Daikin ETSH16P30D, ETSH16P50D, ETSX16P30D, ETSX16P50D, ETSHB16P30D Installation manuals

...
Installation manual
Daikin Altherma 3 H HT ECH2O
ETSH(B)16P30D ETSH(B)16P50D
06/2019
Heat pump (indoor unit) with integrated heat accumulator
Wärmepumpe (Innengerät) mit integriertem Wärmespeicher
ETSX(B)16P30D ETSX(B)16P50D
Installation manual
Installationsanleitung
Manuel d'installation
Pompe à chaleur (pompe intérieure) à
Installatiehandleiding
Warmtepomp (binnenunit) met
geïntegreerde boiler
Manuale d'installazione
Pompa di calore (unità interna) con
accumulatore di calore integrato
Installationsvejledning
Varmepumpe (indendørs enhed) med
integreret varmtvandsbeholder
Installationshandbok
Värmepump (inomhusenhet) med
integrerad varmvattenberedare
Installeringshåndbok
Varmepumpe (inneapparat) med
integrert varmeakkumulator
Asennusopas
Lämpöpumppu (sisäyksikkö) jossa
integroitu lämpövaraaja
English
Deutsch
Français
Nederlands
Italiano
Dansk
Svenska
Norsk
Suomi

List of contents

List of contents
1 General safety precautions 3
1.1 Particular safety instructions ..................................................... 3
1.1.1 Observing the instructions .......................................... 3
1.1.2 Meaning of warnings and symbols.............................. 4
1.2 Safety instructions for installation and operation....................... 4
1.2.1 General ....................................................................... 4
1.2.2 Intended use ............................................................... 5
1.2.3 Device installation room.............................................. 5
1.2.4 Electrical installation ................................................... 6
1.2.5 Requirements for heating and storage water.............. 6
1.2.6 Heating system and sanitary connection .................... 6
1.2.7 Operation .................................................................... 6
1.3 Maintenance, troubleshooting and decommissioning ............... 6
1.4 Warranty conditions................................................................... 7
2 Product description 8
2.1 Design and components............................................................ 8
2.2 Function of the 3-way switch valves.......................................... 10
3 Set-up and installation 11
3.1 Dimensions and connection dimensions ................................... 11
3.2 Transport and delivery............................................................... 12
3.3 Installing the heat pump ............................................................ 12
3.3.1 Selecting the installation site....................................... 12
3.3.2 Installing the device .................................................... 13
3.4 Preparing the device for installation .......................................... 14
3.4.1 Remove the front screen............................................. 14
3.4.2 Remove the protective cover ...................................... 14
3.4.3 Moving the controller housing to the service position . 14
3.4.4 Open the controller housing........................................ 15
3.4.5 Removing the bottom thermal insulation..................... 15
3.4.6 Opening the vent valve ............................................... 16
3.4.7 Aligning the connections of the heating inflow and
return flow ................................................................... 16
3.4.8 Making the hood opening............................................ 17
3.4.9 Installing the rotary switch of the controller................. 17
3.4.10 Securing the hood....................................................... 17
3.5 Installing optional accessories................................................... 18
3.5.1 Installation of electric backup heater (EKBUxx).......... 18
3.5.2 Installation of the external heat generator connection
set ............................................................................... 18
3.5.3 Installation of the DB connection kit............................ 18
3.5.4 Installation of the P connection kit .............................. 18
3.6 Water connection ...................................................................... 19
3.6.1 Connecting hydraulic lines.......................................... 19
3.7 Electrical connection ................................................................. 20
3.7.1 Overall connection diagram ........................................ 22
3.7.2 Position of the printed circuit boards and terminal
strips ........................................................................... 23
3.7.3 Mains connection........................................................ 23
3.7.4 General information on the electrical connection........ 23
3.7.5 Connecting the heat pump outdoor unit...................... 23
3.7.6 Connecting the outside temperature sensor
(optional) ..................................................................... 24
3.7.7 External switching contact .......................................... 24
3.7.8 EBA (external requirement request) ........................... 24
3.7.9 Connecting an external heat generator....................... 25
3.7.10 Connecting the room thermostat................................. 26
3.7.11 Connection of optional RoCon system components ... 26
3.7.12 Connecting the HP convector ..................................... 26
3.7.13 Connecting switching contacts (AUX outputs) ............ 27
3.7.14 Off-peak mains connection (HT/NT) ........................... 27
3.7.15 Connecting an intelligent controller (Smart Grid - SG) 28
3.8 Filling the system....................................................................... 28
3.8.1 Checking the water quality and adjusting the
pressure gauge ........................................................... 28
3.8.2 Filling hot water heat exchangers ................................ 28
3.8.3 Filling the storage tank................................................. 28
3.8.4 Filling the heating system ............................................ 29
4 Configuration 31 5 Start-up 32
5.1 Requirements ............................................................................. 32
5.2 Commissioning at low ambient temperatures ............................ 32
5.3 Bleeding the hydraulic system.................................................... 32
5.4 Checking the minimum flow ....................................................... 33
5.5 Start screed drying (only if required) .......................................... 33
5.6 Commissioning checklist ............................................................ 33
5.7 Handover to the operating company .......................................... 33
6 Technical data 34
6.1 Information on the type plate...................................................... 34
6.2 Tightening torque ....................................................................... 34
6.3 Electrical connection diagram .................................................... 35
6.4 Piping diagram for refrigerant circuit .......................................... 37
7 Notes 38

Installation manual

2
Heat pump (indoor unit) with integrated heat accumulator
Daikin Altherma ETS(X/H)(B)-D
008.1448499_00 – 06/2019 – EN

1 General safety precautions

1.1 Particular safety instructions

1 General safety precautions
WARNING
Devices that have not been set up and installed correctly can impair the func­tion of the device and/or cause serious or fatal injury to the user.
▪ Work on the indoor unit (e.g. set-up,
inspection, connection and initial commissioning) may only be carried out by persons who are authorised and have successfully completed
qualifying technical or vocational training and who have taken part in
advanced training sessions recog­nised by the relevant responsible au­thorities for the specific activity. These include, in particular, certified
heating engineers, qualified elec­tricians and HVAC specialists who, because of their professional training and expert knowledge,
have experience in the professional installation and maintenance of heat­ing, cooling and air conditioning sys­tems as well as hot water storage tanks.
WARNING
Disregarding the following safety in­structions may result in serious phys­ical injury or death.
▪ This device may only be used by
children aged 8 and above and by persons with restricted physical, sensory or mental capabilities or with a lack of experience and knowledge if they are under supervision or if they have been instructed in the safe use of the equipment and under­stand the dangers arising from it. Children must not play with the device. Cleaning and user mainten-
ance must not be carried out by children without supervision.
▪ Establish the power supply in ac-
cordance with IEC60335-1, via a separate isolator which separates all poles with a contact opening dis­tance that provides full disconnection in accordance with overvoltage cat­egory III.
▪ All electrical work must only be car-
ried out by electrically qualified ex­perts and with consideration of the local and national regulations and the instructions in this manual. Ensure that a suitable electrical cir­cuit is used. Insufficient load capacity of the elec­trical circuit or improperly executed connections can result in electric shock or fire.
▪ The customer must install a pressure
relief device with a rated over-pres­sure of less than 0.6MPa (6bar). The connected drain line must have a continuous gradient and a free out­let in a frost-free environment (see
Chap. 3.3).
▪ Water may drip out of the drain line
of the pressure relief device. The drain opening must be left open to atmosphere.
▪ The pressure relief device must be
operated regularly in order to re­move scale deposits and to make sure it is not blocked.
▪ The storage tank and hot water cir-
cuit can be drained. The instructions in "Temporary decommissioning" in the reference manual for the fitter must be complied with.
1.1.1 Observing the instructions
▪ The original documentation is written in German. All other lan-
guages are translations.
▪ Please read this manual carefully and thoroughly before proceed-
ing with the installation or modification of the heating system.
▪ The precautionary measures described in this document cover
very important topics. Follow them meticulously.
Daikin Altherma ETS(X/H)(B)-D Heat pump (indoor unit) with integrated heat accumulator
008.1448499_00 – 06/2019 – EN
Installation manual
3
1 General safety precautions
▪ The installation of the system and all activities described in this
manual and the applicable documents for the installer must be carried out by an approved installer.
Documentation set
This document is part of a documentation set of other applicable documents.The complete set comprises:
▪ Installation manual for the indoor unit (format: paper – included in
the indoor unit scope of delivery)
▪ Operating instructions for the indoor unit (format: paper – included
in the indoor unit scope of delivery)
▪ Operating manual for the heat pump (format: paper – included in
the indoor unit scope of delivery)
▪ Installation manual for the outdoor unit (format: paper – included
in the outdoor unit scope of delivery)
▪ Installation instructions for optional components (format: paper –
included in the scope of delivery of the respective component) ▪ Installer reference guide of the indoor unit (format: digital) ▪ Installer reference guide of the outdoor unit (format: digital) The reference guides contain the complete set of technical data, a
detailed description of best practices and information on mainten­ance, troubleshooting and decommissioning.
The digital documents and the latest editions of the supplied docu­mentation are available on the regional Daikin website or, on re­quest, from your dealer. The Daikin website is easy to access using the QR code on your device.
1.1.2 Meaning of warnings and symbols
Warnings in this manual are classified according to their severity and probability of occurrence.
DANGER
Indicates an immediate danger. Disregarding this warning can lead to serious injury or
death
WARNING
Indicates a potentially dangerous situation Disregarding this warning may result in serious physical in-
jury or death.
CAUTION
Indicates a situation which may cause possible damage Disregarding this warning can cause damage to property
and the environment and result in minor injuries.
This symbol identifies user tips and particularly useful in­formation, but not warnings or hazards
Special warning signs
Some types of danger are represented by special symbols.
Electric current
Danger of explosion
Risk of burns or scalds
Risk of poisoning
Validity
Some information in this manual has limited validity. The validity is highlighted by a symbol.
Heat pump outdoor unit
Heat pump indoor unit
FWXV-ATV3
Observe the specified tightening torque
Only applies to devices with unpressurised solar system connection (DrainBack).
Only applies to devices with a bivalent solar system connec­tion (Biv).
Only applies to indoor units with cooling function
Handling instructions 1 Handling instructions are shown as a list. Actions where the se-
quential order must be adhered to are numbered.
è
Results of actions are identified with an arrow.

