Read this manual attentively before starting up the unit. Do not throw it away. Keep it in your files for future reference.
Improper installation or attachment of equipment or accessories could result in electric shock, short-circuit, leaks, fire or other damage to the equipment. Be sure only to use accessories made by Daikin which are specifically designed for the use with the equipment and have them installed by a professional.
If unsure of installation procedures or use, always contact your dealer for advice and information.
Contents
1. Introduction ............................................................................1
2. Installation of EKRTW............................................................ 2
3. Setting up codes in the installer menu...................................5
4. Technical characteristics ...................................................... 10

1. Introduction

The room thermostat EKRTW can be used to control floor heating-only applications and floor heating/cooling applications.
It is typically connected to the indoor unit. Refer to the "Typical application examples" in the Installation manual of the indoor unit.
In case of floor heating-only applications the room thermostat can also be connected to the individual motorized valve of the floor heating loop.
If a floor heating-only application is used in combination with fan coil units each fan coil unit should have its dedicated fan coil thermostat.
EKRTW Room thermostat 4PW44896-1C
Installation manual
1

2. Installation of EKRTW

The EKRTW thermostat is wall-mounted, with supplied screws and plugs. Refer to figure 1.
Cabling towards the indoor system (field supply) should be foreseen in advance taking the suggestions for an ideal installation location into account. Refer to figure 2.
Before obtaining access to terminals, all power supply circuits must be interrupted.
1
At the left of the thermostat, gently push the lid.
2
Remove the front cover by pulling it towards you.
3
Unscrew the screw of the cable holder in the bottom left corner of the back part of the thermostat and remove the transparent cable protection.
4
Remove the battery insulator.
4
1
5
Drill holes in the wall taking the dimensions of the thermostat into account and insert the supplied plugs in the holes.
Refer to figure 3 (unit of measurement: mm).
3
3
2
3
Installation manual
2
EKRTW
Room thermostat
4PW44896-1C
6
Pass the indoor unit or motorized valve wiring through the back of the thermostat.
7
According your application, perform the wiring.
7a
When connected to the indoor unit, wire the indoor unit and the thermostat as shown below.
EKHB(H/X)008
EKHB(H/X)007AC***
EKHB(H/X)016
X1M
HCL N
23 17 15 13
C
com
H
EKRTW
X1M
HCL N 1234
X2M
C
com
H
H Heating demand C Cooling demand
For heating-only applications, wire 17-C or 2-C is not to be installed. Use wire size 0.75~1.50 mm
EKRTW Room thermostat 4PW44896-1C