Daikin ATXB50CV1B, ARXB50CV1B, ATXB60CV1B, ARXB60CV1B Installation manuals [es]

INSTALLATION MANUAL
R410A SPLIT SERIES
IM-5WMYJR-1114()-DAIKIN SIESTA
Part Number.: R08019041826$
Installation Manual R410A Split Series
Série split R410A
Installationsanleitung
Split-Baureihe R410A
Manuale d’installazione
Serie Multiambienti R410A
Manual de instalación
Serie Split R410A
Руководство по монтажу
Серия R410A с раздельной установкой
Montaj kılavuzu
R410A Split serisi
English
Français
Deutsch
Italiano
Español
Русский
Türkçe
MODELS
ATXB50CV1B ARXB50CV1B ATXB60CV1B ARXB60CV1B
Indoor Unit
Through the wall hole Ø 65mm
Drain hose position
OUTLINE AND DIMENSIONS
©
Recommended mounting plate retention spots
(7 spots in all)
Original Instruction
All dimensions are in mm
Gas pipe end
INSTALLATION PLATE ATXB50/60CV1B
Dimension
Model
A B C D E F G H I J K L M
ATXB50/60CV1B 1065 310 228 190 173 61 40 45 48 91 219 580 45
All dimensions are in mm
Liquid pipe end
D E
B
F
G
K I
ML
H I
FG
A
B
FRONT VIEW
TOP VIEW
C
SIDE VIEW
B
REAR REAR
RIGHTLEFT
BOTTOM BOTTOM
FRONT GRILLE FIXED SCREWS (INSIDE)
LOUVER
SIGNAL RECEIVER
INDOOR UNIT ON/OFF SWITCH ROOM TEMPERATURE THERMISTOR (INSIDE)
NAME PLATE
TERMINAL BLOCK WITH EARTH TERMINAL
THE MARK SHOWS PIPING DIRECTION
English
1-1
B
A
Q
P
R
S
D
O
KL L
M
N
F
E
C
G H
I
J
N
Dimension
Model
A B C D E F G H I J K L M N
ARXB50/60CV1B 855 730 328 520 179 46 93 149 101 113 603 126 164 15
Outdoor Unit ARXB50/60CV1B
All dimensions are in mm
Dimension
Model
O P Q R S
ARXB50/60CV1B 34 23 362 73 75
1-2
English
1-3
! WARNING ! CAUTION
Installation and maintenance should be performed by qualifi ed persons who are familiar with local code and regulation, and experienced with this type of appliance. All fi eld wiring must be installed in accordance with the national wiring regulation. Ensure that the rated voltage of the unit corresponds to that of the name plate before commencing wiring work according to the wiring diagram. The unit must be GROUNDED to prevent possible hazard due to insulation failure. All electrical wiring must not touch the refrigerant piping or any moving parts of the fan motors. Confi rm that the unit has been switched OFF before installing or servicing the unit. Disconnect from the main power supply before servicing the air conditioner unit. DO NOT pull out the power cord when the power is ON. This may cause serious electrical shocks which may result in the re hazards. Keep the indoor and outdoor units, power cable and transmission wiring, at least 1m from TVs and radios, to prevent distorted pictures and static. {Depending on the type and source of the electrical waves, static may be heard even when more than 1m away}.
Please take note of the following important points when installing.
Do not install the unit where leakage of fl ammable gas may occur.
If gas leaks and accumulates around the unit, it may cause
re ignition.
Ensure that drainage piping is connected properly.
If the drainage piping is not connected properly, it may
cause water leakage which will dampen the furniture.
Do not overcharge the unit.
This unit is factory pre-charged. Overcharge will cause over-current or damage to the
compressor.
Ensure that the unit’s panel is closed after service or installation.
Unsecured panels will cause the unit to operate noisily.
Sharp edges and coil surfaces are potential locations which may cause injury hazards. Avoid from being in contact with these places. Before turning off the power supply, set the remote controller’s ON/OFF switch to the “OFF” position to prevent the nuisance tripping of the unit. If this is not done, the unit’s
fans will start turning automatically when power resumes, posing a hazard to service personnel or the user.
Do not install the units at or near doorway. Do not operate any heating apparatus too close to the air conditioner unit or use in room where mineral oil, oil vapour or oil steam exist, this may cause plastic part to melt or deform as a result of excessive heat or chemical reaction. When the unit is used in kitchen, keep fl our away from going into suction of the unit. This unit is not suitable for factory used where cutting oil mist or iron powder exist or voltage fl uctuates greatly. Do not install the units at area like hot spring or oil refi nery plant where sulphide gas exists. Ensure the color of wires of the outdoor unit and the terminal markings are same to the indoors
respectively. IMPORTANT: DO NOT INSTALL OR USE THE AIR CONDITIONER UNIT IN A LAUNDRY ROOM.
Don’t use joined and twisted wires for incoming power supply. The equipment is not intended for use in a potentially explosive atmosphere.
SAFETY PRECAUTIONS
INSTALLATION MANUAL
NOTICE
Disposal requirements
Your air conditioning product is marked with this symbol. This means that electrical and electronic products shall not be mixed with unsorted household waste.
Do not try to dismantle the system yourself: the dismantling of the air conditioning system, treatment of the refrigerant, of oil and of other parts must be done by a qualifi ed installer in accordance with relevant local and national legislation.
Air conditioners must be treated at a specialized treatment facility for re-use, recycling and recovery. By ensuring this product is disposed of correctly, you will help to prevent potential negative consequences for the environment and human health. Please contact the installer or local authority for more information.
Batteries must be removed from the remote controller and disposed of separately in accordance with relevant local and national legislation.
This manual provides the procedures of installation to ensure a safe and good standard of operation for the air conditioner unit. Special adjustment may be necessary to suit local requirement. Before using your air conditioner, please read this instruction manual carefully and keep it for future reference. This appliance is intended to be used by expert or trained users in shops, in light industry and on farms, or for commercial use by lay persons. This appliance is not intended for use by persons, including children, with reduced physical, sensory or mental capabilities, or lack of experience and knowledge, unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety. Children should be supervised to ensure that they do not play with the appliance.
IMPORTANT
Important information regarding the refrigerant used
This product contains fluorinated greenhouse gases. Do not vent gases into the atmosphere. Refrigerant type: R410A
(1)
GWP
(1)
Please fill in with indelible ink,
on the refrigerant charge label supplied with the product. The filled out label must be adhered in the proximity of the product charging port (e.g. onto the inside of the service cover).
value: 2087.5
GWP = Global Warming Potential
1 the factory refrigerant charge of the product, 2 the additional refrigerant amount charged in the field and 1 + 2 the total refrigerant charge
1
factory refrigerant charge of the product:
see unit name plate
2
additional refrigerant amount charged in the field
3
total refrigerant charge
4
contains fluorinated greenhouse gases
5
outdoor unit
(2)
6
refrigerant cylinder and manifold for charging
(2)
In case of multiple indoor systems, only 1 label must be adhered*, mentioning the total factory refrigerant charge of all
indoor units connected in the refrigerant system. Periodical inspections for refrigerant leaks may be required depending on European or local legislation. Please contact your
local dealer for more information.
* on the outdoor unit
1-4
English
1-5
INSTALLATION DIAGRAM
Air Inlet
Discharge air
A
B
Obstacle
Return air
Service access
C
D
Obstacle
Obstacle
Obstacle
Indoor Unit
Air filter
M4 x 12L
Front panel
75mm or more from ceiling
Outdoor Unit
50mm or more from walls (on both sides)
Caulk pipe hole gap with putty.
Cut thermal insulation pipe to an appropriate length and wrap it with tape, making sure that no gap is left in the insulation pipe’s cut line.
Wrap the insulation pipe with the finishing tape from bottom to top.
Service lid
Opening service lid
Service lid is opening/ closing type.
Opening method
1) Remove the service lid screws.
2) Pull out the service lid diagonally down in the direction of the arrow.
3) Pull down.
y
y
500mm from wall
INSTALLATION OF THE OUTDOOR UNIT
The outdoor unit must be installed in such a way, so as to prevent short circuit of the hot discharged air or obstruction to the smooth air flow. Please follow the installation clearances shown in the figure. Select the coolest possible place where intake air temperature is not greater than the outside air temperature (Refer to operating range).
