Daikin 2MXM40M4V1B, 2MXM50M3V1B9, 2AMXM40M4V1B, 2AMXM50M4V1B, 2AMXF40A2V1B Installer reference guide [sl]

...
Vodnik za monterja
R32 serija split
2MXM40M4V1B 2MXM50M3V1B9 2AMXM40M4V1B 2AMXM50M4V1B 2AMXF40A2V1B 2AMXF50A2V1B 2MXF40A2V1B 2MXF50A2V1B
Vodnik za monterja
R32 serija split
Slovenščina

Vsebina

Vsebina
1 Splošni varnostni ukrepi 3
1.1 O dokumentaciji......................................................................... 3
1.1.1 Pomen opozoril in simbolov........................................ 3
1.2 Za monterja ............................................................................... 3
1.2.1 Splošno....................................................................... 3
1.2.2 Mesto namestitve........................................................ 3
1.2.3 Hladivo........................................................................ 5
1.2.4 Slanica ........................................................................ 6
1.2.5 Voda............................................................................ 6
1.2.6 Električna dela ............................................................ 6
2 O dokumentaciji 7
2.1 O tem dokumentu...................................................................... 7
2.2 Kratek pregled referenčnega vodnika za monterja.................... 7
3 O škatli 7
3.1 Pregled: O škatli ........................................................................ 7
3.2 Zunanja enota ........................................................................... 7
3.2.1 Razpakiranje zunanje enote ....................................... 7
3.2.2 Odstranjevanje opreme iz zunanje enote ................... 8
4 O enotah in opcijskih dodatkih 8
4.1 Pregled: O enotah in opcijskih dodatkih .................................... 8
4.2 Oznaka ...................................................................................... 8
4.2.1 Nazivna ploščica: zunanja enota ................................ 8
5 Priprava 8
5.1 Pregled: Priprava....................................................................... 8
5.2 Priprava mesta namestitve........................................................ 8
5.2.1 Zahteve za namestitveno mesto za zunanjo enoto..... 9
5.2.2 Dodatne zahteve za namestitveno mesto za zunanjo
enoto v hladnih predelih.............................................. 10
5.2.3 Dolžina cevi za hladivo in višinske razlike .................. 10
5.3 Priprava cevi za hladivo ............................................................ 10
5.3.1 Zahteve za cevi za hladivo.......................................... 10
5.3.2 Izolacija cevi za hladivo .............................................. 11
5.4 Priprava električnega ožičenja .................................................. 11
5.4.1 O pripravi električnega ožičenja.................................. 11
6 Montaža 11
6.1 Pregled: Montaža ...................................................................... 11
6.2 Odpiranje enote......................................................................... 11
6.2.1 O odpiranju enote ....................................................... 11
6.2.2 Odpiranje zunanje enote............................................. 11
6.3 Nameščanje zunanje enote....................................................... 12
6.3.1 O nameščanju zunanje enote ..................................... 12
6.3.2 Varnostni ukrepi pri nameščanju zunanje enote......... 12
6.3.3 Priprava montažne konstrukcije.................................. 12
6.3.4 Montaža zunanje enote............................................... 12
6.3.5 Priprava drenaže......................................................... 12
6.3.6 Preprečevanje prevračanja zunanje enote ................. 13
6.4 Povezovanje cevi za hladivo ..................................................... 13
6.4.1 O priključevanju cevi za hladivo.................................. 13
6.4.2 Varnostni ukrepi pri priključevanju cevi za hladivo...... 13
6.4.3 Navodila pri priključevanju cevi za hladivo.................. 14
6.4.4 Napotki za upogibanje cevi......................................... 14
6.4.5 Robljenje konca cevi................................................... 14
6.4.6 Povezave med zunanjo in notranjo enoto z
reducirnimi priključki.................................................... 14
6.4.7 Uporaba zapornega ventila in servisnega priključka... 15
6.4.8 Priključevanje cevi za hladivo na zunanjo enoto......... 16
6.5 Preverjanje cevi za hladivo........................................................ 16
6.5.1 O preverjanju cevi za hladivo...................................... 16
6.5.2 Napotki za varnost pri preverjanju cevi za hladivo...... 16
6.5.3 Preverjanje puščanja .................................................. 16
6.5.4 Vakuumsko praznjenje................................................ 16
6.6 Polnjenje s hladivom .................................................................. 17
6.6.1 O polnjenju s hladivom................................................. 17
6.6.2 Varnostni ukrepi pri polnjenju s hladivom .................... 17
6.6.3 O hladivu...................................................................... 17
6.6.4 Določanje dodatne količine hladiva.............................. 18
6.6.5 Določanje celotne količine ponovnega polnjenja ......... 18
6.6.6 Dolivanje dodatnega hladiva........................................ 18
6.6.7 Pritrjevanje nalepke o fluoriranih toplogrednih plinih ... 18
6.7 Priključevanje električnega ožičenja........................................... 18
6.7.1 O priključevanju električnega ožičenja......................... 18
6.7.2 Napotki za varnost pri priključevanju električnega
ožičenja........................................................................ 19
6.7.3 Napotki za priključevanje električnega ožičenja........... 19
6.7.4 Specifikacije standardnih komponent ožičenja ............ 20
6.7.5 Priključevanje električnega ožičenja na zunanjo
enoto ............................................................................ 20
6.8 Zaključevanje montaže zunanje enote ....................................... 20
6.8.1 Zaključevanje montaže zunanje enote......................... 20
6.8.2 O nastavitvi načina z omejitvijo ECONO...................... 21
6.8.3 O tihem nočnem načinu delovanja............................... 21
6.8.4 O načinu zaklepanja na ogrevanje............................... 21
6.8.5 O funkciji za varčevanje elektrike v stanju
pripravljenosti............................................................... 21
6.8.6 Zapiranje zunanje enote .............................................. 22
7 Zagon 22
7.1 Pregled: zagon ........................................................................... 22
7.2 Napotki za varnost pri zagonu.................................................... 22
7.3 Seznam preverjanj pred zagonom ............................................. 22
7.4 Seznam preverjanj med zagonom.............................................. 22
7.5 Preizkus delovanja ..................................................................... 23
7.5.1 Izvajanje testnega zagona ........................................... 23
7.6 Zagon zunanje enote.................................................................. 23
7.7 Diagnosticiranje napak s svetlečo diodo na tiskanem vezju
zunanje enote............................................................................. 23
8 Izročitev uporabniku 23 9 Vzdrževanje in servisiranje 23
9.1 Pregled: Vzdrževanje in servisiranje .......................................... 23
9.2 Varnostni ukrepi za vzdrževanje ................................................ 24
9.3 Seznam preverjanj za letno vzdrževanje zunanje enote ............ 24
9.4 O kompresorju............................................................................ 24
10 Odpravljanje težav 24
10.1 Pregled: Odpravljanje težav ....................................................... 24
10.2 Varnostni ukrepi pri odpravljanju težav ...................................... 24
10.3 Reševanje težav na podlagi simptomov ..................................... 24
10.3.1 Simptom: Notranje enote padajo, vibrirajo ali
oddajajo zvoke ............................................................. 24
10.3.2 Simptom: Enota NE ogreva oziroma ne hladi po
pričakovanjih ................................................................ 24
10.3.3 Simptom: Iztekanje vode.............................................. 24
10.3.4 Simptom: Električno puščanje...................................... 24
10.3.5 Simptom: Enota NE deluje ali ožganine....................... 25
11 Odstranjevanje 25
11.1 Pregled: odstranjevanje.............................................................. 25
11.2 Izčrpavanje ................................................................................. 25
11.3 Zagon in zaustavitev prisilnega hlajenja..................................... 25
11.3.1 Da bi zagnali in zaustavili prisilno hlajenje s stikalom
za vklop/izklop na notranji enoti ................................... 25
11.3.2 Da bi zagnali in zaustavili prisilno hlajenje z
uporabniškim vmesnikom notranje enote .................... 25
12 Tehnični podatki 25
12.1 Vezalna shema........................................................................... 25
12.1.1 Poenotena legenda za vezalno shemo........................ 25
12.2 Shema napeljave cevi: zunanja enota........................................ 26
13 Slovar 27
Vodnik za monterja
2
2(A)MXM40+50M(3)(4)V1B(9)_2(A)MXF40+50A2V1B
R32 serija split
4P600463-2 – 2019.10

