Daikin DCS601B51 User Manual

Operation Manual
Use smart and save smart
Thank you for purchasing intelligent Touch Controller.
This operation manual contains notes for safe use of the
product.
For correct use, be sure to read this manual carefully before use.
Model
DCS601B51
intelligent Touch Controller
We use recycled paper for making this operation manual.
Maintenance
Precautions 56 Maintenance
LCD Maintenance 57 When Leaving the Product Turned OFF for a Long Time
57
Troubleshooting 58
Maintenance
For Your Information
Before useOperation
Before use
Safety Instructions
Be sure to follow the instructions below 1
System Overview 3 Features and Functions 4 Part Names and Functions 5 Part Names on the Monitoring Screen and the Functions
List 9
Icon 11
Operation
Operation Quick Reference
13
Air Conditioner Operation 14 Monitoring the Operation of Air Conditioner
22
System Setup Menu
25
For Your Information
Error Diagnostic Functions 65 Options 67 Double intelligent Touch Controllers
67
Specification 68 After-sales Service 69
1
Instructions given here are classified into the following two categories. Instructions in both categories are important for safety and must be duly followed.
Caution
Warning
Failure to follow the instruction may lead to serious consequences including death or serious injury.
Failure to follow the instruction may cause injury or material damage, which, in some cases, leads to serious consequences.
When you have read this manual, be sure to store it in a place where the operator can conveniently refer to at
anytime.
In case of personnel change, be sure to give the manual to the new operator.
The symbol given in the manual shows the following:
Do not attempt to do things described in the instruction.
Be sure to follow the instruction.
Be sure to follow the instructions below
Safety Instructions
Read the manual carefully in advance for correct use
Warning Notes on use for users
When any abnormality (such as burnt smell) is
generated, turn the power OFF and contact the dealer you purchased the product from.
Continuing to operate with the abnormality left unattended may cause failure, electric shock or fire.
For remodelling or repair, contact the dealer
you purchased the product from.
Failure to remodel or repair properly may cause water leak, electric shock or fire.
For transferring or reinstallation, contact the
dealer you purchased the product from.
Failure to install properly may cause water leak, electric shock or fire.
Do not touch the inside of the controller.
Do not remove the front panel. Touching the inside is dangerous and may cause failure. For inspection and adjustment of the inside of the controller, contact the dealer you purchased the product from.
2
Caution Notes on use for users
Do not install in a place subject to flammable
gas.
Leakage of gas resulting in accumulation around the unit may lead to ignition.
Do not install in a place subject
to direct sunlight.
Failure to follow the instruction may lead to discoloring of the LCD that hinders proper display.
Be sure to provide grounding.
Do not connect the grounding wire to any gas pipe, water pipe, lightning rod or telephone grounding. Inappropriate grounding may lead to electric shock.
Do not install the controller in a place subject
to water.
Water in the device may lead to electrical leak and failure in the electronic components inside.
Do not wipe the surface of the controller touch
panel with benzine, thinner or chemically­treated dust cloth.
Failure to follow the instruction may lead to discoloring or peeling of the paint. Any soiling must be wiped off with a piece of cloth soaked in a diluted neutral detergent and wrung sufficiently. Wipe again with a dry piece of cloth.
To clean, be sure to stop operation and turn the
power OFF.
Failure to follow the instruction may lead to electric shock or injury.
Washing may lead to electric shock.
Be sure to operate with the touch pen provided.
Failure to follow the instruction may lead to damage or failure.
Do not wash the controller
with water.
benzine
thinner
Before use
3
System Overview
This intelligent Touch Controller is capable of controlling/monitoring up to 64 groups of indoor units (hereafter “groups”).
The main functions of the intelligent Touch Controller include:
1. Collective starting/stopping of operation of the indoor units connected to the
intelligent
Touch Controller.
2. Starting/stopping of operation, temperature setting, switching between temperature control modes and enabling/disabling of operation with the hand-held remote control by zone or group .
3. Scheduling by zone or group .
4. Monitoring of the operation status by zone or group .
5. Display of the air conditioner operation history.
6. Compulsory contact stop input from the central monitoring panel (non-voltage, normally-open contact).
7. Power distribution of the air conditioners. (With the optional DCS002A51)
A group of indoor units include:
Zone control with the intelligent Touch Controller Zone control, which allows collective settings for more than one group, is available with the intelligent Touch
Controller, which facilitates the setting operations.
q One indoor unit without a remote control.
e Up to 16 indoor units controlled with one or two remote controls.
One setting makes the same setting for all of the units in one zone.
Up to 128 zones can be set with one intelligent Touch Controller.
(The maximum number of groups in one zone is 64.)
Groups can be zoned at will with the intelligent Touch Controller.
Units in one group can be divided into more than one zone.
w One indoor unit controlled with one or two remote controls.
intelligent Touch Controller
Zone 1
Up to 16 units Up to 16 unitsTwo remote controlsRemote control
No remote control
Remote control Remote control
or
Indoor unit
Zone 5
Zone 2 Zone 3 Zone 4
4
Features and Functions
Operation Menu
intelligent
Touch Controller is capable of starting/stopping of the operation by the
group or zone. Collective starting/stopping is also available.
Air Conditioner Detail Setup
Temperature setting, switching between temperature control modes, switching of speed and direction of wind and remote control mode setting are available by the group, by the zone or collectively.
Monitoring of Various Information on Indoor Units
Information on operation such as the operation mode and temperature setting of the indoor units, maintenance information including the filter or element cleaning sign, troubleshooting information such as error codes can be displayed by the group or the zone.
Zone Control Simplifying Complicated Setting Operations
Up to 64 groups can be controlled with the intelligent Touch Controller. More than one group can be consolidated into a zone, which can be registered, to allow the following settings by the zone. This eliminates the need for repeating the same setting operation for each group. Function to allow collective setting for all groups is also available.
Detailed Scheduled Operation Control
The intelligent Touch Controller allows detailed scheduled operation by the group, by the zone or collectively. Up to 8 options for annual schedule can be set. Each schedule can include four types of plans: for Weekdays, Holidays, Special days 1 and Special days 2. Each of the plans allows setting of up to 16 operations.
Diversified Operation Modes
Operation can be controlled both with the main unit and the remote control to provide diversified operation management. Setting with the main unit allows the following remote control settings by the group, by the zone or collectively:
1. Start/Stop 2. Operation Mode 3.Temperature Setting
:(Remote control) Inhibited
:(Remote control) Inhibited
:(Remote control) Inhibited
:(Remote control) Permitted
:(Remote control) Permitted :(Remote control) Permitted
:Priority
Start/stop
Temperature setting
Switching between operation modes
Setting of direction and fan speed
Disabling/enabling the remote control
See pages
14 16
to
See pages
17 21
to
See pages
22 24
to
See page
21
See pages
14 24
to
26
See pages
27 28
to
See pages
29 38
to
Handy Automated Control
The Intelligent Touch Controller can do the following.
Change Over Settings: automatically switches between cooling and heating
according to the room temperature.
