Daikin 2AMXM40M4V1B9, 2AMXM50M4V1B9, 2AMXF40A2V1B, 2AMXF50A2V1B, 2MXF40A2V1B Installer reference guide [sl]

...
Vodnik za monterja
R32 serija split
2AMXM40M4V1B9 2AMXM50M4V1B9 2AMXF40A2V1B 2AMXF50A2V1B 2MXF40A2V1B 2MXF50A2V1B 2MXM40N2V1B9 2MXM50N2V1B9

Vsebina

Vsebina
1 O dokumentaciji 4
1.1 O tem dokumentu........................................................................................................................................................... 4
2 Splošni varnostni ukrepi 5
2.1 O dokumentaciji.............................................................................................................................................................. 5
2.1.1 Pomen opozoril in simbolov ........................................................................................................................... 5
2.2 Za monterja..................................................................................................................................................................... 6
2.2.1 Splošno ........................................................................................................................................................... 6
2.2.2 Mesto namestitve........................................................................................................................................... 7
2.2.3 Hladivo — v primeru R410A ali R32 ............................................................................................................... 10
2.2.4 Električna dela ................................................................................................................................................ 12
3 Specifična varnostna navodila za monterja 15
4 O škatli 20
4.1 Pregled: O škatli .............................................................................................................................................................. 20
4.2 Zunanja enota ................................................................................................................................................................. 20
4.2.1 Razpakiranje zunanje enote ........................................................................................................................... 20
4.2.2 Odstranjevanje opreme iz zunanje enote...................................................................................................... 21
5 O enoti 23
5.1 Pregled: O enoti .............................................................................................................................................................. 23
5.2 Oznaka............................................................................................................................................................................. 23
5.2.1 Nazivna ploščica: zunanja enota .................................................................................................................... 23
6 Montaža enote 24
6.1 Priprava mesta namestitve............................................................................................................................................. 24
6.1.1 Zahteve za namestitveno mesto za zunanjo enoto ....................................................................................... 25
6.1.2 Dodatne zahteve za namestitveno mesto za zunanjo enoto v hladnih predelih.......................................... 27
6.2 Odpiranje enote.............................................................................................................................................................. 28
6.2.1 O odpiranju enote .......................................................................................................................................... 28
6.2.2 Odpiranje zunanje enote................................................................................................................................ 28
6.3 Nameščanje zunanje enote ............................................................................................................................................ 29
6.3.1 O nameščanju zunanje enote......................................................................................................................... 29
6.3.2 Varnostni ukrepi pri nameščanju zunanje enote ........................................................................................... 29
6.3.3 Priprava montažne konstrukcije .................................................................................................................... 29
6.3.4 Montaža zunanje enote ................................................................................................................................. 30
6.3.5 Priprava drenaže............................................................................................................................................. 30
6.3.6 Preprečevanje prevračanja zunanje enote .................................................................................................... 31
7 Montaža cevi 32
7.1 Priprava cevi za hladivo................................................................................................................................................... 32
7.1.1 Zahteve za cevi za hladivo .............................................................................................................................. 32
7.1.2 Izolacija cevi za hladivo................................................................................................................................... 33
7.1.3 Dolžina cevi za hladivo in višinske razlike....................................................................................................... 33
7.2 Povezovanje cevi za hladivo............................................................................................................................................ 34
7.2.1 O priključevanju cevi za hladivo ..................................................................................................................... 34
7.2.2 Varnostni ukrepi pri priključevanju cevi za hladivo ....................................................................................... 34
7.2.3 Navodila pri priključevanju cevi za hladivo .................................................................................................... 35
7.2.4 Napotki za upogibanje cevi ............................................................................................................................ 36
7.2.5 Robljenje konca cevi ....................................................................................................................................... 36
7.2.6 Povezave med zunanjo in notranjo enoto z reducirnimi priključki ............................................................... 37
7.2.7 Uporaba zapornega ventila in servisnega priključka ..................................................................................... 38
7.2.8 Priključevanje cevi za hladivo na zunanjo enoto ........................................................................................... 40
7.3 Preverjanje cevi za hladivo ............................................................................................................................................. 40
7.3.1 O preverjanju cevi za hladivo ......................................................................................................................... 40
7.3.2 Napotki za varnost pri preverjanju cevi za hladivo ........................................................................................ 41
7.3.3 Preverjanje puščanja ...................................................................................................................................... 41
7.3.4 Vakuumsko praznjenje ................................................................................................................................... 42
Vodnik za monterja
8 Polnjenje s hladivom 44
8.1 O polnjenju s hladivom ................................................................................................................................................... 44
8.2 O hladivu ......................................................................................................................................................................... 45
8.3 Varnostni ukrepi pri polnjenju s hladivom ..................................................................................................................... 46
8.4 Določanje dodatne količine hladiva................................................................................................................................ 46
8.5 Določanje celotne količine ponovnega polnjenja .......................................................................................................... 46
8.6 Dolivanje dodatnega hladiva .......................................................................................................................................... 46
2(A)MXM40+50 + 2(A)MXF40+50
R32 serija split
4P600463-3D – 2021.03
Vsebina
8.7 Pritrjevanje nalepke o fluoriranih toplogrednih plinih................................................................................................... 47
9 Električna napeljava 48
9.1 O priključevanju električnega ožičenja........................................................................................................................... 48
9.1.1 Napotki za varnost pri priključevanju električnega ožičenja ......................................................................... 48
9.1.2 Napotki za priključevanje električnega ožičenja ............................................................................................ 50
9.1.3 Specifikacije standardnih komponent ožičenja ............................................................................................. 51
9.2 Da bi povezali električno ožičenje na zunanjo enoto..................................................................................................... 51
10 Zaključevanje montaže zunanje enote 54
10.1 Zaključevanje montaže zunanje enote........................................................................................................................... 54
10.2 Zapiranje zunanje enote................................................................................................................................................. 54
11 Konfiguracija 55
11.1 O nastavitvi načina z omejitvijo ECONO......................................................................................................................... 55
11.1.1 Da bi vključili nastavitev načina z omejitvijo ECONO..................................................................................... 55
11.2 O tihem nočnem načinu delovanja................................................................................................................................. 56
11.2.1 Da bi vključili tiho nočno delovanje................................................................................................................ 56
11.3 O načinu zaklepanja na ogrevanje.................................................................................................................................. 56
11.3.1 Da bi enoto zaklenili na ogrevanje ................................................................................................................. 56
11.4 O funkciji za varčevanje elektrike v stanju pripravljenosti............................................................................................. 57
11.4.1 Da bi izklopili varčevanje z električno energijo v pripravljenosti................................................................... 57
12 Zagon 58
12.1 Pregled: zagon................................................................................................................................................................. 58
12.2 Napotki za varnost pri zagonu........................................................................................................................................ 58
12.3 Seznam preverjanj pred zagonom.................................................................................................................................. 58
12.4 Seznam preverjanj med zagonom.................................................................................................................................. 59
12.5 Preizkus delovanja .......................................................................................................................................................... 59
12.5.1 Izvajanje testnega zagona .............................................................................................................................. 60
12.6 Zagon zunanje enote ...................................................................................................................................................... 60
13 Izročitev uporabniku 61
14 Vzdrževanje in servisiranje 62
14.1 Pregled: Vzdrževanje in servisiranje............................................................................................................................... 62
14.2 Varnostni ukrepi za vzdrževanje..................................................................................................................................... 62
14.3 Seznam preverjanj za letno vzdrževanje zunanje enote................................................................................................ 62
14.4 O kompresorju ................................................................................................................................................................ 63
15 Odpravljanje težav 64
15.1 Pregled: Odpravljanje težav............................................................................................................................................ 64
15.2 Varnostni ukrepi pri odpravljanju težav ......................................................................................................................... 64
15.3 Reševanje težav na podlagi simptomov ......................................................................................................................... 64
15.3.1 Simptom: Notranje enote padajo, vibrirajo ali oddajajo zvoke..................................................................... 64
15.3.2 Simptom: Enota NE ogreva oziroma ne hladi po pričakovanjih .................................................................... 64
15.3.3 Simptom: Iztekanje vode................................................................................................................................ 65
15.3.4 Simptom: Električno puščanje........................................................................................................................ 65
15.3.5 Simptom: Enota NE deluje ali ožganine ......................................................................................................... 65
15.4 Reševanje težav glede na to, kako svetijo svetleče diode ............................................................................................. 65
15.4.1 Diagnosticiranje napak s svetlečo diodo na tiskanem vezju zunanje enote ................................................. 65
16 Odstranjevanje 67
16.1 Pregled: odstranjevanje.................................................................................................................................................. 67
16.2 Izčrpavanje...................................................................................................................................................................... 67
16.3 Zagon in zaustavitev prisilnega hlajenja......................................................................................................................... 68
16.3.1 Da bi zagnali in zaustavili prisilno hlajenje s stikalom za vklop/izklop na notranji enoti .............................. 68
16.3.2 Da bi zagnali in zaustavili prisilno hlajenje z uporabniškim vmesnikom notranje enote.............................. 68
17 Tehnični podatki 69
17.1 Vezalna shema................................................................................................................................................................ 69
17.1.1 Poenotena legenda za vezalno shemo........................................................................................................... 69
17.2 Shema napeljave cevi: zunanja enota ............................................................................................................................ 71
2(A)MXM40+50 + 2(A)MXF40+50 R32 serija split 4P600463-3D – 2021.03
18 Slovar 73
Vodnik za monterja
1 | O dokumentaciji

1 O dokumentaciji

1.1 O tem dokumentu

Ciljni prejemniki
Pooblaščeni monterji
INFORMACIJA
Uporaba naprave je predvidena za strokovnjake oziroma usposobljene uporabnike v delavnicah, v manj zahtevnem industrijskem okolju ter na kmetijah oziroma za nestrokovnjake v poslovnem okolju in gospodinjstvih.
OPOZORILO
Prepričajte se, da so materiali za namestitev, servisiranje, vzdrževanje, popravila in sploh uporabljeni materiali v skladu z navodili iz Daikin ter da se skladajo z ustrezno zakonodajo in da so vsa našteta dejanja izvedle kvalificirane osebe. V Evropi in na območjih, kjer so v uporabi standardi IEC, je ustrezen standard EN/IEC 60335-2-40.
INFORMACIJA
V tem dokumentu so samo navodila za montažo, ki se nanašajo na zunanjo enoto. Za nameščanje notranje enote (nameščanje notranje enote, priključevanje cevi za hladivo na notranjo enoto, priključevanje električnega ožičenja na notranjo enoto …), glejte priročnik za montažo notranje enote.
Komplet dokumentacije
Ta dokument je del kompleta dokumentacije. Celotno dokumentacijo sestavljajo:
Splošni varnostni ukrepi:
- Varnostna navodila, ki jih morate prebrati pred montažo
- Format: Papirni izvod (v škatli zunanje enote)
Priročnik za montažo zunanje enote:
- Navodila za montažo
- Format: Papirni izvod (v škatli zunanje enote)
Vodnik za monterja:
- Priprava za namestitev, referenčni podatki …
- Format: Digitalne datoteke na naslovu http://www.daikineurope.com/support-
and-manuals/product-information/
V območnem spletnem mestu Daikin ali pri vašem prodajalcu so morda na voljo najnovejše posodobitve priložene dokumentacije.
Vodnik za monterja
Izvorna dokumentacija je pisana v angleščini. Dokumentacija v drugih jezikih je prevod.
Tehnično-inženirski podatki
Povzetek najnovejših tehničnih podatkov je na voljo na regionalni Daikin spletni
strani (javno dostopna).
Popolni tehnični podatki so na voljo na Daikin Business Portal (zahtevana
avtentikacija).
2(A)MXM40+50 + 2(A)MXF40+50
R32 serija split
4P600463-3D – 2021.03

2 Splošni varnostni ukrepi

2.1 O dokumentaciji

Izvorna dokumentacija je pisana v angleščini. Dokumentacija v drugih jezikih je
prevod.
Varnostni ukrepi, opisani v tem dokumentu, obravnavajo zelo pomembne teme;
skrbno se jih držite.
Namestitev sistema in vse dejavnosti, opisane v priročniku za montažo in v vodiču
za inštalaterja, MORA izvesti kvalificiran inštalater.

2.1.1 Pomen opozoril in simbolov

NEVARNOST
Označuje situacijo, ki vodi v smrt in hude telesne poškodbe.
2 | Splošni varnostni ukrepi
NEVARNOST: TVEGANJE SMRTI ZARADI ELEKTRIČNEGA UDARA
Označuje situacijo, ki lahko povzroči smrt zaradi električnega udara.
NEVARNOST: TVEGANJE ZA OŽGANINE/OPEKLINE
Prikazuje situacijo, ki bi lahko povzročila ožganine/opekline zaradi izjemno visokih ali nizkih temperatur.
NEVARNOST: NEVARNOST EKSPLOZIJE
Označuje situacijo, ki lahko povzroči eksplozijo.
OPOZORILO
Označuje situacijo, ki lahko povzroči smrt in hude telesne poškodbe.
OPOZORILO: VNETLJIV MATERIAL
OPOMIN
Označuje situacijo, ki lahko povzroči manjše ali srednje nevarne telesne poškodbe.
2(A)MXM40+50 + 2(A)MXF40+50 R32 serija split 4P600463-3D – 2021.03
OPOMBA
Označuje situacijo, ki lahko povzroči poškodbe opreme ali lastnine.
INFORMACIJA
Označuje uporabne nasvete ali dodatne informacije.
Simboli, uporabljeni na enoti:
Simbol Razlaga
Pred namestitvijo preberite navodila za montažo in uporabo ter shemo z navodili za ožičenje.
Vodnik za monterja
2 | Splošni varnostni ukrepi
Simboli, uporabljeni v dokumentaciji:
Simbol Razlaga
Preden začnete izvajati vzdrževalne in servisne postopke preberite priročnik za servisiranje.
Za več informacij glejte vodnik za monterja in uporabnika.
Enota vsebuje vrtljive dele. Pri servisiranju in pregledovanju bodite pazljivi.
Simbol Razlaga
Pomeni naslov slike ali sklic nanjo. Primer: " 1–3 naslov slike" pomeni "3. slika v 1. poglavju".
Pomeni naslov tabele ali sklic nanjo. Primer: " 1–3 naslov tabele" pomeni "3. tabela v 1.
poglavju".

2.2 Za monterja

2.2.1 Splošno

Če NISTE prepričani, kako montirati ali upravljati enoto, se obrnite na svojega prodajalca.
NEVARNOST: TVEGANJE ZA OŽGANINE/OPEKLINE
NE dotikajte se cevi za hladivo, cevi za vodo in notranjih delov med delovanjem ali
neposredno po delovanju. Lahko so prevroči ali premrzli. Počakajte, da se njihova temperatura normalizira. Če se jih morate dotikati, si nadenite zaščitne rokavice.
Z golo kožo se NE dotikajte ponesreči razlitega hladiva.
OPOZORILO
Nestrokovna montaža ali priklop naprave in opreme lahko povzroči električni udar, kratek stik, uhajanje tekočin ali požar ali drugače poškoduje napravo ali opremo. Uporabljajte samo dodatke, opcijsko opremo in nadomestne dele, ki jih izdela ali odobri Daikin.
OPOZORILO
Montaža, preizkus in uporabljeni materiali morajo biti (razen z navodili, opisanimi v dokumentaciji Daikin) skladni tudi z veljavno zakonodajo.
Vodnik za monterja
OPOMIN
Pri nameščanju, vzdrževanju ali servisiranju sistema uporabljajte ustrezno osebno zaščitno opremo (zaščitne rokavice, varnostna očala…).
OPOZORILO
Raztrgajte in odvrzite plastične vreče, da se z njimi nihče ne bi mogel igrati, zlasti ne otroci. Možna nevarnost: zadušitev.
2(A)MXM40+50 + 2(A)MXF40+50
R32 serija split
4P600463-3D – 2021.03
2 | Splošni varnostni ukrepi
OPOZORILO
Z zagotavljanjem primernih ukrepov preprečite, da bi enota postala zavetišče za majhne živali. Majhne živali, ki se dotaknejo električnih delov, lahko povzročijo okvare, dim ali požar.
OPOMIN
Ne dotikajte se odprtine za vstop zraka ali aluminijastih platic enote.
OPOMIN
Na vrh enote NE postavljajte predmetov ali opreme.NE sedite na napravi, ne plezajte nanjo in ne stojte na njej.
OPOMBA
Dela na zunanji enoti je najbolje opraviti v suhem vremenu, da bi se izognili vdoru vode.
V skladu z zadevno zakonodajo bo treba morda skupaj z izdelkom priskrbeti dnevnik, v katerem se beležijo najmanj: podatki o vzdrževanju, popravila, rezultati testov, obdobja pripravljenosti…
Najmanj naslednje informacije MORAJO biti zagotovljene na dostopnem mestu izdelka:
Navodila za izklop sistema v nujnem primeruNaziv in naslov gasilske službe, policije in bolnišniceIme, naslov ter dnevna in nočna telefonska številka za servis
Potrebne smernice za tak dnevnik za Evropo podaja standard EN378.

