-carrying ca-
pacity of the ground of 1050kg/m2 plus safety margin is
ensured. The ground must be flat, horizontal and level.
▪ Outdoor installation is not permissible.
▪ Installation in an explosion-risk environment is not per-
missible.
▪ The electronic control system must not be exposed to
whether effects like rain and snow under any circumstances.
▪ The storage tank may not be exposed to continuous
direct sunlight, as the UV radiation and the effects of
the weather will damage the plastic.
▪ The indoor unit must be installed protected from frost.
▪ Make sure that the supply company does not provide
corrosive domestic water. Suitable water treatment may
be required.
▪ Always ensure the minimum distances from walls and other ob-
jects (Chap. 3.3).
CAUTION
▪ If a DrainBack solar heating system is connected:
Install the indoor unit far enough under the solar panels
to allow complete emptying of the solar heating system.
(Follow instructions in the DrainBack solar heating sys-
tem manual). An insufficient height difference may lead
to destruction of the DrainBack solar heating system.
▪ The indoor unit must not be operated in rooms with am-
bient temperatures of more than 40°C.
CAUTION
▪ The required concentration may vary depending on the
type of glycol. ALWAYS compare the requirements
from the table above with the specifications provided by
the glycol manufacturer. If necessary, meet the require-
ments set by the glycol manufacturer.
▪ The added concentration of glycol must NEVER ex-
ceed 35%.
▪ If the fluid in the system is frozen, the pump CANNOT
start. Mind that if you only prevent the system from
bursting, the liquid inside might still freeze.
▪ If NO glycol has been added to the system and a power
failure or a pump failure occurs, drain the water from
the system.
▪ When the water inside the system is stationary, it can
easily freeze and thus damage the system.
CAUTION
Glycol absorbs water from its environment. Therefore do
NOT add glycol that has been exposed to air. Leaving the
cap off the glycol container causes the concentration of
water to increase. The glycol concentration is then lower
than assumed. As a result, the hydraulic components
might freeze up after all. Take preventive actions to ensure
a minimal exposure of the glycol to air.
To guarantee frost protection in the event of a power failure, glycol can be added to the heating water circuit.
Please observe the notes in Chap. 3.8.4.
Measures for desalination, softening or hardness stabilisation are
necessary if the filling and top-up water have a high total hardness
(>3mmol/l – total of the calcium and magnesium concentrations,
calculated as calcium carbonate). We recommend the use of Fernox
KSK limescale and corrosion protector. For other properties deviating from the minimum requirements, suitable conditioning measures
are necessary to maintain the required water quality.
Using filling water and top-up water which does not meet the stated
quality requirements can cause a considerably reduced service life
of the device. The responsibility for this lies solely with the operator.
1.2.6Heating system and sanitary connection
▪ Create a heating system according to the safety requirements of
EN12828.
▪ The plumbing connection must comply with the requirements of
EN12897. The requirements of the following must also be observed:
▪ EN1717 – Protection against pollution of potable water installa-
tions and general requirements of devices to prevent pollution
by backflow
▪ EN61770 – Electric appliances connected to the water mains –
Avoidance of backsiphonage and failure of hose-sets
▪ EN806 – Specifications for installations inside buildings con-
veying water for human consumption
▪ and, in addition, the country-specific legislation.
When operating the indoor unit, the storage tank temperature may
exceed 65°C.
▪ For this reason, some form of scalding protection needs to be in-
cluded when you install the system (hot water mixing device, e.g.
VTA32).
If the indoor unit is connected to a heating system with steel pipes,
radiators or non-diffusion-proof floor heating pipes, sludge and chips
can enter the hot water storage tank and cause blockages, local
overheating or corrosion damage.
▪ To prevent possible damage, install a dirt filter or sludge separator
into the heating return flow of the system (SAS 1 or SAS 2).
▪ The dirt filter must be cleaned at regular intervals.
1.2.7Operation
The indoor unit:
▪ Do not operate until all installation and connection work is com-
pleted.
▪ Only operate with a completely full storage tank (check level indic-
ator) and heating circuit.
▪ Operate at a maximum pressure of 3bar.
▪ Only connect with a pressure reducer on the external water supply
(supply line).
▪ Only operate if the protective cover is installed.
The specified servicing intervals should be adhered to and inspec-
tion work must be carried out.
1.3Maintenance, troubleshooting and
decommissioning
Work for maintenance, troubleshooting and decommissioning must
not be carried out without knowledge of the relevant safety precautions and in the event of disposal of the country-specific guidelines.
Please refer to the corresponding information in the installer reference guide.
Recommendations for disposal
We designed the indoor unit in an environmentally friendly manner.
During the disposal process, the only waste created is that which
can be used for material or thermal recycling. The materials used
that are suitable for recycling can be sorted into individual types.
Thanks to the environmentally friendly design of the indoor unit, we have established requirements to ensure environmentally friendly disposal. Proper disposal in compliance with the
respective national regulations of the country of use is the responsibility of the user/owner.
Installation manual
6
Heat pump (indoor unit) with integrated heat accumulator
Daikin Altherma ETS(X/H)(B)-D
008.1448499_00 – 06/2019 – EN
The designation of the product means that electrical and
electronic products may not be disposed of together with unsorted
domestic waste.
Proper disposal in compliance with the respective national regulations of the country of use is the responsibility of the user/owner.
▪ Disassembly of the system, handling of coolant, oil and other
parts may only be carried out by a qualified fitter.
▪ Disposal may only be carried out by an organization that special-
ises in reuse, recycling and recovery.
Further information is available from the installation company or the
responsible local authorities.
1.4Warranty conditions
The legal guarantee conditions fundamentally apply. Our more extensive warranty conditions can be found in the Internet. Ask your
suppliers if necessary.
Incorrect installation, commissioning and maintenance will void the
warranty. If you have any questions, please contact our customer
service.
Warranty claims can only be made if the annual maintenance work is
demonstrably carried out regularly according to the information in the
installer reference guide.