Temperature Limit Settings: prevents the temperature from rising too high or too
low in unmanned rooms.
Heating Optimization Settings: stops uncomfortable hot air from blowing when
the heating thermo is off.
Before use
5
Be sure to use the touch pen for operation of the touch panel of the intelligent Touch Controller. Operating with an object other than the touch pen provided may cause damage and failure.
Note
Part Names and Functions
Color LCD with Touch Panel
Provides a display for monitoring and operation. Be sure to use the touch pen provided for operation.
The display shows the Monitoring and System Setup screens.
PCMCIA Card Slot
Used when using the optional power distribution (DCS002A51) or updating the intelligent Touch Controller software to a newer version.
6
Maintenance Door
Generally not used. Close the door for general use. Use the door when adjusting the contrast of the LCD or luminance of the backlight.
Touch Pen
Use the touch pen for operation. Be sure to use the touch pen for operation. Use caution not to lose the touch pen.
When the pen is lost, contact the dealer you purchased the product from.
Before use
7
Terminals on the Back of intelligent Touch Controller
Use these ports for modem communication when using the AIRNET Service.
Connect the collective remote control adapter to this connector for collective start of operation,
collective stop of operation or error monitoring remotely with a
contact signal.
This port is not used with this model.
Connect a non-voltage contact for collective stopping of operation with a contact signal.
232C-1 232C-2
CN2
Ethernet LON
L2 L1
COM Dil Pi3 COM Pi2 Pi1 F2 F1
8
Connect a watt-hour meter when using the optional power distribution function software (DCS002A51).
Terminals for communication with air conditioning system.
Terminal for the grounding wire.
Terminals for the power supply. Connect single-phase power of 100 to 240 VAC, 50/60 Hz.
232C-1 232C-2
CN2
Ethernet LON
L2 L1
COM Dil Pi3 COM Pi2 Pi1 F2 F1
This port is not used with this model.
Before use
Contents of the List Currently Displayed
When Group List is displayed Zone: Zone Name
When Zone List is displayed Zone List
Display Mode Selection
Select between Zone and Group.
Zone/Group Name
Set the names in the Group Registration or Zone Registration in the System Setup Mode.
Filter/Element Sign
Displayed when there is any air conditioner showing a filter or element sign in the zone or the group.
Target of Automatic Control
Displayed when there is any air conditioner with the registration of scheduled or change over or temperature limit or heating mode optimization operation in the zone or in the group.
Monitoring Screen Legend
Pressing the ? button shows more detailed legend.
Button to Switch to the System Setup Mode
Use this button for settings including the time, group, zone and schedule.
Description of Zone/Group
Set the names in the Group Registration or Zone Registration in the System Setup Mode.
System Status Display Area
Area for displaying the system status (compulsory stop, etc.).
9
Part Names on the Monitoring Screen and the Functions
List
Information on Zone/Group Currently Displayed
Generally, the temperature setting and the operation mode are displayed. If any error occurs in the air conditioner, the error code is displayed.
Zone/Group Currently Displayed
The name of the zone/group currently selected is highlighted.
10
Scroll Bars
Use the bars to monitor any area of the group/zone list not currently shown.
Sliding the bars up/down and left/right changes the range monitored.
Display Type Selection
Select the type between Icon and List.
The example below shows the List Display. For Icon Display, see pages .
Display for Collective Monitoring of Air Conditioners Connected to intelligent Touch Controller
When operation is normal and any air conditioner is in operation:
Red/Normal When operation is normal and all air conditioners are in stoppage:
Green/Normal When there is any air conditioner generating an error:
Yellow/Abnormal When there is any air conditioner with communication error:
Blue/Abnormal
Start All Button
Button to collectively start all the air conditioners connected to intelligent Touch Controller.
Stop All Button
Button to collectively stop all the air conditioners connected to intelligent Touch Controller.
Group/Zone Start Button
Button to start operation of the group/zone selected.
Group/Zone Stop Button
Button to stop operation of the group/zone selected.
Group/Zone Set/Prop Button
Makes detailed settings (temperature setting, temperature control mode, etc.) and display of the group/zone selected.
Current Time Display
Shows the current date and time.
11,12
Before use
Contents of the List Currently Displayed
When Group List is displayed Zone: Zone Name
When Zone List is displayed Zone List
Display Mode Selection
Select between Zone and Group.
Information on Zone/Group Currently Displayed
Generally, the temperature setting and the operation mode are displayed. If any error occurs in the air conditioner, the error code is displayed.
Zone/Group Currently Displayed
The name of the zone/group currently selected is highlighted.
Zone/Group Name
Set the names in the Group Registration or Zone Registration in the System Setup Mode.
Filter/Element Sign
Displayed when there is any air conditioner showing a filter or element sign in the zone or the group.
Target of Automatic Control
Displayed when there is any air conditioner with the registration of scheduled or change over or temperature limit or heating mode optimization operation in the zone or in the group.
Monitoring Screen Legend
Pressing the ? button shows more detailed legend.
Button to Switch to the System Setup Mode
Use this button for settings including the time, group, zone and schedule.
Description of Zone/Group
Set the names in the Group Registration or Zone Registration in the System Setup Mode.
System Status Display Area
Area for displaying the system status (compulsory stop, etc.).
11
Icon
Scroll Bars
Use the bars to monitor any area of the group/zone list not currently shown.
Sliding the bars up/down and left/right changes the range monitored.
Display for Collective Monitoring of Air Conditioners Connected to intelligent Touch Controller
When operation is normal and any air conditioner is in operation:
Red/Normal When operation is normal and all air conditioners are in stoppage:
Green/Normal When there is any air conditioner generating an error:
Yellow/Abnormal When there is any air conditioner with communication error:
Blue/Abnormal
Start All Button
Button to collectively start all the air conditioners connected to intelligent Touch Controller.
Stop All Button
Button to collectively stop all the air conditioners connected to intelligent Touch Controller.
Group/Zone Start Button
Button to start operation of the group/zone selected.
Group/Zone Stop Button
Button to stop operation of the group/zone selected.
Group/Zone Set/Prop Button
Makes detailed settings (temperature setting, temperature control mode, etc.) and display of the group/zone selected.
Current Time Display
Shows the current date and time.
Display Type Selection
Select the type between Icon and List.
The example below shows the Icon Display. For List Display, see pages .
9, 10
12
Before use
13
Quick Reference
Air Conditioner Operation
To collectively start/stop the operation of all devices connected
to the intelligent Touch Controller
To start/stop the operation of devices by zone
To start/stop the operation of devices by group
To change the operation mode
To change the temperature setting
To change the direction or fan speed
To change the range of operation allowed with remote control
Air Conditioner Operation Monitoring
To monitor by zone or by group
To monitor detailed information
System Setup Menu
To change the name of a group
To change the zone setup
To change the schedule setup
To calibrate the touch panel
To adjust the contrast of the screen
To review the history of errors
See page
14
15
to
See page
16
See page
17
See page
18
See page
To reset the filter or element sign
19
See page
20
See page
21
See page
22
See page
26
See page
26
See page
39
See page
39
See page
64
See page
23 24
See pages
to
27 28
See pages
to
29 33
See pages
to
34 36
See pages
to
37 38
See pages
To change the change over settings
To change the temperature limit settings
To change the heating optimization settings
14
Air Conditioner Operation
Starting/Stopping Operation Collectively
1
2
3
Screen 1 Monitoring
Screen 2 Confirm
To start/stop the operation of all devices connected
1.
