Indicates a situation that results in death or
serious injury.
DANGER:RISKOFELECTROCUTION
Indicates a situation that could result in
electrocution.
DANGER:RISKOFBURNING
Indicates a situation that could result in burning
because of extreme hot or cold temperatures.
DANGER:RISKOFEXPLOSION
Indicates a situation that could result in
explosion.
WARNING
Indicates a situation that could result in death
or serious injury.
WARNING:FLAMMABLEMATERIAL
CAUTION
Indicates a situation that could result in minor
or moderate injury
NOTICE
Indicates a situation that could result in
equipment or property damage
INFORMATION
Indicates useful tips or additional information.
Symbol
Explanation
Before installation, read the installation
and operation manual, and the wiring
instruction sheet.
Before performing maintenance and
service tasks, read the service manual.
For more information, see the installer
and user
WARNING
To prevent electric shocks or fire:
x
x Do NOT operate the unit with wet hands.
x
NOTICE
x
NOT place any objects or equipment
x
1 General safety
precautions
1.1 About the documentation
x The original documentation is written in English. All
other languages are translations.
x The precautions described in this document cover
very important topics, follow them carefully.
x The installation of the system, and all activities
described in the installation manual must be
performed by an authorized installer.
reference guide.
1.1.1 Meaning of warnings and
symbols
.
.
1.2 For the user
x If you are not sure how to operate the unit, contact
your installer.
x This appliance can be used by children aged from
8 years and above and persons with reduced
physical, sensory or mental capabilities or lack of
experience and knowledge if they have been given
supervision or instruction concerning use of the
appliance in a safe way and understand the
hazards involved. Children shall not play with the
appliance. Cleaning and user maintenance shall
not be made by children without supervision.
Do NOT rinse the unit.
Do NOT place any objects containing
water on the unit..
Do
on top of the unit.
Do NOT sit, climb or stand on the unit.
x Units are marked with the following symbol:
This means that electrical and electronic products may
not be mixed with unsorted household waste. Do NOT
try to dismantle the system yourself: the dismantling of
the system, treatment of the refrigerant, of oil and of
other parts must be done by an authorized installer
and must comply with applicable legislation.
Units must be treated at a specialized treatment
facility for reuse, recycling and recovery. By ensuring
this product is disposed of correctly, you will help to
prevent potential negative consequences for the
environment and human health. For more
information, contact your installer or local authority.
Page
Installation and user manual
NOTICE
Improper installation or attachment of
equipment or accessories could result in
electric shock, short
circuit, leaks, fire or other
damage to the equipment. Only use
accessories, optional equipment
and spare
parts made or approved by Daikin
WARNING
Make sure installation, testing and applied materials
comply with applicable legislation (on top of the
instructions
documentation).
CAUTION
Wear adequate personal protective equipment
(protective gloves, safety glasses,…) when
installing, maintaining or servicing the system.
DANGER:RISKOFBURNING
x Do NOT touch the refrigerant piping,
water piping or internal parts during and
operation. It could be
too hot or too cold. Give it time to return
to normal temperature. If you must touch
x
WARNING
Provide adequate measures to prevent that the unit
can be used as a shelter by small animals. Small
animals that make contact with electrical parts can
cause malfunctions, smoke or fire.
CAUTION
Do NOT touch the air inlet or aluminium fins
of the unit
NOTICE
x Do NOT place any objects or equipment
x Do NOT sit, climb or stand on the unit.
NOTICE
Works executed on the outdoor unit are best
done under dry weather conditions to avoid
water ingress
WARNING
During tests, NEVER pressurize the product
with a pressure higher than the maximum
allowable pressure (as indicated on t
nameplate of the unit).
WARNING
Take sufficient precautions in case of
refrigerant leakage. If refrigerant gas leaks,
ventilate the area immediately. Possible risks:
x
Excessive refrigerant concentrations in a
deficiency.
1.3 For the installer
1.3.1 General
If you are not sure how to install or operate the unit,
contact your dealer.
-
.
described in the Daikin
immediately after
it, wear protective gloves.
Do NOT touch any accidental leaking
refrigerant.
In accordance with the applicable legislation, it might be
necessary to provide a logbook with the product
containing at least: information on maintenance, repair
work, results of tests, stand-by periods,…
Also, at least, following information must be provided at
an accessible place at the product:
x Instructions for shutting down the system in case
of an emergency
x Name and address of fire department, police and
hospital
x Name, address and day and night telephone
numbers for obtaining service
In Europe, EN378 provides the necessary guidance for
this logbook.
1.3.2 Installation site
x Provide sufficient space around the unit for
servicing and air circulation.
x Make sure the installation site withstands the unit's
weight and vibration.
x Make sure the area is well ventilated. Do NOT
block any ventilation openings.
x Make sure the unit is level.
Do NOT install the unit in the following places:
x In potentially explosive atmospheres.
x In places where there is machinery that emits
electromagnetic waves. Electromagnetic waves
may disturb the control system, and cause
malfunction of the equipment.
x In places where there is a risk of fire due to the
leakage of flammable gases (example: thinner or
gasoline), carbon fibre, ignitable dust.
x In places where corrosive gas (example:
sulphurous acid gas) is produced. Corrosion of
copper pipes or soldered parts may cause the
refrigerant to leak.
.
on top of the unit.
.
4
If applicable. See the installation manual of your
application for more information.
closed room can lead to oxygen
he
1.3.3 Refrigerant
Installation and user manual
Page 5
x Toxic gas may be produced if refrigerant
DANGER:RISKOFEXPLOSION
Pump down
. If you
want to pump down the system, and there is a
leakage in the refrigerant circuit:
x
t's automatic pump
down function, with which you can collect
all refrigerant from the system into the
Possible consequence:
combustion and explosion of the
compressor because of air going into the
x
overy system so that
the unit's compressor does NOT have to
WARNING
Always recover the refrigerant. Do NOT
release them directly into the environment.
Use a vacuum pump to evacuate the
installation.
NOTICE
x
breakdown, do
NOT charge more than the specified
x When the refrigerant system is to be
according to the applicable legislation.
WARNING
Make sure there is no oxygen in the system.
Refrigerant m
performing the leak test and the vacuum drying.
If
Then
A siphon tube is present
(i.e., the cylinder is marked
with "Liquid filling siphon
attached")
Charge with the cylinder
upright.
A siphon tube is NOT
present
Charge with the cylinder
upside down.
CAUTION
When the refrigerant charging procedure is
done or when pausing, close the valve of the
refrigerant tank immediately. If the valve is not
closed immediately, remaining pressure might
charge additional refrigerant. Possible
consequence: Incorrect refrigerant amount.
NOTICE
Make sure water quality complies with EU
directive 98/83 EC.
DANGER:RISKOFELECTROCUTION
x
touching
x Disconnect the power supply for more
than 1 minute, and measure the voltage
at the terminals of main circuit capacitors
servicing. The voltage MUST be less
cal components. For the location of
the terminals, see the wiring diagram.
x Do NOT touch electrical components
x Do NOT leave the unit unattended when
gas comes into contact with fire.
– Refrigerant leakage
Do NOT use the uni
outdoor unit.
Self-
operating compressor.
Use a separate rec
operate.
x Open refrigerant cylinders slowly.
x Charge the refrigerant in liquid form. Adding it in
gas form may prevent normal operation.
To avoid compressor
amount of refrigerant.