1 Splošni varnostni ukrepi

1 Splošni varnostni ukrepi

1.1 O dokumentaciji

▪ Izvorna dokumentacija je pisana v angleščini. Dokumentacija v
drugih jezikih je prevod.
▪ Varnostni ukrepi, opisani v tem dokumentu, obravnavajo zelo
pomembne teme; skrbno se jih držite.
▪ Namestitev sistema in vse dejavnosti, opisane v priročniku za
montažo in v vodiču za inštalaterja, MORA izvesti kvalificiran inštalater.

1.1.1 Pomen opozoril in simbolov

NEVARNOST
Označuje situacijo, ki vodi v smrt in hude telesne poškodbe.
NEVARNOST: SMRTNA NEVARNOST ZARADI ELEKTRIČNEGA UDARA
Označuje situacijo, ki lahko povzroči smrt zaradi električnega udara.
NEVARNOST: NEVARNOST OPEKLIN IN OZEBLIN
Označuje situacijo, ki lahko povzroči opekline ali ozebline zaradi izredno visokih ali izredno nizkih temperatur.
NEVARNOST: NEVARNOST EKSPLOZIJE
Označuje situacijo, ki lahko povzroči eksplozijo.
OPOZORILO
Označuje situacijo, ki lahko povzroči smrt in hude telesne poškodbe.
OPOZORILO: VNETLJIV MATERIAL
POZOR
Označuje situacijo, ki lahko povzroči manjše ali srednje nevarne telesne poškodbe.
OPOMBA
Označuje situacijo, ki lahko povzroči poškodbe opreme ali lastnine.
INFORMACIJE
Označuje uporabne nasvete ali dodatne informacije.
Simbol Razlaga
Pred namestitvijo preberite navodila za montažo in uporabo ter shemo z navodili za ožičenje.
Preden začnete izvajati vzdrževalne in servisne postopke preberite priročnik za servisiranje.
Za več informacij glejte vodnik za monterja in uporabnika.

