Daikin DCS601C51 User Manual

Operation Manual

Use smart and save smart
¡Thank you for purchasing intelligent Touch Controller.
¡This operation manual contains notes for safe use of the
product.
For correct use, be sure to read this manual carefully before use.
place where the operator can conveniently refer to at anytime.
In case of personnel change, be sure to give the manual to the new operator.
Model
DCS601C51
intelligent Touch Controller
Maintenance
Precautions 83 Maintenance
LCD Maintenance 84 When Leaving the Product Turned OFF for a Long Time
84
Troubleshooting 85
Maintenance
For Your Information
Before useOperation
Before use
Safety Considerations
Be sure to follow the instructions below 1
System Overview 3 Features and Functions 4 Part Names and Functions 5 Part Names on the Monitoring Screen and the Functions
List 7
Icon 9
Operation
Operation Quick Reference
13
Air Conditioner Operation 15 Monitoring Operation of Air Conditioner
26
System Setup Menu
32
For Your Information
Options 93 Specification 94 After-sales Service 95
Warning
Warning
caution
Note

Safety Considerations

Please read these “SAFETY CONSIDERATIONS” carefully before installing air conditioning equipment and be sure to install it correctly. After completing the installation, make sure that the unit operates properly during the start-up operation. Please instruct the customer on how to operate the unit and keep it maintained. Also, inform customers that they should store this installation manual along with the operation manual for future reference. This air conditioner comes under the term “appliances not accessible to the general public”.
Meaning of warning, caution and note symbols.
Indicates a potentially hazardous sit uationwhich, if not avoided, could result in death or serious injury.
Indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury. It may also be used to alert against unsafe practices.
Indicates situation that may result in equipment or property-damage­only accidents.
Keep these warning sheets handy so that you can refer to them if needed.
Also, if this equipment is transferred to a new user, make sure to hand over this operation manual to the new user.
In order to avoid electric shock, fire or injury, or if you detect any abnormality such as smell of fire, turn off power and call your dealer for instructions.
Ask your dealer for installation of the air conditioner.
Incomplete installation performed by yourself may result in a water leakage, electric shock, and fire.
Ask your dealer for improvement, repair, and maintenance.
Incomplete improvement, repair, and maintenance may result in a water leakage, electric shock, and fire.
Improper installation or attachment of equipment or accessories could result in electric shock, short-circuit, leaks, fire or other damage to the equipment. Be sure only to use accessories made by Daikin which are specifically designed for use with the equipment and have them installed by a professional.
Ask your dealer to move and reinstall the air con­ditioner or the remote controller.
Incomplete installation may result in a water leakage, electric shock, and fire.
Never let the indoor unit or the remote controller get wet.
It may cause an electric shock or a fire.
Never use flammable spray such as hair spray, lacquer or paint near the unit.
It may cause a fire.
Never replace a fuse with that of wrong ampere ratings or other wires when a fuse blows out.
Use of wire or copper wire may cause the unit to break down or cause a fire.
Never inspect or service the unit by yourself.
Ask a qualified service person to perform this work.
Cut off all electric waves before maintenance. Do not wash the air conditioner or the remote controller with excessive water.
Electric shock or fire may result. Do not install the air conditioner or the remote controller at any place where flammable gas may leak out. If the gas leaks out and stays around the air condi­tioner, a fire may break out.
Do not touch the switch with wet fingers.
Touching a switch with wet fingers can cause electric shock.
CISPR 22 Class A Warning:
This is a class A product. In a domestic environment this prod-uct may cause radio interference in which case the user may be required to take adequate measures.
1
After a long use, check the unit stand and fitting for damage.
If they are left in a damaged condition, the unit may fall and result in injury.
Do not allow a child to mount on the unit or avoid placing any object on it.
Falling or tumbling may result in injury.
Do not let children play on and around the unit.
If they touch the unit carelessly, it may result in injury.
Do not place a flower vase and anything contain­ing water.
Water may enter the unit, causing an electric shock or fire.
Never touch the internal parts of the controller.
Do not remove the front panel. Some parts inside are dan-gerous to touch, and a machine trouble may happen. For checking and adjusting the internal parts, contact your dealer.
Avoid placing the controller in a spot splashed with water.
Water coming inside the machine may cause an electric leak or may damage the internal electronic parts.
Do not operate the air conditioner when using a room fumigation - type insecticide.
Failure to observe could cause the chemicals to become deposited in the unit, which could endanger the health of those who are hypersensitive to chemicals.
Safely dispose of the packing materials.
Packing materials, such as nails and other metal or wooden parts, may cause stabs or other injuries. Tear apart and throw away plastic packaging bags so that children will not play with them. If children play with a plastic bag which was not torn apart, they face the risk of suffocation.
Do not turn off the power immediately after stop­ping operation.
Always wait at least five minutes before turning off the power. Otherwise, water leakage and trouble may occur.
The appliance is not intended for use by young children or infirm persons without supervision. The remote controller should be installed in such away that children cannot play with it.
Never press the button of the remote controller with a hard, pointed object.
The remote controller may be damaged.
Never pull or twist the electric wire of the remote controller.
It may cause the unit to malfunction.
Do not place the controller exposed to direct sunlight.
The LCD display may get discolored, failing to dis­play the data.
Do not wipe the controller operation panel with benzine, thinner, chemical dustcloth, etc.
The panel may get discolored or the coating peeled off. If it is heavily dirty, soak a cloth in water-diluted neutral detergent, squeeze it well and wipe the panel clean. And wipe it with another dry cloth.
Dismantling of the unit, treatment of the refriger­ant, oil and eventual other parts, should be done in accordance with the relevant local and national regulations.
2
CAUTION NOTE
Before use
3

