This manual describes how to start up and switch off the unit, set
parameters and configure the schedule timer by means of the
controller, maintain the unit and solve operational problems.
For "Checks before initial start-up" and "Initial start-up"
procedures refer to the installation manual of this unit.
This unit
The AD indoor unit is the indoor part of the
reversible air to water Daikin ERHQ heat pumps. These units are
designed for wall mounted indoor installation and used for both
heating and cooling applications. The units can be combined with
Daikin fan coil units, floor heating, low temperature radiators, the
Daikin domestic hot water tanks and the solar option kit.
The AD indoor unit range consists of two main
versions: a heating/cooling (EKHBX) version and a heating only
(EKHBH) version.
Both versions are delivered with an integrated backup heater for
additional heating capacity during cold outdoor temperatures. The
backup heater also serves as a backup in case of malfunctioning of
the outdoor unit. The backup heaters are available in different
capacities.
NOTE
An EKHBH/X008AA indoor unit can only be connected
to an ERHQ00*AD series outdoor unit.
Options
READ THIS MANUAL ATTENTIVELY BEFORE STARTING
UP THE UNIT. DO NOT THROW IT AWAY. KEEP IT IN
YOUR FILES FOR FUTURE REFERENCE.
Before operating the unit, make sure the installation has
been carried out correctly by a professional Daikin dealer.
If you feel unsure about operation, contact your Daikin
dealer for advice and information.
Operation manual
1
Domestic hot water tank option
An optional EKHWS(U) domestic hot water tank with integrated 3 kW
electrical booster heater can be connected to the indoor unit. The
domestic hot water tank is available in different sizes. For more
information about the domestic hot water tank, refer to the installation
manual of the domestic hot water tank.
Solar kit for domestic hot water tank option
For information concerning the EKSOLHW solar kit, refer to the
installation manual of that kit.
Remote alarm kit option
For information concerning the EKRP1HB remote alarm, refer to the
installation manual of that kit.
Indoor unit for air to water heat pump system and options
EKHBH/X008AA
4PW39351-1C
■
■
■
■
■
O
PERATING
I
NTRODUCTION
The AD heat pump system is designed to provide
you a comfortable indoor climate for many years at low energy
consumption.
To get the most comfort with the lowest energy consumption out of
your system, it is very important to observe the items listed below.
Defining possible schedule timer actions for each day and filling out
the form at the very end of this manual can help you minimize the
energy consumption. Ask your installer for support if required.
Make sure the AD heat pump system works at
the lowest possible hot water temperature required to heat your
house.
To optimize this, make sure the weather dependent set point is
used and configured to match the installation environment.
Refer to "Field settings" on page 10.
Make sure the equilibrium temperature field setting is configured
correctly.
Refer to "Field settings" on page 10.
This function applies to operation of the backup heater. Setting
the equilibrium temperature correctly will avoid the backup
heater to operate when the heat pump has sufficient capacity to
heat up your house.
It is advised to install a room thermostat connected to the indoor
unit. This will prevent excessive space heating and will stop the
outdoor unit and the indoor circulation pump when the room
temperature is above the thermostat set point.
Next recommendations only apply to installations with an
optional domestic hot water tank.
■
Make sure the domestic water is only heated up to the
domestic hot water temperature you require.
Start with a low domestic hot water temperature set point
(e.g. 45°C), and only increase if you feel that the domestic
hot water supply temperature is not sufficient.
■
Make sure both the domestic water heating and booster
heating only start 1 to 2 hours before you expect domestic
hot water usage.
In case you only need a lot of domestic hot water in the
evening or in the morning, only allow domestic water heating
during early morning and early evening. Also keep hours with
low electricity cost tariffs in mind.
To do this, program both the domestic water heating and
booster heating schedule timer. Refer to Programming in
chapter "Programming and consulting the schedule timer" on
page 7.
THE
UNIT
■
■
■
■
■
■
■
O
PERATING
Operating the EKHB* unit comes down to operating the digital
controller.
THE
DIGITAL
Never let the digital controller get wet. This may cause an
electric shock or fire.
Never press the buttons of the digital controller with a hard,
pointed object. This may damage the digital controller.
Never inspect or service the digital controller yourself, ask
a qualified service person to do this.
CONTROLLER
Features and functions
The digital controller is a state of the art controller that offers full
control over your installation. It can control a cooling/heating and a
heating only installation.
Both installations are available in multiple versions which vary in
capacity, electrical supply and installed equipment (with an optional
domestic hot water tank with a booster heater).
