Daikin BRR9B1V1 Installation manuals

Installation manual
Communication box
BRR9B1V1

Table of contents

Table of contents
1 About the documentation 3
1.1 About this document ...................................................................................................................................................... 3
2 General safety precautions 4
2.1 About the documentation .............................................................................................................................................. 4
2.1.1 Meaning of warnings and symbols ................................................................................................................ 4
2.2 For the installer............................................................................................................................................................... 5
2.2.1 General ........................................................................................................................................................... 5
2.2.2 Installation site ............................................................................................................................................... 6
2.2.3 Electrical ......................................................................................................................................................... 7
3 Specific installer safety instructions 9
4 About the box 10
4.1 Communication box........................................................................................................................................................ 10
4.1.1 To remove the accessories from the communication box ............................................................................ 10
5 About the communication box 11
5.1 Identification ................................................................................................................................................................... 11
5.1.1 Identification label: Communication box ....................................................................................................... 11
6 Unit installation 12
6.1 Preparing the installation site......................................................................................................................................... 12
6.1.1 Installation site requirements of the communication box ............................................................................ 12
6.2 Opening and closing the unit.......................................................................................................................................... 12
6.2.1 To open the communication box ................................................................................................................... 12
6.2.2 To close the communication box ................................................................................................................... 13
6.3 Installing the communication box .................................................................................................................................. 13
6.3.1 Precautions when installing the communication box ................................................................................... 13
6.3.2 To install the communication box .................................................................................................................. 13
7 Electrical installation 14
7.1 General overview of the field wiring .............................................................................................................................. 14
7.2 Field wiring: Overview .................................................................................................................................................... 15
7.3 Guidelines when connecting the electrical wiring ......................................................................................................... 16
7.4 Specifications of standard wiring components .............................................................................................................. 16
7.5 To connect the electrical wiring on the communication box ........................................................................................ 17
7.6 To connect the transmission wiring ............................................................................................................................... 18
7.6.1 Between communication box and outdoor unit ........................................................................................... 18
7.6.2 Between communication box and monitoring system.................................................................................. 18
7.7 To fix the wiring cables with cable ties........................................................................................................................... 19
8 Configuration 20
8.1 About the PCBs ............................................................................................................................................................... 20
8.2 Setting the addresses of outdoor units and indoor units .............................................................................................. 20
8.3 To set the addresses of the outdoor unit and capacity up unit..................................................................................... 21
8.4 To set the addresses of the indoor units........................................................................................................................ 22
8.5 Configuring the communication box.............................................................................................................................. 22
8.5.1 To configure the communication box PCB for the indoor units.................................................................... 23
8.5.2 To configure the communication box PCB for the outdoor unit and capacity up unit................................. 24
9 Commissioning 28
10 Troubleshooting 29
10.1 Troubleshooting for PCB for indoor unit communication ............................................................................................. 29
10.2 Troubleshooting for PCB for outdoor unit and capacity up unit communication......................................................... 29
11 Technical data 33
11.1 Wiring diagram: Communication box............................................................................................................................. 33
12 Glossary 34
Installation manual
2
BRR9B1V1
Communication box

1 About the documentation

1.1 About this document

Target audience
Authorised installers
WARNING
Make sure installation, servicing, maintenance, repair and applied materials follow the instructions from Daikin and, in addition, comply with applicable legislation and are performed by qualified persons only. In Europe and areas where IEC standards apply, EN/IEC 60335-2-40 is the applicable standard.
Documentation set
This document is part of a documentation set. The complete set consists of:
Installation manual:
- Installation instructions, configuration,…
1 | About the documentation
- Format: Paper (supplied in the kit) + digital files on http://
www.daikineurope.com/support-and-manuals/product-information/
Latest revisions of the supplied documentation may be available on the regional Daikin website or via your dealer.
The original documentation is written in English. All other languages are translations.
Technical engineering data
A subset of the latest technical data is available on the regional Daikin website
(publicly accessible).
The full set of latest technical data is available on the Daikin Business Portal
(authentication required).
BRR9B1V1 Communication box 4P617761-1B – 2020.10
Installation manual
3
2 | General safety precautions

2 General safety precautions

2.1 About the documentation

The original documentation is written in English. All other languages are
translations.
The precautions described in this document cover very important topics, follow
them carefully.
The installation of the system, and all activities described in the installation
manual and in the installer reference guide MUST be performed by an authorised installer.

2.1.1 Meaning of warnings and symbols

DANGER
Indicates a situation that results in death or serious injury.
DANGER: RISK OF ELECTROCUTION
Indicates a situation that could result in electrocution.
DANGER: RISK OF BURNING/SCALDING
Indicates a situation that could result in burning/scalding because of extreme hot or cold temperatures.
DANGER: RISK OF EXPLOSION
Indicates a situation that could result in explosion.
WARNING
Indicates a situation that could result in death or serious injury.
WARNING: FLAMMABLE MATERIAL
CAUTION
Indicates a situation that could result in minor or moderate injury.
Installation manual
4
NOTICE
Indicates a situation that could result in equipment or property damage.
INFORMATION
Indicates useful tips or additional information.
Symbols used on the unit:
BRR9B1V1
Communication box
Symbol Explanation
Before installation, read the installation and operation manual, and the wiring instruction sheet.
Before performing maintenance and service tasks, read the service manual.
For more information, see the installer and user reference guide.
The unit contains rotating parts. Be careful when servicing or inspecting the unit.
Symbols used in the documentation:
Symbol Explanation
Indicates a figure title or a reference to it.
Example: " 1–3 Figure title" means "Figure 3 in chapter 1".
Indicates a table title or a reference to it.
Example: " 1–3 Table title" means "Table 3 in chapter 1".
2 | General safety precautions

