2.1 General ............................................................................................................................................................................................ 6
2.4 PC Interface .................................................................................................................................................................................... 8
2.5 Test programs ................................................................................................................................................................................. 8
4.2 Installation space ........................................................................................................................................................................... 13
5.4 Connecting gas ............................................................................................................................................................................. 20
5.5 Flue and air supply duct ................................................................................................................................................................ 21
5.6 Outlet systems ............................................................................................................................................................................... 22
5.7 Flue material .................................................................................................................................................................................. 23
5.8 Connection to a flue system without air inlet (B23, B33) .............................................................................................................. 25
5.9 Connection to a sealed flue system. ............................................................................................................................................. 26
Commissioning the unit and the Installation 34
6.1 Filling and air purge of unit and installation ................................................................................................................................... 34
6.2 Commissioning the unit ................................................................................................................................................................. 35
6.3 Switching off the unit ..................................................................................................................................................................... 36
Setting and adjustment 37
7.1 Direct via operating panel .............................................................................................................................................................. 37
7.2 Parameter settings via the service code ....................................................................................................................................... 38
7.4 Setting maximum CH power .......................................................................................................................................................... 40
7.7 Conversion to different type of gas................................................................................................................................................ 42
8.1 Show last malfunction ................................................................................................................................................................... 45
8.3 Other faults .................................................................................................................................................................................... 46
Maintenance 49
Technical specifications 51
10.1 Technical Product Fiche in accordance to CELEX-32013R0811 .................................................................................................. 52
All rights reserved.
The information provided applies to the product in its standard version. Daikin Europe NV can therefore not be held liable for any damages arising from any
specifications of the product which deviate from the standard version. The available information has been compiled with the greatest possible care, but Daikin Europe
NV can not be held liable for any mistakes in the information, or for any consequences thereof. Daikin Europe NV cannot be held liable for any damage arising from
work carried out by third parties.
Subject to change.
Daikin Europe NV
3
These installation instructions
With these installation instructions, you can safely assemble, install and maintain the
unit. Carefully follow the instructions.
In case of any doubt, please contact the manufacturer.
Keep the installation instructions near the unit.
Abbreviations and terms used
Description To be referred to as
Daikin EHOB12AAV1 H, EHOB18AAV1 H,
EHOB42ABV1H
Unit with piping for central heating CH installation
System with pipes for domestic hot water DHW installation
Unit
Symbols
The following symbols are used in this manual:
CAUTION
Procedures which - if they are not carried out with the
necessary care - may cause damage to the product, the
surroundings, the environment or injury.
IMPORTANT
Procedures and/or instructions which, if they are not
followed, will have a negative effect on the functioning of the
unit.
Daikin Europe NV
4
Service and technical support for the installer
For information about specific settings, installation, maintenance and repair work, as an
installer, please contact your local Daikin dealer.
Identification of the product
You will find the unit details on the type plate on the bottom of the unit.
You will find the unit details on the data plate on the bottom of the unit.
The data plate contains, beside the supplier information and the boiler specification (boiler type
and model name) the following information:
******-yymm****** Product code-Serial No.
YY= year of production, mm = month of production
PIN Product Identification Number
Data related to Central Heating
Information regarding electrical power supply
Voltage, mains frequency, elmax, IP-class)
PMS Permissible overpressure in CH circuit in bar
Qn HS Input related to gross caloric value in kilowatts
Qn Hi Input related to net caloric value in kilowatts
Pn Output in kilowatts
BE, FR, IT, PL, DE Countries of Destination (EN 437)
II2H3P, II2Esi3P,
I2E(S), I2E3P;
II2ELL3P
G20-20 mbar
G25-25 mbar
B23, …. C93(x) Approved flue gas category (EN 15502)
Tmax Max. flow temperature in °C
IPX4D Electrical protection class
Approved unit categories (EN 437)
Gas group and gas connection pressure as set at the factory
(EN 437)
1 SAFETY INSTRUCTIONS
The manufacturer Daikin Europe NV accepts no liability for damage or injury caused
by the failure to (strictly) observe the safety instructions, or negligence during the
installation of the Daikin EHOB*A*V1H wall-mounted gas boiler and any associated
accessories.
This device is not intended for use by people (including children) with reduced
physical, sensory or mental abilities, or lack of experience and knowledge, unless they
are given supervision or instructions on the use of the device by a person who is
responsible for their safety.
The entire installation must meet the applicable local technical and (safety)
instructions, for the gas installation, the electrical installation, smoke extraction
installation, drinking water installation, and central heating installation.
IMPORTANT
This product is intended for domestic use only.
Daikin Europe NV
5
2 UNIT DESCRIPTION
2.1 General
The Daikin EHOB*A*V1H wall-mounted gas boiler is a closed unit. The unit is intended
to provide heat to the water of a CH-installation and the domestic hot water installation.
The air supply and combustible gas outlet can be connected to the unit by means of
two separate pipes. A concentric connection can be supplied upon demand. The unit
was tested in combination with the combi feedthrough, but the unit may also be
connected to combi feedthroughs which meet the universal test standards for combi
feedthroughs.
The unit can be connected to an assembly bracket if required, a frame with top
connection, and various installation sets. These are provided separately.