System Overview

This intelligent Touch Controller is capable of controlling / monitoring up to 64 groups of indoor units (hereafter “groups”).
The main functions of the intelligent Touch Controller include :
1. Collective starting / stopping of operation of the indoor units connected to the
intelligent
Touch Controller.
2. Starting / stopping of operation, temperature setting, switching between temperature control modes and enabling / disabling of operation with the hand-held remote control by zone or group .
3. Scheduling by zone or group .
4. Monitoring of the operation status by zone or group .
5. Display of the air conditioner operation history.
6. Compulsory contact stop input from the central monitoring panel (non-voltage, normally-open contact).
7. Power distribution of the air conditioners. (With the optional DCS002A51)
A group of indoor units include :
Zone control with the intelligent Touch Controller Zone control, which allows collective settings for more than one group, is available with the intelligent Touch
Controller, which facilitates the setting operations.
q One indoor unit without a remote control.
e Up to 16 indoor units controlled with one or two remote controls.
¡One setting makes the same setting for all of the units in one zone. ¡Up to 128 zones can be set with one intelligent Touch Controller.
(The maximum number of groups in one zone is 64.)
¡Groups can be zoned at will with the intelligent Touch Controller. ¡Units in one group can be divided into more than one zone.
w One indoor unit controlled with one or two remote controls.
intelligent Touch Controller
Zone 1
Up to 16 units Up to 16 unitsTwo remote controlsRemote control
No remote control
Remote control Remote control
or
Indoor unit
Zone 5
Zone 2 Zone 3 Zone 4
4

Features and Functions

Operation Menu
intelligent
Touch Controller is capable of starting / stopping of the operation by
the group or zone. Collective starting / stopping is also available.
Air Conditioner Detail Setup
Temperature setting, switching between temperature control modes, switching of speed and direction of wind and remote control mode setting are available by the group, by the zone or collectively.
Monitoring of Various Information on Indoor Units
Information on operation such as the operation mode and temperature setting of the indoor units, maintenance information including the filter or element cleaning sign, troubleshooting information such as error codes can be displayed by the group or the zone.
Zone Control Simplifying Complicated Setting Operations
Up to 64 groups can be controlled with the intelligent Touch Controller. More than one group can be consolidated into a zone, which can be registered, to allow the following settings by the zone. This eliminates the need for repeating the same setting operation for each group. Function to allow collective setting for all groups is also available.
Detailed Scheduled Operation Control
The intelligent Touch Controller allows detailed scheduled operation by the group, by the zone or collectively. Up to 8 options for annual schedule can be set. Each schedule can include four types of plans : for Weekdays, Holidays, Special days 1 and Special days 2. Each of the plans allows setting of up to 16 operations.
Diversified Operation Modes
Operation can be controlled both with the main unit and the remote control to provide diversified operation management. Setting with the main unit allows the following remote control settings by the group, by the zone or collectively:
1. Start/Stop 2. Operation Mode 3.Temperature Setting
: (Remote control) Inhibited
: (Remote control) Inhibited
: (Remote control) Inhibited
: (Remote control) Permitted
: (Remote control) Permitted : (Remote control) Permitted
: Priority
¡Start / stop ¡Temperature setting ¡Switching between operation modes ¡Setting of direction and fan speed
¡Disabling / enabling the remote control
See pages
15 17
to
See pages
18 22
to
See pages
26 29
to
See page
22
See pages
15 29
to
33
See pages
35 36
to
See pages
37 46
to
Handy Automated Control
The Intelligent Touch Controller can do the following.
¡
Change Over Settings : automatically switches between cooling and heating
according to the room temperature.
¡
Temperature Limit Settings : prevents the temperature from rising too high or
too low in unmanned rooms.
¡
Heating Optimization Settings : stops uncomfortable hot air from blowing when
the heating thermo is off.
Before use
Be sure to use the touch pen for operation of the touch panel of the intelligent Touch Controller. Operating with an object other than the touch pen provided may cause damage and failure.