Installation clearances
Note: If there is any obstacle higher than 2m, or if there is any
obstruction at the upper part of the unit, please allow more space than the figure indicated in the above table.
Dimension
A B C D
Minimum Distance, mm 300 1000 300 500
H
H/2
Condensed Water Disposal Of Outdoor Unit (Heat Pump Unit Only)
There are 2 holes on the base of Outdoor Unit for condensed water to flow out. Insert the drain elbow to one of the holes. To install the drain elbow, first insert one portion of the hook to the base (portion A), then pull the drain elbow in the direction shown by the arrow while inserting the other portion to the base. After installation, check to ensure that the drain elbow clings to base firmly. If the unit is installed in a snowy and chilly area, condensed water may freeze in the base. In such case, please remove plug at the bottom of unit to smooth the drainage.
Please remove side plate when connecting the piping and connecting cord
PUSH & PULL UP
BASE
A
DRAIN ELBOW
DRAIN ELBOW
PLUG
The indoor unit must be installed in such a way so as to prevent short circuit of the cool discharged air with the hot return air. Please follow the installation clearance shown in the figure. Do not place the indoor unit where there could be direct sunlight shining on it. Also, this location must be suitable for piping and drainage, and be away from doors or windows.
min. 50
(Space for maintenance)
Air flow (Indoor)
The refrigerant piping can be routed to the unit in a number of ways (left or right from the back of the unit), by using the cut­out holes on the casing of the unit (see figure). Bend the pipes carefully to the required position in order to align it with the holes. For the side and bottom, hold the bottom of the piping and then position it to the required direction (see figure). The condensation drain hose can be taped to the pipes.
Right-side, right-back or right-bottom piping
min. 50
(Space for maintenance)
min. 75
(Space for
performance)
Required space
Right-back piping
All dimensions are in mm
Right-bottom piping
Right-side piping
Remove pipe port cover here for right-side piping
Left-back piping
Left-side piping
Left-bottom piping
Left-side, left-back or left-bottom piping
INSTALLATION OF THE INDOOR UNIT
Remove pipe port cover here for right-bottom piping
Bind coolant pipe and drain hose together with insulating tape.
Remove pipe port cover here for left-side piping
Remove pipe port cover here for left-bottom piping
1-6
English
1-7
How To Attach The Indoor Unit
Hook the claws of the bottom frame to the mounting plate.
How To Remove The Indoor Unit
Push up the marked area (at the lower part of the front grille) to release the claws.
Mount The Unit Onto The Installation Plate
Hook the indoor unit onto the upper portion of the installation plate (Engage the two hooks at the rear top of the indoor unit with the upper edge of the installation plate). Ensure that the hooks are properly seated on the installation plate by moving it to the left and right.
Mounting plate
Clip
Bottom frame
Mark (Rear side)
Front grille
Water
leaking
Water retention
End dipped into water
Drain
Correct Wrong
Water
leaking
Water
leaking
Wrong Wrong
Water Drainage Piping
The indoor drain pipe must be in a downward gradient for smooth drainage. Avoid situations that are likely to cause water to leak.
Water Drainage
When str ipp ing the end s of interconnecting wires in advance, bind right ends of wires with insulating tape.
Hand indoor unit’s hook here.
Mounting plate
Interconnecting wires
Wire guide
! CAUTION
• Do not install the unit at altitude over 2000m for both indoor & outdoor.
Mounting Installation Plate
Ensure that the wall is strong enough to withstand the weight of the unit. Otherwise, it is necessary to reinforce the wall with plates, beams or pillars. Use the level gauge for horizontal mounting, and fix it with 7 suitable screws for ATXB50/60CV1B. In case the rear piping draws out, drill a hole 65mm in diameter with a cone drill, slightly lower on the outside wall (see figure).
Mounting plate
Mounting plate fixing screw
Recommended Mounting Plate Retention Spots And Dimensions
Through the wall hole Ø 65mm
190
173
61
310
61
Drain hose position
Gas pipe end
Liquid pipe end
48
45
580
1065
219
40
40
91
45
All dimensions are in mm
©
Recommended mounting plate retention spots (7 spots in all)
Hole with cone drill
Inside
Ø 65
Wall embedded pipe (Field supply)
Wall hole cover (Field supply)
Wall embedded pipe (Field supply)
Outside
Caulking
Model ATXB50CV1B ATXB60CV1B
Min. Allowable Length (L), m 3
Max. Allowable Length (L), m 30
Max. Allowable Elevation (E), m 10
Gas Pipe Size, mm/(in) 12.70 (1/2") 15.88 (5/8")
Liquid Pipe Size, mm/(in) 6.35 (1/4")
L E
*Be sure to add the proper amount of additional refrigerant. Failure to do so may result in reduced performance.
Remark: The refrigerant pre-charged in the outdoor unit is for piping length up to 7.5m.
Outdoor Unit
Indoor unit
Allowable Piping Length
If the pipe is too long, both the capacity and reliability of the unit will drop. As the number of bends increases, resistance to the flow of refrigerant system increases, thus lowering cooling capacity. As a result, the compressor may become defective. Always choose the shortest path and follow the recommendations as tabulated below:
REFRIGERANT PIPING
Bending must be carefully made so as not to crush the pipe. Use a pipe bender to bend a pipe where possible.
Notes:
1. Equivalent piping length is obtained with actual length of gas piping.
2. 90° bend of piping is equivalent to L joint.
Equivalent length for various fitting (meter)
Pipe Size L joint
Trap bend
3/8" (OD9.52mm) 0.18 1.3 1/2" (OD12.7mm) 0.20 1.5 5/8" (OD15.9mm) 0.25 2 3/4" (OD19.1mm) 0.35 2.4 7/8" (OD22.2mm) 0.40 3 1" (OD25.4mm) 0.45 3.4 1 1/8" (OD28.6mm) 0.50 3.7 1 3/8" (OD34.9mm) 0.60 4.4
1-8
English
1-9
Piping Works And Flaring Technique
Do not use contaminated or damaged copper tubing. If any piping, evaporator or condenser had been exposed or had been opened for 15 seconds or more, the system must be vacuumed. Generally do not remove plastic, rubber plugs and brass nuts from the valves, fittings, tubing and coils until it is ready to connect suction or liquid line into valves or fittings.
If any brazing work is required, ensure that nitrogen gas is passed through coil and joints while the brazing work is being done. This will eliminate soot formation on the inside wall of copper tubings.
Cut the pipe stages by stages, advancing the blade of pipe cutter slowly. Extra force and a deep cut will cause more distortion of pipe and therefore extra burr. See Figure I.
Remove burrs from cut edges of the pipes with remover. See Figure II. Hold the pipe on top position and burr remover at lower position to prevent metal chips from entering the pipe. This will avoid unevenness on the flare faces which will cause gas leak.
Insert the flare nuts, mounted on the connection parts of both the indoor unit and outdoor unit, into the copper pipes.
The exact length of pipe protruding from the top surface of the swaging block is determined by the flaring tool. See Figure III.
Fix the pipe firmly on the swaging block. Match the centers of both the swaging block and the flaring punch, then tighten the flaring punch fully.
Piping Connection To The Units
Align the center of the piping and tighten the flare nut sufficiently with fingers. See Figure IV.
Finally, tighten the flare nut with torque wrench until the wrench clicks.
When tightening the flare nut with the torque wrench, ensure that the tightening direction follows the arrow indicated on the wrench.
The refrigerant pipe connection are insulated by closed cell polyurethane.
1/4t
Cutting Copper Tube
Copper Tube
Swaging Block
Remove Burr
Figure I
D
A
Pipe Size, mm (in) Torque, Nm/(ft-lb)
6.35 (1/4") 18 (13.3)
12.70 (1/2") 55 (40.6)
15.88 (5/8") 65 (48.0)
Flared Tube
Flare Joint
Flare NutIndoor Piping
Torque Wrench
Ø Tube, D A (mm)
Inch mm Imperial
(Wing-nut Type)
Rigid
(Clutch Type)
1/4" 6.35 1.30 0.70 1/2" 12.70 1.90 1.30 5/8" 15.88 2.20 1.70
REFRIGERANT PIPING
Figure II
Figure III
Figure IV
Copper Tube
Spanner
Attach insulation sleeve
Round crimp-style terminal
Electric wire
Model
ATXB50/60CV1B ARXB50/60CV1B
Voltage range
**
220-240V/~/50Hz +
!