1.2 Za monterja

1.2.1 Splošno

Če NISTE prepričani, kako montirati ali upravljati enoto, se obrnite na svojega prodajalca.
OPOMBA
Nestrokovna montaža ali priklop naprave in opreme lahko povzroči električni udar, kratek stik, uhajanje tekočin ali požar ali drugače poškoduje napravo ali opremo. Uporabljajte samo dodatke, opcijsko opremo in nadomestne dele, ki jih izdela ali odobri Daikin.
OPOZORILO
Montaža, preizkus in uporabljeni materiali morajo biti (razen z navodili, opisanimi v dokumentaciji Daikin) skladni tudi z veljavno zakonodajo.
POZOR
Pri nameščanju, vzdrževanju ali servisiranju sistema uporabljajte ustrezno osebno zaščitno opremo (zaščitne rokavice, varnostna očala…).
OPOZORILO
Raztrgajte in odvrzite plastične vreče, da se z njimi nihče ne bi mogel igrati, zlasti ne otroci. Možna nevarnost: zadušitev.
NEVARNOST: NEVARNOST OPEKLIN IN OZEBLIN
▪ NE dotikajte se cevi za hladivo, cevi za vodo in
notranjih delov med delovanjem ali neposredno po delovanju. Lahko so prevroči ali premrzli. Počakajte, da se njihova temperatura normalizira. Če se jih morate dotikati, si nadenite zaščitne rokavice.
▪ Z golo kožo se NE dotikajte ponesreči razlitega hladiva.
OPOZORILO
Z zagotavljanjem primernih ukrepov preprečite, da bi enota postala zavetišče za majhne živali. Majhne živali, ki se dotaknejo električnih delov, lahko povzročijo okvare, dim ali požar.
POZOR
Ne dotikajte se odprtine za vstop zraka ali aluminijastih platic enote.
OPOMBA
▪ Na vrh enote NE postavljajte predmetov ali opreme. ▪ NE sedite na napravi, ne plezajte nanjo in ne stojte na
njej.
OPOMBA
Dela na zunanji enoti je najbolje opraviti v suhem vremenu, da bi se izognili vdoru vode.
V skladu z zadevno zakonodajo bo treba morda skupaj z izdelkom priskrbeti dnevnik, v katerem se beležijo najmanj: podatki o vzdrževanju, popravila, rezultati testov, obdobja pripravljenosti…
Najmanj naslednje informacije MORAJO biti zagotovljene na dostopnem mestu izdelka:
▪ Navodila za izklop sistema v nujnem primeru ▪ Naziv in naslov gasilske službe, policije in bolnišnice ▪ Ime, naslov ter dnevna in nočna telefonska številka za servis Potrebne smernice za tak dnevnik za Evropo podaja standard
EN378.