ETS(X/H)B only)
6Circulation pump30Manual vent valve
7Pressure relief valve31Outdoor unit water inlet
connection
7aCirculation stop valve
(accessory)
32Outdoor unit water outlet
connection
Installation manual
9
2 Product description
ItemDesignationItemDesignation
8Automatic vent valve33Status display
9Storage tank (polypropyl-
ene, double-walled jacket
34Ball valve (heating cir-
cuit)
with PUR hard foam heat
insulation)
10Filling and draining con-
nection or solar return
flow connection
11Mount for solar controller
or handle
12Heat exchanger (stain-
less steel) for domestic
35Combined filling and
draining valve (heating
circuit)
37
Storage tank temperature
sensor
t
DHW1
38Diaphragm expansion
vessel connection
hot water heating
13Heat exchanger (stain-
39Controller housing
less steel) for storage
tank charging or heating
support
14Biv heat exchanger
(stainless steel) for charging with external heat
41EKSRPS4 Optional:
Solar control and pump
unit
generator (e.g. pressurised solar system)
15Connection for optional
electrical backup heater
EKBUxx
16Solar inflow layering pipe 3UV
17Fill level indicator (tank
3UVB1
3-way switch valve (in-
ternal heat generator cir-
cuit)
3-way switch valve (hot
DHW
water/heating)
DSPressure sensor
water)
18Optional: electric backup
FLSFlowSensor
heater (EKBUxx)
19Sensor pocket for tank
temperature sensor t
20Pressure-free storage
water
21Solar zoneRoCon
DHW1
t
Inflow temperature
V
sensor
t
Backup heater inflow
V,BH
temperature sensor
Controller control panel
+ B1
22Hot water zoneMAG Diaphragm expansion
vessel
23Safety overflow connec-
FSFlow switch
tion
24Mount for handle
Tab.2-1Legend for Fig. 2-1 to Fig. 2-4
2.2Function of the 3-way switch
valves
Fig.2-5Function of 3-way switch valve
Installation manual
10
Heat pump (indoor unit) with integrated heat accumulator
Daikin Altherma ETS(X/H)(B)-D
008.1448499_00 – 06/2019 – EN
3Set-up and installation
WARNING
Cooling systems (heating pumps), climate control systems
and heating devices that have been set up and installed incorrectly can both endanger human life and health and be
impaired in their function.
▪ Work on the indoor unit (such as installation, repair,
connection and initial commissioning, for example)
must only be carried out by persons who are authorised, who have successfully completed qualifying technical or vocational training for the respective activity
and who have taken part in advanced training sessions
recognised by the relevant responsible authority. These
include, in particular, certified heating engineers, qualified electricians and HVAC specialists who, because of
their professional training and expert knowledge, have
experience in the professional installation and maintenance of heating, cooling and air conditioning systems
and heat pumps.
Incorrect set-up and installation would render the manufacturer's
guarantee void. If you have questions, please contact our Technical
Customer Service.
3.1Dimensions and connection
dimensions
3 Set-up and installation
Fig.3-2Dimensions, top of unit – type ETS(X/H)B16P30D
Fig.3-3Dimensions, side view – type ETS(X/H)B16P50D
Installation manual
11
3 Set-up and installation
Fig.3-4Dimensions, top of unit – type ETS(X/H)B16P50D
ItemDesignationItemDesignation
1Solar inflow7Outdoor unit water inlet
connection
2Cold water8Bivalent feed (type
ETS(X/H)B only)
3Hot water9Bivalent return (type
ETS(X/H)B only)
4Heating flow
5Heating return flowAfront
6Outdoor unit water outlet
connection
Tab.3-1Legend for Fig. 3-1 to Fig. 3-4
Brear
3.2Transport and delivery
WARNING
When unfilled, the indoor unit is top-heavy and could tip
over during transport. That could put persons in danger or
damage the unit.
▪ Secure the indoor unit well, transport carefully, use the
handles.
The indoor unit is delivered on a pallet. All industrial trucks, such as
lifting trucks and forklift trucks, are suitable for transport.
Scope of delivery
▪ Indoor unit (pre-mounted),
▪ Bag of accessories (see Fig. 3-5),
▪ Document pack.
Fig.3-5Contents of bag of accessories
A Handles (only required for transport)
B Cover panel
C Hose connecting piece for safety overflow
D Assembly wrench
E Ball valve
F Flat gasket
G O-ring
H Cable tie
I Securing clip
J Venting hose
K Drain hose cover
L Controller rotary switch
M Hood screws
For further accessories for the indoor unit, see price list.
3.3Installing the heat pump
3.3.1Selecting the installation site
The installation site of the indoor unit must meet the minimum requirements below (see also Chap. 1.2.3).
Installation area
▪ The base must be level and smooth and have sufficient ground
load-bearing capacity of 1050kg/m² plus safety factor. Install a
pedestal if necessary.
▪ Observe the installation dimensions (see Chap. 3.1).
Installation manual
12
Heat pump (indoor unit) with integrated heat accumulator
Daikin Altherma ETS(X/H)(B)-D
008.1448499_00 – 06/2019 – EN
3 Set-up and installation
Minimum distance
DANGER: RISK OF BURNING
The plastic wall of the storage tank on the indoor unit can
melt under the effects of external heat (>80°C) and, in the
extreme case, can catch fire.
▪ Only install the indoor unit at a minimum clearance of
1m from other heat sources (>80°C) (e.g. electrical
heater, oil heater, chimney) and combustible material.
CAUTION
If the indoor unit is not installed at a sufficient dis-
tance below the flat solar panels (the top edge of the storage tank is higher than the bottom edge of the solar panels), the unpressurised solar system in the outdoor area
will not be able to drain completely.
▪ When a solar connection is used, install the indoor unit
low enough under the flat solar panels (observe the
minimum gradient of the solar connection lines).
Recommended minimum distances:
From the wall: (rear) ≥100mm, (sides) ≥500mm
From the ceiling: ≥1200mm, at least 480mm.
Distances from the outdoor unit:
When selecting the installation location, the data in the Tab. 3-2
must be taken into account.
Maximum line length between the indoor and outdoor units
Maximum height difference between the indoor and
outdoor units
Tab.3-2
50m
10m
Installation
3.3.2Installing the device
WARNING
When unfilled, the indoor unit is top-heavy and could tip
over during transport. That could put persons in danger or
damage the unit.
▪ Secure the indoor unit well, transport carefully, use the
handles.
Precondition
▪ The installation site complies with applicable country-specific reg-
ulations and meets the minimum requirements described in
Chap. 3.3.1.
Fig.3-6Installing the handles
A Handle
B Cover panel
F Threaded piece
1 Remove the packaging and dispose of it in an environment-
friendly manner.