1.2 Safety instructions for installation and operation

1.2.1 General
WARNING
Devices that have not been set up and installed correctly can impair the function of the device and/or cause serious or fatal injury to the user.
▪ Work on the indoor unit (e.g. set-up, inspection, con-
nection and initial commissioning) may only be carried out by persons who are authorised and have success­fully completed qualifying technical or vocational training and who have taken part in advanced training sessions recognised by the relevant responsible au­thorities for the specific activity. These include, in par­ticular, certified heating engineers, qualified electri-
cians and HVAC specialists who, because of their professional training and expert knowledge, have
experience in the professional installation and mainten­ance of heating, cooling and air conditioning systems as well as hot water storage tanks.
▪ Before starting any work on the indoor unit, switch off
the external main switch and secure it against uninten­tional switch-on.
▪ Do not leave any tools or other objects below the hood
of the device after finishing installation or maintenance work.
Avoiding danger
The indoor unit conforms to the state of the art and meets all recog­nised technical requirements. However, improper use may result in serious physical injuries or death, as well as property damage. To prevent such risks, only install and operate the devices:
▪ as stipulated and in perfect condition, ▪ with an awareness of safety and the hazards involved.
This assumes knowledge and use of the contents of this manual, of the relevant accident prevention regulations as well as the recog­nised safety-related and occupational health rules.
Before working on the hydraulic system
▪ Work on the system (such as installation, connection and initial
commissioning, for example) must only be carried out by persons who are authorised, who have successfully completed qualifying technical or vocational training for the respective activity and who have taken part in advanced training sessions recognised by the relevant responsible authority.
▪ When carrying out any work on the system, switch off the main
switch and secure against being switched on inadvertently.
Installation manual
4
Heat pump (indoor unit) with integrated heat accumulator
Daikin Altherma ETS(X/H)(B)-D
008.1448499_00 – 06/2019 – EN
1 General safety precautions
▪ Seals must not be damaged or removed. ▪ Make sure that the safety valves comply with the requirements of
EN12828 when connecting on the heating side, and with the re­quirements of EN12897 when connecting on the domestic water side.
1.2.2 Intended use
The indoor unit may only be used for domestic hot water prepara­tion, as a room heating system and, depending on its design, as a room cooling system.
The indoor unit must only be installed, connected and operated ac­cording to the indications in these instructions.
Only the use of a suitable outdoor unit approved by the manufacturer is permitted.
ETSH16P30D
ETSHB16P30D
ETSX16P30D
ETSXB16P30D
ETSH16P50D
ETSHB16P50D
ETSX16P50D
ETSXB16P50D EPRA14DAV3 P EPRA16DAV3 P EPRA18DAV3 P
EPRA14DAW1 P EPRA16DAW1 P EPRA18DAW1 P
Tab.1-1 Permissible combinations
Any other use outside the intended use is considered as improper. The operator alone shall bear responsibility for any resulting dam­age.
Intended use also includes compliance with the maintenance and in­spection conditions. Replacement parts must at least satisfy the technical requirements defined by the manufacturer. This is the case, for example, with original spare parts.
1.2.3 Device installation room
WARNING
The plastic wall of the storage tank on the indoor unit can melt under the effects of external heat (>80 °C) and, in the extreme case, can catch fire.
▪ Only install the indoor unit at a minimum clearance of
1m from other heat sources (>80°C) (e.g. electrical heater, oil heater, chimney) and combustible materials.
CAUTION
▪ Only install the indoor unit if sufficient load-carrying ca-
pacity of the ground of 1050kg/m2 plus safety margin is ensured. The ground must be flat, horizontal and level.
Outdoor installation is not permissible. ▪ Installation in an explosion-risk environment is not per-
missible.
▪ The electronic control system must not be exposed to
whether effects like rain and snow under any circum­stances.
▪ The storage tank may not be exposed to continuous
direct sunlight, as the UV radiation and the effects of
the weather will damage the plastic. ▪ The indoor unit must be installed protected from frost. ▪ Make sure that the supply company does not provide
corrosive domestic water. Suitable water treatment may
be required.
▪ Always ensure the minimum distances from walls and other ob-
jects (Chap. 3.3).
CAUTION
If a DrainBack solar heating system is connected:
Install the indoor unit far enough under the solar panels
to allow complete emptying of the solar heating system.
(Follow instructions in the DrainBack solar heating sys-
tem manual). An insufficient height difference may lead
to destruction of the DrainBack solar heating system. ▪ The indoor unit must not be operated in rooms with am-
bient temperatures of more than 40°C.
CAUTION
▪ The required concentration may vary depending on the
type of glycol. ALWAYS compare the requirements
from the table above with the specifications provided by
the glycol manufacturer. If necessary, meet the require-
ments set by the glycol manufacturer. ▪ The added concentration of glycol must NEVER ex-
ceed 35%. ▪ If the fluid in the system is frozen, the pump CANNOT
start. Mind that if you only prevent the system from
bursting, the liquid inside might still freeze. ▪ If NO glycol has been added to the system and a power
failure or a pump failure occurs, drain the water from
the system. ▪ When the water inside the system is stationary, it can
easily freeze and thus damage the system.
CAUTION
Glycol absorbs water from its environment. Therefore do NOT add glycol that has been exposed to air. Leaving the cap off the glycol container causes the concentration of water to increase. The glycol concentration is then lower than assumed. As a result, the hydraulic components might freeze up after all. Take preventive actions to ensure a minimal exposure of the glycol to air.
Daikin Altherma ETS(X/H)(B)-D Heat pump (indoor unit) with integrated heat accumulator
008.1448499_00 – 06/2019 – EN
CAUTION
Use only propylene glycol including the required inhibitors, classified as categoryIII as per EN1717.
Installation manual
5
1 General safety precautions
CAUTION
▪ If overpressure occurs, the system releases some of
the fluid through the pressure relief valve. If glycol was added to the system, take adequate measures so as to safely recover it.
▪ Under all circumstances, make sure that the hose of
the pressure relief valve is ALWAYS free to release the pressure. Prevent water from staying and/or freezing up inside the hose.
1.2.4 Electrical installation
▪ Electrical installations may only be carried out by electrical techni-
cians and in compliance with valid electrical guidelines as well as the specifications of the responsible energy supply company.
▪ Compare the mains voltage indicated on the nameplate with the
supply voltage before connecting to the mains.
▪ Before beginning work on live parts, disconnect them from the
power supply (switch off main switch, remove fuse) and secure against unintentional restart.
▪ Device covers and service panels must be replaced as soon as
the work is completed.
1.2.5 Requirements for heating and storage water
Damage due to deposits and corrosion: observe the relevant tech­nical rules to avoid corrosion products and deposits.
Minimum requirements regarding the quality of filling and top-up wa­ter:
▪ Water hardness (calcium and magnesium, calculated as calcium
carbonate): ≤3mmol/l ▪ Conductivity: ≤1500 (ideal: ≤100) μS/cm ▪ Chloride: ≤250mg/l ▪ Sulphate: ≤250mg/l ▪ pH value: 6.5 – 8.5
INFORMATION
To guarantee frost protection in the event of a power fail­ure, glycol can be added to the heating water circuit. Please observe the notes in Chap. 3.8.4.
Measures for desalination, softening or hardness stabilisation are necessary if the filling and top-up water have a high total hardness (>3mmol/l – total of the calcium and magnesium concentrations, calculated as calcium carbonate). We recommend the use of Fernox KSK limescale and corrosion protector. For other properties deviat­ing from the minimum requirements, suitable conditioning measures are necessary to maintain the required water quality.
Using filling water and top-up water which does not meet the stated quality requirements can cause a considerably reduced service life of the device. The responsibility for this lies solely with the operator.
1.2.6 Heating system and sanitary connection
▪ Create a heating system according to the safety requirements of
EN12828.
▪ The plumbing connection must comply with the requirements of
EN12897. The requirements of the following must also be ob­served:
▪ EN1717 – Protection against pollution of potable water installa-
tions and general requirements of devices to prevent pollution by backflow
▪ EN61770 – Electric appliances connected to the water mains –
Avoidance of backsiphonage and failure of hose-sets
▪ EN806 – Specifications for installations inside buildings con-
veying water for human consumption
▪ and, in addition, the country-specific legislation.
When operating the indoor unit, the storage tank temperature may exceed 65°C.
▪ For this reason, some form of scalding protection needs to be in-
cluded when you install the system (hot water mixing device, e.g. VTA32).
If the indoor unit is connected to a heating system with steel pipes, radiators or non-diffusion-proof floor heating pipes, sludge and chips can enter the hot water storage tank and cause blockages, local overheating or corrosion damage.
▪ To prevent possible damage, install a dirt filter or sludge separator
into the heating return flow of the system (SAS 1 or SAS 2).
▪ The dirt filter must be cleaned at regular intervals.
1.2.7 Operation
The indoor unit: ▪ Do not operate until all installation and connection work is com-
pleted.
▪ Only operate with a completely full storage tank (check level indic-
ator) and heating circuit. ▪ Operate at a maximum pressure of 3bar. ▪ Only connect with a pressure reducer on the external water supply
(supply line). ▪ Only operate if the protective cover is installed. The specified servicing intervals should be adhered to and inspec-
tion work must be carried out.
1.3 Maintenance, troubleshooting and
decommissioning
Work for maintenance, troubleshooting and decommissioning must not be carried out without knowledge of the relevant safety precau­tions and in the event of disposal of the country-specific guidelines. Please refer to the corresponding information in the installer refer­ence guide.
Recommendations for disposal
We designed the indoor unit in an environmentally friendly manner. During the disposal process, the only waste created is that which can be used for material or thermal recycling. The materials used that are suitable for recycling can be sorted into individual types.
Thanks to the environmentally friendly design of the in­door unit, we have established requirements to ensure environ­mentally friendly disposal. Proper disposal in compliance with the respective national regulations of the country of use is the respons­ibility of the user/owner.
Installation manual
6
Heat pump (indoor unit) with integrated heat accumulator
Daikin Altherma ETS(X/H)(B)-D
008.1448499_00 – 06/2019 – EN
The designation of the product means that electrical and electronic products may not be disposed of together with unsorted domestic waste.
Proper disposal in compliance with the respective national regula­tions of the country of use is the responsibility of the user/owner.
▪ Disassembly of the system, handling of coolant, oil and other
parts may only be carried out by a qualified fitter.
▪ Disposal may only be carried out by an organization that special-
ises in reuse, recycling and recovery.
Further information is available from the installation company or the responsible local authorities.