1.2.2 Mesto namestitve

▪ Zagotovite dovolj prostora okoli enote za servisiranje in kroženje
zraka.
▪ Prepričajte se, da mesto namestitve prenese težo in vibracije
enote.
2(A)MXM40+50M(3)(4)V1B(9)_2(A)MXF40+50A2V1B R32 serija split 4P600463-2 – 2019.10
Vodnik za monterja
3
1 Splošni varnostni ukrepi
Contains fluorinated greenhouse gases
2
1
1
1
2
2
kg
tCO2eq
1000
GWP × kg
=
=
+
kg
=
kg
=
GWP: xxx
R32
0
10
20
30
40
50
60
70
80
90
100
110
120
130
140
150
160
170
180
190
200
210
220
230
240
250
260
270
280
290
300
310
320
330
340
350
360
370
380
390
400
410
420
430
440
450
460
470
480
490
500
510
520
530
540
550
1.822.2
2.4
2.6
2.833.2
3.4
3.6
3.844.2
4.4
4.6
4.855.2
5.4
5.6
5.866.2
6.4
6.6
6.877.2
7.4
7.6
7.8
1.843 7.956
8.0
A
min
(m2)
Floor-standing unit
(c)
Wall-mounted unit
(b)
Ceiling-mounted unit
(a)
m (kg)
▪ Prepričajte se, da je območje dobro prezračeno. NE blokirajte
prezračevalnih odprtin. ▪ Pazite, da bo enota izravnana. Enote NE nameščajte na naslednja mesta: ▪ V potencialno eksplozivnem okolju. ▪ Na mestih, kjer so stroji, ki oddajajo elektromagnetne valove.
Elektromagnetni valovi lahko motijo krmilni sistem in lahko
povzročijo okvare na opremi. ▪ Na mestih, kjer obstaja nevarnost požara zaradi uhajanja vnetljivih
plinov (primer: razredčilo ali bencin), ogljikovih vlaken ali
vnetljivega prahu. ▪ Na mestih, kjer nastajajo korozivni plini (primer: kisli žvepleni plin).
Zaradi korozije bakrenih cevi ali zvarov bi lahko začelo puščati
hladivo.
Navodila za opremo, ki uporablja hladivo R32
Če se uporablja.
OPOZORILO
▪ NE prebadajte in ne zažigajte. ▪ NE uporabite sredstev in načinov za pospeševanje
odmrzovanja ali čiščenja opreme, razen tistih, ki jih priporoča proizvajalec.
▪ Bodite pozorni na to, da je R32 BREZ vonja.
OPOZORILO
Naprava mora biti skladiščena tako, da se prepreči mehanske poškodbe, in v dobro prezračenem prostoru, kjer ni neprestano prisotnih virov vžiga (na primer: odprtega plamena, delujoče naprave na plin ali delujočega električnega grelnika). Poleg tega mora biti prostor v izmeri, navedeni v nadaljevanju.
Da bi določili najmanjšo potrebno kvadraturo prostora
1 Izračunajte skupno količino hladiva v sistemu (= tovarniška
polnitev hladiva + dolito hladivo).
2 Določite, kateri grafikon ali tabelo uporabiti.
▪ Za notranje enote: Je enota nameščena na strop, na steno
ali stoji na tleh?
▪ Za zunanje enote, nameščene ali skladiščene v notranjih
prostorih, in za cevovode v neprezračenih prostorih, je kvadratura odvisna od višine namestitve:
Če je višina namestitve… Uporabite grafikon ali tabelo
za…
<1,8m Stoječe enote 1,8≤x<2,2m Enote, nameščene na steno ≥2,2m Enote, nameščene na strop
3 Uporabite grafikon ali tabelo za določanje minimalne kvadrature
prostora.
OPOMBA
▪ Spojev, ki so že bili uporabljeni, NE uporabljajte znova. ▪ Spoji, ki so bili narejeni na inštalaciji med deli
hladilnega sistema, morajo biti dostopni za vzdrževanje.
OPOZORILO
Prepričajte se, da so namestitev, servisiranje, vzdrževanje in popravila izvedeni v skladu z navodili Daikin in v skladu z veljavno zakonodajo (na primer predpisom o plinu) in da jih izvajajo pooblaščene osebe.
Zahteve namestitve po prostoru
OPOMBA
▪ Cevovod mora biti zaščiten pred fizičnimi poškodbami. ▪ Cevi mora biti najmanj, kar je mogoče.
OPOZORILO
Če je v napravah hladivo R32, MORA biti kvadratura prostora, v katerega se namešča, v katerem deluje ali je skladiščena naprava, večja od najmanjše kvadrature prostora, določene v spodnji tabeli A (m2). To velja za:
▪ Notranje enote brez tipala za puščanje hladiva; v
primeru notranjih enot s tipalom za puščanje hladiva glejte priročnik za montažo
▪ Zunanje enote, nameščene ali skladiščene v notranjih
prostorih (npr. zimski vrt, garaža, strojnica)
▪ Cevovode v neprezračenih prostorih
Vodnik za monterja
4
2(A)MXM40+50M(3)(4)V1B(9)_2(A)MXF40+50A2V1B
R32 serija split
4P600463-2 – 2019.10
1 Splošni varnostni ukrepi
Ceiling-mounted
unit
(a)
4.6 13.4
4.6 180
4.8 14.6
4.8 196
5.0 15.8
5.0 213
≤1.842
5.2 17.1
≤1.842
5.2 230
1.843 3.64
5.4 18.5
1.843 28.9
5.4 248
2.0 3.95
5.6 19.9
2.0 34.0
5.6 267
2.2 4.34
5.8 21.3
2.2 41.2
5.8 286
2.4 4.74
6.0 22.8
2.4 49.0
6.0 306
2.6 5.13
6.2 24.3
2.6 57.5
6.2 327
2.8 5.53
6.4 25.9
2.8 66.7
6.4 349
3.0 5.92
6.6 27.6
3.0 76.6
6.6 371
3.2 6.48
6.8 29.3
3.2 87.2
6.8 394
3.4 7.32
7.0 31.0
3.4 98.4
7.0 417
3.6 8.20
7.2 32.8
3.6 110
7.2 441
3.8 9.14
7.4 34.7
3.8 123
7.4 466
4.0 10.1
7.6 36.6
4.0 136
7.6 492
4.2 11.2
7.8 38.5
4.2 150
7.8 518
4.4 12.3
7.956 40.1
4.4 165
7.956 539
m (kg)
A
min
(m2)
4.6 20.0
4.8 21.8
5.0 23.6
≤1.842
5.2 25.6
1.843 4.45
5.4 27.6
2.0 4.83
5.6 29.7
2.2 5.31
5.8 31.8
2.4 5.79
6.0 34.0
2.6 6.39
6.2 36.4
2.8 7.41
6.4 38.7
3.0 8.51
6.6 41.2
3.2 9.68
6.8 43.7
3.4 10.9
7.0 46.3
3.6 12.3
7.2 49.0
3.8 13.7
7.4 51.8
4.0 15.1
7.6 54.6
4.2 16.7
7.8 57.5
4.4 18.3
7.956 59.9
Wall-mounted
unit
(b)
m (kg)
A
min
(m2)
Floor-standing
unit
(c)
m (kg)
A
min
(m2)
NEVARNOST: NEVARNOST EKSPLOZIJE Izčrpavanje – Puščanje hladiva. Če želite sistem izčrpati
in nekje na tokokrogu hladilnega sredstva pušča:
▪ NE uporabljajte funkcije za samodejno izčrpavanje na
enoti, s katero lahko zberete vse hladivo iz sistema v zunanji enoti. Možna posledica: Samoizgorevanje in eksplozija kompresorja zaradi zraka, ki pride v delujoč kompresor.
▪ Uporabite ločen sistem za izčrpavanje, tako da
kompresorju enote NI treba delovati.
OPOZORILO
Hladivo VEDNO zberite. NE izpuščajte jih neposredno v okolje. Uporabite vakuumsko črpalko, da boste izpraznili napeljavo.
OPOMBA
Ko so vse cevi priključene, se prepričajte, da plin ne uhaja. S pomočjo dušika preverite, ali plin uhaja.
OPOMBA
▪ Preprečevanje okvare kompresorja, NE dolijte več
hladiva, kot je navedeno v specifikaciji.
▪ Kadar je treba sistem hladiva odpreti, morate s
hladivom ravnati v skladu z zadevno zakonodajo.
m Skupna polnitev hladiva v sistemu
A
Najmanjša kvadratura prostora
min
(a) Ceiling-mounted unit (= Enota, nameščena na stropu) (b) Wall-mounted unit (= Enota, nameščena na steni) (c) Floor-standing unit (= Stoječi tip enote)