NOTE
Descriptions in this manual that apply to a specific
installation or that depend on the installed
equipment, are marked with an asterisk (*).
Some functions described in this manual may not
be available or should not be available. Ask your
installer or your local dealer for more information
on permission levels.
Basic controller functions
The basic controller functions are:
Tu r ning the unit ON/OFF.
Operation mode change-over:
- space heating (refer to page 4),
- space cooling (refer to page 5) (*),
- domestic water heating (refer to page 5) (*).
Selection of features:
- quiet mode (refer to page 5),
-weather dependent control (refer to page 6).
Temperature set point adjustment (refer to page 5).
NOTE
The digital controller supports a power cut off of maximum 2 hours.
When autorestart is enabled (see "Field settings" on page 10) this
allows a power supply shut down of 2 hours without user intervention
(e.g. benefit kWh rate power supply).
(*) The functions 'space cooling' and 'domestic water
heating' can only be selected when the corresponding
equipment is installed.
Clock function
The clock functions are:
24 hour real time clock.
Day of the week indicator.
EKHBH/X008AA
Indoor unit for air to water heat pump system and options
4PW39351-1C
Schedule timer function
The schedule timer function allows the user to schedule the
operation of the installation according to a daily or a weekly program.
Operation manual
2
1.
y
e
2.
0
3.
h
c
w
s
c
w
w
4.
e
5.
6.
8
7.
p
8.
q
9.
x
k
l
ç
(
§
§
u
a
b
Name and function of buttons and icons
1173
56 248
7
9
12
10
23
22
34
29
27
30
28
COOLING/HEATING ON/OFF BUTTON
The ON/OFF button starts or stops the heating or cooling
function of the unit.
When the unit is connected with an external room thermostat,
this button is not operable and the icon
Pressing the ON/OFF button consecutively too many times may
cause malfunction of the system (maximum 20 times per hour).
NOTE
Remark that pushing the y button has no influence
on the domestic water heating. Domestic water
heating is only switched on or off by means of the v
button.
OPERATION LED
The operation LED is lit during space cooling or space heating
operation. The LED blinks if a malfunction occurs. When the
LED is OFF, space cooling or space heating are inactive while
the other operation modes can still be active.
OPERATION MODE ICONS
hcws
These icons indicate the current operation mode(s): space
heating (
quiet mode (
), space cooling (
), domestic water heating (
). Within limits, different modes can be combined,
e.g. space heating and domestic water heating. The
corresponding mode icons will be displayed simultaneously.
In a heating only installation, the
If the domestic hot water tank is not installed, the
never be displayed.
If the solar option is installed and active, the
blinking.
EXTERNAL CONTROL ICON
This icon indicates that an external room thermostat with higher
priority is controlling your installation. This external room
thermostat can start and stop the space heating/cooling
operation and change the operation mode (cooling/heating).
When an external room thermostat with a higher priority is
connected, the schedule timer for space cooling and space
heating will not function.
DAY OF THE WEEK INDICATOR
This indicator shows the current weekday.
When reading or programming the schedule timer, the indicator
shows the set day.
CLOCK DISPLAY
The clock display shows the current time.
When reading or programming the schedule timer, the clock
display shows the action time.
2161815
is shown.
icon will never be displayed.
icon will be
1234567
4
14
21
19
11
20
13
25
26
33
32
31
) or
icon will
SCHEDULE TIMER ICON
This icon indicates that the schedule timer is enabled.
ACTION ICONS
These icons indicate the programming actions for each day of
the schedule timer.
OFF ICON
This icon indicates that the OFF action is selected when
programming the schedule timer.
10.INSPECTION REQUIRED
and
These icons indicate that inspection is required on the
installation. Consult your dealer.
11.SET TEMPERATURE DISPLAY
9
The display shows the current set temperature of the
installation.
12.SETTING
$
Not used. For installation purposes only.
13.NOT AVAILABLE
n
This icon is displayed whenever a non-installed option is
addressed or a function is not available.
14.DEFROST/STARTUP MODE ICON
d
This icon indicates that the defrost/startup mode is active.
15.COMPRESSOR ICON
This icon indicates that the compressor in the outdoor unit of the
installation is active.
16.BACKUP HEATER STEP ONE
OR STEP TWO
These icons indicate that the backup heater is operating on low
capacity (
) or on high capacity (
(
). The backup heater
provides extra heating capacity in case of low ambient outdoor
temperature (high heating load).
17.
BOOSTER HEATER ICON
m
This icon indicates that the booster heater is active. The booster
heater provides auxiliary heating for the domestic hot water
tank.
The booster heater is located in the domestic hot water tank.