1.4 Warranty conditions

The legal guarantee conditions fundamentally apply. Our more ex­tensive warranty conditions can be found in the Internet. Ask your suppliers if necessary.
Incorrect installation, commissioning and maintenance will void the warranty. If you have any questions, please contact our customer service.
Warranty claims can only be made if the annual maintenance work is demonstrably carried out regularly according to the information in the installer reference guide.
1 General safety precautions
Daikin Altherma ETS(X/H)(B)-D Heat pump (indoor unit) with integrated heat accumulator
008.1448499_00 – 06/2019 – EN
Installation manual
7

2 Product description

33
RoCon+ B1
26
24
10
25
2 Product description

2.1 Design and components

Outside of the device
Upper side of the device
Fig.2-1 Design and components – Outside of the device
(1)
Fig.2-2 Design and components – Top of the device
(1)
Installation manual
8
(1)
For legend, see Tab. 2-1
Heat pump (indoor unit) with integrated heat accumulator
Daikin Altherma ETS(X/H)(B)-D
008.1448499_00 – 06/2019 – EN
2 Product description
Internal structure of ETS(X/H)(B)16P30D
Internal structure of ETS(X/H)(B)16P50D
Fig.2-3 Structure and components – internal structure of ETS(X/
H)(B)16P30D
(1)
For legend, see Tab. 2-1
Daikin Altherma ETS(X/H)(B)-D Heat pump (indoor unit) with integrated heat accumulator
008.1448499_00 – 06/2019 – EN
(1)
Fig.2-4 Structure and components – internal structure of ETS(X/
H)(B)16P50D
(1)
Item Designation Item Designation
1 Solar inflow 25 Type plate 2 Cold water connection 26 Protective cover 3 Hot water 27 Solar return flow 4 Heating flow 28 Bivalent feed (type
ETS(X/H)B only)
5 Heating return flow 29 Bivalent return (type
ETS(X/H)B only) 6 Circulation pump 30 Manual vent valve 7 Pressure relief valve 31 Outdoor unit water inlet
connection 7a Circulation stop valve
(accessory)
32 Outdoor unit water outlet
connection
Installation manual
9
2 Product description
Item Designation Item Designation
8 Automatic vent valve 33 Status display 9 Storage tank (polypropyl-
ene, double-walled jacket
34 Ball valve (heating cir-
cuit) with PUR hard foam heat insulation)
10 Filling and draining con-
nection or solar return flow connection
11 Mount for solar controller
or handle
12 Heat exchanger (stain-
less steel) for domestic
35 Combined filling and
draining valve (heating
circuit)
37
Storage tank temperature
sensor
t
DHW1
38 Diaphragm expansion
vessel connection hot water heating
13 Heat exchanger (stain-
39 Controller housing less steel) for storage tank charging or heating support
14 Biv heat exchanger
(stainless steel) for char­ging with external heat
41 EKSRPS4 Optional:
Solar control and pump
unit generator (e.g. pressur­ised solar system)
15 Connection for optional
electrical backup heater EKBUxx
16 Solar inflow layering pipe 3UV
17 Fill level indicator (tank
3UVB1
3-way switch valve (in-
ternal heat generator cir-
cuit)
3-way switch valve (hot
DHW
water/heating)
DS Pressure sensor
water)
18 Optional: electric backup
FLS FlowSensor
heater (EKBUxx)
19 Sensor pocket for tank
temperature sensor t
20 Pressure-free storage
water
21 Solar zone RoCon
DHW1
t
Inflow temperature
V
sensor
t
Backup heater inflow
V,BH
temperature sensor
Controller control panel
+ B1
22 Hot water zone MAG Diaphragm expansion
vessel
23 Safety overflow connec-
FS Flow switch
tion
24 Mount for handle
Tab.2-1 Legend for Fig. 2-1 to Fig. 2-4

2.2 Function of the 3-way switch valves

Fig.2-5 Function of 3-way switch valve
Installation manual
10
Heat pump (indoor unit) with integrated heat accumulator
Daikin Altherma ETS(X/H)(B)-D
008.1448499_00 – 06/2019 – EN

3 Set-up and installation

WARNING
Cooling systems (heating pumps), climate control systems and heating devices that have been set up and installed in­correctly can both endanger human life and health and be impaired in their function.
▪ Work on the indoor unit (such as installation, repair,
connection and initial commissioning, for example) must only be carried out by persons who are author­ised, who have successfully completed qualifying tech­nical or vocational training for the respective activity and who have taken part in advanced training sessions recognised by the relevant responsible authority. These include, in particular, certified heating engineers, quali­fied electricians and HVAC specialists who, because of their professional training and expert knowledge, have experience in the professional installation and mainten­ance of heating, cooling and air conditioning systems and heat pumps.
Incorrect set-up and installation would render the manufacturer's guarantee void. If you have questions, please contact our Technical Customer Service.