1.3.4 Water
If applicable. See the installation manual of your
application for more information.
opened, refrigerant must be treated
1.3.5 Electrical
ay only be charged after
x In case re-charge is required, refer to the
nameplate of the unit. It states the type of
refrigerant and necessary amount.
x The unit is factory charged with refrigerant and
depending on pipe sizes and pipe lengths some
systems require additional charging of refrigerant.
x Only use tools exclusively for the refrigerant type
used in the system, this to ensure pressure
resistance and prevent foreign materials from
entering into the system.
x Charge the liquid refrigerant as follows:
Turn OFF all power supply before
removing the switch box cover,
connecting electrical wiring or
electrical parts.
or electrical components before
than 50 V DC before you can touch
electri
with wet hands.
the service cover is removed.
Page
Installation and user manual
WARNING
If NOT factory installed, a main switch or other
means for disconnection, having a contact
separation in all poles providing full
disconnection under overvoltage category III
condition, shall be installed in the fixed wiring.
WARNING
x
x
complies with
x
x NEVER squeeze bundled cables and make
sure they do not come in contact with the
no
external pressure is applied to the terminal
x Make sure to install earth wiring. Do NOT
absorber, or telephone earth. Incomplete
x
cuit. NEVER use a power supply shared
x Make sure to install the required fuses or
x
x
rotector, make sure it is compatible with
the inverter (resistant to high frequency
NOTICE
Precautions when laying power wiring:
x
thicknesses
to the power terminal block (slack in the power
x When connecting wiring which is the same
thickness, do as shown in the figure below.
x For wiring, use the designated power wire
prevent
x
x
s may
WARNING
x After finishing the electrical work, confirm
terminal inside the electrical components
x Make sure all covers are closed before
Over-tightening the terminal screw
break them.
Install power cables at least 1 metre away from
televisions or radios to prevent interference. Depending
on the radio waves, a distance of 1 metre may not be
sufficient.
ONLY use copper wires.
Make sure the field wiring
the applicable legislation.
All field wiring must be performed in
accordance with the wiring diagram
supplied with the product.
that each electrical component and
box is connected securely.
starting up the unit.
piping and sharp edges. Make sure
connections.
earth the unit to a utility pipe, surge
earth may cause electrical shock.
Make sure to use a dedicated power
cir
by another appliance.
circuit breakers;
Make sure to install an earth leakage
protector. Failure to do so may cause
electric shock or fire.
When installing the earth leakage
p
electric noise) to avoid unnecessary
opening of the earth leakage protector.
Do not connect wiring of different
wiring may cause abnormal heat).
and connect firmly, then secure to
outside pressure being exerted on the
terminal board.
Use an appropriate screwdriver for
tightening the terminal screws.
A screwdriver with a small head will
damage the head and make proper
tightening impossible.
6
Installation and user manual
Page 7
1.4 Glossary
Dealer
Sales distributor for the product.
Authorized installer
Technical skilled person who is qualified to
install the product.
User
Person who is owner of the product and/or
operates the product.
Applicable legislation
All international, European, national and local
directives, laws, regulations and/or codes that
are relevant and applicable for a certain product
or domain.
Service company
Qualified company which can perform or
coordinate the required service to the product.
Installation manual
Instruction manual specified for a certain product
or application, explaining how to install,
configure and maintain it.
Operation manual
Instruction manual specified for a certain product
or application, explaining how to operate it.
Accessories
Labels, manuals, information sheets and
equipment that are delivered with the product
and that need to be installed according to the
instructions in the accompanying documentation.
Optional equipment
Equipment made or approved by Daikin that can
be combined with the product according to the
instructions in the accompanying documentation.
Field supply
Equipment not made by Daikin that can be
combined with the product according to the
instructions in the accompanying documentation.
Page
Installation and user manual
WARNING!
The
can be used by children of at
least
by people with
reduced physical, sensory or mental abilities
or by those who lack the necessary
experience or knowledge
as they are
supervised or after they have received
instructions relating to the safe use of the
equipment
ng to
the use of such
Children must not play with the equipment.
Cleaning and
intended to be
carried out by the user must not be performed
by unsupervised children
2 Introduction
This installation and maintenance manual is to be
considered an integral part of the present heat pump
(hereafter referred to as equipment).
The manual must be kept for future reference until the
heat pump itself has been dismantled. This manual is
intended for both the specialised installer (installers –
maintenance technicians) as well as the end user.
The installation modes to be complied with in order to
achieve a correct and safe operation of the equipment
as well as methods of use and maintenance are
described in this manual.
In case of the sale of the equipment or the change of
owner, the manual must accompany the equipment to
its new destination.
Before installing and/or using the equipment, read this
instruction manual carefully and, in particular, chapter 5
relating to safety.
The manual must be kept together with the equipment
and, in any case, it must always be at the disposal of
the qualified personnel in charge of installation and
maintenance.
The following symbols are used inside the manual in
order to rapidly find the most important information
Information on safety
Procedures to follow
Information/ Suggestions
2.1 Products
Dear Customer,
Thank you for having purchased this product.
Our company has always paid a great deal of attention
to environmental problems, therefore, it has used
technologies and materials with a low environmental
impact to manufacture its products in conformity with
RAEE 2012/19/UE and RoHS 2011/65/UE community
standards.
2.2 Disclaimer
The conformity of the content of these user instructions
with hardware and software has been submitted to
thorough verification. Regardless of this, it is still
possible for some non-compliances to occur; therefore,
no liability will be assumed for complete conformity.
In the interest of achieving technical perfection, we
reserve the right to carry out modifications to the
equipment construction or to data at any time
whatsoever. Therefore we do not accept any liability
8
:
claims whatsoever attributable to instructions, figures,
drawings or descriptions, without prejudice to errors of
any kind.
The Supplier shall not be held responsible for damages
attributable to misuse, improper use, or as a
consequence of unauthorised repairs or modifications.
equipment
8 years of age as well as
, as long
as well as explanations relati
equipment.
maintenance
.
2.3 Copyright
These user instructions contain information protected
by copyright. It is forbidden to photocopy, duplicate,
translate or record these user instructions on memory
equipment, either in whole or in part without prior
authorisation of Daikin. Any breaches shall be subject
to the payment of compensation for any damage
caused. All rights are reserved, including those deriving
from the issuing of patents or the registration of utility
models.
2.4 Operating principle
The equipment belonging to the 1.9 kW and 2.9 kW
series is capable of producing domestic hot water
mainly by using heat pump technology. A heat pump is
capable of transferring thermal energy from a low
temperature source to another with a higher
temperature and vice versa (heat exchangers).
The equipment uses a water circuit consisting of a
compressor, an evaporator, a condenser and a
lamination valve; a liquid/gas coolant flows inside this
circuit (see paragraph 4.6).
The compressor creates a difference in pressure inside
the circuit that allows a thermodynamic cycle to be
obtained: this sucks the coolant fluid in through an
evaporator, where the fluid itself evaporates at a low
pressure by absorbing heat, it is compressed and
driven towards the condenser where the fluid
condenses at a high pressure releasing the absorbed
heat. After the condenser, the fluid passes through the
so-called “lamination valve” and by losing pressure and
the temperature starts to vaporise, it re-enters the
evaporator and the cycle starts all over again.
Installation and user manual
Page 9
Fig.
Version
Configuration description
EKHH2E200AAV3
EKHH2E200BAV33
EKHH2E260AAV3
Air source heat pump for
the production of domestic
hot water
EKHH2E260PAAV3
Air source heat pump for
the production of domestic
hot water suitable for use
with the solar power
system
WARNING!
Packaging items
staples, cardboard boxed,
etc.)
children as they are dangerous
Ecological heat
Evaporator
Lamination
Condenser
Tank
Compressor
.