Part Names and Functions

Color LCD with Touch Panel
Provides a display for monitoring and operation. Be sure to use the touch pen provided for operation.
PCMCIA Card Slot
Used when using the optional Power Proportional Distribution (DCS002C51) or updating the intelligent Touch Controller software to a newer version.
Touch Pen
5
Use the touch pen for operation. Be sure to use the touch pen for operation. Use caution not to lose the touch pen.
When the pen is lost, contact the dealer you purchased the product from.
Front and Side View
Note
Before use
Terminals on the Back of intelligent Touch Controller
Using D3-NET Plus adapter being sold as an accessory, you can increase the number of indoor units to be controlled.
RS232-C connector for D3-NET Plus adapter
When using AIRNET service, connect it to the telephone line.
Modem connector for AIRNET
This is used when distributing the power supply to indoor units using optional Power Proportional Distribution software sold separately and when stopping the indoor units compulsorily by contact input. The size of terminal block is M3.5.
Terminal block for watt hour meter and force stop input of indoor units
When monitoring and operating the indoor units using the optional Web and E-mail function software sold separately, connect to LAN via Ethernet cable.
Ethernet connector for web
Securely connect the earth wire. Terminal size is M4.
Earth terminal block
Connect to AC100-240V power supply. Terminal size is M4.
Terminal block for power supply
The terminal size of the terminal block for communication with indoor units is M3.5.
Terminal block for D3-NET communication
LINE
COM L0Dil Pi3 COM Pi2 Pi1 F2 F1 N L
PHONE
RS-232C LAN
6
Contents of the List Currently Displayed
¡When Group List is displayed
Zone : Zone Name
¡
When Zone List is displayed Zone List
Display Mode Selection
Press the button and display change between Zone and Group.
System Condition Displayed Domain
Domain displaying system condition (Compulsory Stop etc.)
Zone / Group Name
Set the names in the Group Registration or Zone Registration in the System Setup Mode.
Filter / Element Sign
Displayed when there is any air conditioner showing a filter or element sign in the zone or the group.
Target of Automatic Control
Displayed when there is any air conditioner with the registration of scheduled in the zone or in the group.
Monitoring Screen Legend
Pressing the ? button shows more detailed legend.
Button to Switch to the System Setup Mode
Use this button for settings including the time, group, zone and schedule.
7