2.2 For the installer

2.2.1 General

If you are NOT sure how to install or operate the unit, contact your dealer.
DANGER: RISK OF BURNING/SCALDING
Do NOT touch the refrigerant piping, water piping or internal parts during and
immediately after operation. It could be too hot or too cold. Give it time to return to normal temperature. If you must touch it, wear protective gloves.
Do NOT touch any accidental leaking refrigerant.
WARNING
Improper installation or attachment of equipment or accessories could result in electrical shock, short-circuit, leaks, fire or other damage to the equipment. Only use accessories, optional equipment and spare parts made or approved by Daikin.
WARNING
Make sure installation, testing and applied materials comply with applicable legislation (on top of the instructions described in the Daikin documentation).
BRR9B1V1 Communication box 4P617761-1B – 2020.10
CAUTION
Wear adequate personal protective equipment (protective gloves, safety glasses,…) when installing, maintaining or servicing the system.
WARNING
Tear apart and throw away plastic packaging bags so that nobody, especially children, can play with them. Possible risk: suffocation.
Installation manual
5
2 | General safety precautions
In accordance with the applicable legislation, it might be necessary to provide a logbook with the product containing at least: information on maintenance, repair work, results of tests, stand-by periods,…
WARNING
Provide adequate measures to prevent that the unit can be used as a shelter by small animals. Small animals that make contact with electrical parts can cause malfunctions, smoke or fire.
CAUTION
Do NOT touch the air inlet or aluminium fins of the unit.
CAUTION
Do NOT place any objects or equipment on top of the unit.Do NOT sit, climb or stand on the unit.
NOTICE
Works executed on the outdoor unit are best done under dry weather conditions to avoid water ingress.

2.2.2 Installation site

Also, at least, following information MUST be provided at an accessible place at the product:
Instructions for shutting down the system in case of an emergency
Name and address of fire department, police and hospital
Name, address and day and night telephone numbers for obtaining service
In Europe, EN378 provides the necessary guidance for this logbook.
Provide sufficient space around the unit for servicing and air circulation.
Make sure the installation site withstands the weight and vibration of the unit.
Make sure the area is well ventilated. Do NOT block any ventilation openings.
Make sure the unit is level.
Do NOT install the unit in the following places:
In potentially explosive atmospheres.
In places where there is machinery that emits electromagnetic waves.
Electromagnetic waves may disturb the control system, and cause malfunction of the equipment.
In places where there is a risk of fire due to the leakage of flammable gases
(example: thinner or gasoline), carbon fibre, ignitable dust.
Installation manual
6
In places where corrosive gas (example: sulphurous acid gas) is produced.
Corrosion of copper pipes or soldered parts may cause the refrigerant to leak.
BRR9B1V1
Communication box

2.2.3 Electrical

2 | General safety precautions
DANGER: RISK OF ELECTROCUTION
Turn OFF all power supply before removing the switch box cover, connecting
electrical wiring or touching electrical parts.
Disconnect the power supply for more than 10minutes, and measure the voltage
at the terminals of main circuit capacitors or electrical components before servicing. The voltage MUST be less than 50VDC before you can touch electrical components. For the location of the terminals, see the wiring diagram.
Do NOT touch electrical components with wet hands.Do NOT leave the unit unattended when the service cover is removed.
WARNING
If NOT factory installed, a main switch or other means for disconnection, having a contact separation in all poles providing full disconnection under overvoltage categoryIII condition, MUST be installed in the fixed wiring.
WARNING
ONLY use copper wires.Make sure the field wiring complies with the applicable legislation.All field wiring MUST be performed in accordance with the wiring diagram
supplied with the product.
NEVER squeeze bundled cables and make sure they do NOT come in contact with
the piping and sharp edges. Make sure no external pressure is applied to the terminal connections.
Make sure to install earth wiring. Do NOT earth the unit to a utility pipe, surge
absorber, or telephone earth. Incomplete earth may cause electrical shock.
Make sure to use a dedicated power circuit. NEVER use a power supply shared by
another appliance.
Make sure to install the required fuses or circuit breakers.Make sure to install an earth leakage protector. Failure to do so may cause
electrical shock or fire.
When installing the earth leakage protector, make sure it is compatible with the
inverter (resistant to high frequency electric noise) to avoid unnecessary opening of the earth leakage protector.
BRR9B1V1 Communication box 4P617761-1B – 2020.10
CAUTION
When connecting the power supply: connect the earth cable first, before making
the current-carrying connections.
When disconnecting the power supply: disconnect the current-carrying cables
first, before separating the earth connection.
The length of the conductors between the power supply stress relief and the
terminal block itself must be as such that the current-carrying wires are tautened before the earth wire is in case the power supply is pulled loose from the stress relief.
Installation manual
7
2 | General safety precautions
NOTICE
Precautions when laying power wiring:
Do NOT connect wiring of different thicknesses to the power terminal block (slack
in the power wiring may cause abnormal heat).
When connecting wiring which is the same thickness, do as shown in the figure
above.
For wiring, use the designated power wire and connect firmly, then secure to
prevent outside pressure being exerted on the terminal board.
Use an appropriate screwdriver for tightening the terminal screws. A screwdriver
with a small head will damage the head and make proper tightening impossible.
Over-tightening the terminal screws may break them.
WARNING
After finishing the electrical work, confirm that each electrical component and
terminal inside the electrical components box is connected securely.
Make sure all covers are closed before starting up the unit.
NOTICE
Only applicable if the power supply is three‑phase, and the compressor has an ON/ OFF starting method.
If there exists the possibility of reversed phase after a momentary black out and the power goes on and off while the product is operating, attach a reversed phase protection circuit locally. Running the product in reversed phase can break the compressor and other parts.
Installation manual
8
BRR9B1V1
Communication box
3 | Specific installer safety instructions