3 Handling and transport
Air
Electric heat
1 – Operating principle
The operating principle of the equipment is as follows
(Fig. 1):
I-II: The coolant fluid sucked in by the compressor flows
inside the evaporator and while it evaporates, it absorbs
the “ecological” heat given by the air.
At the same time, the ambient air is sucked in by the
equipment by a fan; the air loses it heat by passing over
the finned-tube battery of the evaporator;
II-III: The coolant gas passes inside the compressor
and it under goes an increase in pressure that causes a
rise in temperature; transforming this into superheated
steam;
III-IV: Inside the condenser, the coolant gas releases its
heat to the water inside the tank (boiler). This exchange
process makes it possible for the coolant to pass from
superheated steam to a liquid state by condensing at a
constant pressure and undergoing a reduction in
temperature;
IV-I: The liquid coolant passes through the lamination
valve, it undergoes a sudden drop in both pressure and
temperature and it partially vaporises bringing pressure
and temperature back to the initial conditions. The
thermodynamic cycle can begin.
2.5 Available versions and
configurations
The heat pump is available, in relation to the thermal
power (1.9 kW version), which can be set up in different
configurations, depending on the possible integrations
with other heating sources (e.g. solar thermal, biomass
power, etc.).
valve
Hot water
Cold water
The equipment is supplied in a cardboard box (*). It is
fastened to a pallet with three screws.
Use a fork-lift truck or a pallet truck in order to unload
the equipment: it is opportune for these to have a load
capacity of at least 250 kg.
In order to make it
easier to loosen the
fixing screws the
packaged equipment
may be put in a
horizontal position on its
back side.
The unpacking
operations must be
carried out carefully so
as not to damage the
equipment enclosure if
this is carried out with
knives or cutters to
open the cardboard
packaging.
After having removed
the packaging, make sure that the unit is intact. If in
doubt, do not use the equipment and seek help from
authorised technical staff.
In conformity with environmental protection regulations,
make sure that all the accessories supplied have been
removed before discarding the packaging.
must not be left within the reach of
(
.
(*) Note: at Daikin’s discretion, the type of packaging
may be subject to change.
For the entire period in which the equipment remains
idle, waiting to be used, it is opportune to protect it from
atmospheric agents.
Page
Installation and user manual
WARNING!
During the product handling and installation
stages, it is forbidden to put the upper part of the
device under any kind of stress whatsoever due
to the fact that it is not of a structural nature.
WARNING!
The equipment can be transported horizontally
only during the last km according to what
indicated above (see “Positions permitted for
transporting and handling”) and taking care of
positioning some supports on the lower side of
the boiler in order not to lean against the upper
part, which is not of a structural nature. When
the equipment is transported horizontally, the
display must be oriented toward the upper side.
√
√
Positions permitted for transporting and handling:
Positions that are not permitted for transporting and
handling purposes:
10
Installation and user manual
Page 11
1
Heat pump
2
Control panel
3
E
4
Steel t
enamelled according to UNI
standards
5
Upper boiler probe
6
Lower boiler probe
7
Coolant re
8
Ambient air recirculation fan
9
Lamination
10
High
The quantity
of fluid put into this is regulated by an
appropriate thermostatic valve
11
Air
12
Air outlet
13
Hermetically
14
Replaceable magnesium anode
15
(1.5 kW
16
Condenser
17
C
18
Replaceable magnesium anode
19
Hot water outlet connection joint
20
Recirculation fitting
21
Inlet
thermal power system
(G
22
Condens
23
Outlet, coil fitting for solar thermal power
system
24
Cold water
25
50 mm polyurethane insulation
26
Automatic resetting safety pressure switch
29
Air
30
½”G fitting for probe immersion sleeve
1
4
6
11
10
9
2
8
18
25
24
16
14
5
4
15
12
22
19
23
20
21
17
3
29
7
13
26
30
4 Construction characteristics
.
.
nclosure in embossed ABS.
ank (boiler)
(capacity: 200; 260 litres).
.
.
charge.
.
valve.
-efficiency finned evaporator.
.
inlet ( 160 mm).
( 160 mm).
-sealed rotary compressor.
.
– 230 W) Electric heating element
pump discharge line.
ondenser return.
.
(G 1”).
(G ¾”).
, coil fitting for solar
1/4
1”
; 1 m2 exchange surface).
ate drain (G 1/2”).
1/4
(G 1”
; 1 m2 surface).
inlet connection joint (G 1”).
.
.
inlet filter.
Page
Installation and user manual
1.9 kW
Descriptions
u.m.
EKHH2E200AAV3
0AAV3
EKHH2E260PAAV3
EKHH2E200BAV33
HP
Total thermal
Heating time (
min
Heating time in BOOST mode (
min
Thermal losses (
Electrical data
Power supply
Frequency
Hz
Degree
HP
Average absorption
Heating element + HP maximum
absorption
Electric heating element power
Maximum current in HP
Required overload protections
characteristic C (to be expected
Internal protection
Operating conditions
Min.÷ max temperature heat pump
air intake (90% R.H.)
Min. ÷ max temperature installation
site
Working temperature
HP Maximum settable temperature ECO cycle
Maximum settable temperature in an
AUTOMATIC cycle
Compressor
Compressor protection
thermodynamic circuit protection
type
Fan
Ejection outlet diameter
Revolutions per minute
rpm
4.1 Technical characteristics
EKHH2E26
thermal power yield kW
power kW
1
) h:
1
)
h:
2
) W
V
of protection IPX4
maximum absorption kW
kW
8:17 10:14 10:14 7:05
3:58 5:06 5:06 3:02
60 70 71 53
1.82
3.4
1/N/230
50
0.53
0.43
kW
kW
A
16A T fuse/ 16A automatic switch,
A
during installation on power supply systems)
Single safety thermostat with manual reset on a resistive element
2.03
1.5
2.4
°C
°C
-7÷38
5÷38
°C
°C
Thermal circuit breaker with automatic reset
Safety pressure switch with automatic reset
56
70
Rotary
Centrifugal
mm
160
1650÷2100
12
Installation and user manual
Page 13
Nominal air capacity
/h
Max. pressure head
Pa
Motor protection
Condenser
Coolant
Load
Water storage
Water storage nominal capacity
Max. quantity of hot water that can
be used Vmax (
Coil for connection to solar thermal
power system
Cathodic protection
Mg AnodeØ26x400 mm
1 x Mg anodeØ26x250
1 x Mg anodeØ26x250
Mg anode Ø26x400 mm
Insulation
Defrosting
Dimensions
H1707xD600x
H2000xD600x
H2000xD600x
H1744xD600x
Transport weight
Sound power indoors Lw(A)
dB(A)
Automatic anti
disinfection cycle
Maximum working pressure
Bar
(
(
(
(
(
m
3
available
Internal thermal circuit breaker with automatic reset
Wrapped externally, not in contact with water
R134a
g
900 900 900 1300
l
3
)
l
2
m
196 252 242 196
275 342 342 266
N/A N/A 1.0 m
50 mm high-density polyurethane foam
kg
mm
D
650
max
103 115 132 105
(4)
-Legionnella
(5)
YES
1
) temperature of incoming air supply 7°C (6°C), temperature of boiler storage environment 20°C, water
heated from 10°C to 55°C, (according to UNI EN 16147-2011 and 2017)
2
) measurements carried out according to UNI EN 12897-2006
3
) measurements carried out according to UNI EN 16147-2011 and 2017
4
) measurements carried out according to EN 12102-2013
5
) automatic activation every 30 days of operation
350÷500
120
mm
+
mm
Active with Hot Gas valve
D
650
max
D
650
max
53
7
2
N/A
D
650
max
Page
Installation and user manual
WARNING!