The Daikin EHOB*A*V1H wall-mounted gas boilers have the CE marking, electrical
protection class IPX4D
The unit is delivered for natural gas (G20) as a standard. On request, the unit can also
be provided for propane (G31).
2.2 Functioning
The Daikin EHOB*A*V1H wall-mounted gas boiler is a modulating high-efficiency boiler.
This means that the power is modulated to suit the required heat demand.
A copper CH circuit is integrated in the aluminum heat exchanger.
The water of the DHW installation can be heated by connecting the unit to an indirectly
heated tank using a three-way valve and tank sensor (see par.5.1 and 5.2). The built in
tank regulation of the unit ensures the domestic hot water provision takes precedence
over the heating. Both cannot work at the same time.
The unit is fitted with an electronic boiler controller, which operates the fan at every
heat requirement of the heating or the warm water supply, opens the gas valve, ignites
the boiler controller, and continuously monitors and regulates the flame, depending on
the requested power.
2.3 Operating modes
The operating mode of the unit is indicated by means of a code on the service display
of the operating panel.
-
Off
The unit is not in operation, but is connected to the electricity supply. No response is
given to requests for domestic hot water or CH water. The unit frost protection is active.
This means that the pump will start running and the exchanger will be heated up if the
temperature of the water in the system drops too far.
If the frost protection intervenes, the code
The pressure in the CH installation can also be read from the temperature display in
this operating mode (in bar).
Standby
The LED at the key is lit and possibly one of the LEDs of the tap comfort function.
The unit is ready to respond to a request for CH or tap water.
0
Post-running CH
After the end of the CH-operation, the pump will run for a specified time. The postpumping time is set to the value in par. 7.2 in its factory settings. This setting can be
changed. In addition to this, the pump will run automatically 1 time per 24 hours, for 10
seconds, in order to prevent it from getting stuck. This automatic switching on of the
pump takes place at the time of the last heating request. In order to change this, the
room thermostat needs to be set higher for a moment, at the required time of day.
7
will be displayed (heating up exchanger).
1
Requested temperature reached
The boiler controller may temporarily block the heat request. The boiler controller will
then be stopped. The block occurs because the required temperature has been
reached. When the temperature has sufficiently decreased, the block will be lifted.
2
Selftest
Once every 24 hours, the boiler controller tests the connected sensors. During the test,
the relay will not carry out any other tasks.
Daikin Europe NV
6
3
Ventilating
When the unit is started, the fan is first brought up to its correct start rpm. When the
start rpm is reached, the boiler controller will be ignited. Code 3 is also visible when
there is post-fanning after the boiler controller is stopped.
4
Igniting
When the fan has reached the start rpm, the burner relay will be ignited by means of
electrical sparks. During the ignition, code
not ignite, a new attempt will be made after approximately 15 seconds. If after 4 ignition
attempts, the boiler controller has still not been ignited, the controller will go into downtime.
5
CH operation
An on/off thermostat, an OpenTherm thermostat, an outdoor sensor or a combination
thereof can be connected to the controller (see par. 5.3 )
When there is a heat request from a thermostat, after the fan has started running (code
3
), the ignition will take place (code
During CH operation, the rpm of the fan and therefore the power of the unit can be
adjusted so the temperature of the CH water to the required CH supply temperature can
be controlled. If an on/off thermostat has been connected, this will be the CH supply
temperature set on the display. In case of an OpenTherm thermostat, the required CH
supply temperature is determined by the thermostat. In case of an outdoor sensor, the
required CH supply temperature is determined by the fuel line programmed in the boiler
controller. For the last two situations, the temperature set on the display is the
maximum.
During CH operation, the requested CH supply temperature will be displayed on the
operating panel.
The CH supply temperature can be set between 30 and 90°C (see par. 7.1). Caution:
for a low temperature system, a lower maximum setting may be required than the
standard setting of 80°C.
You can press the service button during CH operation to read the actual CH supply
temperature.
4
is displayed. If the boiler controller does
4
) followed by the CH operating mode (code 5 ).
If the tap comfort function is switched on (see code
of less than 40 degrees will be generated.
7
), an OpenTherm heatingrequest
Daikin Europe NV
7
6
•
freezing. If the temperature of the heat exchanger drops too low, the
Tap water operation
EHOB*A*V1H in combination with indirectly fired tank
The hot water supply takes precedence over the heating. When a tank sensor is used,
any CH request will be interrupted when the tank sensor detects a temperature of
5 degrees lower than the set value. After the fan has switched on (code
has been an ignition (code 4 ), the boiler controller will switch to domestic water
operation (code
the thermostat is opened, and it will end when the thermostat closes again. The
fanspeed, and therefore the power of the unit, is in that case controlled by the boiler
controller on the basis of a fixed leaving water temperature. The domestic hot water
temperature can be set between 40°C and 65°C. The set tank temperature is displayed
on the operating panel during domestic hot water operation. You can press the service
button during tap water operation to read the actual tank temperature.
6
). When a tank thermostat is used, the heat request will start when
3
) and there
2.4 PC Interface
The boiler controller is provided with an interface for a PC. A PC can be connected by
means of a dongle, and the associated software. This facility enables you to follow the
behavior of the boiler controller, the unit and the heat installation over a long period.