3 Specific installer safety instructions

Always observe the following safety instructions and regulations.
WARNING
Installation shall be done by an installer, the choice of materials and installation shall comply with the applicable legislation. In Europe, EN378 is the applicable standard.
WARNING
Provide adequate measures to prevent that the unit can be used as a shelter by small animals. Small animals that make contact with electrical parts can cause malfunctions, smoke or fire.
WARNING
Make sure the electrical wiring does NOT obstruct correct reattachment of the
communication box cover. Incorrect reattachment of the communication box cover might result in electrical shocks, fire, or terminal overheating.
Do NOT connect the power supply wires to the terminal block for the
transmission wiring. Incorrect connection is very dangerous, results in damage, and possible burnout of the electrical components.
Do NOT use stranded wires with a solder finish applied. A loose wire or other
abnormalities might cause abnormal heating.
WARNING
When opening the front plate of an outdoor unit during operation, be careful of a
rotating fan. The fan continues rotating for a while even after the operation is stopped.
Before turning ON the power supply, make sure that the operation switch of the
outdoor unit is turned OFF. You can check this via the inspection hole of the electrical component box (middle) of the outdoor unit.
After turning ON the power supply, operate the push buttons and check the LED
indication via the inspection hole of the electrical component box (middle) of the outdoor unit. Operating with the cover open might cause an electrical shock.
For more information on how to configure the monitoring system (field supply),
see the manual of the supplier.
WARNING
Do NOT turn ON the power when the communication box cover is open. An
electrical shock might occur.
Before turning ON the power, make sure that the communication box cover is
closed.
CAUTION: Precautions when setting the slave address
Do NOT set the same slave address for devices connected to the Modbus master
device.
Apart from the slave address set in the communication box, there are 2 other
slave addresses that cannot be set. When the slave address on the PCB for the outdoor unit (A2P) is set to "A", slave addresses "A+1" and "A+2" CANNOT be set. Slave address "A" is used for the outdoor unit, "A+1" is used for the capacity up unit, and "A+2" may NOT be used.
BRR9B1V1 Communication box 4P617761-1B – 2020.10
Installation manual
9
4 | About the box
×1
×2

4 About the box

4.1 Communication box

4.1.1 To remove the accessories from the communication box

a Installation manual b Cable tie (2×)
Installation manual
10
BRR9B1V1
Communication box
5 | About the communication box

5 About the communication box

Communication box (BRR9B1V1)
Install the modbus communication box to fully integrate your CO2 Conveni-Pack system with building control automation networks and other monitoring systems.
NOTICE
ALWAYS check with the reference guide of the installed outdoor unit if the communication box is compatible with it. Do NOT connect the communication box to any other unit.
Also see: "8.1About the PCBs"[420].
General names and product names
In this manual, we use the following names:
General name Product name
Communication box BRR9B1V1
Outdoor unit Main outdoor unit. For example:
LRYEN10A7Y1
Capacity up unit Additional outdoor unit for extra

5.1 Identification

5.1.1 Identification label: Communication box

Location
refrigeration capacity. For example: LRNUN5A7Y1
BRR9B1V1 Communication box 4P617761-1B – 2020.10
Installation manual
11
6 | Unit installation
100 mm 50 mm300 mm
50 mm 50 mm
a
b

6 Unit installation

In this chapter

6.1 Preparing the installation site

6.1.1 Installation site requirements of the communication box

6.1 Preparing the installation site ................................................................................................................................................ 12
6.1.1 Installation site requirements of the communication box.................................................................................... 12
6.2 Opening and closing the unit ................................................................................................................................................. 12
6.2.1 To open the communication box ........................................................................................................................... 12
6.2.2 To close the communication box ........................................................................................................................... 13
6.3 Installing the communication box.......................................................................................................................................... 13
6.3.1 Precautions when installing the communication box ........................................................................................... 13
6.3.2 To install the communication box ......................................................................................................................... 13
Mind the following spacing installation guidelines:

6.2 Opening and closing the unit

6.2.1 To open the communication box

a Front view b Top view
The communication box is designed for indoor installation only and for ambient
temperatures ranging from –5~35°C.
Installation manual
12
BRR9B1V1
Communication box

6.2.2 To close the communication box

a
a
aa
515
529
100
120
b
40
87
(mm)

6.3 Installing the communication box

6.3.1 Precautions when installing the communication box

INFORMATION
Also read the precautions and requirements in the following chapters:
General safety precautionsPreparation
6 | Unit installation

6.3.2 To install the communication box

1 Drill 4 holes at the fixing points.
a Hole for a M5 self-tapping screw (4 fixing points) b Wiring intake
2 Secure the communication box using 4 screws (field supply).
INFORMATION
Install the communication box on a sufficiently strong wall using fixing screws (field supply) suitable for the wall.
INFORMATION
Make sure that the wiring intakes face downward.Make sure that dew or rainwater will not drop on the field wiring.Provide traps in front of the wiring intakes.
BRR9B1V1 Communication box 4P617761-1B – 2020.10
Installation manual
13
7 | Electrical installation

7 Electrical installation

In this chapter

DANGER: RISK OF ELECTROCUTION
WARNING
ALWAYS use multicore cable for power supply cables.
7.1 General overview of the field wiring...................................................................................................................................... 14
7.2 Field wiring: Overview ............................................................................................................................................................ 15
7.3 Guidelines when connecting the electrical wiring................................................................................................................. 16
7.4 Specifications of standard wiring components...................................................................................................................... 16
7.5 To connect the electrical wiring on the communication box................................................................................................ 17
7.6 To connect the transmission wiring ....................................................................................................................................... 18
7.6.1 Between communication box and outdoor unit ................................................................................................... 18
7.6.2 Between communication box and monitoring system ......................................................................................... 18
7.7 To fix the wiring cables with cable ties .................................................................................................................................. 19