2.2.2 Mesto namestitve

Zagotovite dovolj prostora okoli enote za servisiranje in kroženje zraka.Prepričajte se, da mesto namestitve prenese težo in vibracije enote.Prepričajte se, da je območje dobro prezračeno. NE blokirajte prezračevalnih
Pazite, da bo enota izravnana.
Enote NE nameščajte na naslednja mesta:
V potencialno eksplozivnem okolju.Na mestih, kjer so stroji, ki oddajajo elektromagnetne valove. Elektromagnetni
Na mestih, kjer obstaja nevarnost požara zaradi uhajanja vnetljivih plinov
odprtin.
valovi lahko motijo krmilni sistem in lahko povzročijo okvare na opremi.
(primer: razredčilo ali bencin), ogljikovih vlaken ali vnetljivega prahu.
Navodila za opremo, ki uporablja hladivo R32
2(A)MXM40+50 + 2(A)MXF40+50 R32 serija split 4P600463-3D – 2021.03
Na mestih, kjer nastajajo korozivni plini (primer: kisli žvepleni plin). Zaradi
korozije bakrenih cevi ali zvarov bi lahko začelo puščati hladivo.
OPOZORILO: BLAGO VNETLJIV MATERIAL
Hladivo v enoti je blago vnetljivo.
Vodnik za monterja
2 | Splošni varnostni ukrepi
OPOZORILO
NE prebadajte in ne zažigajte.NE uporabite sredstev in načinov za pospeševanje odmrzovanja ali čiščenja
opreme, razen tistih, ki jih priporoča proizvajalec.
Bodite pozorni na to, da je R32 BREZ vonja.
OPOZORILO
Naprava mora biti skladiščena tako, da se prepreči mehanske poškodbe, in v dobro prezračenem prostoru, kjer ni neprestano prisotnih virov vžiga (na primer: odprtega plamena, delujoče naprave na plin ali delujočega električnega grelnika). Poleg tega mora biti prostor v izmeri, navedeni v nadaljevanju.
OPOZORILO
Prepričajte se, da so namestitev, servisiranje, vzdrževanje in popravila izvedeni v skladu z navodili Daikin in v skladu z veljavno zakonodajo (na primer predpisom o plinu) in da jih izvajajo pooblaščene osebe.
OPOZORILO
Če je na enoto prek sistema cevovodov povezana ena ali več sob, se prepričajte:
da ni delujočih virov vžiga (npr.: odprtega plamena, delujoče plinske naprave ali
delujočega električnega grelnika), če je površina tal manjša od minimalne kvadrature prostora A (m²);
da na cevovodu ni nameščenih pomožnih naprav, ki bi lahko bile morebitni vir
vžiga (npr.: vroče površine s temperaturo, višjo od 700°C, in električne stikalne naprave);
da so v cevovodu uporabljene le pomožne naprave, ki jih je odobril proizvajalec;da sta vstopna IN izstopna zračna odprtina neposredno povezani z istim
prostorom s cevmi. NE uporabljajte prostorov, kot so spuščeni strop, za dovodni ali odvodni vod za zrak.
OPOMBA
Uporabite varnostne ukrepe za izogibanje prevelikemu vibriranju ali utripanju cevi
za hladivo.
Zaščitne naprave, cevovodi in spoji morajo biti čim bolj zaščiteni pred neugodnimi
okoljskimi vplivi.
Poskrbite za prostor za raztezanje in krčenje dolgih cevi.Cevovodi in sistemi za hladivo morajo biti načrtovani in nameščeni tako, da je
verjetnost hidravličnega šoka, ki bi poškodoval sistem, kar se da majhna.
Notranja oprema in cevi morajo biti varno nameščeni in zavarovani tako, da ne
more priti do pokov na opremi ali ceveh zaradi premikanja pohištva ali obnavljanja prostorov.
OPOMIN
NE uporabite morebitnih virov vžiga pri iskanju ali beleženju puščanja hladiva.
OPOMBA
Spojev in bakrenih tesnil, ki so že bili uporabljeni, NE uporabljajte znova.Spoji, ki so bili narejeni na inštalaciji med deli hladilnega sistema, morajo biti
dostopni za vzdrževanje.
Vodnik za monterja
2(A)MXM40+50 + 2(A)MXF40+50
R32 serija split
4P600463-3D – 2021.03
Zahteve namestitve po prostoru
Contains fluorinated greenhouse gases
2
1
1
1
2
2
kg
tCO2eq
1000
GWP × kg
=
=
+
kg
=
kg
=
GWP: xxx
R32
OPOZORILO
Če je v napravah hladivo R32, MORA biti kvadratura prostora, v katerega se namešča, v katerem deluje ali je skladiščena naprava, večja od najmanjše kvadrature prostora, določene v spodnji tabeli A (m2). To velja za:
Notranje enote brez tipala za puščanje hladiva; v primeru notranjih enot s tipalom
za puščanje hladiva glejte priročnik za montažo
Zunanje enote, nameščene ali skladiščene v notranjih prostorih (npr. zimski vrt,
garaža, strojnica)
OPOMBA
Cevovod mora biti zaščiten pred fizičnimi poškodbami.Cevi mora biti najmanj, kar je mogoče.
Da bi določili najmanjšo potrebno kvadraturo prostora
1 Izračunajte skupno količino hladiva v sistemu (=tovarniška polnitev hladiva +
dolito hladivo).
2 | Splošni varnostni ukrepi
2 Določite, kateri grafikon ali tabelo uporabiti.
Za notranje enote: Je enota nameščena na strop, na steno ali stoji na tleh?Za zunanje enote, nameščene ali shranjene notri, je to odvisno od višine
namestitve:
Če je višina namestitve … Uporabite grafikon ali tabelo za …
<1,8m Stoječe enote
1,8≤x<2,2m Enote, nameščene na steno
≥2,2m Enote, nameščene na strop
3 Uporabite grafikon ali tabelo za določanje minimalne kvadrature prostora.
2(A)MXM40+50 + 2(A)MXF40+50 R32 serija split 4P600463-3D – 2021.03
Vodnik za monterja
2 | Splošni varnostni ukrepi
0
10
20
30
40
50
60
70
80
90
100
110
120
130
140
150
160
170
180
190
200
210
220
230
240
250
260
270
280
290
300
310
320
330
340
350
360
370
380
390
400
410
420
430
440
450
460
470
480
490
500
510
520
530
540
550
560
570
580
590
600
610
620
630
640
650
660
670
680
690
700
710
720
730
740
750
760
770
1.843
9.55
2.21.8
2.4 2.8 3.2 3.6 4 4.4 4.8 5.2 5.6 6 6.4 6.8 7.2 7.6 8 8.4 8.8 9.22
2.6 3 3.4 3.8 4.2
4.6
5 5.4 5.8 6.2 6.6 7 7.4 7.8 8.2 8.6 9 9.4
Floor-standing unit
(c)
Wall-mounted unit
(b)
Ceiling-mounted unit
(a)
m [kg]
A
min
[m
2
]
Ceiling-mounted
unit
(a)
4.6 13.4
4.6 180
4.8 14.6
4.8 196
5.0 15.8
5.0 213
≤1.842
5.2 17.1
≤1.842
5.2 230
1.843 3.64
5.4 18.5
1.843 28.9
5.4 248
2.0 3.95
5.6 19.9
2.0 34.0
5.6 267
2.2 4.34
5.8 21.3
2.2 41.2
5.8 286
2.4 4.74
6.0 22.8
2.4 49.0
6.0 306
2.6 5.13
6.2 24.3
2.6 57.5
6.2 327
2.8 5.53
6.4 25.9
2.8 66.7
6.4 349
3.0 5.92
6.6 27.6
3.0 76.6
6.6 371
3.2 6.48
6.8 29.3
3.2 87.2
6.8 394
3.4 7.32
7.0 31.0
3.4 98.4
7.0 417
3.6 8.20
7.2 32.8
3.6 110
7.2 441
3.8 9.14
7.4 34.7
3.8 123
7.4 466
4.0 10.1
7.6 36.6
4.0 136
7.6 492
4.2 11.2
7.8 38.5
4.2 150
7.8 518
4.4 12.3
4.4 165
m (kg)
A
min
(m2)
4.6 20.0
4.8 21.8
5.0 23.6
≤1.842
5.2 25.6
1.843 4.45
5.4 27.6
2.0 4.83
5.6 29.7
2.2 5.31
5.8 31.8
2.4 5.79
6.0 34.0
2.6 6.39
6.2 36.4
2.8 7.41
6.4 38.7
3.0 8.51
6.6 41.2
3.2 9.68
6.8 43.7
3.4 10.9
7.0 46.3
3.6 12.3
7.2 49.0
3.8 13.7
7.4 51.8
4.0 15.1
7.6 54.6
4.2 16.7
7.8 57.5
4.4 18.3
8 40.5
8.2 42.6
8.4 44.7
8.6 46.8
8.8 49.0 9 51.3
9.2 53.6
9.4 55.9
9.55 57.7
8 60.5
8.2 63.6
8.4 66.7
8.6 69.9
8.8 73.2 9 76.6
9.2 80.0
9.4 83.6
9.55 86.2
8 545
8.2 572
8.4 601
8.6 629
8.8 659 9 689
9.2 720
9.4 752
9.55 776
Wall-mounted
unit
(b)
m (kg)
A
min
(m2)
Floor-standing
unit
(c)
m (kg)
A
min
(m2)
Vodnik za monterja
10
m Skupna polnitev hladiva v sistemu
A
min
(a) Ceiling-mounted unit (= Enota, nameščena na stropu) (b) Wall-mounted unit (= Enota, nameščena na steni)
Najmanjša kvadratura prostora
(c) Floor-standing unit (= Stoječi tip enote)

2.2.3 Hladivo — v primeru R410A ali R32

Če se uporablja. Za več informacij glejte priročnik za montažo ali referenčni vodnik za monterja za vašo uporabo.
OPOMBA
Napeljava cevi mora biti skladna z veljavno zakonodajo. Zadevni standard za Evropo je EN378.
OPOMBA
Poskrbite, da zunanje cevi in priključki NE bodo obremenjeni.
OPOZORILO
Med testiranjem v izdelku NIKOLI ne smete vzpostaviti tlaka, višjega od maksimalnega dovoljenega tlaka (ki je naveden na nazivni ploščici enote).
2(A)MXM40+50 + 2(A)MXF40+50
R32 serija split
4P600463-3D – 2021.03
2 | Splošni varnostni ukrepi
OPOZORILO
Poskrbite za ustrezne varnostne ukrepe za primer puščanja hladiva. Če med nameščanjem izteče hladilno sredstvo v plinastem stanju, takoj prezračite prostor. Možna tveganja:
Prevelika koncentracija hladiva v zaprtem prostoru lahko privede do pomanjkanja
kisika.
Če pride plinasto hladivo v stik z ognjem, lahko nastanejo strupeni plini.
NEVARNOST: NEVARNOST EKSPLOZIJE
Izčrpavanje – Puščanje hladiva. Če želite sistem izčrpati in nekje na tokokrogu
hladilnega sredstva pušča:
NE uporabljajte funkcije za samodejno izčrpavanje na enoti, s katero lahko
zberete vse hladivo iz sistema v zunanji enoti. Možna posledica: Samoizgorevanje in eksplozija kompresorja zaradi zraka, ki pride v delujoč kompresor.
Uporabite ločen sistem za izčrpavanje, tako da kompresorju enote NI treba
delovati.
OPOZORILO
Hladivo VEDNO zberite. NE izpuščajte jih neposredno v okolje. Uporabite vakuumsko črpalko, da boste izpraznili napeljavo.
OPOMBA
Ko so vse cevi priključene, se prepričajte, da plin ne uhaja. S pomočjo dušika preverite, ali plin uhaja.
OPOMBA
Preprečevanje okvare kompresorja, NE dolijte več hladiva, kot je navedeno v
specifikaciji.
Kadar je treba sistem hladiva odpreti, morate s hladivom ravnati v skladu z
zadevno zakonodajo.
OPOZORILO
Pazite, da v sistemu ni kisika. Hladivo lahko natočite šele, ko opravite preizkus tesnjenja in vakuumsko praznjenje.
Možna posledica: Samovžig in eksplozija kompresorja zaradi vstopa kisika v delujoči kompresor.
Če je to potrebno, preverite napisno ploščico na enoti. Na njej sta navedena tip
hladiva in potrebna količina.
Enota je tovarniško napolnjena s hladivom. Odvisno od velikosti in dolžine cevi je
treba v nekaterih sistemih dotočiti hladivo.
Da bi zagotovili upornost tlaka in preprečili vdor drugih snovi v sistem,
uporabljajte samo orodje, zasnovano posebej za vrsto hladiva, uporabljeno v sistemu.
2(A)MXM40+50 + 2(A)MXF40+50 R32 serija split 4P600463-3D – 2021.03
Hladivo točite upoštevaje naslednje:
Vodnik za monterja
11
2 | Splošni varnostni ukrepi
Če Potem
Je prisotna sifonska cev (tj., na jeklenki je oznaka “Liquid filling
Pri polnjenju mora biti jeklenka postavljena pokonci.
siphon attached” (pritrjena sifonska cev za tekoče hladivo))
Sifonska cev NI prisotna Pri polnjenju mora biti jeklenka
obrnjena na glavo.
Počasi odprite vsebnike hladiva.Hladivo točite v tekočem stanju. Dodajanje hladiva v plinskem stanju lahko
onemogoči normalno delovanje.
OPOMIN
Ko je postopek dolivanja hladiva dokončan ali ga prekinete, takoj zaprite ventil rezervoarja za hladivo. Če se ventil NE zapre takoj, lahko preostanek tlaka napolni dodatno hladivo. Možna posledica: Nepravilna količina hladiva.

2.2.4 Električna dela

NEVARNOST: TVEGANJE SMRTI ZARADI ELEKTRIČNEGA UDARA
Izključite vse napajanje, preden snamete pokrov stikalne omarice, priključujete
električno napeljavo ali se dotikate električnih delov.
Odklopite napajanje za več kot 10 minut ter izmerite napetost na priključnih
sponkah kondenzatorjev glavnega tokokroga ali električnih sestavnih delih, preden začnete servisiranje. Napetost mora biti nižja od 50VDC, preden se lahko dotaknete električnih sestavnih delov. Za mesto priključnih sponk glejte vezalno shemo.
Električnih sestavnih delov se NE dotikajte z mokrimi rokami.Enote NE puščajte brez nadzora, če ste z nje odstranili servisni pokrov.
OPOZORILO
Če NI nameščeno, JE NUJNO v fiksno ožičenje namestiti glavno stikalo ali druge možnosti odklopa, ki imajo ločen stik na vseh polih in omogočajo popolni odklop v pogojih previsoke napetosti kategorijeIII.
Vodnik za monterja
12
2(A)MXM40+50 + 2(A)MXF40+50
R32 serija split
4P600463-3D – 2021.03
2 | Splošni varnostni ukrepi
OPOZORILO
Uporabljajte LE bakrene vodnike.Pazite, da bodo električne napeljave ustrezale veljavni zakonodaji.Vse lokalno ožičenje mora biti izvedeno skladno z vezalno shemo, priloženo
izdelku.
NIKOLI ne stiskajte šopov kablov in pazite, da NE pridejo v stik s cevmi ali z ostrimi
robovi. Prepričajte se, da na priključne sponke ne pritiska nič z zunanje strani.
Pazite, da boste zagotovo namestili ozemljitveni vodnik. Ne ozemljujte naprave s
pomočjo komunalne cevi, prenapetostnega odvodnika ali ozemljitve telefona. Nepopolna ozemljitev lahko povzroči električni šok.
Zagotovo uporabite ločeno električno vezje. NIKOLI ne delite vira napajanja z
drugo napravo.
Pazite, da boste zagotovo namestili zahtevane varovalke ali prekinjala vezij.Zagotovo namestite odklopnik z uhajanjem toka. Če tega ne storite, lahko pride
do električnega udara ali požara.
Ko nameščate zemljostično zaščito, pazite, da je združljiva z inverterjem (odporna
na visokofrekvenčne električne šume), da bi se izognili nepotrebnemu odpiranju zaščite.
OPOMIN
Ko priključujete napajanje: najprej povežite ozemljitev, nato pa izvedite povezave
za prenos električnega toka.
Ko izključujete napajanje: najprej odklopite povezave za prenos električnega toka,
nato pa še ozemljitev.
Dolžina vodnikov med oporo napajalnega kabla in samim prikjučnim blokom mora
biti taka, da so napajalni vodniki napeti pred ozemljitvenim vodnikom, za primer, da bi se napajalni kabel snel z opore kabla.
OPOMBA
Varnostni ukrepi pri napeljavi napajalnih vodnikov:
NE priključujte vodnikov različnih debelin na priključne sponke napajanja
(ohlapnost napajalnih vodnikov lahko povzroči neobičajno segrevanje).
Pri priključevanju vodnikov enake debeline naredite tako, kot je prikazano na sliki
zgoraj.
Za ožičenje uporabite predvideni napajalni vodnik in ga trdno priključite, nato pa
zavarujte, da bi preprečili, da se zunanja sila prenese na priključno ploščo.
Uporabite ustrezen izvijač za privijanje vijakov na priključku. Izvijač z malim
nastavkom lahko poškoduje glavo vijaka in onemogoči ustrezno zategovanje.
S premočnim zategovanjem lahko vijake na priključkih polomite.
2(A)MXM40+50 + 2(A)MXF40+50 R32 serija split 4P600463-3D – 2021.03
Električne kable napeljite najmanj 1 m stran od televizije in radia, da bi preprečili motnje. Odvisno od radijskih valov, tudi 1m morda ne bo dovolj.
OPOZORILO
Ko zaključite napeljavo električnih kablov, se prepričajte, da so vsi električni
sestavni deli in vse priključne sponke v omarici z električnimi sestavnimi deli varno pritrjeni.
Obvezno zaprite vse pokrove, preden zaženete enoto.
Vodnik za monterja
13
2 | Splošni varnostni ukrepi
OPOMBA
Velja samo, če je napajanje trifazno in je način zagona kompresorja VKLOP/IZKLOP.
Če obstaja možnost, da bi do obrnjene faze prišlo po trenutnem izpadu in se napajanje vklaplja in izklaplja med delovanjem izdelka, priključite vezje za zaščito pred obrnjeno fazo lokalno. Delovanje izdelka z obrnjeno fazo lahko povzroči okvaro kompresorja in drugih delov.
Vodnik za monterja
14
2(A)MXM40+50 + 2(A)MXF40+50
R32 serija split
4P600463-3D – 2021.03
3 | Specifična varnostna navodila za monterja

