13.3.3 Symptom: The system is making gurgling noises
after commissioning .................................................... 78
13.3.4 Symptom: The pump is making noise (cavitation) ...... 78
CHYHBH05+08AA + EHYKOMB33A
Daikin hybrid for multi heat pump – heat pump module
4P471761-1 – 2016.12
1.1About the documentation
▪ The original documentation is written in English. All other
languages are translations.
▪ The precautions described in this document cover very important
topics, follow them carefully.
▪ The installation of the system, and all activities described in the
installation manual and the installer reference guide must be
performed by an authorized installer.
1.1.1Meaning of warnings and symbols
DANGER
Indicates a situation that results in death or serious injury.
DANGER: RISK OF ELECTROCUTION
Indicates a situation that could result in electrocution.
Installer reference guide
3
1 General safety precautions
DANGER: RISK OF BURNING
Indicates a situation that could result in burning because of
extreme hot or cold temperatures.
DANGER: RISK OF EXPLOSION
Indicates a situation that could result in explosion.
DANGER: RISK OF POISONING
Indicates a situation that could result in poisoning.
WARNING
Indicates a situation that could result in death or serious
injury.
WARNING: PROTECT AGAINST FROST
Indicates a situation that could result in equipment or
property damage.
WARNING: FLAMMABLE MATERIAL
CAUTION
Indicates a situation that could result in minor or moderate
injury.
NOTICE
Indicates a situation that could result in equipment or
property damage.
INFORMATION
Indicates useful tips or additional information.
SymbolExplanation
Before installation, read the installation and
operation manual, and the wiring instruction sheet.
Before performing maintenance and service tasks,
read the service manual.
For more information, see the installer and user
reference guide.
1.2For the installer
1.2.1General
If you are not sure how to install or operate the unit, contact your
dealer.
NOTICE
Improper installation or attachment of equipment or
accessories could result in electric shock, short-circuit,
leaks, fire or other damage to the equipment. Only use
accessories, optional equipment and spare parts made or
approved by Daikin.
WARNING
Make sure installation, testing and applied materials
comply with applicable legislation (on top of the
instructions described in the Daikin documentation).
WARNING
Tear apart and throw away plastic packaging bags so that
nobody, especially children, can play with them. Possible
risk: suffocation.
DANGER: RISK OF BURNING
▪ Do NOT touch the refrigerant piping, water piping or
internal parts during and immediately after operation. It
could be too hot or too cold. Give it time to return to
normal temperature. If you must touch it, wear
protective gloves.
▪ Do NOT touch any accidental leaking refrigerant.
WARNING
Provide adequate measures to prevent that the unit can be
used as a shelter by small animals. Small animals that
make contact with electrical parts can cause malfunctions,
smoke or fire.
CAUTION
Do NOT touch the air inlet or aluminium fins of the unit.
NOTICE
▪ Do NOT place any objects or equipment on top of the
unit.
▪ Do NOT sit, climb or stand on the unit.
NOTICE
Works executed on the outdoor unit are best done under
dry weather conditions to avoid water ingress.
In accordance with the applicable legislation, it might be necessary
to provide a logbook with the product containing at least: information
on maintenance, repair work, results of tests, stand-by periods,…
Also, at least, following information must be provided at an
accessible place at the product:
▪ Instructions for shutting down the system in case of an emergency
▪ Name and address of fire department, police and hospital
▪ Name, address and day and night telephone numbers for
obtaining service
In Europe, EN378 provides the necessary guidance for this logbook.
For Swiss market, domestic hot water operation should only be
prepared in combination with a tank. Instant domestic hot water by
the gas boiler is NOT allowed. Make the correct settings as
described in this manual.
Please follow following Swiss regulations and directives:
▪ SVGW-gas principles G1 for gas installations,
▪ SVGW-gas principles L1 for liquid gas installations,
▪ cautional instances regulations (e.g., fire regulation).
1.2.2Installation site
▪ Provide sufficient space around the unit for servicing and air
circulation.
▪ Make sure the installation site withstands the total weight and
vibration of the installation.
CAUTION
Wear adequate personal protective equipment (protective
gloves, safety glasses,…) when installing, maintaining or
servicing the system.
Installer reference guide
4
ModuleWeight
Hybrid module30kg
Gas module36kg
Indoor part (Hybrid module + gas
module)
▪ Make sure the area is well ventilated. Do NOT block any
ventilation openings.
Daikin hybrid for multi heat pump – heat pump module
Total weight: 66kg
CHYHBH05+08AA + EHYKOMB33A
4P471761-1 – 2016.12
1 General safety precautions
▪ Make sure the unit is level.
▪ Make sure walls sensitive to heat (e.g. wood) are protected by
suitable insulation.
▪ ONLY operate the gas boiler if a sufficient supply of combustion
air is ensured. In case of a concentric air/flue gas system
dimensioned according to the specifications of this manual, this is
fulfilled automatically and there are no other conditions for the
equipment installation room. This method of operation applies
exclusively.
▪ This gas boiler is NOT designed for room air dependent operation.
Do NOT install the unit in the following places:
▪ In potentially explosive atmospheres.
▪ In places where there is machinery that emits electromagnetic
waves. Electromagnetic waves may disturb the control system,
and cause malfunction of the equipment.
▪ In places where there is a risk of fire due to the leakage of
flammable gases (example: thinner or gasoline), carbon fibre,
ignitable dust.
▪ In places where corrosive gas (example: sulphurous acid gas) is
produced. Corrosion of copper pipes or soldered parts may cause
the refrigerant to leak.
▪ In bathrooms.
▪ In places where frost is possible. The ambient temperature around
the indoor unit should be >5°C.
DANGER: RISK OF EXPLOSION
Pump down – Refrigerant leakage. If you want to pump
down the system, and there is a leakage in the refrigerant
circuit:
▪ Do NOT use the unit's automatic pump down function,
with which you can collect all refrigerant from the
system into the outdoor unit. Possible consequence:
Self-combustion and explosion of the compressor
because of air going into the operating compressor.
▪ Use a separate recovery system so that the unit's
compressor does NOT have to operate.
WARNING
Always recover the refrigerant. Do NOT release them
directly into the environment. Use a vacuum pump to
evacuate the installation.
NOTICE
After all the piping has been connected, make sure there is
no gas leak. Use nitrogen to perform a gas leak detection.
NOTICE
▪ To avoid compressor breakdown, do NOT charge more
than the specified amount of refrigerant.
▪ When the refrigerant system is to be opened,
refrigerant must be treated according to the applicable
legislation.
1.2.3Refrigerant
If applicable. See the installation manual or installer reference guide
of your application for more information.
NOTICE
Make sure refrigerant piping installation complies with
applicable legislation. In Europe, EN378 is the applicable
standard.
NOTICE
Make sure the field piping and connections are not
subjected to stress.
WARNING
During tests, NEVER pressurize the product with a
pressure higher than the maximum allowable pressure (as
indicated on the nameplate of the unit).
WARNING
Take sufficient precautions in case of refrigerant leakage. If
refrigerant gas leaks, ventilate the area immediately.
Possible risks:
▪ Excessive refrigerant concentrations in a closed room
can lead to oxygen deficiency.
▪ Toxic gas may be produced if refrigerant gas comes
into contact with fire.
WARNING
Make sure there is no oxygen in the system. Refrigerant
may only be charged after performing the leak test and the
vacuum drying.
▪ In case re-charge is required, refer to the nameplate of the unit. It
states the type of refrigerant and necessary amount.
▪ The unit is factory charged with refrigerant and depending on pipe
sizes and pipe lengths some systems require additional charging
of refrigerant.
▪ Only use tools exclusively for the refrigerant type used in the
system, this to ensure pressure resistance and prevent foreign
materials from entering into the system.
▪ Charge the liquid refrigerant as follows:
IfThen
A siphon tube is present
(i.e., the cylinder is marked with
"Liquid filling siphon attached")
A siphon tube is NOT presentCharge with the cylinder upside
Charge with the cylinder upright.
down.
CHYHBH05+08AA + EHYKOMB33A
Daikin hybrid for multi heat pump – heat pump module
4P471761-1 – 2016.12
▪ Open refrigerant cylinders slowly.
▪ Charge the refrigerant in liquid form. Adding it in gas form may
prevent normal operation.
Installer reference guide
5
1 General safety precautions
CAUTION
When the refrigerant charging procedure is done or when
pausing, close the valve of the refrigerant tank
immediately. If the valve is not closed immediately,
remaining pressure might charge additional refrigerant.
Possible consequence: Incorrect refrigerant amount.
1.2.4Water
If applicable. See the installation manual or installer reference guide
of your application for more information.
NOTICE
Make sure water quality complies with EU directive
98/83EC.
Avoid damages caused by deposits and corrosion. To prevent
corrosion products and deposits, observe the applicable regulations
of technology.
Measures for desalination, softening or hardness stabilization are
necessary if the filling and top-up water have a high total hardness
(>3 mmol/l–sum of the calcium and magnesium concentrations,
calculated as calcium carbonate).
Using filling water and top-up water which does NOT meet the stated
quality requirements can cause a considerably reduced service life
of the equipment. The responsibility for this is entirely that of the
user.
1.2.5Electrical
DANGER: RISK OF ELECTROCUTION
▪ Turn OFF all power supply before removing the
switch box cover, connecting electrical wiring or
touching electrical parts.
▪ Disconnect the power supply for more than 1minute,
and measure the voltage at the terminals of main circuit
capacitors or electrical components before servicing.
The voltage MUST be less than 50 V DC before you
can touch electrical components. For the location of the
terminals, see the wiring diagram.
▪ Do NOT touch electrical components with wet hands.
▪ Do NOT leave the unit unattended when the service
cover is removed.
WARNING
If NOT factory installed, a main switch or other means for
disconnection, having a contact separation in all poles
providing full disconnection under overvoltage category III
condition, MUST be installed in the fixed wiring.
WARNING
▪ ONLY use copper wires.
▪ Make sure the field wiring complies with the applicable
legislation.
▪ All field wiring must be performed in accordance with
the wiring diagram supplied with the product.
▪ NEVER squeeze bundled cables and make sure they
do not come in contact with the piping and sharp
edges. Make sure no external pressure is applied to the
terminal connections.
▪ Make sure to install earth wiring. Do NOT earth the unit
to a utility pipe, surge absorber, or telephone earth.
Incomplete earth may cause electrical shock.