7.1 General overview of the field wiring

INFORMATION
Indoor units (air conditioning). This field wiring overview shows only one possible
wiring for the indoor units (air conditioning). For more possibilities, see the indoor unit manual.
Installation manual
14
BRR9B1V1
Communication box
7 | Electrical installation
g
F2F1 F1
X1M (A1P)
F2 Q1 Q2
TO MULTI UNIT
TO OUT/D UNIT
TO IN/D UNIT
L1 L2 L3 N
X1M PE X2M
C C1 W1 R P1 P2
21 3
X3M
L N
X2M
P1 P2 F1 F2 T1 T2
F2F1 F1
X1M (A1P)
F2 Q1 Q2
TO MULTI UNIT
TO OUT/D UNIT
TO IN/D UNIT
L1 L2 L3 N
X1M PEX4M
C C1 W1 R P1 P2
21 3
X5M
L N
X2M
X1M
X1M
P1 P2 F1 F2 T1 T2
P1 P2
L N
X1M PEX3M
A+ B- F1 F2
220-240 V AC
220-240 V AC
220-240 V AC
12 V DC
12 V DC
12 V DC
12 V DC
220-240 V AC
220-240 V AC
220-240 V AC
220-240 V AC
1N~ 50 Hz
220-240 V AC
RS-485
DIII
DIII
DIII
DIII
DIII
f gf
d
ed e
a
i
i
b
d1 d2
h
h1 h2
d1 d2
X1M (A1P) X5M
X4M
X1M
PE
X1M
X3M
PE
X1M (A1P)
X2M
X1M
X3M
PE
k1
k
l
m
k2
k4
k3
j
3N~ 50 Hz
380-415 V AC
c1 c2
3N~ 50 Hz
380-415 V AC
c1 c2
c1 c2
1N~ 50 Hz
220-240 V AC
c1 c2
k5
R1
R1
RS-485
DIII
R1
BRR9B1V1 Communication box 4P617761-1B – 2020.10
a Capacity up unit (LRNUN5A7Y1) i Indoor unit (air conditioning)
b Outdoor unit (LRYEN10A7Y1) j User interface for indoor units (air conditioning) c1 Overcurrent fuse (field supply) k Safety system (field supply). Example: c2 Earth leakage circuit breaker (field supply) k1: Control panel
d Alarm panel (field supply) for: k2: CO2 refrigerant leak detector
d1: Caution output signal k3: Safety alarm (lamp) d2: Warning output signal k4: Ventilation (natural or mechanical)
e Control panel (field supply) for operation output
signal
f Remote operation switch (field supply) l Communication box (BRR9B1V1)
g Remote low noise switch (field supply) m Monitoring system (field supply)
OFF: normal mode ON: low noise mode
h Operation output signal to expansion valves of all:
h1: Blower coils (field supply) h2: Showcases (field supply)

7.2 Field wiring: Overview

Field wiring consists of:
power supply (including earth),
k5: Shut off valve
Wiring:
RS-485 transmission wiring (mind polarity) DIII transmission wiring (no polarity) Operation output
Installation manual
15
7 | Electrical installation
DIII transmission wiring between communication box and outdoor unit,
RS‑485 transmission wiring between communication box and monitoring system.
NOTICE
Be sure to keep the power line and transmission line apart from each other.
Transmission wiring and power supply wiring may cross, but may NOT run parallel.
In order to avoid any electrical interference the distance between both wirings
should ALWAYS be at least 50mm.
Transmission wiring
7‒1 DIII weak current – Transmission wiring between each unit except monitoring system
Transmission wiring specification and limits
(a)
Vinyl cords with 0.75 to 1.25mm² sheath or cables (2‑core wires)
Maximum wiring length 1000m
Total wiring length ≤2000m
(a)
If the total transmission wiring exceeds these limits, communication errors might occur.
7‒2 RS-485 weak current – Transmission wiring between monitoring system and communication
box
Transmission wiring specification and limits
Vinyl cords with 0.75 to 1.25mm² sheath or cables (2‑core wires)
Maximum wiring length 1200m
(a)
If the total transmission wiring exceeds these limits, communication errors might occur.

7.3 Guidelines when connecting the electrical wiring

7‒3 Tightening torque for power supply
Item Tightening torque (N•m)
Terminal block (X1M) (M4) 1.18~1.44
Earth terminal (M5) 3.02~4.08
7‒4 Tightening torque for transmission wiring
Item Tightening torque (N•m)
Communication box terminal block (X3M) (M3.5)
(a)
0.79~0.97

7.4 Specifications of standard wiring components

Installation manual
16
Outdoor unit terminal block (X1M
0.80~0.96
(A1P)) (M3.5)
7‒5 Power supply and earth wire
Component Specification
Power supply wire Minimum cable section of 2mm²
(Ø1.6mm)
BRR9B1V1
Communication box
7 | Electrical installation
a
m
k
j
l
j
50 mm
h
g
i
A1P A2P
d e
f
n
o
p
n
o
p
7±2 mm
a
X1M
c
b
Component Specification
Power supply wire – maximum wiring length 250m
Earth wire 2mm2 (Ø1.6mm)

7.5 To connect the electrical wiring on the communication box

WARNING
Make sure the electrical wiring does NOT obstruct correct reattachment of the
communication box cover. Incorrect reattachment of the communication box cover might result in electrical shocks, fire, or terminal overheating.
Do NOT connect the power supply wires to the terminal block for the
transmission wiring. Incorrect connection is very dangerous, results in damage, and possible burnout of the electrical components.
Do NOT use stranded wires with a solder finish applied. A loose wire or other
abnormalities might cause abnormal heating.
See also "7.1General overview of the field wiring"[414].
1 Insert the wiring in the intake hole from the bottom of the communication
box.
BRR9B1V1 Communication box 4P617761-1B – 2020.10
a Intake hole
2 Remove the sheath of the transmission cables.
3 Twist the transmission cables.
4 Connect the power supply to the terminal block (X1M) of the communication
box.
a Sheath
b Twist together before connecting.
c Connect to X1M. d Round crimp-style terminal e Insulation sleeve
f Wire g Round crimp-style terminal h Cutout section
i Cup washer
j Wiring intake k Transmission wiring (RS‑485 weak current) to the monitoring system (mind polarity)
Installation manual
17
7 | Electrical installation
7±2 mm
a
X3M
c
b
l Transmission wiring (DIII weak current) to outdoor unit (no polarity)
m Power wire and earth wire (copper)
n Cable clamp o Cable tie p Wiring

7.6 To connect the transmission wiring

7.6.1 Between communication box and outdoor unit

5 Connect the earth wire to the earth terminal.
6 Connect the transmission wiring as described in "7.6 To connect the
transmission wiring"[418].
INFORMATION
Mind the maximum length of the transmission wiring. Otherwise transmission
errors might occur.
Use sheathed vinyl cords or cables (2 cores).Use ONLY 2-core cables. Do NOT use cables with 3 or more cores, otherwise
transmission errors might occur.
Prerequisite: Use DIII weak current wire.
Prerequisite: Cut the end portion of the transmission wiring that has to be
connected. Strip insulation from the wire before connecting it to the terminal block (X3M).
Prerequisite: Twist the wires together before connecting the wires.
1 Connect F1 and F2 of the X3M terminal block of the communication box to F1
and F2 (TO OUT/D UNIT) of the X1M (A1P) terminal block of the outdoor unit.
2 Connect F1 and F2 (TO OUT/D UNIT) of the X1M (A1P) terminal block of the
outdoor unit to F1 and F2, respectively, of the terminal block of the capacity up unit.
7‒1 Cut, twist, and connect the wire to the terminal block
a Sheath b Twist together before connecting.
c Connect to X3M.