1.2.3 Hladivo

Če se uporablja. Za več informacij glejte priročnik za montažo ali referenčni vodnik za monterja za vašo uporabo.
OPOMBA
Napeljava cevi mora biti skladna z veljavno zakonodajo. Zadevni standard za Evropo je EN378.
OPOMBA
Poskrbite, da zunanje cevi in priključki NE bodo obremenjeni.
OPOZORILO
Med testiranjem v izdelku NIKOLI ne smete vzpostaviti tlaka, višjega od maksimalnega dovoljenega tlaka (ki je naveden na nazivni ploščici enote).
OPOZORILO
Izvedite varnostne ukrepe, če pride do puščanja hladiva. Če hladilni plin uhaja, nemudoma prezračite prostor. Možne nevarnosti:
▪ Previsoka koncentracija hladiva v zaprtem prostoru
lahko povzroči pomanjkanje kisika.
▪ Če pride hladilni plin v stik z ognjem, se lahko tvorijo
strupeni plini.
2(A)MXM40+50M(3)(4)V1B(9)_2(A)MXF40+50A2V1B R32 serija split 4P600463-2 – 2019.10
OPOZORILO
Pazite, da v sistemu ni kisika. Hladivo lahko natočite šele, ko opravite preizkus tesnjenja in vakuumsko praznjenje.
▪ Če je to potrebno, preverite napisno ploščico na enoti. Na njej sta
navedena tip hladiva in potrebna količina.
▪ Enota je tovarniško napolnjena s hladivom. Odvisno od velikosti in
dolžine cevi je treba v nekaterih sistemih dotočiti hladivo.
▪ Da bi zagotovili upornost tlaka in preprečili vdor drugih snovi v
sistem, uporabljajte samo orodje, zasnovano posebej za vrsto hladiva, uporabljeno v sistemu.
▪ Hladivo točite upoštevaje naslednje:
Če Potem
Je prisotna sifonska cev (tj., na jeklenki je oznaka “Liquid
Pri polnjenju mora biti jeklenka postavljena pokonci.
filling siphon attached” (pritrjena sifonska cev za tekoče hladivo))
Sifonska cev NI prisotna Pri polnjenju mora biti jeklenka
obrnjena na glavo.
▪ Počasi odprite vsebnike hladiva. ▪ Hladivo točite v tekočem stanju. Dodajanje hladiva v plinskem
stanju lahko onemogoči normalno delovanje.
POZOR
Ko je postopek dolivanja hladiva dokončan ali ga prekinete, takoj zaprite ventil rezervoarja za hladivo. Če se ventil NE zapre takoj, lahko preostanek tlaka napolni dodatno hladivo. Možna posledica: Nepravilna količina hladiva.
Vodnik za monterja
5
1 Splošni varnostni ukrepi

1.2.4 Slanica

Če se uporablja. Za več informacij glejte priročnik za montažo ali referenčni vodnik za monterja za vašo uporabo.
OPOZORILO
Izbira slanice MORA biti skladna z veljavno zakonodajo.
OPOZORILO
Izvedite varnostne ukrepe, če pride do puščanja slanice. Če slanica izteka, takoj prezračite območje in se obrnite na lokalnega prodajalca.
OPOZORILO
Temperatura okolja v notranjosti enote je lahko bistveno višja od temperature v prostoru, npr. 70°C. V primeru iztekanja slanice lahko vroči deli enote povzročijo nevarno situacijo.
OPOZORILO
Uporaba in namestitev sistema MORATA biti skladni z varnostnimi in okoljskimi previdnostnimi ukrepi, ki jih določa veljavna zakonodaja.