2.
Screen 2 Confirm appears. Press the OK e button.
To exit without activating collective start or stop, press the Cancel button.
Start or stop collectively the operation of devices connected.
On the Monitoring screen, operation is allowed with either Zone or Group as the display mode and with either Icon or List as the display type. In the example on the left, the display mode is Group in the collective mode and the display type is Icon.
On Screen 1 Monitoring, press the Start All q or Stop All w button.
[Procedure]
Operation
15
Screen 1 Monitoring
To start/stop the operation of devices by group
1.
On Screen 1 Monitoring, select a zone from the pull-down menu q.
Start or stop the operation of air conditioners by group.
The example on the left shows the screen for starting/stopping the operation of Group Name: 1F North registered for Zone Name: Canteen.
2.
Select a zone that includes the group of which the operation is to be started or stopped w.
3.
4.
Select a group to be started or stopped as in e and press the Start r or Stop t button.
Starting/Stopping Operation by the Group
Screen 2 Monitoring (Group)
1
2
3
4
5
Select a group from the pull-down menu q. Screen 2 Monitoring (Group) appears.
Zone Name
Canteen
1F North
1F West
1F South
1F East
2F North
2F West
2F South
2F East
3F North
Air conditioner group to be started or stopped
[Procedure]
16
Collective Zone
Zone Name
Office
Canteen
Meeting
1F
2F
3F
Air conditioner group to be started or stopped
Screen 1 Monitoring
To start/stop the operation of devices by group
1.
On Screen 1 Monitoring, select a zone from the pull-down menu q.
2.
Starting/Stopping Operation by the Zone
3
4
1
2
Select the zone of which the operation is to be started/stopped as shown in w.
3.
Press the Start e or Stop r button.
Start or stop by zone the operation of groups of air conditioners set in zones.
The example on the left shows a screen for starting or stopping the operation of air conditioners in the canteen.
[Procedure]
Operation
17
Screen 1 Monitoring
1.
On Screen 1 Monitoring, select a zone or a group from the pull-down menu q.
Switch the operation mode of the air conditioner.
On the Monitoring screen, operation is allowed with either Icon or List as the display type.
The operation mode can be switched by zone or by group.
Selecting a zone and switching the operation mode switches the mode of all air conditioners in the zone. Selecting a group and switching the operation mode switches the mode of air conditioners in the group selected.
Ex.: For the following zone setting, the
operation modes available are Fan, Cool, Heat and Auto. If Cool/Heat option is not available for any air conditioner in the zone, Fan and Set Point are the available operation modes.
2.
Select with w a zone or a group of which the operation mode is to be switched.
3.
Press the Set/Prop button e. Screen 2 Operation appears.
4.
Select Set for the Operation Mode r. Select the operation mode to be set from the pull down menu t.
5.
Switching the Operation Mode
Screen 2 Operation
3
4
5
6
2
1
To cancel the setting, press the Cancel button.
On the menu, operation modes available for air conditioners in the zone are displayed if the switching is to be made by zone. See the example below.
Press the OK button y.
Zone name Group name
Operation modes available
Canteen
1F North Cool Air
Cool Heat Auto Air
1F West
[Procedure]
18
Screen 1 Monitoring
1.
On Screen 1 Monitoring, select a zone or a group from the pull-down menu q.
Change the temperature setting of air conditioners.
On the Monitoring screen, operation is allowed with either Icon or List as the display type.
The temperature setting can be switched by zone or by group.
Selecting a zone and changing the temperature setting changes the setting of the air conditioner groups in Cool, Heat, Auto or Temp operation in the zone.
Selecting a group and changing the temperature setting changes the temperature setting of air conditioners in the group selected.
If all of the air conditioners in the group selected are in Fan operation, temperature setting cannot be changed.
2.
Select a zone or a group of which the temperature setting is to be changed w.
3.
Press the Set/Prop button e. Screen 2 Operation appears.
4.
Select Set for the Set Point r. Set the integer part of the setting in t and the decimal part in y.
Ex.: For the following zone setting, the
temperature settings available are between 20°C and 30°C inclusive.
When the temperature setting is 30°C, the actual temperature settings for air conditioners are as shown below:
Note: Range of temperature settings available is
the range specified in accordance with the following.
Range of temperature setting inherent to
the air conditioner main unit.
Range of temperature as a result of the
restriction by the temperature setting limit.
5.
Changing the Temperature Setting
Screen 2 Operation
1
2
3
4
5 6 7
To cancel the setting, press the Cancel button.
On the menu, temperature settings available for air conditioners in the zone are displayed if the setting is to be made by the zone. See the example below.
Press the OK button
u
.
Zone name Group name
Range of temperature settings available (see Note)
Group name
Temperature setting
Canteen
1F North 25 to 30
°C
20 to 25
°C
1F West
1F North 30
°C
25
°C
1F West
[Procedure]
See page
44
Operation
19
Screen 1 Monitoring
1.
On Screen 1 Monitoring, select a zone or a group from the pull-down menu q.
Reset the filter or element sign after cleaning any air conditioner showing the filter or element sign.
On the Monitoring screen, operation is allowed with either Icon or List as the display type.
The filter or element sign can be reset by zone or by group.
2.
Select a zone or a group of which the filter or element sign is to be reset w.
3.
Press the Set/Prop button e. Screen 2 Operation appears.
4.
Press the Advanced Func button r. Screen 3 Advance Function appears.
5.
To reset the filter sign, select Yes for Filter Sign Reset t. To reset the element sign, select Yes for Element Sign Reset y. Then press the OK button u.
To cancel the setting, press the Cancel button.
Screen 2 Operation reappears.
Resetting the Filter/Element Sign
Screen 2 Operation
6.
1
2
3
4
8
Screen 3 Advanced Operation
5
6
7
To cancel the setting, press the Cancel button.
Then press the OK button i on Screen 2 Operation.
[Procedure]
20
Screen 1 Monitoring
1.
On Screen 1 Monitoring, select a zone or a group from the pull-down menu q.
Change the fan direction or volume of air conditioners.
On the Monitoring screen, operation is allowed with either Icon or List as the display type.
The fan direction or volume can be changed by zone or by group.
2.
Select a zone or a group of which the fan direction or volume is to be reset w.
3.
4.
Press the Advanced Func button r. Screen 3 Advance Function appears.
To change the wind volume, select Set for Wind Volume u. Select between High and Low with the pull-down menu i.
To cancel the setting, press the Cancel button.
Screen 2 Operation reappears.
5.
Changing the Direction/Fan Speed
Screen 2 Operation
6.