▪ Make sure to use a dedicated power circuit. NEVER
use a power supply shared by another appliance.
▪ Make sure to install the required fuses or circuit
breakers.
▪ Make sure to install an earth leakage protector. Failure
to do so may cause electric shock or fire.
▪ When installing the earth leakage protector, make sure
it is compatible with the inverter (resistant to high
frequency electric noise) to avoid unnecessary opening
of the earth leakage protector.
NOTICE
Precautions when laying power wiring:
▪ Do not connect wiring of different thicknesses to the
power terminal block (slack in the power wiring may
cause abnormal heat).
▪ When connecting wiring which is the same thickness,
do as shown in the figure below.
▪ For wiring, use the designated power wire and connect
firmly, then secure to prevent outside pressure being
exerted on the terminal board.
▪ Use an appropriate screwdriver for tightening the
terminal screws. A screwdriver with a small head will
damage the head and make proper tightening
impossible.
▪ Over-tightening the terminal screws may break them.
Install power cables at least 1 metre away from televisions or radios
to prevent interference. Depending on the radio waves, a distance of
1metre may not be sufficient.
Installer reference guide
6
WARNING
▪ After finishing the electrical work, confirm that each
electrical component and terminal inside the electrical
components box is connected securely.
▪ Make sure all covers are closed before starting up the
unit.
NOTICE
Only applicable if the power supply is three‑phase, and the
compressor has an ON/OFF starting method.
If there exists the possibility of reversed phase after a
momentary black out and the power goes on and off while
the product is operating, attach a reversed phase
protection circuit locally. Running the product in reversed
phase can break the compressor and other parts.
CHYHBH05+08AA + EHYKOMB33A
Daikin hybrid for multi heat pump – heat pump module
4P471761-1 – 2016.12
2 About the product
1.2.6Gas
The gas boiler is factory‑set to:
▪ the type of gas quoted on the type identification plate or on the
setting type identification plate,
▪ the gas pressure quoted on the type identification plate.
Operate the unit ONLY with the gas type and gas pressure indicated
on these type identification plates.
Installation and adaptation of the gas system MUST be conducted
by:
▪ personnel qualified for this work,
▪ in compliance with valid gas installation related guidelines,
▪ in accordance with applicable regulations of the gas supply
company,
▪ In accordance with local and national regulations.
Boilers that use natural gas MUST be connected to a governed
meter.
Boilers that use liquid petroleum gas (LPG) MUST be connected to a
regulator.
The size of the gas supply pipe should under no circumstance be
less than 22mm.
The meter or regulator and pipe work to the meter MUST be
checked preferably by the gas supplier. This is to ensure that the
equipment works good and meets the gas flow and pressure
requirements.
DANGER
If you smell gas:
▪ call immediately your local gas supplier and your
installer,
▪ call the suppliers's number on the side of the LPG tank
(if applicable),
▪ turn off the emergency control valve at the meter/
regulator,
▪ do NOT turn electrical switches ON or OFF,
▪ do NOT strike matches or smoke,
▪ put out naked flames,
▪ open doors and windows immediately,
▪ keep people away from the affected area.
1.2.7Gas exhaust
Flue systems must NOT be modified or installed in any way other
than as described in the fitting instructions. Any misuses or
unauthorized modifications to the appliance, flue or associated
components and systems could invalidate the warranty. The
manufacturer accepts no liability arising from any such actions,
excluding statutory rights.
It is NOT allowed to combine flue system parts purchased from
different suppliers.
1.2.8Local legislation
See the local and national regulations.
Local regulations for UK
It is law that all gas appliances are installed by a gas safe registered
competent engineer and in accordance with the following
recommendations:
▪ Current Gas Safety (Installation and Use) Regulations
▪ All current building regulations
▪ Building Standards (Scotland) Consolidated
▪ This appliance MUST be installed in accordance with the Gas
(Safety and Use) Regulations, current Building Regulations,
Building Standards (Scotland), I.S.813 Installation of Gas
Appliances (Ireland), IEE Wiring Regulations (BS 7671), Health
and Safety Document No. 635 (Electricity at Work Regulations)
and Local Water Authority Bye Laws
▪ UK Water Regulations and Bye Laws
▪ Health & Safety
The installation MUST comply with the following British Standards
codes of practice:
▪ BS 5440: Flues and Ventilation for gas appliances of rated input
NOT exceeding 70kW (Part 1 Flues)
▪ BS 5440: Flues and Ventilation for gas appliances of rated input
NOT exceeding 70kW (Part 2 Air Supply)
▪ BS 5546: 2000 Installation of gas hot water supplies for domestic
purposes.
▪ BS 5549: 1990 Forced circulation hot water systems.
▪ BS 6700: 1997 Design, Installation, testing and maintenance of
services supplying hot water
▪ BS 6798: 2000 Specification for installation of gas fired hot water
boilers of rated input NOT exceeding 70kW
▪ BS 6891: 1998 Installation of low pressure gas pipe-work
installation up to 35mm (RI)
▪ BS 7593: 1992 Code of practice for treatment of water in heating
systems
▪ BS 7671: 2001 Requirements for electrical installations, IEE
Wiring regulations
▪ BS 7074: 1 Code of practice for domestic and hot water supply
▪ EN12828 Central heating for domestic premises
Potable water: all seals, joints and compounds (including flux and
solder) and components used as part of the secondary domestic
water system MUST be approved by WRAS.
2About the product
Especially for UK:
The Benchmark Scheme
Benchmark places responsibilities on both manufacturers and
installers. The purpose is to ensure that customers are provided with
the correct equipment for their needs, that it is installed,
commissioned and serviced in accordance with the manufacturer’s
instructions by competent persons and that it meets the
requirements of the appropriate Building Regulations. The
Benchmark Checklist can be used to demonstrate compliance with
Building Regulations and should be provided to the customer for
future reference.
Installers are required to carry out installation, commissioning and
servicing work in accordance with the Benchmark Code of Practice
which is available from the Heating and Hotwater Industry Council
who manage and promote the Scheme. Visit http://
www.centralheating.co.uk for more information.
Approvals
British Gas Service listing:
EHYKOMB33AA*: G.C.N. 47-464-01
The product (hybrid system) is composed of two modules:
CHYHBH05+08AA + EHYKOMB33A
Daikin hybrid for multi heat pump – heat pump module
4P471761-1 – 2016.12
Installer reference guide
7
3 About the documentation
ab
▪ heat pump module,
▪ gas boiler module.
These modules MUST always be installed and used together.
a Heat pump module
b Gas boiler module
3About the documentation
3.1About this document
Target audience
Authorised installers
Documentation set
This document is part of a documentation set. The complete set
consists of:
▪ General safety precautions:
▪ Safety instructions that you must read before installing
▪ Format: Paper (in the box of the indoor unit)
▪ Heat pump module installation manual:
▪ Installation instructions
▪ Format: Paper (in the box of the indoor unit)
▪ Gas boiler module installation manual:
▪ Installation and operation instructions
▪ Format: Paper (in the box of the gas boiler unit)
▪ Outdoor unit installation manual:
▪ Installation instructions
▪ Format: Paper (in the box of the outdoor unit)
▪ Installer reference guide:
▪ Preparation of the installation, reference data,…
▪ Format: Digital files on http://www.daikineurope.com/support-
and-manuals/product-information/
▪ Addendum book for optional equipment:
▪ Additional info about how to install optional equipment
▪ Format: Paper (in the box of the indoor unit) + Digital files on
Latest revisions of the supplied documentation may be available on
the regional Daikin website or via your dealer.
The original documentation is written in English. All other languages
are translations.
Technical engineering data
▪ A subset of the latest technical data is available on the regional
Daikin website (publicly accessible).
▪ The full set of latest technical data is available on the Daikin
extranet (authentication required).
3.2Installer reference guide at a
glance
ChapterDescription
General safety
precautions
About the productRequired combination of heat pump
About the documentation What documentation exists for the
About the boxHow to unpack the units and remove
About the units and
options
PreparationWhat to do and know before going
InstallationWhat to do and know to install the
ConfigurationWhat to do and know to configure the
OperationOperation modes of the gas boiler
CommissioningWhat to do and know to commission the
Hand‑over to the userWhat to give and explain to the user
Maintenance and service How to maintain and service the units
TroubleshootingWhat to do in case of problems
DisposalHow to dispose of the system
Technical dataSpecifications of the system
GlossaryDefinition of terms
Field settings tableTable to be filled in by the installer, and
Safety instructions that you must read
before installing
module and gas boiler module
installer
their accessories
▪ How to identify the units
▪ Possible combinations of units and
options
on‑site
system
system after it is installed
module
system after it is configured
kept for future reference
Note: There is also an installer settings
table in the user reference guide. This
table has to be filled in by the installer
and handed over to the user.
4About the box
4.1Overview: About the box
It contains information about:
▪ Unpacking and handling the units
Installer reference guide
8
Daikin hybrid for multi heat pump – heat pump module
CHYHBH05+08AA + EHYKOMB33A
4P471761-1 – 2016.12
4 About the box
a
b
abcde
fg
1
2
▪ Removing the accessories from the units
Keep the following in mind:
▪ At delivery, the unit must be checked for damage. Any damage
must be reported immediately to the carrier's claims agent.
▪ Bring the packed unit as close as possible to its final installation
position to prevent damage during transport.
4.2Indoor unit
4.2.1To unpack the indoor unit
INFORMATION
Do NOT throw away the upper cardboard cover. On the
outside of the cardboard cover, the installation pattern is
printed.
4.2.2To remove the accessories from the
indoor unit
The installation manual, operation manual, addendum book for
optional equipment, general safety precautions, quick installation
guide, and boiler communication cable are located in the upper part
of the box. The connection pieces for the gas boiler are attached to
the water piping.
1 Remove the accessories as described in "4.2.1To unpack the
indoor unit"on page9.
a General safety precautions
b Addendum book for optional equipment
c Indoor unit installation manual
d Operation manual
e Quick installation guide
f Connection pieces for gas boiler
g Boiler communication cable
4.3Gas boiler
4.3.1To unpack the gas boiler
Before unpacking, move the gas boiler as close as possible to its
installation position.
a Installation manual, operation manual, addendum book for
optional equipment, quick installation guide, general safety
precautions, boiler communication cable
b Connection pieces for the gas boiler
CHYHBH05+08AA + EHYKOMB33A
Daikin hybrid for multi heat pump – heat pump module
4P471761-1 – 2016.12
Installer reference guide
9
5 About the units and options
a
b
c
abc
a Mounting strip
b Condensate trap
c Installation manual and operation manual
WARNING
Tear apart and throw away plastic packaging bags so that
nobody, especially children, can play with them. Possible
risk: suffocation.