2.5 Test programs
There is an option in the burner relay, to bring the unit into a test status.
Activating a test program, will switch on the unit with a set fan rotations per minute,
without the control functions intervening.
The safety functions do remain active.
The test program is ended by pressing and simultaneously.
Test programs
Description of program Button combination Display reading
Burner on with minimum DHW
capacity (see parameter d par. 7.2)
Burner on with set maximum CH
power (see parameter 3 par. 7.2)
Burner on with maximum DHW power
(see parameter 3 par. 7.2)
Switching off test program and
During test mode the following data can be read :
• By pressing the button continuously in the display the CH water pressure is shown.
• By pressing the button continuously in the display the ionisation current is shown.
and “L”
and (1x)
and (2x)
Current operation
“h”
“H”
situation
2.5.1 Frost protection
The unit is fitted with frost protection in order to prevent it from
pump will start running until the temperature of the heat exchanger
is sufficiently high. If the frost protection intervenes, the code
be displayed (heating up exchanger).
•If the installation (or a part thereof) can freeze, the coldest place
should be fitted with an (external) frost thermostat on the return
pipe. This must be connected in accordance with the electrical
diagram (see par.10.3 ).
Note
When the unit is switched off (
remain active, however a heating request from an (external) frost thermostat will be
ignored.
-
on the service display), the unit frost protection will
7
will
Daikin Europe NV
8
3 MAIN COMPONENTS
Ignition/ionization pin
0207010009
A. CH pump K. Flue gas/air inlet concentric adapter
B. Gas valve L. Air supply (only when using twin pipe flue system)
C. Burner controller (incl. operating panel) M. Connection block / terminal strip X4
D. Sensor S1 (flow) N. Condensate collector
E. Sensor S2 (return) O. Siphon
F. Fan P. Heat exchanger
G. Pressure sensor central heating Q. Operating panel and display
H. Connection wire 230 V ~ R.
I. Manual air bleed S. Position of data plate
J. Inspection glass
Daikin Europe NV
9
3.1 Accessories
Description Article numbers
B-pack small EKFJS*AA
B-pack middle EKFJM*AA
B-pack large EKFJL*AA
Valve kit EKVK4AA
Cover plate EKCP1AA
Outdoor sensor EKOSK1AA
3-way valve set EK3WV1AA
Flue gas adapter Concentric Ø80x125 EKHY090717
Flue gas adapter Parallel 80 mm
EKHY090707
Propane conversion set EHOB12AAV1 H EKPS075917
Propane conversion set EHOB18AAV1 H EKPS075867
Propane conversion set EHOB42ABV1H EKHY075787
Daikin Europe NV
10
4 INSTALLATION
A = Supply CH
G ¾” (ext)
B = Return CH
G ¾” (ext)
C = Gas G ½” (int)
D = Condense outlet
Ø dn25 (flexible)
h =
517mm
EHOB
12
AAV1 H
&
637mm
EHOB42ABV1
H
H =
590mm
EHOB
12
AAV1 H
&
710mm
EHOB42ABV1
H
Z = Flue gas outlet/air inlet
Ø60/100 (concentric)
020601005
161
161
450
240
77
135
h
D
130130
77
4.1 Installation measurements
Unit with pipes connected downwards:
Unit + mounting bracket
EHOB18AAV1 H
EHOB18AAV1 H
Daikin Europe NV
11
A = Supply CH
G ¾” (
ext)
B = Return CH
G ¾” (ext)
C = Gas G ½” (int)
D = Condense outlet
Ø dn25 (flexible)
H = 770mm
EHOB
12
AAV1 H
&
890mm
EHOB42ABV1
H
Z = Flue gas outlet/air inlet
Ø60/100 (concentric)
020601006
265
265
77
77
D
50
130130
Unit connected to B-pack:
Unit + B-pack
EHOB18AAV1 H
Daikin Europe NV
12
4.2 Installation space
The unit must be installed against a wall with sufficient load bearing capacity.
In case of light wall constructions, there is a risk of resonance noises.
Within 1 meter of the unit, there must be an earthed wall plug.
In order to prevent the condense outlet from freezing, the unit must be installed in a
frost-free room. Preferably ensure there is a space of at least 2 cm next to the boiler.
No free space is required due to danger of singeing.
4.2.1 Installing in kitchen cabinet
The unit can be placed between two kitchen cabinets, or inside a kitchen cabinet.
Make sure there is sufficient ventilation at the bottom and the top.
If the unit is installed inside a cabinet, ventilation openings of at least 50 cm2 are
required.
4.2.2 Removing cover plate and front panel
For various activities on the unit, the cover plate and front panel have to be removed
from the unit, if they were installed. Do this as follows:
• If you are using the cover plate (A), remove it to the front.
• Unscrew both screws (1) behind the display window.
• Pull the bottom of the front panel (2) forwards.
Danger: risk of burning
In case of high leaving water set ponts for space heating (eighter a high fixed set point
or a high weather-dependent set point at low ambient temperatures), the heat
exchanger of the boiler can be very hot, for example 70°C.
Beware that in case of a tapping demand, the water can initially have a higher water
temperature than requested.