Part Names on the Monitoring Screen and the Functions

List
Zone / Group Currently Displayed
The name of the zone / group currently selected is highlighted in light-blue.
8
List
Display for Collective Monitoring of Air Conditioners Connected to intelligent Touch Controller
When operation is normal and any air conditioner is in operation :
Red / Normal When operation is normal and all air conditioners are in stoppage :
Green / Normal When there is any air conditioner generating an error :
Yellow / Abnormal When there is any air conditioner with communication error :
Blue / Abnormal
Change in color of Start/Stop is possible by Iconcolor Settings in System Settings.
Start All Button
Button to collectively start all the air conditioners connected to intelligent Touch Controller.
Stop All Button
Button to collectively stop all the air conditioners connected to intelligent Touch Controller.
Display Mode Selection
Select the mode among icon / list / detailed icon.
Displayed in List in the right figure. Icon display is P9, 10. Detailed icon display is P11, 12.
Group / Zone Start Button
Button to start operation of the group / zone selected.
Group / Zone Stop Button
Button to stop operation of the group / zone selected.
Group / Zone Set Button
Makes settings (temperature setting, temperature control mode, etc.) and display of the group / zone selected.
Current Time Display
Shows the current date and time.
Group / Zone Prop Button
Detailed display of the group / zone selected
Lock Setting / Cancel Button
Displays possibititiy of monitor operation. Expresses detailed information in P31, 32.
Scroll Buttons
Up / Down scroll button used when monitoring zone / group which are not currently displayed. Left/Right scroll button used when monitoring temperature and errors etc. Which are not currently displayed.
Before use
Contents of the List Currently Displayed
¡When Group List is displayed
Zone : Zone Name
¡When Zone List is displayed
Zone List Display
Display Mode Selection
Select between Zone and Group.
Information on Zone / Group Currently Displayed
Generally, the temperature setting and the operation mode are displayed. If any error occurs in the air conditioner, the error code is displayed.
Displayed Abnormality in Air Conditioner or Communication
Blue triangular mark shows communication abnormality in air conditioner. Yellow triangular mark shows abnormality in air conditioner.
Zone / Group Currently Displayed
The name of the zone / group currently selected is highlighted in blue flame.
Zone / Group Name
Set the names in the Group Registration or Zone Registration in the System Setup Mode.
Filter / Element Sign
Displayed when there is any air conditioner showing a filter or element sign in the zone or the group.
Target of Automatic Control
Displayed when there is any air conditioner with the registration of scheduled in the zone or in the group.
Monitoring Screen Legend
Pressing the ? button shows more detailed legend.
Button to Switch to the System Setup Mode
Use this button for settings including the time, group, zone and schedule.
Description of Zone / Group
Set the names in the Group Registration or Zone Registration in the System Setup Mode.
9
Icon
System Condition Displayed Domain
Domain displaying system condition (Compulsory Stop etc.)
10
Icon
Display for Collective Monitoring of Air Conditioners Connected to intelligent Touch Controller
When operation is normal and any air conditioner is in operation :
Red / Normal
When operation is normal and all air conditioners are in stoppage :
Green / Normal
When there is any air conditioner generating an error :
Yellow / Abnormal
When there is any air conditioner with communication error :
Blue / Abnormal
Change in color of Start / Stop is possible by Iconcolor Settings in System Settings.
Start All Button
Button to collectively start all the air conditioners connected to intelligent Touch Controller.
Stop All Button
Button to collectively stop all the air conditioners connected to intelligent Touch Controller.
Display Mode Selection
Select the mode among icon / list / detailed icon.
Displayed is List in the right figure. List display in P7, 8. Detailed icon display is P11, 12.
Group / Zone Start Button
Button to start operation of the group / zone selected.
Group / Zone Stop Button
Button to stop operation of the group / zone selected.
Group / Zone Set Button
Makes settings (temperature setting, temperature control mode, etc.) and display of the group / zone selected.
Current Time Display
Shows the current date and time.
Group / Zone Prop Button
Detailed display of the group / zone selected
Lock Setting / Cancel Button
Displays possibititiy of monitor operation. Expresses detailed information in P31, 32.