The icon is not used when the domestic hot water tank is not
installed.
18.PUMP ICON
é
This icon indicates that the circulation pump is active.
19.OUTDOOR TEMPERATURE DISPLAY
When this icon is flashing, the outdoor ambient temperature is
displayed.
20.WEATHER DEPENDENT SET POINT ICON
This icon indicates that the controller will adapt the temperature
set point automatically, based on the outdoor ambient
temperature.
21.TEMPERATURE ICON
This icon is displayed when the water outlet temperature of the
indoor unit, the outdoor ambient temperature and the domestic
hot water tank temperature are shown.
The icon is also displayed when the temperature set point is set
in schedule timer programming mode.
22.TEST OPERATION ICON
t
This icon indicates that the unit runs in test mode. Refer to the
installation manual.
23. FIELD SET CODE
;
This code represents the code from the field set list. Refer to the
installation manual.
24. ERROR CODE :
This code refers to the error code list and is for service purposes
only. Refer to the installation manual.
Operation manual
3
Indoor unit for air to water heat pump system and options
EKHBH/X008AA
4PW39351-1C
25. SPACE HEATING/COOLING BUTTON =
This button allows manual switching between cooling or heating
mode (provided the unit is not a heating only unit).
When the unit is connected with an external room thermostat,
this button is not operable and the icon e is shown.
26. DOMESTIC WATER HEATING BUTTON v
This button enables or disables heating of the domestic water.
This button is not used when the domestic hot water tank is not
installed.
NOTE
Remark that pushing the y button has no influence
on the domestic water heating. Domestic water
heating is only switched on or off by means of the v
button.
27. WEATHER DEPENDENT SET POINT BUTTON ba
This button enables or disables the weather dependent set point
function which is available in space heating operation only.
If the controller is set in permission level 2 or 3 (refer to "Field
settings" on page 10), the weather dependent set point button
will not be operable.
28. INSPECTION/TEST OPERATION BUTTON
z
This button is used for installation purposes and changing field
settings. Refer to "Field settings" on page 10.
29. PROGRAMMING BUTTON <
This multi-purpose button is used to program the controller. The
function of the button depends on the actual status of the
controller or on previous actions carried out by the operator.
30. SCHEDULE TIMER BUTTON r/p
The main function of this multi-purpose button is to
enable/disable the schedule timer.
The button is also used to program the controller. The function of
the button depends on the actual status of the controller or on
previous actions carried out by the operator.
If the controller is set in permission level 3 (refer to "Field
settings" on page 10), the schedule timer button will not be
operable.
31. TIME ADJUST BUTTON pi and pj
These multi-purpose buttons are used to adjust the clock, to
toggle between temperatures (water outlet temperature of the
indoor unit, outdoor ambient temperature and domestic hot
water temperature) and in schedule timer programming mode.
32. TEMPERATURE ADJUST BUTTONS bi and bj
These multi-purpose buttons are used to adjust the current set
point in normal operation mode or in schedule timer
programming mode. In weather dependent set point mode the
buttons are used to adjust the shift value. Finally, the buttons are
also used to select the weekday while setting the clock.
33. DOMESTIC HOT WATER TEMPERATURE ADJUST BUTTONS
wbi and wbj
These buttons are used to adjust the current set point of the
domestic hot water temperature.
The buttons are not used when the domestic hot water tank is
not installed.
34. QUIET MODE BUTTON
s
This button enables or disables quiet mode.
If the controller is set in permission level 2 or 3 (refer to "Field
settings" on page 10), the quiet mode button will not be
operable.
Setting up the controller
After initial installation, the user can set the clock and day of the
week.
The controller is equipped with a schedule timer that enables the
user to schedule operations. Setting the clock and day of the week is
required to be able to use the schedule timer.
Setting the clock
1Hold down the pr button for 5 seconds.
The clock read-out and the day of week indicator start flashing.
2Use the pi and pj buttons to adjust the clock.
Each time the pi or pj button is pressed, the time will
increase/decrease by 1 minute. Keeping the pi or pj
button pressed will increase/decrease the time by 10 minutes.
3Use the bi or bj button to adjust the day of the week.
Each time the bi or bj button is pressed the next or
previous day is displayed.
4Press the < button to confirm the current set time and day of the
week.
To leave this procedure without saving, press the pr button.
If no button is pressed for 5 minutes the clock and day of the
week will return to their previous setting.
NOTE
The clock needs to be set manually. Adjust the setting
when switching from summertime to wintertime and
vice versa.
Setting the schedule timer
To set the schedule timer, refer to chapter "Programming and
consulting the schedule timer" on page 7.