This
nor is
it
environments
of
according to
a
level exceeding that of the
equipment
that require
(fault
characteristics
breaking
systems and/or technologies or in any other
context in which the malfunctioning of an
application could cause death or injury to
people or animals or serious damage
could
be caused
.
N.B.
In the event of a product breakdown or fault,
this could cause damage
to people, animals
and goods
. It is necessary to arrange for
a separate functional monitoring system
with
functions in order to avoid such
damage being caused
necessary to
up service in
case of failure!
N.B.
Daikin
shall not be held responsible under any
circumstances in the event that the equipment
is used for other purposes than for which it has
been designed and as regards any installation
errors or
WARNING!
It is forbidden to use the
for purposes
other than those intended
Any other use is to
be considered improper and therefore not
allowed
N.B.
During the design and construction stage of the
systems, current local rules and provisions are
complied with
N.B.
Maintenance
operations must be
carried out only by qualified personnel
WARNING!
Installation
maintenance of
the
by qualified and
authorised personnel
Do not attempt to install
the
5 Important information
5.1 Conformity with European regulations
The present heat pump is a device intended for
domestic use in conformity with the following European
directives:
x 2011/65/UE Directive on the restrictions of use of
certain hazardous substances in electric and
electronic equipment (RoHS);
x Directive 2014/30/UE - Electromagnetic
compatibility (EMC);
x Directive 2014/35/UE – Low Voltage Directive
(LVD)
x Directive 2009/125/CE Ecodesign Requirements.
5.2 Degrees of protection
provided by enclosures
The degree of protection of the equipment is equal to:
IPX4.
5.3 Limitations of use
device has not been designed,
intended for use within hazardous
potentially explosive atmospheres –
requested IP
alarm
5.4 Operating limits
The above mentioned device is intended to be used
exclusively for the heating of domestic hot water within
the foreseen limitations of use.
The equipment can only be installed and started up for
the intended use within closed heating systems in
conformity with the EN 12828 standard.
14
(due to the presence
ATEX standards or with
) or in applications
-tolerant, fail-safe) safety
such as in circuit-
to objects or the environment
)
arrange for a back-
(
. Moreover, it is
equipment misuse.
device
.
.
.
5.5 Fundamental safety rules
x The device must be used by adults;
x Do not open or disassemble the device when this
is connected to the power supply;
x Do not touch the device with wet or humid body
parts when barefoot;
x Do not pour or spray the device with water;
x Do not stand, sit and/or rest anything on the
device.
5.6 Information on coolant used
This device contains fluorinated greenhouse gas
included in the Kyoto protocol. Do not discard such gas
into the environment.
Coolant type: HFC-R134a.
and disposal
.
6 Installation and
connections
, commissioning and
device must be performed
device yourself.
.
Installation and user manual
Page 15
Fig.
X1
X2
X3
Y1
mm Mm
mm
mm
3
EKHH2E260PAAV3
650
650
200
300
WARNING!
In order to avoid the propagation of mechanical
vibrations
on floor
slabs with wooden beams
Fig.
Fig.
X3
Y1
X2X1
Ð
≥
6.1 Preparation of the
installation site
The installation of the device must be carried out in a
suitable place in order to allow the normal use and
adjustment operations, together with ordinary and
extraordinary maintenance to be performed.
Therefore it is important to allow for the necessary
working space by referring to the dimensions shown in
Fig. 2.
500 kg
2 – Minimum spaces
Model
EKHH2E200AAV3
EKHH2E200BAV3
EKHH2E260AAV3
Moreover, the premises must:
x Have adequate water and power supply lines;
x Be available and ready for connection to the
condense drain;
x Be available and ready with adequate discharge
pipes in case of damage caused to the boiler or
actuation of the safety valve or breakage of
pipes/connections;
x Have containment systems in case of serious
water leaks;
x Be sufficiently lit (where appropriate);
x Not measure less than 20 m
x Be frost-proof and dry.
3
;
6.1.1 Securing to the floor
To secure the product to the floor, fasten the supplied
brackets as shown in fig. 3.
3 - Fastening brackets
Then secure the unit to the floor with the aid of suitable
plugs not supplied, as shown in fig. 3a.
3a - Securing to the floor
6.2 Ventilation connection
Apart from the space indicated in paragraph 6.1, the
heat pump requires adequate ventilation.
It is necessary to create a dedicated air duct as
indicated in the following illustration (Fig. 4a and 4b).
, do not install the equipment
(e.g. in lofts).
Page
Installation and user manual
Fig.
Fig.
During operation, the heat pump tends to lower
the ambient temperature if the external air duct
is not carried out.
An appropriate protection grid must be installed
in line with the
conveying air to
the outside with the aim of avoiding foreign
bodies from entering the
In order to
guarantee maximum
performance, the
grid chosen must ensure low pressure loss.
In order to avoid the formation of condensate:
insulate the
pipes and the air duct
cover connections with steam
cladding of an adequate thickness.
If it is considered necessary in order to prevent
flow noise, s
on back
Example AExample B
Fig. 4 – Example of dual duct connection
Outside
Outside
side (optional)
3b – Example of dual duct connection
Carry out the installation of each air duct taking care
that:
x The weight of such does not adversely affect the
equipment itself;
x Maintenance operations can be carried out;
x This is adequately protected so as to avoid the
accidental intrusion of material inside the
equipment itself;
xIt doesn’t exceed the maximum suggested length
of 6 meters (with 2 elbow junctions 90°).
x The maximum total allowable pressure drop for all
components, including through holes for mounting
on external wall, within the pipe system does not
exceed 120 Pa.
4a – Example of an air outlet duct
Moreover, it is important to ensure an adequate
ventilation of the premises where the equipment is to be
installed.
An alternative solution is indicated in the following
illustration (Fig. 4 and 4b): this consists of a second
duct that draws air in from outside instead of directly
from inside the premises.
16
discharge pipe
equipment.
device
air discharge
-tight thermal
ound mufflers can be mounted.
Installation and user manual
Page 17
Fit the pipes, the wall through holes and the
connections to the
vibration
damping systems.
WARNING!
The simultaneous operation of an
firebox
together
with the
environmental
This could cause
the backflow of exhaust gas into the
environment itself
Do not operate the
together with
an
Use only sealed
approved)
with a separate duct for combustion air
Keep the doors to the boiler room closed and
hermetically
combustion air supply in common with
inhabited
Fig.
Fig. 5b
closed
open
open
closed
heat pump with
(e.g. an open-flue fireplace)
heat pump causes a dangerous
pressure drop.
open-flue
.
open-flue firebox.
heat pump
-chamber fireboxes (
.
sealed if it does not have a
areas.
conditions
One of the peculiarities of the heat pump heating
system is represented by the fact that these units cause
a considerable reduction of the air temperature that is
generally ejected from inside the home. Apart from
being colder than the ambient air, the exhaust air is also
completely dehumidified; for this reason, it is possible to
allow the air to flow back into the home in order to cool
specific environments or rooms during the summer.
Installation consists of the splitting of the discharge pipe
to which two shutters are applied (“A” and ”B”) with the
aim of directing the air flow either towards the inside
(Fig. 5a) or the outside of the home (Fig. 5b).
Shutter “A”
Outside area
4a – Example of installation in summer
Shutter “B”
Indoor area
6.2.1 Particular installation
Shutter “A”
Outside area
Shutter “B”
Indoor area
– Example of installation in winter
Page
Installation and user manual
Fig.