Scroll Buttons
Up / Down scroll button used when monitoring zone / group which are not currently displayed. Left / Right scroll button used when monitoring temperature and errors etc. Which are not currently displayed.
Before use
11
Icon
Contents of the List Currently Displayed
¡When Group List is displayed
Zone : Zone Name
¡When Zone List is displayed
Zone List Display
Display Mode Selection
Press the button ana display change between Zone and Group.
Displayed Abnormality in Air Conditioner or Communication
Blue triangular mark shows communication abnormality in air conditioner. Yellow triangular mark shows abnormality in air conditioner.
Zone / Group Currently Displayed
The name of the zone / group currently selected is highlighted in blue frame.
Zone / Group Name
Set the names in the Group Registration or Zone Registration in the System Setup Mode.
Filter / Element Sign
Displayed when there is any air conditioner showing a filter or element sign in the zone or the group.
Target of Automatic Control
Displayed when there is any air conditioner with the registration of scheduled in the zone or in the group.
Monitoring Screen Legend
Pressing the ? button shows more detailed legend.
Button to Switch to the System Setup Mode
Use this button for settings including the time, group, zone and schedule.
System Condition Displayed Domain
Domain displaying system condition (Compulsory Stop etc.).
12
Display for Collective Monitoring of Air Conditioners Connected to intelligent Touch Controller
When operation is normal and any air conditioner is in operation :
Red / Normal
When operation is normal and all air conditioners are in stoppage :
Green / Normal
When there is any air conditioner generating an error :
Yellow / Abnormal
When there is any air conditioner with communication error :
Blue / Abnormal
Change in color of Start / Stop is possible by Iconcolor Settings in System Settings.
Start All Button
Button to collectively start all the air conditioners connected to intelligent Touch Controller.
Stop All Button
Button to collectively stop all the air conditioners connected to intelligent Touch Controller.
Display Mode Selection
Select the mode among icon / list / detailed icon.
Displayed in List in the right figure. List display is P7, 8. Icon display is P9, 10.
Group / Zone Start Button
Button to start operation of the group / zone selected.
Group / Zone Stop Button
Button to stop operation of the group / zone selected.
Group / Zone Set Button
Makes settings (temperature setting, temperature control mode, etc.) and display of the group / zone selected.
Current Time Display
Shows the current date and time.
Group / Zone Prop Button
Detailed display of the group / zone selected
Lock Setting / Cancel Button
Displays possibititiy of monitor operation. Expresses detailed information in P31, 32.
Scroll Buttons
Up / Down scroll button used when monitoring zone/group which are not currently displayed. Left/Right scroll button used when monitoring temperature and errors etc. Which are not currently displayed.
Icon
Before use
13

Quick Reference

15
16
17
18
19
20
21
22
23
24
25
26 27
28 29
30
31
Air Conditioner Operation
To collectively start / stop the operation of all devices connected to the intelligent Touch Controller
To start / stop the operation of devices by zone
To start / stop the operation of devices by group
To change the operation mode
To change the temperature setting
To change the direction or fan speed
To change the range of operation allowed with remote control
To change the ventilation mode
To change the ventilation volume
To permit / prohibit the remote control at hand for ventilation
Air Conditioner Operation Monitoring
To monitor by zone or by group
To monitor detailed information
To monitor the operation condition for ventilation
To set / release the lock of screen operation
To reset the filter or element sign
See page
See page
See page
See page
See page
See page
See page
See page
See page
See pages to
See pages to
See page
See page
See page
See page
14
33
33
35 36
37 41
42 44
45 46
55
55
34
34
34
34
92
47
50 54
49
See pages to
System Setup Menu
To change the name of a group
To change the zone setup
To change the schedule setup
To calibrate the touch panel
To adjust the contrast of the screen
To set the e-mail
To review the history of errors
To set the locale
To set the icon color
To set the network
To set the license key
To change the change over settings
To change the temperature limit settings
To change the heating optimization settings
See page
See page
See pages to
See pages to
See pages to
See pages to
See pages to
See page
See page
See page
See page
See page
See page
See page
To xxxx
Operation
15