3 Specifična varnostna navodila za monterja

Vedno upoštevajte naslednje varnostne ukrepe in predpise.
Nameščanje enote (glejte
OPOZORILO
Montažo mora izvesti monter, izbira materialov in montaža pa morata ustrezati veljavni zakonodaji. Zadevni standard za Evropo je EN378.
Mesto nameščanja (glejte
OPOMIN
Preverite, ali lahko mesto namestitve prenese težo enote. Neprimerna montaža
je nevarna. Lahko povzroči tudi vibracije in nenavadne zvoke med delovanjem.
Poskrbite, da bo dovolj prostora za vzdrževanje.Enote NE nameščajte tako, da bo v stiku s stropom ali steno, saj to lahko povzroči
vibracije.
OPOZORILO
Napravo je treba hraniti v prostoru, v katerem ni neprekinjeno delujočih virov vžiga (kot so odprti plameni, delujoča plinska naprava ali delujoči električni grelnik).
Odpiranje enote (glejte
"6.2Odpiranje enote"[428]
"6Montaža enote"[424]
)
"6.1Priprava mesta namestitve"[424]
)
)
NEVARNOST: TVEGANJE SMRTI ZARADI ELEKTRIČNEGA UDARA
Enote NE puščajte brez nadzora, če ste z nje odstranili servisni pokrov.
NEVARNOST: TVEGANJE ZA OŽGANINE/OPEKLINE
NEVARNOST: TVEGANJE SMRTI ZARADI ELEKTRIČNEGA UDARA
Povezovanje cevi za hladivo (glejte
OPOMIN
Enot, ki so pri pošiljanju že napolnjene s hladivom R32, ne smete spajkati ali variti
na mestu namestitve.
Med nameščanjem hladilnega sistema morate pri spajanju delov, pri katerem je
vsaj v enem delu že hladivo, upoštevati naslednje zahteve: v obljudenih prostorih niso dovoljeni nepermanentni spoji za hladivo R32, razen za spoje, ki jih na mestu namestitve neposredno na notranjo enoto za priključevanje cevi. Spoji, narejeni na mestu namestitve za neposredno povezovanje cevi na notranje enote, morajo biti nepermanentnega tipa.
"7.2Povezovanje cevi za hladivo"[434]
)
2(A)MXM40+50 + 2(A)MXF40+50 R32 serija split 4P600463-3D – 2021.03
OPOMIN
NE priključite vložene odcepne cevi in zunanje enote, ko izvajate dela na ceveh brez priključene notranje enote, tako da lahko dodate notranjo enoto kasneje.
Vodnik za monterja
15
3 | Specifična varnostna navodila za monterja
OPOMIN
V delu z razširitvijo NE uporabljajte mineralnih olj.NE smete uporabiti cevi iz prejšnjih namestitev.Da bi zagotovili dobo uporabnosti te enote R32, vanjo NIKOLI ne vstavljajte sušila.
Sušilni material se lahko raztopi in poškoduje sistem.
OPOMIN
Uporabite holandsko matico, pritrjeno na enoto.Da bi preprečili uhajanje plina, hladilno olje nanesite samo na notranjo površino
razširitve. Uporabite hladilno olje za R32.
Spojev NE uporabljajte znova.
OPOZORILO
Varno povežite cevi za hladivo, preden zaženete kompresor. Če cevi za hladivo niso priključene in je zaustavitveni ventil ob zagonu kompresorja odprt, se bo vanj vsesal zrak, kar bo povzročilo previsok pritisk v zanki hladilnega sredstva, kar lahko povzroči škodo na opremi ali poškodbe oseb.
OPOMIN
Nepopolna razširitev lahko povzroči iztekanje hladiva.Priviha NE smete ponovno uporabiti. Uporabite nove razširitve, da preprečite
uhajanje plinastega hladiva.
Uporabite holandske matice, ki so priložene enoti. Uporaba drugačnih holandskih
matic lahko povzroči puščanje plinastega hladiva.
Preverjanje cevi za hladivo (
NEVARNOST: NEVARNOST EKSPLOZIJE
Enote NE zaženite, dokler ni ustvarjen vakuum.
Dolivanje hladiva (glejte
"8Polnjenje s hladivom"[444]
OPOZORILO: BLAGO VNETLJIV MATERIAL
Hladivo v enoti je blago vnetljivo.
OPOZORILO
Hladivo v enoti je blago vnetljivo, vendar navadno NE pušča. Če hladivo uhaja v prostor in pride v stik z ognjem z gorilnika, grelca ali štedilnika, lahko pride do požara ali do nastajanja škodljivega plina.
Izključite vse vnetljive grelne naprave, prostor prezračite in stopite v stik s prodajalcem, pri katerem ste kupili enoto.
Enote ne uporabljajte, dokler serviser ne potrdi, da je bil del, iz katerega je puščalo hladivo, popravljen.
"7.3Preverjanje cevi za hladivo"[440]
)
)
Vodnik za monterja
16
OPOZORILO
Nikoli se z golo kožo ne dotaknite ponesreči razlitega hladiva. To bi lahko povzročilo rane zaradi ozeblin.
2(A)MXM40+50 + 2(A)MXF40+50
R32 serija split
4P600463-3D – 2021.03
3 | Specifična varnostna navodila za monterja
OPOZORILO
Za hladivo uporabljajte samo R32. Druge snovi lahko povzročijo eksplozije in
nesreče.
R32 vsebuje fluorirane toplogredne pline. Njegova vrednost potenciala
globalnega segrevanja (GWP) je 675. Teh plinov NE izpuščajte v ozračje.
Pri točenju hladiva vedno uporabljajte zaščitne rokavice in zaščitna očala.
OPOMIN
Da preprečite okvaro kompresorja, NE točite večje količine hladiva od predpisane.
Nameščanje električnih sestavnih delov (glejte
OPOZORILO
Ožičenje MORA v celoti opraviti pooblaščen električar, izvedba pa MORA ustrezati
veljavni zakonodaji.
Izdelajte električne priključke na fiksno ožičenje.Vse komponente, ki se priskrbijo na mestu vgradnje, in vse električne napeljave
MORAJO biti skladne z veljavno zakonodajo.
OPOZORILO
Če N-faza ni priključena ali pa je napačno priključena, lahko to povzroči okvaro
opreme.
Vzpostavite primerno ozemljitev. Enote NE ozemljujte s pomočjo komunalne cevi,
prenapetostnega odvodnika ali telefonskega ozemljitvenega kabla. Nepopolna ozemljitev lahko povzroči električni udar.
Vgradite zahtevane varovalke ali odklopnike.Pritrdite električno ožičenje z vezicami za kable, tako da se kabli NE dotikajo ostrih
robov ali cevi, zlasti na strani visokega tlaka.
NE uporabljajte sestavljenih vodnikov, pletenih žičnih vodnikov, podaljševalnih
kablov ali povezav iz zvezdišča. To lahko povzroči pregrevanje, električni udar ali požar.
NE nameščajte kondenzatorja za fazni premik, saj je ta enota opremljena z
inverterjem. Kondenzator za fazni premik bo zmanjšal zmogljivost in lahko povzroči nesreče.
"9Električna napeljava"[448]
)
2(A)MXM40+50 + 2(A)MXF40+50 R32 serija split 4P600463-3D – 2021.03
OPOZORILO
Za napajalne kable VEDNO uporabite večžilni kabel.
OPOZORILO
Uporabite prekinjalo za odklop vseh polov z vsaj 3mm med kontaktnimi točkovnimi režami, ki omogočajo popolni odklop v III. kategoriji previsoke napetosti.
OPOZORILO
Če je napajalni kabel poškodovan, ga MORAJO proizvajalec, serviser ali podobno usposobljena oseba zamenjati, da ne bi prišlo do nevarne situacije.
OPOZORILO
NE povezujte napajalnega kabla na notranjo enoto. To lahko povzroči električni udar ali požar.
Vodnik za monterja
17
3 | Specifična varnostna navodila za monterja
OPOZORILO
V enoto ne nameščajte električnih delov, kupljenih v lokalni trgovini.NE razpeljujte napajanja za odvodno črpalko itd. s priključnega bloka. To lahko
povzroči električni udar ali požar.
OPOZORILO
Pazite, da bodo kabli za medsebojne povezave stran od bakrenih cevi brez termoizolacije, saj se te cevi zelo segrejejo.
NEVARNOST: TVEGANJE SMRTI ZARADI ELEKTRIČNEGA UDARA
Vsi električni deli (vključno s termistorji) se napajajo iz napajalnega omrežja. Ne dotikajte s jih z golimi rokami.
NEVARNOST: TVEGANJE SMRTI ZARADI ELEKTRIČNEGA UDARA
Odklopite napajanje za več kot 10minut ter izmerite napetost na priključnih sponkah kondenzatorjev glavnega tokokroga ali električnih sestavnih delih, preden začnete servisiranje. Napetost mora biti nižja od 50 V DC, preden se lahko dotaknete električnih sestavnih delov. Za mesto priključnih sponk glejte vezalno shemo.
Zaključevanje montaže zunanje enote (glejte
enote"[454]
)
NEVARNOST: TVEGANJE SMRTI ZARADI ELEKTRIČNEGA UDARA
Prepričajte se, da je sistem ustrezno ozemljen.Pred servisiranjem izklopite napajanje.Namestite pokrov stikalne omarice, preden vključite napajanje.
Konfiguracija (glejte
"11Konfiguracija"[455]
OPOMIN
Ko vračate na njegovo mesto pokrov električne omarice, pazite, da ne boste stisnili glavnega vodnika ventilatorja za motor.
Vzdrževanje in servisiranje (glejte
"14Vzdrževanje in servisiranje"[462]
NEVARNOST: TVEGANJE SMRTI ZARADI ELEKTRIČNEGA UDARA
NEVARNOST: TVEGANJE ZA OŽGANINE/OPEKLINE
"10Zaključevanje montaže zunanje
)
)
Vodnik za monterja
18
OPOZORILO
Preden pričnete z izvajanjem vzdrževanja ali popravila, vedno izklopite odklopnik
na napajalni plošči, odstranite varovalke oz. odprite zaščitne naprave enote.
Ne dotikajte se delujočih delov 10 min po izključitvi napajanja, saj obstaja
možnost visoke napetosti.
Pazite, ker je nekaj delov električne omarice izjemno vročih.Pazite, da se ne boste dotaknili prevodnega dela.NE izpirajte enote. To bi lahko povzročilo električni udar ali požar.
2(A)MXM40+50 + 2(A)MXF40+50
R32 serija split
4P600463-3D – 2021.03
3 | Specifična varnostna navodila za monterja
NEVARNOST: TVEGANJE SMRTI ZARADI ELEKTRIČNEGA UDARA
Kompresor uporabljajte le v ozemljenem sistemu.Izključite napajanje pred servisiranjem.Spet pritrdite pokrov stikalne omarice in servisni pokrov po servisiranju.
OPOMIN
vedno uporabljajte zaščitna očala in rokavice.
NEVARNOST: NEVARNOST EKSPLOZIJE
Uporabite cevni rezalnik, da bi odstranili kompresor.NE uporabljajte plamenskega spajkalnika.Uporabite le odobrena hladiva in maziva.
NEVARNOST: TVEGANJE ZA OŽGANINE/OPEKLINE
Kompresorja se Ne dotikajte z golimi rokami.
Odpravljanje težav (glejte
NEVARNOST: TVEGANJE SMRTI ZARADI ELEKTRIČNEGA UDARA
NEVARNOST: TVEGANJE ZA OŽGANINE/OPEKLINE
OPOZORILO
Ko pregledujete stikalno omarico enote, VEDNO preverite, ali je enota
odklopljena iz omrežnega napajanja. Izklopite ustrezen odklopnik.
Če se je aktivirala varnostna naprava, zaustavite enoto in ugotovite vzrok za njeno
aktiviranje, preden jo ponastavite. NIKOLI ne zaobidite varnostnih naprav in ne spreminjajte njihovih vrednosti na vrednost, ki se razlikuje od tovarniške nastavitve. Če ne morete ugotoviti vzroka težave, pokličite svojega prodajalca.
OPOZORILO
Preprečite nevarnosti zaradi nehotene ponastavitve termičnega odklopa: napajanje te naprave NE SME biti izvedeno preko zunanjega preklopnika, denimo časovnika, in naprava ne sme biti priključena na tokokrog, ki ga vzdrževanje redno vklaplja in izklaplja.
"15Odpravljanje težav"[464]
)
2(A)MXM40+50 + 2(A)MXF40+50 R32 serija split 4P600463-3D – 2021.03
NEVARNOST: TVEGANJE SMRTI ZARADI ELEKTRIČNEGA UDARA
Ko enota ne deluje, so svetleče diode na tiskanem vezju izključene zaradi
varčevanja z energijo.
Tudi ko so svetleče diode izključene, sta priključna sponka in tiskano vezje lahko
pod napetostjo.
Vodnik za monterja
19
4 | O škatli

4 O škatli

4.1 Pregled: O škatli

4.2 Zunanja enota

To poglavje opisuje, kaj morate storiti ob dobavi paketov z zunanjo in notranjo enoto na mesto montaže.
Vedno imejte v mislih naslednje:
Ob dobavi je treba enoto NUJNO pregledati glede poškodb. Vsako poškodbo
MORATE takoj sporočiti prevoznikovemu agentu.
Enoto postavite še zapakirano čim bližje mestu montaže, da bi preprečili
morebitne poškodbe med premikanjem.
Vnaprej pripravite pot, po kateri nameravate vnesti enoto v prostor.

4.2.1 Razpakiranje zunanje enote

Vodnik za monterja
20
2(A)MXM40+50 + 2(A)MXF40+50
R32 serija split
4P600463-3D – 2021.03
4 | O škatli
1
2
c d e f g
h
a b

4.2.2 Odstranjevanje opreme iz zunanje enote

1 Dvignite zunanjo enoto.
OPOMIN
Z zunanjo enoto ravnajte samo v skladu z naslednjim:
2 Odstranite opremo iz spodnjega dela embalaže.
2(A)MXM40+50 + 2(A)MXF40+50 R32 serija split 4P600463-3D – 2021.03
a Priročnik za montažo zunanje enote
b Splošni varnostni ukrepi
c Nalepka z informacijo o toplogrednih fluoriranih plinih d Večjezična nalepka z informacijo o toplogrednih fluoriranih plinih e Odvodna pipa
f Vrečka z vijaki (za pritrditev zadrževalnika žice)
Vodnik za monterja
21
4 | O škatli
g Sestav reduktorja
h Nalepka z informacijami o energiji
Vodnik za monterja
22
2(A)MXM40+50 + 2(A)MXF40+50
R32 serija split
4P600463-3D – 2021.03

5 O enoti

5 | O enoti
INFORMACIJA
Notranje enote NI mogoče priključiti samo za 1 prostor. Obvezno priključite notranjo
enoto najmanj 2 prostorov.
INFORMACIJA
Odvisno od enot in/ali od pogojev nameščanja bo morda treba povezati električno
ožičenje, preden lahko napolnite hladivo.
OPOZORILO: BLAGO VNETLJIV MATERIAL
Hladivo v enoti je blago vnetljivo.
INFORMACIJA
Za omejitve pri delovanju glejte najnovejše tehnične podatke za zunanjo enoto na
regionalni spletni strani Daikin (javno dostopno).

5.1 Pregled: O enoti

V tem poglavju so informacije:
Prepoznavanje zunanje enote

5.2 Oznaka

OPOMBA
Če sočasno nameščate ali servisirate več enot, NE smete zamenjati servisnih plošč
med različnimi modeli.

