Daikin BSVQ-P, BSVQ36PVJU, BSVQ60PVJU Engineering Data

EDUS 39 - 800 - F8
AMERICAS
BSVQ-P
BS Units
EDUS39-800-F8
BSVQ-P
BS Units
1. Specifications ..............................................................................................2
2. Dimensions .................................................................................................3
3. Piping Diagrams..........................................................................................5
4. Wiring Diagrams..........................................................................................6
5. Electric Characteristics................................................................................7
6. Sound Levels ..............................................................................................8
7. Installation ...................................................................................................9
8. Accessories...............................................................................................24
Specifications EDUS39-800-F8
2 BSVQ-P
1. Specifications
BS Units
Note:
1 In case of connecting with a 07~18 type indoor unit, match to the size of field pipe using the attached pipe.
(Connection between the attached pipe and the field pipe must be brazed.)
2 In case of connecting with indoor unit capacity index 54 or more and 60 or less, match to the size of the field pipe using the attached pipe.
(Connection between the attached pipe and the field pipe must be brazed.)
Model BSVQ36PVJU BSVQ60PVJU
Power Supply 1 Phase 60Hz 208~230V 1 Phase 60Hz 208~230V Total Capacity Index of Connectable Indoor
Unit
Less than 36 Less than 60
No. of Connectable Indoor Units Max. 5 Max. 8 Casing Galvanized Steel Plate Galvanized Steel Plate Dimensions: (H×W×D) in 8-1/8 × 15-1/4 × 12-13/16 8-1/8 × 15-1/4 × 12-13/16 Sound Absorbing Thermal Insulation
Mater ial
Foamed Polyurethane, Frame Resisting Needle Felt Foamed Polyurethane, Frame Resisting Needle Felt
Piping Connection
Indoor Unit
Liquid Pipes
φ
3/8 C1220T (Brazing Connection) ★1
φ
3/8 C1220T (Brazing Connection)
Gas Pipes
φ
5/8 C1220T (Brazing Connection) ★1
φ
5/8 C1220T (Brazing Connection) ★2
Outdoor Unit
Liquid Pipes
φ
3/8 C1220T (Brazing Connection)
φ
3/8 C1220T (Brazing Connection)
Suction Gas Pipes
φ
5/8 C1220T (Brazing Connection)
φ
5/8 C1220T (Brazing Connection) ★2
Discharge Gas Pipes
φ
1/2 C1220T (Brazing Connection)
φ
1/2 C1220T (Brazing Connection) ★2
Mass Lbs 26 26
Standard Accessories
Installation Manual, Attached Pipe, Insulation Pipe Cover, Clamps
Installation Manual, Attached Pipe, Insulation Pipe Cover, Clamps
Drawing No. 4D058233A 4D058234A
EDUS39-800-F8 Dimensions
BSVQ-P 3
2. Dimensions
BSVQ36PVJU
φ
3/8 brazing connection
Description
φ
3/8 brazing connection
Liquid pipe connection port
Suction gas pipe connection port
Electric box (Note 1.)
Grounding terminal
φ
1/4 brazing connectionφ 5/8 brazing connection
φ
5/8 brazing connection
φ
1/2 brazing connection
M4
M8~M10
Liquid pipe connection port
Suspension brackets
Number
1234567
8
9
10
Attached pipe (2) (Note. 3)
Attached pipe (1) (Note. 3)
Part name
φ
1/2 brazing connectionHP/LP gas pipe connection port
Gas pipe connection port
(Servicing space)
Servicing space
(Servicing space)
2 or more
3 or more
(Servicing space)
10 or more
(Servicing space)
10 or more
(In case of use Attached pipe)
(Servicing space)
12 or more
(Suspension bolt pitch)
(Suspension bolt pitch)
(Servicing space)
18
(Note 2.)
8-5/812
(6-3/16)
16-7/8
(6-5/16)
Inspection door
Location of unit's Name Plate
Right side of electric box
(Note 1.)
1-7/8
2-5/88-3/8
(4-5/16)
8-1/8
6-5/8
1-7/8
15-1/4
7/8
2-1/16
10-3/16
2-13/16
(4-5/16)
4-5/8
2-13/16
5-3/16
3/8
7-9/16
3-13/16
Notes) 1. Electric box can also be fixed on the other side
of the unit.
2. Be sure to install a inspection door at electric
box side.
3. Attached pipe is only used in case of
connecting with a 07~18 class indoor unit.
4. Small sound of refrigerant will be made, which
may be disturbing.
Do not install it at the place such as bedroom
under roof.
1
2
3
4
9
5
10
7
8
6
3D058236
Dimensions EDUS39-800-F8
4 BSVQ-P
BSVQ60PVJU
(Servicing space)
(Suspension bolt pitch)
(Suspension bolt pitch)
8-5/8
(8-5/8)
(8-9/16)
12
16-7/8
(8-9/16)
18 (Note 2.)