1.2.5 Voda

Če se uporablja. Za več informacij glejte priročnik za montažo ali referenčni vodnik za monterja za vašo uporabo.
OPOZORILO
▪ Uporabljajte LE bakrene vodnike. ▪ Pazite, da bodo električne napeljave ustrezale veljavni
zakonodaji.
▪ Vse lokalno ožičenje mora biti izvedeno skladno z
vezalno shemo, priloženo izdelku.
▪ NIKOLI ne stiskajte šopov kablov in pazite, da NE
pridejo v stik s cevmi ali z ostrimi robovi. Prepričajte se, da na priključne sponke ne pritiska nič z zunanje strani.
▪ Pazite, da boste zagotovo namestili ozemljitveni
vodnik. Ne ozemljujte naprave s pomočjo komunalne cevi, prenapetostnega odvodnika ali ozemljitve telefona. Nepopolna ozemljitev lahko povzroči električni šok.
▪ Zagotovo uporabite ločeno električno vezje. NIKOLI ne
delite vira napajanja z drugo napravo.
▪ Pazite, da boste zagotovo namestili zahtevane
varovalke ali prekinjala vezij.
▪ Zagotovo namestite odklopnik z uhajanjem toka. Če
tega ne storite, lahko pride do električnega udara ali požara.
▪ Ko nameščate zemljostično zaščito, pazite, da je
združljiva z inverterjem (odporna na visokofrekvenčne električne šume), da bi se izognili nepotrebnemu odpiranju zaščite.
OPOMBA
Kakovost vode mora ustrezati Direktivi EU 98/83ES.

1.2.6 Električna dela

NEVARNOST: SMRTNA NEVARNOST ZARADI ELEKTRIČNEGA UDARA
▪ Izklopite napajanje, preden odstranjujete pokrov
stikalne omarice, priklapljate električno ožičenje ali se dotikate električnih delov.
▪ Pred servisiranjem odklopite napajanje za več kot
1 minuto in izmerite napetost na priključkih kondenzatorjev glavnega tokokroga ali električnih sestavnih delih. Napetost MORA biti nižja od 50V DC, preden se lahko dotaknete električnih sestavnih delov. Za mesta priključkov glejte vezalno shemo.
▪ Električnih sestavnih delov se NE dotikajte z mokrimi
rokami.
▪ Enote NE puščajte brez nadzora, če ste z nje odstranili
servisni pokrov.
OPOZORILO
Če NI nameščeno, JE NUJNO v fiksno ožičenje namestiti glavno stikalo ali druge možnosti odklopa, ki imajo ločen stik na vseh polih in omogočajo popolni odklop v pogojih previsoke napetosti kategorijeIII.
POZOR
Ko priključujete napajalni kabel, je treba ozemljitev izvesti, preden so priključeni kabli za prenos toka. Ko izključujete napajalni kabel, najprej izključite tega in šele nato tudi kabel za ozemljitev. Dolžina vodnikov med oporo napajalnega kabla in samim prikjučnim blokom mora biti taka, da so napajalni vodniki napeti pred ozemljitvenim vodnikom, za primer, da bi se napajalni kabel snel z opore kabla.
OPOMBA
Varnostni ukrepi pri napeljavi napajalnih vodnikov:
▪ NE priključujte vodnikov različnih debelin na priključne
sponke napajanja (ohlapnost napajalnih vodnikov lahko povzroči neobičajno segrevanje).
▪ Pri priključevanju vodnikov enake debeline naredite
tako, kot je prikazano na sliki zgoraj.
▪ Za ožičenje uporabite predvideni napajalni vodnik in ga
trdno priključite, nato pa zavarujte, da bi preprečili, da se zunanja sila prenese na priključno ploščo.
▪ Uporabite ustrezen izvijač za privijanje vijakov na
priključku. Izvijač z malim nastavkom lahko poškoduje glavo vijaka in onemogoči ustrezno zategovanje.
▪ S premočnim zategovanjem lahko vijake na priključkih
polomite.
Namestite napajalne kable vsaj 1 meter stran od televizijskih ali radijskih sprejemnikov, da bi se izognili motnjam. Odvisno od radijskih valov tudi 1meter lahko ni dovolj, da bi se preprečil šum.
Vodnik za monterja
6
2(A)MXM40+50M(3)(4)V1B(9)_2(A)MXF40+50A2V1B
R32 serija split
4P600463-2 – 2019.10

2 O dokumentaciji

OPOZORILO
▪ Ko zaključite napeljavo električnih kablov, se
prepričajte, da so vsi električni sestavni deli in vse priključne sponke v omarici z električnimi sestavnimi deli varno pritrjeni.
▪ Obvezno zaprite vse pokrove, preden zaženete enoto.
OPOMBA
Velja samo, če je napajanje trifazno in je način zagona kompresorja VKLOP/IZKLOP.
Če obstaja možnost, da bi do obrnjene faze prišlo po trenutnem izpadu in se napajanje vklaplja in izklaplja med delovanjem izdelka, priključite vezje za zaščito pred obrnjeno fazo lokalno. Delovanje izdelka z obrnjeno fazo lahko povzroči okvaro kompresorja in drugih delov.
2 O dokumentaciji

