Specifications EDUS39-800-F8
2 BSVQ-P
1. Specifications
BS Units
Note:
★
1 In case of connecting with a 07~18 type indoor unit, match to the size of field pipe using the attached pipe.
(Connection between the attached pipe and the field pipe must be brazed.)
★
2 In case of connecting with indoor unit capacity index 54 or more and 60 or less, match to the size of the field pipe using the attached pipe.
(Connection between the attached pipe and the field pipe must be brazed.)
Model BSVQ36PVJU BSVQ60PVJU
Power Supply 1 Phase 60Hz 208~230V 1 Phase 60Hz 208~230V
Total Capacity Index of Connectable Indoor
Unit
Less than 36 Less than 60
No. of Connectable Indoor Units Max. 5 Max. 8
Casing Galvanized Steel Plate Galvanized Steel Plate
Dimensions: (H×W×D) in 8-1/8 × 15-1/4 × 12-13/16 8-1/8 × 15-1/4 × 12-13/16
Sound Absorbing Thermal Insulation
Mater ial
Foamed Polyurethane, Frame Resisting Needle Felt Foamed Polyurethane, Frame Resisting Needle Felt
Piping
Connection
Indoor
Unit
Liquid Pipes
φ
3/8 C1220T (Brazing Connection) ★1
φ
3/8 C1220T (Brazing Connection)
Gas Pipes
φ
5/8 C1220T (Brazing Connection) ★1
φ
5/8 C1220T (Brazing Connection) ★2
Outdoor
Unit
Liquid Pipes
φ
3/8 C1220T (Brazing Connection)
φ
3/8 C1220T (Brazing Connection)
Suction Gas Pipes
φ
5/8 C1220T (Brazing Connection)
φ
5/8 C1220T (Brazing Connection) ★2
Discharge Gas
Pipes
φ
1/2 C1220T (Brazing Connection)
φ
1/2 C1220T (Brazing Connection) ★2
Mass Lbs 26 26
Standard Accessories
Installation Manual, Attached Pipe, Insulation Pipe Cover,
Clamps
Installation Manual, Attached Pipe, Insulation Pipe Cover,
Clamps
Drawing No. 4D058233A 4D058234A