3.1 Dimensions and connection dimensions

3 Set-up and installation
Fig.3-2 Dimensions, top of unit – type ETS(X/H)B16P30D
Dimensions, ETS(X/H)B16P50D
Dimensions, ETS(X/H)B16P30D
Fig.3-1 Dimensions, side view – ETS(X/H)B16P30D
Daikin Altherma ETS(X/H)(B)-D Heat pump (indoor unit) with integrated heat accumulator
008.1448499_00 – 06/2019 – EN
Fig.3-3 Dimensions, side view – type ETS(X/H)B16P50D
Installation manual
11
3 Set-up and installation
Fig.3-4 Dimensions, top of unit – type ETS(X/H)B16P50D
Item Designation Item Designation
1 Solar inflow 7 Outdoor unit water inlet
connection
2 Cold water 8 Bivalent feed (type
ETS(X/H)B only)
3 Hot water 9 Bivalent return (type
ETS(X/H)B only) 4 Heating flow 5 Heating return flow A front 6 Outdoor unit water outlet
connection
Tab.3-1 Legend for Fig. 3-1 to Fig. 3-4
B rear

3.2 Transport and delivery

WARNING
When unfilled, the indoor unit is top-heavy and could tip over during transport. That could put persons in danger or damage the unit.
▪ Secure the indoor unit well, transport carefully, use the
handles.
The indoor unit is delivered on a pallet. All industrial trucks, such as lifting trucks and forklift trucks, are suitable for transport.
Scope of delivery
▪ Indoor unit (pre-mounted), ▪ Bag of accessories (see Fig. 3-5), ▪ Document pack.
Fig.3-5 Contents of bag of accessories
A Handles (only required for transport) B Cover panel C Hose connecting piece for safety overflow D Assembly wrench E Ball valve
F Flat gasket G O-ring H Cable tie
I Securing clip
J Venting hose K Drain hose cover
L Controller rotary switch M Hood screws
For further accessories for the indoor unit, see price list.

3.3 Installing the heat pump

3.3.1 Selecting the installation site
The installation site of the indoor unit must meet the minimum re­quirements below (see also Chap. 1.2.3).
Installation area ▪ The base must be level and smooth and have sufficient ground
load-bearing capacity of 1050kg/m² plus safety factor. Install a
pedestal if necessary.
▪ Observe the installation dimensions (see Chap. 3.1).
Installation manual
12
Heat pump (indoor unit) with integrated heat accumulator
Daikin Altherma ETS(X/H)(B)-D
008.1448499_00 – 06/2019 – EN
3 Set-up and installation
Minimum distance
DANGER: RISK OF BURNING
The plastic wall of the storage tank on the indoor unit can melt under the effects of external heat (>80°C) and, in the extreme case, can catch fire.
▪ Only install the indoor unit at a minimum clearance of
1m from other heat sources (>80°C) (e.g. electrical heater, oil heater, chimney) and combustible material.
CAUTION
If the indoor unit is not installed at a sufficient dis-
tance below the flat solar panels (the top edge of the stor­age tank is higher than the bottom edge of the solar pan­els), the unpressurised solar system in the outdoor area will not be able to drain completely.
▪ When a solar connection is used, install the indoor unit
low enough under the flat solar panels (observe the minimum gradient of the solar connection lines).
Recommended minimum distances: From the wall: (rear) ≥100mm, (sides) ≥500mm From the ceiling: ≥1200mm, at least 480mm.
Distances from the outdoor unit:
When selecting the installation location, the data in the Tab. 3-2 must be taken into account.
Maximum line length between the indoor and out­door units
Maximum height difference between the indoor and outdoor units
Tab.3-2
50m
10m
Installation
3.3.2 Installing the device
WARNING
When unfilled, the indoor unit is top-heavy and could tip over during transport. That could put persons in danger or damage the unit.
▪ Secure the indoor unit well, transport carefully, use the
handles.
Precondition
▪ The installation site complies with applicable country-specific reg-
ulations and meets the minimum requirements described in
Chap. 3.3.1.
Fig.3-6 Installing the handles
A Handle B Cover panel F Threaded piece
1 Remove the packaging and dispose of it in an environment-
friendly manner.
2 Pull the cover screens off the storage tank (Fig. 3-6, itemB) and
unscrew the threaded fittings (Fig. 3-6, itemF) from the open­ings at which the handles are to be fitted.
3 Screw the handles (Fig. 3-6, itemA) into the now uncovered
threaded holes.
4 Carefully transport the indoor unit to the installation site, use the
handles.
5 Install the indoor unit at the installation site.
Daikin Altherma ETS(X/H)(B)-D Heat pump (indoor unit) with integrated heat accumulator
008.1448499_00 – 06/2019 – EN
Installation manual
13
3 Set-up and installation

3.4 Preparing the device for installation

3.4.1 Remove the front screen
1 Undo the screws (1.). 2 Press the lateral holding burls upwards with your fingers (2.),
stem from above with the thumbs.
3 Remove the front screen to the front (3.).
Fig.3-8 Remove the protective cover
Fig.3-7 Remove the front screen
3.4.2 Remove the protective cover
1 Unhook the protective cover from the rearward facing holding
burls (1.), lift at the back (2.) and remove to the front (3.).
Fig.3-9 Without protective cover
3.4.3 Moving the controller housing to the service position
To facilitate work on the hydraulics of the indoor unit, the control box can be moved to the service position.
1 Loosen the screws(1) of the holder of the controller housing.
Fig.3-10 Moving the controller housing to the service position
2 Remove the controller housing from the front and insert it into
the bracket with the hooks on the rear brackets.
Installation manual
14
Heat pump (indoor unit) with integrated heat accumulator
Daikin Altherma ETS(X/H)(B)-D
008.1448499_00 – 06/2019 – EN
Fig.3-11 Controller housing in the service position
3.4.4 Open the controller housing
To make the electrical connections, the controller housing itself must be opened. This can be done in both the normal and the service po­sition.
1 Loosen the front screw. 2 Push the cover upwards and pull it away to the front.
3 Set-up and installation
3.4.5 Removing the bottom thermal insulation
CAUTION
The thermal insulation consists of pressure-sensitive EPP moulded parts that can be easily damaged if not handled correctly.
▪ Only remove the thermal insulation in the order stated
below and in the stated directions. ▪ Do not use force. ▪ Do not use tools.
1 Remove the thermal insulation in the following order:
▪ Pull the side insulating element off horizontally (itemA). ▪ Pull the rear insulating element off horizontally (itemB). ▪ Pull the front insulating element off horizontally (itemC).
Fig.3-12 Open the controller housing
3 Hook in the cover on the controller housing with the lateral
hooks.
Fig.3-14 Removing the top thermal insulation
2 As required: Remove the bottom thermal insulation in the fol-
lowing order: ▪ Pull the side insulating element off vertically (itemA). ▪ Pull the rear insulating element off vertically (itemB).
Fig.3-13 Hooking in the cover
Daikin Altherma ETS(X/H)(B)-D Heat pump (indoor unit) with integrated heat accumulator
008.1448499_00 – 06/2019 – EN
Fig.3-15 Removing the bottom thermal insulation
Installation manual
15
3 Set-up and installation
INFORMATION
The thermal insulation is installed in reverse order.
3.4.6 Opening the vent valve
1 Removing the thermal insulation (see Chap. 3.4.5). 2 Open the vent valve on the pump by one turn.
Fig.3-16 Opening the vent valve
3.4.7 Aligning the connections of the heating inflow and return flow
CAUTION
When working on the hydraulics, pay attention to the in­stallation position of the O-rings to avoid damaging them and causing leaks.
▪ Always place O-rings on the part to be inserted after
disassembly or before assembly (see Fig. 3-19).
▪ The heating lines must be connected free of tension via
the plug connectors. Establish a suitable strain relief especially when connecting with flexible lines (not open to diffusion!) (see Fig. 3-31).
The device is supplied with upwards aligned connections as stand­ard. The following conversion steps are required in order to direct the connections to the rear out of the device:
1 Remove the protective cover and top thermal insulation
(seeChap. 3.4.2).
Fig.3-18 Aligning the heating inflow and return flow upwards
2 Pull the two securing clips off the connection couplings
(Fig. 3-18, itemC).
3 Pull off the two connection couplings (Fig. 3-18, itemB).
CAUTION
If the plug brackets cannot be put on properly, the coup­lings can be detached from their mountings to ensure a very strong or continuous escape of liquid can occur.
▪ Before putting on a plug bracket, make sure that the
stirrup engages in the coupling groove. To do so, insert the coupling far enough into the mounting that the groove is visible through the plug bracket mounting.
▪ Insert the plug bracket up to the end stop.
The connections of the heating inflow and return flow can be direc­ted upwards or backwards in order to adapt it optimally to the struc­tural conditions of the installation site.
Fig.3-17 Variants for aligning the heating feed and return
Fig.3-19 Hydraulic system plug connectors
4 Remove the retaining plate (Fig. 3-18, itemA). 5 Pull off the sealing plug securing clip (Fig. 3-18, itemD). 6 Pull out the sealing plug (Fig. 3-18, itemE). 7 Turn the elbow (Fig. 3-18, itemH) 90° to the rear. 8 Pull the securing clip off the manifold (Fig. 3-18, itemG). 9 Carefully pull the manifold (Fig. 3-18, itemF) so far backwards
out of its horizontal mounting that the retaining plate (Fig. 3-20, itemA) can be pushed vertically in between.
Installation manual
16
Heat pump (indoor unit) with integrated heat accumulator
Daikin Altherma ETS(X/H)(B)-D
008.1448499_00 – 06/2019 – EN
Fig.3-20 Heating inflow and return flow connections aligned to the
rear
10 Slide the retaining plate between the manifold and its horizontal
mounting and insert the manifold (Fig. 3-20, itemF) back into its mounting through the middle hole of the retaining plate.
11 Secure the manifold with securing clip (Fig. 3-20, itemG) in its
mounting again.
12 Insert the two connection couplings (Fig. 3-20, itemB) into the
lateral mountings through the retaining plate.
13 Secure the two connection couplings with securing clips
(Fig. 3-20, itemC) in their mountings.
14 Insert the sealing plug (Fig. 3-20, itemE) into the upper mount-
ing.
15 Secure the sealing plug with securing clip (Fig. 3-20, itemD). 16 Cut out side openings in the thermal insulation (Fig. 3-21,
itemA) using a suitable tool.
3 Set-up and installation
Fig.3-22 Making the hood opening
3.4.9 Installing the rotary switch of the controller
1 Place the rotary switch on the rotary switch holder of the RoCon
+ HP and press it on.
Fig.3-23 Putting on the rotary switch
3.4.10 Securing the hood
After the installation is fully completed: 1 Attach the screws for fixing the hood (accessory bag).
Fig.3-21 Cut-out in thermal insulation
3.4.8 Making the hood opening
1 With the heating inflow and return flow directed upwards: Cut the
hood along the perforation with a suitable tool.
Daikin Altherma ETS(X/H)(B)-D Heat pump (indoor unit) with integrated heat accumulator
008.1448499_00 – 06/2019 – EN
Fig.3-24 Securing the hood
2 Place the front cover straight over the rotary switch of the RoCon
+ HP. Press on the top and bottom until the front screen is se­curely engaged again.
Installation manual
17
3 Set-up and installation