To cancel the setting, press the Cancel button.
1
2
3
4
10
Screen 3 Advanced Operation
5
7
98
6
The larger the value for wind direction setting (0 - 6), the closer to vertical the direction becomes. The value 7 indicates automatic swing. (Note: See the figure below.) The description given above may not exactly apply depending on the model. Check the wind direction sign on the remote control after operation.
To change the fan direction, select Set for Wind Direction t. Set the direction with the pull-down menu y.
Then press the OK button o.
Then press the OK button !0 on Screen 2 Operation.
Note: Guidelines for wind direction value and
actual direction
0
4
5
6 7: Wind direction auto
swing
Indoor unit
[Procedure]
Press the Set/Prop button e. Screen 2 Operation appears.
Operation
21
Screen 1 Monitoring
1.
On Screen 1 Monitoring, select a zone or a group from the pull-down menu q.
Change the setting of operation with the remote control of air conditioners between Permitted and Prohibited.
On the Monitoring screen, operation is allowed with either Icon or List as the display type.
The setting between Permitted and Prohibited can be changed by zone or by group.
2.
Select with w a zone or a group for which the setting of the range of operation al­lowed with remote control is to be reset.
3.
4.
Press the Advanced Func button r. Screen 3 Advance Function appears.
5.
Press Set for R/C Mode t. Then make setting with the pull-down menus y - i. There are three settings as shown below:
yStart/Stop
Prohibited” “Stop Only” “Permitted
uOperation Mode
Permitted or Prohibited
iSet Point
Permitted or Prohibited
Changing the Range of Operation Allowed with Remote Control
Screen 2 Operation
6.
1
2
3
4
10
Screen 3 Advanced Operation
9
5
6
7
8
To cancel the setting, press the Cancel button.
Screen 2 Operation reappears.
To cancel the setting, press the Cancel button.
Press the OK button o after setting y - i.
Then press the OK button !0 on Screen 2 Operation.
Item Setting Meaning
Start/Stop
Prohibited
The remote control cannot start or stop operation.
The remote control can start or stop operation.
The remote control can change the operation mode.
The remote control cannot change the operation mode.
The remote control can change the temperature setting.
The remote control cannot change the temperature setting.
The remote control can stop the operation of air conditioners in operation but cannot start air conditioners not in operation.
Stop Only
Permitted
Permitted
Prohibited
Permitted
Prohibited
Operation
Mode
Set Point
[Procedure]
[Details of Setting]
Press the Set/Prop button e. Screen 2 Operation appears.
22
Monitoring the Operation of Air Conditioner
Screen 1 Monitoring (Icon)
The display type of the operation monitor can be selected between Icon and List. To select, use the pull-down menu
q
to choose
either Icon or List.
Monitoring can be selected between by Zone and by Group. To select, use the pull-down menu
w
to choose either Zone or Group. The example on the left shows the following:
For Screen 1, Display type: Icon; Monitoring by: Group For Screen 2, Display type: List; Monitoring by: Zone
[Display on the Screen]
Display area e allows monitoring the start/stop status of the zone or group, whether any error has occurred, whether automatic control is set and the status of the filter/element sign.
Moving the scroll bar
r
up and down changes
the area that can be viewed.
When the number of zones or groups registered is small enough to be covered by the area viewed at one time, no scroll bar is shown. (Ex.: Screen 2)
The display
t
shows a legend.
For more detailed legend, press the ? button
y
. Screen 3 Legend appears. To go back to the
previous view, press the Close button u.
The highlighted display
i
shows the zone or group currently selected. Touching the screen allows selecting another zone or group.
Display
o
shows the settings for the zone or group selected with i. The settings include the following (from left):
Zone or group name
Display
!
0 is an indicator for checking at a
glance the status of all air conditioners connected to the intelligent Touch Controller. Meanings of indications are as shown below:
When operation is normal and any air conditioner is in operation: Red When operation is normal and all air conditioners are in stoppage: Green When there is any air conditioner generating an error: Yellow When there is any air conditioner with communication error: Blue
Screen 2 Monitoring Screen (List)
Screen 3 Legend
To monitor by the zone or by group
To Monitor the Operation by the Zone or Group
Temperature setting
Operation mode
for a zone, the temperature setting of the representative unit is shown. (See Note)
for a zone, the operation mode of the representative unit is shown. (See Note)
3
2
4
5
9
5
9
7
10
3
6
6
1
1
10
8
8
2
(Note): Representative unit for a zone
One group shows a representative unit when monitoring is performed by the group on the Monitoring screen as described below:
Icon display: the leftmost group
shown in the top line
List display: the group shown in the
top line See page 46 for changing the representative unit for a zone.
See page
46
Operation
23
Detailed operation status can be monitored by zone or by group.
The contents of Display on Screen 2 are as shown below. Obscured indication for
r - y shows the current status
of the zone or group selected. The example on the left shows the following:
u includes the following as the maintenance information:
To monitor detailed information on one zone or group
The display on Screen 2 and Screen 3, which is on the following page, is updated when the screen appears. Once the screen is open, it is not undated before it is closed and opened again.
The display type for monitoring detailed operation status can be selected between Icon and List.
Monitoring Detailed Information
Screen 1 Monitoring (Icon)
Screen 2 Operation
[ Group ]
Name Description ID Type D3 Address Schedule Heating Optimization Heating Mode Optimization Temperature Limit Temperature Limit Ctrl Change Over Slv R/C Cool/Heat Option Ou/Unit Addr Err Type Err Code Err Unit No
Rm Temp
[ Zone ]
Name Description ID Start 1 by 1 Interval Registered Grp No Schedule Slv R/C Cool/Heat Option Ou/Unit Addr Err Type Err Code Err Unit No
Rm Temp
: Zone name : Zone description : 0 - 63 : Enabled/Disabled : Interval when Enabled is set for the above : The number of groups registered for a zone : Enabled/Disabled : Mst/Slv (*1) : With/Without (*2) : Address of the outdoor unit (*3) : Normal; Error code when any error is generated (*4) : 2-digit error code when any error is generated (*4) : 0 when there is no error Unit No. when error is generated (*4) : Inlet temperature of the representative group for a zone (*1)
: Group name : Group description : 0 - 63 : Air conditioner or device : Address between 1-00 and 4-15 : Enable/Disabled : Enabled/Disabled : Only displayed during control. : Enable/Disable : Only displayed during control. : Enable/Disable : Mst/Slv : With/Without : Address of the outdoor unit : Normal; Error code when any error is generated : 2-digit error code when any error is generated : 0 when there is no error
Unit No. when error is generated
: Inlet temperature of the indoor unit
On/Off Operation Mode Set Point
: Start : Cool : 24.0
°C
For detailed information on a zone, the indication (*1) is Mst when there is any master R/C is included for air conditioners in the zone and Slv when all of them are slave R/C. The indication (*2) is Enabled when any of the air conditioners in the zone has the Cool/Heat option and Disabled when none of them has the option. The indication (*3) shows information on the representative unit for a zone and the error-related indications (*4) show information on any air conditioner generating an error.