In this case, it is recommended to install a thermostatic valve to prevent scalding.
This can be done according to the schematics below.
a=boiler, b=DHW from boiler, c= cold water inlet,
d=shower, e=thermostatic valve (field supply)
Daikin Europe NV
13
4.3 Assembly
020601020
The boiler can be hung to the wall using :
• the wall suspension strip and a the connection kit EKVK4AA
• a B-pack including an expension vessel and a connection kit.
4.3.1 Assembling suspension strip and assembly bracket
• Make sure the construction of the wall is suitable for hanging the boiler.
• Drill the holes for the suspension strip and the connection kit in the wall
using the template delivered with the boiler.
•Mount the suspension strip and the assembly bracket horizontally on the
wall, using the associated attachment materials.
•The boiler can now be placed on the suspension strip simultaniously sliding
the pipes of the boiler into the valves in the assembly bracket.
4.3.2 Assembling B-pack
•Make sure the construction of the wall is suitable for hanging the boiler and
B-pack.
•Drill the holes for the B-pack kit in the wall using the template delivered
with the boiler.
• Mount the B-pack on the wall using the associated attachment materials.
• Place the assembly bracket in the frame as described in the manual
inclued in the B-pack.
•Connect the flexible hose on the expension vessel and the conenction on
the return valve. Make sure the seal rings are placed !
•The boiler can now be placed on B-pack simultaniously sliding the pipes of
the boiler into the valves in the assembly bracket.
Daikin Europe NV
14
4.3.3 Assembling the unit
1. Unpack the unit.
2. Check the content of the packaging, which consists of:
• Unit (A)
• Suspension strip (B)
• Siphon + flexible hose (C)
• Installation instructions
• Operating instructions
• Warranty card
3. Check the unit for any damage: immediately report damages to the supplier.
4. Install the suspension strip.
5. Check whether the compression rings are positioned straight in the couplings of
the assembly bracket.
6. Position the unit: slide it from top to bottom over the suspension strip (B).
Make sure the pipes slide into the compression fittings simultaneously.
7. Tighten the compression fittings onto the assembly bracket.
The nipples and pipes must not rotate with it!
8. Open the display valve and loosen the two screws on the left and right of the
display, and remove the front panel.
9. Assemble the flexible tube (D) onto the outlet of the siphon.
Fill the siphon with water, and slide it as far as possible on top of the condense
output connector (E) under the unit.
IMPORTANT
The unit EHOB42ABV1H may only be connected using the
extended siphon provided. In case of any replacement, make
sure the correct version is ordered.
10. Seal flexible tube (D) of the siphon, if possible together with the overflow pipe of
the inlet combination and the overflow valve, to the sewage via open connection
(F).
11. Assemble the air supply and the burning gas outlet (see par. 0).
12. Assemble the cover and tighten the two screws to the left and the right of the
display, and close the display cover.
4.3.4 Apply cover plate (optional)
Suspend the converted top edge of the cover plate from the washers underneath the
bottom of the unit, and slide the cover plate as far back as possible.
Please note: When installing the boiler in combination with a cover plate, the siphon
will extend underneath the cover plate.
Daikin Europe NV
15
5 CONNECTING
A
B
020601009
B
A
020601010
5.1 Connecting CH installation
1. Rinse the CH installation carefully.
2. Fit the supply pipe (A) and return pipe (B) to the connection set.
3. All pipes must be assembled with no electrical current, in order to prevent shocks
from the pipes.
4. Existing connections may not be rotated, in order to prevent leakages.
The CH installation must be fitted with:
• A filling/draining tap (A) in the return pipe, immediately underneath the unit.
• A draining tap at the lowest point of the installation.
• An overflow valve (B) of 3 bar in the input pipe at a distance of no more than 500 mm
from the unit.
Between the unit and the overflow valve there may be no valve or constriction.
• An expansion vessel in the return pipe (in the B-pack or in the installation).
• A check valve, if there are pipes running up, within close distance of the unit. This
prevents a thermosiphon effect from occurring during tap water operation (a non
spring-operated return valve, must be assembled vertically).
5.1.1 Thermostatic radiator taps
If all radiators are fitted with thermostatic or cable radiator taps, a minimum water
circulation must be safeguarded. See par. 7.5.
Daikin Europe NV
16
5.1.2 Dividing CH installation in groups in case of additional heat
sources
Operating principle
If the room thermostat switches off the boiler because another heat source (wood heater,
open fire etc.) heats the room, the other rooms may cool down. This can be resolved by
splitting the CH installation into two zones. The zone with the external heat source (Z2)
can be shut off from the main circuit by means of an electrical shut-off valve. Both zones
are fitted with their own room thermostat.
Please note: This “external heat source” regulation may only be applied if no extra
external tank has to be heated up (installation type 1).
Installation instructions
1. Install the valve in accordance with the connection diagram.
2. Connect the room thermostat of zone 1 to X4 – 6/7.
3. Connect the room thermostat of zone 2 to X4 – 11/12.
4. Change parameter A (see Parameter settings via the service code par. 7.2).
Please note: The room thermostat in zone
thermostat in zone 2 may be an OpenTherm thermostat or an on/off thermostat.