2 Pull the cover screens off the storage tank (Fig. 3-6, itemB) and
unscrew the threaded fittings (Fig. 3-6, itemF) from the openings at which the handles are to be fitted.
3 Screw the handles (Fig. 3-6, itemA) into the now uncovered
threaded holes.
4 Carefully transport the indoor unit to the installation site, use the
handles.
5 Install the indoor unit at the installation site.
1 Undo the screws (1.).
2 Press the lateral holding burls upwards with your fingers (2.),
stem from above with the thumbs.
3 Remove the front screen to the front (3.).
Fig.3-8Remove the protective cover
Fig.3-7Remove the front screen
3.4.2Remove the protective cover
1 Unhook the protective cover from the rearward facing holding
burls (1.), lift at the back (2.) and remove to the front (3.).
Fig.3-9Without protective cover
3.4.3Moving the controller housing to the
service position
To facilitate work on the hydraulics of the indoor unit, the control box
can be moved to the service position.
1 Loosen the screws(1) of the holder of the controller housing.
Fig.3-10Moving the controller housing to the service position
2 Remove the controller housing from the front and insert it into
the bracket with the hooks on the rear brackets.
Installation manual
14
Heat pump (indoor unit) with integrated heat accumulator
Daikin Altherma ETS(X/H)(B)-D
008.1448499_00 – 06/2019 – EN
Fig.3-11Controller housing in the service position
3.4.4Open the controller housing
To make the electrical connections, the controller housing itself must
be opened. This can be done in both the normal and the service position.
1 Loosen the front screw.
2 Push the cover upwards and pull it away to the front.
3 Set-up and installation
3.4.5Removing the bottom thermal insulation
CAUTION
The thermal insulation consists of pressure-sensitive EPP
moulded parts that can be easily damaged if not handled
correctly.
▪ Only remove the thermal insulation in the order stated
below and in the stated directions.
▪ Do not use force.
▪ Do not use tools.
1 Remove the thermal insulation in the following order:
▪ Pull the side insulating element off horizontally (itemA).
▪ Pull the rear insulating element off horizontally (itemB).
▪ Pull the front insulating element off horizontally (itemC).
Fig.3-12Open the controller housing
3 Hook in the cover on the controller housing with the lateral
hooks.
Fig.3-14Removing the top thermal insulation
2 As required: Remove the bottom thermal insulation in the fol-
lowing order:
▪ Pull the side insulating element off vertically (itemA).
▪ Pull the rear insulating element off vertically (itemB).
The thermal insulation is installed in reverse order.
3.4.6Opening the vent valve
1 Removing the thermal insulation (see Chap. 3.4.5).
2 Open the vent valve on the pump by one turn.
Fig.3-16Opening the vent valve
3.4.7Aligning the connections of the heating
inflow and return flow
CAUTION
When working on the hydraulics, pay attention to the installation position of the O-rings to avoid damaging them
and causing leaks.
▪ Always place O-rings on the part to be inserted after
disassembly or before assembly (see Fig. 3-19).
▪ The heating lines must be connected free of tension via
the plug connectors. Establish a suitable strain relief
especially when connecting with flexible lines (not open
to diffusion!) (see Fig. 3-31).
The device is supplied with upwards aligned connections as standard. The following conversion steps are required in order to direct
the connections to the rear out of the device:
1 Remove the protective cover and top thermal insulation
(seeChap. 3.4.2).
Fig.3-18Aligning the heating inflow and return flow upwards
2 Pull the two securing clips off the connection couplings
(Fig. 3-18, itemC).
3 Pull off the two connection couplings (Fig. 3-18, itemB).
CAUTION
If the plug brackets cannot be put on properly, the couplings can be detached from their mountings to ensure a
very strong or continuous escape of liquid can occur.
▪ Before putting on a plug bracket, make sure that the
stirrup engages in the coupling groove. To do so, insert
the coupling far enough into the mounting that the
groove is visible through the plug bracket mounting.
▪ Insert the plug bracket up to the end stop.
The connections of the heating inflow and return flow can be directed upwards or backwards in order to adapt it optimally to the structural conditions of the installation site.
Fig.3-17Variants for aligning the heating feed and return
Fig.3-19Hydraulic system plug connectors
4 Remove the retaining plate (Fig. 3-18, itemA).
5 Pull off the sealing plug securing clip (Fig. 3-18, itemD).
6 Pull out the sealing plug (Fig. 3-18, itemE).
7 Turn the elbow (Fig. 3-18, itemH) 90° to the rear.
8 Pull the securing clip off the manifold (Fig. 3-18, itemG).
9 Carefully pull the manifold (Fig. 3-18, itemF) so far backwards
out of its horizontal mounting that the retaining plate (Fig. 3-20,
itemA) can be pushed vertically in between.
Installation manual
16
Heat pump (indoor unit) with integrated heat accumulator
Daikin Altherma ETS(X/H)(B)-D
008.1448499_00 – 06/2019 – EN
Fig.3-20Heating inflow and return flow connections aligned to the
rear
10 Slide the retaining plate between the manifold and its horizontal
mounting and insert the manifold (Fig. 3-20, itemF) back into its
mounting through the middle hole of the retaining plate.
11 Secure the manifold with securing clip (Fig. 3-20, itemG) in its
mounting again.
12 Insert the two connection couplings (Fig. 3-20, itemB) into the
lateral mountings through the retaining plate.
13 Secure the two connection couplings with securing clips
(Fig. 3-20, itemC) in their mountings.
14 Insert the sealing plug (Fig. 3-20, itemE) into the upper mount-
ing.
15 Secure the sealing plug with securing clip (Fig. 3-20, itemD).
16 Cut out side openings in the thermal insulation (Fig. 3-21,
itemA) using a suitable tool.
3 Set-up and installation
Fig.3-22Making the hood opening
3.4.9Installing the rotary switch of the
controller
1 Place the rotary switch on the rotary switch holder of the RoCon
+ HP and press it on.
Fig.3-23Putting on the rotary switch
3.4.10Securing the hood
After the installation is fully completed:
1 Attach the screws for fixing the hood (accessory bag).
Fig.3-21Cut-out in thermal insulation
3.4.8Making the hood opening
1 With the heating inflow and return flow directed upwards: Cut the
2 Place the front cover straight over the rotary switch of the RoCon
+ HP. Press on the top and bottom until the front screen is securely engaged again.