A B C
D
E F G
mm
mm
mm
mm
mm
mm
mm
650
2000
600
160
1391
1190
1085
H I J K L M N
mm
mm
mm
mm
mm
mm
mm
980
860
275
70
150
380
195
O
P
Q R
mm
mm
mm
mm
337,5
10
850
A B C
D
E F G
mm
mm
mm
mm
mm
mm
mm
650
1504
1714
600
160
891
1101
670
795
H I J K L M N
mm
mm
mm
mm
mm
mm
mm
/
590
275
70
150
380
195
O
P
Q R
mm
mm
mm
mm
337,5
10
535
560
Pos.
Description
Connection/hole
Cold water
G
H
G 1”
Condensat
G
R
G
Coil for solar thermal
power
G
Probe immersion sleeve
(only in models provided
with it)
½”G
Fig. 7
Air outlet
Air inlet
N
M
Q
P
h
D
P
6.3 Device mounting and
connection
The device must be installed on a stable, flat floor
surface that is not subject to vibration.
E
F
G
H
5 – Overall dimensions
Ø
D
LOM
A
B
I
J
K
C
N
Ø
P
(200l versions)
6.4 Water supply connections
Connect the cold water inlet and the outlet pipes to the
appropriate connection points (Fig.7).
The table below shows the characteristics of the
connection points.
c
N
O
P
Q
h
inlet pipe
ot water outlet pipe
e drain
ecirculation pipe
1”
½”
¾”
1”
1/4
(260l versions)
– Water supply connections
18
Installation and user manual
Page 19
Fig. 8
N.B.
It is compulsory to install a dirt filter on the cold
water inlet pipe
The equipment should not work
with water hardness lower
contrary, when the water hardness is particularly
high
it is recommended to use
a water softener
monitored; in this case the residual hardness
should not
PLEASENOTE!
It is
the system installer to install
a 7
bar safety valve on the cold water intake
pipe
N.B.
The safety
for protection against
over
pressure must be operated regularly in
order to remove limescale deposits and to
check that it is not blocked
N.B.
For a proper installation of the equipment, a
hydraulic safety group
UNI
EN 1487:2002
standard should be provided. It
should include at least:
check valve, a control device of the check
valve, a safety valve, a device to interrupt the
water load
N.B.
The drain hose connected to the equipment
for overpressure protection must be installed
with a continuous downward slope (slope> 3
°) and in an area protected aga
formation of ice (Fig. 8)
WARNING!
In case an expansion vessel
installed, make sure that in
cold water
intake there is not any non
installed.
WARNING!
The
for the production of domestic
hot water is capable of heating water up to
more than
protection against burns, it is necessary to
insta
equipment
Boiler connection
The following illustration (Fig. 8) shows an example of a
water supply connection.
advisable for
(Fig. 8a).
equipment
(Fig. 8a)
in accordance to
a shut-off valve, a
M Water inlet pipe;
N Shut-off valve;
O Automatic thermostat mixing equipment
P Heat pump
Q Ricirculation pump
R Spring check valve
S Hot water outlet pipe
T Safety valve
U Inspectionable end of discharge pipe
V Drain tap
Expansion vessel
L
Pressure regulator
M
Pressure gauge
– Example of the water supply system
Fig. 8a – Example of heavy series safety valve
.
(higher than 25°F),
than 12°F; on the
, properly calibrated and
fall below 15°F.
Cold water inlet
Drain tap connection
(Fig. 8a)
inst the
is not being
the
-return valve
heat pump
60°C. For this reason, as a
ll an automatic thermostat mixing
to the hot water pipe (Fig. 8).
Page
Installation and user manual
Fig. 9a
connection
via siphon
Fig. 9b
using siphon with water
Fig. 10
≥ 60
≥ 60
Ø20
G ½”
M
N
O
P
Q R S
U
T
6.4.1 Condense drain connections
Condensate that forms during the operation of the heat
pump flows through an appropriate discharge pipe
(G 1/2”) that passes inside cladding and it comes out on
the side of the equipment.
This must be connected to a duct via a siphon so that
the condensate can flow freely (Fig. 9a or Fig. 9b).
– Examples of condensate drain
6.5 Solar power system
integration
The following illustration (Fig. 10) shows an example of
solar power system integration.
M Cold water intake pipe
N Solar power system pump and accessories
O Solar collectors
P Heat pump
Q Recirculation pump
R Spring check valve
S Drain tap
T Solar thermal power coil
U Hot water outlet pipe
– Example of condensate drain connection
20
interceptor
– Example of solar power system integration
Installation and user manual
Page 21
It is advisable to carry out a check on the
electrical system to verify conformity to the
regulation in force.
Verify that the electrical system can suitably
withstand the water heater’s maximum power
consumption values ( refer to data plate), in
terms of the size of the cables and their
conformity to the regulation in force. It is
forbidden to use multiple outlet sockets,
exte
connection of the appliance is required. It is
forbidden to use piping from the water, heating
and gas systems for earthing the appliance
Prior to operating the machine, make sure that
the electricity mains voltage conforms to the
value indicated on the appliance’s data plate.
The manufacturer of the appliance shall not be
held liable for any damage caused by failure to
eart
the system or due to anomalies in the
electric power supply. To disconnect the
appliance from the mains, use a bipolar swith
complying with all applicable CEI
regulations in force ( minimum distance
between contacts 3 mm, switch preferably
equipped with fuse). The appliance must comply
with European and national standards, and
must be protect by a 30
mA differential switch.
Fig. 11
socket
Fig. 12
plug
Fig. 13
6.6 Electrical connections
The appliance is supplied with a power supply cable
(should the latter need to be replaced, use only original
spare parts supplied by the manufacturer or its service
agent). It is powered through a flexible cable and a
socket/plug combination (Fig. 11 and Fig. 12). An
earthed Schuko socket with separate protection is
needed for the connection to the mains power supply.
nsion cable or adaptor. The earth
h
-EN
and time set by C13 is passed or immediately if
the lower probe temperature is lower than SP8.
xDigital 2: Input from photovoltaic system.
When a free contact is established between
terminals 31 and 32 (cable: green/white) and the
heat pump reaches the SP5 temperature (default
setting 62°C), the hot water nominal temperature is
raised by 7°C. It is possible to change the SP6
parameter (e.g.: raising the temperature from 62°C
to 70°C) so that, if there is enough PV electrical
energy, the heat drop from 62°C to 70°C is made
by the immersion electric heating element (if SP6
is the same as SP5, the electric heating element
will never activate).
6.6.1.1 Remote link mode
As regards links to digital inputs, the equipment is
provided with an additional 4-core cable that has
already been linked to circuit board of the user interface
(placed inside the equipment Fig. 14). The remote links
to any energy systems must be carried out by a
qualified installer (junction boxes, terminals and
connection cables).
The following illustrations show an example of a remote
link (Fig. 13 and Fig. 13a).
3031 31 32
30313132
–A Schuko
– Equipment
6.6.1 Remote links
The equipment is designed to be connected to other
remote energy systems (photovoltaic and solar thermal
power systems).