Connection diagram “external heat source” regulation
A. Boiler
B. Electrical shut-off valve 230 V ~
C. Radiators
T1. Room thermostat zone 1
T2. Room thermostat zone 2
Z1. Zone 1
Z2. Zone 2
1 MUST
be an on/off thermostat. The room
Connecting external tank
For the connection of the EHOB*A*V1H to an indirectly fired tank, the following is
delivered upon order:
• Tank sensor
• Three-way valve set 230V
Connect the tank and three-way valve to the boiler in accordance with the diagram.
Remove the through connection between 9 and 10 to connector X4. Connect the threeway valve to connector X2 and connect the tank sensor or thermostat to connector X4
in accordance with the wiring diagram (see par. 10.2).
Connection diagram indirectly fired tank
C. Unit
D. Tanks
E. CH installation
F. Expansion vessel
G. Safety valve 3 Bar
H. Three-way valve
I. Tank sensor or thermostat
Note
When an on/off tank thermostat is used, the heat request will start when the thermostat is
opened, and it will end when the thermostat closes again.
In case of old installations or domestic hot water circuits which can contain small
particles, install a filter in the domestic hot water circuit.
This pollution could cause a fault during domestic hot water operation.
Daikin Europe NV
17
5.2 Connecting electronically
CAUTION
A socket with safety ground must be no further than 1 meter
from the unit.
The socket must be easily accessible.
When installing the unit in a damp space, a fixed connection is
obligatory, by means of an all-pole main switch with a
minimum contact gap of 3 mm.
If the mains cable is damaged or requires replacement for any
other reason, the replacement mains cable must be ordered
from the manufacturer or its representative. In case of any
doubt, contact the manufacturer or its representative.
1. Remove the plug from the socket, when working on the electrical circuit.
2. If there is a cover plate (A), remove it to the front.
3. Unscrew both screws (1) behind the display window.
4. Slide the bottom of the front panel (2) forwards, and remove it.
5. Pull the boiler controller forward. The boiler controller will tip downwards in the
process.
6. Consult par. 5.2.1 to make the connections.
7. After the required connections have been made, slide the boiler controller back into
the unit and return the cover plate, if you are using one.
8. After making the required connections, connect the unit to the socket with safety
ground.
5.2.1 Electrical connections
Temperature regulation Connector X4 Comments
Room thermostat on/off 6 - 7 Modulating thermostat with
comfort function in use
Outdoor temperature
sensor
Frost thermostat 6 - 7 Parallel over room thermostat
Boiler Sensor 9 - 10 Remove yellow cable bridge
Daikin Europe NV
11 - 12
8 - 9 -
18
5.3 Connect room thermostat
5.3.1 Room thermostat on/off
1. Connect the room thermostat (see par. 10.2).
2. If necessary, set the feedback resistance of the room thermostat to 0.1 A. If unsure,
measure the electrical current and set it accordingly.
The maximum resistance of the thermostat pipe and the room thermostat amounts to a
total of 15 Ohm.
5.3.2 Modulating thermostat, Open Therm
The unit is suitable for connecting a modulating room thermostat, in accordance with
the OpenTherm communication protocol.
The most important function of the modulating room thermostat is to calculate the input
temperature at a required room temperature, in order to make optimal use of the
modulating. At every heating request, the required input temperature is shown on the
display of the unit.
Connect the modulating thermostat (see par.10.2).
If you want to use the tap water on/off switch function of the OpenTherm thermostat, the
tap water comfort function must be set to eco or on.
For more information, consult the manual of the room thermostat.
5.3.3 Modulating room thermostat, wireless
The EHOB*A*V1H CH boiler is suitable to communicate wireless without
sending/receiving module with the Honeywell room thermostats T87RF1003 Round RF,
DTS92 and CMS927. The CH boiler and the room thermostat must be appointed to each
other:
• Press the reset button of the unit for approximately 5 seconds in order to get to the RF-
room thermostat menu.
• One of the following codes will be shown on the display of the unit:
1. rF and L / - : the display above the button shows an L alternated by a –
red led : flashing
The CH boiler has not been appointed. A unit in this operating status, can be linked
by using the method of the appropriate room thermostat.
The method of appointment depends on the type of room thermostat and is
described in the installation and operating instructions of the wireless
room thermostat.
2. rF and L / 1 : the display above button shows an L alternated by a 1
red led : off
The CH boiler has already been appointed. There is already an existing link with
an RF room thermostat. In order to allow a new link to be made, the existing link
will have to be removed.
See: Undo the appointment of an RF room thermostat to the CH boiler.
• Press the reset button to exit the RF room thermostat menu or wait for 1 minute.
Testing the connection between the unit and the RF room thermostat
1. Press the reset button of the unit for approximately 5 seconds to access
the RF room thermostat menu of the boiler controller.
2. Press the service button 1x. On the display above the button, a
will be shown.
3. Set the room thermostat to the test mode (see the installation and operating
instructions of the room thermostat).
4. The red led above the reset button will flash if the appointment has
been carried out correctly.
5. Press the reset button of the unit to exit the RF room thermostat menu of
the boiler controller. You will automatically exit the test mode 1 minute after
the last test message of the RF room thermostat has been received.
t
Daikin Europe NV
19
020601011
E
Undo the appointment of an RF room thermostat to the CH boiler.