7.6.2 Between communication box and monitoring system

Installation manual
18
NOTICE
Mind the polarity of the transmission wiring.
See also "7.1General overview of the field wiring"[414].
Prerequisite: Use RS‑485 weak current wire.
BRR9B1V1
Communication box
7 | Electrical installation
7±2 mm
a
X3M
c
b
a
b
c
a
b
c
Prerequisite: Cut the end portion of the transmission wiring that has to be connected. Strip insulation from the wire before connecting it to the terminal block (X3M).
Prerequisite: Use wires with the same diameter and twist the core wires together before connecting the wires.
1 Connect wires from A+ and B– of the terminal block of the communication box
to the monitoring system.
2 Connect the wires to the X3M terminal block in the same way as "Between
communication box and outdoor unit"[418].
7‒2 Cut, twist, and connect the wire to the terminal block
a Sheath b Twist together before connecting.
c Connect to X3M.

7.7 To fix the wiring cables with cable ties

NOTICE
Transmission wiring is used for communication between the units. Do NOT fix the transmission wiring together with the power wiring or earth wire. Otherwise communication errors might occur.
1 Fix the transmission wires using a cable tie (delivered as accessory).
a Cable clamp b Cable tie
c Wiring
2 Fix the power and earth wires using a cable tie (delivered as accessory).
BRR9B1V1 Communication box 4P617761-1B – 2020.10
a Cable clamp b Cable tie
c Wiring
3 Cut off the excess part of the cable ties.
4 Seal all gaps to prevent small animals from entering the wiring intake (sealing
material is field supply).
Installation manual
19
8 | Configuration
A1P A2P

8 Configuration

In this chapter

INFORMATION
It is important that all information in this chapter is read sequentially by the installer and that the system is configured as applicable.
DANGER: RISK OF ELECTROCUTION
8.1 About the PCBs ....................................................................................................................................................................... 20
8.2 Setting the addresses of outdoor units and indoor units...................................................................................................... 20
8.3 To set the addresses of the outdoor unit and capacity up unit ............................................................................................ 21
8.4 To set the addresses of the indoor units ............................................................................................................................... 22
8.5 Configuring the communication box...................................................................................................................................... 22
8.5.1 To configure the communication box PCB for the indoor units ........................................................................... 23
8.5.2 To configure the communication box PCB for the outdoor unit and capacity up unit ........................................ 24

8.1 About the PCBs

The communication box is for connection to an outdoor unit only. Do NOT connect any other types of units.
The communication box contains 2 PCBs:
A1P PCB for communication with the indoor unit. A2P PCB for communication with the outdoor unit and capacity up unit.
NOTICE
Communication settings (slave address, baud rate, parity and stop bits) MUST be made for A1P and A2P.

8.2 Setting the addresses of outdoor units and indoor units

WARNING
When opening the front plate of an outdoor unit during operation, be careful of a
rotating fan. The fan continues rotating for a while even after the operation is stopped.
Before turning ON the power supply, make sure that the operation switch of the
outdoor unit is turned OFF. You can check this via the inspection hole of the electrical component box (middle) of the outdoor unit.
After turning ON the power supply, operate the push buttons and check the LED
indication via the inspection hole of the electrical component box (middle) of the outdoor unit. Operating with the cover open might cause an electrical shock.
For more information on how to configure the monitoring system (field supply),
see the manual of the supplier.
Installation manual
20
BRR9B1V1
Communication box
8 | Configuration
a
g
f
i
h
e
d
c
b
OFF
ON
REMOTE
HAP
BS1
DS1 DS2
BS2 BS3
MODEMODE
MODE
MODE
About the effective address range
Set an address in accordance with the model to be connected to the communication box. The following table shows the numbers to which an address can be set.
Model Effective address range
Outdoor unit + capacity up unit
1-7
(LRYEN10A7Y1 + LRNUN5A7Y1)
Indoor unit 1‑00 – 4‑15
INFORMATION
The numbers in the table show the effective range of address setting. For the number of outdoor units that can communicate with 1 communication box, see the specifications.
The address of an outdoor unit and capacity up unit needs to be different.
Setting an address outside the effective range disables proper communication.
After an address of the outdoor unit and capacity up unit is set or changed, reset
the power supply of the communication box.

8.3 To set the addresses of the outdoor unit and capacity up unit

1 Open the left inspection hole cover.
2 Turn OFF the power supply.
3 Turn OFF the operation switch.
a Inspection hole (left) b Inspection hole (right)
c Electrical component box d Operation switch e PCB (A1P)
f Push buttons (BS1~BS3) g 7-segments display h DIP switch
i HAP LED
4 Turn the power supply ON and leave the operation switch OFF.
5 Open the right inspection hole cover.
6 Set the addresses as described in the table below.
Procedure 7-segments display Remarks
Initial indication Show the initial indication in a
normal condition.
BRR9B1V1 Communication box 4P617761-1B – 2020.10
Installation manual
21
8 | Configuration
BS1 BS2 BS3
MODEMODE
MODE
MODE
BS1 BS2 BS3
MODEMODE
MODE
MODE
BS1 BS2 BS3
MODEMODE
MODE
MODE
BS1 BS2 BS3
MODEMODE
MODE
MODE
BS1 BS2 BS3
MODEMODE
MODE
MODE
BS1 BS2 BS3
MODEMODE
MODE
MODE
BS1 BS2 BS3
MODEMODE
MODE
MODE
Procedure 7-segments display Remarks
Press and hold BS1 for 5seconds.
Press BS2 6times.
Press BS3 once.
Press BS2 to
No address set 0 is factory setting. If no setting select the desired setting.
Address 1 Displays the total number of
Address 63 An address can be setup to 63.
Make sure that the left 7­segment is 2.
Check the number of button presses with the right 7-segment. (You see number 6 in the right 7­segment, this means that you pressed 6 times on BS2).
This displays the Airnet address.
has been made, communication cannot be established.
button presses in the 7-segment (center and right).
When BS2 is pressed after that, the setting will change to "Address not set".
Press BS3 once.
Press BS3 once.
Press BS1 once.