Inspection door
10-3/16
8-3/8
(4-5/16)
15-1/4
7-9/16
3/8
3-13/16
1-7/8
4-5/8
7/8
8-1/8
(4-5/16)
2-13/16
5-3/16
2-13/16
2-1/16
6-5/8
1-7/8
2-5/8
(Note 1.)
Location of unit's Name Plate
Right side of electric box
Servicing space
(Servicing space)
(Servicing space)
2 or more
3 or more
(Servicing space)
10 or more
(Servicing space)
10 or more
(In case of use Attached pipe)
(Servicing space)
13-3/4 or more
(Servicing space)
13-3/4 or more
Notes) 1. Electric box can also be fixed on the other side
of the unit.
2. Be sure to install a inspection door at electric
box side.
3. Attached pipe is only used in case of connecting
with indoor unit capacity indey 54 or more and
60 or less.
4. Small sound of refrigerant will be made, which
may be disturbing.
Do not install it at the place such as bedroom
under roof.
φ
3/8 brazing connection
Description
φ
3/8 brazing connection
Liquid pipe connection port
Suction gas pipe connection port
Electric box (Note 1.)
Grounding terminal
φ
5/8 brazing connectionφ 5/8 brazing connection
φ
5/8 brazing connection
φ
3/4 brazing connection
M4
M8~M10
Liquid pipe connection port
Suspension brackets
Number
1234567
8
9
10
Attached pipe (2) (Note. 3)
Attached pipe (1) (Note. 3)
Part name
φ
1/2 brazing connection
HP/LP gas pipe connection port
Gas pipe connection port
19
2
10
3
4 9
5
7
6
8
3D058237
EDUS39-800-F8 Piping Diagrams
BSVQ-P 5
3. Piping Diagrams
4D057985A
Wiring Diagrams EDUS39-800-F8
6 BSVQ-P
4. Wiring Diagrams
POWER SUPPLY
~208-230V
60Hz
RED
HAP
X1A
Y4E
F1
Y1E
X5A
X1M
BLU
F1
Y3E
NOTE) 7.
F1U
Y5E
X6A
L1
OUTDOOR
UNIT
X8A
F2
DS2
INDOOR
UNIT
F2
X7A
X2M
L2
NOTE) 3.
DS1
Y2E
X4A
X1M
X2A
A1P
Z1C
N=2
PS
Y4E
M
6
6
Y3E
M
CAB
6
Y1EMY2E
6
M
6
Y5E
M
BS UNIT TOP
TO IN/D
UNIT
TO OUT/D
UNIT
Y5E
CONNECTOR FOR OPTIONAL PARTS
X2M
Y4E
NOISE FILTER (FERRITE CORE)
PRINTED CIRCUIT BOARD
F1U
Z1C
X1M (A1P)
DIP SWITCH
ELECTRIC EXPANSION VALVE (MAIN DISCHARGE)
X1MPSY1E
ELECTRIC EXPANSION VALVE (SUB DISCHARGE)
TERMINAL STRIP (CONTROL)
A1P
FLASHING LAMP
(SERVICE MONITOR-GREEN)
Y3E
ELECTRIC EXPANSION VALVE (SUB COOL)
FUSE (T, 3.15A, 250V)
Y2E
ELECTRIC EXPANSION VALVE (SUB SUCTION)DS1, DS2
ELECTRIC EXPANSION VALVE (MAIN SUCTION)
TERMINAL STRIP (C/H SELECTOR)
SWITCHING POWER SUPPLY (A1P)
TERMINAL STRIP (POWER)
X2A
HAP
CONNECTOR (WIRING EXTERNAL CONTROL
ADAPTOR FOR OUTDOOR UNIT)
BSVQ60PVJUBSVQ36PVJU
OFF
ON
DS1
1234 1234 1234 1234
DS2
DS2DS1
OFF
ON
FOR USING DIP SWITCH (DS1 · 2), REFER TO INSTALLATION MANUAL
OR "SERVICE PRECAUTION" LABEL ON EL. COMPO. BOX COVER.
NOTES) 1. THIS WIRING DIAGRAM APPLIES TO THE BS UNIT ONLY.
2. : TERMINAL STRIP, : CONNECTOR, : TERMINAL
: FIELD WIRING, : PROTECTIVE EARTH
3. WHEN USING THE COOL/HEAT SELECTOR (OPTIONAL ACCESSORY),
CONNECT IT TO TERMINALS A, B AND C ON X2M.
4. AS FOR WIRING TO THE IN/D UNIT (F1) · (F2) AND OUT/D UNIT (F1) · (F2)
ON X1M (A1P), REFER TO INSTALLATION MANUAL.
5. SYMBOLS SHOW AS FOLLOWS. (BLU : BLUE RED : RED)
6. USE COPPER CONDUCTORS ONLY.
7. DIP SWITCH (DS1 · 2) INITIAL SETTINGS ARE AS FOLLOWS.
3D058235A
EDUS39-800-F8 Electric Characteristics
BSVQ-P 7
5. Electric Characteristics
4D058238