Installation manual
17
3 Set-up and installation
3.5Installing optional accessories
3.5.1Installation of electric backup heater
(EKBUxx)
INFORMATION
If the ceiling height is low, the storage tank must be tilted to
install the backup heater when empty. This must be done
before any further installation steps.
The indoor unit provides the option of installing an electrical auxiliary
heater (backup heater EKBUxx). For example, renewable energy
can be used as an additional heat source.
INFORMATION
A separate manual containing instructions about installation and operation is included with this component.
3.5.2Installation of the external heat generator
connection set
The connection set for external heat generators must be installed to
control an electrical backup heater or another external heat generator.
1 Open the housing by removing the screw.
2 Remove additional components from the housing (strain relief
clip, cable tie, grommet).
3 Attach the connection set to the controller housing of the indoor
unit. To do this, insert the hooks(1) of the connection set into
the slots of the controller housing(2); then press the connection
set downwards.
7 After the installation and the electrical connections (see
Chap. 3.6 or Chap. 3.7) have been completed, replace the cover
and close it with the screw.
3.5.3Installation of the DB connection kit
The optional DB connection kit allows better access for connecting
the DrainBack pipe (solar feed).
Fig.3-27DB connection kit
A DB pipe connection (solar inflow)
B FlowSensor (not part of the DB connection kit, but included
with EKSRPS4)
C Flow rate limiter (FlowGuard)
D
Solar inflow connection on the storage tank
Fig.3-25Fitting the connection set
4 Attach the grommet(3) to the bushing between the connection
set(A) and the controller housing(B).
5 Attach the fastening rivet(4).
3.5.4Installation of the P connection kit
The optional P connection kit for Biv device types allows better access for connecting the inflow and return flow lines of a pressurised
solar system or another external heat generator on the storage tank.
The kit contains two thermally insulated corrugated pipes that are
connected to the connections of the storage tank via a union nut. At
the other end of the corrugated pipes there is an adapter for different
connection sizes of the supply and return pipes.
Fig.3-26Cable gland
6 Guide the cable of the Ultra EHS PCB through the cable grom-
met and connect it to the RoCon BM2C (see Fig. 3-41).
Installation manual
18
Fig.3-28P connection kit for Biv device types
A Connection for inflow (red)
B Connection for return flow (blue)
Daikin Altherma ETS(X/H)(B)-D
Heat pump (indoor unit) with integrated heat accumulator
008.1448499_00 – 06/2019 – EN
3 Set-up and installation
3.6Water connection
Important information
CAUTION
If the indoor unit is connected to a heating system with
steel pipes or radiators or non-diffusion-proof floor heating pipes, slurry and swarf could enter the hot water storage tank and cause blockages, local overheating or cor-rosion damage.
▪ Rinse supply lines before filling the device.
▪ Rinse out the heat distribution network (in the existing
heating system).
▪ Install a dirt filter or sludge separator in the heating re-
turn flow (see Chap. 1.2.6).
CAUTION
If the indoor unit is connected to a cold water line where
steel pipes are used, chips can get into the stainless steel
corrugated pipe heat exchanger and remain there. This
can lead to contact corrosion damage and subsequently to
leakage.
▪ Flush the feed pipes before filling the heat exchanger.
▪ Install the dirt filter in the cold water supply (e.g. SAS 1
or SAS 2).
CAUTION: BIV ONLY
If the heat exchanger for pressurised solar system charging (see Chap. 3.1, items8 + 9) is connected to an ex-ternal heater (e.g. wood-burning boiler), the indoor unit
can be damaged or destroyed due to an excessively high
inflow temperature at these connections.
▪ The inflow temperature of the external heater should
be limited to max. 95°C.
CAUTION
Corrosion may be caused by air entering the heating water
network and by a quality of the heating water that does not
comply with the requirements in accordance with
Chap. 1.2.5. Corrosion products (particles) thus created
may clog pumps and valves and cause malfunctions.
▪ Device may not be connected by permeable, flexible
lines.
▪ Install the indoor unit close to the withdrawal point to dispense
with the need for a circulation line. If a circulation line is mandatory, it must be installed according to the schematic diagrams in
"Hydraulic system connection" in the installer reference guide.
3.6.1Connecting hydraulic lines
DANGER: RISK OF BURNING
There is a danger of scalding at hot water temperatures
over 65°C. This is possible when using solar energy if an
external heater is connected, the Legionella protection is
activated, or the target hot water temperature is set to be
greater than 65°C or if the Smart-Grid function is activated.
▪ Install scalding protection (hot water mixer device (e.g.
VTA32)).
INFORMATION
The indoor unit is equipped with a pressure sensor. The
system pressure in monitored electronically and can be
displayed with the device switched on.
Nevertheless, we recommend installing a mechanical pressure gauge between the indoor unit and the diaphragm expansion vessel, for example.
▪ Install the manometer so that it is easy to see when
filling.
Prerequisite: Optional accessories (e.g. solar, backup heater) are
mounted on the Daikin Altherma 3 H HT ECH2O as specified in the
enclosed instructions.
1 Check cold water pressure (maximum 6bar).
▪ If a higher pressure is present in the domestic water pipe, a
pressure reducer will need to be installed.
2 Make the hydraulic connections to the Daikin Altherma 3 H HT
ECH2O.
▪ Refer to Fig. 3-1 up to Fig. 3-4 and from Tab. 2-1 for the posi-
tion and dimensions of the heater connections and the outdoor
unit connections. The details of the hydraulic connection from
the indoor unit to the water inlet and outlet of the outdoor unit
can be seen in Fig. 3-29.
INFORMATION
In accordance with EN12828, a safety valve that limits the
maximum permissible operating pressure in the heating
system must be installed on or in the immediate vicinity of
the heat generator. There may not be any hydraulic blocking elements between the heat generator and the safety
valve.
Any steam or heating water that may escape must be
drained by a suitable blow-off line with constant gradient in
a frost-protected, safe and observable manner.
A diaphragm expansion vessel suitably sized and preset
for the heating system must be connected to the Daikin
Altherma 3 H HT ECH2O. There may not be any hydraulic
blocking elements between the heat generator and the diaphragm expansion vessel.
We recommend installing a mechanical pressure gauge for
filling the heating system.