Power supply cable size
*
mm
2
Number of Conductors
2.5 3
Interconnection cable size
*
mm
2
Number of Conductors
2.5 4
Recommended fuse/circuit breaker rating A 20
* If the length of the cable is more than 2m, use cable with
bigger size.
ELECTRICAL WIRING CONNECTION
IMPORTANT : * The figures shown in the table are for information purpose only. They should be checked and selected
to comply with the local/national codes of regulations. This is also subject to the type of installation and conductors used.
** The appropriate voltage range should be checked with label data on the unit.
All wires must be firmly connected. Make sure all the wire do not touch the refrigerant pipings, compressor or any moving parts. The connecting wire between the indoor unit and the outdoor unit must be clamped by using provided cord anchorage. The power supply cord must be equivalent to H07RN-F which is the minimum requirement. Make sure no external pressure is applied to the terminal connectors and wires. Make sure all the covers are properly fixed to avoid any gap. Use round crimp-style terminal for connecting wires to the power supply terminal block. Connect the wires by matching to the indication on terminal block. (Refer to the wiring diagram attached on the unit).
Connect wires of the same gauge to both side.
Do not connect wires of the same gauge to one side.
Do not connect wires of different gauges.
Used the correct screwdriver for terminal screws tightening. Unsuitable screwdrivers can damage the screw head. Over tightening can damage the terminal screws. Do not connect wire of different gauge to same terminal. Keep wiring in an orderly manner. Prevent the wiring from obstructing other parts and the terminal box cover.
2
SIG
1
Outdoor Unit
Terminal Block
Indoor Unit
Terminal Block
There must be an all pole disconnection in the supply mains with a contact separation of at least 3mm.
!
2
SIG
1
Interconnection
cable
N
L
Power supply terminal block
Use the specified wire type and connect it securely.
Firmly secure wire retainer so wire terminations will not receive external stress.
Shape wires so that the service lid and stop valve cover fit securely.
N / L2 L / L1
Power
Supply
Main
Switch
Fuse / Circuit
Breaker
Power Supply Cable
1-10
English
1-11
SPECIAL PRECAUTIONS WHEN DEALING WITH R410A UNIT
R410A is a new HFC refrigerant which does not damage the ozone layer. The working pressure of this new refrigerant is
1.6 times higher than conventional refrigerant (R22), thus proper installation/servicing is essential.
Never use refrigerant other than R410A in an air conditioner which is designed to operate with R410A. POE or PVE oil is used as lubricant for R410A compressor, which is different from the mineral oil used for R22 compressor. During installation or servicing, extra precaution must be taken not to expose the R410A system too long to moist air. Residual POE or PVE oil in the piping and components can absorb moisture from the air. To prevent mischarging, the diameter of the service port on the flare valve is different from that of R22.
Use tools and materials exclusively for refrigerant R410A. Tools exclusively for R410A are manifold valve, charging hose, pressure gauge, gas leak detector, flare tools, torque wrench, vacuum pump and refrigerant cylinder. As an R410A air conditioner incurs higher pressure than R22 units, it is essential to choose the copper pipes correctly. Never use copper pipes thinner than 0.8mm even though they are available in the market. If the refrigerant gas leakage occurs during installation/ servicing, be sure to ventilate fully. If the refrigerant gas comes into contact with fire, a poisonous gas may occur. When installing or removing an air conditioner, do not allow air or moisture to remain in the refrigerant cycle.
VACUUMING AND CHARGING
Vacuuming is necessary to eliminate all moisture and air from the system.
Vacuuming The Piping And The Indoor Unit
Except for the outdoor unit which is pre-charged with refrigerant, the indoor unit and the refrigerant connection pipes must be air-purged because the air containing moisture that remains in the refrigerant cycle may cause malfunction of the compressor.
Remove the caps from the valve and the service port. Connect the center of the charging gauge to the vacuum pump. Connect the charging gauge to the service port of the 3-way valve. Start the vacuum pump. Evacuate for approximately 30 minutes. The evacuation time varies with different vacuum pump capacity. Confirm that the charging gauge needle has moved towards -760mmHg.
Caution
If the gauge needle does not move to -760mmHg, be sure to check for leakage at flare type connection of the indoor and outdoor unit and repair the leak before proceeding to the next step. Close the valve of the changing gauge and stop the vacuum pump. On the outdoor unit, open the suction valve (3 way) and liquid valve (2 way) (in anti-clockwise direction) with 4mm key for hexagon sacked screw.
Charge Operation
This operation must be done by using a gas cylinder and a precise weighing machine. The additional charge is topped-up into the outdoor unit using the suction valve via the service port.
Remove the service port cap. Connect the low pressure side of the charging gauge to the suction service port center of the cylinder tank and close the high pressure side of the gauge. Purge the air from the service hose. Start the air conditioner unit. Open the gas cylinder and low pressure charging valve. When the required refrigerant quantity is pumped into the unit, close the low pressure side and the gas cylinder valve. Disconnect the service hose from service port. Put back the service port cap.
Refrigerant Piping
Outdoor Unit 3 ways valve
Allen key
Service Port
Flare nut
HIGH PRESSURE GAUGE
GAUGE MANIFOLD
LOW PRESSURE GAUGE
HANDLE HI (ALWAYS CLOSED)
CHARGE HOSE
-760mmHg
HANDLE LO
CHARGE HOSE
VACUUM PUMP ADAPTER FOR
COUNTER FLOW PREVENTION
CHECK VALVE
LIQUID VALVE
HIGH PRESSURE GAUGE
LOW PRESSURE GAUGE
GAUGE MANIFOLD
-760mmHg
HANDLE LO
HANDLE HI (ALWAYS CLOSED)
CHARGE HOSE
CHARGE HOSE
CHECK VALVE
LIQUID VALVE
GAS VALVE (3-WAY)
CONFIGURATION OF AIR PURGE BY CHARGING
GAS VALVE (3-WAY)
CONFIGURATION OF AIR PURGE BY CHARGING
COOL/HEAT
(GREEN/RED)
Operation
GREEN
Cool mode
RED
Heat mode
RED
Auto mode in Heating operation
GREEN
Auto mode in Cooling operation
Timer on Sleep mode on
GREEN
Fan mode on
GREEN
Dry mode on
RED
Defrost operation
GREEN
Unit error
ON
Blinking
IR Signal Receiver
When an infrared remote control operating signal has been transmitted, the signal receiver on the indoor unit will respond as below to confi rm acceptance of the signal transmission.
LED Indicator Lights for Cooling Unit/Heat Pump Unit
Cooling Unit/Heat Pump Unit
The table shows the LED indicator lights for the air conditioner unit under normal operation and fault conditions. The LED indicator lights are located at the side of the air conditioner unit. The heat pump units are equipped with an “auto” mode sensor whereby it will provide reasonable room temperature by switching automatically to either “cool” or “heat” mode according to the temperature set by the user.
IR Receiver
ON/OFF
Cool/Heat Timer
Sleep
ON/OFF switch
IR Receiver
INDICATOR LIGHTS
ON to OFF 1 Long Beep
OFF to ON Pump down / Cool force on
2 Short Beep
Others 1 Short Beep
LED Indicator Lights: Normal Operation And Fault Conditions For Cooling/Heat Pump Unit
ADDITIONAL CHARGE
The refrigerant is pre-charged in the outdoor unit. If the piping length is less than 7.5m, then additional charge after vacuuming is not necessary. If the piping length is more than 7.5m, then use the additional charge value as indicated in the table.
Additional refrigerant charge [g] per additional 1m length as tabulated
Indoor ATXB50CV1B ATXB60CV1B Outdoor ARXB50CV1B ARXB60CV1B Additional charge [g/m] 20 20
Example:
ATXB50CV1B & ARXB50CV1B with 12m piping length, additional piping length is 4.5m. Thus, Additional charge = 4.5[m] x 20[g/m]
= 90.0[g]
1-12
English
1-13
20 18
10
0
201510 25 27 30
-10
-15
-20
50 46 43
40
30
20
10
10 14 15 19 20 23 25
-10
-20
0
Dry Mode
When the air humidity is high, the unit can operate in dry mode. Press <MODE> button and choose <DRY>. If the room temperature is 2°C/3.6°F higher than the set temperature, the air conditioner will operate under cooling mode until it reaches within the 2°C/3.6°F range of difference compared to the set temperature before it converts to dry mode. If the room temperature is within the 2°C/3.6°F range of difference compared to the set temperature, it will directly operate under dry mode. The unit will operate at LOW speed under dry mode.