5.2.1 Nazivna ploščica: zunanja enota

Mesto
2(A)MXM40+50 + 2(A)MXF40+50 R32 serija split 4P600463-3D – 2021.03
Vodnik za monterja
23
6 | Montaža enote

6 Montaža enote

V tem poglavju

OPOZORILO
Montažo mora izvesti monter, izbira materialov in montaža pa morata ustrezati veljavni zakonodaji. Zadevni standard za Evropo je EN378.
6.1 Priprava mesta namestitve..................................................................................................................................................... 24
6.1.1 Zahteve za namestitveno mesto za zunanjo enoto............................................................................................... 25
6.1.2 Dodatne zahteve za namestitveno mesto za zunanjo enoto v hladnih predelih.................................................. 27
6.2 Odpiranje enote...................................................................................................................................................................... 28
6.2.1 O odpiranju enote .................................................................................................................................................. 28
6.2.2 Odpiranje zunanje enote ....................................................................................................................................... 28
6.3 Nameščanje zunanje enote .................................................................................................................................................... 29
6.3.1 O nameščanju zunanje enote ................................................................................................................................ 29
6.3.2 Varnostni ukrepi pri nameščanju zunanje enote................................................................................................... 29
6.3.3 Priprava montažne konstrukcije ............................................................................................................................ 29
6.3.4 Montaža zunanje enote ......................................................................................................................................... 30
6.3.5 Priprava drenaže .................................................................................................................................................... 30
6.3.6 Preprečevanje prevračanja zunanje enote ............................................................................................................ 31

6.1 Priprava mesta namestitve

Enote NE nameščajte na mesta, ki so pogosto v uporabi kot delovna mesta. Če morate izvajati tudi gradbene posege (npr. brušenje, razbijanje zidov itd.), pri katerih nastaja veliko prahu, MORATE enoto pokriti.
Izberite namestitveno mesto, ki omogoča dovolj prostora za prenos enote na mesto namestitve in z njega.
OPOMIN
Preverite, ali lahko mesto namestitve prenese težo enote. Neprimerna montaža
je nevarna. Lahko povzroči tudi vibracije in nenavadne zvoke med delovanjem.
Poskrbite, da bo dovolj prostora za vzdrževanje.Enote NE nameščajte tako, da bo v stiku s stropom ali steno, saj to lahko povzroči
vibracije.
Izberite mesto, kjer hrup zaradi delovanja ali izpust vročega/mrzlega zraka iz
enote ne bo nikogar motil.
Zagotovite dovolj prostora okoli enote za servisiranje in kroženje zraka.Izogibajte se območjem, v katerih lahko uhaja plin ali izdelek.Namestite enote, napajalne kable in ožičenje za prenos vsaj 3 m stran od
televizijskih ali radijskih sprejemnikov, da bi se izognili motnjam. Odvisno od radijskih valov tudi 3m lahko niso dovolj, da bi se preprečil šum.
Vodnik za monterja
24
OPOMBA
Predmetov, ki se ne smejo zmočiti, NE postavljajte pod notranjo in/ali zunanjo enoto. Sicer lahko kondenziranje na enoti ali na ceveh za hladivo, umazanija v zračnem filtru ali zamašitev odvodnih cevi povzročijo kapljanje in se lahko predmeti pod enoto zamažejo ali poškodujejo.
2(A)MXM40+50 + 2(A)MXF40+50
R32 serija split
4P600463-3D – 2021.03
OPOZORILO
(mm)
>50
a
b
>100
<1200
a
b
(mm)
>100
>50
b
a
>150
>50
b
a
(mm)
>150
>50
>300
b
a
>250
>300
(mm)
Napravo je treba hraniti v prostoru, v katerem ni neprekinjeno delujočih virov vžiga
(kot so odprti plameni, delujoča plinska naprava ali delujoči električni grelnik).

6.1.1 Zahteve za namestitveno mesto za zunanjo enoto

INFORMACIJA
Preberite tudi naslednje zahteve:
"2Splošni varnostni ukrepi"[45]."7.1.3Dolžina cevi za hladivo in višinske razlike"[433].
Upoštevajte naslednja prostorska navodila:
Stena z ene strani:
6 | Montaža enote
Stena z dveh strani:
Stena s treh strani:
a Izstopna zračna odprtina b Vstopna zračna odprtina
Ustvarite 300mm delovnega prostora pod stropom in 250mm za servisiranje cevi in električnih povezav.
2(A)MXM40+50 + 2(A)MXF40+50 R32 serija split 4P600463-3D – 2021.03
OPOMBA
Enot NE nameščajte eno na drugo.Enote NE obešajte na strop.
Vodnik za monterja
25
6 | Montaža enote
b
a
b
c
Močni vetrovi (≥18km/h), ki pihajo proti izpustu zraka na zunanji enoti, povzročajo skrajšanje delovnega cikla (vsesavanje izpustnega zraka). Posledice so lahko:
poslabšanje delovne zmogljivosti;pogosta hitra zaledenitev pri ogrevanju;motnje v delovanju zaradi padca nizkega tlaka, ali povečanja visokega tlaka;lomljenje ventilatorja (če močan veter neprekinjeno piha v ventilator, se
ventilator lahko začne vrteti zelo hitro, dokler se ne polomi). Če je izstop zraka izpostavljen vetru, priporočamo, da namestite pregrado. Priporočamo, da zunanjo enoto namestite tako, da bo vstop zraka obrnjen proti
steni in NE neposredno izpostavljen vetru.
a Plošča za preusmerjanje b Pretežna smer vetra
c Izstopna zračna odprtina
Enote NE nameščajte na naslednja mesta:
Izogibajte se občutljivim mestom (npr. blizu spalnice), tako da hrup pri delovanju
ne bo povzročal nevšečnosti.
Opomba: Če je zvok izmerjen v dejanskih pogojih nameščanja, bo izmerjena
vrednost višja od stopnje zvočnega tlaka, navedene v poglavju Zvočni spekter v
knjižici s tehničnimi podatki, zaradi okoljskega hrupa in odbojev zvoka.
INFORMACIJA
Raven zvočnega tlaka je manj kot 70dBA.
Na mestih, kjer so lahko v atmosferi pare mineralnih olj, razpšeno olje ali oljne
pare. Plastični deli lahko propadejo in odpadejo ter povzročijo puščanje vode. Enote NI priporočljivo nameščati na naslednjih mestih, saj to lahko skrajša
življenjsko dobo enote:
Kjer napetost močno nihaV vozilih ali plovilihKjer so prisotne kisle ali alkalne pare
Vodnik za monterja
26
Pri namestitvi na ob morski obali. Prepričajte se, da, zunanja enota NI neposredno izpostavljena morskim vetrovom. Tako boste preprečili korozijo zaradi visoke vsebnosti soli v zraku, ki bi lahko skrajšala življenjsko dobo enote.
Zunanjo enoto namestite stran od morskih vetrov. Primer: Za stavbo.
2(A)MXM40+50 + 2(A)MXF40+50
R32 serija split
4P600463-3D – 2021.03
6 | Montaža enote
b
c
a
a
b
c
d
c
d
a
b
c
c
d
Če je zunanja enota izpostavljena neposrednim morskim vetrovom, namestite vetrno zaščito.
Višina vetrne zaščite≥1,5×višina zunanje enoteKo nameščate vetrno zaščito, bodite pozorni na prostor, ki ga morate pustiti za
servisiranje.
a Morski veter b Stavba
c Zunanja enota
d Vetrna zaščita
Zunanja enota je načrtovana za zunanjo namestitev in okoljske temperature v naslednjih obsegih (razen če je v priročniku za uporabo priključene notranje enote navedeno drugače):
Hlajenje Ogrevanje
–10~46°C DB –15~24°C DB

6.1.2 Dodatne zahteve za namestitveno mesto za zunanjo enoto v hladnih predelih

Zaščitite zunanjo enoto pred neposrednim sneženjem in pazite, da zunanja enota ne bo NIKOLI zasnežena.
2(A)MXM40+50 + 2(A)MXF40+50 R32 serija split 4P600463-3D – 2021.03
a Snežna streha ali lopa b Podstavek
Vodnik za monterja
27
6 | Montaža enote
2
1
1

6.2 Odpiranje enote

6.2.1 O odpiranju enote

c Pretežna smer vetra
d Izstopna zračna odprtina
Priporočamo, da poskrbite za vsaj 150 mm prostora pod enoto (300 mm za območja z veliko snega). Dodatno lahko poskrbite za to, da bo enota vsaj 100mm nad maksimalno pričakovano višino zapadlega snega. Če je treba, naredite podstavek. Za več podrobnosti glejte "6.3Nameščanje zunanje enote"[429].
V krajih z močnim sneženjem je zelo pomembno, da si izberete takšno mesto montaže, kjer sneg NE BO vplival na delovanje enote. Če so možni snežni zameti, pazite, da na tuljavo izmenjevalnika toplote sneg NE BO vplival. Če je to potrebno, namestite pokrov za sneg ali lopo in podstavek.
V določenih primerih morate enoto odpreti. Primer:
Ko priključujete cevi za hladivoPri priključevanju električnega ožičenjaPri vzdrževanju ali servisiranju enote

6.2.2 Odpiranje zunanje enote

NEVARNOST: TVEGANJE SMRTI ZARADI ELEKTRIČNEGA UDARA
Enote NE puščajte brez nadzora, če ste z nje odstranili servisni pokrov.
NEVARNOST: TVEGANJE SMRTI ZARADI ELEKTRIČNEGA UDARA
NEVARNOST: TVEGANJE ZA OŽGANINE/OPEKLINE
Vodnik za monterja
28
2(A)MXM40+50 + 2(A)MXF40+50
R32 serija split
4P600463-3D – 2021.03

6.3 Nameščanje zunanje enote

20 mm

6.3.1 O nameščanju zunanje enote

Kdaj
Zunanjo in notranjo enoto je treba namestiti, preden se nanju priključijo cevi za hladivo.
Običajen potek
Namestitev zunanje enote običajno obsega naslednje faze:
1 Priprava montažne konstrukcije. 2 Montaža zunanje enote. 3 Priprava odvoda vode. 4 Zaščita enote pred snegom in vetrom z namestitvijo snežne strehe in pregrad.
Glejte "6.1Priprava mesta namestitve"[424].

6.3.2 Varnostni ukrepi pri nameščanju zunanje enote

INFORMACIJA
Preberite tudi varnostne ukrepe in zahteve v naslednjih poglavjih:
"2Splošni varnostni ukrepi"[45]"6.1Priprava mesta namestitve"[424]
6 | Montaža enote

6.3.3 Priprava montažne konstrukcije

Preverite nosilnost in izravnanost namestitvenih temeljev, da enota ne bi povzročala vibracij med delovanjem ali hrupa.
Uporabite antivibracijsko gumijasto podlogo (iz lokalne dobave) v primerih, kjer bi se vibracije lahko prenesle na stavbo.
Enoto je mogoče namestiti neposredno na betonsko verando ali drugo trdno površino, če ima pravilno odvodnjavanje.
Enoto varno pritrdite s pomočjo temeljnih vijakov v skladu s sliko. Pripravite 4 komplete temeljnih vijakov, matic in podložk M8 ali M10 (iz lokalne
dobave).
2(A)MXM40+50 + 2(A)MXF40+50 R32 serija split 4P600463-3D – 2021.03
Vodnik za monterja
29
6 | Montaža enote
(mm)
311
574
240
240
a

6.3.4 Montaža zunanje enote

a 100mm nad pričakovano višino zapadlega snega

6.3.5 Priprava drenaže

Vodnik za monterja
30
Poskrbite za pravilno odvajanje kondenzata.Enoto namestite na podstavek, da zagotovite pravilno drenažo, ki bo preprečila
nabiranje ledu.
Okoli temeljev pripravite drenažni kanal, v katerem se bodo zbirale odpadne
vode iz okolice enote.
Preprečite prelivanje odvodne vode čez pohodno pot, da pot ne bi postala
spolzka v primeru zunanjih temperatur pod lediščem.
Če enoto nameščate na okvir, montirajte vodotesno ploščo na razdalji 150mm
od spodnje strani enote, da bi preprečili vdor vode v enoto in kapljanje odvodne
vode (glejte naslednjo ilustracijo).
2(A)MXM40+50 + 2(A)MXF40+50
4P600463-3D – 2021.03
R32 serija split
OPOMBA
b
c
d
a
Če je enota nameščena v hladnem podnebju, naredite, kar je treba, da iztekajoči kondenzat NE bo mogel zmrzniti.
OPOMBA
Če je izpustna odprtina zunanje enote blokirana z montažnim temeljem ali površino tal, postavite dodatne podnožnike ≤30mm pod noge zunanje enote.
INFORMACIJA
Za informacije o razpoložljivih možnostih se obrnite na svojega prodajalca.
1 Uporabite čep za odvod kondenzata. 2 Uporabite gibljivo cev Ø16mm (iz lokalne dobave).
a Izpustna odprtina b Spodnji okvir
c Čep za odvod kondenzata
d Gibljiva cev (iz lokalne dobave)
6 | Montaža enote

6.3.6 Preprečevanje prevračanja zunanje enote

Če je enota nameščena na mestu, kjer bi jo lahko močan veter nagnil ali prevrnil, izvedite naslednje varnostne ukrepe:
1 Pripravite 2 kabla, kot je prikazano na naslednji risbi (iz lokalne dobave). 2 Postavite 2 kabla čez zunanjo enoto. 3 Med kabla in zunanjo enoto vstavite plast gume, da kabli ne bi opraskali barve
(iz lokalne dobave).
4 Pritrdite končnike kablov. 5 Zategnite kable.
2(A)MXM40+50 + 2(A)MXF40+50 R32 serija split 4P600463-3D – 2021.03
Vodnik za monterja
31
7 | Montaža cevi
t
Ø

7 Montaža cevi

V tem poglavju

7.1 Priprava cevi za hladivo .......................................................................................................................................................... 32
7.1.1 Zahteve za cevi za hladivo ...................................................................................................................................... 32
7.1.2 Izolacija cevi za hladivo .......................................................................................................................................... 33
7.1.3 Dolžina cevi za hladivo in višinske razlike .............................................................................................................. 33
7.2 Povezovanje cevi za hladivo ................................................................................................................................................... 34
7.2.1 O priključevanju cevi za hladivo ............................................................................................................................. 34
7.2.2 Varnostni ukrepi pri priključevanju cevi za hladivo ............................................................................................... 34
7.2.3 Navodila pri priključevanju cevi za hladivo ............................................................................................................ 35
7.2.4 Napotki za upogibanje cevi .................................................................................................................................... 36
7.2.5 Robljenje konca cevi............................................................................................................................................... 36
7.2.6 Povezave med zunanjo in notranjo enoto z reducirnimi priključki ....................................................................... 37
7.2.7 Uporaba zapornega ventila in servisnega priključka ............................................................................................. 38
7.2.8 Priključevanje cevi za hladivo na zunanjo enoto ................................................................................................... 40
7.3 Preverjanje cevi za hladivo ..................................................................................................................................................... 40
7.3.1 O preverjanju cevi za hladivo ................................................................................................................................. 40
7.3.2 Napotki za varnost pri preverjanju cevi za hladivo................................................................................................ 41
7.3.3 Preverjanje puščanja .............................................................................................................................................. 41
7.3.4 Vakuumsko praznjenje ........................................................................................................................................... 42

7.1 Priprava cevi za hladivo

7.1.1 Zahteve za cevi za hladivo

INFORMACIJA
Preberite tudi varnostne ukrepe in zahteve v "2Splošni varnostni ukrepi"[45].
OPOMBA
Cevi in deli pod tlakom morajo ustrezati delovanju s hladivom. Uporaba fosforne kisline deoksidira brezšivni baker za hladivo.
Material za cevi: Fosforna kislina deoksidira brezšivni baker.Premer cevi:
Razred 40
Cevi za tekočine 2× Ø6,4mm (1/4")
Cevi za plin 2× Ø9,5mm (3/8")
Razred 50
Cevi za tekočine 2× Ø6,4mm (1/4")
Cevi za plin 1× Ø9,5mm (3/8")
1× Ø12,7mm (1/2")
Stopnja trdote materiala za cevi in debelina sten:
Zunanji premer (Ø) Stopnja trdote Debelina (t)
(a)
6,4mm (1/4") Kaljeno (O) ≥0,8mm
9,5mm (3/8")
12,7mm (1/2")
Vodnik za monterja
32
2(A)MXM40+50 + 2(A)MXF40+50
R32 serija split
4P600463-3D – 2021.03
(a)
ØiØ
i
t
ØpØ
p
Odvisno od veljavne zakonodaje in maksimalnega delovnega tlaka enote (glejte "PS High" na identifikacijski ploščici enote) bodo morda potrebne širše cevi.
Morda bo glede na notranjo enoto treba uporabiti reducirni element. Glejte
"7.2.6Povezave med zunanjo in notranjo enoto z reducirnimi priključki"[437] za
več informacij.

7.1.2 Izolacija cevi za hladivo

Za izolacijski material uporabite polietilensko peno:
- s toplotno prevodnostjo od 0,041 do 0,052W/mK (od 0,035 do 0,045kcal/mh
°C),
- s toplotno obstojnostjo najmanj 120°C.
Debelina izolacije
7 | Montaža cevi
Zunanji premer cevi (Øp) Notranji premer izolacije
6,4mm (1/4") 8~10mm ≥10mm
9,5mm (3/8") 12~15mm ≥13mm
12,7mm (1/2") 14~16mm ≥13mm
Če je temperatura višja od 30°C in je vlažnost višja od RH80%, mora biti debelina izolativnega materiala vsaj 20mm, da se prepreči nastajanje kondenzata na površju izolacije.