▪ For potable water lines, observe the provisions of EN806,
DIN1988 and the additional applicable national regulations for
potable water installation.
Fig.3-29Establishing the hydraulic connection to the outdoor unit
▪ Pay attention to the stipulated tightening torque (see
Chap. 6.2). To avoid damage, apply the necessary counter-
torque with a suitable tool, see Fig. 3-30.
Installation manual
19
3 Set-up and installation
Fig.3-30Establishing the heating connections
▪ Install the line so that the sound insulation hood can be posi-
tioned easily after installation.
▪ For rearward facing connections: Support hydraulic lines suit-
ably according to the spatial conditions, see Fig. 3-31.
Fig.3-32Installation of drain hose at safety overflow
6 Connect the discharge fitting on the cover (Fig. 2-2, item30) to
the waste water installation with the enclosed hose section.
7 Connecting a diaphragm expansion vessel (see Fig. 3-33)
▪ Connect a suitably dimensioned and preset diaphragm expan-
sion vessel for the heating system. There may not be any hydraulic blocking elements between the heat generator and the
safety valve.
▪ Position the diaphragm expansion vessel in an easily access-
ible place (maintenance, parts replacement)
Fig.3-31Supporting rear-facing hydraulic lines
▪ Connect the water for filling or refilling the heating system as
per EN1717 so that contamination of the drinking water due to
return flow is reliably prevented.
3 Connect the drain line to the safety overpressure valve and dia-
phragm expansion vessel as per EN12828.
▪ Check the seat of the drain hose on the pressure relief valve.
▪ If necessary, connect and install a separate hose.
4 Carefully insulate pipework against heat loss and to avoid con-
densation (insulation thickness at least 20mm).
▪ Water shortage protection: the controller's pressure and tem-
perature monitoring function reliably shuts off the Daikin
Altherma 3 H HT ECH2O if there is a shortage of water. No additional water shortage protection is needed in the construction.
▪ Avoid damage caused by deposits and corrosion: see
Chap. 1.2.5
5 Connect the drain hose to the hose connecting piece for the
safety overflow (Fig. 2-3, item23).
▪ Use transparent drain hose (draining water must be visible).
▪ Connect the drain hose to an adequately dimensioned waste
water installation.
▪ Drain should not be lockable.
Fig.3-33Mounting the diaphragm expansion vessel
3.7Electrical connection
DANGER: RISK OF ELECTROCUTION
Touching live parts can result in an electric shock and
lead to potentially fatal injuries and burns.
▪ Before beginning work on live parts, disconnect all of
the systems circuits from the power supply (switch off
external main switch, disconnect fuse) and secure
against unintentional restart.
▪ Establishment of the electrical connection and work on
electrical components should only be performed by
electrical technicians in compliance with valid standards and guidelines as well as the specifications of the
energy supply company and the instructions in this
manual.
▪ Never make constructional changes to connectors or
other electrical equipment components.
▪ Device covers and service panels must be replaced
as soon as the work is completed.
Installation manual
20
Heat pump (indoor unit) with integrated heat accumulator
Daikin Altherma ETS(X/H)(B)-D
008.1448499_00 – 06/2019 – EN
CAUTION
Increased temperatures can occur in the controller housing
of the indoor unit during operation. This can result in currently-carrying wires from reaching higher temperatures
during operation due to self-heating. For this reason, these
lines need to have a continuous use temperature of 90°C.
▪ For the following connections, only use cables with a
long-term use temperature ≥90°C: Heat pump outdoor
unit and optional: Electric backup heater (EKBUxx)
CAUTION
If the mains cable of the indoor unit is damaged, it must be
replaced by the manufacturer or his customer service or a
similarly qualified person to avoid hazards.
All electronic control and safety devices of the indoor unit are connected ready for use and tested. Modifications on the electrical installation are dangerous and prohibited. The operator alone bears
responsibility for any resulting damage.
Fig.3-34Overall connection diagram – for the electrical connection during the device installation (for the legend and pin assignment of the
Installation manual
22
PCB, see Chap. 6.3)
Daikin Altherma ETS(X/H)(B)-D
Heat pump (indoor unit) with integrated heat accumulator
008.1448499_00 – 06/2019 – EN
3.7.2Position of the printed circuit boards and
terminal strips
3 Set-up and installation
Fig.3-35Position of the printed circuit boards and terminal strips
(for the legend, see Chap. 6.3)
3.7.3Mains connection
A flexible cable for the mains connection is already connected inside
the device.
1 Check the supply voltage (~230V, 50Hz).
2 Disconnect the junction box of the domestic installation.
3 Connect the cable for connecting the indoor unit to the mains to
the domestic installation's junction box (isolator according to
EN60335-1) via an all-pole separating main switch to be installed in the building. Ensure that the polarity is correct.
3.7.4General information on the electrical
connection
1 Check the supply voltage.
2 Set the mains switch to "Off".
3 Switch off the circuit breaker in the junction box of the domestic
power supply.
4 Open the controller housing (see Chap. 3.4.4).
5 Insert the cable through one of the cable glands into the interior
of the controller housing. When cutting and laying cables to be
connected, make sure that the controller housing can be brought
into the service position without any tension.
Fig.3-36Cable gland
6 Make electrical connections according to Chap. 3.7.1 and the
following sections.
7 Effective strain relief in the controller housing by means of cable
ties must be ensured for all cables connected to the indoor unit
(steps 1 – 3, Fig. 3-37).
Fig.3-37Establishing and checking the strain relief
8 Check the holding force of the strain relief (step 4, Fig. 3-37).
9 After the installation is complete: Close the controller housing
again and, if necessary, move it to the normal position.
A separate manual containing instructions about installation and operation is included with this component.
1 Follow the installation steps in Chap. 3.7.4.
2 Connect the heat pump outdoor unit to terminal strip XAG1 (see
Fig. 3-38).
Installation manual
23
3 Set-up and installation
Fig.3-38Connecting the heat pump outdoor unit
INFORMATION
If the heat pump outdoor unit is shut off via a circuit specified by the utility company, the indoor unit is not shut off.
3.7.6Connecting the outside temperature
sensor (optional)
The heat pump outdoor unit has an integrated outside temperature
sensor which is used for weather-compensated inflow temperature
control with frost protection function. The weather-compensated inflow temperature control can be further optimised with the optional
outside temperature sensor.
