Daikin Air Conditioner
DTA114A61 • 61-9
Adaptor for Multi tenant Installation Manual
INSTALLATION
3
〈〈Ceiling-mounted Duct Type〉〉〈〈Ceiling-mounted Cassette Round-flow Type〉〉
Accessories NoteCheck that the following accessories are provided with the adaptor before installation.
Applicable models Relay harness
FXFQ~P
Adaptor for Multi tenant
1 pc.
FXMQ~P
BSVQ~P
PCB support
Tiewrap
Relay harness
Installation Manual
4 pcs.
4 pcs.
4 pcs. (see the table on the right-hand
side for applicable models)
1 pc.
FXAQ~M
700
White White, 4 pins
UL electric wire
350
White White, 4 pins
UL electric wire
260
White Blue, 3 pins
UL electric wire
1900
White White, 3 pins
VCTF electric wire
• An adaptor mounting plate and mounting box
are required in addition to the provided
component parts in the case of mounting the
adaptor to the following models.
FXFQ~P: KRP1H98
FXMQ~P: KRP4A96
FXAQ~M: KRP4A93
• Both ends of harness are for connection of
PCB of indoor unit (or BS unit) and for
connection of adaptor for multi tenant. Be
careful when connecting them.
FXFQ
Lid of installation box
(KRP1H98, sold separately)
Adaptor
PCB support
Installation box for adaptor PCB
(KRP1H98, sold separately)
NOTE
1) Installation box for adaptor PCB is
required in addition to the provided
component parts in the case of
mounting the adaptor.
2) Connect the wiring to the adaptor PCB
first. The work will be easier.
(Refer to .)
〈〈Wall-mounted type〉〉
FXAQ
Installation box for adaptor PCB
(KRP4A93, sold separately)
METHOD OF WIRING
5
FXMQ
Mounting plate for adaptor PCB
(KRP4A96, sold separately)
PCB support
Adaptor
〈〈BS unit〉〉
BSVQ
NOTE
1) Mounting plate for adaptor PCB is
required in addition to the provided
component parts in the case of
mounting the adaptor.
2) Connect the wiring to the indoor PCB
first. The work will be easier.
(Refer to .)
METHOD OF WIRING
5
GENERAL DESCRIPTION OF SYSTEM
1
• The use of this adaptor allows the system to operate with no system error indication in the event of the interruption of power supply to other indoor units.
(In the case of the following diagram, there will be no error indication on the remote controllers of tenant 1 or tenant 3 or tenant 4 in the event of the
interruption of power supply to tenant 2.)
Tenant 1 Tenant
open
Adaptor
PCB support
NOTE)
Tenant
2
Tenant
3
No error indicationNo error indication
4
BSVQ
FX~
ELECTRIC WIRING
4
Three-pole contact
(Field supply)
Installation box for adaptor PCB is
required in addition to the provided
component parts in the case of
mounting the adaptor.
•
Example with FXFQ, FXAQ, and FXMQ
(2)
(4)
This adaptor
(1)
Adaptor
(1) Connect this adaptor and the PCB of the indoor unit with the
provided relay harness (varying with each indoor unit model).
(2) Connect the 24VAC (±20%) power supply to the X1M terminals of
the adaptor through the normally closed contacts of the relay. Be
sure to contact the relay contacts to both poles of the power
supply so that the positive and negative lines of the power supply
will be turned off simultaneously. A transformer may be used for
the 24VAC power supply provided for each adaptor on the
condition that the transformer has a capacity of 24VA or over.
(3) Provide a relay (with a normally closed contact) between the T1
and T2 terminals of the PCB.
PCB support
NAMES AND FUNCTIONS
2
Contact input (T1/T2)
Receives power under ON/OFF
control for the indoor unit
through the contact relay.
Adaptor power supply
Receives 24VAC power
Indoor power supply
Supplies power to the indoor
unit through the provided
harness connected.
•
Example with BSVQ
Two-pole contact
(Field supply)
(3)
(2)
(3)
PCB of indoor unit
This adaptor
(1)
BSVQ PCB
Minimum contact load: 1mA normally closed contact at 15VDC
Rated current: 3 A min.
Wire specifications: Vinyl cord with sheath or cable (2 wire)
Wiring thickness: 0.75 to 1.25 mm
Wiring length: 100 m max.
(4) Short-circuit the T1 and T2 terminals of the adaptor.
(1) Connect the adaptor and BSVQ PCB through the relay harness.
(2) Connect the 24VAC (±20%) power supply to the X1M terminals of
the adaptor through the normally closed contacts of the relay. Be
sure to contact the relay contacts to both poles of the power
supply so that the positive and negative lines of the power supply
will be turned off simultaneously. A transformer may be used for
the 24VAC power supply provided for each adaptor on the
condition that the transformer has a capacity of 24VA or over.
(3) Short-circuit the T1 and T2 terminals of the adaptor.
Minimum contact load: 1mA normally closed contact at 15VDC
Rated current: 3 A min.
Wire specifications: Vinyl cord with sheath or cable (2 wire)
Wiring thickness: 0.75 to 1.25 mm
Wiring length: 100 m max.
2
2