5About the units and options
5.1Overview: About the units and
options
This chapter contains information about:
▪ Identifying the indoor unit
▪ Identifying the gas boiler
▪ Combining outdoor and indoor units
▪ Combining the indoor unit with options
▪ Combining the gas boiler with options
5.2Identification
NOTICE
When installing or servicing several units at the same time,
make sure NOT to switch the service panels between
different models.
5.2.1Identification label: Indoor unit
Location
4.3.2To remove the accessories from the gas
boiler
1 Remove the accessories.
Installer reference guide
10
Model identification
Example: CHYHBH05AAV3
CodeDescription
CResidential multi compatible model
CHYHBH05+08AA + EHYKOMB33A
Daikin hybrid for multi heat pump – heat pump module
4P471761-1 – 2016.12
5 About the units and options
No:
Anno:
Type:
NOx classe:
PIN:
G.C.:
SVGW:
Qnw(net)
PMW
kW
kW
kW
bar
Qn (net)
Pn
PMS
bar
°C
0063
2013
Tmax
Condensing boiler
b
i
j
a
c
d
e
f
k
l
m
n
o
p
q
r
s
g
h
CodeDescription
HYHybrid indoor unit
HBHHydrobox heating only
o Maximum space heating pressure (bar)
p Maximum flow temperature (°C)
q Electrical supply
r GCN gas council number
s SVGW number
05Capacity class
AAModel series
5.3Combining units and options
V3Power supply
5.3.1Possible options for the indoor unit
5.2.2Identification label: gas boiler
Location
Model identification
a Model
b Serial number
c Production year
d Appliance type
e NOx class
f PIN number: notified body reference
g Destination country
CHYHBH05+08AA + EHYKOMB33A
Daikin hybrid for multi heat pump – heat pump module
4P471761-1 – 2016.12
h Gas type
i Gas supply pressure (mbar)
j Appliance category
k Domestic hot water heat output (kW)
l Maximum domestic hot water pressure (bar)
m Heat output (space heating) (kW)
n Nominal power (kW)
User interface (EKRUCBL*)
The user interface and a possible additional user interface are
available as an option.
The additional user interface can be connected:
▪ To have both:
▪ control close to the indoor unit,
▪ room thermostat functionality in the principal space to be
heated.
▪ To have an interface containing other languages.
Following user interfaces are available:
▪ EKRUCBL1 contains following languages: German, French,
Dutch, Italian.
▪ EKRUCBL2 contains following languages: English, Swedish,
Norwegian, Finnish.
▪ EKRUCBL3 contains following languages: English, Spanish,
Greek, Portuguese.
▪ EKRUCBL4 contains following languages: English, Turkish,
Polish, Romanian.
▪ EKRUCBL5 contains following languages: German, Czech,
Slovenian, Slovakian.
▪ EKRUCBL6 contains following languages: English, Croatian,
Hungarian, Estonian.
▪ EKRUCBL7 contains following languages: English, German,
Russian, Danish.
Languages on the user interface can be uploaded by PC software or
copied from an user interface to the other.
For installation instructions, see "7.10.8 To connect the user
interface"on page36.
Simplified user interface (EKRUCBS)
▪ The simplified user interface can only be used in combination with
the main user interface.
▪ The simplified user interface acts as room thermostat and needs
to be installed in the room that you want it to control.
For installation instructions, see the installation and operation
manual of the simplified user interface.
Room thermostat (EKRTWA, EKRTR1, RTRNETA)
You can connect an optional room thermostat to the indoor unit. This
thermostat can either be wired (EKRTWA) or wireless (EKRTR1 and
RTRNETA). Thermostat RTRNETA can only be used in heating-only
systems.
For installation instructions, see the installation manual of the room
thermostat and addendum book for optional equipment.
Remote sensor for wireless thermostat (EKRTETS)
You can use a wireless indoor temperature sensor (EKRTETS) only
in combination with the wireless thermostat (EKRTR1).
For installation intructions, see the installation manual of the room
thermostat and addendum book for optional equipment.
Digital I/O PCB (EKRP1HB)
The digital I/O PCB is required to provide the following signals:
▪ Alarm output
Installer reference guide
11
5 About the units and options
▪ Space heating/cooling On/OFF output
For installation instructions, see the installation manual of the digital
I/O PCB and the addendum book for optional equipment.
Remote indoor sensor (KRCS01-1)
By default the internal user interface sensor will be used as room
temperature sensor.
As an option the remote indoor sensor can be installed to measure
the room temperature on another location.
For installation instructions, see the installation manual of the remote
indoor sensor and addendum book for optional equipment.
INFORMATION
▪ The remote indoor sensor can only be used in case the
user interface is configured with room thermostat
functionality.
▪ You can only connect either the remote indoor sensor
or the remote outdoor sensor.
Remote outdoor sensor (EKRSCA1)
By default the sensor inside the outdoor unit will be used to measure
the outdoor temperature.
As an option the remote outdoor sensor can be installed to measure
the outdoor temperature on another location (e.g. to avoid direct
sunlight) to have an improved system behaviour.
For installation instructions, see the installation manual of the remote
outdoor sensor.
INFORMATION
You can only connect either the remote indoor sensor or
the remote outdoor sensor.
PC configurator (EKPCCAB)
The PC cable makes a connection between the switch box of the
indoor unit and a PC. It gives the possibility to upload different
language files to the user interface and indoor parameters to the
indoor unit. For the available language files, contact your local
dealer.
The software and corresponding operating instructions are available
on http://www.daikineurope.com/support-and-manuals/software-
downloads/.
For installation instructions, see the installation manual of the PC
cable and "8Configuration"on page45.
Heat pump convector (FWXV)
For installation instructions, refer to the installation manual of the
heat pump convectors, and the addendum book for optional
equipment.
Solar kit (EKSRPS3)
The solar kit is required to connect the solar application with the
domestic hot water tank.
For installation, see the installation manual of the solar kit and
addendum book for optional equipment.
Domestic hot water tank
The domestic hot water tank can be connected to the indoor unit for
providing domestic hot water. The polypropylene tank is available in
2 types:
▪ EKHWP300B: 300l.
▪ EKHWP500B: 500l.
Use the appropriate connection kit for the tank (EKEPHT3H), as
described in the addendum book for optional equipment.
Connection kit for the tank (EKEPHT3H)
Use the connection kit to connect the domestic hot water tank to the
indoor unit.
For installation instructions, see the installation manual of the
connection kit.
Mounting kit (EKHYMNT1A, EKHYMNT2A, EKHYMNT3A)
Mounting fixture for easy installation of the hybrid system (heat
pump module + gas boiler module). For the selection of the correct
kit, see the combination table.
For installation instructions, see the installation manual of the
mounting kit.
Filling loop kit (EKFL1A)
Filling loop for easy filling of the water circuit. This kit can only be
used in combination with mounting kit EKHYMNT1A.
For installation instructions, see the installation manual of the filling
loop kit.
Valve kit (EKVK1A, EKVK2A, EKVK3A)
A set of valves for the easy connection of the field piping. For the
connection of the correct kit, see the combination table.
For installation instructions, see the installation manual of the valve
kit.
Recirculation thermistor (EKTH2)
Kit for recirculating the water on the gas boiler. Only use this kit
when there is no domestic hot water tank installed.
Connection kit for 3rd‑party tank (EKHY3PART)
Use the connection kit to connect a 3rd‑party tank to the system.
The connection kit exists of a thermistor and a 3-way valve.
LAN adapter for smartphone control (BRP069A62)
You can install this LAN adapter to control the system via a
smartphone app.
For installation instructions, see the installation manual of the LAN
adapter.
5.3.2Possible options for the gas boiler
Main options
Boiler cover plate (EKHY093467)
Cover plate to protect the gas boiler’s piping and valves.
For installation instructions, see the installation manual of the cover
plate.
Gas conversion kit G25 (EKPS076227)
Kit for the conversion of the gas boiler for use with gas type G25.
Gas conversion kit G31 (EKHY075787)
Kit for the conversion of the gas boiler for use with gas type G31
(propane).
Dual pipe conversion kit (EKHY090707)
Kit for the conversion of a concentric flue gas system to a dual pipe
system.
For installation instructions, see the installation manual of the dual
pipe conversion kit.
80/125 concentric connection kit (EKHY090717)
Kit for the conversion of 60/100 concentric flue gas connections to
80/125 concentric flue gas connections.
For installation instructions, see the installation manual of the
concentric connection kit.
Flue gas flap valve (EKFGF1A)
Non-return flap valve for use in multi-boiler flue gas systems. This
valve can only be used in systems using natural gas (G20, G25),
and CANNOT be used in systems using propane (G31).