2.1 O tem dokumentu

Ciljni prejemniki
Pooblaščeni monterji
INFORMACIJE
Uporaba naprave je predvidena za strokovnjake oziroma usposobljene uporabnike v delavnicah, v manj zahtevnem industrijskem okolju ter na kmetijah oziroma za nestrokovnjake v poslovnem okolju in gospodinjstvih.
OPOZORILO
Prepričajte se, da so materiali za namestitev, servisiranje, vzdrževanje, popravila in sploh uporabljeni materiali v skladu z navodili iz Daikin ter da se skladajo z ustrezno zakonodajo in da so vsa našteta dejanja izvedle kvalificirane osebe. V Evropi in na območjih, kjer so v uporabi standardi IEC, je ustrezen standard EN/IEC 60335-2-40.
Komplet dokumentacije
Ta dokument je del kompleta dokumentacije. Celotno dokumentacijo sestavljajo:
Splošni varnostni ukrepi:
▪ Varnostna navodila, ki jih morate prebrati pred montažo ▪ Format: Papirni izvod (v škatli zunanje enote)
Priročnik za montažo zunanje enote:
▪ Navodila za montažo ▪ Format: Papirni izvod (v škatli zunanje enote)
Vodnik za monterja:
▪ Priprava za namestitev, referenčni podatki … ▪ Format: Digitalne datoteke na naslovu http://
www.daikineurope.com/support-and-manuals/product­information/
V območnem spletnem mestu Daikin ali pri vašem prodajalcu so morda na voljo najnovejše posodobitve priložene dokumentacije.
Izvorna dokumentacija je pisana v angleščini. Dokumentacija v drugih jezikih je prevod.
Tehnično-inženirski podatki
Povzetek najnovejših tehničnih podatkov je na voljo na regionalni
Daikin spletni strani (javno dostopna).
Popolni tehnični podatki so na voljo na Daikin Business Portal
(zahtevana avtentikacija).

2.2 Kratek pregled referenčnega vodnika za monterja

Poglavje Opis
Splošni varnostni ukrepi Varnostna navodila, ki jih morate
prebrati pred montažo
O dokumentaciji Katera dokumentacija obstaja za
monterja
O škatli Kako odpakirati enote in odstraniti vse
njihove dodatke O enoti Kako prepoznati enoto Priprava Kaj je treba narediti in vedeti pred
odhodom na mesto namestitve Montaža Kaj je treba narediti in vedeti za
nameščanje sistema Zagon Kaj je treba narediti in vedeti za
primopredajo sistema, ko je ta
nastavljen Izročitev uporabniku Kaj predati in kaj razložiti uporabniku Vzdrževanje in
servisiranje Odpravljanje težav Kaj narediti, če se pojavijo težave Odstranjevanje Kako zavreči sistem Tehnični podatki Specifikacije sistema Pojmovnik Opredelitev terminov
Kako vzdrževati in servisirati enote

3 O škatli

3.1 Pregled: O škatli

To poglavje opisuje, kaj morate storiti ob dobavi paketov z zunanjo in notranjo enoto na mesto montaže.
Vedno imejte v mislih naslednje: ▪ Ob dobavi je treba enoto NUJNO pregledati glede poškodb.
Vsako poškodbo MORATE takoj sporočiti prevoznikovemu agentu.
▪ Enoto postavite še zapakirano čim bližje mestu montaže, da bi
preprečili morebitne poškodbe med premikanjem.
▪ Vnaprej pripravite pot, po kateri nameravate vnesti enoto v
prostor.

3.2 Zunanja enota

3.2.1 Razpakiranje zunanje enote

2(A)MXM40+50M(3)(4)V1B(9)_2(A)MXF40+50A2V1B R32 serija split 4P600463-2 – 2019.10
Vodnik za monterja
7

4 O enotah in opcijskih dodatkih

1
2
c d e f g
h
a b
4 O enotah in opcijskih
dodatkih

4.1 Pregled: O enotah in opcijskih dodatkih

To poglavje vsebuje naslednje informacije: ▪ Prepoznavanje zunanje enote

4.2 Oznaka

OPOMBA
Če sočasno nameščate ali servisirate več enot, NE smete zamenjati servisnih plošč med različnimi modeli.

4.2.1 Nazivna ploščica: zunanja enota

Mesto

3.2.2 Odstranjevanje opreme iz zunanje enote

1 Dvignite zunanjo enoto.
POZOR
Z zunanjo enoto ravnajte samo v skladu z naslednjim:
2 Odstranite opremo iz spodnjega dela embalaže.
a Priročnik za montažo zunanje enote b Splošni varnostni ukrepi c Nalepka z informacijo o toplogrednih fluoriranih plinih d Večjezična nalepka z informacijo o toplogrednih fluoriranih
plinih
e Odvodna pipa
f Vrečka z vijaki (za pritrditev zadrževalnika žice) g Sestav reduktorja h Nalepka z informacijami o energiji

5 Priprava

5.1 Pregled: Priprava

To poglavje opisuje, kaj je treba narediti in vedeti, preden greste na mesto namestitve.
V njem so informacije o: ▪ Priprava mesta namestitve ▪ Priprava cevi za hladivo ▪ Priprava električnega ožičenja