•Press the reset button of the unit for approximately 5 seconds to
access the RF room thermostat menu of the CH boiler.
•Press the service button 2x. On the display above the button, a
C
will be shown.
•Press the reset button of the unit again to remove the existing
appointments. The display of the unit will show rF again, with a flashing
L / - . If required, an RF room thermostat can be appointed to the unit
again.
•Press the reset button of the unit to exit the RF room thermostat menu
or wait for 1 minute.
5.3.4 Outdoor temperature sensor
The unit is provided with a connection for an outdoor temperature sensor. The
outdoor temperature sensor should be used in combination with an on/off room
thermostat.
In principle, any on/off room thermostat can be combined with an outdoor sensor.
Upon request of the room thermostat, the boiler will provide heat until the maximum
set temperature in the boiler has been reached. This maximum set temperature is
automatically regulated via the outdoor sensor, in accordance with the set fuel line
in the boiler.
Connect the room outdoor sensor (see par. 10.2).
For the fuel line setting, see the weather dependent regulation (see par. 0).
5.4 Connecting gas
1. Fit the gas valve directly on the 1/2" gas connection of the connection set
using appropriate seal.
2. Place a gas sieve in the connection for the unit if the gas may be
contaminated.
3. Connect the gas pipe in the gas valve using appropriate seal.
4. Check the gas carrying parts for leakages at a pressure of up to 50 mbar.
5. The gas pipe should be fitted pressure free.
Daikin Europe NV
20
5.5 Flue and air supply duct
Don not use screws or parkers to mount the flue system as leakage can
Use water instead. The sealing rubbers can be negatively affected when
5.5.1 Concentric connection 60/100
The boiler is fitted with a flue gas adapter suitable for connecting to a concentric flue gas extractor
system with a diameter of 60/100.
Fit the concentric pipe thoughtfully in the adapter. The built in gaskets ensure there is an air tight
seal.
For the installation of the flue and air supply duct material, see the
manual included with the materials. Contact the
manufacturer of the relevant flue and air supply duct materials for
extensive technical information and specific
assembly instructions.
Make sure that the socket connections of the flue and air supply duct
materials are correctly sealed.
Improper fastening of the flue and the air supply duct
can lead to hazardous situations or result in personal injury.
Check all flue components for tightness.
occur.
Do not use any sort of grease when mounting the pipe system.
grease is applied.
Do not mix any components, materials or ways of coupling from
different manufacturers.
5.5.2 Concentric connection 80/125
If required, the flue gas adapter 60/100 can be replaced by a version for a flue gas extractor
system with a 80/125 diameter.
1. Carefully follow the instruction as provided with the adapter set 80/125.
2. Fit the concentric pipe thoughtfully in the adapter. The built in gaskets ensure there is an air
tight seal.
5.5.3 Parallel connection 80/80
If required, the flue gas adapter 60/100 can be replaced by a version for a parallel flue system (2
pipes) with a 80 mm diameter.
1. Carefully follow the instruction as provided with the adapter set 80.
2. Fit the pipes for the air supply and flue gas thoughtfully in the air inlet opening and flue gas
adapter of the unit. The built in gaskets ensure there is an air tight seal. Make sure that the
connections are not mixed.
Daikin Europe NV
21
5.6 Outlet systems
Explanation
flue systems
Category in accordance to CE
B23 A flue that evacuates the products of combustion to the outside of
Make sure the air inlet is open
B33 A flue system which is connected to a common duct system. This common duct system
Make sure the air inlet is open
C13 Horizontal flue system. Discharge in the outside wall.
For example : a wall terminal
C33 Vertical flue system. Flue gas discharge via the roof.
For example : a vertical roof
C43 Joint air supply and
flue gas discharge duct (CLV system)
C53 Separate air supply and separate flue gas discharge duct.
C63 Free in the market available flue material with CE approval
Do not mix flue mate
rials from
C83 Joint air supply and flue gas discharge duct (CLV system)
Only as twin pipe system
C93 Air supply and flue gas discharge duct in shaft or ducted: Concentric. Air supply from
Concentric flue system
Please note that not all flue gas configurations described below are permitted in all
countries. Therefore observe local regulations prior to installation.
The drawings above are a sample and can differ on details.
the room containing the appliance. The combustion air is drawn directly from the room.
consists of a single natural draught flue. All pressurized parts of the appliance containing
products of combustion are completely enclosed by parts of the appliance supplying
combustion air. Combustion air is drawn into the appliance from the room by means of a
concentric duct, which encloses the flue. The air enters through defined orifices situated
in the surface of the duct.
Inlet opening for the air supply is in the same pressure zone as the discharge
Inlet opening for the air supply is in the same pressure zone as the discharge
Twin-pipe or concentric
Discharging into different pressure zones
and complies to the demands
and complies to the demands
through the facede.
terminal.
Discharging into different pressure zones
existing duct. Flue gas discharge via the roof. Air supply and flue gas discharge are in
the same pressure zone.
Daikin Europe NV
different suppliers.
between the boiler and the
duct.
22
5.7 Flue material
The following flue materials can be ordered at Daikin.