Other options
Installer reference guide
12
Daikin hybrid for multi heat pump – heat pump module
CHYHBH05+08AA + EHYKOMB33A
4P471761-1 – 2016.12
5 About the units and options
Accessories Part numberDescription
EKFGP6837Roof terminal PP/GLV 60/100
AR460
EKFGS0518Weather slate steep Pb/GLV
60/100 18°-22°
EKFGS0519Weather slate steep Pb/GLV
60/100 23°-17°
EKFGP7910Weather slate steep PF 60/100
25°-45°
EKFGS0523Weather slate steep Pb/GLV
60/100 43°-47°
EKFGS0524Weather slate steep Pb/GLV
60/100 48°-52°
EKFGS0525Weather slate steep Pb/GLV
60/100 53°-57°
EKFGP1296Weather slate flat Aluminium
60/100 0°-15°
EKFGP6940Weather slate flat Aluminium
60/100
EKFGP2978Wall terminal kit PP/GLV
60/100
EKFGP2977Wall terminal kit low profile PP/
GLV 60/100
EKFGP4651Extension PP/GLV
60/100×500mm
Accessories Part numberDescription
EKFGW5333Weather slate flat aluminium
80/125
EKFGW6359Wall terminal kit PP/GLV
80/125
EKFGP4801Extension PP/GLV
80/125×500mm
EKFGP4802Extension PP/GLV
80/125×1000mm
EKFGP4814Elbow PP/GLV 80/125 30°
EKFGP4811Elbow PP/ALU 80/125 45°
EKFGP4810Elbow PP/ALU 80/125 90°
EKFGP4820Inspection elbow Plus PP/ALU
80/125 90° EPDM
EKFGP6864Roof Terminal PP/GLV 80/125
AR300 RAL9011
EKFGP4652Extension PP/GLV
60/100×1000mm
EKFGP4664Elbow PP/GLV 60/100 30°
EKFGP4661Elbow PP/GLV 60/100 45°
EKFGP4660Elbow PP/GLV 60/100 90°
EKFGP4667Meas. tee with inspection panel
PP/GLV 60/100
EKFGP4631Wall bracket Ø100
EKFGP1292Wall terminal Kit PP/GLV
60/100
EKFGP1293Wall terminal kit low profile PP/
GLV 60/100
EKFGP1294Plume management kit 60 (UK
only)
EKFGP1295Flue deflector 60 (UK only)
EKFGP1284PMK elbow 60 90 (UK only)
EKFGP1285PMK elbow 60 45° (2pieces)
(UK only)
EKFGP1286PMK extension 60 L=1000
includes bracket (UK only)
EKFGT6300Weather slate steep Pb/GLV
80/125 18°-22°
EKFGT6301Weather slate steep Pb/GLV
80/125 23°-27°
EKFGP7909Weather slate steep PF 80/125
25°-45° RAL9011
EKFGT6305Weather slate steep Pb/GLV
80/125 43°-47°
EKFGT6306Weather slate steep Pb/GLV
80/125 48°-52°
EKFGT6307Weather slate steep Pb/GLV
80/125 53°-57°
EKFGP1297Weather slate flat aluminium
80/125 0°-15°
EKFGP6368Tee flex 100 boiler connection
set 1
EKFGP6354Flex 100-60 + support elbow
EKFGP6215Tee flex 130 boiler connection
set 1
EKFGS0257Flex 130-60 + support elbow
CHYHBH05+08AA + EHYKOMB33A
Daikin hybrid for multi heat pump – heat pump module
4P471761-1 – 2016.12
Installer reference guide
13
5 About the units and options
Accessories Part numberDescription
EKFGP4678Chimney connection 60/100
EKFGP5461Extension PP 60×500
EKFGP5497Chimney top PP 100 with
included flue pipe
EKFGP6316Adapter flex-fixed PP 100
EKFGP6337Support bracket top inox Ø100
EKFGP6346Extension flex PP100 L=10m
EKFGP6349Extension flex PP100 L=15m
Accessories Part numberDescription
EKFGP2520Flex kit PP Ø80
EKFGP4828Chimney connection 80/125
EKFGP6340Extension Flex PP80 L=10m
EKFGP6344Extension Flex PP80 L=15m
EKFGP6341Extension Flex PP80 L=25m
EKFGP6342Extension Flex PP80 L=50m
EKFGP6324Connector-flex-flex PP80
EKFGP6347Extension flex PP100 L=25m
EKFGP6325Connector flex-flex PP100
EKFGP5197Chimney top PP 130 with
included flue pipe
EKFGS0252Adapter flex-fixed PP130
EKFGP6353Support bracket top inox Ø130
EKFGS0250Extension flex PP130 L=130m
EKFGP6366Connector flex-flex PP130
EKFGP6333Spacer PP80-100
EKFGP4481Fixation Ø100
EKFGV1101Chimney connection 60/10
airintake Dn.80 C83
EKFGV1102Connection set 60/10-60 Flue/
Air intake Dn.80 C53
EKFGW4001ExtensionPBM-Air 80×500
EKFGW4002ExtensionPBM-Air 80×1000
EKFGW4004ExtensionPBM-Air 80×2000
EKFGW4085ElbowPPBM-Air8090°
EKFGP1856Flex kit PPØ60-80
EKFGP4678Chimney connection 60/100
Installer reference guide
14
EKFGW4086ElbowPPBM-Air8045°
EKGFP1289ElbowPP/GALV 60/100 50°
EKGFP1299Kit horizontal low profile PP/
GLV 60/100 (UK only)
CHYHBH05+08AA + EHYKOMB33A
Daikin hybrid for multi heat pump – heat pump module
4P471761-1 – 2016.12
6 Preparation
H>500
300
h
300
10350500
(mm)
INFORMATION
For extra configuration options regarding the flue gas
system, visit http://fluegas.daikin.eu/.
5.3.3Possible combinations of indoor unit and
outdoor unit
See the combination table in the technical engineering data.
5.3.4Possible combinations of indoor unit and
domestic hot water tank
Indoor unitDomestic hot water tank
EKHWP300B + EKHWP500B
CHYHBH05O
CHYHBH08O
6Preparation
6.1Overview: Preparation
This chapter describes what you have to do and know before going
on-site.
It contains information about:
▪ Preparing the installation site
▪ Preparing the refrigerant piping
▪ Preparing the water piping
▪ Preparing the electrical wiring
6.2.1Installation site requirements of the
indoor unit
INFORMATION
Also read the precautions and requirements in the
"General safety precautions" chapter.
▪ Mind the measurement guidelines:
Maximum refrigerant piping length between indoor
unit and outdoor unit
Minimum refrigerant piping length between indoor
unit and outdoor unit
Maximum height difference between indoor unit and
outdoor unit
Maximum equivalent piping length between the
3‑way valve and the indoor unit (for installations
with domestic hot water tank)
Maximum equivalent piping length between the
domestic hot water tank and the indoor unit (for
installations with domestic hot water tank)
(a) Piping diameter 0.75".
▪ Mind the following spacing installation guidelines:
25m
3m
15m
3m
10m
(a)
(a)
6.2Preparing installation site
Do NOT install the unit in places often used as work place. In case
of construction works (e.g. grinding works) where a lot of dust is
created, the unit must be covered.
Choose the installation location with sufficient place for carrying the
unit in and out of the site.
H Distance measured from the floor to the bottom of the
casing of the gas boiler (minimum 500mm, and in case of
a valve mounting kit: 800mm).
h Distance measured from the floor to the flare nut of the
refrigerant piping.
CHYHBH05+08AA + EHYKOMB33A
Daikin hybrid for multi heat pump – heat pump module
4P471761-1 – 2016.12
Installer reference guide
15
6 Preparation
Input from installer:
▪ Total refrigerant charge (m
c
) (kg)
▪ Installation height (H) (m)
▪ Area of room A (A
room A
) (m2)
Start
Use table 1 in chapter "Technical data" to
calculate the maximum refrigerant charge
(m
max
) (kg) allowed for room A.
Contact your dealer.
Use table 3 in chapter "Technical data" and
dm to calculate the minimum opening area for
natural ventilation between room A and
room B (VA
min
) (cm2). Make sure to select the
correct outdoor unit.
Unit can be installed at room A if:
▪ 2 ventilation openings (permanently open) are provided between room A and B, 1 at the top and 1 at the bottom.
▪ Bottom opening: The bottom opening must meet the minimum area requirements (VA
min
). If the ventilation opening starts from the floor, the height must be
≥20 mm. The bottom of the opening must be situated ≤100 mm from the floor. At least 50% of the required opening area must be situated <200 mm from the
floor. The entire area of the opening must be situated <300 mm from the floor.
▪ Top opening: The area of the top opening must be larger than or equal to the bottom opening. The bottom of the top opening must be situated at least 1.5 m
above the top of the bottom opening.
▪ Ventilation openings to the outside are NOT considered suitable ventilation openings (the user can block them when it is cold). For ventilation opening
requirements, see "Ventilation opening requirements" in the chapter "Technical data".
The unit can be installed in room A at the
specified installation height, and without
further room size or ventilation requirements.
Determine the refrigerant amount that exceeds
m
max
(dm) (kg). (dm=mc–m
max
)
m
max≥mc
?
Yes
No
No
Use table 2 in chapter "Technical data" to
calculate the total minimum floor area
(A
min total
) (m2) required for the total refrigerant
charge (m
c
) at the selected installation height
(H).
A
min total≤Aroom A+Aroom B
?
Yes
Input from installer:
▪ Area of adjacent room B (A
room B
) (m2)
Room A: Room where CHYHBH is installed.
Room B: Room adjacent to room A.
Room ARoom B
CHYHBH
Special requirements for R32
Use the tables in "15.4 Maximum refrigerant charge allowed in a
room: indoor unit" on page 90, "15.5 Minimum floor area: indoor
unit" on page 92, "15.6 Minimum venting opening area for natural
ventilation: indoor unit"on page 93 to calculate the needed values
to make sure that your appliance is installed correctly.
Installer reference guide
16
Daikin hybrid for multi heat pump – heat pump module
B Total refrigerant charge in the system (kg)
H The height measured from the floor to the bottom of the
casing. The graph is based on the height measured from
the floor to the flare nut.
Do NOT install the unit in places such as:
▪ In places where a mineral oil mist, spray or vapour may be
present in the atmosphere. Plastic parts may deteriorate and fall
off or cause water leakage.
▪ Sound sensitive areas (e.g. near a bedroom), so that the
operation noise will cause no trouble.
▪ The foundation must be strong enough to bear the weight of the
unit. Take the weight of the unit with a domestic hot water tank full
of water into account.
Make sure, in the event of a water leak, water cannot cause any
damage to the installation space and surroundings.
▪ In places with high humidity (max. RH=85%), for example a
bathroom.
▪ In places where frost is possible. Ambient temperature around the
indoor unit should be >5°C.
▪ The indoor unit is designed for indoor installation only (in a
technical room or similar) and for ambient temperatures ranging
5~30°C in heating mode.
6.3Preparing refrigerant piping
6 Preparation
4MXM80
Liquid piping4× Ø6.4mm (1/4")
Gas piping1× Ø9.5mm (3/8")
1× Ø12.7mm (1/2")
2× Ø15.9mm (5/8")
5MXM90
Liquid piping5× Ø6.4mm (1/4")
Gas piping2× Ø9.5mm (3/8")
1× Ø12.7mm (1/2")
2× Ø15.9mm (5/8")
▪ Piping temper grade and thickness:
Outer diameter
Temper gradeThickness (t)
(Ø)
6.4mm (1/4")Annealed (O)≥0.8mm
9.5mm (3/8")≥1mm
12.7mm (1/2")≥0.8mm
15.9mm (5/8")≥1mm
(a) Depending on the applicable legislation and the unit's
maximum working pressure (see "PS High" on the unit
name plate), larger piping thickness might be required.