For monitoring further detailed information,
2
1
3
5
4
8
7
9
6
1.
Select Zone or Group from the pull-down menu w. (The example on the left shows Group selected.)
2.
Press the Set/Prop button e. Screen 2 Operation appears.
3.
Press the Advanced Func button i. Screen 3 Advanced Function appears as shown on the following page. To go back to Screen 1 Monitoring, press the Cancel button o.
When Zone is selected, r - y on Screen 2 and !2 - !6 on Screen 3 on the following page show the status of the representative unit for a zone. For
!0
and !1 on Screen 3, if any of the air conditioner of the group in the zone has the filter or element sign illuminated, Yes/No here is shown in black.
24
7:
Wind direction auto swing
Note: Guidelines for wind direction value and
actual direction
Screen 3 Advanced Operation
The contents of Display on Screen 3 Advanced Operation are as shown below.
!0Filter Sign Status
When Yes/No is shown in black, the filter sign is illuminated.
!2Shows the current wind direction.
Indicated with a figure between 0 and 7 inclusive.
The larger the value for wind direction setting (0 - 6), the closer to vertical the direction becomes. The value 7 indicates automatic swing. (Note: See below.) The description given above may not exactly apply depending on the model. Check the wind direction sign on the remote control after operation.
!1Element Sign Status
When Yes/No is shown in black, the element sign is illuminated. (The example on the left shows the filter sign illuminated.)
!3Shows the current wind volume.
Low or High is shown.
!4Shows the remote control setting for starting or
stopping operation. One of the following is shown:
Prohibited Stop Only Permitted
!5Shows the remote control setting for the
operation mode. One of the following is shown:
Prohibited Permitted
Screen 2 Operation on the previous page reappears. Pressing the Cancel button
o on that screen
brings you back to Screen 1 Monitoring.
This screen is for both operation and monitoring. When you have used the screen for monitoring only, press the Cancel button rather than the OK button to exit the window to prevent wrong operation.
Continued from the previous page
10
11
12
14
15
16
17
13
0
4
5
6
Caution
!6Shows the remote control setting for the
temperature setting. One of the following is shown:
Prohibited Permitted
4.
When all the settings have been confirmed, press the Cancel button !7.
Indoor unit
Operation
25
System Setup Menu
The System Setup menu includes the following items:
Operation
(Reference)
System Setup
Menu Item
Description
Setting a password allows restriction of access to the System Setup menu operation to specified personnel Note : If the set password is lost, access to all System Setup menu
operation is denied. Use caution not to lose the password. If it is lost, consult the dealer you purchased the product from.
Password Setup
Password Setup
Time Zone Setup
Time Setup
Backlight Setup
Group Setup
Zone Setup
Schedule Setup
Change Over Settings
Temperature Limit Settings
Heating Optimization Settings
Adjust the system clock (year, month, day, hour, minute and second). The clock is used for scheduled operation, saving history, power distribution (optional) and demand operation (optional).
Note : Adjusting the clock may affect scheduled operation, power distribution
or demand operation.
For the details of the influence, see the following. For power distribution and demand operation, see the respective instruction manual as well.
[Influence of changing the clock setting on scheduled operation]
The operation scheduled to run at a time passed by advancing the clock is
not performed.
Ex.: When an air conditioner is scheduled to start at 10:00 (q):
If the time is adjusted to 10:05 at 9:55, the scheduled operation (q) is not performed.
The operation scheduled to run at a time reached again by turning back
the clock is performed again.
Ex.: When an air conditioner is scheduled to start at 10:00 (q):
If the time is adjusted to 9:55 at 10:05, the scheduled operation (q) is performed again at 10:00.
Time Setup
It is necessary to set Time Zone of intelligent Touch Controller according to your service place. And when it is needed to set Daylight Saving Time, setting may be made by this menu.
Note : Setting Time Zone Setup may affect upon schedule operation, electric
proportional distribution, and demand operation.
As for concrete influences, refer to the following. And as for electric proportional distribution and demand operation, refer to their respective operation manuals.
Time goes ahead 60 minutes at the start of Daylight Saving Time, while time goes back 60 minutes at the completion. As for the influence, there are same influences as in the case time is made ahead and back in the following section Time Setup. Refer to the applicable description.
Time Zone Setup
The following table describes the items mentioned above.
See page
41
See page
43
See page
42
History Display
Touch Panel Calibration
Version Information
26
Operation (Reference)
System Setup
Menu Item
Description
A backlight is used for the LCD of the intelligent Touch Controller. The backlight has its service life and the luminance of the backlight is reduced in proportion to the period of time it is illuminated. This setting is for preventing the luminance from being reduced in a short time by automatically turning the backlight OFF when the touch panel has been left untouched for a set period of time.
If the backlight has been turned off automatically, touching the panel illuminates the backlight again.
Backlight setting includes the following two steps:
1.Set the time before the backlight is automatically turned OFF. Range: 1 - 60 minutes in increments of one minute.
2.Set whether the backlight should be automatically illuminated when any error is generated in the air conditioner while the backlight is turned OFF. Enable/Disable
Note: If this setting is not made, the backlight generally requires replacement every 3
- 4 years. The life of the backlight becomes even shorter if it is illuminated in a low temperature (10°C or lower) environment for a long time. When using the intelligent Touch Controller in a low temperature environment, it is recommended that a shorter time is set for 1. above and Disabled for 2.
Backlight Setup
Set the name, description, icons to be displayed and temperature setting limit (see Note) for the group. If this registration is not made, addresses for central management of the group is used for the Name and Description. Operation is not affected if these settings are not made.
Addresses for central management include up to 64 addresses 1-00, 1-01, ......
1-15, 2-00, ...... 4-15.
(Note): The temperature setting limit is a function to allow operation only within
the preset temperature limit to prevent too much cooling or heating. (The limit function above does not work when the operation mode of the air conditioners is Auto.)
Ex.: Temperature setting limit: 25 - 35°C cooling
If the temperature is set to 20°C with the remote control, the intelligent Touch Controller automatically changes the temperature setting to 25°C.
Group Setup
Set the name, description, icons to be displayed and sequential starting of the groups registered for a zone (see Note), and groups to be registered for the zone.
The zone includes Collective, for which all groups are registered in advance. This zone is made available for making the settings for all of the air conditioners connected to the intelligent Touch Controller. The name, description or registered groups cannot be changed for this Collective zone.
(Note): Setting sequential starting of groups registered for the zone
When multiple groups are registered for a zone and operation is performed by the zone, air conditioner outdoor units start operation at one time. If many outdoor units start at the same time, a large amount of current is used momentarily, which may trip the breaker when the power capacity of the receiving device is not enough. This setting is a function to prevent such phenomenon by starting air conditioners one by one.
(Memo 1): When power distribution (optional) is performed, the zone registered
here becomes the unit for distribution (tenant). Register the zone setting by the tenant.
(Memo 2): One group can be registered for more than one zone.