Heat Mode (for heat pump unit only)
When the unit is switched on from cold start or defrosting cycle, the indoor fan will start to operate only after the coil reaches the desired temperature. When the set temperature is achieved, the indoor fan will operate until the coil cannot provide anymore additional heat.
Air Flow Control
For more effective air circulation, you can manually adjust the air discharge grille to the left or right. During cool mode operation and dry mode operation, do not direct the air discharge louver downwards for too long. If operating continues in this way, condensation may occur on the louver, thus resulting in drippings.
Fan Speed And Rated Cooling Capacity
The rated cooling capacity is provided at the HIGH fan speed. The cooling capacity is lower when the unit is operating at MEDIUM and LOW fan speed.
Notes On Flaps And Louvers Angles
When “SWING button” is selected, the flaps swinging range depends on the operation mode. (See the figure.)
ATTENTION
Always use a remote controller to adjust the flaps angle. If you attempt to move it forcibly with hand when it is swinging, the mechanism may be broken. Be careful when adjusting the louvers. Inside the air outlet, a fan is rotating at a high speed.
Overheating Protection (for heat pump unit only)
In case the internal and/or the external temperature is too high, or that the fi lter is dirty and clogged up, the refrigerant may be overheated. The compressor will cut out when the condensing temperature reaches 62°C/143.6°F.
Frost Prevention
When the air fi lter is dirty, the evaporating temperature will decrease and eventually cause frosting. If the evaporating temperature reaches -1°C/33.8°F, the unit will trip.
AIR CONDITIONER UNIT OPERATION
DB: Dry bulb WB: Wet bulb
INDOOR TEMP (˚CWB)
COOLING HEATING
OUTDOOR TEMP (˚CDB)
OUTDOOR TEMP (˚CWB)
Model: ATXB50/60CV1B ARXB50/60CV1B
INDOOR TEMP (˚CDB)
OPERATING RANGE
FRONT
Recess on main unit
Filter frame
Tab
Air filter
Bio filter with bacteriostatic, virustatic functions
Bio Filter packs in a hermetically-sealed bag.
Take it out at the time of installation.
Slip the Filter in between Filter frame and Titanium Apatite Filter.
Titanium Apatite Filter
Bio Filter
Filter frame
Titanium Apatite Filter (Bio Filter) Attached Concept
Air Filter
Heat exchanger
Bio Filter attached part
Titanium Apatite Filter
AIR FILTER
! CAUTION
Please use this Bio Filter during dry season such as winter. Storage, handling and disposal methods.
The lifetime of this Bio Filter is about a year after opening. In case you do not use this Bio Filter right away, please don’t place the Bio Filter in any place where it will be
subjected to direct sunlight, high temperatures and/or high humidity. There can be slight differences between Bio Filter color because of the manufacturing reasons, there is no effect
on the unit performance. Please open this bag right before you use it. Bio Filter should remain unopened and sealed in its packaging until
right before usage. (It may cause performance deterioration or quality change.) To avoid danger of suffocation and any unexpected accident, please dispose the plastic bag immediately after you
remove the Bio Filter. Keep out of reach of babies and children. If you keep this Bio Filter for a long time, please keep it unopened and store in a cool place avoiding direct
sunlight. Please dispose the old Bio Filter as nonflammable garbage after use.
Operation with dirty filters:
(1) cannot deodorize the air. (3) results in poor heating or cooling. (2) cannot clean the air. (4) may cause odour.
To order Bio Filter, contact the service shop where you bought the air conditioner.
Open the front panel.
Hold the panel at the recesses on the main unit (2 recesses on right and left sides) and lift it until it stops.
1.
Clean or replace each filter.
See figure.
When shaking off remaining water, do not wring the filter.
4.
Pull out the air filters.
Push a little upwards the tab at the center of each air filter, then pull it down.
2.
Set the air filter and Bio filter with bacteriostatic, virustatic functions as they were and close the
front panel.
Insert claws of the filters into slots of the front panel. Close the front panel slowly and push the panel at the 3 points. (1 on each side and 1 in the middle.)
The air filter and Bio filter with bacteriostatic, virustatic functions have a symmetrical form in the horizontal direction.
5.
Take off the Bio filter with bacteriostatic,
virustatic
functions.
Hold the recessed parts of the frame and unhook the four claws.
3.
Installation Procedure for Bio Filter
* Bio Filter and Titanium Apatite Filter are optional accessories.
1-14
English
1-15
Note is valid for Turkey only: The lifetime of our products is ten (10) years
Rotating shaft
Recess on main unit
SERVICE AND MAINTENANCE
Open the front panel.
Hold the panel at the recesses on the main unit (2 recesses on right and left sides) and lift it until it stops.
1.
Remove the front panel.
While lifting the front panel further, slide it to the right and pull it to the front side. The left rotating shaft is detached. Slide the right rotating shaft to the left and pull it to the front side to remove it.
2.
Attach the front panel.
Align the right and left rotating shafts of the front panel with the grooves and push them all the way in.
Gently close the front panel. (Push both ends and the center on the front panel.)
3.
Service Parts Maintenance Procedures Period
Indoor air filter Remove any dust adhering to the filter by using a vacuum cleaner or
wash in lukewarm water (below 40°C/104°F) with a neutral cleaning detergent. Rinse the filter well and dry before placing it back onto the unit. Do not use gasoline, volatile substances or chemicals to clean the filter.
1.
2.
3.
At least once every 2 weeks.
More frequently if necessary.
Indoor unit Clean any dirt or dust on the grille or panel by wiping it with a soft
cloth soaked in lukewarm water (below 40°C/104°F) and a neutral detergent solution. Do not use gasoline, volatile substances or chemicals to clean the indoor unit.
1.
2.
At least once every 2 weeks.
More frequently if necessary.
! CAUTION
• Avoid direct contact of any coil treatment cleaners on plastic part. This may cause plastic part to deform as a result of chemical reaction.
Remove the power plug. If you are using an independent electric circuit for your unit, cut off the circuit. Remove the batteries in the remote control.
! CAUTION
Don’t touch the metal parts of the indoor unit. It may cause an injury. When removing or attaching the front panel, support the panel securely with hand to prevent it from falling. For cleaning, do not use hot water above 40°C, benzine, gasoline, thinner, nor other volatile oils, polishing
compound, scrubbing brushes, nor other hand stuff. After cleaning, make sure that the front panel is securely fixed.
When The Unit Is Not To Be Used For An Extended Long Period Of Time
Operate the unit for 2 hours with the following setting.
Operating mode : cool Temperature : 30°C/86°F
TROUBLESHOOTING
For any enquiries on spare part, please contact your authorized dealer. When any malfunction of the air conditioner unit is noted, immediately switch off the power supply to the unit. Check the following fault conditions and causes for some simple troubleshooting tips.
Fault Causes / Action
The compressor does not operate 3 minutes after the air
1. Protection against frequent starting. Wait for 3 to 4 minutes conditioner unit is started.
The air conditioner unit does not operate.2. Power failure, or the fuse needs to be replaced.
for the compressor to start operating.
The power plug is disconnected.
It is possible that your delay timer has been set
incorrectly.
If the fault persist after all these verifications, please contact the air conditioner unit installer.
The air flow is too low.3. The air filter is dirty.
Discharge air flow has bad odour.4. Odours may be caused by cigarettes, smoke particles,
Condensation on the front air grille of the indoor unit.5. This is caused by air humidity after an extended long
Water flowing out from the air conditioner unit.6. Switch off unit and call dealer.
– –
The doors or windows are open.
The air suction and discharge are clogged.
The regulated temperature is not high enough.
perfume etc. which might have adhered onto the coil.
period of operation. The set temperature is too low, increase the temperature
setting and operate the unit at high fan speed.
If the fault persists, please call your local dealer / serviceman.