Usage of reducers might be required based on the outdoor unit. See
"7.6.8 Usage of reducers to connect the piping to the outdoor
unit"on page28 for more information.
6.3.2Refrigerant piping insulation
▪ Use polyethylene foam as insulation material:
▪ with a heat transfer rate between 0.041 and 0.052W/mK (0.035
and 0.045kcal/mh°C)
▪ with a heat resistance of at least 120°C
▪ Insulation thickness
Pipe outer diameter
(Øp)
6.4mm (1/4")8~10mm≥10mm
9.5mm (3/8")10~14mm≥13mm
12.7mm (1/2")14~16mm≥10mm
15.9mm (5/8")16~20mm≥13mm
Insulation inner
diameter (Øi)
(a)
Insulation thickness
(t)
6.3.1Refrigerant piping requirements
INFORMATION
Also read the precautions and requirements in the
"General safety precautions" chapter.
CHYHBH05+08AA + EHYKOMB33A
Daikin hybrid for multi heat pump – heat pump module
4P471761-1 – 2016.12
If the temperature is higher than 30°C and the humidity is higher
than RH 80%, the thickness of the insulation materials should be at
least 20 mm to prevent condensation on the surface of the
insulation.
Use separate thermal insulation pipes for the gas and liquid
refrigerant piping.
6.4Preparing water piping
6.4.1Water circuit requirements
INFORMATION
Also read the precautions and requirements in the
"General safety precautions" chapter.
Installer reference guide
17
6 Preparation
M
89°C
RAD1 RAD2 RAD3
95°C
65°C
abd e
j
k
i
cfg
FCU1
FCU2
FCU3
hg
l
NOTICE
In case of plastic pipes, make sure they are fully oxygen
diffusion tight according to DIN 4726. The diffusion of
oxygen into the piping can lead to excessive corrosion.
▪ Connecting piping – Legislation. Make all piping connections in
accordance with the applicable legislation and the instructions in
the "Installation" chapter, respecting the water inlet and outlet.
▪ Connecting piping – Force. Do NOT use excessive force when
connecting the piping. Deformation of the piping can cause
malfunctioning of the unit.
▪ Connecting piping – Tools. Only use appropriate tooling to
handle brass, which is a soft material. If NOT, pipes will get
damaged.
▪ Connecting piping – Air, moisture, dust. If air, moisture or dust
gets into the circuit, problems may occur. To prevent this:
▪ Only use clean pipes
▪ Hold the pipe end downwards when removing burrs.
▪ Cover the pipe end when inserting it through a wall, to prevent
dust and/or particles entering the pipe.
▪ Use a decent thread sealant to seal connections.
▪ Closed circuit. Use the indoor unit ONLY in a closed water
system. Using the system in an open water system will lead to
excessive corrosion.
▪ Piping length. It is recommended to avoid long runs of piping
between the domestic hot water tank and the hot water end point
(shower, bath,…) and to avoid dead ends.
▪ Piping diameter. Select the water piping diameter in relation to
the required water flow and the available external static pressure
of the pump. See "15 Technical data"on page84 for the external
static pressure curves of the indoor unit.
▪ Field supply components – Water. Only use materials that are
compatible with water used in the system and with the materials
used in the indoor unit.
▪ Field supply components – Water pressure and temperature.
Check that all components in the field piping can withstand the
water pressure and water temperature.
▪ Water temperature – Heat pump convectors. In case heat
pump convectors are connected, the temperature of the water in
the convectors should NOT exceed 65°C. If necessary, install a
thermostatic controlled valve.
▪ Water temperature – Underfloor heating loops. In case
underfloor heating loops are connected, install a mixing station to
prevent water that is too hot from entering the underfloor heating
circuit.
▪ Water temperature. All installed piping and piping accessories
(valve, connections,…) MUST withstand the following
temperatures:
INFORMATION
The following illustration is an example and might NOT
match your system layout.
a Outdoor unit
b Indoor unit
c Heat exchanger
d Boiler
e Bypass valve
f Pump
g Shut-off valve (field supply)
h Motorised 3-way valve (in option kit)
i Collector
j Domestic hot water tank (optional)
k Heat exchanger coil
l Direct expansion unit
FCU1...3 Fan coil unit (optional)
RAD1…3 Radiator (field supply)
▪ Drainage – Low points. Provide drain taps at all low points of the
system in order to allow complete drainage of the water circuit.
▪ Air vents. Provide air vents at all high points of the system, which
must also be easily accessible for servicing. An automatic air
purge is provided in the indoor unit. Check that the air purge is
NOT tightened too much, so that automatic release of air in the
water circuit is possible.
▪ Zn-coated parts. Never use Zn-coated parts in the water circuit.
Because the unit's internal water circuit uses copper piping,
excessive corrosion may occur.
▪ Non-brass metallic piping. When using non-brass metallic
piping, insulate the brass and non-brass properly so that they do
NOT make contact with each other. This to prevent galvanic
corrosion.
▪ Valve – Separating circuits. When using a 3-way valve in the
water circuit make sure that the domestic hot water circuit and the
floor heating circuit is fully separated.
▪ Valve – Change‑over time. When using a 2-way valve or a 3-way
valve in the water circuit, the maximum change-over time of the
valve must be 60seconds.
▪ Filter. It is strongly recommended to install an additional filter on
the heating water circuit. Especially to remove metallic particles
from foul heating piping, it is recommended to use a magnetic or
cyclone filter, which can remove small particles. Small particles
may damage the unit and will NOT be removed by the standard
filter of the heat pump system.
▪ Dirt separator – Old heating installations. In case of old heating
installations, it is recommended to use a dirt separator. Dirt or
sediment from the heating installation can damage the unit and
reduce its lifetime. The domestic hot water circuit can also be
protected by a filter to prevent failure during domestic hot water
operation.
▪ Domestic hot water tank – Capacity. To avoid stagnation of
water, it is important that the storage capacity of the domestic hot
water tank meets the daily consumption of domestic hot water.
Installer reference guide
18
Daikin hybrid for multi heat pump – heat pump module
CHYHBH05+08AA + EHYKOMB33A
4P471761-1 – 2016.12
▪ Domestic hot water tank – After installation. Immediately after
c
d
ab
RAD1 RAD2 RAD3
T
95°C
abd e
hg
cf
gi
50
0.3
0.4
0.6
0.8
1
1.2
1.4
1.6
1.8
2
2.2
2.4
2.6
1001502002503003504004500
a
b
installation, the domestic hot water tank must be flushed with fresh
water. This procedure must be repeated at least once a day the
first 5 consecutive days after installation.
▪ Domestic hot water tank – Standstills. In cases where during
longer periods of time there is no consumption of hot water, the
equipment MUST be flushed with fresh water before usage.
▪ Domestic hot water tank – Disinfection. For the disinfection
function of the domestic hot water tank, see "Domestic hot water
control: advanced"on page57.
▪ Domestic hot water tank – 3rd party tank installation. When
installing a 3rd party tank, take following requirements into
account:
▪ coil size should be ≥0.45m2,
▪ water piping is ≥3/4" to avoid high pressure drops,
▪ a sensor pocket is foreseen at a correct place (above the
heating coil). The tank sensor should not be in contact with
water.
▪ maximum tank set point for a 3rd party tank is 60°C,
▪ in case of an electrical heater in the tank, make sure it is
installed correctly (above the heating coil).
Refer to the installation manual of the domestic hot water tank for
more information.
▪ Thermostatic mixing valves. In accordance with the applicable
legislation, it may be necessary to install thermostatic mixing
valves.
▪ Hygienic measures. The installation must be in compliance with
the applicable legislation and may require additional hygienic
installation measures.
▪ Recirculation pump. In accordance with the applicable
legislation, it may be required to connect a recirculation pump in
between the hot water end point and the recirculation connection
of the domestic hot water tank.
6 Preparation
a Outdoor unit
b Indoor unit
c Heat exchanger
d Boiler
e Bypass valve
f Pump
g Shut‑off valve (field supply)
h Collector
i Bypass valve (field supply)
RAD1…3 Radiator (field supply)
Maximum water volume
Use the following graph to determine the maximum water volume for
the calculated pre-pressure.
6.4.2Formula to calculate the expansion vessel
The pre-pressure (Pg) of the vessel depends on the installation
height difference (H):
Pg=0.3+(H/10) (bar)
6.4.3To check the water volume and flow rate
The indoor unit has an expansion vessel of 10litre with a factory set
pre-pressure of 1bar.
To make sure that the unit operates properly:
▪ You must check the minimum and maximum water volume.
▪ You might need to adjust the pre-pressure of the expansion
vessel.
CHYHBH05+08AA + EHYKOMB33A
Daikin hybrid for multi heat pump – heat pump module
4P471761-1 – 2016.12
a Recirculation connection
b Hot water connection
c Shower
d Recirculation pump
pre-pressure
a Pre-pressure (bar)
b Maximum water volume (l)
Maximum leaving water temperature of 55°C for underfloor
heating applications
Maximum leaving water temperature of 80°C for radiator
applications
Example in case of an underfloor heating application: Maximum
water volume and expansion vessel pre-pressure in case of
55°C
Installation
height
difference
(a)
≤280l>280l
≤7mNo pre-pressure
adjustment is required.
Water volume
Do the following:
▪ Decrease the pre-
pressure.
▪ Check if the water
volume does NOT
exceed the maximum
allowed water volume.
Installer reference guide
19
6 Preparation
a
Installation
height
difference
>7mDo the following:
Example in case of a radiator application: Maximum water
volume and expansion vessel pre-pressure in case of 80°C
Installation
difference
≤7mNo pre-pressure
>7mDo the following:
Minimum flow rate
Check that the minimum flow rate (required during defrost/backup
heater operation) in the installation is guaranteed in all conditions.
Minimum required flow rate
05+08 models9l/min
See the recommended procedure as described in "10.4 Checklist
during commissioning"on page70.
(a)
▪ Increase the pre-
▪ Check if the water
(a) This is the height difference (m) between the highest point
of the water circuit and the indoor unit. If the indoor unit is
at the highest point of the installation, the installation height
is 0m.
height
(a)
adjustment is required.
▪ Increase the pre-
▪ Check if the water
(a) This is the height difference (m) between the highest point
of the water circuit and the indoor unit. If the indoor unit is
at the highest point of the installation, the installation height
is 0m.