The user interface has two digital inputs with the
following functions:
xDigital 1: Input from the solar thermal power
system. When a free contact is established
between terminals 30 and 31 (cable: brown/yellow)
and the water temperature measured by lower
probe is higher than SP8, the heat pump stops and
water is heated up by the solar panels; the heat
pump starts again when the contact is released
– Example of a remote link
Page
Installation and user manual
Fig. 13
Fig. 14
Fig. 15
Digital input 1
Digital input 2
probe 3
probe 2
probe 1
supply
resistance
defrost
a - Detailed example of a remote link
To access the 4-core cable for remote connection it is
necessary to remove the upper cover of the boiler (see
paragraph 9.1 Fig. 18), and take the cable outside
through the dedicated opening, that is already present
on the back cover, as indicated in Fig. 14.
6.7 Wiring diagram
– Wiring diagram
port 1
(upon
request)
port 1
(upon
request)
– Cables for remote connection
22
Installation and user manual
Page 23
WARNING!
Check that the
connected to the
earth cable
WARNING!
Check that the line voltage corresponds to that
indicated on the
plate.
Below, the term “start” intends the switching
from the Stand
by to the ON status; the term
“switch off” intends the switching from the ON
to the Stand
Below, the term “advanced procedure” refers
to particular procedures of the tool described
in the paragraphs relating to “advanc
management”.
Fig. 16
By means of this key it is possible:
this
status, the instrument can automatically switch on
in certain time slots and independently enable the
When the equipment is switched on, it shows
the status it was in when it was previously
switched off.
By means of this key it is possible to:
By means of this key it is possible to:
By means of
O
7 Commissioning
equipment is
.
equipment identification
The commissioning procedure must be carried out by
performing the following procedures:
x Fill the boiler by acting on the water inlet tap and
check that there are no leaks from gaskets and
connections. Tighten the bolts or connections
where necessary;
x Do not exceed the maximum permitted pressure
indicated in the “general technical data” section;
x Check that the water circuit safety equipment is
working;
x Connect the plug to the power socket;
x When the plug is inserted, the boiler is in stand-by,
the display remains switched off, the power key is
illuminated;
x Press the power key (see paragraph
equipment starts up in the “ECO” mode (default
setting) 5 minutes after pressing the key.
), the
8 Operation and use
The management of the device is assigned to a user
interface that enables the:
x Setting of the operating mode;
x Modification of the operating parameters;
x Display and management of any emergency
situations;
x Verification of the state of resources.
8.1 The User Interface
The user interface (Fig. 16) allows the verification and
the adjustment of the equipment operation. This is
equipped with a display and the following keys:
x On/Stand-by key;
x SET key;
x DOWN key;
x UP key.
Display
SET key
ON/Stand-by key
– User interface
8.1.1 Interface keys and display
8.1.1.1 The ON/Stand-by key
x To switch the device on (ON status);
To switch the device to the Stand-by status (in
x
anti-Legionella and defrosting functions.
8.1.1.2 The [SET] key
Confirm set choices or values.
x
DOWN
UP key
key
-
-by status.
ed
8.1.1.3 The [UP] key
Scroll up the list of the various parameters;
x
Increase the value of a parameter.
x
8.1.1.4 The [DOWN] key
this key it is possible to:
Scroll down the list of the various parameters;
x
Reduce the value of a parameter.
x
Page
Installation and user manual
The interface display (
) makes it possible to
visualise:
Fig. 17
Compressor
LED
If this is lit: the compressor is
active.
It this is flashing:
switching on procedure
The modification of the
operating set points is in
Defrosting
LED
If this is lit: defrosting is in
progress
MF LED
If this is lit: the electric heating
element is on
Fan LED
If this is lit: the fan is active
Maintenance
LED
If this is lit: maintenance of the
air filter is required (if present)
Alarm LED
If this is lit: check the list of
alarms and follow the
procedure indicated in this
manual
Degree
Celsius LED
If this is lit: the unit of
measurement for
temperatures is the degree
Celsius
Degree
Fahrenheit
LED
If this is lit: The unit of
measurement for
temperatures is the degree
Fahrenheit.
On/stand-by
LED
If this is lit: the equipment is in
the stand
If it is flashing, the equipment
has been switched on/off
manually during a switching
on/off
timeslot.
Not used
Loc
The keyboard is locked (see paragraph
).
dEFr
The defrosting procedure is in progress and it is
not possible to enable other functions
Anti
The “Anti
ObSt
The “Overboost” function is in
ECO
The “Economy” function is in progress.
Auto
The “Automatic” function is in progress.
When the equipment is switched on for the
first time, it is pre-set in the ECO (Economy)
mode with a water set point of 55°C with the
aim of guaranteeing the best possible energy
saving function with the support of only
renewable energy sources. Please note that
the use of such function guarantees the user
an average energy saving of approx. 70%
when compared to a normal electric boiler.
8.1.1.5 The Interface Display
Regulation temperatures;
x
Alarm/Error codes;
x
x
Status messages;
Operating parameters.
x
– User interface display
Fig. 17
x
The compressor
is in progress.
x
progress;
-by status.
progress.
8.1.2 Operating logic
8.1.2.1 Operating modes
The equipment foresees the following operating modes:
xAUTOMATIC operating mode:
This mode mainly uses the renewable energy of
the heat pump as a support measure, the electric
heating elements can be enabled; these latter
heating sources are enabled if the water
temperature is below a certain level, or in the
event that a temperature exceeding SP5
parameter is required;
xECONOMY operating mode:
This mode uses only the renewable energy of the
heat pump without ever enabling the electric
heating elements. It takes longer to enable but it
has considerable energy saving characteristics;
x OVERBOOSToperating mode:
This mode makes it possible to heat water rapidly
by using both the heat pump and the electric
heating elements. This function can be manually
enabled when the temperature of the water inside
the storage tank is lower than SP3 parameter.
At the end of the heating process, the function
is automatically disabled and the equipment
is automatically restored to the Automatic or
Economy mode depending on which of these
functions was previously set by the user;
xANTI-LEGIONELLA operating mode
This function is used as an anti-bacterial treatment
by increasing the temperature of the water to
60°C. This function is periodically and, in any case,
automatically enabled every 30days, regardless of
the operating mode enabled;
x DEFROSTINGmode
This function is necessary in order to eliminate the
frost deposits that form and which prevent heat
transmission. This function is automatically
enabled when the equipment is operated at low
environmental temperatures.
8.1.1.6 Warnings
-Legionella” function is in progress.
24
period in a certain
8.1.3.3
Installation and user manual
Page 25
Manual switching on/off always has the priority
over the timeslot o
If the keyboard has been locked (paragraph
8.1.3.3
progress, it will not be possible to carry out the
normal switching on/off of the equipment.
Every time the equipment is switched on, a
series of internal inspections are carried out
before the heat pump is enabled. Such
condition is reported by means of the flashing
of the compressor indicator light . Once the
verification period has passed (approx. 5
minutes) the indicator light remains lit and this
indicates that the unit is switched on.
By pressing any key, “Loc
for 1 second on the display.
8.1.3 Basic management
8.1.3.1 Manual switching on /off of the
equipment
x Keep the key pressed for 1 second: the
on/stand-by LED will switch off/on.
x The equipment can be switched on/off also in
certain timeslots; the parameters HOn and HOF
can be seen (paragraph 8.1.3.6).
perating mode.
) or an advanced procedure is in
8.1.3.2 Change of operating mode
(AUTOMATIC, ECONOMY
and OVERBOOST)
8.1.3.2.1 AUTOMATIC operating mode
To manually start the AUTOMATIC mode, carry out the
following procedure:
x Make sure that the keyboard is not locked
(paragraph 8.1.3.3) and that no other advanced
procedure is in progress
x Press per the key for 1 second, “Auto” starts
to flash;
x Press the key again to confirm and start the
AUTOMATIC operating mode.