7.1.3 Dolžina cevi za hladivo in višinske razlike

Krajše so cevi za hladivo, bolj učinkovit je sistem. Dolžina cevi in višinske razlike morajo ustrezati naslednjim zahtevam.
Model Minimalni zahtevani prostor
Razred 40 1,2m
Razred 50 1,8m
Debelina izolacije (t)
(Øi)
2
2
Najkrajša dovoljena dolžina na prostor je 3m.
Dolžina cevi za hladivo do vsake notranje enote ≤20m
Skupna dolžina cevi za hladivo ≤30m
Zunanja enota,
Maksimalna višinska razlika zunanja-notranja enota
≤15m ≤7,5m
Maksimalna višinska razlika notranja-notranja enota
nameščena više od notranje enote
Zunanja enota,
≤7,5m ≤15m nameščena niže od notranje enote
2(A)MXM40+50 + 2(A)MXF40+50 R32 serija split 4P600463-3D – 2021.03
Vodnik za monterja
33
7 | Montaža cevi

7.2 Povezovanje cevi za hladivo

7.2.1 O priključevanju cevi za hladivo

OPOMIN
Enot, ki so pri pošiljanju že napolnjene s hladivom R32, ne smete spajkati ali variti
na mestu namestitve.
Med nameščanjem hladilnega sistema morate pri spajanju delov, pri katerem je
vsaj v enem delu že hladivo, upoštevati naslednje zahteve: v obljudenih prostorih niso dovoljeni nepermanentni spoji za hladivo R32, razen za spoje, ki jih na mestu namestitve neposredno na notranjo enoto za priključevanje cevi. Spoji, narejeni na mestu namestitve za neposredno povezovanje cevi na notranje enote, morajo biti nepermanentnega tipa.
OPOMIN
NE priključite vložene odcepne cevi in zunanje enote, ko izvajate dela na ceveh brez priključene notranje enote, tako da lahko dodate notranjo enoto kasneje.
Pred priključevanjem cevi za hladivo
Prepričajte se, da sta zunanja in notranja enota nameščeni.
Običajen potek
Priključevanje cevi za hladivo zajema:
Priključevanje cevi za hladivo na notranjo enotoPriključevanje cevi za hladivo na zunanjo enotoIzoliranje cevi za hladivoUpoštevajte navodila za:
- Upogibanje cevi
- Izdelavo razširitev na koncih cevi
- Uporabo zapornih ventilov

7.2.2 Varnostni ukrepi pri priključevanju cevi za hladivo

INFORMACIJA
Preberite tudi varnostne ukrepe in zahteve v naslednjih poglavjih:
"2Splošni varnostni ukrepi"[45]"7.1Priprava cevi za hladivo"[432]
Vodnik za monterja
34
NEVARNOST: TVEGANJE ZA OŽGANINE/OPEKLINE
OPOMIN
V delu z razširitvijo NE uporabljajte mineralnih olj.NE smete uporabiti cevi iz prejšnjih namestitev.Da bi zagotovili dobo uporabnosti te enote R32, vanjo NIKOLI ne vstavljajte sušila.
Sušilni material se lahko raztopi in poškoduje sistem.
2(A)MXM40+50 + 2(A)MXF40+50
R32 serija split
4P600463-3D – 2021.03
7 | Montaža cevi
OPOMIN
Uporabite holandsko matico, pritrjeno na glavno enoto.Da bi preprečili uhajanje plina, hladilno olje nanesite samo na notranjo površino
razširitve. Uporabite hladilno olje za R32.
Spojev NE uporabljajte znova.
OPOMBA
Pri napeljavi cevi za hladivo ravnajte v skladu z naslednjimi varnostnimi ukrepi:
Pazite, da v krog hladiva razen predpisanega hladiva ne vstopijo nobene druge
snovi (npr. zrak).
Pri dodajanju hladiva uporabljajte samo R32.Uporabljajte samo montažno orodje (npr. komplet z manometrskim priključkom),
ki je zasnovano posebej za napeljavo R32 in je tlačno obstojno, da bi preprečili, da se tuje snovi (npr. mineralno olje in vlaga) primešajo v sistem.
Cevi montirajte tako, da razširitev NE bo izpostavljena mehanski obremenitvi.Cevi zaščitite, kot je opisano v naslednji tabeli, da bi preprečili vstop umazanije,
tekočine ali prahu v cevi.
Bodite previdni pri napeljavi bakrenih cevi skozi stene (glejte naslednjo sliko).
Enota Namestitveno obdobje Način zaščite
Zunanja enota >1mesec Zatisnite cev
<1mesec Zatisnite ali zalepite cev
Notranja enota Ne glede na obdobje
INFORMACIJA
Zapornega ventila za hladivo NE odpirajte, dokler ne preverite cevi za hladivo. Kadar dodajate hladivo, priporočamo, da po polnjenju odprete zaporni ventil za hladivo.
OPOZORILO
Varno povežite cevi za hladivo, preden zaženete kompresor. Če cevi za hladivo niso priključene in je zaustavitveni ventil ob zagonu kompresorja odprt, se bo vanj vsesal zrak, kar bo povzročilo previsok pritisk v zanki hladilnega sredstva, kar lahko povzroči škodo na opremi ali poškodbe oseb.
OPOMBA
Tudi če je zaporni ventil popolnoma zaprt, lahko skozenj počasi izteka hladivo. Pazite, da holandska matica NE bo sneta dlje časa.

7.2.3 Navodila pri priključevanju cevi za hladivo

2(A)MXM40+50 + 2(A)MXF40+50 R32 serija split 4P600463-3D – 2021.03
Pri priključevanju cevi upoštevajte naslednje napotke:
Ko priključujete holandsko matico, premažite razširitev z notranje strani z etrskim
ali esterskim oljem. Privijte jo ročno za 3 ali 4 obrate, preden jo zategnete.
Vodnik za monterja
35
7 | Montaža cevi
a
b
c
d
R=
0.4~0.8
±2
45°
90°
±2
ØA
a b
A
Ko odvijate holandsko matico, VEDNO uporabljajte dva ključa hkrati.Ko priključujete cevi, za zategovanje holandske matice vedno uporabite sočasno
viličasti in momentni ključ. S tem boste preprečili pokanje matic in puščanje.
a Momentni ključ b Viličasti ključ
c Cevna spojka
d Holandska matica
Premer cevi (mm) Navojni moment
(N•m)
Premer razširitve
(A) (mm)
Oblika razširitve
(mm)
Ø6,4 15~17 8,7~9,1
Ø9,5 33~39 12,8~13,2
Ø12,7 50~60 16,2~16,6

7.2.4 Napotki za upogibanje cevi

Za krivljenje cevi uporabite orodje za krivljenje cevi. Vse krivine cevi naj bodo kar se da blage (polmer krivine naj bo 30~40mm ali večji).

7.2.5 Robljenje konca cevi

1 Odrežite konec cevi z rezalnikom za cevi. 2 Odstranite srh z roba cevi in jo pri tem držite obrnjeno navzdol, tako da opilki
NE zaidejo v cev.
OPOMIN
Nepopolna razširitev lahko povzroči iztekanje hladiva.Priviha NE smete ponovno uporabiti. Uporabite nove razširitve, da preprečite
uhajanje plinastega hladiva.
Uporabite holandske matice, ki so priložene enoti. Uporaba drugačnih holandskih
matic lahko povzroči puščanje plinastega hladiva.
Vodnik za monterja
36
a Režite točno pod pravim kotom. b Odstranite srh.
3 Odstranite holandsko matico z zapornega ventila in jo namestite na cev. 4 Zarobite cev. Postavite jo natanko v položaj, prikazan v naslednji sliki.
2(A)MXM40+50 + 2(A)MXF40+50
R32 serija split
4P600463-3D – 2021.03
7 | Montaža cevi
a b
c
Orodje za robljenje
cevi za R32 (sklopni tip)
Običajno orodje za razširitev cevi
Sklopni tip
(Tip Ridgid)
A 0~0,5mm 1,0~1,5mm 1,5~2,0mm
5 Preverite, ali je razširitev pravilno izvedena.
a Notranja površina razširitve MORA biti brezhibna. b Konec cevi mora biti enakomerno zarobljen v popoln krog.
c Prepričajte se, da ste namestili holandsko matico.

7.2.6 Povezave med zunanjo in notranjo enoto z reducirnimi priključki

Skupni razred notranjih enot, ki jih je mogoče priključiti na to zunanjo enoto:
Zunanja enota Razred skupne zmogljivosti notranje
enote
2MXM40, 2AMXM40, 2AMXF40, 2MXF40
≤6,0kW
Tip s krilno matico
(Tip Imperial)
2MXM50, 2AMXM50, 2AMXF50,
≤8,5kW
2MXF50
Vrata Razred Reducirni del
2MXM40, 2AMXM40
A 15, 20, 25, 35
B 15, 20, 25, 35
2AMXF40
A 25, 35
B 25, 35
2MXF40
A 20, 25, 35
B 20, 25, 35
2MXM50, 2AMXM50
A 15, 20, 25, 35, 42
(a)
B 15, 20, 25, 35 1+2
42, 50
2(A)MXM40+50 + 2(A)MXF40+50 R32 serija split 4P600463-3D – 2021.03
2AMXF50
A 25, 35
B 25, 35 1+2
2MXF50
A 20, 25, 35
Vodnik za monterja
37
7 | Montaža cevi
a b d ec
c
d
a
b
Vrata Razred Reducirni del
B 20, 25, 35 1+2
(a)
Uporabite opcijsko dodatno opremo.
Tip reducirnega dela Povezava
1 Ø12,7mm → Ø9,5mm
2 Ø12,7mm → Ø9,5mm
Zgled povezave:
Povezovanje Ø9,5mm cevi na priključek za cev Ø12,7mm
a Priključek za zunanjo enoto b Reducirni del tip 1
c Reducirni del tip 2 d Holandska matica za Ø12,7mm e Cevi za povezavo enot
Navoj priključka na zunanji enoti, kjer vanjo vstopi holandska matica, namažite z oljem za hladivo.
OPOMBA
Uporabite ustrezen ključ, da ne bi poškodovali navojnega priključka s premočnim zategovanjem holandske matice. Pazite, da matice NE boste preveč zategnili, sicer lahko poškodujete tanjšo cev (za pribl. 2/3-1× običajnega navojnega momenta).

7.2.7 Uporaba zapornega ventila in servisnega priključka

Ravnanje z zapornim ventilom
Upoštevajte naslednje napotke:
Zaporni ventili so tovarniško zaprti.Naslednja slika prikazuje dele zapornega ventila, potrebne pri rokovanju z
ventilom.
Vodnik za monterja
38
a Servisni priključek in pokrov servisnega priključka b Steblo ventila
c Priključek na cevi, nameščene na licu mesta d Pokrovček stebla
2(A)MXM40+50 + 2(A)MXF40+50
R32 serija split
4P600463-3D – 2021.03
7 | Montaža cevi
a
b
Oba zaporna ventila naj bosta med delovanjem odprta.Na steblo zapornega ventila ne delujte s preveliko silo. To bi lahko polomilo
ohišje ventila.
Zaporni ventil morate VEDNO priviti z viličastim ključem, in nato odviti ali priviti
holandsko matico z momentnim ključem. Viličastega ključa NE postavljajte na pokrov stebla ventila, ker bi s tem lahko povzročili uhajanje hladiva.
a Viličasti ključ b Momentni ključ
Če pričakujete nizek delovni tlak (npr. kadar se bo pri nizki zunanji temperaturi
izvajalo hlajenje), v zadostni meri zatesnite holandsko matico na zapornem ventilu na plinskem vodu s silikonskim tesnilom, da bi preprečili zamrznitev.
Silikonsko tesnilo; pazite, da ne bo vrzeli.
Odpiranje/zapiranje zapornega ventila
1 Odstranite pokrov zapornega ventila. 2 Vstavite šestkotni ključ (tekočinska stran: 4mm, plinska stran: 6mm) v steblo
ventila in ga obračajte:
V nasprotni smeri urinega kazalca za odpiranje V smeri urinega kazalca za zapiranje
3 Ko zapornega ventila ni več mogoče vrteti, se zaustavite. 4 Namestite pokrov zapornega ventila.
Rezultat: Ventil je zdaj odprt/zaprt.
Ravnanje s pokrovom stebla ventila
Pokrov stebla ventila je zatesnjen na mestu, ki ga prikazuje puščica. NE
poškodujte ga.
2(A)MXM40+50 + 2(A)MXF40+50 R32 serija split 4P600463-3D – 2021.03
Po delu z zapornim ventilom privijte pokrov stebla in preverite puščanje
hladilnega sredstva.
Pokrovček stebla Širina ploščatega ključa
Navojni moment (N•m)
(mm)
Visokotlačni del
22 21~28
(tekočina)
Vodnik za monterja
39
7 | Montaža cevi
a
c
b
a
b
Pokrovček stebla Širina ploščatega ključa
Nizkotlačni del (plin) 22 21~28
Ravnanje s servisnim pokrovom
Vedno uporabljajte cev za polnjenje, opremljeno z zatičem za zniževanje tlaka, saj
je to servisni priključek za ventil tipa Schrader.
Po delu s servisnim priključkom zategnite pokrovček servisnega priključka in
preverite, ali kje pušča hladivo.
Element Navojni moment (N•m)
Pokrov servisnega priključka 11~14

7.2.8 Priključevanje cevi za hladivo na zunanjo enoto

Dolžine cevi. Cev na mestu namestitve naj bodo kolikor je mogoče kratke.Zaščita cevi. Zaščitite cevi na mestu namestitve pred fizičnimi poškodbami.
1 Priključite priključek notranje enote za hladivo v tekočem stanju na zaporni
ventil zunanje enote za tekočino.
Navojni moment (N•m)
(mm)
27 48~59
a Zaporni ventil za tekočino b Zaporni ventil za plin
c Servisni priključek
2 Priključite priključek za plin notranje enote na zaporni ventil za plin zunanje
enote.
OPOMBA
Priporočamo, da cevi za hladivo med notranjo in zunanjo enoto namestite v kanal ali da cevi za hladivo ovijete z zaključnim trakom.

7.3 Preverjanje cevi za hladivo

7.3.1 O preverjanju cevi za hladivo

Notranje cevi za hladivo v zunanji enoti so tovarniško preizkušene glede puščanja. Preveriti morate samo zunanje cevi za hladivo zunanje enote.
Pred preverjanjem cevi za hladivo
Cev za hladivo mora biti priključena med zunanjo in notranjo enoto.
Vodnik za monterja
40
2(A)MXM40+50 + 2(A)MXF40+50
R32 serija split
4P600463-3D – 2021.03
Običajen potek
Preverjanje cevi za hladivo običajno obsega naslednje faze:
1 preverjanje, ali cevi za hladivo puščajo, in 2 izvajanje vakuumskega praznjenja, da odstranite vso tekočino iz cevi za hladivo.
Če je možno, da je vlaga v ceveh za hladivo (na primer če vanje zaide voda), najprej izvedite postopek vakuumskega sušenja, tako da odstranite vso vlago.

7.3.2 Napotki za varnost pri preverjanju cevi za hladivo

INFORMACIJA
Preberite tudi varnostne ukrepe in zahteve v naslednjih poglavjih:
"2Splošni varnostni ukrepi"[45]"7.1Priprava cevi za hladivo"[432]
OPOMBA
Uporabite 2-stopenjsko vakuumsko črpalko z nepovratnim ventilom, ki lahko sistem izprazni do tlaka na manometru −⁠100,7kPa (−⁠1,007 bar) (5Torr absolutno). Pazite, da olje črpalke ne bo teklo v nasprotni smeri v sistem, kadar črpalka ne deluje.
7 | Montaža cevi

7.3.3 Preverjanje puščanja

OPOMBA
To vakuumsko črpalko uporabljajte izključno za R32. Uporaba iste črpalke za druga hladiva lahko povzroči poškodbe črpalke in enote.
OPOMBA
Priključite vakuumsko črpalko na servisni priključek plinskega zapornega ventila.Pazite, da bosta plinski zaporni ventil in tekočinski zaporni ventil tesno zaprta,
preden izvajate preizkus tesnjenja ali vakuumsko praznjenje.
OPOMBA
NE smete preseči maksimalnega delovnega tlaka enote (glejte “PS High” na nazivni ploščici enote).
OPOMBA
VEDNO uporabite priporočeno raztopino za preverjanje puščanja, ki jo dobite pri svojem dobavitelju.
NIKOLI ne uporabljajte milnice:
Milnica lahko povzroči razpoke na komponentah, kot so holandske matice in
pokrovi zapornih ventilov.
Milnica lahko vsebuje sol, ki bo vpila vlago, ki bo zamrznila, ko se cevi shladijo.Milnica vsebuje amoniak, ki lahko povzroči korozijo razširjenih spojev (med
medeninasto in bakreno holandsko matico).
2(A)MXM40+50 + 2(A)MXF40+50 R32 serija split 4P600463-3D – 2021.03
1 Sistem napolnite z dušikovim plinom, do tlaka na manometru najmanj 200kPa
(2 bar). Priporočamo, da zaradi prepoznavanja manjših puščanj vzpostavite tlak 3000kPa (30barov).
2 Tesnjenje preizkusite tako, da na vse povezave nanesete testno raztopino, ki
se peni.
Vodnik za monterja
41
7 | Montaža cevi
g
f
d
e
a c
b
j
i
h
h
k

7.3.4 Vakuumsko praznjenje

3 Izpustite ves dušikov plin.
NEVARNOST: NEVARNOST EKSPLOZIJE
Enote NE zaženite, dokler ni ustvarjen vakuum.
Priključite vakuumsko črpalko in zbiralnik, kot sledi:
a Merilni instrument za prenizek tlak b Zbiralnik manometra
c Merilni instrument za previsok tlak d Nizkotlačni ventil (Lo) e Visokotlačni ventil (Hi)
f Cevi za polnjenje g Vakuumska črpalka h Pokrovčki ventilov
i Servisni priključek
j Zaporni ventil za plin k Zaporni ventil za tekočino
OPOMBA
Priključite vakuumsko črpalko na oba servisna priključka zaustavitvenih ventilov za plin.
1 Sistem praznite, dokler ni tlak na manometru −0,1MPa (−1bar). 2 Počakajte 4–5minut in preverite tlak:
Če tlak… Potem…
Se ne spremeni V sistemu ni vlage. Postopek je
končan.
Naraste V sistemu je vlaga. Pojdite na
naslednji korak.
3 Vakuumsko praznjenje sistema izvajajte najmanj 2 uri, dokler ni tlak na
manometru −0,1MPa (−1bar).
4 Tlak preverjajte še najmanj 1uro po izklopu črpalke.
Vodnik za monterja
42
5 Če ciljnega vakuuma NE dosežete ali ga NE MORETE obdržati 1uro, naredite
naslednje:
Znova preverite puščanje.Ponovite vakuumsko praznjenje.
2(A)MXM40+50 + 2(A)MXF40+50
R32 serija split
4P600463-3D – 2021.03
7 | Montaža cevi
OPOMBA
Po namestitvi cevi in praznjenju obvezno odprite plinski zaporni ventil. Če sistem deluje z zaprtim ventilom, lahko pride do okvare kompresorja.
INFORMACIJA
Ko odprete zaporni ventil, se tlak v cevni napeljavi hladiva morda NE bo zvišal. To lahko povzroči npr. zaprt ekspanzijski ventil v krogotoku zunanje enote, vendar to NE ovira pravilnega delovanja enote.
2(A)MXM40+50 + 2(A)MXF40+50 R32 serija split 4P600463-3D – 2021.03
Vodnik za monterja
43
8 | Polnjenje s hladivom