1-16
Unité Intérieure
CONTOUR ET DIMENSIONS
PLAQUE D’INSTALLATION ATXB50/60CV1B
Dimension
Modèle
A B C D E F G H I J K L M
ATXB50/60CV1B 1065 310 228 190 173 61 40 45 48 91 219 580 45
D E
B
F
G
K I
ML
H I
FG
Toutes les dimensions sont données en mm
Trou percé dans le mur à Ø 65mm
Position du tuyau d’évacuation
Extrémité du tuyau de liquide
Extrémité du tuyau de gaz
©
Points de fixation de la plaque de montage recommandés
(7 points en tout)
Toutes les dimensions sont données en mm
A
B
VUE DE DEVANT
VUE DE DESSUS
C
VUE LATÉRALE
B
LA MARQUE INDIQUE LA DIRECTION DES TUYAUX
ARRIÈRE ARRIÈRE
DROITEGAUCHE
BAS BAS
VIS FIXES DE LA GRILLE AVANT (INTÉRIEUR)
VOLET
SIGNAL DE RÉCEPTION
UNITÉ INTÉRIEURE INTERRUPTEUR DE MARCHE/ARRÊT
THERMISTOR DE TEMPÉRATURE DE LA PIÈCE (INTÉRIEUR)
PLAQUE D’IDENTIFICATION
RÉPARTITEUR AVEC BORNE DE MISE À LA TERRE
Français
Traduction des instructions d’origine
2-1
B
A
Q
P
R
S
DO
KL L
M
N
F
E
C
G H
I
J
N
Dimension
Modèle
A B C D E F G H I J K L M N
ARXB50/60CV1B 855 730 328 520 179 46 93 149 101 113 603 126 164 15
Unité Extérieure ARXB50/60CV1B
Dimension
Modèle
O P Q R S
ARXB50/60CV1B 34 23 362 73 75
Toutes les dimensions sont données en mm
2-2
Français
! ATTENTION ! AVERTISSEMENT
L’installation et la maintenance doivent être exécutées par une personne qualifi ée qui est familiarisée avec les lois et réglementations en vigueur, et aussi expérimentée dans ce type d’équipements. Tous les câblages doivent répondre aux réglementations électriques nationales. Avant de commencer le raccordement suivant le schéma électrique, s’assurer que la tension nominale de l’appareil corresponde bien à celle indiquée sur la plaque signalétique. L’unité doit être raccordée à la TERRE pour prévenir tous les risques possibles dûes à un défaut d’isolation. Aucun câble électrique ne doit toucher la tuyauterie du réfrigérant, le compresseur ou les pièces mobiles des moteurs de ventilation. Avant l’installation ou l’entretien du climatiseur, s’assurer que l’appareil est éteint (OFF). Débrancher l’appareil du circuit d’alimentation secteur avant de procéder à l’entretien du climatiseur. NE PAS retirer le câble d’alimentation électrique de la prise quand l’appareil est sous branché. Il peut en résulter des décharges électriques importantes susceptibles de provoquer un incendie. Les unités intérieures et extérieures, le cordon d’alimentation et le câblage de transmission doivent rester à une distance d’au moins 1m des téléviseurs et des radios, ce afi n d’éviter les images déformées et les parasites. {En fonction du type et de la source des ondes électriques, des parasites peuvent être entendus même avec une distance supérieure à 1m}.
Vérifier les points suivants au cours de l’installation.
Ne pas installer l’appareil où il peut se produire des fuites de gaz inflammable.
En cas de fuite et accumulation de gaz autour de l’appareil, il y a risque d’incendie.
S’assurer que le tuyau d’évacuation du condensat est correctement branché.
Si le tuyau d’évacuation n’est pas correctement branché, les éventuelles fuites d’eau risquent de mouiller le mobilier.
Ne pas surcharger l’unité (en fluide frigorigène).
Cet appareil est préchargé en usine. Une charge trop importante risque de provoquer une surcharge électrique ou d’endommager le compresseur.
S’assurer que le panneau supérieur de l’appareil est remis en place après l’installation ou l’entretien.
Avec un panneau mal fixé l’appareil va fonctionner bruyamment.
Les bords coupants et les surfaces du refroidisseur tubulaire présentent un risque de blessure. Mieux vaut éviter le contact avec ces endroits. Avant de couper l’alimentation électrique, veiller à ce que
l’interrupteur ON/OFF de la télécommande soit en position « OFF » afin d’éviter une mise en marche
intempestive de l’appareil. Si l’interrupteur de la
télécommande n’est pas en position « OFF », les ventilateurs de l’appareil se mettront en marche dès que l’alimentation électrique est rétablie. Il peut en résulter un danger pour le personnel d’entretien ou l’utilisateur.
Ne pas installer les appareils à proximité ou près d’un passage de porte. Ne pas utiliser un appareil de chauffage trop près d’une unité de climatisation ou l’utiliser dans une pièce où, de l’huile minérale ou de la vapeur d’huile existent, cela peut faire fondre ou se déformer les pièces en plastique en raison de la chaleur excessive ou de réaction chimique. Lorsque l’appareil est utilisé dans la cuisine, le garder loin de la farine qui
peut aller dans d’aspiration de l’appareil. Cet appareil n’est pas approprié pour une utilisation en usine lorsqu’un brouillard d’huile de coupe ou de la poudre de fer existe ou bien quand la tension fluctue grandement. Ne pas installer les unités à des endroits comme une source d’eau chaude ou une raffinerie de pétrole où des gaz sulfureux existent. S’assurer que la couleur des câbles de l’unité extérieure et les marquages de bornes sont identiques à ceux de l’unité intérieure. IMPORTANT : NE PAS INSTALLER OU UTILISER LE CLIMATISEUR DANS UNE BUANDERIE.
N’utilisez pas de câbles joints et torsadés pour l’alimentation électrique entrante. L’équipement n’est pas destiné à être utilisé dans une atmosphère potentiellement explosive.
PRÉCAUTIONS DE SÉCURITÉ
MANUEL D’INSTALLATION
AVIS
Instructions d’élimination
Cet appareil de conditionnement d’air porte le symbole ci-joint. Ce symbole signifi e que les appareils électriques et électroniques doivent être éliminés séparément des ordures ménagères non triées. N’essayez pas de démonter vous-même l’appareil : le démontage de l’appareil de conditionnement d’air ainsi que le traitement du réfrigérant, de l’huile et d’autres composants doivent être effectués par un installateur qualifi é, en accord avec les réglementations locales et nationales en vigueur. Les appareils de conditionnement d’air doivent être traités dans des installations spécialisées de dépannage, réutilisation ou recyclage. En vous assurant que cet appareil est éliminé correctement, vous contribuez à éviter les conséquences potentiellement néfastes sur l’environnement et la santé. Veuillez contacter votre installateur ou les autorités locales pour plus d’information. Les piles de la télécommande doivent être enlevées et éliminées séparément, conformément aux réglementations locales et nationales en vigueur.
Ce manuel fournit les procédures d’installation pour assurer le bon fonctionnement et la sécurité de cet appareil. Des ajustements peuvent être nécéssaires pour suivre les réglementations locales. Avant d’installer et de faire fonctionner le climatiseur, lisez attentivement ce manuel et conservez le. Cet appareil est destiné à être utilisé par des utilisateurs experts ou formés dans les magasins, dans l’industrie légère ou dans les fermes, oupour un usage commercial par des personnes non spécialisées. Cet appareil n’est pas destiné à être utilisé par des personnes, y compris les enfants, souffrant de capacités physiques, sensorielles ou mentales réduites, ou accusant un manque d’expérience et de connaissances, sauf si elles sont supervisées ou ont reçu des instructions concernant l’emploi de cet appareil d’une personne responsable de leur sécurité. Les enfants doivent être supervisés pour s’assurer qu’ils ne jouent pas avec l’appareil.