Description of the operation modes
Space heating operation (
In this mode, heating will be activated as required by the water
temperature set point. The set point can be set manually (refer to
"Manual operation" on page 5) or weather dependent (refer to
"Selecting weather dependent set point operation (only in heating
mode)" on page 6).
Startup (d)
At the start of a heating operation, the pump is not started until a
certain refrigerant heat exchanger temperature is reached. This
guarantees correct startup of the heat pump. During startup, icon
d is displayed.
Defrost (d)
In space heating operation or domestic water heating operation,
freezing of the outdoor heat exchanger may occur due to low outdoor
temperature. If this risk occurs, the system goes into defrost
operation. It reverses the cycle and takes heat from the indoor
system to prevent freezing of the outdoor system. After a maximum
of 8 minutes of defrost operation, the system returns to space
heating operation.
h)
EKHBH/X008AA
Indoor unit for air to water heat pump system and options
4PW39351-1C
Operation manual
4
Space cooling operation (c)
In this mode, cooling will be activated as required by the water
temperature set point.
NOTE
■The space cooling temperature set point can only
be set manually (refer to "Manual operation" on
page 5).
■Switching between space heating and space
cooling operation can only be done by pressing
the = button or by an external room thermostat.
■Space cooling operation is not possible if the
installation is a heating only installation.
Domestic water heating operation (w)
In this mode, the indoor unit will deliver hot water to the domestic hot
water tank when the space heating or space cooling operation has
reached its temperature set point. When necessary and when
allowed by the booster heater schedule timer (refer to "Programming
quiet mode, booster heating or domestic water heating" on page 9),
the booster heater provides auxiliary heating for the domestic hot
water tank.
NOTE
■In order to provide domestic hot water throughout
the day, it is advised to keep the domestic water
heating operation on continuously.
■The domestic hot water temperature set point can
only be set manually (refer to "Manual operation"
on page 5).
■Any domestic water heating operation is
impossible when the domestic hot water tank is
not installed.
■When the w icon is blinking, hot water is
delivered to the domestic hot water tank by the
solar kit option and not by the
AD indoor unit. Refer to
installation manual of the EKSOLHW solar kit.
Powerful domestic water heating operation
In the case of urgent need of domestic hot water, the domestic hot
water temperature set point can be reached quickly by using the
booster heater. Powerful domestic water heating operation is forcing
the booster heater to operate until the domestic hot water
temperature set point is reached.
This function remains available in solar operation.
Quiet mode operation (s)
Quiet mode operation means that the outdoor unit works at reduced
capacity so that the noise produced by the outdoor unit drops. This
implies that the indoor heating and cooling capacity will also drop.
Beware of this when a certain level of heating is required indoors.
Controller operations
Manual operation
In manual operation, the user manually controls the settings of the
installation. The last setting remains active until the user changes it or
until the schedule timer forces another setting (refer to "Schedule
timer operation" on page 6).
As the controller can be used for a wide variety of installations, it is
possible to select a function which is not available on your
installation. In that case the message n will appear.
Switching on and setting space cooling (c) and heating (h)
1Use the = button to select space cooling (c) or space heating
(h).
Icon c or h appears on the display as well as the corresponding
water temperature set point.
2Use the bi and bj buttons to set the desired water
temperature.
•Temperature range for heating: 25°C to 55°C
The temperature for heating can be set as low as 15°C (see
"Field settings" on page 10). However, the temperature for
heating should only be set lower than 25°C during
commissioning of the installation. When set lower than 25°C,
only the backup heater will operate.
In order to avoid overheating, space heating is not operable
when the outdoor ambient temperature rises above a certain
temperature (as set through field setting [4-02], refer to "Field
settings" on page 10).
•Temperature range for cooling: 5°C to 22°C
NOTE
3Switch on the unit by pushing the
NOTE
In heating mode (h), the water temperature set point
can also be weather dependent (icon a is shown).
This means that the controller calculates the water
temperature set point based on the outdoor
temperature.
In this case, instead of showing the water temperature
set point, the controller shows the "shift value" which
can be set by the user. This shift value is the
temperature difference between the temperature set
point calculated by the controller and the real set point.
E.g. a positive shift value means that the real
temperature set point will be higher than the calculated
set point.
y button.
The operation LED 0 lights up.
When the unit is connected to an external room
thermostat, buttons = and y are not operable and
the icon e is shown. In this case, the external room
thermostat switches the unit on or off and determines
the operation mode (space cooling or space heating).