8 Polnjenje s hladivom

V tem poglavju

8.1 O polnjenju s hladivom

8.1 O polnjenju s hladivom........................................................................................................................................................... 44
8.2 O hladivu................................................................................................................................................................................. 45
8.3 Varnostni ukrepi pri polnjenju s hladivom ............................................................................................................................. 46
8.4 Določanje dodatne količine hladiva ....................................................................................................................................... 46
8.5 Določanje celotne količine ponovnega polnjenja .................................................................................................................. 46
8.6 Dolivanje dodatnega hladiva .................................................................................................................................................. 46
8.7 Pritrjevanje nalepke o fluoriranih toplogrednih plinih .......................................................................................................... 47
Zunanja enota je tovarniško napolnjena s hladivom, vendar je v nekaterih primerih morda potrebno naslednje:
Kaj Kdaj
Dolivanje dodatnega hladiva Ko je skupna dolžina cevi večja od
določene (glejte v nadaljevanju).
Polnjenje celotnega hladiva Primer:
Pri selitvi sistema.Po puščanju.
Dolivanje dodatnega hladiva
Prepričajte se, da so bile zunanje cevi za hladivo zunanje enote pregledane (preizkus tesnosti, vakuumsko sušenje).
INFORMACIJA
Odvisno od enot in/ali od pogojev nameščanja bo morda treba povezati električno ožičenje, preden lahko napolnite hladivo.
Običajni potek dela – Dolivanje dodatnega hladiva navadno sestoji iz naslednjih stopenj:
1 Določanje, ali je treba doliti hladivo in koliko.
2 Če je to potrebno, doliti dodatno hladivo.
3 Izpolnjevanje nalepke z informacijo o toplogrednih fluoriranih plinih in
prilepljanje nalepke na notranjo stran zunanje enote.
Polnjenje celotnega hladiva
Vodnik za monterja
44
Pred polnjenjem celotnega hladiva se prepričajte, da je bilo narejeno naslednje:
1 Vse hladivo je bilo izčrpano iz sistema.
2 Zunanje cevi za hladivo zunanje enote so bile pregledane (preizkus tesnosti,
vakuumsko sušenje).
3 Vakuumsko sušenje notranjih cevi za hladivo zunanje enote je bilo izvedeno.
OPOMBA
Pred vnovičnim polnjenjem s hladivom opravite tudi vakuumsko praznjenje notranje cevi za hladivo v zunanji enoti.
2(A)MXM40+50 + 2(A)MXF40+50
R32 serija split
4P600463-3D – 2021.03

8.2 O hladivu

8 | Polnjenje s hladivom
Običajni potek dela – Polnjenje celotnega hladiva navadno sestoji iz naslednjih stopenj:
1 Določanje, koliko hladiva doliti.
2 Polnjenje s hladivom.
3 Izpolnjevanje nalepke z informacijo o toplogrednih fluoriranih plinih in
prilepljanje nalepke na notranjo stran zunanje enote.
Izdelek vsebuje fluorirane toplogredne pline. Plinov NE izpuščajte v ozračje. Tip hladiva: R32 Vrednost potenciala globalnega segrevanja (GWP): 675
OPOMBA
Zadevna zakonodaja o toplogrednih fluoriranih plinih zahteva, da je polnitev hladiva na enoti označena v teži in enakovredni vrednosti CO2.
Formula za izračun enakovredne vrednosti v tonah CO2: GWP vrednost hladiva × Skupno polnjenje hladiva [v kg] / 1000
Prosimo, da stopite v stik z monterjem, če želite več informacij.
OPOZORILO: BLAGO VNETLJIV MATERIAL
Hladivo v enoti je blago vnetljivo.
OPOZORILO
Napravo je treba hraniti v prostoru, v katerem ni neprekinjeno delujočih virov vžiga (kot so odprti plameni, delujoča plinska naprava ali delujoči električni grelnik).
OPOZORILO
NE luknjajte in ne sežigajte delov hladilnega kroga.NE uporabljajte čistilnih snovi ali sredstev za pospeševanje postopka
odmrzovanja, razen tistih, ki jih priporoča proizvajalec.
Zavedajte se, da hladivo v sistemu nima nikakršnega vonja.
OPOZORILO
Hladivo v enoti je blago vnetljivo, vendar navadno NE pušča. Če hladivo uhaja v prostor in pride v stik z ognjem z gorilnika, grelca ali štedilnika, lahko pride do požara ali do nastajanja škodljivega plina.
Izključite vse vnetljive grelne naprave, prostor prezračite in stopite v stik s prodajalcem, pri katerem ste kupili enoto.
Enote ne uporabljajte, dokler serviser ne potrdi, da je bil del, iz katerega je puščalo hladivo, popravljen.
2(A)MXM40+50 + 2(A)MXF40+50 R32 serija split 4P600463-3D – 2021.03
OPOZORILO
Nikoli se z golo kožo ne dotaknite ponesreči razlitega hladiva. To bi lahko povzročilo rane zaradi ozeblin.
Vodnik za monterja
45
8 | Polnjenje s hladivom

8.3 Varnostni ukrepi pri polnjenju s hladivom

8.4 Določanje dodatne količine hladiva

INFORMACIJA
Preberite tudi varnostne ukrepe in zahteve v naslednjih poglavjih:
"2Splošni varnostni ukrepi"[45]"7.1Priprava cevi za hladivo"[432]
Če je skupna dolžina cevi za
tekočino…
≤20m NE dodajajte hladiva.
>20m R=(skupna dolžina (m) tekočinskih cevi–20m)×0,020
R=dodatno polnjenje (kg)(zaokroženo na enote po 0,1kg)
INFORMACIJA
Dolžina cevi je dolžina tekočinskih cevi v eni smeri.

8.5 Določanje celotne količine ponovnega polnjenja

INFORMACIJA
Če je potrebno ponovno polnjenje, je skupna količina ponovnega polnjenja hladiva: tovarniško polnjenje s hladivom (glejte nazivno ploščico enote) + ugotovljena dodatna količina.
Potem…

8.6 Dolivanje dodatnega hladiva

Vodnik za monterja
46
OPOZORILO
Za hladivo uporabljajte samo R32. Druge snovi lahko povzročijo eksplozije in
nesreče.
R32 vsebuje fluorirane toplogredne pline. Njegova vrednost potenciala
globalnega segrevanja (GWP) je 675. Teh plinov NE izpuščajte v ozračje.
Pri točenju hladiva vedno uporabljajte zaščitne rokavice in zaščitna očala.
OPOMIN
Da preprečite okvaro kompresorja, NE točite večje količine hladiva od predpisane.
Predpogoj: Pred polnjenjem s hladivom se prepričajte, da so cevi za hladivo priključene in preverjene (preverjanje puščanja in vakuumsko izčrpavanje).
1 Priključite vsebnik hladiva na servisni priključek. 2 Natočite dodatno količino hladiva. 3 Odprite zaporni ventil za plin.
2(A)MXM40+50 + 2(A)MXF40+50
R32 serija split
4P600463-3D – 2021.03
8 | Polnjenje s hladivom
b
Contains fluorinated greenhouse gases
2
1
1
1
2
2
kg
tCO2eq
GWP × kg
1000
=
=
+
kg
=
kg
=
GWP: XXX
RXXX
a
f
c
d
e

8.7 Pritrjevanje nalepke o fluoriranih toplogrednih plinih

1 Nalepko izpolnite na naslednji način:
a Če je z enoto dobavljena večjezična nalepka z informacijo o toplogrednih fluoriranih
plinih, odlepite del nalepke z ustreznim jezikom in ga nalepite na vrh a.
b Tovarniško polnjenje hladiva: glejte identifikacijsko ploščico enote
c Količina dodatno dolitega hladiva d Skupno polnjenje hladiva e Količina toplogrednih fluoriranih plinov skupnega polnjenja hladiva, izražena v
enakovrednih tonah CO2.
f GWP = potencial globalnega segrevanja
OPOMBA
Zadevna zakonodaja o toplogrednih fluoriranih plinih zahteva, da je polnitev hladiva na enoti označena v teži in enakovredni vrednosti CO2.
Formula za izračun enakovredne vrednosti v tonah CO2: GWP vrednost hladiva × Skupno polnjenje hladiva [v kg] / 1000
Uporabite omenjeno vrednost GWP na nalepki za dolivanje hladiva.
2 Nalepko prilepite v notranjščino zunanje enote poleg zapornih ventilov za plin
in tekočino.
2(A)MXM40+50 + 2(A)MXF40+50 R32 serija split 4P600463-3D – 2021.03
Vodnik za monterja
47
9 | Električna napeljava

9 Električna napeljava

V tem poglavju

9.1 O priključevanju električnega ožičenja

9.1 O priključevanju električnega ožičenja................................................................................................................................... 48
9.1.1 Napotki za varnost pri priključevanju električnega ožičenja ................................................................................. 48
9.1.2 Napotki za priključevanje električnega ožičenja.................................................................................................... 50
9.1.3 Specifikacije standardnih komponent ožičenja ..................................................................................................... 51
9.2 Da bi povezali električno ožičenje na zunanjo enoto............................................................................................................. 51
Pred priključevanjem električnega ožičenja
Prepričajte se, da so cevi za hladivo priključene in pregledane.
Običajen potek
Priključevanje električnega ožičenja običajno obsega naslednje faze:
1 Prepričajte se, da napajalni sistem ustreza električnim specifikacijam enot. 2 Priključevanje električnega ožičenja na zunanjo enoto. 3 Priključevanje električnega ožičenja na notranjo enoto. 4 Priključitev glavnega napajanja.

9.1.1 Napotki za varnost pri priključevanju električnega ožičenja

NEVARNOST: TVEGANJE SMRTI ZARADI ELEKTRIČNEGA UDARA
OPOZORILO
Naprava mora biti nameščena v skladu z nacionalnimi predpisi za ožičenje.
OPOZORILO
Za napajalne kable VEDNO uporabite večžilni kabel.
INFORMACIJA
Preberite tudi varnostne ukrepe in zahteve v "2Splošni varnostni ukrepi"[45].
INFORMACIJA
Preberite tudi "9.1.3Specifikacije standardnih komponent ožičenja"[451].
OPOZORILO
Ožičenje MORA v celoti opraviti pooblaščen električar, izvedba pa MORA ustrezati
veljavni zakonodaji.
Izdelajte električne priključke na fiksno ožičenje.Vse komponente, ki se priskrbijo na mestu vgradnje, in vse električne napeljave
MORAJO biti skladne z veljavno zakonodajo.
Vodnik za monterja
48
2(A)MXM40+50 + 2(A)MXF40+50
R32 serija split
4P600463-3D – 2021.03
9 | Električna napeljava
OPOZORILO
Če N-faza ni priključena ali pa je napačno priključena, lahko to povzroči okvaro
opreme.
Vzpostavite primerno ozemljitev. Enote NE ozemljujte s pomočjo komunalne cevi,
prenapetostnega odvodnika ali telefonskega ozemljitvenega kabla. Nepopolna ozemljitev lahko povzroči električni udar.
Vgradite zahtevane varovalke ali odklopnike.Pritrdite električno ožičenje z vezicami za kable, tako da se kabli NE dotikajo ostrih
robov ali cevi, zlasti na strani visokega tlaka.
NE uporabljajte sestavljenih vodnikov, pletenih žičnih vodnikov, podaljševalnih
kablov ali povezav iz zvezdišča. To lahko povzroči pregrevanje, električni udar ali požar.
NE nameščajte kondenzatorja za fazni premik, saj je ta enota opremljena z
inverterjem. Kondenzator za fazni premik bo zmanjšal zmogljivost in lahko povzroči nesreče.
OPOZORILO
Uporabite prekinjalo za odklop vseh polov z vsaj 3mm med kontaktnimi točkovnimi režami, ki omogočajo popolni odklop v III. kategoriji previsoke napetosti.
OPOZORILO
Če je napajalni kabel poškodovan, ga MORAJO proizvajalec, serviser ali podobno usposobljena oseba zamenjati, da ne bi prišlo do nevarne situacije.
OPOZORILO
NE povezujte napajalnega kabla na notranjo enoto. To lahko povzroči električni udar ali požar.
OPOZORILO
V enoto ne nameščajte električnih delov, kupljenih v lokalni trgovini.NE razpeljujte napajanja za odvodno črpalko itd. s priključnega bloka. To lahko
povzroči električni udar ali požar.
OPOZORILO
Pazite, da bodo kabli za medsebojne povezave stran od bakrenih cevi brez termoizolacije, saj se te cevi zelo segrejejo.
NEVARNOST: TVEGANJE SMRTI ZARADI ELEKTRIČNEGA UDARA
Vsi električni deli (vključno s termistorji) se napajajo iz napajalnega omrežja. Ne dotikajte s jih z golimi rokami.
2(A)MXM40+50 + 2(A)MXF40+50 R32 serija split 4P600463-3D – 2021.03
NEVARNOST: TVEGANJE SMRTI ZARADI ELEKTRIČNEGA UDARA
Odklopite napajanje za več kot 10minut ter izmerite napetost na priključnih sponkah kondenzatorjev glavnega tokokroga ali električnih sestavnih delih, preden začnete servisiranje. Napetost mora biti nižja od 50 V DC, preden se lahko dotaknete električnih sestavnih delov. Za mesto priključnih sponk glejte vezalno shemo.
Vodnik za monterja
49
9 | Električna napeljava
ACDC
DC
­+
efghij
a
b
k
c
d
l
b a
c b
c
aa
A
AA´
a DB1 premostitev diode b S90 glavni vodnik termistorja
c LED A d S40 glavni vodnik termične preobremenitve e S20 (bel) navitje elektronskega ekspanzijskega ventila prostora A
f S21 (rdeč) navitje elektronskega ekspanzijskega ventila prostora B g S80 (bel) štirismerni ventil priključka glavnega vodnika h S70 glavni vodnik motorja ventilatorja
i S99 ključavnica ogrevanja
j S91 (rdeč) glavni vodnik termistorja za tekočino k S92 (bel) glavni vodnik termistorja za plin
l Multimeter (enosmerno napetostno območje)

9.1.2 Napotki za priključevanje električnega ožičenja

Ves čas upoštevajte naslednje:
Če uporabite večžilni vodnik, namestite cevni kabelski čeveljček z ušesom na
konec vodnika. Okrogle priključke z ušesom postavite na vodnike na pokritih delih in pritrdite priključne sponke z ustreznim orodjem.
a Standardni vodnik b Okrogla obrobljena ferula
Pri nameščanju vodnikov uporabite naslednji postopek:
Tip vodnika Način montaže
Enožilni vodnik
a Spiralni enožilni vodnik b Vijak
Vodnik za monterja
50
c Ploska podložka
2(A)MXM40+50 + 2(A)MXF40+50
R32 serija split
4P600463-3D – 2021.03
9 | Električna napeljava
c b ba c
a
B
B
1-3
Tip vodnika Način montaže
Pleteni žični vodnik z okroglim obrobljenim priključkom
a Priključek b Vijak c Ploska podložka
Dovoljeno
NI dovoljeno
Navojni momenti
Predmet Navojni moment (N•m)
M4 (X1M) 1,2 M4 (zemlja)
Ozemljitveni vodnik med zadrževalnikom vodnika in priključkom mora biti daljši
od drugih vodnikov.