Zone Setup
See page
43
45 46
to
See page
44
See pages
Operation
27
Operation (Reference)
System Setup
Menu Item
Description
Menu for setting scheduled operation by zone or by group.
Scheduled operation is a function to automatically start or stop air conditioners at a certain time (year, month, day, day of week, hour, minute) preset for the intelligent Touch Controller in accordance with the operating status of air conditioners.
Schedule setting includes the following steps:
Each schedule can include four types of plans: for Weekday, Day off, Special 1 and
Special 2. Allocate the four types above to Weekly Setup and Calendar Setup as described below.
Weekly Setup: set general operation schedule.
(Ex.: setting for Day off for Saturdays and Sundays and setting for Weekday for days other than Saturdays and Sundays)
Calendar Setup: set days that do not fall within the range of Weekly Setup above. (Ex.: New Years holidays, etc.)
Make Patterns Setup for the four types of plans above: for Weekday, Day off,
Special 1 and Special 2. (Ex.: Start operation for Zone 1 at 9:00 and stop at 17:00, etc.)
Up to 8 settings as described above can be made.
Specific Example
1. [Floor Usage] 1F: Reception: 1F is registered as the zone name. 2F: Office: 2F is registered as the zone name. 3F: Canteen: 3F is registered as the zone name.
Schedule Setup
Setting can be made for up to 13 months in advance.
Each of the plans allows setting of up to 16 operations.
2.Make Weekly Setup in accordance with the usage for one week of the zone above.
Day off
Weekly Setup
Calendar Setup
Weekday
Special 1
Weekday
3.
Make Calendar Setup for special usage other than the weekly usage of the zone above.
47
See page
47
Day off
Day off
Special 2
See page
Zone name
Day of week
Sunday
Monday
Working hours: 8:30 - 17:00
1F
Tuesday
Wednesday
Thursday
Friday
Saturday
Set Saturday and Sunday as Day off and Tuesday to Friday as Weekday.
Set the third Saturday of each month as Weekday and April 30 - May 5, August 10 - August 15 and December 29 - January 4 as Day off, December 28 as Special 1 and January 5 as Special 2.
Apr. 30 -
May 5
Aug. 10 -
Aug. 15
Dec. 29 -
Jan. 4
10:00 - 14:00
9:00 - 12:00
Working hours: 10:00 - 15:00 Lunch break: 12:00 - 13:00
Day off Day off Day off
Day off9:00 - 12:00
10:00 - 15:00
Workday: regarded
as Weekday.
Working hours: 9:30 - 14:00
3F
Working hours: 9:30 - 18:00
Lunch break: 12:00 - 13:00
Overtime: 18:00 - 22:00
Closing: 22:00
Same as above Same as above Same as above Same as above
Day off
Same as above Same as above Same as above Same as above
Day off
2F
Day off Day offDay off
Same as above Same as above Same as above Same as above
Day off
Zone name
Day of week
1F 3F2F
Third Saturday of each month
Dec. 28
Jan. 5
Workday: regarded
as Weekday.
Workday: regarded
as Weekday.
28
Operation
(Reference)
System Setup
Menu Item
Description
Schedule Setup
4. [Make Pattern Setup for Weekday, Day off, Special 1 and Special 2.]
(Note): The patterns shown below are examples. Make settings in
accordance with the actual usage.
Pattern Setup for Weekday
Hour
8:30 9:00
9:30 12:00 13:00 14:00 17:00 18:00 22:00
Zone concerned
Zone 1F Zone 2F Zone 3F Zone 2F Zone 2F Zone 3F Zone 1F Zone 2F Zone 2F
Start/Stop
Start Start Start Stop Start Stop Stop
Disabled
Stop
Temperature setting
Disabled Disabled Disabled Disabled Disabled Disabled Disabled Disabled Disabled
Operation mode
Disabled Disabled Disabled Disabled Disabled Disabled Disabled Disabled Disabled
R/C mode Permitted Permitted Permitted
Disabled
Permitted Prohibited Prohibited Stop Only Prohibited
Hour
9:00
Zone concerned
Zone 1F
Start/Stop
Start
Temperature setting
25°C
Operation mode
Heat
R/C mode
Permitted
Prohibited Prohibited
Disabled Disabled
Disabled Disabled
Stop Stop
Pattern Setup for Day off
Disabled means no change.
Disabled means no change.
Disabled means no change.
Disabled means no change.
Hour
9:00
17:00
Zone concerned
Zone 2F Zone 2F
Start/Stop
Disabled
Stop
Temperature setting
Disabled Disabled
Operation mode
Disabled Disabled
R/C mode
Permitted Prohibited
Pattern Setup for Special 1
9:00
12:00 12:00
Zone 2F
Zone 1F Zone 2F
Start Heat 25°C
Permitted
R/C Set Point
Prohibited
Change Ope Mode Prohibited
Permitted
R/C Set Point
Prohibited
Change Ope Mode Prohibited
Permitted
R/C Set Point
Prohibited
Change Ope Mode Prohibited
Permitted
R/C Set Point
Prohibited
Change Ope Mode Prohibited
Hour
10:00
Zone concerned
Zone 1F
Start/Stop
Start
Temperature setting
25°C
Operation mode
Heat
R/C mode
Permitted
Prohibited Prohibited Prohibited
Disabled Disabled Disabled
Disabled Disabled Disabled
Stop Stop Stop
Pattern Setup for Special 2
10:00
14:00 15:00 15:00
Zone 2F
Zone 3F Zone 1F Zone 2F
DisabledDisabledDisabledStop12:00 Zone 2F
Start Heat 25°C
10:00 Zone 3F Start Heat 25°C
13:00 Zone 2F Start Heat 25°C
Set whether the set schedule is enabled or disabled.
See pages
48 50
to
Operation
29
Operation (Reference)
System Setup
Menu Item
Description
This function allows the optimal room temperature to be maintained without the users having to change the operation mode by automatically switching the air conditioners operation mode (cooling or heating) according to the room temperature for locations where the temperature difference during the day and at night is very large.
< Overview of Function >
This function automatically switches the air conditioners operation mode and set temperature in units of one (4) automatic cooling/heating switch group according to the following 3 parameters: (1) main set temperature, (2) main room temperature, and the difference between the set temperatures when in cooling and in heating operation (listed hereafter as (3) temperature difference).
[1]
Control Method (How to determine the (1) Main Set Temperature and (2) Main Room Temperature)
The 3 following methods exist for determining the above temperatures.
1.Fixed Air Conditioner Method
The first indoor unit (the one highest on the screen) among those registered in the automatic cooling/heating switch group is designated the main indoor unit and the set temperature and room temperature of that indoor unit are designated the main set temperature and main room temperature. Note, however that if the main indoor unit is in fan operation mode, its automatic cooling/heating switch group cannot be controlled.