Also visit the website: fluegas.daikin.eu
C13
Art.no. Description
EKFGP2978
EKFGP4651
EKFGP4652
EKFGP4660
EKFGP4661
EKFGP2977
EKFGP4664
EKFGP4631
EKFGP4667
Wall Terminal Kit PP/GLV 60/100
Extension PP/GLV 60/100 x 500mm
Extension PP/GLV 60/100 x 1000mm
Elbow PP/GLV 60/100 90°
Elbow PP/GLV 60/100 45°
Wall Terminal Kit low profile PP/GLV 60/100
Elbow PP/GLV 60/100 30°
Wall Bracket Dn.100
Measurement Tee with Inspection Panel PP/GLV 60/100
C33
Art.no. Description
EKFGP4631 Wall Bracket Dn.100
EKFGP4651 Extension PP/GLV 60/100 x 500mm
EKFGP4652 Extension PP/GLV 60/100 x 1000mm
EKFGP4660 Elbow PP/GLV 60/100 90°
EKFGP4661 Elbow PP/GLV 60/100 45°
EKFGP4664 Elbow PP/GLV 60/100 30°
EKFGP4667 Measurement Tee with Inspection Panel PP/GLV 60/100
EKFGP6837 Roof Terminal PP/GLV 60/100 AR460
Daikin Europe NV
23
C53
Art.no. Description
EKFGP4651 Extension PP/GLV 60/100 x 500mm
EKFGP4652 Extension PP/GLV 60/100 x 1000mm
EKFGP6837 Roof Terminal PP/GLV 60/100 AR460
EKFGW4085 Elbow PP 80 90°
EKFGW4086 Elbow PP 80 45°
EKFGV1102 Chimney Conection Set 60/100 Air Intake Dn.80 C53
EKFGP4660 Elbow PP/GLV 60/100 90°
EKFGP4661 Elbow PP/GLV 60/100 45°
EKFGP4664 Elbow PP/GLV 60/100 30°
EKFGP4667 Measurement Tee with Inspection Panel PP/GLV 60/100
EKFGP4631 Wall Bracket Dn.100
EKFGW4001 Extension PP 80x500
EKFGW4002 Extension PP 80x1000
EKFGW4004 Extension PP 80x2000
C93
Art.no. Description
EKFGP4678 Chimney Connection 60/100
EKFGP1856 Flex Kit PP Dn.60-80
EKFGP6340 Extension Flex PP 80 L=10 M
EKFGP6344 Extension Flex PP 80 L=15 M
EKFGP6341 Extension Flex PP 80 L=25 M
EKFGP6342 Extension Flex PP 80 L=50 M
EKFGP6324 Connector Flex-Flex PP 80
EKFGP4664 Elbow PP/GLV 60/100 30°
EKFGP4661 Elbow PP/GLV 60/100 45°
EKFGP4660 Elbow PP/GLV 60/100 90°
EKFGP6333 Spacer PP 80-100
EKFGP4667 Measurement Tee with Inspection Panel PP/GLV 60/100
EKFGP4631 Wall Bracket Dn.100
EKFGP4651 Extension PP/GLV 60/100 x 500mm
Daikin Europe NV
24
5.8 Connection to a flue system without air inlet (B23, B33)
CAUTION
•Make sure the boiler room complies to the regulatory
requirements for connecting to a flue system in
accordance to B23 or B33
•When connection the boiler to a flue system in
accordance to B23 or B33 the electrical protection
class is IP20 instead of IPX4D
General assembly
1. Slide the combustion gas outlet pipes into each other.
From the unit, every pipe has to be slid into the previous one.
Mount a non-vertical combustion gas outlet pipe on a slope towards the unit (min. 5mm/m).
5.8.1 Permitted pipe lengths at parallel air supply and flue tube systems
Permitted pipe lengths B23 and B33 when applying Ø80 mm
C13 C33 C43 C53 C83
EHOB12AAV1 H 100 m 100 m 100 m 100 m 100 m
EHOB18AAV1 H 100 m 100 m 100 m 100 m 100 m
EHOB42ABV1 H 60 m 60 m 60 m 60 m 60 m
Daikin Europe NV
25
5.9 Connection to a sealed flue system.
5.9.1 Pipe lengths
As the resistance of the flue tube and air supply pipes increases, the power of the unit will
decrease. The maximum permitted power reduction is 5%.
The resistance of the air supply and the combustible gas outlet depends on the length, diameter
and all components of the pipe system. Per unit category, the total permitted pipe length has been
indicated for the air supply and the combustible gas outlet.
5.9.2 Permitted pipe lengths in concentric flue tube systems
Permitted pipe lengths when applying concentric 60/100
C13 C33
EHOB12AAV1 H 10 m 11 m
EHOB18AAV1 H 10 m 11 m
Permitted pipe lengths when applying concentric 80/125
C13 C33 C93
EHOB12AAV1 H 29 m 29 m See par. 5.9.8
EHOB18AAV1 H 29 m 29 m See par. 5.9.8
EHOB42ABV1 H 29 m 29 m See par. 5.9.8
Contact the manufacturer for test calculations for the resistance of the air supply and
combustible gas outlet pipe and the wall temperature at the end of the combustible gas
outlet pipe.