9.1.3 Specifikacije standardnih komponent ožičenja

Komponenta
Kabel za električno napajanje
Kabel za medsebojno povezavo (notranja ↔ zunanja)
Priporočeno prekinjalo vezja 16A
Naprava za tokovni ostanek MORA ustrezati veljavni
Napetost 220~240V
Faza 1~
Frekvenca 50Hz
Tip vodnika 3-žilni kabel 2,5mm
2
H05RN-F (60245 IEC 57) H07RN-F (60245 IEC 66)
3-žilni kabel 4,0 mm
2
H07RN-F (60245 IEC 66)
4-žilni kabel 1,5mm2 ali 2,5mm
in uporabno pri 220~240V
H05RN-F (60245 IEC 57)
zakonodaji
2

9.2 Da bi povezali električno ožičenje na zunanjo enoto

2(A)MXM40+50 + 2(A)MXF40+50 R32 serija split 4P600463-3D – 2021.03
1 Odstranite pokrov stikalne omarice (2 vijaka).
Vodnik za monterja
51
9 | Električna napeljava
2
1
a b
e-A
a-A a-B
e-B
b c
d
1 2 3
L N
1 2 3
f
2 Odstranite izolacijo (20mm) z vodnikov.
a Izolacijo odstranite do te točke b Predolg ogoljeni del žice lahko povzroči električni šok ali uhajanje toka
3 Povežite žice med notranjo in zunanjo enoto, tako da se številke priključkov
ujemajo. Prepričajte se, da se simboli za cevi in ožičenje ujemajo.
4 Prepričajte se, da ste priključili ožičenje na pravi prostor (A na A, B na B).
a Priključna sponka za prostor (A, B) b Prekinjalo vezja
c Naprava za tokovni ostanek d Vodnik za električno napajanje e Povezovalni vodnik za prostor (A, B)
f Držalo žice
5 Dobro privijte vijake priključkov s križnim izvijačem. 6 Preverite, da se kabli ne bodo sneli, tako da jih narahlo pocukate. 7 Varno pritrdite zadrževalnik vodnika, da bi se izognili zunanjemu pritisku na
končnike vodnikov.
8 Ožičenje povlecite skozi luknjo na dnu zaščitne plošče. 9 Zagotovite, da se električno ožičenje dotika plinskih cevi.
Vodnik za monterja
52
2(A)MXM40+50 + 2(A)MXF40+50
R32 serija split
4P600463-3D – 2021.03
9 | Električna napeljava
1 2 3
1 2 3 1 2 3
1 2 3
L N
A B
10 Spet pritrdite pokrov stikalne omarice in servisni pokrov.
2(A)MXM40+50 + 2(A)MXF40+50 R32 serija split 4P600463-3D – 2021.03
Vodnik za monterja
53
10 | Zaključevanje montaže zunanje enote
g
b
a
f
e
cd

10 Zaključevanje montaže zunanje enote

10.1 Zaključevanje montaže zunanje enote

NEVARNOST: TVEGANJE SMRTI ZARADI ELEKTRIČNEGA UDARA
Prepričajte se, da je sistem ustrezno ozemljen.Pred servisiranjem izklopite napajanje.Namestite pokrov stikalne omarice, preden vključite napajanje.
OPOMBA
Priporočamo, da cevi za hladivo med notranjo in zunanjo enoto namestite v kanal ali da cevi za hladivo ovijete z zaključnim trakom.
1 Izolirajte in pritrdite cevi za hladivo in kable, kot sledi:
a Cev za hladivo v plinastem stanju b Izolacija cevi za hladivo v plinastem stanju
c Kabel za medsebojno povezavo d Zunanje ožičenje (če je na voljo) e Cev za hladivo v tekočem stanju
f Izolacija cevi za hladivo v tekočem stanju
g Ovojni trak
2 Namestite servisni pokrov.

10.2 Zapiranje zunanje enote

1 Zaprite pokrov stikalne omarice. 2 Zaprite servisni pokrov.
Vodnik za monterja
54
2(A)MXM40+50 + 2(A)MXF40+50
R32 serija split
4P600463-3D – 2021.03

11 Konfiguracija

a
cde
b
J26
J24
J23
J6
J22
J8

V tem poglavju

11.1 O nastavitvi načina z omejitvijo ECONO................................................................................................................................. 55
11.1.1 Da bi vključili nastavitev načina z omejitvijo ECONO............................................................................................. 55
11.2 O tihem nočnem načinu delovanja ........................................................................................................................................ 56
11.2.1 Da bi vključili tiho nočno delovanje ....................................................................................................................... 56
11.3 O načinu zaklepanja na ogrevanje.......................................................................................................................................... 56
11.3.1 Da bi enoto zaklenili na ogrevanje......................................................................................................................... 56
11.4 O funkciji za varčevanje elektrike v stanju pripravljenosti..................................................................................................... 57
11.4.1 Da bi izklopili varčevanje z električno energijo v pripravljenosti .......................................................................... 57

11.1 O nastavitvi načina z omejitvijo ECONO

Nastavitev onemogoči vhodni krmilni signal z uporabniškega vmesnika. To nastavitev uporabite, ko želite blokirati sprejem vhodnih ukazov (hlajenje/ ogrevanje) z uporabniških vmesnikov notranje enote.

11.1.1 Da bi vključili nastavitev načina z omejitvijo ECONO

11 | Konfiguracija
Predpogoj: Glavno napajanje MORA biti izklopljeno.
1 Odstranite zgornjo ploščo zunanje enote (2 vijaka na stranicah) 2 Odstranite pokrov omarice z električnimi deli, tako da za zadrsate stran.
Pazite, da ne ukrivite kavlja električne omarice.
3 Prerežite mostiček (J23).
2(A)MXM40+50 + 2(A)MXF40+50 R32 serija split 4P600463-3D – 2021.03
a Zgornja plošča b Pokrov električne omarice
c Električna omarica d Tiskano vezje e Tiskano vezje z mostički
Vodnik za monterja
55
11 | Konfiguracija
J26
J24
J23
J6
J22
J8
bc
a

11.2 O tihem nočnem načinu delovanja

11.2.1 Da bi vključili tiho nočno delovanje

4 Spet namestite pokrov električne omarice in zgornjo ploščo v nasprotnem
vrstnem redu in vključite glavno napajanje.
Ko je vključeno tiho nočno delovanje, zunanja enota ponoči deluje tiše. To tudi zmanjša zmogljivost hlajenja enote. Stranki razložite, kako deluje način tiho nočno delovanje in naj vam potrdi, ali ga želi uporabljati.
Predpogoj: Glavno napajanje MORA biti izklopljeno.
1 Odstranite zgornjo ploščo in pokrov električne omarice zunanje enote (glejte
"11.1.1Da bi vključili nastavitev načina z omejitvijo ECONO"[455])
2 Prerežite mostiček J6.
3 Spet namestite zgornjo ploščo in pokrov električne omarice.
OPOMIN
Ko vračate na njegovo mesto pokrov električne omarice, pazite, da ne boste stisnili glavnega vodnika ventilatorja za motor.

11.3 O načinu zaklepanja na ogrevanje

Zaklep na ogrevanje enoto zaklene na ogrevanje.

11.3.1 Da bi enoto zaklenili na ogrevanje

1 Odstranite zgornjo ploščo (2 vijaka) in sprednjo ploščo (8 vijakov). 2 Da bi nastavili način zaklepanja na ogrevanje, snemite priključek S99. 3 Da bi ponastavili način toplotne črpalke (hlajenje/ogrevanje), spet vtaknite
priključek.
Vodnik za monterja
56
2(A)MXM40+50 + 2(A)MXF40+50
R32 serija split
4P600463-3D – 2021.03
11 | Konfiguracija
a Sprednja plošča b Zgornja plošča
c Konektor S99
Način Konektor S99
Toplotna črpalka (hlajenje, ogrevanje) Povezana
Samo ogrevanje Prekinjam povezavo
4 Spet namestite zgornjo in sprednjo ploščo.
INFORMACIJA
Prisiljeno delovanje je na voljo tudi v načinu ogrevanja.

11.4 O funkciji za varčevanje elektrike v stanju pripravljenosti

O funkciji za varčevanje elektrike v stanju pripravljenosti:
izključi napajanje zunanje enote invključi način varčevanje z električno energijo v pripravljenosti notranje enote.
O funkciji za varčevanje elektrike v stanju pripravljenosti: deluje z naslednjimi enotami:
FTXM, FTXP, FTXJ, FVXM, ATXF Če je uporabljena druga notranja enota, je treba priključiti vtič za varčevanje z z
električno energijo v pripravljenosti. Funkcija za varčevanje elektrike v stanju pripravljenosti se izključi pred dobavo.

11.4.1 Da bi izklopili varčevanje z električno energijo v pripravljenosti

Predpogoj: Glavno napajanje MORA biti izklopljeno.
1 Odstranite servisni pokrov. 2 Odklopite izbirni priključek za varčevanje z električno energijo v
pripravljenosti.
2(A)MXM40+50 + 2(A)MXF40+50 R32 serija split 4P600463-3D – 2021.03
3 Vklopite napajanje.
Vodnik za monterja
57
12 | Zagon

12 Zagon

OPOMBA
Splošni kontrolni seznam za zagon. Poleg navodil za zagon v tem poglavju je v
spletišču Daikin Business Portal (potrebna je prijava) na voljo splošni kontrolni seznam za zagon.
Splošni kontrolni seznam za zagon je dopolnilo navodilom v tem poglavju in se lahko uporabi kot smernica ter predloga za poročanje med zagonom in predajo uporabniku.

V tem poglavju

12.1 Pregled: zagon ........................................................................................................................................................................ 58
12.2 Napotki za varnost pri zagonu................................................................................................................................................ 58
12.3 Seznam preverjanj pred zagonom.......................................................................................................................................... 58
12.4 Seznam preverjanj med zagonom.......................................................................................................................................... 59
12.5 Preizkus delovanja.................................................................................................................................................................. 59
12.5.1 Izvajanje testnega zagona ...................................................................................................................................... 60
12.6 Zagon zunanje enote.............................................................................................................................................................. 60

12.1 Pregled: zagon

To poglavje opisuje, kaj morate narediti in vedeti, da poženete sistem, potem ko je bil nameščen.
Običajen potek
Zagon običajno obsega naslednje faze:
1 Preverjanje "Seznama preverjanj pred začetkom uporabe". 2 Izvajanje preizkusa delovanja sistema.

12.2 Napotki za varnost pri zagonu

INFORMACIJA
Med prvim zagonom enote bo potrebna moč morda večja od moči, navedene na nazivni ploščici enote. Ta pojav povzroča kompresor, ki potrebuje 50ur delovanja, preden postane delovanje tekoče in se poraba električne energije ustali.
OPOMBA
Enoto VEDNO poganjajte s termistorji in/ali tlačnimi tipali/stikali. Če tega NE boste naredili, lahko kompresor pregori.

12.3 Seznam preverjanj pred zagonom

Vodnik za monterja
58
OPOMBA
VEDNO dokončajte cevovod za hladivo, preden zaženete enoto. Če tega NE boste naredili, se bo kompresor pokvaril.
Po namestitvi enote najprej preverite elemente s seznama. Ko preverite vse elemente, je treba enoto zapreti. Zaganjanje enote po zaprtju.
2(A)MXM40+50 + 2(A)MXF40+50
R32 serija split
4P600463-3D – 2021.03
12 | Zagon
Notranja enota je pravilno nameščena.
Zunanja enota je pravilno nameščena.
Sistem je pravilno ozemljen in ozemljitvene priključne sponke so čvrsto pritrjene.
Napajalna napetost mora ustrezati napetosti, navedeni na identifikacijski nalepki enote.
Spoji v stikalniomarici NISO zrahljani in električni sestavni deli NISO poškodovani.
Sestavni deli v notranji in zunanji enoti NISO poškodovani in cevi NISO stisnjene.
Hladivo NE uhaja.
Cevi za hladivo (plinasto in tekoče) so toplotno izolirane.
Montirane so cevi ustrezne velikosti, cevi so tudi primerno izolirane.
Zaporna ventila na zunanji enoti (za plin in tekočino) sta popolnoma odprta.
Kondenzat
Prepričajte se, da kondenzat nemoteno odteka.
Možna posledica: Vodni kondenzat bi lahko kapljal.
Notranja enota sprejema signale z uporabniškega vmesnika.
Za kabelske povezave med enotami so uporabljeni predpisani kabli.
Varovalke, prekinjala vezij ali lokalno nameščene zaščitne naprave so nameščene v skladu s tem dokumentom in NISO premoščene.
Preverite, ali se oznake (prostor A~E) na ožičenju in ceveh ujemajo za vsako notranjo enoto.
Preverite, ali je nastavitev prednosti prostorov nastavljena za 2 ali več prostorov. Ne pozabite, da generator DHW za multi ali Hybrid za multi ne sme biti izbran kot glavni prostor.

12.4 Seznam preverjanj med zagonom

Preverite ožičenje.
Odzračevanje
Izvajanje testnega zagona

12.5 Preizkus delovanja

2(A)MXM40+50 + 2(A)MXF40+50 R32 serija split 4P600463-3D – 2021.03
Pred zagonom preizkusa delovanja izmerite napetost na primarni strani varnostnega
odklopnika.
Cevi in ožičenje se ujemajo.
Zaporna ventila na zunanji enoti (za plin in tekočino) sta popolnoma odprta.
Inicializacija multi-sistema lahko traja nekaj minut, odvisno od števila notranjih enot in uporabljenih možnosti.
Vodnik za monterja
59
12 | Zagon

12.5.1 Izvajanje testnega zagona

Predpogoj: Napajanje MORA biti v navedenem območju. Predpogoj: Preizkus delovanja je mogoče izvesti v načinu hlajenja ali ogrevanja. Predpogoj: Preizkus mora biti izveden v skladu s priročnikom za delovanje notranje
enote, da zagotovite, da pravilno delujejo vse funkcije in vsi deli.
1 V načinu hlajenje izberite najnižjo temperaturo, ki jo lahko nastavite. V načinu
ogrevanje izberite najvišjo temperaturo, ki jo lahko nastavite.
2 Izmerite temperaturo na vhodu in izhodu notranje enote, ko enota deluje
približno 20minut. Razlika mora biti več od 8°C (hlajenje) ali 15°C (ogrevanje).
3 Najprej preverite delovanje vsake enote posebej, nato preverite sočasno
delovanje vseh notranjih enot. Preverite delovanje ogrevanja in hlajenja.
4 Ko je preizkus delovanja končan, temperaturo nastavite na normalno
vrednost. V načinu hlajenje: 26~28°C, v načinu ogrevanje: 20~24°C.
INFORMACIJA
Preizkus delovanja je mogoče onemogočiti, če je to potrebno.Ko enoto izključite, je 3 minute ni mogoče spet zagnati.Med hlajenjem se lahko na zapornem ventilu za plin ali drugimi deli pojavi
zasreženost. To je normalno.
INFORMACIJA
Tudi če je enota izključena, troši elektriko.Ko je po izpadu elektrike spet vzpostavljeno napajanje, se bo vključil prej izbrani

12.6 Zagon zunanje enote

Glejte priročnik za montažo notranje enote za konfiguracijo in začetek uporabe za sistem.
način delovanja.
Vodnik za monterja
60
2(A)MXM40+50 + 2(A)MXF40+50
R32 serija split
4P600463-3D – 2021.03

13 Izročitev uporabniku

Ko se testni zagon konča in enota pravilno deluje, preverite in potrdite naslednje točke za uporabnika:
Preverite, ali je uporabnik prejel natisnjeno dokumentacijo, in ga prosite, da jo
shrani za uporabo v prihodnje. Uporabnika obvestite, da je celotna dokumentacija na voljo na spletnem naslovu, prej omenjenem v tem priročniku.
Uporabniku pojasnite pravilno uporabo sistema in kaj mora storiti, če se pojavijo
težave.
Pokažite uporabniku, kaj mora narediti za vzdrževanje enote.
13 | Izročitev uporabniku
2(A)MXM40+50 + 2(A)MXF40+50 R32 serija split 4P600463-3D – 2021.03
Vodnik za monterja
61
14 | Vzdrževanje in servisiranje

14 Vzdrževanje in servisiranje

14.1 Pregled: Vzdrževanje in servisiranje

V tem poglavju so informacije:
Varnostni ukrepi za vzdrževanjeVsakoletno vzdrževanje zunanje enote

14.2 Varnostni ukrepi za vzdrževanje

OPOMBA
Vzdrževanje MORA opraviti pooblaščen monter ali servisni zastopnik.
Priporočamo, da vzdrževanje izvedete vsaj enkrat letno. Je pa mogoče, da veljavna zakonodaja zahteva krajša vzdrževalna obdobja.
NEVARNOST: TVEGANJE SMRTI ZARADI ELEKTRIČNEGA UDARA
NEVARNOST: TVEGANJE ZA OŽGANINE/OPEKLINE
OPOMBA:Nevarnost izpraznitve elektrostatičnega naboja
Pred izvajanjem vzdrževalnih ali servisnih del se dotaknite kovinskega dela enote, da bi odvedli statično elektriko in tako zaščitili tiskano vezje.
OPOZORILO
Preden pričnete z izvajanjem vzdrževanja ali popravila, vedno izklopite odklopnik
na napajalni plošči, odstranite varovalke oz. odprite zaščitne naprave enote.
Ne dotikajte se delujočih delov 10 min po izključitvi napajanja, saj obstaja
možnost visoke napetosti.
Pazite, ker je nekaj delov električne omarice izjemno vročih.Pazite, da se ne boste dotaknili prevodnega dela.NE izpirajte enote. To bi lahko povzročilo električni udar ali požar.