2-3
Information importante relative au réfrigérant utilisé
Ce produit contient des gaz fluorés. Ne pas laisser les gaz s’échapper dans l’atmosphère. Type de réfrigérant: R410A
Valeur GWP
(1)
: 2087,5
(1)
GWP = Potentiel De Réchauffement Global
Prière de compléter à l’encre indélébile,
1 la charge de réfrigerant d’usine du produit, 2 la quantité de réfrigérant supplémentaire chargée sur place et 1 + 2 la charge de réfrigérant totale
sur l’étiquette de charge de réfrigérant fournie avec le produit. L’étiquette complétée doit être apposée à proximité de l’orifice de recharge du produit (par ex. à l’intérieur du couvercle d’entretien).
charge de réfrigérant d’usine du produit : voir plaquette signalétique de l’unité
(2)
quantité de réfrigérant supplémentaire chargée sur place
charge de réfrigérant totale
contient effet de serre fluorés
Unité extérieure
cylindre de réfrigérant et collecteur de recharge
(2)
Dans le cas de multiples systèmes intérieurs, seule 1 étiquette doit être apposée*, mentionnant la charge de réfrigérant
d’usine totale de toutes les unités intérieures raccordées au système de réfrigérant. Des inspections périodiques de fuites de réfrigérant peuvent être exigées en fonction de la législation européenne ou locale.
Veuillez contacter votre distributeur local pour plus d’informations. * sur l’unité extérieure
1
2
3
4
5
6
IMPORTANT
2-4
DIAGRAMME D’INSTALLATION
2-5
Français
Unité Intérieure
Filtre à air
M4 x 12L
Panneau avant
75mm ou plus du plafond
Unité Extérieure
50mm ou plus des murs (des deux côtés)
Trou pour la tuyauterie calfaté avec du mastic.
Coupez le tuyau d’isolation thermique sur une longueur appropriée et enroulez-la de ruban en vous assurant qu’aucun espac en’est laissé à l’endroit de la coupe du tuyau d’isolation thermique.
Enroulez le tuyau d’isolation avec la bande de finition du bas jusqu’en haut.
Couvercle de service
Ouverture du couvercle de service
Le couvercle de service est de type à ouverture/fermeture.
Méthode d’ouverture
1) Enlevez les vis du couvercle de service.
2) Abaissez le couvercle de service en diagonale dans le sens de la flèche.
3) Tirez vers le bas.
y
y
250mm des murs
INSTALLATION DE L’UNITÉ EXTÉRIEURE
L’unité extérieure doit être installée de manière à ce qu’il n’y ait pas de reprise d’air chaud ou d’obstruction au débit régulier d’air. Veuillez respecter l’écartement d’installation illustré sur le diagramme. Choisir l’emplacement le plus frais possible, où l’admission d’air ne soit pas plus élevée que la température de l’air extérieure (se reporter à la plage de fonctionnement).
Dégagements minimum
Remarque : En cas d’obstacles de part et d’autre de l’unité
d’une hauteur supérieure à 2 mètres ou toute obstruction d’air sur le dessus de l’unité, augmenter sensiblement les dégagements minimum prévus.
Dimension
A B C D
Distance Minimume, mm 300 1000 300 500
Reprise d’air
Accès de service
C
D
Obstacle
Obstacle
Entrée d’air
Refoulement d’air
A
B
Obstacle
Obstacle
H
H/2
Disposition Condensée De L’eau D’unité Extérieure (Unité De Pompe À Chaleur Seulement)
Il y a 2 trous sur la base de l’unité extérieure pour que l’eau condensée sorte. Insérez le coude de drain à un des trous. Pour installer le coude de drain, première insertion une partie du crochet sur la base (partie A), tirer alors le coude de drain dans la direction montrée par la flèche tout en insérant l’autre partie à la base. Après installation, contrôle pour s’assurer que le coude de drain s’accrochent à la base fermement. Si l’unité est installée dans un neigeux et chily un secteur, l’eau condensée peut geler dans la base. Dans un tel cas, enlevez svp la prise au fond de l’unité pour lisser le drainage.
Veuillez enlever le plat latéral en reliant lat uyauterie et en reliant la corde
POUSSER ET TIRER VERS LE HAUT
BASE
A
VIDANGEZ LE COUDE VIDANGEZ LE COUDE
PRISE
Installer l’unité intérieure de traitement d’air de façon à ce qu’il n’y ait aucun obstacle sur la circulation de l’air (risque de recyclage de l’air refroidi au refoulement de l’unité et l’air à l’entrée). Veuillez respecter l’écartement d’installation illustré sur le diagramme. Ne pas exposer l’unité intérieure à l’influence directe de l’éclairage. L’emplacement de l’unité, doit permettre une évacuation aisée des condensats, et permettre une evacuation aisee des condensats, et doit être suffisamment loin des portes.
min. 50
(Espace pour
entretien)
Flux d’air (Intérieur)
La tuyauterie de réfrigérant peut être dirigée vers l’appareil de plusieurs façons (sur la gauche ou la droite, depuis l’arrière de l’appareil), par le biais des orifices défonçables situés sur l’enveloppe de l’appareil. Cintrer les tuyaux avec précaution afin de les aligner avec les orifices. Pour les sorties latérale et inférieure, maintenir le bas de la tuyauterie et la positionner dans la bonne direction. Le flexible d’évacuation des condensats peut être fixé aux tuyaux.
Tuyauterie sur le côté droit, à l’arrière droite ou en bas à droite
min. 50 (Espace pour
entretien)
min 75
(Espace pour
performance)
Espace nécessaire
Tuyautage du côté arrière droit
Toutes les dimensions sont données en mm
Tuyautage du côté inférieur droit
Tuyautage du côté droit
Retirez le couvercle du port du tube ici pour le tuyautage du côté droit
Tuyautage du côté arrière gauche
Tuyautage du côté gauche
Tuyautage du côté inférieur gauche
Tuyauterie sur le côté gauche, à l’arrière gauche ou en bas à gauche
INSTALLATION DE L’UNITÉ INTÉRIEURE
Retirez le couvercle du port du tube ici pour le tuyautage du côté inférieur droit
Attachez ensemble le tube de réfrigérant avec le tuyau de vidange avec du ruban isolant.
Retirez le couvercle du port du tube ici pour le tuyautage du côté gauche
Retirez le couvercle du port du tube ici pour le tuyautage du côté arrière gauche
2-6
Français
Montage De La Platine Support
S’assurrer que le mur de support soit suffisamment résistant, pour supporter le poids de l’unité et éviter toutes vibrations. Selon la composition du mur, utiliser des vis chevilles appropriées pour la fixation de la platine support. Utilisez l’indicateur de niveau pour le montage horizontal, et fixez-le avec 7 vis adaptées pour ATXB50/60CV1B. Dans le cas de sortie arrière des tuyauteries, percer le trou Ø 65mm pour les canalisations à l’aide d’une scie cloche. Le trou aura une légère pente vers l’unité extérieure (voir figure).
Point De Retenue Et Dimensions Recommandés Pour La Platine De Montage
Trou Avec Perceuse En Cône
Intérieur
Ø 65
Tube noyé dans le mur (À se procurer sur place)
Couvercle de trou de mur (À se procurer sur place)
Tube noyé dans le mur (À se procurer sur place)
Extérieur
Calfatage
Plaque de montage
Vis de fixation de la plaque de montage
Trou percé dans le mur à Ø 65mm
190
173
61
310
61
Position du tuyau d’évacuation
Extrémité du tuyau de gaz
Extrémité du tuyau de liquide
48
45
580
1065
219
40
40
91
45
Toutes les dimensions sont données en mm
©
Points de fixation de la plaque de montage recommandés (7 points en tout)
Fuite
d’eau
Rétention de l’eau
Evacuation d’eau de condensation plongé dans l’eau
Drainage
Correct Mauvais
Fuite
d’eau
Fuite
d’eau
Mauvais Mauvais
Évacuation Des Condensats
Le tube d’évacuation des condensats de l’unité devra être, dans la mesure du possible, dirigé vers la sortie arriere des tuyauteries a travers le mur de support. Evitez les situations susceptibles de causer une fuite d’eau.
Drainage De L’eau
Comment Fixer L’unité Interne
Accrochez les griffes de la structure inférieure à la plaque de montage.
Comment Démonter L’unité Interne
Soulevez la zone marquée d’un repère (au bas de la grille avant) pour libérer les griffes.
Mise En Place De L’unite De La Platine Support
Positionner dans un premier temps l’unité intérieure sur la languette d’accrochage supérieure de support. Pour vous assurer que les crochets sont correctement installés sur la plaque d’installation, essayez de les faire légèrement bouger de gauche à droite.
Quand vous dénudez en avance les fil s d’in terconn exion, recouvrez les extrémités des fils avec du ruban isolant.
Accrochez les crochets de l’appareil intérieur ici.