8.4 To set the addresses of the indoor units

8.5 Configuring the communication box

When the value is determined, the 7-segment display changes from blinking to lit.
Returns to the initial indication.
Refer to the installation manual of the controller.
WARNING
Do NOT turn ON the power when the communication box cover is open. An
electrical shock might occur.
Before turning ON the power, make sure that the communication box cover is
closed.
Installation manual
22
BRR9B1V1
Communication box

8.5.1 To configure the communication box PCB for the indoor units

A1P
BS1
H1P H2P H3P H4P H5P H6P H7P
SS2 SS3
BS2 BS3 BS4 BS5
1234
DS1
ON
OFF
DS2
1234
120Ω100Ω
SS1
X2M
a
A1P A2P
1 2 3 4 1 2 3 4
DS1 DS2
ON
OFF
Overview of buttons, switches, and other parts
a DIP switches (DS1, DS2)
You can configure 3 different settings on PCB A1P:
RS‑485 Modbus baud rate
Modbus communication parity/stop bit
Modbus slave address setting
RS‑485 Modbus baud rate setting
Setting
8 | Configuration
DS1 pin 2: OFF 9600bps
DS1 pin 2: ON 19200bps
Modbus communication parity/stop bit
Setting
DS1 pin 3: OFF, pin 4: OFF Even 1 stop bit
DS1 pin 3: OFF, pin 4: ON Odd 1 stop bit
DS1 pin 3: ON, pin 4: OFF None 2 stop bits
DS1 pin 3: ON, pin 4: ON None 1 stop bit
Modbus slave address setting
Setting
DS2 pin 1/2/3/4 When Modbus address is set (e.g. 1, ….,
15), then Modbus RS‑485 is enabled.
OFF/OFF/OFF/OFF No Modbus address is set, this means
no Modbus RS‑485 communication.
OFF/OFF/OFF/ON
OFF/OFF/ON/OFF
Address 1
Address 2
BRR9B1V1 Communication box 4P617761-1B – 2020.10
ON/ON/ON/ON
Address 15
DS1 Switch 2 = baud rate. DS1 Switch 3+4 = parity stop bits. DS2 Switch 1~4 = Modbus slave address.
Installation manual
23
8 | Configuration
b
a
c
A2P
BS1
H1P H2P H3P H4P H5P H6P H7P
SS2 SS3
BS2 BS3 BS4 BS5
1234
DS1
ON
OFF
DS2
1234
120Ω100Ω
SS1
X2M
a
b
c
d
A1P A2P
INFORMATION
For more information, see the design guide of Modbus Interface DIII (EKMBDX*).
CAUTION: Precautions when setting the slave address
Do NOT set the same slave address for devices connected to the Modbus master
device.
Apart from the slave address set in the communication box, there are 2 other
slave addresses that cannot be set. When the slave address on the PCB for the outdoor unit (A2P) is set to "A", slave addresses "A+1" and "A+2" CANNOT be set. Slave address "A" is used for the outdoor unit, "A+1" is used for the capacity up unit, and "A+2" may NOT be used.
a Modbus master device b Communication box 1
c Communication box 2
8‒1 Settings for slave address for communication box 1
PCB A1P A2P
Address set 1 2
Unit/system Indoor Outdoor Capacity up
unit
Valid slave
1 2 3 4
Reserved
address
address
8‒2 Settings for slave address for communication box 2
PCB A1P A2P
Address set 8 5
Unit/system Indoor Outdoor Capacity up
unit
Valid slave
8 5 6 7
Reserved
address
address