▪ Choose a location at about one third of the building height (min-
imum distance from floor: 2m) on the coldest side of the building
(north or north-east). Ensure that the location is not near any external heat sources (flues, air ducts), nor subject to direct solar radiation.
▪ Place outside temperature sensors in such a way that the cable
exit points face downwards (prevents the ingress of humidity).
CAUTION
Laying the sensor and mains lines in parallel within an installation conduit can lead to major malfunctions during
controlled operation of the indoor unit.
▪ Always lay the sensor line separately.
1 Connect the outside temperature sensor to a twin-core sensor
line (minimum diameter 1mm2).
2 Lay the sensor line to the indoor unit.
3 Follow the installation steps in Chap. 3.7.4.
4 Connect the sensor line to terminal strip XTA1 (see Chap. 3.7.2).
5 In the controller, RoCon+ HP set the [Outside temperature
sensor] parameter to "On" [→Main menu →Configuration
→Sensors].
Fig.3-39EXT switching contact connection
Operating modeResistance RVTolerance
Standby<680Ω±5%
Heating1200Ω
Reduce1800Ω
Summer2700Ω
Automatic 14700Ω
Automatic 28200Ω
Tab.3-3Resistance values for evaluating the EXT signal
INFORMATION
The input is not considered for resistance values greater
than the value for "Automatic 2".
INFORMATION
The [Heating support (HZU)] function integrated in the RoCon+ HP controller (see the controller operating instructions) makes it unnecessary to connect the EXT connection to the burner blocking contact connection of the solar
system.
3.7.8EBA (external requirement request)
By connecting the EBA switching contact to the indoor unit
(Fig. 3-40) and corresponding parametrisation in its RoCon+ HP
controller, an external switching contact can be used to generate a
heat request. If the switching contact is closed, the indoor unit
switches to heating mode. The feed temperature is regulated to the
temperature set in the [Feed temperature, heating mode] parameter
[→Main menu →Configuration →Heating].
The EBA switching contact has priority over a request from the room
thermostat.
The switching contact is not evaluated in cooling mode, standby,
manual or summer mode. The heating limits are also ignored.
3.7.7External switching contact
Connecting an external switching contact (Fig. 3-39) enables the operating mode of the indoor unit to be switched over.
The current operating mode is switched by a changing resistance
value (Tab. 3-3). The changeover of the operating mode is only effective for a long as the external switching contact is closed.
The operating mode has an effect on the direct circuit of the indoor
unit as well as all other heating circuits connected to this device as
an option.
When special functions (e.g. "Manual operation") are activated, the
input is not evaluated.
Installation manual
24
Fig.3-40EBA switching contact connection
Daikin Altherma ETS(X/H)(B)-D
Heat pump (indoor unit) with integrated heat accumulator
008.1448499_00 – 06/2019 – EN
3.7.9Connecting an external heat generator
INFORMATION
To connect an external heat generator, the connection set
for external heat generators must be installed (see
Chap. 3.5).
For heating support or as an alternative to an electric backup heater,
an external heat generator (e.g. gas- or oil-fired boiler) can be connected to the indoor unit. To connect an external heat generator, the
connection set for external heat generators must be installed (see
Chap. 3.5).
The heat supplied by the external heat generator must be fed to the
unpressurised storage tank water in the hot water storage tank of the
indoor unit.
Implement the hydraulic connection according to one of the two following options:
▪ unpressurised via the connections (solar inflow and solar re-
turn flow) of the hot water storage tank
▪ for ...bivalent indoor unit device types, via the integrated
pressurised solar heat exchanger.
▪ Comply with the instructions on hydraulic connections (see
Chap. 1.2)
▪ Examples of hydraulic connection (see "Hydraulic connection"
in the installer reference guide).
The external heat generator request is connected on PCB RTX-EHS
(see Fig. 3-41) via a relay. Electrical connection to the indoor unit is
possible as follows:
▪ External heat generator has a potential-free switching contact con-
nection for heat request:
▪ Connection to K3 if the external heat generator is responsible
for the domestic hot water preparation and the backup heating
(setting of the [Config. ext. heat source] parameter = DHW +
heating support [→Main menu →Settings →Ext. source])
or
▪ Connection to K1 and K3 if two external heat generators are
used (setting of the [Config. ext. heat source] parameter = Two
external heat generators [→Main menu →Settings →Ext.
source]). In this case, K1 connects the external heat generator
(e.g. gas-fired or oil-fired boiler) for heating support and K3 connects the external heat generator (EKBUxx) for domestic hot
water preparation.
or
▪ Connection to AUX connection A (see Chap. 3.7.13)
▪ External heat generator can only be connected via mains voltage:
Connection (~230V, maximum load 3000W) to K1 and K3.
CAUTION
Danger of voltage flash-overs.
▪ The connections of the RTX-EHS PCB must not be
used simultaneously for connecting mains voltage
(~230V) and SELV ("Safety Extra Low Voltage").
3 Set-up and installation
Fig.3-41Connection on the RTX-EHS printed circuit board
1 Refer to the external heat generator's respective installation in-
structions for a suitable electrical connection.
2 Installing the connection set for external heat generators (see
Chap. 3.5).
3 Make suitable connections on the RTX-EHS PCB of the connec-
tion set (see Fig. 3-41).
4 Fix cables that are fed into the connection set from the outside
using the strain relief clips and cable ties included (see steps7
A separate manual containing instructions about installation and operation is included with this component.
Fig.3-42Connection with wired room thermostat (RT = Daikin
EKRTW)
A maximum of 16 devices with a total line length of up to 800m can
be connected in the entire RoCon system.
EHS157034 room controller
A separate EHS157034 room controller can be connected for each
heating circuit to enable remote adjustment of operating modes and
target room temperatures from another room.
INFORMATION
Separate installation instructions are included with this
component. See the enclosed control system manual for
instructions on setting and operation.
EHS157068 mixer module
The EHS157068 mixer module can be connected to the indoor unit
(J13 PCB connector) and is controlled by the electronic controller.
INFORMATION
Separate installation instructions are included with this
component. See the enclosed control system manual for
instructions on setting and operation.
EHS157056 Internet gateway
The controller can be connected to the internet with the optional
EHS157056 gateway. This enables remote control of the indoor unit
by mobile phones (by app).