Air Conditioner Operation

Starting / Stopping Operation Collectively
1 2
3
Screen 1 Monitoring
Screen 2 Confirm
To start / stop the operation of all devices connected
1.
2.
Screen 2 Confirm appears. Press the [OK] button e.
To exit without activating collective start or stop, press the [Cancel] button.
Start or stop collectively the operation of devices connected.
On the Monitoring screen, operation is allowed with either Zone or Group as the display mode and with either Icon or List as the display type. In the example on the left, the display mode is Group in the collective mode and the display type is Icon.
On Screen 1 Monitoring, press the [Start All] button q or [Stop All] button w .
[Procedure]
16
Screen 1 Monitoring
To start / stop the operation of devices by group
1.
On Screen 1 Monitoring, select a zone from the button q.
Start or stop the operation of air conditioners by group.
The example on the left shows the screen for starting / stopping the operation of Group Name : 1F North registered for Zone Name : Canteen.
2.
Select a zone that includes the group of which the operation is to be started or stopped w.
3.
4.
Select a group to be started or stopped as in e and press the [Start] button r or [Stop] button t.
Starting / Stopping Operation by the Group
Screen 2 Monitoring (Group)
1
2
3
4
5
Select a group from the button q. Screen 2 Monitoring (Group) appears.
Zone Name
Canteen
1F North
1F West
1F South
1F East
2F North
2F West
2F South
2F East
3F North
Air conditioner group to be started or stopped
[Procedure]
Operation
17
Collective Zone
Zone Name
Office
Canteen
Meeting
1F
2F
3F
Air conditioner group to be started or stopped
Screen 1 Monitoring
To start / stop the operation of devices by group
1.
On Screen 1 Monitoring, select a zone from the button q.
2.
Starting / Stopping Operation by the Zone
1
3
4
2
Select the zone of which the operation is to be started / stopped as shown in w.
3.
Press the [Start] button e or [Stop] button r.
Start or stop by zone the operation of groups of air conditioners set in zones.
The example on the left shows a screen for starting or stopping the operation of air conditioners in the canteen.
[Procedure]
18
Screen 1 Monitoring
1.
On Screen 1 Monitoring, select a zone or a group from the button q.
Switch the operation mode of the air conditioner.
On the Monitoring screen, operation is allowed with either Icon or List as the display type.
The operation mode can be switched by zone or by group.
Selecting a zone and switching the operation mode switches the mode of all air conditioners in the zone. Selecting a group and switching the operation mode switches the mode of air conditioners in the group selected.
Ex.: For the following zone setting, the
operation modes available are Fan, Cool, Heat and Auto. If Cool/Heat option is not available for any air conditioner in the zone, Fan and Set Point are the available operation modes.
2.
Select with w a zone or a group of which the operation mode is to be switched.
3.
Press the [Set] button e. Screen 2 Operation appears.
4.
Select the operation mode to be set from the pull down menu r.
5.
Switching the Operation Mode
Screen 2 Operation
3
2
5
1
4
To cancel the setting, press the Cancel button.
On the menu, operation modes available for air conditioners in the zone are displayed if the switching is to be made by zone. See the example below.
Press the [OK] button t.
Zone name Group name
Operation modes available
Canteen
1F North Cool Air
Cool Heat Auto Air
1F West
[Procedure]
Operation
19
Screen 1 Monitoring
1.
On Screen 1 Monitoring, select a zone or a group from the button q.
Change the temperature setting of air conditioners.
On the Monitoring screen, operation is allowed with either Icon or List as the display type.
The temperature setting can be switched by zone or by group.
Selecting a zone and changing the temperature setting changes the setting of the air conditioner groups in Cool, Heat, Auto or Temp operation in the zone.
Selecting a group and changing the temperature setting changes the temperature setting of air conditioners in the group selected.
If all of the air conditioners in the group selected are in Fan operation, temperature setting cannot be changed.
2.
Select a zone or a group of which the temperature setting is to be changed w.
3.
Press the [Set] button e. Screen 2 Operation appears.
4.
For temperature setting, press the [Modify] button r. Set Temperature dialog is displayed and input temperature for setting.
Ex.: For the following zone setting, the
temperature settings available are between 20°C and 30°C inclusive.
When the temperature setting is 30°C, the actual temperature settings for air conditioners are as shown below:
Note: Range of temperature settings available is
the range specified in accordance with the following.
¡
Range of temperature setting inherent to
the air conditioner main unit.
¡
Range of temperature as a result of the
restriction by the temperature setting limit.
5.
Changing the Temperature Setting
Screen 2 Operation
1
3
2
4
5
To cancel the setting, press the [Cancel] button.
On the menu, temperature settings available for air conditioners in the zone are displayed if the setting is to be made by the zone. See the example below.
Press the [OK] button
t
.
Zone name Group name
Range of temperature settings available (see Note)
Group name
Temperature setting
Canteen
1F North 25 to 30
°C
20 to 25
°C
1F West
1F North 30
°C
25
°C
1F West
[Procedure]
See page
60
20
Screen 1 Monitoring
1.
On Screen 1 Monitoring, select a zone or a group from the button q.
Reset the filter or element sign after cleaning any air conditioner showing the filter or element sign.
On the Monitoring screen, operation is allowed with either Icon or List as the display type.
The filter or element sign can be reset by zone or by group.
2.
Select a zone or a group of which the filter or element sign is to be reset w.
3.
Press the [Set] button e. Screen 2 Operation appears.
4.
Press the [Advanced Operation] button
r.
Screen 3 Advance
Operation
appears.
5.
To reset the filter / element sign, select "Filter Sign Reset" in pull-down menu
t.
Then press the [OK] button y.
To cancel the setting, press the [
Cancel] button.
Screen 2 Operation reappears.
Resetting the Filter / Element Sign
Screen 2 Operation
6.
1
2
3
4
5
7
6
Screen 3 Advanced Operation
To cancel the setting, press the [
Cancel] button.
Then press the
[OK]
button u on Screen
2 Operation.
[Procedure]
Operation
21
Screen 1 Monitoring
1.
On Screen 1 Monitoring, select a zone or a group from the button q.
Change the fan direction or volume of air conditioners.