NOTICE
When circulation in each or certain space heating loops is
controlled by remotely controlled valves, it is important that
the minimum flow rate is guaranteed, even if all valves are
closed. In case the minimum flow rate cannot be reached,
a flow error 7H will be generated (no heating/operation).
≤280l>280l
pressure.
volume does NOT
exceed the maximum
allowed water volume.
≤140l>140l
pressure.
volume does NOT
exceed the maximum
allowed water volume.
Water volume
The expansion vessel of
the indoor unit is too
small for the installation.
In this case, it is
recommended to install
an extra vessel outside
the unit.
Water volume
Do the following:
▪ Decrease the pre-
pressure.
▪ Check if the water
volume does NOT
exceed the maximum
allowed water volume.
The expansion vessel of
the indoor unit is too
small for the installation.
In this case, it is
recommended to install
an extra vessel outside
the unit.
▪ Inappropriate setting of the expansion vessel pre-pressure will
lead to malfunction of the system.
Changing the pre-pressure of the expansion vessel should be done
by releasing or increasing nitrogen pressure through the Schrader
valve of the expansion vessel.
a Schrader valve
6.4.5To check the water volume: Examples
Example 1
The indoor unit is installed 5 m below the highest point in the water
circuit. The total water volume in the water circuit is 100l.
No actions or adjustments are required for either underfloor heating
loops or radiators.
Example 2
The indoor unit is installed at the highest point in the water circuit.
The total water volume in the water circuit is 350 l. Radiators are
installed, so use the graph of 80°C.
Actions:
▪ Because the total water volume (350l) is more than the default
water volume (140l), the pre-pressure must be decreased.
▪ The required pre-pressure is:
Pg = (0.3+(H/10))bar = (0.3+(0/10))bar=0.3bar.
▪ The corresponding maximum water volume at 0.3 bar is 205 l.
(See the graph in the chapter above).
▪ Because 350 l is more than 205l, the expansion vessel is too
small for the installation. Therefore install an extra vessel outside
the installation.
6.5Preparing electrical wiring
6.5.1About preparing electrical wiring
INFORMATION
Also read the precautions and requirements in the
"General safety precautions" chapter.
6.4.4Changing the pre-pressure of the
expansion vessel
NOTICE
Only a licensed installer may adjust the pre-pressure of the
expansion vessel.
When changing the default pre-pressure of the expansion vessel
(1bar) is required, take following guidelines into account:
▪ Only use dry nitrogen to set the expansion vessel pre-pressure.
Installer reference guide
20
Daikin hybrid for multi heat pump – heat pump module
CHYHBH05+08AA + EHYKOMB33A
4P471761-1 – 2016.12
6 Preparation
1
5
8
0
1
5
0
0
0
2
a
3
M
4
7
8
9
10
14
15
11
2
5
6
12
c
a
d
b
13
3
1
WARNING
▪ If the power supply has a missing or wrong N-phase,
equipment might break down.
▪ Establish proper earthing. Do NOT earth the unit to a
utility pipe, surge absorber, or telephone earth.
Incomplete earthing may cause electrical shock.
▪ Install the required fuses or circuit breakers.
▪ Secure the electrical wiring with cable ties so that the
cables do NOT come in contact with sharp edges or
piping, particularly on the high-pressure side.
▪ Do NOT use taped wires, stranded conductor wires,
extension cords, or connections from a star system.
They can cause overheating, electrical shock or fire.
▪ Do NOT install a phase advancing capacitor, because
this unit is equipped with an inverter. A phase
advancing capacitor will reduce performance and may
cause accidents.
WARNING
▪ All wiring must be performed by an authorized
ItemDescriptionWiresMaximum
electrician and must comply with the applicable
legislation.
▪ Make electrical connections to the fixed wiring.
Outdoor unit and indoor unit power supply
1Power supply for
▪ All components procured on the site and all electrical
construction must comply with the applicable
legislation.
2Power supply and
WARNING
ALWAYS use multicore cable for power supply cables.
6.5.2Overview of electrical connections except
external actuators
Power supply
3Power supply gas
User interface
4User interface2
Optional equipment
53‑way valve3100mA
6Domestic hot water
7Room thermostat/heat
8Outdoor ambient
9Indoor ambient
Field supplied components
10Shut-off valve2100mA
11Domestic hot water
a Power supply
1 Power supply for outdoor unit
2 Power supply and interconnection cable to indoor unit
3 Power supply for gas boiler
12Alarm output2
13Changeover to external
14Space heat operation
6.5.3Overview of electrical connections for
external and internal actuators
The following illustration shows the required field wiring.
INFORMATION
The following illustration is an example and might NOT
match your system layout.
CHYHBH05+08AA + EHYKOMB33A
Daikin hybrid for multi heat pump – heat pump module
4P471761-1 – 2016.12
15Safety thermostat2
a Outdoor unit
b Indoor unit
c Gas boiler
d Domestic hot water tank
running
current
2+GND
(a)
outdoor unit
3+GND
(g)
interconnection cable to
indoor unit
2+GND
(c)
boiler
(f)
2
(d)
tank thermistor
3 or 4100mA
pump convector
2
(b)
temperature sensor
2
(b)
temperature sensor
2
(b)
pump
(b)
2
(b)
heat source control
2
(b)
control
(e)
(a) Refer to name plate on outdoor unit.
(b) Minimum cable section 0.75mm².
(c) Use the cable supplied with the boiler.
(d) The thermistor and connection wire (12m) are delivered
with the domestic hot water tank.
(e) Cable section 0.75mm² till 1.25mm²; maximum length:
50m. Voltage-free contact shall ensure the minimum
applicable load of 15VDC, 10mA.
(f) Cable section 0.75mm² till 1.25mm²; maximum length:
500m. Applicable for both single user interface and dual
user interface connection.
(g) Cable section 1.5mm2; maximum length: 50m.
Installer reference guide
(b)
(b)
(b)
21
7 Installation
2×
2×
2
4
5
3
6
6
7
8
NOTICE
More technical specifications of the different connections
are indicated on the inside of the indoor unit.
7Installation
7.1Overview: Installation
This chapter describes what you have to do and know on-site to
install the system.
Typical workflow
Installation typically consists of the following stages:
1Mounting the outdoor unit.
2Mounting the indoor unit.
3Mounting the gas boiler.
4Connecting the condensate pipe.
5Connecting the refrigerant piping.
6Checking the refrigerant piping.
7Charging refrigerant.
8Connecting the water piping.
9Connecting the electrical wiring.
10 Connecting the gas piping.
11 Connecting the boiler to the flue gas system.
12 Finishing the outdoor installation.
13 Finishing the indoor installation.
14 Finishing the gas boiler installation.
INFORMATION
Depending on the units and/or the installation conditions, it
might be necessary to connect electrical wiring before you
can charge refrigerant.
4 Remove the upper and lower screw on the front panel of the
switch box.
5 The front panel of the switch box will open.
When the boiler is installed and access to the switch box is required,
please follow the steps below.
6 Remove the upper and lower screw on the side panel of the
switch box.
7 Remove the switch box from the unit.
8 Hook the switch box to the side of the unit with the hooks
foreseen on the switch box.
INFORMATION
It is NOT possible to connect an indoor unit of 1 room only.
Be sure to connect indoor units of at least 2 rooms.
The Hybrid for Multi is considered as 1 room connection.
For the correct combination, see the combination table and the
installation manual of the Hybrid for Multi.
7.2Opening the units
7.2.1About opening the units
At certain times, you have to open the unit. Example:
▪ When connecting the electrical wiring
▪ When maintaining or servicing the unit
DANGER: RISK OF ELECTROCUTION
Do NOT leave the unit unattended when the service cover
is removed.
7.2.2To open the switch box cover of the
indoor unit
1 Remove the side panel at the right side of the indoor unit. The
side panel is fixed at the bottom with 1 screw.
2 Remove the upper and lower screw on the side panel of the
switch box.
3 The right panel of the switch box will open.
Installer reference guide
22
Daikin hybrid for multi heat pump – heat pump module
CHYHBH05+08AA + EHYKOMB33A
4P471761-1 – 2016.12
7 Installation
1
2
213
2×
30kg
7.2.3To open the gas boiler
1 Open the display cover.
2 Unscrew both screws.
3 Tilt the front panel towards you and remove the front panel.
7.3.2Precautions when mounting the indoor
unit
INFORMATION
Also read the precautions and requirements in the
following chapters:
▪ General safety precautions
▪ Preparation
7.3.3To install the indoor unit
1 Put the installation pattern (see box) on the wall and follow the
steps as shown below.
2 Fix the wall bracket to the wall with 2 M8 bolts.
7.2.4To open the switch box cover of the gas
boiler
1 Open the gas boiler, see "7.2.3 To open the gas boiler" on
page23.
2 Pull the boiler controller unit forwards. The boiler controller will
tip downwards to provide access.
7.3Mounting the indoor unit
3 Lift the unit.
7.3.1About mounting the indoor unit
When
You have to mount the outdoor and indoor unit before you can
connect the refrigerant and water piping.
Typical workflow
Mounting the indoor unit typically consists of the following stages:
1Installing the indoor unit.
CHYHBH05+08AA + EHYKOMB33A
Daikin hybrid for multi heat pump – heat pump module
4P471761-1 – 2016.12
4 Tilt the top of the unit against the wall at the position of the wall
bracket.
Installer reference guide
23
7 Installation
36kg
5 Slide the bracket on the back of the unit over the wall bracket.
Make sure the unit is fixed properly. You can additionally fix the
bottom side of the unit with 2 M8 bolts.
6 The unit is mounted to the wall.
6 Slide the boiler downwards to fix the boiler bracket onto the
indoor unit mounting bracket.
7.4Mounting the gas boiler
INFORMATION
Removing the top plate of the indoor unit makes it easier to
install the gas boiler.
7.4.1To install the gas boiler
1 Lift the unit from the package.
2 Remove the top plate from the indoor unit.
3 The bracket to mount the boiler on the heat pump module is
already mounted to the backside of the gas boiler.
4 Lift the boiler. One person lifts the gas boiler on the left side (left
hand on the top and right hand on the bottom) and another
person lift the gas boiler on the right side (left hand on the
bottom and right hand on the top).
5 Tilt the top of the unit at the position of the indoor unit mounting
bracket.
7 Make sure the gas boiler is fixed properly and well aligned with
the indoor unit.
7.4.2To install the condensate trap
INFORMATION
The boiler is provided with a 25mm flexible pipe on the
condensate trap.