INFORMATION
Separate installation instructions are included with this
component. See the enclosed control system manual for
instructions on setting and operation.
Fig.3-43Connection with radio-controlled room thermostat (RT-E
= Daikin EKRTR)
3.7.11Connection of optional RoCon system
components
The optional RoCon devices must be connected to the indoor unit
via a 4-wire CAN bus cable (connection J13).
For this, we recommend shielded lines with the following characteristics:
▪ Standardisation according to ISO11898, UL/CSA type CMX
(UL444)
▪ PVC outer sheath with flame retardancy according to
IEC60332-1-2
▪ Up to 40m, minimum cross-section 0.75mm2. Larger conductor
cross-section necessary with increasing length.
Commercially available junction boxes can be used to connect CAN
bus lines of several RoCon devices.
Ensure that mains, sensor and data bus lines are routed separately.
Use only cable ducts with separators or separate cable ducts spaced
at least 2cm apart. Line crossings are permissible.
3.7.12Connecting the HP convector
INFORMATION
Only the EKRTCTRL1 and EKWHCTRL(0/1) convector
controllers can be connected to the indoor unit.
INFORMATION
A separate manual containing instructions about installation and operation is included with this component.
INFORMATION
When changing the operating mode (Heating/Cooling) on a
convector, all other convectors must either also be
changed or deactivated.
Installation manual
26
Heat pump (indoor unit) with integrated heat accumulator
Daikin Altherma ETS(X/H)(B)-D
008.1448499_00 – 06/2019 – EN
Fig.3-44FWX(V/M)-AATV3 connection
3.7.13Connecting switching contacts (AUX
outputs)
The switching contacts (AUX outputs) can be used for various parametrisable functions.
Switchover contact A-A1-A2 switches under the conditions set in
parameter [AUX switching function] [→Main menu →Settings →Inputs/Outputs] (see controller operating instructions).
3 Set-up and installation
Switchover contact A-A1-A2 can be used, for example, to control the
heat generators in bivalent heating systems consisting of an indoor
unit and an oil- or gas-fired boiler. Examples of hydraulic system integration are described in "Hydraulic connection" in the installer reference guide.
INFORMATION
If an A2F or G-plus condensing boiler is connected, the
[AUX switching function ] and [AUX wait time] parameters
must be set according to the desired function [→Main
menu →Settings →Inputs/Outputs].
See Controller operating instructions → chapter Parameter
settings.
Precise information on the electrical connection and the required parameter settings for such bivalent heating systems are available on the Internet (www.daikin.com) or
from your service partner.
3.7.14Off-peak mains connection (HT/NT)
If the outdoor unit is connected to a low rate mains connection, the
potential-free switching contact S2S of the receiver, which evaluates
the low rate input signal output from the utility company must be connected to plug J8, EVU connection on the RoCon BM2C PCB (see
Fig. 3-46).
When setting the [HT/NT function] parameter > 0 [→Main menu
→Settings →Inputs/Outputs], certain system components are
switched off during peak periods (see controller operating instructions).
The following types of low rate mains connection are common:
▪ Type 1: With this type of low rate mains connection, the power
supply to the heat pump outdoor unit is not interrupted.
▪ Type 2: With this type of low rate mains connection, the power
supply to the heat pump outdoor unit is interrupted after a certain
period of time.
▪ Type 3: With this type of low rate mains connection, the power
supply to the heat pump outdoor unit is interrupted immediately.
Potential-free switching contact S2S can be implemented as a normally closed or normally open switching contact.
▪ If implemented as a normally closed switching contact, the [HT/NT
contact] parameter = 1 must be set [→Main menu →Settings
→Inputs/Outputs]. When the utility company sends the off-peak
signal, switching contact S2S is opened. The system switches to
"Mandatory OFF". If the signal is sent again, potential-free switching contact S2S closes and the system resumes operation.
▪ If implemented as a normally open switching contact, the [HT/NT
contact] parameter = 0 must be set [→Main menu →Settings
→Inputs/Outputs]. When the utility company sends the off-peak
signal, switching contact S2S is closed. The system switches to
"Mandatory OFF". If the signal is sent again, potential-free switching contact S2S opens and the system resumes operation.
Fig.3-45Connection of switching contact (AUX output)
The relays user for variant 2 (switched output >15W) must be suitable for a 100% power-on time.
Connection terminals B+B1 are not occupied for these devices or
are available for additional functions.
The relays user for variant 2 (switched output >15W) must be suitable for a 100% power-on time.
Only fill the indoor unit after all installation work is completed in the
order shown below.
3.8.1Checking the water quality and adjusting
the pressure gauge
1 Comply with the instructions for the water connection (see
Chap. 3.6) and for the water quality.
2 Adjust the mechanical pressure gauge (mounted on site in ac-
cordance with Chap. 3.6.1 or temporarily installed with filling
hose): Turn the pressure gauge glass so that the minimum pressure marking corresponds to the system height +2m (1m water column corresponds to 0.1bar).
3.8.2Filling hot water heat exchangers
1 Open the shut-off valve for the cold water supply pipe.
2 Open the hot water tap connections so that the draw-off volume
can be set as high as possible.
3 Once water has been discharged from the tap connections, do
not interrupt the cold water flow to ensure that the heat exchanger will be fully vented and that any impurities or residue
will be discharged.
3.8.3Filling the storage tank
Fig.3-46HT/NT contact connection
1 Mains connection box for low rate mains connection
2 Receiver for evaluating the HT/NT control signal
3 Power supply of the heat pump outdoor unit (see respect-
ive installation manual for the heat pump outdoor unit)
4 Potential-free switching contact for heat pump indoor unit
3.7.15Connecting an intelligent controller
(Smart Grid - SG)
If the [Smart grid] parameter = 1, the function [→Main menu →Settings →Inputs/Outputs] is activated (see controller operating instructions), the heat pump is switched to normal or a mode with higher
temperatures depending on the utility company signal.
For this purpose, the SG1/SG2 floating switching contacts of the intelligent controller must be connected to the J8 connector, Smart
Grid and EVU connections on the RoCon BM2C PCB (see
Fig. 3-47).
As soon as the Smart Grid function is active, the HT/NT function is
automatically deactivated. Smart grid mode The heat pump is operated differently depending on the value of the parameter [→Main
menu →Settings →Inputs/Outputs] (see controller operating instructions).