On the Monitoring screen, operation is allowed with either Icon or List as the display type.
The fan direction or volume can be changed by zone or by group.
2.
Select a zone or a group of which the fan direction or volume is to be reset w.
3.
4.
Press the [Advanced Operation] button r
.
Screen 3 Advance
Operation
appears.
Select between High and Low with the pull­down menu t.
To cancel the setting, press the [Cancel] button.
Screen 2 Operation reappears.
5.
Changing the Direction / Fan Speed
Screen 2 Operation
6.
To cancel the setting, press the [Cancel] button.
1
2
3
4
5
6
8
7
Screen 3 Advanced Operation
The larger the value for wind direction setting (0 - 6), the closer to vertical the direction becomes. The value 7 indicates automatic swing. (Note: See the figure below.) The description given above may not exactly apply depending on the model. Check the wind direction sign on the remote control after operation.
Set the direction with the pull-down menu y.
Then press the [OK] button u.
Then press the
[OK]
button i on Screen
2 Operation.
Note: Guidelines for wind direction value and
actual direction
0
4
5
6 7: Wind direction auto
swing
Indoor unit
[Procedure]
Press the [Set] button e. Screen 2 Operation appears.
22
Screen 1 Monitoring
1.
On Screen 1 Monitoring, select a zone or a group from button q.
Change the setting of operation with the remote control of air conditioners between Permitted and Prohibited.
On the Monitoring screen, operation is allowed with either Icon or List as the display type.
The setting between Permitted and Prohibited can be changed by zone or by group.
2.
Select with w a zone or a group for which the setting of the range of operation allowed with remote control is to be reset.
3.
4.
Press the [Advanced Operation] button
r.
Screen 3 Advance
Operation
appears.
5.
Then make setting with the pull-down menus t - u. There are three settings as shown below:
tStart/Stop
Prohibited” “Stop Only” “Permitted” “No change
yOperation Mode
Permitted or Prohibited” “No change
uSet Point
Permitted or Prohibited No change
Changing the Range of Operation Allowed with Remote Control
Screen 2 Operation
6.
1
3
2
4
9
8
Screen 3 Advanced Operation
5
6
7
To cancel the setting, press the [Cancel] button.
Screen 2 Operation reappears.
To cancel the setting, press the [Cancel] button.
Press the [OK] button i after setting t - u.
Then press the [OK] button o on Screen 2 Operation.
Item Setting Meaning
Start/Stop
Prohibited
The remote control cannot start or stop operation.
The remote control can start or stop operation.
The remote control can change the operation mode.
The remote control cannot change the operation mode.
The remote control can change the temperature setting.
The remote control cannot change the temperature setting.
The remote control can stop the operation of air conditioners in operation but cannot start air conditioners not in operation.
Stop Only
Permitted
Permitted
Prohibited
Permitted
Prohibited
Operation
Mode
Set Point
[Procedure]
[Details of Setting]
Press the [Set] button e. Screen 2 Operation appears.
Operation
23
Screen 1 Monitoring (Icon)
Screen 2 Set
1
4
5
3
2
1.
On Monitoring Screen Screen 1, select a zone or group by pushing the button q
.
Perform the following procedure to switch the ventilation mode.
For this operation, you can select any of three display types, icon, detailed icon and list on the monitoring screen
When changing the ventilation modes of all the ventilation groups of a zone, select the zone and switch the ventilation mode.
When changing the ventilation mode of a group, select the group and switch the ventilation mode.
∗ Note that some models of ventilation
systems permit you to make the above settings but the others dont.
2.
To select a zone or group subject to ventilation mode switching, push the icon w.
3.
4.
Select a desired ventilation mode on the pull-down menu r.
5.
Last, press [OK] button t.
To cancel above settings, press [Cancel] button.
[Procedure]
Push [Set] button e to display Set Screen Screen 2.
Set Ventilation Mode
24
Screen 1 Monitoring
Screen 2 Set
Set Ventilation Volume
1
4
5
3
2
1.
On the Monitoring Screen Screen 1, select a zone or group by pushing the button q.
Note that some models of ventilation
systems permit you to make the above settings but the others dont.
2.
To select a zone or group subject to ventilation volume switching, push the icon w.
3.
4.
Select a desired ventilation volume on the pull-down menu r.
5.
Lastly, push [OK] button t.
To cancel above settings, press [Cancel] button.
[Procedure]
Push [Set] button e to display the Set Screen Screen 2.
Perform the following procedure to change the ventilation volume.
For this operation, you can select any of three display types, icon, detailed icon and list on the monitoring screen.
When changing the ventilation volumes of all the ventilation groups of a zone, select the zone and switch the ventilation volume.
When changing the ventilation volume of a group, select the group and switch the ventilation volume.
Operation
25
Screen 1 Monitoring
Screen 2 Set
Screen 3 Advanced Operatioon
Permit / Inhibit setting of Ventilation Remote Control Operations
1
4
7
5
6
3
2
1.
On the Monitoring Screen Screen 1, select a zone or group by pushing the button q.
Perform the following procedure to enable or disable the ventilation remote control operations.
For this operation, you can select any of three display types, icon, detailed icon and list on the Monitoring Screen.
You may enable or disable the remote control operations in units of zones or groups.
Note that some models of ventilation
systems permit you to make the above settings but some models dont.
2.
To select a zone or group subject to ventilation volume switching, push the icon
w.
3.
4.
Push [Advanced Operation] button r to display the Advanced Operation Screen Screen 3.
5.
Make a desired setting on the pull-down menu t. You can enable or disable the following setup items for remote control:
Disabling remote control operations Enabling only stop operation Assigning priority to button pushed later
After making the setting, push [OK] button y to display the Set Screen Screen 2 again.
To cancel above settings, push [Cancel] button.
[Procedure]
Push [Set] button e to display the Set Screen Screen 2.
6.
Lastly, push [OK] button u on the Set Screen.
To cancel above settings, push [Cancel] button.
26
Screen 1 Monitoring (Icon Display)
Screen 2 Monitoring
(Detailed Icon Display)
Screen 3 Monitoring (List Display)
Monitor Zone or Group Operation Status
12
12
3
3
4
3
6
8
9
4
5
6
8
8
9
7
5
12
5
6