Replacement lengths
Bend 90° R/D=1 2 m
Bend 45° R/D=1 1 m
Knee 90° R/D=0.5 4 m
Knee 45° R/D=0.5 2 m
General assembly:
For all outlets, the following assembly applies:
1. Slide the concentric combustion gas outlet pipe and air supply pipe.
2. Slide the concentric pipes into each other.
From the unit, every pipe has to be slid into the previous one.
3. Mount a non-vertical combustion gas outlet pipe on a slope towards the unit
(min. 5mm/m).
4. Fit the assembly brackets in accordance with the assembly instructions of the supplier of
the air supply/flue tube system.
Daikin Europe NV
26
5.9.3 Permitted pipe lengths at parallel air supply and flue tube systems
Permitted pipe lengths when applying Ø80 mm (total of flue pipe and air intake pipe
together).
C13 C33 C43 C53 C83
EHOB12AAV1 H 100 m 100 m 100 m 100 m 100 m
EHOB18AAV1 H 100 m 100 m 100 m 100 m 100 m
EHOB42ABV1 H 60 m 60 m 60 m 60 m 60 m
Replacement lengths
Bend 90° R/D=1 2 m
Bend 45° R/D=1 1 m
Knee 90° R/D=0.5 4 m
Knee 45° R/D=0.5 2 m
Calculation example
Pipe Pipe lengths Pipe length total
Flue gas outlet L1 + L2 + L3 + 2x2 m 13 m
Air supply L4 + L5 + L6 + 2x2m 12 m
Note:
The total pipe length is: sum of the straight pipe lengths + sum of the replacement pipe
lengths of bends/knees amounts to a total of 25 meters. If this value is less than the
maximum permitted pipe length, the flue gas outlet meets the requirements on this point.
Daikin Europe NV
27
5.9.4 Free in the market available flue gas materials (C63).
+0,3
- 0,7
+0,3
- 0,7
+ 2
- 0
+0,3
- 0,7
+ 2
- 0
The properties of the combustion determine the choices for the flue material. The flue
materials need to be CE approved and provided with the CE marking.
The standards EN 1443 and EN 1856-1 provide the necessary information for choosing the
flow material by means of a sticker including an identification string.
The Identification string contains the following information:
A CE marking
B The standard to comply to: Metal, EN 1856-2
Plastic, EN 14471
The ID string needs to contain the following information:
C Temperature class : T120
D Pressure class : Pressure (P) or High Pressure (Hi)
E Resistance class : W (Wet)
F Resistance class in case of fire : E
Dimensions C63 Flue system (external dimensions in mm)
Parallel Concentric 80/125 Concentric 60/100
Flue pipe Air inlet Flue pipe Air inlet
ø 80
ø 80
ø 125
ø 60
ø 100
Flue materials of different markings must not be combined !
Daikin Europe NV
28
5.9.5 Securing the flue system
Exception at connecting on boiler:If the lenght of the pipes before and after
IMPORTANT
•These regulations are typical for both concentric and parallel flue
systems.
• The flue system must be secured to a solid structure.
• The flue system should have a continuous fall back to the boiler (1.5° to
3°). N.B. Wall terminals must be installed leveled..
• Only use accompanying brackets.
• Every elbow must be secured by using the bracket.
the first elbow, are no more than 250 mm, the second element after the
first elbow has to contain a bracket.
Note: The bracket must be positioned on the elbow!
•Every extension must be secured per metre with a bracket.
This bracket must not be clamped around the pipe ensuring free
movement of the pipe..
•Make sure bracket is locked into the correct position depending on the
position of the bracket on the pipe or elbow:
•Do not mix flue parts or clamps of different suppliers.
Max. distance between clamps
Vertical Others
2000 mm 1000 mm
• Divide the lengths between the brackets evenly.
• Every system must contain at least 1 bracket.
• Position the first clam at a maximum of 500 mm from the boiler.
Daikin Europe NV
29
Daikin Europe NV
30
5.9.6 Air supply from the facade and a roof outlet with communal
•
exhaust system
Unit category: C83
An air supply from the facade and a roof outlet with communal exhaust system is
permitted.
IMPORTANT
The air supply in the facade must be fitted with an inlet
roster (A).
• The communal output system must be fitted with a traction
extractor hood (B).
• If the communal output system is situated in the outdoors,
the output pipe must be double-walled or insulated.
Permitted pipe length
Combustion gas outlet pipe between the unit and the communal output system and
air supply pipe between the unit and the inlet roster together:
EHOB12 & 18AAV1 H 100 m
The minimum diameters of the communal output system based on vacuum
Flue tube diameter
Number of units EHOB12 & 18AAV1 H
IMPORTANT
If you wish to use the unit EHOB42ABV1H in combination
with a C83 smoke gas outlet system, please contact Daikin
Europe NV.
Communal combustible gas outlet
The output of the combustion gas outlet can be made in any location on the sloping
roof surface, providing the outlet in the roof surface has the same orientation as the
air supply in the facade. On a flat roof, the outlet of the combustion gas outlet must be
made in the “free” outlet area.
Fit a condense output.
31
Note
The communal outlet is certified in combination with the unit.
Daikin Europe NV
Loading...
+ 294 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.