8.5.2 To configure the communication box PCB for the outdoor unit and capacity up unit

Overview of buttons, switches, and other parts
Installation manual
24
a LEDs b Push buttons (BS1~BS5)
BRR9B1V1
Communication box
8 | Configuration
DS1
1 2 3 4
DS2
1 2 3 4
ON
OFF
OFF
ON
SS2
120 Ω
SS3
100 Ω
SS2
120 Ω
SS3
100 Ω
OFF
ON
SS2
120 Ω
SS3
100 Ω
SS2
120 Ω
SS3
100 Ω
c DIP switches (DS1, DS2)
d Switches to set the terminating resistance (SS1~SS3)
1 Set the slave address using the DIP switches (DS1, DS2) on PCB A2P of the
communication box.
INFORMATION
Make sure to set the slave address before you turn the power ON. The setting is invalid when the setting was done after power ON.
Slave address
1 2 3 4 1 2 3 4
DS1 DS2 Remarks
0 OFF OFF OFF OFF OFF OFF OFF OFF Default
value
1 OFF OFF OFF OFF OFF OFF OFF ON
2 OFF OFF OFF OFF OFF OFF ON OFF
3 OFF OFF OFF OFF OFF OFF ON ON
26 OFF OFF OFF ON ON OFF ON OFF
245 ON ON ON ON OFF ON OFF ON Maximum
effective address
2 If needed, set the terminating resistance. You can set this setting with 2 slide
switches (SS2, SS3). If both switches are "OFF" (default setting), the terminating resistance is 0Ω.
BRR9B1V1 Communication box 4P617761-1B – 2020.10
8‒1 Example of slide switch settings when resistance is 120Ω
8‒2 Example of slide switch settings when resistance is 100Ω
3 Check all transmission wiring (DIII weak current).
4 Check all transmission wiring (RS‑485 weak current) from the monitoring
system to the communication box.
5 Close the communication box cover when you turn ON the power supply.
6 Set the parity using the push buttons (BS1~BS5) on the A2P PCB of the
communication box. The table below shows the setting method. Set the parity as specified by the monitoring system.
Installation manual
25
8 | Configuration
Procedure LED indication
(a)
Remarks
H1P H2P H3P H4P H5P H6P H7P
Initial indication Shows the initial indication in
normal conditions.
Press and hold BS1 for 5seconds. Make sure that the H1P LED has
turned ON.
Press BS2 2 times. Check the pressing count against
the LED indication.
Press BS3 once. Indicates the last setting status.
Press BS2 to select the desired setting.
None Factory setting
Odd
Even
Press BS3 once. The LED indication will change
from flashing to ON.
Press BS3 once.
Press BS1 once. Returns to the initial indication
(a)
= OFF, = ON, and = flashing.
7 Set the baud rate setting using the push buttons (BS1~BS5) on PCB A2P of the
communication box. The following table shows the setting method. Set the baud rate as specified by the monitoring system.
Procedure LED indication
(a)
Remarks
H1P H2P H3P H4P H5P H6P H7P
Initial indication Shows the initial indication in
normal conditions.
Press and hold BS1 for 5seconds. Make sure that the H1P LED has
turned ON.
Press BS2 once. Check the pressing count against
the LED indication.
Press BS3 once. Indicates the last setting status.
Press BS2 to select the desired setting.
9600bps Factory setting
19200bps
Press BS3 once. The LED indication will change
from flashing to ON.
Press BS3 once.
Press BS1 once. Returns to the initial indication
(a)
= OFF, = ON, and = flashing.
8 Set the stop bit settings using the push buttons (BS1~BS5) on PCB A2P of the
communication box. The following table shows the setting method. Set the stop bit settings as specified on the monitoring system.
Procedure LED indication
(a)
Remarks
H1P H2P H3P H4P H5P H6P H7P
Initial indication Shows the initial indication in
normal conditions.
Installation manual
26
Communication box
BRR9B1V1
8 | Configuration
Procedure LED indication
(a)
Remarks
H1P H2P H3P H4P H5P H6P H7P
Press and hold BS1 for 5seconds. Make sure that the H1P LED has
turned ON.
Press BS2 6 times. Check the pressing count against
the LED indication.
Press BS3 once. Indicates the last setting status.
Press BS2 to select the desired setting.
Auto LED indication is the desired
1 stop bit
setting.
2 stop bits
Press BS3 once. The LED indication will change
from flashing to ON.
Press BS3 once.
Press BS1 once. Returns to the initial indication
(a)
= OFF, = ON, and = flashing.
9 After the settings are set, reset the power supply of the communication box.
INFORMATION
The power supply must be reset before the settings of parity, baud rate, and stop bits become effective.
BRR9B1V1 Communication box 4P617761-1B – 2020.10
Installation manual
27
9 | Commissioning

9 Commissioning

INFORMATION
For more information on how to do a test run of each unit, see the installation manual or installer reference guide of each unit.
Are the LEDs (H1P~H4P) on the PCB (A1P) flashing?
H1P: DIII connection (send).
H2P: DIII connection (receive).
H3P: RS‑485 connection (send).
H4P: RS‑485 connection (receive).
Are the LEDs (H6P, H7P) on the PCB (A2P) ON?
If the LEDs are still flashing, communication is not established.
H6P ON: RS‑485 communication is established.
H7P ON: DIII communication of 1 or more units is established.
Can the operation data of each address be monitored on the monitoring system?
Make sure that the power supply to each unit is turned ON.
Check that the address set on each unit corresponds with the address displayed on the monitoring system.
Make sure that the power supply to each unit is turned ON.
Result: If there are no problems with the operation data and the remote settings, the H2P LED will be OFF and the H6P and H7P LEDs will be ON. The test run is then complete for A2P.
INFORMATION
Confirmation of an error takes about 12 minutes.If there is no communication from the monitoring system (e.g. monitoring system
is turned OFF, incorrect polarity or disconnection), a communication error occurs on the RS‑485 side.
What to do in case of a communication error?
The operation data cannot be checked on the monitoring system.
Check all items in "10Troubleshooting"[429] and correct any problem.
"   10‒1 Operation procedure step 1" [4 30] describes how you can check
some errors.
Installation manual
28
BRR9B1V1
Communication box

10 Troubleshooting

In this chapter

10.1 Troubleshooting for PCB for indoor unit communication ..................................................................................................... 29
10.2 Troubleshooting for PCB for outdoor unit and capacity up unit communication ................................................................ 29

10.1 Troubleshooting for PCB for indoor unit communication

What to check? How to check? Solution
10 | Troubleshooting
No Modbus communication
Incorrect Modbus address setting was present at power ON on the Modbus interface DIII.
No Modbus address is set (=DS2: OFF/OFF/OFF/ OFF).
During power OFF, set DS2 on A1P to the required Modbus address. See
"8.4To set the addresses of the indoor units"[422]. The ON/OFF
status of the DIP switch is detected only at the time of power ON of the PCB.
Set DS2 on A1P to the required Modbus address. See "8.4To set the
addresses of the indoor units"[422].