3.5 Installing optional accessories

3.5.1 Installation of electric backup heater (EKBUxx)
INFORMATION
If the ceiling height is low, the storage tank must be tilted to install the backup heater when empty. This must be done before any further installation steps.
The indoor unit provides the option of installing an electrical auxiliary heater (backup heater EKBUxx). For example, renewable energy can be used as an additional heat source.
INFORMATION
A separate manual containing instructions about installa­tion and operation is included with this component.
3.5.2 Installation of the external heat generator connection set
The connection set for external heat generators must be installed to control an electrical backup heater or another external heat gener­ator.
1 Open the housing by removing the screw. 2 Remove additional components from the housing (strain relief
clip, cable tie, grommet).
3 Attach the connection set to the controller housing of the indoor
unit. To do this, insert the hooks(1) of the connection set into the slots of the controller housing(2); then press the connection set downwards.
7 After the installation and the electrical connections (see
Chap. 3.6 or Chap. 3.7) have been completed, replace the cover
and close it with the screw.
3.5.3 Installation of the DB connection kit
The optional DB connection kit allows better access for connecting the DrainBack pipe (solar feed).
Fig.3-27 DB connection kit
A DB pipe connection (solar inflow) B FlowSensor (not part of the DB connection kit, but included
with EKSRPS4)
C Flow rate limiter (FlowGuard) D
Solar inflow connection on the storage tank
Fig.3-25 Fitting the connection set
4 Attach the grommet(3) to the bushing between the connection
set(A) and the controller housing(B).
5 Attach the fastening rivet(4).
3.5.4 Installation of the P connection kit
The optional P connection kit for Biv device types allows better ac­cess for connecting the inflow and return flow lines of a pressurised solar system or another external heat generator on the storage tank. The kit contains two thermally insulated corrugated pipes that are connected to the connections of the storage tank via a union nut. At the other end of the corrugated pipes there is an adapter for different connection sizes of the supply and return pipes.
Fig.3-26 Cable gland
6 Guide the cable of the Ultra EHS PCB through the cable grom-
met and connect it to the RoCon BM2C (see Fig. 3-41).
Installation manual
18
Fig.3-28 P connection kit for Biv device types
A Connection for inflow (red) B Connection for return flow (blue)
Daikin Altherma ETS(X/H)(B)-D
Heat pump (indoor unit) with integrated heat accumulator
008.1448499_00 – 06/2019 – EN
3 Set-up and installation

3.6 Water connection

Important information
CAUTION
If the indoor unit is connected to a heating system with steel pipes or radiators or non-diffusion-proof floor heat­ing pipes, slurry and swarf could enter the hot water stor­age tank and cause blockages, local overheating or cor- rosion damage.
▪ Rinse supply lines before filling the device. ▪ Rinse out the heat distribution network (in the existing
heating system).
▪ Install a dirt filter or sludge separator in the heating re-
turn flow (see Chap. 1.2.6).
CAUTION
If the indoor unit is connected to a cold water line where steel pipes are used, chips can get into the stainless steel corrugated pipe heat exchanger and remain there. This can lead to contact corrosion damage and subsequently to leakage.
▪ Flush the feed pipes before filling the heat exchanger. ▪ Install the dirt filter in the cold water supply (e.g. SAS 1
or SAS 2).
CAUTION: BIV ONLY
If the heat exchanger for pressurised solar system char­ging (see Chap. 3.1, items8 + 9) is connected to an ex- ternal heater (e.g. wood-burning boiler), the indoor unit can be damaged or destroyed due to an excessively high inflow temperature at these connections.
▪ The inflow temperature of the external heater should
be limited to max. 95°C.
CAUTION
Corrosion may be caused by air entering the heating water network and by a quality of the heating water that does not comply with the requirements in accordance with
Chap. 1.2.5. Corrosion products (particles) thus created
may clog pumps and valves and cause malfunctions.
▪ Device may not be connected by permeable, flexible
lines.
▪ Install the indoor unit close to the withdrawal point to dispense
with the need for a circulation line. If a circulation line is mandat­ory, it must be installed according to the schematic diagrams in "Hydraulic system connection" in the installer reference guide.
3.6.1 Connecting hydraulic lines
DANGER: RISK OF BURNING
There is a danger of scalding at hot water temperatures over 65°C. This is possible when using solar energy if an external heater is connected, the Legionella protection is activated, or the target hot water temperature is set to be greater than 65°C or if the Smart-Grid function is activ­ated.
▪ Install scalding protection (hot water mixer device (e.g.
VTA32)).
INFORMATION
The indoor unit is equipped with a pressure sensor. The system pressure in monitored electronically and can be displayed with the device switched on.
Nevertheless, we recommend installing a mechanical pres­sure gauge between the indoor unit and the diaphragm ex­pansion vessel, for example.
▪ Install the manometer so that it is easy to see when
filling.
Prerequisite: Optional accessories (e.g. solar, backup heater) are mounted on the Daikin Altherma 3 H HT ECH2O as specified in the enclosed instructions.
1 Check cold water pressure (maximum 6bar).
▪ If a higher pressure is present in the domestic water pipe, a
pressure reducer will need to be installed.
2 Make the hydraulic connections to the Daikin Altherma 3 H HT
ECH2O.
▪ Refer to Fig. 3-1 up to Fig. 3-4 and from Tab. 2-1 for the posi-
tion and dimensions of the heater connections and the outdoor unit connections. The details of the hydraulic connection from the indoor unit to the water inlet and outlet of the outdoor unit can be seen in Fig. 3-29.
INFORMATION
In accordance with EN12828, a safety valve that limits the maximum permissible operating pressure in the heating system must be installed on or in the immediate vicinity of the heat generator. There may not be any hydraulic block­ing elements between the heat generator and the safety valve.
Any steam or heating water that may escape must be drained by a suitable blow-off line with constant gradient in a frost-protected, safe and observable manner.
A diaphragm expansion vessel suitably sized and preset for the heating system must be connected to the Daikin Altherma 3 H HT ECH2O. There may not be any hydraulic blocking elements between the heat generator and the dia­phragm expansion vessel.
We recommend installing a mechanical pressure gauge for filling the heating system.
▪ For potable water lines, observe the provisions of EN806,
DIN1988 and the additional applicable national regulations for potable water installation.
Daikin Altherma ETS(X/H)(B)-D Heat pump (indoor unit) with integrated heat accumulator
008.1448499_00 – 06/2019 – EN
Fig.3-29 Establishing the hydraulic connection to the outdoor unit
▪ Pay attention to the stipulated tightening torque (see
Chap. 6.2). To avoid damage, apply the necessary counter-
torque with a suitable tool, see Fig. 3-30.
Installation manual
19
3 Set-up and installation
Fig.3-30 Establishing the heating connections
▪ Install the line so that the sound insulation hood can be posi-
tioned easily after installation.
▪ For rearward facing connections: Support hydraulic lines suit-
ably according to the spatial conditions, see Fig. 3-31.
Fig.3-32 Installation of drain hose at safety overflow
6 Connect the discharge fitting on the cover (Fig. 2-2, item30) to
the waste water installation with the enclosed hose section.
7 Connecting a diaphragm expansion vessel (see Fig. 3-33)
▪ Connect a suitably dimensioned and preset diaphragm expan-
sion vessel for the heating system. There may not be any hy­draulic blocking elements between the heat generator and the safety valve.
▪ Position the diaphragm expansion vessel in an easily access-
ible place (maintenance, parts replacement)
Fig.3-31 Supporting rear-facing hydraulic lines
▪ Connect the water for filling or refilling the heating system as
per EN1717 so that contamination of the drinking water due to return flow is reliably prevented.
3 Connect the drain line to the safety overpressure valve and dia-
phragm expansion vessel as per EN12828. ▪ Check the seat of the drain hose on the pressure relief valve. ▪ If necessary, connect and install a separate hose.
4 Carefully insulate pipework against heat loss and to avoid con-
densation (insulation thickness at least 20mm). ▪ Water shortage protection: the controller's pressure and tem-
perature monitoring function reliably shuts off the Daikin Altherma 3 H HT ECH2O if there is a shortage of water. No ad­ditional water shortage protection is needed in the construction.
▪ Avoid damage caused by deposits and corrosion: see
Chap. 1.2.5
5 Connect the drain hose to the hose connecting piece for the
safety overflow (Fig. 2-3, item23). ▪ Use transparent drain hose (draining water must be visible). ▪ Connect the drain hose to an adequately dimensioned waste
water installation.
▪ Drain should not be lockable.
Fig.3-33 Mounting the diaphragm expansion vessel