To exit the procedure:
x Press the key to exit this procedure without
changing the mode.
8.1.3.2.2 ECO (economy) operating mode
To manually start the ECO operating mode, carry out
the following procedure:
x Make sure that the keyboard is not locked
(paragraph 8.1.3.3), that no other advanced
procedure is in progress and that the equipment
is not in the Overboost operating mode;
;
x Press the key for 1 second, “ECO” starts to
flash;
x Press the key again to confirm and start the
ECONOMY operating mode.
To exit the procedure:
x Press the key to exit this procedure without
changing the mode.
8.1.3.2.3 OVERBOOST operating mode
To manually start the OVERBOOST operating mode,
carry out the following procedure:
x Make sure that the keyboard is not locked
(paragraph 8.1.3.3) and that no other advanced
procedure is in progress;
x Press the key for 1 second, either “ECO” or
“Auto” starts to flash;
x Press the or keys until “ObSt” flashes on
the display;
x Press the key again to confirm and start the
OVERBOOST operating mode.
To exit the procedure:
x Press the key to exit this procedure without
changing the mode.
8.1.3.3 Keyboard locking/unlocking
To lock the keyboard, carry out the following procedure:
x Make sure that no other advanced procedure is in
progress;
x Keep the and the keys pressed for
1 second: “Loc” will be shown on the display for
1 second.
If the keyboard is locked, it will not be possible to carry
out any kind of operation on the display interface.
” will be shown
To unlock the keyboard:
x Keep the and the keys pressed for
1 second: “UnL” will be shown for 1 second
on the display.
8.1.3.4 Temperature setting in the ECO
operating mode (SP1)
x Make sure that the keyboard is not locked
(paragraph 8.1.3.3) and that no other advanced
procedure is in progress
x Press and release the key: “SP1” will be
shown on the display;
x Press and release the key: the compressor
LED will flash;
x Press either the or the key within 15
seconds; parameters r3, r4 and r5 can be seen;
;
Page
Installation and user manual
N.B.
Before proceeding with the timeslot settings,
set day and real time as described in
paragraph
Carefully evaluate enabling of time slot operation
in order to avoid malfunctions caused by users.
N.B.
The following instructions are reserved for
specialised technical assistance personnel.
x Press and release the key or do not carry out
any other operations for 15 seconds: the
compressor LED will switch off;
x Press and release the key.
To exit the procedure before its completion:
x Do not carry out any operations for 15 seconds
(any changes will be saved).
8.1.3.5 Temperature setting in the
Automatic mode (SP2)
x Make sure that the keyboard is not locked
(paragraph 8.1.3.3) and that no other advanced
procedure is in progress;
x Press and release the key: “SP1” will be
shown on the display;
x Press either the or the key until “SP2” is
shown on the display;
x Press and release the key: the compressor
LED will flash;
x Press either the or the key within 15
seconds; parameters r1, r2 and r5 can also be
seen;
x Press and release the key or do not carry out
any other operations for 15 seconds: the
compressor LED ( ) will switch off;
x Press and release the key.
To exit the procedure before its completion:
x Do not carry out any operations for 15 seconds
(any changes will be saved).
8.1.3.6 Timeslot settings for the switching
on/off of the equipment
x Press and release either the or the key
and within 15 seconds;
x Press and release the key or do not carry out
any other operations for 15 seconds.
To associate a time slot to a certain day of the week:
x After the previous procedure has been carried out,
press either the or the key and then let it
go within 15 seconds in order to select “Hd1”
(switch on time for day 1, or rather Monday) and/or
“Hd2...7” (switching on time for days 2-7, or rather
Tuesday-Sunday);
x Press and release the key;
x Press and release either the or the key
within 15 seconds in order to select “1” (the first
switch on/off time) or “2” (the second switch on/off
time);
x Press and release the key or do not carry out
any other operations for 15 seconds.
To exit the procedure before its completion:
x Do not carry out any operations for 15 seconds
(any changes will be saved) or press the key
and then let it go.
8.1.3.7 Display of the operating status
x Make sure that the keyboard is not locked
(paragraph 8.1.3.3) and that no other advanced
procedure is in progress;
x Press and release the key:
Auto/ECO/Obst/Anti will be displayed for 3
seconds depending on the current active operative
status.
8.1.3.14.
To start the procedure:
x Make sure that the keyboard is not blocked and
that no other advanced procedure is in progress;
x Press and release the key: “SP1” will be
shown on the display.
To set the first timeslot:
x Press and release either the or the key
within 15 seconds to select “HOn1” (first switching
on time) and/or “HOf1” (first switching off time);
select “HOn2” and “HOF2” for the second
switching on/off time;
x Press and release the key;
26
8.1.3.8 Silencing of the alarm sound
To silence the alarm, carry out the following procedure:
x Make sure that no other advanced procedure is in
progress;
x Press any key once.
Installation and user manual
Page 27
NOTE
In case of “
addition to the display visualization, the
equipment emits an acoustic signal that can
be switched off pressing any key on the
controller. The alarm it is never canceled
unless the equipment is switched off or put in
stand
The heat pump working mode is automatically
disabled and the one with electric resistance is
activated in order to ensure the continuity of
the warm water supply.
PLEASENOTE!
In case of “UtL” alarm it
contact the technical assistance.
AL
Minimum temperature alarm
Solution:
- Check the temperature associated with the
- Parameters displayed: A0, A1, A2 and A11.
-
AH
Maximum temperature alarm
Solutions:
- Check the temperature associated with the
- Parameters displayed: A3, A4, A5 and A11.
Main consequences:
-
id
Digital input alarm
Solutions:
- Check the causes that originated the input
-
Main consequences:
-
-
iSd
Blocked
Solutions:
- Check the causes that originated the digital
-
- Switch the equipment off and then back on
again or disconnect the equipment from the
Main consequences:
-
-
FiL
Ventilation filter check alarm
Solutions:
-
clean the filter is (to switch off the
UtL
Probable fan fault
Solutions:
-
-
Main consequences:
-
-
occurs using only the electric
8.1.3.9 Different operating mode start
conditions
Each operating mode must comply with precise
conditions in order to be enabled:
xAUTOMATIC operating mode
The condition in order to enable the start of this
function is as follows: lower probe< SP2 – r0
(hysteresis);
xECO operating mode
The condition in order to enable the start of this
function is as follows: lower probe< SP1 – r0
(hysteresis);
xOVERBOOST operating mode
The condition in order to enable the start of this
function is as follows: lower probe< SP3and upper
probe< SP3.Once a temperature exceeding SP3
has been detected, the Overboost operating mode
terminates and the previously set operative mode
is restored.
8.1.3.10 The display
If the equipment is in the “ON” status, during normal
operation, the display will show the established
temperature by means of parameter P5:
x If P5 = 0, the display will show the temperature of
the upper part of the boiler;
x If P5 = 1, the display will show the active working
set point;
x If P5 = 2, the display will show the temperature of
the lower part of the boiler;
x If P5 = 3, the display will show the temperature of
the evaporator;
xIf the equipment is in the “stand-by” status, the
display will be switched off.
8.1.3.11 Alarms
UtL” alarm (fault of the fan), in
-by.
is necessary to
alarm;
Main consequences:
The equipment will continue to work as
normal
alarm;
The equipment will continue to work as
normal.
activation (possible short circuit in signal
cables)
See parameters: i0; i1 and i2;
Compressor will be switched off;
Defrosting will not be activated.
equipment alarm
input activation
See parameters: i0; i1; 18 and i9
mains power supply.