10.2 Troubleshooting for PCB for outdoor unit and capacity up unit communication

What to check? How to check? Solution
Address setting of each unit
Slave address setting DIP switches (DS1, DS2) of the communication
Data of each address can be checked on the monitoring system.
box PCB (A2P).
Set the addresses of the outdoor unit and capacity up unit again. See
"8Configuration"[420].
Set the slave address correctly. See
"To configure the communication box PCB for the outdoor unit and capacity up unit"[424].
Parity setting Parity setting on the monitoring system against
the parity setting on the communication box.
Stop bit setting Stop bit setting on the monitoring system against
the stop bit setting on the communication box.
Baud rate setting Baud rate setting on the monitoring system
against the baud rate setting on the communication box.
BRR9B1V1 Communication box 4P617761-1B – 2020.10
Set the parity setting correctly. See
"To configure the communication box PCB for the outdoor unit and capacity up unit"[424].
Set the stop bit setting correctly. See
"To configure the communication box PCB for the outdoor unit and capacity up unit"[424].
Set the baud rate setting correctly. See "To configure the
communication box PCB for the outdoor unit and capacity up unit"[424].
Installation manual
29
10 | Troubleshooting
What to check? How to check? Solution
DIII weak current
Data of each address on the monitoring system. Check the wiring of the unit with
transmission wiring
H2P is ON and H7P is flashing on the communication box. Follow the instructions in "
10‒1 Operation procedure step 1"[430] to
diagnose the communication box.
RS‑485 weak current transmission wiring
Make sure that the field settings are made correctly, check whether the data can be checked on the monitoring system.
Refrigerator connection other than an outdoor unit and capacity up unit
H2P is ON on the communication box. Follow the instructions in " 10‒2 Operation procedure
step 2"[431] to diagnose the communication
box.
PCB error H2P is ON on the communication box. Follow the
instructions in " 10‒1 Operation procedure
step 1"[430] to diagnose the communication
box.
No LED is ON on PCB (A2P).
data that cannot be checked and correct the wiring.
Communication cannot be established with any of the outdoor units. Check the transmission wiring (DIII weak current) and address settings.
Check RS‑485 weak current transmission wiring and correct it (e.g. disconnection, incorrect polarity).
Disconnect the non-CO₂ refrigerator.
Replace PCB (A2P).
Check conditions of all units (indoor unit, outdoor unit and capacity up unit).
10‒1 Operation procedure step 1
Procedure LED indication
(a)
Remarks
H1P H2P H3P H4P H5P H6P H7P
Initial indication
(b)
Press BS1 once.
Press BS2 twice.
H6P flashing: RS‑485 communication error
H7P flashing: DIII communication error (if communication is not established with any of the indoor units).
Installation manual
30
BRR9B1V1
Communication box
10 | Troubleshooting
Procedure LED indication
H1P H2P H3P H4P H5P H6P H7P
Press BS3 once (error check).
DIII side
(c)
communication error
RS‑485 communication error
Board error Error of the PCB (A2P) of the
Duplicate outdoor unit addresses
Outdoor unit address not set
Slave address setting error
(a)
Remarks
Communication error of all outdoor units.
(d)
Communication error on the RS‑485 side. An error is detected even when the polarity is correct. Check the address settings and the RS‑485 wiring.
(d)
communication box. Replace the PCB.
Duplicate outdoor unit addresses. Check the address settings and DIII wiring.
The address of an outdoor unit is not set. Check the address setting and DIII wiring.
Slave address setting error. Check the slave address setting and wiring.
Press BS1 once. In normal conditions, H2P is OFF,
and H6P and H7P are ON.
(a)
= OFF, = ON, and = flashing.
(b)
The initial indication in the table shows the indication when an error is detected. If there are no communication errors, the H2P LED is OFF and the H6P and H7P LEDs are ON.
(c)
When multiple errors are detected, multiple LEDs (H2P to H7P) are flashing.
(d)
For both DIII side and RS‑485 side, if a communication error occurs after the communication is confirmed, an error is generated. If the communication has not been confirmed, errors are not detected.
10‒2 Operation procedure step 2
Procedure LED indication
(a)
Remarks
H1P H2P H3P H4P H5P H6P H7P
Initial indication
(b)
H6P flashing: RS‑485 communication error.
H7P flashing: DIII communication error (if communication is not established with any of the indoor units).
Press BS1 once.
Press BS2 3 times.
Press BS3 once (error check).
Reserve
Reserve
Different refrigerator
A non-CO₂ refrigerator is connected.
Press BS1 once. In normal conditions, H2P turns
OFF, and H6P and H7P turn ON.
BRR9B1V1 Communication box 4P617761-1B – 2020.10
Installation manual
31
10 | Troubleshooting
(a)
= OFF, = ON, and = flashing.
(b)
The initial indication in the table shows the indication when an error is detected. If there are no communication errors, the H2P LED is OFF and the H6P and H7P LEDs are ON.
Installation manual
32
BRR9B1V1
Communication box

11 Technical data

11.1 Wiring diagram: Communication box

A1P PCB (communication with indoor unit for air
conditioning)
A2P PCB (communication with outdoor unit and capacity
up unit)
A3P PCB
BS1~BS5 Push buttons (see Note1)
DS1, DS2 DIP switches (see Note1)
F1S Varistor
F1U Fuse (T, 3.15A, 250V)
H1P~H7P LED
HAP LED
11 | Technical data
SS1~SS3 Switches to set the terminating resistance (see Note
1)
T1R Transformer (220~240V/22V)
X3A~X11A Connectors
X1M~X3M Terminal strips
Field wiring
Terminal strip
Connector
Protective earth
BLK Black
ORG Orange
WHT White
YLW Yellow
HIGH VOLTAGE High voltage
LOW VOLTAGE Low voltage
BRR9B1V1 Communication box 4P617761-1B – 2020.10
MONITORING SYSTEM Monitoring system
OUTDOOR UNIT Outdoor unit
POWER SUPPLY Power supply
SWITCH BOX Switch box
Note1
Communication settings can be changed using the push buttons. For information on how to do this, see the installation manual of the outdoor unit and the capacity up unit.
Installation manual
33
12 | Glossary

12 Glossary

Dealer
Sales distributor for the product.
Authorised installer
Technical skilled person who is qualified to install the product.
User
Person who is owner of the product and/or operates the product.
Applicable legislation
All international, European, national and local directives, laws, regulations and/or codes that are relevant and applicable for a certain product or domain.
Service company
Qualified company which can perform or coordinate the required service to the product.
Installation manual
Instruction manual specified for a certain product or application, explaining how to install, configure and maintain it.
Operation manual
Instruction manual specified for a certain product or application, explaining how to operate it.
Maintenance instructions
Instruction manual specified for a certain product or application, which explains (if relevant) how to install, configure, operate and/or maintain the product or application.
Accessories
Labels, manuals, information sheets and equipment that are delivered with the product and that need to be installed according to the instructions in the accompanying documentation.
Optional equipment
Equipment made or approved by Daikin that can be combined with the product according to the instructions in the accompanying documentation.
Field supply
Equipment NOT made by Daikin that can be combined with the product according to the instructions in the accompanying documentation.
Installation manual
34
BRR9B1V1
Communication box
4P617761-1 B 0000000%
Verantwortung für Energie und Umwelt
Copyright 2020 Daikin
4P617761-1B 2020.10
Loading...