5.2 Priprava mesta namestitve

Enote NE nameščajte na mesta, ki so pogosto v uporabi kot delovna mesta. Če morate izvajati tudi gradbene posege (npr. brušenje, razbijanje zidov itd.), pri katerih nastaja veliko prahu, MORATE enoto pokriti.
Izberite namestitveno mesto, ki omogoča dovolj prostora za prenos enote na mesto namestitve in z njega.
▪ Izberite mesto, kjer izpihovani vroči/hladni zrak ali hrup delovanja
enote NE bo motil nikogar.
OPOZORILO
Ne nameščajte klimatske naprave, kjer lahko pride do puščanja vnetljivega plina. Če začne plin uhajati in se zadrži okoli klimatske naprave, lahko pride do požara.
Vodnik za monterja
8
2(A)MXM40+50M(3)(4)V1B(9)_2(A)MXF40+50A2V1B
R32 serija split
4P600463-2 – 2019.10
▪ Namestite enote, napajalne kable in ožičenje za prenos vsaj 3m
(mm)
>50
a
b
>100
<1200
a
b
(mm)
>100
>50
b
a
>150
>50
b
a
(mm)
>150
>50
>300
b
a
>250
>300
(mm)
b
a
b
c
stran od televizijskih ali radijskih sprejemnikov, da bi se izognili motnjam. Odvisno od radijskih valov tudi 3m lahko niso dovolj, da bi se preprečil šum.
▪ Predmete pod enoto lahko poškoduje voda iz odtočne pipe.
OPOZORILO
Če je v napravah hladivo R32, mora biti kvadratura
prostora, v katerega se namešča, v katerem deluje ali je
skladiščena naprava, večja od najmanjše kvadrature
prostora. To velja za:
▪ Notranje enote brez tipala za puščanje hladiva; v
primeru notranjih enot s tipalom za puščanje hladiva glejte priročnik za montažo
▪ Zunanje enote, nameščene ali skladiščene v notranjih
prostorih (npr. zimski vrt, garaža, strojnica)
▪ Napeljava zunanjih cevi v neprezračenih prostorih
OPOZORILO
Napravo je treba hraniti v prostoru, v katerem ni
neprekinjeno delujočih virov vžiga (kot so odprti plameni,
delujoča plinska naprava ali delujoči električni grelnik).

5.2.1 Zahteve za namestitveno mesto za zunanjo enoto

INFORMACIJE
Preberite tudi naslednje zahteve:
▪ Splošne zahteve za namestitveno mesto. Glejte
poglavje “Splošni napotki za varnost”.
▪ Zahteve za cevi za hladivo (dolžina, višinska razlika).
Glejte nadaljevanje v tem poglavju “Priprava”.
Upoštevajte naslednja prostorska navodila: ▪ Stena z ene strani:
5 Priprava
OPOMBA
▪ Enot NE nameščajte eno na drugo. ▪ Enote NE obešajte na strop.
Močni vetrovi (≥18 km/h), ki pihajo proti izpustu zraka na zunanji enoti, povzročajo skrajšanje delovnega cikla (vsesavanje izpustnega zraka). Posledice so lahko:
▪ poslabšanje delovne zmogljivosti; ▪ pogosta hitra zaledenitev pri ogrevanju; ▪ motnje v delovanju zaradi padca nizkega tlaka, ali povečanja
visokega tlaka;
▪ lomljenje ventilatorja (če močan veter neprekinjeno piha v
ventilator, se ventilator lahko začne vrteti zelo hitro, dokler se ne polomi).
Če je izstop zraka izpostavljen vetru, priporočamo, da namestite pregrado.
Priporočamo, da zunanjo enoto namestite tako, da bo vstop zraka obrnjen proti steni in NE neposredno izpostavljen vetru.
▪ Stena z dveh strani:
▪ Stena s treh strani:
a Izstop zraka b Dovod za zrak
Ustvarite 300 mm delovnega prostora pod stropom in 250 mm za servisiranje cevi in električnih povezav.
2(A)MXM40+50M(3)(4)V1B(9)_2(A)MXF40+50A2V1B R32 serija split 4P600463-2 – 2019.10
a Pregrada b Pretežna smer vetra c Izstop zraka
Enote NE nameščajte na naslednja mesta: ▪ Izogibajte se območjem, ki so občutljiva za zvok (npr. v bližini
spalnice), da hrup delovanja ne bi povzročal težav. Opomba: Če je zvok izmerjen v dejanskih pogojih namestitve, bo izmerjena vrednost zaradi okoljskega hrupa in odbojev zvoka morda višja od stopnje zvočnega tlaka, navedene v poglavju Zvočni spekter v knjižici s tehničnimi podatki.
INFORMACIJE
Raven zvočnega tlaka je manj kot 70dBA.
▪ Na mestih, kjer so lahko v atmosferi pare mineralnih olj, razpšeno
olje ali oljne pare. Plastični deli lahko propadejo in odpadejo ter povzročijo puščanje vode.
Enote NI priporočljivo nameščati na naslednjih mestih, saj to lahko skrajša življenjsko dobo enote:
▪ Kjer napetost močno niha ▪ V vozilih ali plovilih ▪ Kjer so prisotne kisle ali alkalne pare
Vodnik za monterja
9