3.7 Electrical connection

DANGER: RISK OF ELECTROCUTION
Touching live parts can result in an electric shock and lead to potentially fatal injuries and burns.
▪ Before beginning work on live parts, disconnect all of
the systems circuits from the power supply (switch off external main switch, disconnect fuse) and secure against unintentional restart.
▪ Establishment of the electrical connection and work on
electrical components should only be performed by electrical technicians in compliance with valid stand­ards and guidelines as well as the specifications of the energy supply company and the instructions in this manual.
▪ Never make constructional changes to connectors or
other electrical equipment components.
Device covers and service panels must be replaced
as soon as the work is completed.
Installation manual
20
Heat pump (indoor unit) with integrated heat accumulator
Daikin Altherma ETS(X/H)(B)-D
008.1448499_00 – 06/2019 – EN
CAUTION
Increased temperatures can occur in the controller housing of the indoor unit during operation. This can result in cur­rently-carrying wires from reaching higher temperatures during operation due to self-heating. For this reason, these lines need to have a continuous use temperature of 90°C.
▪ For the following connections, only use cables with a
long-term use temperature ≥90°C: Heat pump outdoor unit and optional: Electric backup heater (EKBUxx)
CAUTION
If the mains cable of the indoor unit is damaged, it must be replaced by the manufacturer or his customer service or a similarly qualified person to avoid hazards.
All electronic control and safety devices of the indoor unit are con­nected ready for use and tested. Modifications on the electrical in­stallation are dangerous and prohibited. The operator alone bears responsibility for any resulting damage.
3 Set-up and installation
Daikin Altherma ETS(X/H)(B)-D Heat pump (indoor unit) with integrated heat accumulator
008.1448499_00 – 06/2019 – EN
Installation manual
21
3 Set-up and installation
3.7.1 Overall connection diagram
Fig.3-34 Overall connection diagram – for the electrical connection during the device installation (for the legend and pin assignment of the
Installation manual
22
PCB, see Chap. 6.3)
Daikin Altherma ETS(X/H)(B)-D
Heat pump (indoor unit) with integrated heat accumulator
008.1448499_00 – 06/2019 – EN
3.7.2 Position of the printed circuit boards and terminal strips
3 Set-up and installation
Fig.3-35 Position of the printed circuit boards and terminal strips
(for the legend, see Chap. 6.3)
3.7.3 Mains connection
A flexible cable for the mains connection is already connected inside the device.
1 Check the supply voltage (~230V, 50Hz). 2 Disconnect the junction box of the domestic installation. 3 Connect the cable for connecting the indoor unit to the mains to
the domestic installation's junction box (isolator according to EN60335-1) via an all-pole separating main switch to be in­stalled in the building. Ensure that the polarity is correct.
3.7.4 General information on the electrical connection
1 Check the supply voltage. 2 Set the mains switch to "Off". 3 Switch off the circuit breaker in the junction box of the domestic
power supply.
4 Open the controller housing (see Chap. 3.4.4). 5 Insert the cable through one of the cable glands into the interior
of the controller housing. When cutting and laying cables to be connected, make sure that the controller housing can be brought into the service position without any tension.
Fig.3-36 Cable gland
6 Make electrical connections according to Chap. 3.7.1 and the
following sections.
7 Effective strain relief in the controller housing by means of cable
ties must be ensured for all cables connected to the indoor unit (steps 1 – 3, Fig. 3-37).
Fig.3-37 Establishing and checking the strain relief
8 Check the holding force of the strain relief (step 4, Fig. 3-37). 9 After the installation is complete: Close the controller housing
again and, if necessary, move it to the normal position.
Daikin Altherma ETS(X/H)(B)-D Heat pump (indoor unit) with integrated heat accumulator
008.1448499_00 – 06/2019 – EN
3.7.5 Connecting the heat pump outdoor unit
INFORMATION
A separate manual containing instructions about installa­tion and operation is included with this component.
1 Follow the installation steps in Chap. 3.7.4. 2 Connect the heat pump outdoor unit to terminal strip XAG1 (see
Fig. 3-38).
Installation manual
23
3 Set-up and installation
Fig.3-38 Connecting the heat pump outdoor unit
INFORMATION
If the heat pump outdoor unit is shut off via a circuit spe­cified by the utility company, the indoor unit is not shut off.
3.7.6 Connecting the outside temperature sensor (optional)
The heat pump outdoor unit has an integrated outside temperature sensor which is used for weather-compensated inflow temperature control with frost protection function. The weather-compensated in­flow temperature control can be further optimised with the optional outside temperature sensor.
▪ Choose a location at about one third of the building height (min-
imum distance from floor: 2m) on the coldest side of the building (north or north-east). Ensure that the location is not near any ex­ternal heat sources (flues, air ducts), nor subject to direct solar ra­diation.
▪ Place outside temperature sensors in such a way that the cable
exit points face downwards (prevents the ingress of humidity).
CAUTION
Laying the sensor and mains lines in parallel within an in­stallation conduit can lead to major malfunctions during controlled operation of the indoor unit.
▪ Always lay the sensor line separately.
1 Connect the outside temperature sensor to a twin-core sensor
line (minimum diameter 1mm2).
2 Lay the sensor line to the indoor unit. 3 Follow the installation steps in Chap. 3.7.4. 4 Connect the sensor line to terminal strip XTA1 (see Chap. 3.7.2). 5 In the controller, RoCon+ HP set the [Outside temperature
sensor] parameter to "On" [→Main menu →Configuration →Sensors].
Fig.3-39 EXT switching contact connection
Operating mode Resistance RV Tolerance
Standby <680Ω ±5%
Heating 1200Ω Reduce 1800Ω
Summer 2700Ω Automatic 1 4700Ω Automatic 2 8200Ω
Tab.3-3 Resistance values for evaluating the EXT signal
INFORMATION
The input is not considered for resistance values greater than the value for "Automatic 2".
INFORMATION
The [Heating support (HZU)] function integrated in the Ro­Con+ HP controller (see the controller operating instruc­tions) makes it unnecessary to connect the EXT connec­tion to the burner blocking contact connection of the solar system.
3.7.8 EBA (external requirement request)
By connecting the EBA switching contact to the indoor unit (Fig. 3-40) and corresponding parametrisation in its RoCon+ HP controller, an external switching contact can be used to generate a heat request. If the switching contact is closed, the indoor unit switches to heating mode. The feed temperature is regulated to the temperature set in the [Feed temperature, heating mode] parameter [→Main menu →Configuration →Heating].
The EBA switching contact has priority over a request from the room thermostat.
The switching contact is not evaluated in cooling mode, standby, manual or summer mode. The heating limits are also ignored.
3.7.7 External switching contact
Connecting an external switching contact (Fig. 3-39) enables the op­erating mode of the indoor unit to be switched over.
The current operating mode is switched by a changing resistance value (Tab. 3-3). The changeover of the operating mode is only ef­fective for a long as the external switching contact is closed.
The operating mode has an effect on the direct circuit of the indoor unit as well as all other heating circuits connected to this device as an option.
When special functions (e.g. "Manual operation") are activated, the input is not evaluated.
Installation manual
24
Fig.3-40 EBA switching contact connection
Daikin Altherma ETS(X/H)(B)-D
Heat pump (indoor unit) with integrated heat accumulator
008.1448499_00 – 06/2019 – EN
3.7.9 Connecting an external heat generator
INFORMATION
To connect an external heat generator, the connection set for external heat generators must be installed (see
Chap. 3.5).
For heating support or as an alternative to an electric backup heater, an external heat generator (e.g. gas- or oil-fired boiler) can be con­nected to the indoor unit. To connect an external heat generator, the connection set for external heat generators must be installed (see
Chap. 3.5).
The heat supplied by the external heat generator must be fed to the unpressurised storage tank water in the hot water storage tank of the indoor unit.