CAUTION
Filling the storage tank with too high a water pressure or
too high a flow speed can cause damage to the indoor unit.
▪ Only fill with a water pressure <6bar and a flow speed
<15l/min.
Without installed solar system
1 Connect the filling hose with non-return valve (1/2") to the
"Solar inflow" connection (Fig. 3-48, item1).
2 Fill the storage tank of the indoor unit until water escapes from
the overflow connection (Fig. 3-48, item2).
3 Remove the filling hose with non-return valve (1/2").
With installed solar system
1 Install the filling connection with combined filling and draining
valve (accessory KFE BA) following the solar control and pump
unit (EKSRPS4).
2 Connect the filling hose with non-return valve (1/2") to the pre-
viously installed combined filling and draining valve.
3 Fill the storage tank of the indoor unit until water escapes from
the overflow connection (Fig. 3-48, item2).
4 Remove the filling hose with non-return valve (1/2").
Fig.3-47Connecting the Smart Grid
Installation manual
28
Heat pump (indoor unit) with integrated heat accumulator
Daikin Altherma ETS(X/H)(B)-D
008.1448499_00 – 06/2019 – EN
Fig.3-48Filling the buffer tank - without connected DrainBack
solar system
1
Solar inflow
2 Safety overflow
3 Set-up and installation
INFORMATION
Comply with the instructions for the water connection (see
Chap. 3.6) and water quality (see Chap. 1.2.6).
1 Connect the filling hose (Fig. 3-49, item1) with the non-return
valve (1/2") and an external pressure gauge (on the building
side) to the combined filling and draining valve (Fig. 3-49, item2)
and secure it against slipping off with a hose clamp.
2 Connect the drain hose to the vent valve, and route it away from
the device. Open the vent valve with the hose connected; check
to make sure that the other vent valve is closed.
3 Open the water tap (Fig. 3-49, item4) on the feed pipe.
4 Open the combined filling and draining valve (Fig. 3-49, item2)
and monitor the pressure gauge.
5 Fill the system with water until the external pressure gauge
shows that the system target pressure is reached (system height
+2m; 1m water column = 0.1bar). The overpressure valve
must not actuate!
6 Close the manual vent valve as soon as water emerges free of
bubbles.
7 Close the water tap (Fig. 3-49, item4). The combined filling and
draining valve must remain open in order to read off the water
pressure on the external pressure gauge.
8 Switch on the power supply of the indoor unit.
9 In the RoCon+ HP controller in the "Operating mode" menu, se-
lect the "Heating" operating mode [→Main menu →Operating
mode].
– After the start phase, the indoor unit runs in hot water heat-
ing operation.
10 Constantly check the water pressure on the external pressure
gauge during hot water heating mode, and top up water via the
combined filling and draining valve (Fig. 3-49, item2) if necessary.
11 Vent the entire heating system as described inBleeding the hy-
draulic system (open the system's control valves. At the same
time, the underfloor heating system can be filled and flushed by
the underfloor distributor.
12 Again check the water pressure on the external pressure gauge,
and top up water via the combined filling and draining valve
(Fig. 3-49, item2) if necessary.
13 Disconnect the filling hose (Fig. 3-49, item1) with non-return
valve from the combined filling and draining valve (Fig. 3-49,
item2).
3.8.4Filling the heating system
DANGER: RISK OF ELECTROCUTION
During the filling process, water can escape from any leaking points and can cause an electric shock if it comes into
contact with live parts.
▪ Before the filling process, de-energise the indoor unit.
▪ After the first filling and before switching on the indoor
unit at the mains switch, check that all electric parts
and connection points are dry.
WARNING
Polluted domestic water is hazardous to health.
▪ When filling the heating system, make sure that heating
water cannot flow back into the domestic water pipe.
▪ The required concentration may vary depending on the
type of glycol. ALWAYS compare the requirements
from the table above with the specifications provided by
the glycol manufacturer. If necessary, meet the requirements set by the glycol manufacturer.
▪ The added concentration of glycol must NEVER ex-
ceed 35%.
▪ If the fluid in the system is frozen, the pump CANNOT
start. Mind that if you only prevent the system from
bursting, the liquid inside might still freeze.
▪ If NO glycol has been added to the system and a power
failure or a pump failure occurs, drain the water from
the system.
▪ When the water inside the system is stationary, it can
5.2 Unlocking key of the drive lock
6 Water tap
7 Automatic vent valve
8 Pressure gauge
3UV DHW 3-way distribution valve (distribution valve, hot water/heat-
ing/heating support)
3UVB1 3-way distribution valve
MAG Diaphragm expansion vessel
(1)
)
Protecting the water circuit against freezing
Frost can damage the system. To prevent the hydraulic components
from freezing, the software is equipped with special frost protection
functions, that include the activation of pump, internal heaters, and/
or backup heater operation in case of low temperatures.
However, in case of a power failure, these functions cannot guarantee protection. It is therefore recommended to add glycol to the water circuit. The required concentration depends on the lowest expected outdoor temperature, and on whether you want to protect the
system from bursting or from freezing. To prevent the system from
freezing, more glycol is required. Add glycol according to the table
below.
CAUTION
Use only propylene glycol including the required inhibitors,
classified as categoryIII as per EN1717.
CAUTION
Glycol absorbs water from its environment. Therefore do
NOT add glycol that has been exposed to air. Leaving the
cap off the glycol container causes the concentration of
water to increase. The glycol concentration is then lower
than assumed. As a result, the hydraulic components
might freeze up after all. Take preventive actions to ensure
a minimal exposure of the glycol to air.
CAUTION
▪ If overpressure occurs, the system releases some of
the fluid through the pressure relief valve. If glycol was
added to the system, take adequate measures so as to
safely recover it.
▪ Under all circumstances, make sure that the hose of
the pressure relief valve is ALWAYS free to release the
pressure. Prevent water from staying and/or freezing
up inside the hose.
INFORMATION
▪ Protection against bursting: the glycol protects the
pipes against bursting, but does NOT protect the fluid
in the pipes against freezing.
▪ Protection against freezing: the glycol protects the fluid
in the pipes against freezing.
Installation manual
30
(1)
if not already installed in the heating system
Heat pump (indoor unit) with integrated heat accumulator
Daikin Altherma ETS(X/H)(B)-D
008.1448499_00 – 06/2019 – EN
Loading...
+ 314 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.