Plaque de montage
Fils d’interconnexion
Guide de fil
! AVERTISSEMENT
N’installez pas l’unité, intérieure comme extérieure, à une altitude supérieure à 2000m.
Plaque de montage
Attache
Châssis inférieur
Repère (à l’arrière)
Grille frontale
2-7
2-8
L E
* Assurez-vous d’ajouter la quantité correcte de réfrigérant additionnel. Sinon, cela pourrait conduire à une réduction de
performance
Remarque : La charge complète de gaz se trouve dans l’unité extérieure jusqe’à une longueur nominale de 7,5 mètres aucun
complément en réfrigérant n’est nécéssaire.
Longueur admissible de tuyauterie
Une tuyauterie trop longue va diminuer à la fois la performance et la fiabilité de lάappareil. Plus le nombre dάangles est grand,
plus le système de réfrigérant résiste au flux, ce qui affaiblit la capacité de refroidissement. En conséquence, le compresseur peut connaître des défectuosités. Choisissez toujours le chemin le plus court et suivez les recommandations données dans le tableau ci-dessous:
RACCORDEMENTS DES TUYAUTERIES
Modèle ATXB50CV1B ATXB60CV1B Longueur minimum admissible (L), m 3 Longueur maximale autorisée (L), m 30 Élévation Admise Max (E), m 10 Racc. Tube Aspiration, mm / (pouces) 12,70 (1/2") 15,88 (5/8") Racc. Tube Liquide, mm / (pouces) 6,35 (1/4")
Unité Extérieure
Unité intérieure
Remarques :
Longueur de tuyauterie équivalente est obtenue avec la longueur réelle de tuyauterie de gaz. 90° coude de la tuyauterie est équivalent à L joint.
1.
2.
Longueur èquivalente pour le montage différents (mètre)
Tuyau L conjointe
Virage piège
3/8" (OD9,52mm) 0,18 1,3 1/2" (OD12,7mm) 0,20 1,5 5/8" (OD15,9mm) 0,25 2 3/4" (OD19,1mm) 0,35 2,4 7/8" (OD22,2mm) 0,40 3 1" (OD25,4mm) 0,45 3,4 1 1/8" (OD28,6mm) 0,50 3,7 1 3/8" (OD34,9mm) 0,60 4,4
Les coudes doivent être réalisés avec soin afin de ne pas écraser le tuyau. Utilisez un cintreuse de plier un tuyau lorsque cela est possible.
2-9
Français
Travail Des Tuyauteries Et Technique Flare
Ne pas utiliser de tuyauteries en cuivre encrassé ou endommagé. Si de la tuyauterie, un évaporateur ou un condensateur a été exposé ou a été ouvert pendant 15 secondes, passer le système à l’aspirateur. En règle générale ne pas retirer le plastique, les bouchons en caoutchouc et les écrous en laiton des vannes, raccords, tuyaux et bobines jusqu’à ce que cela soit prêt de raccorder le conduit d’aspiration ou de liquide dans les vannes ou les raccords.
Si l’on doit effectuer un travail de soudage, s’assurer que l’azote passe par les serpentins et les joints durant le travail du soudage. Cela permettra d’éliminer la formation de suie sur la paroi interne des tubes en cuivre.
Couper le tuyau étape par étape, avancer la lame du coupe­tube lentement. Une coupe profonde et forcée va déformer le tube davantage et ainsi causer plus de bavures. Voir Schéma I.
Ebarber les bords coupés des tubes à l’aide d’un alésoir. Voir Schéma II. Tenir le tuyau en haut et l’ébarbeur à une position plus basse pour éviter que des morceaux de métal n’entrent dans le tuyau. Pour éviter toutes irrégularités sur les faces évasées, qui risqueraient de causer des fuites de gaz.
Relier les écrous ‘flare’ montés sur les connexions des unités intérieure et extérieure aux tubes de cuivre.
La longueur exacte de tube dépassant de la dudgonnière dépend du type de dudgonnière utilisé. Voir Schéma III.
Placer le tube fermement dans la dudgeonnière. Aligner les centres des deux blocs d’emboutissage et poinçonnage, et puis serrez le poinçon au maximum.
Raccordement de la tuyauterie aux unités
Aligner le centre de la tuyauterie et serrer assez fort le raccord conique à la main. Voir Schéma IV.
Enfin, serrer l’écrou à l’aide d’une clef dynamométrique jusqu’au clic.
En serrant l’écrou avec la clef dynamométrique, veiller à respecter le sens de la flèche indiqué sur la clef.
Le raccordement du tuyau de réfrigérant doit être isolé par du polyuréthane à cellules fermées.
1/4t
Coupe des Tubes Cuivre
Tube Cuivre
Dudgeonniere
Ebavurage
Schéma I
D
A
Tuyau, mm (pouce) Couple, Nm / (ft-lb)
6,35 (1/4") 18 (13,3)
12,70 (1/2") 55 (40,6)
15,88 (5/8") 65 (48,0)
Ø Tube, D A (mm)
Pouce mm Impérial
(Type d’écrou à oreilles)
Normal
(Type d’embrayage)
1/4" 6,35 1,30 0,70 1/2" 12,70 1,90 1,30 5/8" 15,88 2,20 1,70
RACCORDEMENTS DES TUYAUTERIES
Schéma II
Schéma III
Tube Cuivre
Tube Avec Dudgeon
Raccord à Visser
ÉcrouTube de l’Unité Intérieure
Clef Dynamométrique
Clef d’Immobilisation
Schéma IV
Fixez le manchon d’isolation
Borne à sertir ronde
Fil électrique
RACCORDEMENT ÉLECTRIQUE
IMPORTANT : * Les valeurs ci-dessus ne sont données qu’à titre indicatif. Elles doivent, par conséquent, être vérifiées
et choisies de façon à répondre aux lois et aux réglementations en vigueur dans le pays concerné. Elles sont en plus fonction du type d’installation et des conducteurs utilisés.
** Le voltage adéquat doit être vérifié avec les données de l’étiquette sur l’appareil.
Tous les fils doivent être fermement connectés. Aucun fil électrique ne doit toucher ni la tuyauterie du réfrigérant, ni le compresseur, ni les pièces mobiles du moteur de ventilation. Le câble de raccordement entre l’unité intérieure et l’unité extérieure doit être fixé à l’aide du collier fourni. Le cordon électrique doit être êquivalent à H07RN-F au minimum. Les connecteurs et les câbles du répartiteur ne doivent subir aucune pression externe. Tous les couvercles doivent être correctement fixés pour éviter tout vide. Utilisez des bornes à sertir rondes pour la connexion des fils au bloc d’alimentation. Connectez les fils en les faisant correspondre aux indications du bornier. (Référez-vous au schéma de câblage apposé sur l’unité).
Connect wires of the same gauge to both side.
Do not connect wires of the same gauge to one side.
Do not connect wires of different gauges.
Utilisez le bon tournevis pour serrer les vis du répartiteur. Utiliser un tournevis non adapté peut endommager la tête de la vis. Ne pas trop serrer sous peine d’endommager la vis de bornes. Ne connectez pas de fils de sections différentes au même répartiteur. Réalisez le câblage de façon ordonnée. Le câblage ne doit pas obstruer les autres pièces ni le couvercle du boîtier du répartiteur.
2
SIG
1
Bornier De L’unité
Extérieure
Bornier De L’unité
Intérieure
Il doit y avoir une déconnexion de tour les pôles de l’alimentation secteur avec une séparation des contacts d’au moins 3mm.
!
2
SIG
1
Câble
d’interconnexion
N
L
Bornier d'alimentation
Utilisez le type de fil spécifié et le connecter en toute sécurité.
Fermement retenue de fil sécurisé terminaisons de sorte fils ne recevront pas une contrainte externe.
Forme fils de façon à ce que le couvercle de service et arrêter couvercle de soupape se adaptent en toute sécurité.
N / L2 L / L1
Alimentation
électrique
Interrupteur
principal
Fusible /
disjoncteur
Câble d’alimentation
Modèle
ATXB50/60CV1B ARXB50/60CV1B
Tension d’alimentation
**
220-240V/~/50Hz +
!