Implement the hydraulic connection according to one of the two fol­lowing options:
unpressurised via the connections (solar inflow and solar re-
turn flow) of the hot water storage tank
for ...bivalent indoor unit device types, via the integrated
pressurised solar heat exchanger. ▪ Comply with the instructions on hydraulic connections (see
Chap. 1.2)
▪ Examples of hydraulic connection (see "Hydraulic connection"
in the installer reference guide).
The external heat generator request is connected on PCB RTX-EHS (see Fig. 3-41) via a relay. Electrical connection to the indoor unit is possible as follows:
▪ External heat generator has a potential-free switching contact con-
nection for heat request: ▪ Connection to K3 if the external heat generator is responsible
for the domestic hot water preparation and the backup heating (setting of the [Config. ext. heat source] parameter = DHW + heating support [→Main menu →Settings →Ext. source])
or
▪ Connection to K1 and K3 if two external heat generators are
used (setting of the [Config. ext. heat source] parameter = Two external heat generators [→Main menu →Settings →Ext. source]). In this case, K1 connects the external heat generator (e.g. gas-fired or oil-fired boiler) for heating support and K3 con­nects the external heat generator (EKBUxx) for domestic hot water preparation.
or
▪ Connection to AUX connection A (see Chap. 3.7.13)
▪ External heat generator can only be connected via mains voltage:
Connection (~230V, maximum load 3000W) to K1 and K3.
CAUTION
Danger of voltage flash-overs.
▪ The connections of the RTX-EHS PCB must not be
used simultaneously for connecting mains voltage (~230V) and SELV ("Safety Extra Low Voltage").
3 Set-up and installation
Fig.3-41 Connection on the RTX-EHS printed circuit board
1 Refer to the external heat generator's respective installation in-
structions for a suitable electrical connection.
2 Installing the connection set for external heat generators (see
Chap. 3.5).
3 Make suitable connections on the RTX-EHS PCB of the connec-
tion set (see Fig. 3-41).
4 Fix cables that are fed into the connection set from the outside
using the strain relief clips and cable ties included (see steps7
and 8 in Chap. 3.7.4).
Daikin Altherma ETS(X/H)(B)-D Heat pump (indoor unit) with integrated heat accumulator
008.1448499_00 – 06/2019 – EN
Installation manual
25
3 Set-up and installation
3.7.10 Connecting the room thermostat
INFORMATION
A separate manual containing instructions about installa­tion and operation is included with this component.
Fig.3-42 Connection with wired room thermostat (RT = Daikin
EKRTW)
A maximum of 16 devices with a total line length of up to 800m can be connected in the entire RoCon system.
EHS157034 room controller
A separate EHS157034 room controller can be connected for each heating circuit to enable remote adjustment of operating modes and target room temperatures from another room.
INFORMATION
Separate installation instructions are included with this component. See the enclosed control system manual for instructions on setting and operation.
EHS157068 mixer module
The EHS157068 mixer module can be connected to the indoor unit (J13 PCB connector) and is controlled by the electronic controller.
INFORMATION
Separate installation instructions are included with this component. See the enclosed control system manual for instructions on setting and operation.
EHS157056 Internet gateway
The controller can be connected to the internet with the optional EHS157056 gateway. This enables remote control of the indoor unit by mobile phones (by app).
INFORMATION
Separate installation instructions are included with this component. See the enclosed control system manual for instructions on setting and operation.
Fig.3-43 Connection with radio-controlled room thermostat (RT-E
= Daikin EKRTR)
3.7.11 Connection of optional RoCon system components
The optional RoCon devices must be connected to the indoor unit via a 4-wire CAN bus cable (connection J13).
For this, we recommend shielded lines with the following character­istics:
▪ Standardisation according to ISO11898, UL/CSA type CMX
(UL444)
▪ PVC outer sheath with flame retardancy according to
IEC60332-1-2
▪ Up to 40m, minimum cross-section 0.75mm2. Larger conductor
cross-section necessary with increasing length.
Commercially available junction boxes can be used to connect CAN bus lines of several RoCon devices.
Ensure that mains, sensor and data bus lines are routed separately. Use only cable ducts with separators or separate cable ducts spaced at least 2cm apart. Line crossings are permissible.
3.7.12 Connecting the HP convector
INFORMATION
Only the EKRTCTRL1 and EKWHCTRL(0/1) convector controllers can be connected to the indoor unit.
INFORMATION
A separate manual containing instructions about installa­tion and operation is included with this component.
INFORMATION
When changing the operating mode (Heating/Cooling) on a convector, all other convectors must either also be changed or deactivated.
Installation manual
26
Heat pump (indoor unit) with integrated heat accumulator
Daikin Altherma ETS(X/H)(B)-D
008.1448499_00 – 06/2019 – EN
Fig.3-44 FWX(V/M)-AATV3 connection
3.7.13 Connecting switching contacts (AUX outputs)
The switching contacts (AUX outputs) can be used for various para­metrisable functions.
Switchover contact A-A1-A2 switches under the conditions set in parameter [AUX switching function] [→Main menu →Settings →In­puts/Outputs] (see controller operating instructions).
3 Set-up and installation
Switchover contact A-A1-A2 can be used, for example, to control the heat generators in bivalent heating systems consisting of an indoor unit and an oil- or gas-fired boiler. Examples of hydraulic system in­tegration are described in "Hydraulic connection" in the installer ref­erence guide.
INFORMATION
If an A2F or G-plus condensing boiler is connected, the [AUX switching function ] and [AUX wait time] parameters must be set according to the desired function [→Main menu →Settings →Inputs/Outputs].
See Controller operating instructions → chapter Parameter settings.
Precise information on the electrical connection and the re­quired parameter settings for such bivalent heating sys­tems are available on the Internet (www.daikin.com) or from your service partner.
3.7.14 Off-peak mains connection (HT/NT)
If the outdoor unit is connected to a low rate mains connection, the potential-free switching contact S2S of the receiver, which evaluates the low rate input signal output from the utility company must be con­nected to plug J8, EVU connection on the RoCon BM2C PCB (see
Fig. 3-46).
When setting the [HT/NT function] parameter > 0 [→Main menu →Settings →Inputs/Outputs], certain system components are switched off during peak periods (see controller operating instruc­tions).
The following types of low rate mains connection are common: ▪ Type 1: With this type of low rate mains connection, the power
supply to the heat pump outdoor unit is not interrupted.
▪ Type 2: With this type of low rate mains connection, the power
supply to the heat pump outdoor unit is interrupted after a certain period of time.
▪ Type 3: With this type of low rate mains connection, the power
supply to the heat pump outdoor unit is interrupted immediately.
Potential-free switching contact S2S can be implemented as a nor­mally closed or normally open switching contact.
▪ If implemented as a normally closed switching contact, the [HT/NT
contact] parameter = 1 must be set [→Main menu →Settings →Inputs/Outputs]. When the utility company sends the off-peak signal, switching contact S2S is opened. The system switches to "Mandatory OFF". If the signal is sent again, potential-free switch­ing contact S2S closes and the system resumes operation.
▪ If implemented as a normally open switching contact, the [HT/NT
contact] parameter = 0 must be set [→Main menu →Settings →Inputs/Outputs]. When the utility company sends the off-peak signal, switching contact S2S is closed. The system switches to "Mandatory OFF". If the signal is sent again, potential-free switch­ing contact S2S opens and the system resumes operation.
Fig.3-45 Connection of switching contact (AUX output)
The relays user for variant 2 (switched output >15W) must be suit­able for a 100% power-on time.
Connection terminals B+B1 are not occupied for these devices or are available for additional functions.
The relays user for variant 2 (switched output >15W) must be suit­able for a 100% power-on time.
Daikin Altherma ETS(X/H)(B)-D Heat pump (indoor unit) with integrated heat accumulator
008.1448499_00 – 06/2019 – EN
Installation manual
27
3 Set-up and installation
[HT/NT contact] = 1 [HT/NT contact] = 0