Compressor will be switched off;
Defrosting will be never activated.
Check how
alarm message, press any key on the
display)
See parameters SP10 and C14
Check the fan conditions
Compressor and fan are switched off;
Water heating
resistance.
Page
Installation and user manual
When the cause of the alarm has been
removed, the normal operation of the
equipment is restored.
Pr1
Error in probe in upper part of the boiler
Solutions:
-
-
-
- Check the temperature of the upper part of
Main consequences:
-
Pr2
Error in probe in lower
Solutions:
relating to the probe in the lower part of the
Main consequences:
-
Pr3
Error in evaporator probe
Solutions:
-
-
When the cause of the alarm has been
removed, the normal operation of the
equipment is restored.
If the “Anti
functions are in progress, the defrosting
procedure will not be enabled.
8.1.3.12 Error messages
Check that the type of probe is in
conformity with parameter P0 settings;
Check the probe is intact;
Check the equipment-probe connection;
the boiler.
The equipment stops working.
part of the boiler
The same as the previous situation but
boiler.
The equipment stops working.
The same as the previous situation but
relating to the evaporator probe.
The equipment stops working.
8.1.3.13 Defrosting
Defrosting can be enabled in the following way:
x Automatically, when the temperature of the
evaporator is below that established in parameter
d17 (only if P4 has a value other than 0);
In any case, between one defrosting procedure and
another, the compressor must have been left switched
on for a period either longer than or equal to d18
minutes. Otherwise the request to enable the defrosting
procedure will not be accepted.
If P4 = 1, d2 represents the temperature of the
evaporator, above which the defrosting procedure is
terminated. Vice versa, if P4 = 0 or P4 = 2, parameter
d2 is not taken into consideration.
If during the defrosting procedure the evaporate or
probe is above the threshold set by means of
parameters d2 and P4 = 1, the request to enable the
defrosting procedure is not accepted.
The defrosting procedure consists of three stages:
x Defrosting stage: Parameter d3 establishes the
maximum duration of the stage.
Output status:
x The compressor is active if d1 = 1,otherwise it is
switched off;
x The defrosting relay is active if d1 = 0 or d1 =
1,otherwise it is switched off;
x The fans are switched on if d1 = 2, otherwise they
are switched off.
x Dripping stage: Parameter d7 establishes the
duration of the stage.
Output status:
- The compressor is switched off;
- The defrosting relay is active if d1 = 0 or d1 =
1,otherwise it is switched off;
- The fans are switched off.
x Drying stage.
Parameter d16 establishes the duration of the
stage. Output status:
x The compressor acts according to parameter d8;
- The defrosting relay is active if d1 = 0 or d1 =
1,otherwise it is switched off;
- The fans are switched off.
-Legionella” or the “Overboost”
8.1.3.14 Day and real time settings
x Make sure that the keyboard is not locked
(paragraph 8.1.3.3) and that no other advanced
procedure is in progress;
x Press and release the key: the display will
show the first code available;
x Press and release either the or the key
until “rtc” is shown;
The day is displayed as 1...7 (number 1 corresponding
to Monday).
To change the day of the week:
x Press and release the key: the display will
show “dd” followed by the two numbers
representing the day;
x Press and release either the or the key
within 15 seconds.
To change the time:
x Press and release the key while changing the
day of the month: the display will show “hh”
followed by the two numbers representing the time
(Time is shown in the 24 hr. format);
x Press and release either the or the key
within 15 seconds.
28
Installation and user manual
Page 29
To set operations within timeslots, it is
necessary to have carried out the settings
relating to the day and the real time
beforehand.
Switch the equipment off and then back on
again
parameters effective.
To change the minutes:
x Press and release the key while changing the
time: the display will show “nn” followed by the two
numbers representing the minutes;
x Press and release either the or the key
within 15 seconds;
x Press and release the key or do not carry out
any operations for 15 seconds;
To exit the procedure:
x Press and release the key until the display
shows the temperature established by parameter
P5 or do not carry out any operations for 60
seconds.
Alternatively:
x Press and release the key.
8.1.3.15 Configuration parameter settings
To carry out the procedure:
x Make sure that the keyboard is not locked
(paragraph 8.1.3.3) and that no other advanced
procedure is in progress;
x Keep the and the keys pressed for
4 seconds: the display will show “PA” (password);
x Press and release the key;
x Press and release either the or the key
within 15 seconds to set “-19” on the display;
x Press and release the key or do not carry out
any other operations for 15 seconds;
x Keep the and the keys pressed for
4 seconds: the display will show the first
parameter “SP1”.
To select a parameter:
x Press and release either the or the key.
To change a parameter:
x Press and release the key;
x Press either the or the key to either
increase or reduce the parameter value (within 15
seconds);
x Press and release the key or do not carry out
any operations for 15 seconds.
To exit the procedure:
x Keep the and the keys pressed for 4
seconds or do not carry out any operations for 60
seconds (any changes will be saved).
to make the changes made to the
8.1.3.16 Restoring default factory settings
To carry out the procedure:
x Ensure that the keyboard is not locked (paragraph
8.1.3.3) and that no other advanced procedure is
in progress;
x Keep the and the keys pressed for
4 seconds: the display will show “PA” (password);
x Press and release the key;
x Press and release either the or the key
within 15 seconds to set “149”;
x Press and release the key or do not carry out
any operations for 15 seconds;
x Keep the and the pressed for 4 seconds:
the display will show “dEF”;
x Press and release the key;
x Press and release either the or the within
15 seconds to set “1”;
x Press and release the key or do not carry out
any other operations for 15 seconds: the display
will show “dEF” flashing for 4 seconds, after which
the equipment will exit the procedure;
x Disconnect the equipment from the mains power
supply.
To exit the procedure before its completion:
x Keep the and the key pressed for
4 seconds during the procedure (or rather before
setting “1”: the restoring of default factory settings
will not be carried out).
8.1.3.17 TOTAL OF THE COMPRESSOR
OPERATING HOURS
8.1.3.17.1 General information
The equipment is capable of memorising up to 9,999
compressor operating hours, if the number of hours
exceeds “9,999” it flashes.
8.1.3.17.2 Display of compressor operating hours
x Make sure that the keyboard is not locked
(paragraph 8.1.3.3) and that no other advanced
procedure is in progress;
x Press and release the key: the display will
show “Pb1”;x Press and release either the or the key to
select “CH”;
x Press and release the key.
To exit the procedure:
x Press and release the key or do not carry out
any other operation for 60 seconds.
Alternatively:
x Press and release the key.
Page
Installation and user manual
8.2 Particular operations
The product has a fan speed control system that
increases the speed of the same, when the ambient
temperature drops to below -1°C, at higher
temperatures, the fan maintains a lower speed in order
to reducing the noise of the equipment.
The equipment is also provided with a verification
system of the environmental conditions concerning the
temperatures of the external incoming air. The below
described function is necessary to avoid the equipment
working with the heat pump mode out of specification,
which may cause faults to the compressor and the
consequent interruption of the functionality.
By every start, the fan is activated for a time set up by
parameter C12 corresponding to 1 minute. After this
time, the system measures the incoming air
temperature. If the temperature is equal to or lower than
parameter SP9 (-7°C), then the conditions for the
activation of the heat pump unit are not met, therefore
the electric resistance is activated. The heating-up
process continues with the help of the electrical
resistance until the set point established with the
ongoing active cycle is reached.
The system verifies cyclically (every 120 minutes) the
environmental conditions and activates the heat pump
mode only when these conditions are adequate for its
operation.
30
Loading...
+ 330 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.