2.Operating Air Conditioner Selection Method
Starting with the first indoor unit (the one highest on the screen) of those registered in the automatic cooling/heating switch group and working down, a search is performed to find an indoor unit which is both operating and in either cooling, heating, or automatic operation mode. The first one which satisfies both of these conditions is designated the main indoor unit and the set temperature and room temperature of that indoor unit are designated the main set temperature and main room temperature. If none is found which satisfies these conditions, the main set temperature and main room temperature are determined using the Fixed Air Conditioner Method shown above.
3.Average Method
All the indoor units which are registered in the automatic cooling/heating switch group, are operating, and are either in cooling, heating, or automatic mode are found, and the averages for their set temperatures and room temperatures are calculated and used as the main set temperature and main room temperature. (Decimals are rounded up.) Note, however, that if there no air conditioners among the registered air conditioners for the averages to be calculated, the main set temperature and main room temperature are determined using the Fixed Air Conditioner Method shown above.
[2] (3) Temperature Difference The temperature difference is the difference between the set temperatures when automatically switching between cooling and heating when using this control. The temperature difference is set to between 1°C and 7°C in 1°C units. (When shipped from the factory, the setting is 2°C.)
[3] (4) Automatic Cooling/Heating Switch Group
This control is performed using one automatic cooling/heating switch group as a unit.
Up to 64 indoor unit groups can be registered in one automatic cooling/heating switch group.
It is not possible to register the same indoor unit to multiple automatic cooling/heating switch groups.
Up to 8 automatic cooling/heating switch groups can be registered in this unit.
These controls can be enabled and disenabled for each individual automatic
cooling/heating switch group. (These controls only work for groups set as enabled.)
A mark indicating that the indoor unit is under automatic control will appear on the monitor screen.
Change Over Settings
30
Operation (Reference)
System Setup
Menu Item
Description
Change Over Settings
< Control Implementation Conditions >
The relationship between the main room temperature, the main set temperature, and the operation mode is described below, with examples. (Two examples are given, as the operation differs for temperature differences 2°C and below and 3°C and above.) The controls are implemented when the control conditions are satisfied, every 5 minutes from the time the power is turned on.
< Implementation conditions when the temperature difference is 2°C or lower.> (The figure below is for a temperature difference of 1°C)
Main heating set temperature
(Example:26
°C)
Temperature
Main cooling set temperature
(Example:27
°C)
Heating mode
Heating mode
Time
Shift up from heating to cooling switch set temperature
Shift down from cooling to heating switch set temperature.
Cooling mode
Main room temperature
Main heating set temperature – 1°C
Main cooling set temperature + 1°C
1
2
qConditions for switching from heating to cooling: Main room temperature > main set temperature + temperature difference + 1°C (Example:28.1°C > 26°C + 1°C + 1°C) wConditions for switching from cooling to heating: Main room temperature < main set temperature – temperature difference – 1°C (Example:24.9°C < 27°C – 1°C – 1°C)
qConditions for switching from heating to cooling: Main room temperature > main set temperature + temperature difference (Example:27.1°C > 24°C + 3°C) wConditions for switching from cooling to heating: Main room temperature < main set temperature - temperature difference (Example:23.9°C < 27°C – 3°C)
<Implementation conditions when the temperature difference is 3°C or higher.> (The figure below is for a temperature difference of 3°C)
Main heating set temperature
(Example:24
°C)
Temperature
Main cooling set temperature
(Example:27
°C)
Time
Shift up from heating to cooling switch set temperature
Shift down from cooling to heating switch set temperature.
Main room temperature
Temperature difference
1
2
See the next page for a detailed description of the instructions to the air conditioner.
Heating mode
Cooling mode
Heating mode
Temperature difference
Operation
31
Operation (Reference)
System Setup
Menu Item
Description
Change Over Settings
The control instruction is sent to the indoor units registered in the automatic cooling/heating switch group when the control implementation conditions shown on the previous page are satisfied. The actual control instructions sent differ according to the control method setting (fixed air conditioner/operating air conditioner selection/average) and the satisfied conditions (switch from cooling to heating, etc.). The control instructions for each situation are shown below.
<Instructions sent to indoor units when control is implemented>
1.Fixed air conditioner/operating air conditioner selection methods
The control instructions are determined by the operation mode of the main indoor unit and the main set temperature. Instructions regarding the operation mode and the set temperature, shown below, are sent to all the indoor units registered in the group once all the control implementation conditions on the previous page are satisfied.
For this control, when the operation mode of the main indoor unit is automatic, whether it is automatic cooling mode or automatic heating mode is checked when judging the control conditions. Once the instructions have been determined, either a cooling or a heating instruction is sent to indoor units in automatic operation mode. (They switch from automatic to cooling or heating.)
2. Average Method
Unlike the fixed air conditioner and operating air conditioner selection methods, the set temperature is decided based on considerations of the current set temperature for each individual unit, without sending the same instruction based on the main indoor unit to all the air conditioners. When implementing the control, the following operation modes and set temperature instructions are executed.
When conditions are met for switching from heating to cooling
Operation mode
Set temperature
Heating/Automatic heating
cooling
main unit setting temperature+temperature difference
Cooling/Automatic cooling
cooling
main unit setting temperature
When conditions are met for switching from cooling to heating
Operation mode
Set temperature
Cooling/Automatic cooling
heating
main unit setting temperature–temperature difference
Heating/Automatic heating
heating
main unit setting temperature
Operation mode of the main indoor unit
Operation mode of the main indoor unit
Instructions to indoor units registered in the automatic cooling/heating switch group
Instructions to indoor units registered in the automatic cooling/heating switch group
When conditions are met for switching from heating to cooling
Operation mode
Set temperature
Heating/Automatic heating
cooling
Current set temperature+temperature difference
Cooling/Automatic cooling
No instruction
No instruction
Other than the above
cooling
main unit setting temperature
+
temperature difference
When conditions are met for switching from cooling to heating
Operation mode
Set temperature
Cooling/Automatic cooling
heating
Current set temperature-temperature difference
Heating/Automatic heating
No instruction
No instruction
Other than the above
cooling
main unit setting temperature–
temperature difference
Current indoor unit operation mode
Instructions to indoor units registered in the automatic cooling/heating switch group
Instructions to indoor units registered in the automatic cooling/heating switch group
Current indoor unit operation mode
32
Operation (Reference)
System Setup
Menu Item
Description
Change Over Settings
<Precautions when using this control>
1.Do not use the set temperature restriction function in indoor units which are subject to control. If it is used, operation modes will be switched and the set temperature will be changed repeatedly, possibly causing the air conditioners to break down.
(See P44 for how to set the set temperature restriction function.)
2.The following will happen if a communication error (the icon on the screen is blue) occurs in the air conditioner being controlled. 2-1.Fixed air conditioner If the main unit experiences a communication error, the automatic cooling/heating switch group control will not happen. 2-2.Operating Air Conditioner Selection Method Remove the air conditioner experiencing the communication error from selection as the main unit, and select an air conditioner with normal communication. 2-3.Average Method Remove the air conditioner experiencing the communication error from the calculation for the average, and only use air conditioners with normal communication for calculating the average.