14.3 Seznam preverjanj za letno vzdrževanje zunanje enote

Vodnik za monterja
62
Naslednje točke preverite vsaj enkrat letno:
Izmenjevalnik toplote
Izmenjevalnik toplote zunanje enote se lahko zamaši zaradi prahu, umazanije, listov itd. Priporočamo, da izmenjevalnik toplote očistite letno. Zamašen izmenjevalnik toplote lahko povzroči prenizek ali previsok tlak, kar vodi v poslabšanje zmogljivosti.
2(A)MXM40+50 + 2(A)MXF40+50
R32 serija split
4P600463-3D – 2021.03

14.4 O kompresorju

Pri servisiranju kompresorja upoštevajte naslednja varnostna priporočila:
14 | Vzdrževanje in servisiranje
NEVARNOST: TVEGANJE SMRTI ZARADI ELEKTRIČNEGA UDARA
Kompresor uporabljajte le v ozemljenem sistemu.Izključite napajanje pred servisiranjem.Spet pritrdite pokrov stikalne omarice in servisni pokrov po servisiranju.
OPOMIN
vedno uporabljajte zaščitna očala in rokavice.
NEVARNOST: NEVARNOST EKSPLOZIJE
Uporabite cevni rezalnik, da bi odstranili kompresor.NE uporabljajte plamenskega spajkalnika.Uporabite le odobrena hladiva in maziva.
NEVARNOST: TVEGANJE ZA OŽGANINE/OPEKLINE
Kompresorja se Ne dotikajte z golimi rokami.
2(A)MXM40+50 + 2(A)MXF40+50 R32 serija split 4P600463-3D – 2021.03
Vodnik za monterja
63
15 | Odpravljanje težav

15 Odpravljanje težav

15.1 Pregled: Odpravljanje težav

15.2 Varnostni ukrepi pri odpravljanju težav

To poglavje opisuje, kaj morate narediti v primeru težav. Vsebuje informacije za reševanje težav na podlagi simptomov.
Pred odpravljanjem težav
Preglejte stikalno omarico in pri tem iščite očitne okvare, kot so zrahljane povezave ali okvarjeno ožičenje.
OPOZORILO
Ko pregledujete stikalno omarico enote, VEDNO preverite, ali je enota
odklopljena iz omrežnega napajanja. Izklopite ustrezen odklopnik.
Če se je aktivirala varnostna naprava, zaustavite enoto in ugotovite vzrok za njeno
aktiviranje, preden jo ponastavite. NIKOLI ne zaobidite varnostnih naprav in ne spreminjajte njihovih vrednosti na vrednost, ki se razlikuje od tovarniške nastavitve. Če ne morete ugotoviti vzroka težave, pokličite svojega prodajalca.
NEVARNOST: TVEGANJE SMRTI ZARADI ELEKTRIČNEGA UDARA
OPOZORILO
Preprečite nevarnosti zaradi nehotene ponastavitve termičnega odklopa: napajanje te naprave NE SME biti izvedeno preko zunanjega preklopnika, denimo časovnika, in naprava ne sme biti priključena na tokokrog, ki ga vzdrževanje redno vklaplja in izklaplja.
NEVARNOST: TVEGANJE ZA OŽGANINE/OPEKLINE

15.3 Reševanje težav na podlagi simptomov

15.3.1 Simptom: Notranje enote padajo, vibrirajo ali oddajajo zvoke

Možni vzroki Rešitev
Notranje enote niso varno nameščene Varno namestite notranje enote.

15.3.2 Simptom: Enota NE ogreva oziroma ne hladi po pričakovanjih

Vodnik za monterja
64
Možni vzroki Rešitev
Nepravilne povezave električnih kablov Pravilno povežite električne kable.
Puščanje plina Preverite, ali kje pušča plin.
2(A)MXM40+50 + 2(A)MXF40+50
R32 serija split
4P600463-3D – 2021.03
15 | Odpravljanje težav
Možni vzroki Rešitev
Oznake na ožičenju in ceveh se ne ujemajo

15.3.3 Simptom: Iztekanje vode

Možni vzroki Rešitev
Nepravilna termoizolacija (cevi za plin in tekočino, notranji deli podaljška gibljive odtočne cevi)
Nepravilno priključen odtok Zavarujte odtok.

15.3.4 Simptom: Električno puščanje

Možni vzroki Rešitev
Enota NI pravilno ozemljena Preverite in popravite povezavo

15.3.5 Simptom: Enota NE deluje ali ožganine

Oznake na ožičenju in ceveh (prostor A, prostor B, prostor C, prostor D, prostor E) za vsako notranjo enoto se MORAJO ujemati.
Prepričajte se, da sta termoizolacija cev in gibljive odtočne cevi popolnoma izdelani.
ozemljitvenega vodnika.
Možni vzroki Rešitev
Ožičenje NI bilo izvedeno v skladu s
Popravite ožičenje.
specifikacijo

15.4 Reševanje težav glede na to, kako svetijo svetleče diode

15.4.1 Diagnosticiranje napak s svetlečo diodo na tiskanem vezju zunanje enote

Svetleča dioda Diagnoza
utripa Običajno.
Preverite delovanje notranje enote.
Vključen Izključite in vključite napajanje in v času 3 minut še
enkrat preverite svetlečo diodo. Če sveti, je prišlo do okvare na tiskanem vezju.
Izključeno 1 Napetost napajanja (zaradi varčevanja z energijo).
2 Težave so z napajanjem. 3 Izključite in vključite napajanje in v času 3 minut še
enkrat preverite svetlečo diodo. Če je dioda spet ugasnila, je prišlo do okvare na tiskanem vezju zunanje enote.
2(A)MXM40+50 + 2(A)MXF40+50 R32 serija split 4P600463-3D – 2021.03
Vodnik za monterja
65
15 | Odpravljanje težav
NEVARNOST: TVEGANJE SMRTI ZARADI ELEKTRIČNEGA UDARA
Ko enota ne deluje, so svetleče diode na tiskanem vezju izključene zaradi
varčevanja z energijo.
Tudi ko so svetleče diode izključene, sta priključna sponka in tiskano vezje lahko
pod napetostjo.
Vodnik za monterja
66
2(A)MXM40+50 + 2(A)MXF40+50
R32 serija split
4P600463-3D – 2021.03

16 Odstranjevanje

OPOMBA
Sistema nikar NE poskušajte razstaviti sami: razstavljanje sistema, delo s hladivom,
oljem in drugimi deli MORA biti izvedeno v skladu z zadevno zakonodajo. Enote je
treba obravnavati v specializiranem obratu za ponovno uporabo in reciklažo.

16.1 Pregled: odstranjevanje

Običajen potek
Odstranjevanje sistema običajno obsega naslednje faze:
1 Izčrpavanje sistema. 2 Odvoz sistema v poseben obrat za obdelavo.
INFORMACIJA
Za več podrobnosti glejte priročnik za servisiranje.
16 | Odstranjevanje

16.2 Izčrpavanje

Primer: Zaradi zaščite okolja morate pred prestavljanjem ali odstranjevanjem enote opraviti izčrpavanje.
NEVARNOST: NEVARNOST EKSPLOZIJE
Izčrpavanje – Puščanje hladiva. Če želite sistem izčrpati in nekje na tokokrogu
hladilnega sredstva pušča:
NE uporabljajte funkcije za samodejno izčrpavanje na enoti, s katero lahko
zberete vse hladivo iz sistema v zunanji enoti. Možna posledica: Samoizgorevanje in eksplozija kompresorja zaradi zraka, ki pride v delujoč kompresor.
Uporabite ločen sistem za izčrpavanje, tako da kompresorju enote NI treba
delovati.
OPOMBA
Med izčrpavanjem zaustavite kompresor, preden odstranjujete cevi za hladivo. Če
kompresor še vedno deluje in je zaporni ventil med izčrpavanjem odprt, se bo v
sistem vsesal zrak. Posledica so lahko okvara kompresorja in poškodbe sistema zaradi
neobičajnega tlaka v krogu hladiva.
Med izčrpavanjem se bo vse hladivo izločilo iz sistema v zunanjo enoto.
1 Odstranite pokrov z zapornega ventila za tekočino in zapornega ventila za plin.
2(A)MXM40+50 + 2(A)MXF40+50 R32 serija split 4P600463-3D – 2021.03
2 Izvedite postopek prisilnega hlajenja. Glejte "16.3 Zagon in zaustavitev
prisilnega hlajenja"[468].
3 Po 5 do 10minutah (po samo 1 do 2minutah, če so zunanje temperature zelo
nizke (<−10°C)), zaprite zaporni ventil za tekočino s šestkotnim ključem.
4 Na manometru preverite, ali je dosežen vakuum. 5 Po 2–3minutah zaprite plinski zaporni ventil in zaustavite prisilno hlajenje.
Vodnik za monterja
67
16 | Odstranjevanje
a
c
b
d
d
e

16.3 Zagon in zaustavitev prisilnega hlajenja

a Zaporni ventil za plin b Smer zapiranja
c Šestrobi ključ d Čep ventila e Zaporni ventil za tekočino
Obstajata 2načina za izvajanje prisilnega hlajenja.
1. način. S stikalom ON/OFF na notranji enoti (če je nameščeno na notranji
enoti).
2. način. Z uporabniškim vmesnikom notranje enote.

16.3.1 Da bi zagnali in zaustavili prisilno hlajenje s stikalom za vklop/izklop na notranji enoti

1 Pritisnite stikalo ON/OFF in ga držite vsaj 5sekund.
Rezultat: Naprava se vklopi.
INFORMACIJA
Prisilno hlajenje se bo samodejno zaustavilo po 15minutah.
2 Da bi prej zaustavili delovanje, pritisnite stikalo ON/OFF.

16.3.2 Da bi zagnali in zaustavili prisilno hlajenje z uporabniškim vmesnikom notranje enote

1 Nastavite način delovanja na hlajenje. Glejte poglavje "Da bi izvedli preizkus
delovanja" v priročniku za montažo notranje enote.
Vodnik za monterja
68
2(A)MXM40+50 + 2(A)MXF40+50
R32 serija split
4P600463-3D – 2021.03

17 Tehnični podatki

,
A
INDOOR
OUTDOOR
Povzetek najnovejših tehničnih podatkov je na voljo na regionalni Daikin spletni
strani (javno dostopna).
Popolni tehnični podatki so na voljo na Daikin Business Portal (zahtevana
avtentikacija).

17.1 Vezalna shema

17.1.1 Poenotena legenda za vezalno shemo

Za uporabljene dele in oštevilčevanje glejte shemo povezav na enoti. Oštevilčevanje delov se izvede z arabskimi številkami naraščajoče za vsak del in je v spodnji preglednici predstavljeno s "*" kodo dela.
Simbol Pomen Simbol Pomen
Prekinjalo vezja Zaščitna ozemljitev
17 | Tehnični podatki
Povezava Ozemljitvena zaščita (vijak)
Konektor
Pretvornik
Ozemljitev Priključek za rele
Zunanje ožičenje Priključek kratkega stika
Varovalka Priključna sponka
Notranja enota Povezavna letvica
Zunanja enota Žična sponka
Naprava za tokovni ostanek
Simbol Barva Simbol Barva
BLK Črna ORG Oranžna
BLU Modra PNK Rožnata
BRN Rjava PRP, PPL Vijolična
GRN Zelena RED Rdeča
GRY Siva WHT Bela
2(A)MXM40+50 + 2(A)MXF40+50 R32 serija split 4P600463-3D – 2021.03
YLW Rumena
Simbol Pomen
A*P Ploščica s tiskanim vezjem
BS* Gumb ON/OFF, stikalo za delovanje
BZ, H*O Brenčač
C* Kondenzator
Vodnik za monterja
69
17 | Tehnični podatki
Simbol Pomen
AC*, CN*, E*, HA*, HE*, HL*, HN*, HR*,
Povezava, priključek MR*_A, MR*_B, S*, U, V, W, X*A, K*R_*, NE
D*, V*D Dioda
DB* Premostitev diode
DS* DIP-stikalo
E*H Grelnik
FU*, F*U, (za lastnosti glejte tiskano
Varovalka vezje v vaši enoti)
FG* Priključek (ozemljitev okvirja)
H* Varovalni pas
H*P, LED*, V*L Pilotska lučka, svetlobna dioda
HAP Svetlobna dioda (servisni monitor -
zelena)
HIGH VOLTAGE Visoka napetost
IES Tipalo Intelligent-eye
IPM* Inteligentni napajalni modul
K*R, KCR, KFR, KHuR, K*M Magnetni rele
L Napetostni vodnik
L* Tuljava
L*R Reaktanca
M* Koračni motor
M*C Motor kompresorja
M*F Motor ventilatorja
M*P Motor črpalke za odtok
M*S Nihajni motor
MR*, MRCW*, MRM*, MRN* Magnetni rele
N Nevtralna
n=*, N=* Število prehodov skozi feritno jedro
PAM Modulacija amplitude pulziranja
PCB* Ploščica s tiskanim vezjem
PM* Napajalni modul
PS Preklopno napajanje
Vodnik za monterja
70
PTC* Termistor PTC
Q* Bipolarni tranzistor izoliranih vrat (IGBT)
Q*C Prekinjalo vezja
Q*DI, KLM Zemljostični odklopnik
Q*L Preobremenitvena zaščita
2(A)MXM40+50 + 2(A)MXF40+50
R32 serija split
4P600463-3D – 2021.03
17 | Tehnični podatki
Simbol Pomen
Q*M Termično stikalo
Q*R Naprava za tokovni ostanek
R* Upor
R*T Termistor
RC Sprejemnik
S*C Omejevalno stikalo
S*L Stikalo s plovcem
S*NG Zaznavalo puščanja hladiva
S*NPH Tlačno tipalo (visoki tlak)
S*NPL Tlačno tipalo (nizki tlak)
S*PH, HPS* Tlačno stikalo (visoki tlak)
S*PL Tlačno stikalo (nizki tlak)
S*T Termostat
S*RH Senzor vlažnosti
S*W, SW* Stikalo za delovanje
SA*, F1S Pretokovni zaustavljalnik
SR*, WLU Sprejemnik signala
SS* Izbirno stikalo
SHEET METAL Montažna ploščica povezavne letvice
T*R Transformator
TC, TRC Oddajnik
V*, R*V Varistor
V*R Premostitev diode, Napajalni modul
bipolarnega tranzistorja izoliranih vrat (IGBT)
WRC Brezžični daljinski upravljalnik
X* Priključna sponka
X*M Povezavna letvica (blok)
Y*E Navitje elektronskega ekspanzijskega
ventila
Y*R, Y*S Tuljava obračalnega elektromagnetnega
ventila

17.2 Shema napeljave cevi: zunanja enota

2(A)MXM40+50 + 2(A)MXF40+50 R32 serija split 4P600463-3D – 2021.03
Z*C Feritno jedro
ZF, Z*F Protišumni filter
Kategorija za klasifikacijo komponente PED:
Visokotlačna stikala: kategorija IV
Vodnik za monterja
71
17 | Tehnični podatki
7.9CuT
7.9CuT
M
4.8CuT
4.8CuT
9.5CuT
7.9CuT
9.5CuT
9.5CuT
9.5CuT
9.5CuT
9.5CuT
6.4CuT
6.4CuT
EV
A
EV
B
9.5CuT
6.4CuT
6.4CuT
6.4CuT
9.5CuT
9.5CuT
HPS1
9.5CuT
(9.5CuT)
(12.7CuT)
(6.4CuT)
(6.4CuT)
a
b
c
d
e
f
g
g
h
i
j
A
B
A
B
k
l
l
m
n
o
o
p
q
r
s
t
n
m
i
h
g
c
c
Kompresor: kategorija IIDruge komponente: glejte PED člen 4, odstavek 3
2MXM50, 2AMXM50, 2AMXF50, 2MXF50
A Prostor A B Prostor B
a 4-smerni ventil VKLJUČEN: ogrevanje b Visokotlačno stikalo s samodejno ponastavitvijo
c Dušilka d Termistor izpustne cevi e Kompresor
g Razvodna cev h Termistor (plin)
k Lokalne cevi (tekočina)
m Termistor (tekočina)
n Filter o Motorni ventil p Dušilka
f Akumulator
i Zaporni ventil za plin j Lokalne cevi (plin)
l Zaporni ventil za tekočino
q Termistor temperature zraka zunanje enote
r Izmenjevalnik toplote
M Motor ventilatorja
Pretok hladiva: hlajenje Pretok hladiva: ogrevanje
Vodnik za monterja
72
2(A)MXM40+50 + 2(A)MXF40+50
R32 serija split
4P600463-3D – 2021.03

18 Slovar

18 | Slovar
Prodajalec
Dobavitelj izdelka.
Pooblaščen monter
Tehnično usposobljena oseba, ki je kvalificirana za namestitev izdelka.
Uporabnik
Oseba, ki je lastnik izdelka in/ali izdelek uporablja.
Zadevna zakonodaja
Vse mednarodne, evropske, nacionalne in lokalne direktive, zakoni, predpisi in/ali pravilniki, ki se nanašajo na določen izdelek ali področje.
Servisno podjetje
Kvalificirano podjetje, ki lahko izvaja ali vodi potrebne servisne posege na izdelku.
Priročnik za montažo
Priročnik za namestitev za določen izdelek ali uporabo, ki podaja navodila za namestitev, nastavitev in vzdrževanje.
Priročnik za uporabo
Priročnik za določen izdelek ali uporabo, ki podaja navodila za uporabo.
Navodila za vzdrževanje
Priročnik za določen izdelek ali uporabo, ki podaja navodila za namestitev, nastavitev, uporabo in/ali vzdrževanje (če so upoštevna) za izdelek oziroma uporabo.
Oprema
Nalepke, priročniki, tehnični listi in oprema, priloženi izdelku ob dobavi, ki jih je treba namestiti v skladu z navodili v spremni dokumentaciji.
Opcijska oprema
Oprema, ki jo izdela ali odobri Daikin, in se lahko uporablja s tem izdelkom v skladu z navodili v spremni dokumentaciji.
Lokalna dobava
Oprema, ki je NE izdeluje Daikin in se lahko uporablja s tem izdelkom v skladu z navodili v spremni dokumentaciji.
2(A)MXM40+50 + 2(A)MXF40+50 R32 serija split 4P600463-3D – 2021.03
Vodnik za monterja
73
Verantwortung für Energie und Umwelt
Copyright 2021 Daikin
4P600463-3D 2021.03