Monitoring Operation of Air Conditioner

To monitor the operation status, the monitoring screen permits you to choose any of three display types, icon, detailed icon or list. Push the button w to select a display type.
Display type selection takes place repeatedly in the order of icon, detailed icon and list.
At e displays information concerning a zone or group, including the operation active or inactive status and the presence / absence of faults, automatic control settings, filters and element signs, etc.
Push the button r to change a display scope.
When the number of registered zones or groups is small and all the zones or groups can be displayed within one screen, this button does not appear. See Screen 3.
Display of t indicates a legend. When requiring a more detailed legend, display the Legend Description Screen Screen 4 on the next page by pushing the [?] button y. To return to the previous screen, push Close button.
i displays the current zone or group. You may select another zone or group by pushing the screen.
On Screen 1, u displays the settings of the zone or group selected at i. (Icon display only) Display takes place in the following order:
¡Upper : Detailed name for a zone or group ¡Lower left : Setting temperature
For a zone, this also indicates the temperature set for the representative machine (Note).
¡
Lower right : Operation mode For a zone, this also indicates the operation mode for the representative machine. (Note).
When an error occurs, the corresponding error code is indicated in the lower area.
You may monitor the operation status in units of zones or groups. Examples of display types are shown in left figures.
Screen 1 Display type : Icon
Unit of monitoring : Group
Screen 2 Display type : Detailed icon
Unit of monitoring : Group
Screen 3 Display type : List
Unit of monitoring : Zone
[Descriptions of Display Items on the Screen]
Monitor Zone or Group Operation Status
9
Operation
27
Screen 4 Legend Description
Monitor Zone or Group Operation Status
10
11
12
At o, you can monitor at a glance the operation status of all air-conditioners connected to the Intelligent Touch Controller.
When no problem is found and one or more air­conditioners are operating : Display in red When no problem is found and air-conditioners are not operating : Display in green When one or more wrong air-conditioners are found : Display in yellow When one or more air-conditions with communication errors are found : Display in blue
You may change the colors indicating the operation active or inactive status through the use of Icon Color Setting on the System Setting menu. (See page 34 for Icon color setting.)
(Note) Representative zone When monitoring takes place in units of groups on the Monitoring Screen, the following groups indicate the zone representative machines.
¡
When the display type is icon : Leftmost group on the top line
¡
When the display type is detailed icon or list: Groups on the top line.
!0 displays the operation status of an air­conditioner. For zone list display, display takes place as shown below.
¡
When no problem is found and one or more air­conditioners are operating : Display in red
¡When no problem is found and no air-
conditioner is operating : Display in green
¡When one or more wrong air-conditioners
are found : Display in yellow
¡When one or more air-conditions with
communication errors are found : Display in blue
You may change the colors indicating the operation active or inactive status through the use of Icon Color Setting on the System Setting menu. (See P34 for Icon color setting.)
!1
provides for icon or detailed icon display.
!2
provides for list display.
Machines subject to automatic control are displayed only when schedule settings are made. They cannot be displayed when Heating Mode Optimization or Temperature Limit has been set.
28
Screen 1 Monitoring (Icon Display)
Screen 2 Operation Screen
Screen 3 Advanced Operation Screen
Monitoring Detailed Information
1
2
3
4
10
11
12
15
5
13
14
16
6
7
8
9
Monitor Operation Status of a Zone or Group in Detail
When monitoring the operation status in detail, you may choose any of three display types, icon, detailed icon and list.
You may monitor the details of the operation status in units of zones or groups.
1.
Select either Zone or Group by pushing the button q.
Note that screens in the left-hand column are examples for group selection.
2.
Push [Set] button w to display the Operation Screen Screen 2.
When a zone is selected in the above operation, both r to y on Screen 2 and !0 to !4 on Screen 3 show the operation status of the representative machine in that zone. !55 displays ON so long as at least one of the filter signs or element signs is on in the zone or group.
The following describes in order the contents of display data on Screen 2. The grayed characters in r to y indicate the current status of the selected zone or group. The meanings of screen data in the left­hand column are shown below. Operation/stop status : Start Operation mode setting status: Cool Temperature setting status : 20.0°C
3.
Push [Advanced Operation] button u to display the Advanced Operation Screen Screen 3. To return to the Monitoring Screen Screen 1, push [Cancel] button o.
4.
Check the settings and push [Cancel] button !6
.
!0 displays the settings made for start and
stop remote control operations. Prohibited, Stop Only or Permitted is displayed.
!1
displays the settings made for remote control operations to change the operation mode. Either Permitted or Prohibited is displayed.
!2 displays the settings for remote control
operations to change the setting temperature. Either Permitted or Prohibited is displayed.
!3 displays the settings for remote control
operations to change the setting temperature. E
ither Permitted or Prohibited is displayed.
!4 displays the direction of wind.
A value from 1 to 7 is displayed. Wind flows more vertically as the setting value becomes larger in a range from 0 to
6. When the setting value 7 is displayed, the direction of wind is swung automatically. Note that these descriptions may vary from model to model. Check for a wind direction displayed on the remote control.
!5 displays a filter sign.
Either ON and OFF is displayed.
The following describes in order the contents of display data on the Advanced Operation Screen Screen 3.
Display data on Screens 2 and 3 is updated each
time the respective screens are displayed. Once these screens are displayed, no data is updated unless they are closed and opened again.
Operation
29
Screen 4 Monitoring Screen (Icon Display)
Screen 5 Detailed Information Screen
Screen 6 Fault History
17
Monitoring Detailed Information
18
19
20
Name : Group name Detailed name : Detailed group name Type :
Air-conditioner / ventilation / D3Dio / D3Di
D3 Address : 1:1-00 to 1:4-15
When DIII-NET Plus adapter is enabled: 1:1-00 to 2:4-15
Schedule Setup : Enabled or disabled Heating Optimization : Enabled or disabled Temperature Limit : Enabled or disabled Change Over Settings
: Enabled or disabled SIv R / C : Parent or child Cool / Heat Option
:
Presence / Absence / Under Selection Ou / Unit Addr : Outside unit address Err Code : 2-digit error code in case of error occurence Err Unit No
: [–]
for no error or unit number for error
5.
Push [Prop] button !7. The following maintenance data is
displayed on the Detailed Information Screen Screen 5.
Note that screens in the left-hand column are examples for group selection.
6.
Push [Abnormal history] button !8 to display the
Abnormal
History Screen (Screen
6).
[For group selection]
Name : Zone name Detailed name : Detailed zone name Start1By1 : Enabled or disabled Nb of Regist Grp : Number of groups registered in a zone Schedule Setup : Enabled or disabled
Name : group name Detailed name : Detailed group name Error log :
¡Time : Error occurrence time ¡Err Code : 2-digit error code ¡Err Code No : Unit number
The following data is displayed on the Abnormal History.
[For zone selection]
[For group selection]
Name : group name Error log :
¡Time : Error occurrence time ¡Name : Error occurrence group name ¡Err Code : 2-digit error code ¡Err Code No : Unit number
Top 10 error logs are displayed, assigning the highest priority to the time of the latest error. When the same error recurs, the error time
is renewed.
Check for display data and push [Close] button @0 to return to the detailed information screen Screen 5. To return to the Monitoring Screen Screen 4, push [Close] button !9 on that screen.
[For zone selection]
Loading...
+ 68 hidden pages