Operation manual
5
Indoor unit for air to water heat pump system and options
EKHBH/X008AA
4PW39351-1C
Selection and setting of domestic water heating (w)
1Use the v button to activate domestic water heating (w).
Icon w appears on the display.
2Use the wi or wj button to display the actual
temperature set point and subsequently, to set the correct
temperature.
The actual temperature set point only appears on the display
after pressing one of the buttons wi or wj. If no button is
pressed for 5 seconds, the temperature set point will
automatically disappear from the display again.
Temperature range for domestic water heating: 30°C to 78°C
3Press the v button to deactivate domestic water heating (w).
Icon w disappears from the display.
NOTE
Remark that pushing the y button has no influence
on the domestic water heating. Domestic water
heating is only switched on or off by means of the v
button.
Selecting powerful domestic water heating operation
1Press
v for 5 seconds to activate powerful domestic water
heating operation.
Icons w and m start flashing.
Powerful domestic water heating is deactivated automatically
when the set point for the domestic hot water is reached.
Selecting quiet mode operation (s)
1Use the s button to activate quiet mode operation (s).
Icon s appears on the display.
If the controller is set in permission level 2 or 3 (refer to "Field
settings" on page 10), the s button will not be operable.
Selecting weather dependent set point operation (only in
heating mode)
1Press the ba button to select weather dependent set point
operation.
Icon a appears on the display as well as the shift value. The
shift value is not shown in case it is 0.
2Use the bi and bj buttons to set the shift value.
Range for the shift value: –5°C to +5°C
Displaying actual temperatures
1Push the ba button for 5 seconds.
The b icon and the outgoing water temperature are displayed.
The icons l and = are flashing.
2Use the pi and pj buttons to display:
• The outdoor temperature (u icon is flashing).
• The domestic hot water tank temperature (w icon is
flashing).
• The outgoing water temperature (= are flashing).
If no button is pressed for 5 seconds, the controller leaves the
display mode.
Schedule timer operation
In schedule timer operation, the installation is controlled by the
schedule timer. The actions programmed in the schedule timer will be
executed automatically.
The schedule timer always follows the last command until a new
command is given. This means that the user can temporarily overrule
the last executed programmed command by manual operation (Refer
to "Manual operation" on page 5). The schedule timer will regain
control over the installation as soon as the next programmed
command of the schedule timer occurs.
The schedule timer is enabled (p icon displayed) or disabled (p icon
not displayed), by pressing the pr button.
NOTE
To set up the SCHEDULE TIMER refer to chapter "Programming and
consulting the schedule timer" on page 7.
What can the schedule timer do?
The schedule timer allows the programming of:
1.Space heating and space cooling (refer to "Programming space
NOTE
■Only use the pr button to enable or disable the
schedule timer. The schedule timer overrules the
y button. The y button only overrules the
schedule timer until the next programmed action.
■If the auto restart function is disabled, the
schedule timer will not be activated when power
returns to the unit after a power supply failure.
Press the
pr button to enable the schedule timer
again.
■When power returns after a power supply failure,
the auto restart function reapplies the user
interface settings at the time of the power supply
failure.
It is therefore recommended to leave the auto
restart function enabled.
■The programmed schedule is time driven. Therefore, it
is essential to set the clock and the day of the week
correctly. Refer to "Setting the clock" on page 4.
■Manually adjust the clock for summertime and
wintertime. Refer to "Setting the clock" on page 4.
■A power failure exceeding 1 hour will reset the clock
and the day of the week. The schedule timer will
continue operation, but with a disordered clock. Refer
to "Setting the clock" on page 4 to adjust the clock
and the day of the week.
■The actions programmed in the schedule timer will not
be lost after a power failure so that reprogramming the
schedule timer is not required.
cooling or space heating" on page 8)
Switch on the desired mode at a scheduled time, in combination
with a set point (weather dependent or manually set). Five
actions per weekday can be programmed, totalling 35 actions.
When the unit is connected to an external room
thermostat, the schedule timer for space cooling and
space heating is overruled by the external room
thermostat.
EKHBH/X008AA
Indoor unit for air to water heat pump system and options
4PW39351-1C
2.Quiet mode (refer to "Programming quiet mode, booster heating
or domestic water heating" on page 9)
Switch the mode on or off at a scheduled time. Five actions can
be programmed per mode. These actions are repeated daily.
3.Booster heating (refer to "Programming quiet mode, booster
heating or domestic water heating" on page 9)
Allow or disallow booster heating at a scheduled time. Five
actions can be programmed per mode. These actions are
repeated daily.
Operation manual
6
Loading...
+ 15 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.