Prerequisite: The boiler MUST be opened before installing the
condensate trap.
1 Fit the flexible tube (accessory) to the condensate trap outlet.
2 Fill the condensate trap with water.
3 Slide the condensate trap as far as possible upwards onto the
condensate drain connector below the gas boiler.
Installer reference guide
24
CHYHBH05+08AA + EHYKOMB33A
Daikin hybrid for multi heat pump – heat pump module
4P471761-1 – 2016.12
4 Connect the flexible tube (where applicable with the overflow
Ø22 mm
a
b
c
a
b
c
d
≥75 mm
Ø22 mm
100 mm
pipe from the pressure relief valve) to the drain via an open
connection.
7 Installation
7.5Condensate pipe work
INFORMATION
The condensate discharge system MUST be made of
plastic, no other materials may be used. The discharge
duct MUST have a minimum gradient of 5~20 mm/m.
Condensate discharge via the gutter is NOT allowed due to
risk of frost and the possible damage to the materials.
7.5.1Internal connections
If possible, the condensate drain pipe should be routed and
terminated so that the condensate drains away from the boiler under
gravity to a suitable internal foul water discharge point such as an
internal soil and vent stack. A suitable permanent connection to the
foul waste pipe should be used.
a Condensate discharge from boiler
b Soil and vent stack
c Minimum 450mm and up to 3 storeys
If the first option is NOT possible, an internal kitchen or bathroom
WARNING
▪ ALWAYS fill the condensate trap with water and place
it on the boiler before powering up the boiler. See
illustration below.
▪ NOT placing or filling up the condensate trap may
cause flue gases to come into the installation room and
can lead to dangerous situations!
▪ In order to place the condensate trap, the front cover
MUST be pulled forward or removed entirely.
NOTICE
It is recommended that any external condensate pipe is
insulated and increased to Ø32mm in order to prevent the
condensate from freezing.
waste pipe, washing machine pipe can be used. Make sure that the
condensate drain pipe is connected downstream of the waste trap.
a Condensate discharge from boiler
b Soil and vent stack
c Sink or basin with integrate overflow
d 75mm waste trap and air break
Condensate pump
Where gravity discharge to an internal termination is NOT physically
possible or where very long internal runs of drainage pipe would be
required to reach a suitable discharge point, condensate should be
removed by using a proprietary condensate pump (field supply).
The pump outlet pipe should discharge to a suitable internal foul
water discharge point such as an internal soil and vent stack,
internal kitchen, bathroom waste pipe, or washing machine waste
pipe. A suitable permanent connection to the foul waste pipe should
be used.
CHYHBH05+08AA + EHYKOMB33A
Daikin hybrid for multi heat pump – heat pump module
4P471761-1 – 2016.12
Installer reference guide
25
7 Installation
Ø22 mm
c
≥75 mm
a
b
d
e
a Condensate discharge from boiler
b Soil and vent stack
c Sink or basin with integrated overflow
d 75mm waste trap and air break
e Condensate pump
7.6.2Precautions when connecting the
refrigerant piping
INFORMATION
Also read the precautions and requirements in the
following chapters:
▪ General safety precautions
▪ Preparation
DANGER: RISK OF BURNING
CAUTION
▪ Do NOT use mineral oil on flared part.
▪ Do NOT reuse piping from previous installations.
▪ NEVER install a drier to this R32 unit to guarantee its
lifetime. The drying material may dissolve and damage
the system.
7.5.2External connections
If an externally condensate drainage pipe is used, following
measures should be made to prevent freezing:
▪ The pipe should be run internally as far as possible before going
to the outside. The pipe diameter should be increased to a
minimum inner diameter of 30 mm (typically outer diameter of
32mm) before it goes through the wall.
▪ The external run should be kept as short as possible, taking the
most vertical route possible to the discharge point. Take into
account that there are no horizontal section in which condensate
might collect.
▪ The external pipe should be insulated. Use a suitable waterproof
and weather proof insulation ("ClassO" pipe insulation is suitable
for this purpose).
▪ The use of fittings and elbows should be kept to a minimum. Any
internal burrs should be removed so that the internal pipe section
is as smooth as possible.
7.6Connecting the refrigerant piping
7.6.1About connecting the refrigerant piping
Before connecting the refrigerant piping
Make sure the outdoor and indoor unit are mounted.
Typical workflow
Connecting the refrigerant piping involves:
▪ Connecting the refrigerant piping to the outdoor unit
▪ Connecting the refrigerant piping to the indoor unit
▪ Insulating the refrigerant piping
▪ Keeping in mind the guidelines for:
▪ Pipe bending
▪ Flaring pipe ends
▪ Brazing
▪ Using the stop valves
CAUTION
▪ Use the flare nut fixed to the main unit.
▪ To prevent gas leakage, apply refrigeration oil only to
the inside of the flare. Use refrigeration oil for R32.
▪ Do not reuse joints.
NOTICE
Take the following precautions on refrigerant piping into
account:
▪ Avoid anything but the designated refrigerant to get
mixed into the refrigerant cycle (e.g. air).
▪ Only use R32 when adding refrigerant.
▪ Only use installation tools (e.g. manifold gauge set) that
are exclusively used for R32 installations to withstand
the pressure and to prevent foreign materials (e.g.
mineral oils and moisture) from mixing into the system.
▪ Install the piping so that the flare is NOT subjected to
mechanical stress.
▪ Protect the piping as described in the following table to
prevent dirt, liquid or dust from entering the piping.
▪ Use caution when passing copper tubes through walls
(see figure below).
UnitInstallation periodProtection method
Outdoor unit>1monthPinch the pipe
<1monthPinch or tape the pipe
Indoor unitRegardless of the
period
INFORMATION
Do NOT open the refrigerant stop valve before checking
the refrigerant piping. When you need to charge additional
refrigerant it is recommended to open the refrigerant stop
valve after charging.
Installer reference guide
26
CHYHBH05+08AA + EHYKOMB33A
Daikin hybrid for multi heat pump – heat pump module
4P471761-1 – 2016.12
7 Installation
ab
c
d
R=0.4~0.8
45°
±2
90°
±2
A
ab
A
ab
c
abcde
f
f
c
d
a
b
WARNING
Connect the refrigerant piping securely before running the
compressor. If the refrigerant piping is not connected and
the stop valve is open when the compressor is run, air will
be sucked in. This will cause abnormal pressure in the
refrigeration cycle, which may result in equipment damage
and even injury.
7.6.3Guidelines when connecting the
refrigerant piping
Take the following guidelines into account when connecting pipes:
▪ Coat the flare inner surface with ether oil or ester oil when
connecting a flare nut. Tighten 3 or 4 turns by hand, before
tightening firmly.
▪ Always use 2 wrenches together when loosening a flare nut.
▪ Always use a spanner and torque wrench together to tighten the
flare nut when connecting the piping. This to prevent nut cracking
and leaks.
3 Remove the flare nut from the stop valve and put the flare nut
on the pipe.
4 Flare the pipe. Set exactly at the position as shown in the
following illustration.
5 Check that the flaring is properly made.
a Flare’s inner surface must be flawless.
b The pipe end must be evenly flared in a perfect circle.
c Make sure the flare nut is fitted.
7.6.6To braze the pipe end
The indoor unit and outdoor unit have flare connections. Connect
both ends without brazing. If brazing should be needed, take the
following into account:
▪ When brazing, blow through with nitrogen to prevent creation of
large quantities of oxidised film on the inside of the piping. This
film adversely affects valves and compressors in the refrigerating
system and prevents proper operation.
▪ Set the nitrogen pressure to 20kPa (0.2bar) (just enough so it
can be felt on the skin) with a pressure-reducing valve.
a Torque wrench
b Spanner
c Piping union
d Flare nut
Piping size
(mm)
Tightening
torque (N•m)
Flare
dimensions (A)
Flare shape
(mm)
(mm)
Ø6.414.2~17.28.7~9.1
Ø9.532.7~39.9
Ø12.749.5~60.316.2~16.6
Ø15.961.8~75.419.3~19.7
7.6.4Pipe bending guidelines
Use a pipe bender for bending. All pipe bends should be as gentle
as possible (bending radius should be 30~40mm or larger).
7.6.5To flare the pipe end
CAUTION
▪ Incomplete flaring may cause refrigerant gas leakage.
▪ Do NOT re-use flares. Use new flares to prevent
refrigerant gas leakage.
▪ Use flare nuts that are included with the unit. Using
different flare nuts may cause refrigerant gas leakage.
1 Cut the pipe end with a pipe cutter.
2 Remove burrs with the cut surface facing down so that the
chips do not enter the pipe.
a Refrigerant piping
b Part to be brazed
c Taping
d Manual valve
e Pressure-reducing valve
f Nitrogen
▪ Do NOT use anti-oxidants when brazing pipe joints.
Residue can clog pipes and break equipment.
▪ Do NOT use flux when brazing copper-to-copper refrigerant
piping. Use phosphor copper brazing filler alloy (BCuP), which
does not require flux.
Flux has an extremely harmful influence on refrigerant piping
systems. For instance, if chlorine based flux is used, it will cause
pipe corrosion or, in particular, if the flux contains fluorine, it will
deteriorate the refrigerant oil.
7.6.7Using the stop valve and service port
To handle the stop valve
Take the following guidelines into account:
▪ The stop valves are factory closed.
▪ The following illustration shows each part required in handling the
valve.
a Cut exactly at right angles.
b Remove burrs.
CHYHBH05+08AA + EHYKOMB33A
Daikin hybrid for multi heat pump – heat pump module
4P471761-1 – 2016.12
a Service port and service port cap
b Valve stem
c Field piping connection
d Stem cap
Installer reference guide
27
7 Installation
a
b
b
a
▪ Keep both stop valves open during operation.
▪ Do NOT apply excessive force to the valve stem. Doing so may
break the valve body.
▪ Always make sure to secure the stop valve with a spanner, then
loosen or tighten the flare nut with a torque wrench. Do NOT place
the spanner on the stem cap, as this could cause a refrigerant
leak.
a Spanner
b Torque wrench
▪ When it is expected that the operating pressure will be low (e.g.
when cooling will be performed while the outside air temperature
is low), sufficiently seal the flare nut in the stop valve on the gas
line with silicon sealant to prevent freezing.
Silicon sealant, make sure there is no gap.