Section du câble d’alim
*
mm
2
Nombre de conducteurs
2,5
3
Section du câble de liaison
*
mm
2
Nombre de conducteurs
2,5
4
Fusible/circuit recommandé note du disjoncteur A 20
2-10
Français
PRÉCAUTIONS SPÉCIALES EN TRAITANT L’UNITÉ DE R410A
R410A est un nouveau réfrigérant de HFC qui n’endommage pas la couche d’ozone. La pression de travail de ce nouveau réfrigérant est 1,6 fois supérieure à celle d’un réfrigérant conventionnel (R22), une installation appropriée et un bon entretien sont donc essentiels.
Jamais réfrigérant de l’utilisation autre que R410A dans un climatiseur qui est conçu pour fonctionner avec R410A. De l’huile POE ou PVE est employée comme lubrifiant pour le compresseur de R410A, qui est différente de l’huile minérale utilisée pour le compresseur R22. Pendant l’installation ou l’entretien, des précautions supplémentaires doivent être prises pour ne pas exposer le système de R410A trop long à l’air moite. L’huile résiduelle de POE ou de PVE dans la tuyauterie et les composants peuvent absorber l’humidité de l’air. Pour empêcher mischarging, le diamètre du port de service sur la valve de fusée est différent de celui de R22.
Employez les outils et les matériaux exclusivement pour le réfrigérant R410A. Les outils exclusivement pour R410A sont valve diverse, tuyau de remplissage, indicateur de pression, détecteur de fuite de gaz, outils de fusée, clé dynamométrique, pompe de vide et cylindre de réfrigérant. Car un climatiseur de R410A encourt une pression plus élevée que les unités R22, il est essentiel de choisir les pipes de cuivre correctement. Jamais diluant de cuivre de pipes d’utilisateur que 0,8mm quoiqu’ils soient disponibles sur le marché. Si le gaz de réfrigérant fuit pendant l’installation/servicing, soyez sûr d’aérer entièrement. Si le gaz réfrigérant entre en contact avec le feu, un gaz toxique peut se produire. En installant ou en enlevant un climatiseur, ne laissez pas l’air ou l’humidité rester dans le cycle réfrigérant.
TIRAGE AU VIDE ET CHARGE
Aspirer est nécessaire pour éliminer toute humidité et air du système.
Aspiration sous vide des tuyauteries et de l’unité intérieure
Hormis pour l’appareil extérieur pré-chargé de réfrigérant, l’unité intérieure et les tuyaux de connexion doivent être purgés car l’air restant dans le cycle frigorifique contient de l’humidité et est susceptible de provoquer un dysfonctionnement du compresseur.
Enlever le bouchon central, ainsi que le bouchon de la prise de pression sur chaque vanne. Raccorder le centre de la jauge de chargement à la pompe à vide. Raccorder la jauge de chargement à l’orifice de service de la valve à trois voies. Démarrer la pompe à vide. Évacuer pendant environ 30 minutes. La période d’évacuation varie selon la capacité de la pompe à vide. S’assurer que l’aiguille de la jauge de chargement se soit déplacée vers –760mmHg.
Avertissement
Si l’aiguille du manomètre ne bouge pas -760mmHg, assurez-vous de vérifier les fuites au type de fusée connexion de l’unité intérieure et extérieure et réparer la fuite avant de passer à l’étape suivante. Fermer la valve de la jauge de chargement et éteindre la pompe à vide. Sur l’unité extérieure, ouvrir la valve de succion (3 voies) et la valve de liquide (2 voies) (dans le sens inverse des aiguilles d’une montre) à l’aide d’une clé pour vis hexagonales de 4mm.
Opération de chargement
Cette opération nécessite impérativement l’utilisation d’un cylindre de charge ou une balance de précision. Le complement de charge se fait sur l’unité extérieure par la vanne d’aspiration via la prise de pression de la vanne de service.
Enlever le bouchon de la vanne de service. Raccorder le côté de basse pression de la jauge de chargement à l’orifice de succion du réservoir cylindrique et fermer le côté de haute pression de la jauge. Éliminer l’air du tuyau de service. Mettre le climatisateur en marche. Ouvrir le cylindre de gaz et la valve de chargement de basse pression. Lorsqu’une quantité suffisante de réfrigérant est injectée dans l’unité, fermer le côté basse pression et la valve du cylindre de gaz. Débrancher le tuyau de service de l’orifice de service. Remettre le bouchon de l’orifice de service.
Tuyauteries Frigorifiques
Unité Extérieure Vanne 3 Voies
Cléf Allen
Prise de Pression
Écrou
MANOMÈTRE HAUTE PRESSION
MANOMÈTRE DE PRESSION
MANOMÈTRE BASSE PRESSION
POIGNÉE HI (HAUTE) (TOUJOURS FERMÉE)
TUYAU DE REMPLISSAGE
-760mmHg
POIGNÉE LO
TUYAU DE REMPLISSAGE
ADAPTATEUR DE POMPE A VIDE POUR
LA PRÉVENTION DE RETOUR DE FLOT
CLAPET DE NON-RETOUR
ROBINET DU LIQUIDE
MANOMÈTRE HAUTE PRESSION
MANOMÈTRE BASSE PRESSION
MANOMÈTRE DE PRESSION
-760mmHg
POIGNÉE LO
POIGNÉE HI (HAUTE) (TOUJOURS FERMÉE)
TUYAU DE REMPLISSAGE
TUYAU DE REMPLISSAGE
CLAPET DE NON-RETOUR
ROBINET DU
LIQUIDE ROBINET DE GAZ (3 VOIES)
CONFIGURATION DE PURGE D’AIR PAR CHARGE
CONFIGURATION DE PURGE D’AIR PAR CHARGE
ROBINET DE GAZ (3 VOIES)
2-11
ON/OFF
REFROIDISSEZ/CHALEUR
(VERT/ROUGE)
Fonctionnement
VERT
Mode de refroidissement
ROUGE
Mode chauffage
ROUGE
Mode Chauffage automatique
VERT
Mode Refroidissement automatique Minuterie en marche
Mode de sommeil
VERT
Mode ventilateur activé
VERT
Mode sec activé
ROUGE
Dégivrage
VERT
Erreur de l’unité
SUR
Led clignotante
IR Récepteur De Signal
Lorsqu’un signal de fonctionnement est transmis par une télécommande à infrarouges, le récepteur de signal de l’unité intérieure répond comme ci-dessous pour confi rmer l’acceptation de la transmission du signal.
L’indicateur LED S’allume Pour L’unité De Refroidissement / Module Pompe À Chaleur
IR Récepteur
Froid Seul / Module Pompe À Chaleur
Le tableau ci-dessous reprend en détail la visualisation par led, des conditions normales de fonctionnement, et conditions de défaut du climatiseur. Les voyants de signalisation de LED sont situés au milieu de l’unité de climatiseur. L’unité de pompe de chaleur est équipée d’un mode « auto »;l’unité fournira une température ambiante raisonnable enfaisant passer l’unité automatiquement au mode « refroidissement » ou au mode « chaleur », selon latempérature réglée par l’utilisateur.
Refroidissez/Chaleur Minuterie
Mise en sommeil
Interrupteur de SUR/ARRÊT
IR Récepteur
L’INDICATEUR S’ALLUME
SUR vers ARRÊT 1 bip long ARRÊT vers SUR
Pompe bas/Force de refroidissement activée
2 bips courts
Autres 1 bips courts
L’indicateur LED S’allume : Conditions De Fonctionnement Normales Et Par Défaut Pour L’Unité De Refroidissement/Module Pompe À Chaleur
CHARGE ADDITIONNELLE
Intérieure ATXB50CV1B ATXB60CV1B Extérieure ARXB50CV1B ARXB60CV1B Charge additionnelle [g/m] 20 20
Charge de réfrigérant supplémentaire [g] par longueur supplémentaire de 1m indiquée dans le tableau
Le réfrigérant est pré-chargé dans l’unité extérieure. Si la longueur des tuyaux est inférieure à 7,5m, alors la charge supplémentaire après un tirage n’est pas nécessaire. Si la longueur de la tuyauterie est supérieure à 7,5m, alors utiliser la valeur de charge supplémentaire comme indiqué dans le tableau.
Exemple :
ATXB50CV1B & ARXB50CV1B avec une longueur de tuyauterie de 12m la longueur de tuyauterie supplémentaire est de 4,5m. Ainsi, Charge additionnelle = 4,5[m] x 20[g/m] = 90,0[g]
2-12
Loading...
+ 106 hidden pages