3.Control which matches the main units operation mode (Control for when the operation mode of the main unit does not represent the automatic cooling/heating switch group.) It is possible that only the operation mode for the main unit is changed when control using this function is done based on the main group unit (when the control method is fixed air conditioner or operating air conditioner). The following control is performed because it is possible that the operation mode of air conditioners other than the main unit in the group might be in violation of the purpose of control and not automatically switch if the conditions for implementing control using this function are not satisfied.
[Example] Heating Mode-Matched Control When the main unit is already operating in heating mode, whether or not the conditions for implementing a switch from cooling to heating (main room temperature < main set temperature – temperature difference) depends on the state (environment) of the main unit. (If only the main unit is in heating operation, it is possible that the room temperature might not rise because of the indoor units other than the main unit which are in cooling operation, and the above control conditions might not be satisfied.) Therefore, only when control is performed based on the main group unit is the control below performed depending on the operation mode of the main group unit.
Caution
Cooling Mode-Matched Control
Operation mode
Set temperature
Operation mode
Cooling/Automatic cooling
Temperature
Main room temperature>main set temperature
Heating Mode-Matched Control
Operation mode
Set temperature
Operation mode
Heating/Automatic heating
Temperature
Main room temperature<main set temperature
Instructions to indoor units registered in the automatic cooling/heating switch group
State of main unit (control conditions)
Heating main set temperature
Instructions to indoor units registered in the automatic cooling/heating switch group
State of main unit (control conditions)
Cooling main set temperature
Operation
33
Operation (Reference)
System Setup
Menu Item
Description
Change Over Settings
4.Because this control automatically switches the operation mode, if the air conditioner is not a cooling/heating free unit, always register indoor units which have the right to select cooling or heating for the same cooling system to the same automatic cooling/heating switch group, when controlling indoor units which do not have such rights.
Unexpected things may happen if control is done using the following incorrect automatic cooling/heating switch group settings.
If indoor units (address 1-02) which do not have the right to select cooling or heating for the same cooling system are not registered to the same automatic cooling/heating switch group, address 1-02 will behave in the following way.
[Actions related to operation mode] If the room temperature of Group 1 rises, group 1 will switch to cooling as per this control and the set temperature will become 25°C (if the temperature difference is 5°C). When this happens, the set temperature of the indoor unit at 1-02 will continue at 23°C although only the operation mode will change to cooling, i.e. in a different operation mode from the other indoor units in Group 2. The operation mode will be determined by Group 1.
[Actions regarding set temperature] If the room temperature of Group 2 rises, group 2 will switch to cooling as per this control and the set temperature will become 28°C (if the temperature difference is 5°C). When this happens, the operation mode of the indoor unit at 1-02 will continue in heating and only the set temperature will change to 28°C, i.e. in a different operation mode from the other indoor units in Group 2. The set temperature will be determined by Group 2.
Outdoor
unit
Outdoor
unit
Has right to select cooling or heating
Does not have right to select cooling or heating
Does not have right to select cooling or heating
Automatic cooling/heating switch group 1
Automatic cooling/heating switch group 2
1-00 1-01 1-02
1-03 1-04 1-05
Operation mode:Heating, set temperature 20°C
Operation mode:Heating, set temperature 23°C
Has right to select cooling or heating
Does not have right to select cooling or heating
Does not have right to select cooling or heating
34
Operation (Reference)
System Setup
Menu Item
Description
Temperature Limit Settings
This function automatically starts and stops air conditioners in order to prevent the room temperature of unmanned rooms from getting too high or too low. For example, This has the following advantages.
It prevents overheating of or condensation from forming on equipment which needs to be temperature controlled in unmanned rooms.
It can also help buildings and not just individual rooms to preserve heat by preventing unmanned rooms from reaching extremes of temperature at night.
<Overview of Function>
This function performs automatic control by monitoring the relationship between the set upper and lower limits and the room temperature (the air conditioner intake temperature) to prevent the set room temperature from exceeding those limits. This function starts and stops the air conditioners and changes the operation mode.
Cooling operation control (and stop control) Cooling operation is automatically started when the room temperature rises above the set upper temperature limit. The air conditioner is stopped once the room temperature falls sufficiently far below the upper temperature limit (upper temperature limit – 4°C or more) during cooling due to this control.
Heating operation control (and stop control) Heating operation is automatically started when the room temperature falls below the set lower temperature limit. The air conditioner is stopped once the room temperature rises sufficiently far above the lower temperature limit (lower temperature limit + 4°C or more) during heating due to this control.
q:Controlled air conditioners
This controls auto-start and auto-stop for each air conditioner based on the temperature set for each room temperature limit control group.
This control is not applicable to air conditioners which are already operating, even if they are registered to the room temperature limit control group. (It is only applicable to stopped air conditioners.)
Up to 64 indoor groups can be registered in one room temperature limit control group.
It is not possible to register the same indoor unit to multiple room temperature limit control groups.
Up to 8 room temperature limit control groups can be registered in this unit.
These controls can be enabled and disenabled for each individual room
temperature limit control group. (These controls only work for groups set as enabled.)
A mark indicating that the indoor unit is under automatic control will appear on the monitor screen.
w:Upper room temperature limit
Upper and lower room temperature limit The upper and lower room temperature limits desired for automatic control. The settable range of upper and lower limits is as follows.
Upper limit : 34°C to 50°C in 1°C units. (The default is 36°C.) Lower limit : 2°C to 14°C in 1°C units. (The default is 14°C.)
The temperature different between the upper or lower limit and the room temperature when the air conditioner under cooling (heating) operation control using this function (to prevent hunting) is 4°C.
Operation
35
Operation (Reference)
System Setup
Menu Item
Description
Temperature Limit Settings
e:Control Implementation Conditions
The relationship between room temperature, upper/lower limit, and operation mode is shown below. The controls are implemented when the control conditions are satisfied, every 5 minutes from the time the power is turned on.
This function performs stop control for cooling/heating operation and other operation controls to prevent excessive increase or decrease of the room temperature. The set values of room temperature upper/lower limit control group are used for the upper/lower limit values and other factors of this control. This control is not performed for the group of air conditioners to which this control is set invalid. The set temperatures of the air conditioners are not changed by this control.
qStart condition of cooling operation:
Cooling operation is controlled when the room temperature is higher than the upper limit of room temperature and the unit is stopped.
wStart condition of heating operation:
Heating operation is controlled when the room temperature is lower than the lower limit of room temperature and the unit is stopped.
eStop condition:
The air conditioners under cooling/heating control by this function stop when any of the following conditions are met.
During cooling operation Room temperature is lower than the upper limit of room temperature – 4°C or Room temperature is lower than the cooling set temperature
During heating operation Room temperature is higher than the lower limit of room temperature + 4°C or Room temperature is higher than the heating set temperature
Room temperature
Time
Lower limit
Upper limit
Lower limit + 4°C
Upper limit – 4°C
Heating operation control
Room temperature
is controlled into
this range.
Cooling operation control
Heating operation
Air conditioner stop
Cooling operation
Air conditioner stop
Loading...