To open/close the stop valve
1 Remove the valve cover.
2 Insert a hexagon wrench (liquid side: 4mm, gas side: 6mm)
into the valve stem and turn the valve stem:
ItemTightening torque (N∙m)
Service port cap10.8~14.7
7.6.8Usage of reducers to connect the piping
to the outdoor unit
For connecting the piping to the outdoor unit, you (possibly) need
reducers. Please consult following table to see where you need
which reducer.
Port3MXM52
4MXM684MXM805MXM90
3MXM68
ACHYHBH05
BCHYHBH05
CCHYHBH05
(a)
CHYHBH05
(b)
CHYHBH05
(b)
CHYHBH05
D—CHYHBH05
(a)
CHYHBH05
CHYHBH08
(a)
CHYHBH05
CHYHBH08
(b)
CHYHBH05
CHYHBH08
(b)
CHYHBH05
CHYHBH08
(a)
CHYHBH05
(a)
CHYHBH08
(b)
CHYHBH05
(b)
CHYHBH08
CHYHBH05
CHYHBH08
CHYHBH05
CHYHBH08
E———CHYHBH05
CHYHBH08
— Connection of CHYHBH05 or CHYHBH08 is NOT possible.
(a) Use reducers number 5 and 6 (Ø15.9mm to Ø9.5mm).
(b) Use reducers number 1 and 3 (Ø15.9mm to Ø12.7mm).
7.6.9To connect the refrigerant piping to the
indoor unit
1 Connect the liquid stop valve from the outdoor unit to the
refrigerant liquid connection of the indoor unit.
(a)
(a)
(a)
(a)
(b)
(b)
Counterclockwise to open.
Clockwise to close.
3 When the valve stem cannot be turned any further, stop turning.
The valve is now opened/closed.
To handle the stem cap
▪ The stem cap is sealed where indicated with the arrow. Do NOT
damage it.
▪ After handling the stop valve, tighten the stem cap, and check for
refrigerant leaks.
ItemTightening torque (N∙m)
Stem cap, liquid side13.5~16.5
Stem cap, gas side22.5~27.5
To handle the service cap
▪ Always use a charge hose equipped with a valve depressor pin,
since the service port is a Schrader type valve.
▪ After handling the service port, tighten the service port cap, and
check for refrigerant leaks.
a Refrigerant liquid connection
b Refrigerant gas connection
2 Connect the gas stop valve from the outdoor unit to the
refrigerant gas connection of the indoor unit.
NOTICE
It is recommended that the refrigerant piping between
indoor and outdoor unit is installed in a ducting or the
refrigerant piping is wrapped with finishing tape.
Installer reference guide
28
Daikin hybrid for multi heat pump – heat pump module
CHYHBH05+08AA + EHYKOMB33A
4P471761-1 – 2016.12
7 Installation
a
h
b
f
h
i
e
c
d
e
g
j
7.7Checking the refrigerant piping
7.7.1About checking the refrigerant piping
The outdoor unit's internal refrigerant piping has been factory tested
for leaks. You only have to check the outdoor unit's external
refrigerant piping.
Before checking the refrigerant piping
Make sure the refrigerant piping is connected between the outdoor
unit and the indoor unit.
Typical workflow
Checking the refrigerant piping typically consists of the following
stages:
1Checking for leaks in the refrigerant piping.
2Performing vacuum drying to remove all moisture, air or
nitrogen from the refrigerant piping.
If there is a possibility of moisture being present in the refrigerant
piping (for example, water may have entered the piping), first carry
out the vacuum drying procedure below until all moisture has been
removed.
7.7.2Precautions when checking the
refrigerant piping
INFORMATION
Also read the precautions and requirements in the
following chapters:
▪ General safety precautions
▪ Preparation
NOTICE
Use a 2-stage vacuum pump with a non-return valve that
can evacuate to a gauge pressure of −100.7 kPa
(−1.007 bar)(5 Torr absolute). Make sure the pump oil
does not flow oppositely into the system while the pump is
not working.
NOTICE
Use this vacuum pump for R32 exclusively. Using the
same pump for other refrigerants may damage the pump
and the unit.
NOTICE
▪ Connect the vacuum pump to the service port of the
gas stop valve.
▪ Make sure that the gas stop valve and liquid stop valve
are firmly closed before performing the leak test or
vacuum drying.
7.7.3To check for leaks
NOTICE
Do NOT exceed the unit's maximum working pressure (see
"PS High" on the unit name plate).
NOTICE
Make sure to use a recommended bubble test solution
from your wholesaler. Do not use soap water, which may
cause cracking of flare nuts (soap water may contain salt,
which absorbs moisture that will freeze when the piping
gets cold), and/or lead to corrosion of flared joints (soap
water may contain ammonia which causes a corrosive
effect between the brass flare nut and the copper flare).
1 Charge the system with nitrogen gas up to a gauge pressure of
at least 200 kPa (2 bar). It is recommended to pressurize to
3000kPa (30bar) in order to detect small leaks.
2 Check for leaks by applying the bubble test solution to all
connections.
3 Discharge all nitrogen gas.
7.7.4To perform vacuum drying
Connect the vacuum pump and manifold as follows:
a Pressure meter
b Gauge manifold
c Low-pressure valve (Lo)
d High-pressure valve (Hi)
e Charging hoses
f Vacuum pump
g Service port
h Valve lids
i Gas stop valve
j Liquid stop valve
1 Vacuum the system until the pressure on the manifold indicates
−0.1MPa (−1bar).
2 Leave as is for 4-5minutes and check the pressure:
If the pressure…Then…
Does not changeThere is no moisture in the
system. This procedure is
finished.
IncreasesThere is moisture in the
system. Go to the next step.
3 Evacuate for at least 2 hours to a pressure on the manifold of
−0.1MPa (−1bar).
4 After turning OFF the pump, check the pressure for at least
1hour.
5 If you do NOT reach the target vacuum or cannot maintain the
vacuum for 1hour, do the following:
▪ Check for leaks again.
▪ Perform vacuum drying again.
NOTICE
Be sure to open the gas stop valve after piping installation
and vacuuming. Running the system with the valve closed,
the compressor may break down.
INFORMATION
After opening the stop valve, it is possible that the pressure
in the refrigerant piping does NOT increase. This might be
caused by e.g. the closed state of the expansion valve in
the outdoor unit circuit, but does NOT present any problem
for correct operation of the unit.
7.8Charging refrigerant
7.8.1About charging refrigerant
The outdoor unit is factory charged with refrigerant, but in some
cases the following might be necessary:
CHYHBH05+08AA + EHYKOMB33A
Daikin hybrid for multi heat pump – heat pump module
4P471761-1 – 2016.12
Installer reference guide
29
7 Installation
WhatWhen
Charging additional refrigerantWhen the total liquid piping
length is more than specified
(see later).
Completely recharging refrigerant Example:
▪ When relocating the system.
▪ After a leak.
Charging additional refrigerant
Before charging additional refrigerant, make sure the outdoor unit's
external refrigerant piping is checked (leak test, vacuum drying).
INFORMATION
Depending on the units and/or the installation conditions, it
might be necessary to connect electrical wiring before you
can charge refrigerant.
Typical workflow – Charging additional refrigerant typically consists
of the following stages:
1 Determining if and how much you have to charge additionally.
2 If necessary, charging additional refrigerant.
3 Filling in the fluorinated greenhouse gases label, and fixing it to
the inside of the outdoor unit.
Completely recharging refrigerant
Before completely recharging refrigerant, make sure the following is
done:
1 All refrigerant is recovered from the system.
2 The outdoor unit's external refrigerant piping is checked (leak
test, vacuum drying).
3 Vacuum drying on the outdoor unit's internal refrigerant piping is
performed.
Typical workflow – Completely recharging refrigerant typically
consists of the following stages:
1 Determining how much refrigerant to charge.
2 Charging refrigerant.
3 Filling in the fluorinated greenhouse gases label, and fixing it to
the inside of the outdoor unit.
7.8.2About the refrigerant
This product contains fluorinated greenhouse gases. Do NOT vent
gases into the atmosphere.
Refrigerant type: R32
Global warming potential (GWP) value: 675
NOTICE
In Europe, the greenhouse gas emissions of the total
refrigerant charge in the system (expressed as tonnes
CO2-equivalent) is used to determine the maintenance
intervals. Follow the applicable legislation.
Formula to calculate the greenhouse gas emissions:
GWP value of the refrigerant × Total refrigerant charge [in
kg] / 1000
Please contact your installer for more information.
WARNING: FLAMMABLE MATERIAL
The refrigerant inside this unit is mildly flammable.
WARNING
▪ Do NOT pierce or burn refrigerant cycle parts.
▪ Do NOT use cleaning materials or means to accelerate
the defrosting process other than those recommended
by the manufacturer.
▪ Be aware that the refrigerant inside the system is
odourless.
WARNING
The refrigerant inside the unit is mildly flammable, but
normally does not leak. If the refrigerant leaks in the room
and comes in contact with fire from a burner, a heater, or a
cooker, this may result in fire, or the formation of a harmful
gas.
Turn off any combustible heating devices, ventilate the
room, and contact the dealer from which you purchased
the unit.
Do not use the unit until a service person confirms that the
portion from which the refrigerant leaked is repaired.
7.8.3Precautions when charging refrigerant
INFORMATION
Also read the precautions and requirements in the
following chapters:
▪ General safety precautions
▪ Preparation
7.8.4To determine the additional refrigerant
amount
INFORMATION
Piping length is the one way length of liquid piping.
If the total liquid
piping length is…
≤30mDo NOT add additional refrigerant.
>30mR=(total length (m) of liquid
piping–30m)×0.020
R=Additional charge (kg) (rounded in units
of 0.1kg)
For the maximum allowable refrigerant charge amount, see the
outdoor unit installation manual.
Then…
7.8.5To determine the complete recharge
amount
INFORMATION
If a complete recharge is necessary, the total refrigerant
charge is: the factory refrigerant charge (see unit name
plate) + the determined additional amount.
7.8.6To charge additional refrigerant
WARNING
▪ Only use R32 as refrigerant. Other substances may
cause explosions and accidents.
▪ R32 contains fluorinated greenhouse gases. Its global
warming potential (GWP) value is 675. Do NOT vent
these gases into the atmosphere.
▪ When charging refrigerant, always use protective
gloves and safety glasses.
Installer reference guide
30
Daikin hybrid for multi heat pump – heat pump module
CHYHBH05+08AA + EHYKOMB33A
4P471761-1 – 2016.12
Loading...
+ 78 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.