3.8 Filling the system

Only fill the indoor unit after all installation work is completed in the order shown below.
3.8.1 Checking the water quality and adjusting the pressure gauge
1 Comply with the instructions for the water connection (see
Chap. 3.6) and for the water quality.
2 Adjust the mechanical pressure gauge (mounted on site in ac-
cordance with Chap. 3.6.1 or temporarily installed with filling hose): Turn the pressure gauge glass so that the minimum pres­sure marking corresponds to the system height +2m (1m wa­ter column corresponds to 0.1bar).
3.8.2 Filling hot water heat exchangers
1 Open the shut-off valve for the cold water supply pipe. 2 Open the hot water tap connections so that the draw-off volume
can be set as high as possible.
3 Once water has been discharged from the tap connections, do
not interrupt the cold water flow to ensure that the heat ex­changer will be fully vented and that any impurities or residue will be discharged.
3.8.3 Filling the storage tank
Fig.3-46 HT/NT contact connection
1 Mains connection box for low rate mains connection 2 Receiver for evaluating the HT/NT control signal 3 Power supply of the heat pump outdoor unit (see respect-
ive installation manual for the heat pump outdoor unit)
4 Potential-free switching contact for heat pump indoor unit
3.7.15 Connecting an intelligent controller (Smart Grid - SG)
If the [Smart grid] parameter = 1, the function [→Main menu →Set­tings →Inputs/Outputs] is activated (see controller operating instruc­tions), the heat pump is switched to normal or a mode with higher temperatures depending on the utility company signal.
For this purpose, the SG1/SG2 floating switching contacts of the in­telligent controller must be connected to the J8 connector, Smart Grid and EVU connections on the RoCon BM2C PCB (see
Fig. 3-47).
As soon as the Smart Grid function is active, the HT/NT function is automatically deactivated. Smart grid mode The heat pump is oper­ated differently depending on the value of the parameter [→Main menu →Settings →Inputs/Outputs] (see controller operating in­structions).
CAUTION
Filling the storage tank with too high a water pressure or too high a flow speed can cause damage to the indoor unit.
▪ Only fill with a water pressure <6bar and a flow speed
<15l/min.
Without installed solar system 1 Connect the filling hose with non-return valve (1/2") to the
"Solar inflow" connection (Fig. 3-48, item1).
2 Fill the storage tank of the indoor unit until water escapes from
the overflow connection (Fig. 3-48, item2).
3 Remove the filling hose with non-return valve (1/2").
With installed solar system 1 Install the filling connection with combined filling and draining
valve (accessory KFE BA) following the solar control and pump unit (EKSRPS4).
2 Connect the filling hose with non-return valve (1/2") to the pre-
viously installed combined filling and draining valve.
3 Fill the storage tank of the indoor unit until water escapes from
the overflow connection (Fig. 3-48, item2).
4 Remove the filling hose with non-return valve (1/2").
Fig.3-47 Connecting the Smart Grid
Installation manual
28
Heat pump (indoor unit) with integrated heat accumulator
Daikin Altherma ETS(X/H)(B)-D
008.1448499_00 – 06/2019 – EN
Fig.3-48 Filling the buffer tank - without connected DrainBack
solar system
1
Solar inflow
2 Safety overflow
3 Set-up and installation
INFORMATION
Comply with the instructions for the water connection (see
Chap. 3.6) and water quality (see Chap. 1.2.6).
1 Connect the filling hose (Fig. 3-49, item1) with the non-return
valve (1/2") and an external pressure gauge (on the building side) to the combined filling and draining valve (Fig. 3-49, item2) and secure it against slipping off with a hose clamp.
2 Connect the drain hose to the vent valve, and route it away from
the device. Open the vent valve with the hose connected; check to make sure that the other vent valve is closed.
3 Open the water tap (Fig. 3-49, item4) on the feed pipe. 4 Open the combined filling and draining valve (Fig. 3-49, item2)
and monitor the pressure gauge.
5 Fill the system with water until the external pressure gauge
shows that the system target pressure is reached (system height +2m; 1m water column = 0.1bar). The overpressure valve must not actuate!
6 Close the manual vent valve as soon as water emerges free of
bubbles.
7 Close the water tap (Fig. 3-49, item4). The combined filling and
draining valve must remain open in order to read off the water pressure on the external pressure gauge.
8 Switch on the power supply of the indoor unit. 9 In the RoCon+ HP controller in the "Operating mode" menu, se-
lect the "Heating" operating mode [→Main menu →Operating mode].
– After the start phase, the indoor unit runs in hot water heat-
ing operation.
10 Constantly check the water pressure on the external pressure
gauge during hot water heating mode, and top up water via the combined filling and draining valve (Fig. 3-49, item2) if neces­sary.
11 Vent the entire heating system as described inBleeding the hy-
draulic system (open the system's control valves. At the same time, the underfloor heating system can be filled and flushed by the underfloor distributor.
12 Again check the water pressure on the external pressure gauge,
and top up water via the combined filling and draining valve (Fig. 3-49, item2) if necessary.
13 Disconnect the filling hose (Fig. 3-49, item1) with non-return
valve from the combined filling and draining valve (Fig. 3-49, item2).
3.8.4 Filling the heating system
DANGER: RISK OF ELECTROCUTION
During the filling process, water can escape from any leak­ing points and can cause an electric shock if it comes into contact with live parts.
▪ Before the filling process, de-energise the indoor unit. ▪ After the first filling and before switching on the indoor
unit at the mains switch, check that all electric parts and connection points are dry.
WARNING
Polluted domestic water is hazardous to health.
▪ When filling the heating system, make sure that heating
water cannot flow back into the domestic water pipe.
Daikin Altherma ETS(X/H)(B)-D Heat pump (indoor unit) with integrated heat accumulator
008.1448499_00 – 06/2019 – EN
Installation manual
29
3 Set-up and installation
Lowest anticipated
outside temperature
Protection against
bursting
-5°C 10% 15%
-10°C 15% 25%
-15°C 20% 35%
-20°C 25%
-25°C 30%
Tab.3-4 Required glycol concentration
CAUTION
▪ The required concentration may vary depending on the
type of glycol. ALWAYS compare the requirements from the table above with the specifications provided by the glycol manufacturer. If necessary, meet the require­ments set by the glycol manufacturer.
▪ The added concentration of glycol must NEVER ex-
ceed 35%.
▪ If the fluid in the system is frozen, the pump CANNOT
start. Mind that if you only prevent the system from bursting, the liquid inside might still freeze.
▪ If NO glycol has been added to the system and a power
failure or a pump failure occurs, drain the water from the system.
▪ When the water inside the system is stationary, it can
easily freeze and thus damage the system.
Protection against
freezing
Fig.3-49 Filling the heating circuit
1 Filling hose with non-return valve (and pressure gauge 2 Combined filling and draining valve 3 Heater ball valve inflow 4 Heater ball valve return flow
5.1 Valve drive
5.2 Unlocking key of the drive lock 6 Water tap 7 Automatic vent valve 8 Pressure gauge
3UV DHW 3-way distribution valve (distribution valve, hot water/heat-
ing/heating support)
3UVB1 3-way distribution valve
MAG Diaphragm expansion vessel
(1)
)
Protecting the water circuit against freezing
Frost can damage the system. To prevent the hydraulic components from freezing, the software is equipped with special frost protection functions, that include the activation of pump, internal heaters, and/ or backup heater operation in case of low temperatures.
However, in case of a power failure, these functions cannot guaran­tee protection. It is therefore recommended to add glycol to the wa­ter circuit. The required concentration depends on the lowest expec­ted outdoor temperature, and on whether you want to protect the system from bursting or from freezing. To prevent the system from freezing, more glycol is required. Add glycol according to the table below.
CAUTION
Use only propylene glycol including the required inhibitors, classified as categoryIII as per EN1717.
CAUTION
Glycol absorbs water from its environment. Therefore do NOT add glycol that has been exposed to air. Leaving the cap off the glycol container causes the concentration of water to increase. The glycol concentration is then lower than assumed. As a result, the hydraulic components might freeze up after all. Take preventive actions to ensure a minimal exposure of the glycol to air.
CAUTION
▪ If overpressure occurs, the system releases some of
the fluid through the pressure relief valve. If glycol was added to the system, take adequate measures so as to safely recover it.
▪ Under all circumstances, make sure that the hose of
the pressure relief valve is ALWAYS free to release the pressure. Prevent water from staying and/or freezing up inside the hose.
INFORMATION
▪ Protection against bursting: the glycol protects the
pipes against bursting, but does NOT protect the fluid in the pipes against freezing.
▪ Protection against freezing: the glycol protects the fluid
in the pipes against freezing.
Installation manual
30
(1)
if not already installed in the heating system
Heat pump (indoor unit) with integrated heat accumulator
Daikin Altherma ETS(X/H)(B)-D
008.1448499_00 – 06/2019 – EN
Loading...
+ 314 hidden pages