Daikin FDXS09LVJU, FFQ12LVJU, FDXS12LVJU, FVXS12NVJU, FTXS12LVJU Service Manual

...
Service
Manual
2/3MXL-Q Series
SiUS121602E
[Applied Models] z Inverter Multi : Heat Pump
Multi-Split Type Air Conditioners
SiUS121602E
i Table of Contents
Multi-Split Type
Air Conditioners
2/3MXL-Q Series
zHeat Pump Indoor Unit
CTXS07LVJU FDXS09LVJU FVXS09NVJU FFQ09LVJU FTXS09LVJU FDXS12LVJU FVXS12NVJU FFQ12LVJU FTXS12LVJU CDXS15LVJU FVXS15NVJU FFQ15LVJU FTXS15LVJU CDXS18LVJU FVXS18NVJU FFQ18LVJU FTXS18LVJU
Outdoor Unit
2MXL18QMVJU 3MXL24QMVJU
SiUS121602E
Table of Contents ii
1. Safety Cautions.......................................................................................... vi
1.1 Warnings and Cautions Regarding Safety of Workers .................................vi
1.2 Warnings and Cautions Regarding Safety of Users................................... viii
2. Icons Used ................................................................................................. xi
Part 1 List of Functions ................................................................... 1
1. Functions.....................................................................................................2
Part 2 Specifications ....................................................................... 7
1. Indoor Unit...................................................................................................8
2. Outdoor Unit..............................................................................................13
Part 3 Printed Circuit Board Connector Wiring Diagram ..............15
1. Indoor Unit.................................................................................................16
1.1 CTXS07LVJU, FTXS09/12LVJU ................................................................ 16
1.2 FTXS15/18LVJU ........................................................................................ 18
1.3 FDXS09/12LVJU, CDXS15/18LVJU .......................................................... 20
1.4 FVXS09/12/15/18NVJU.............................................................................. 22
1.5 FFQ09/12/15/18LVJU ................................................................................ 24
2. Wired Remote Controller...........................................................................25
2.1 BRC1E71 ................................................................................................... 25
2.2 BRC1E72/73 .............................................................................................. 26
3. Wireless Remote Controller ......................................................................27
3.1 BRC7E830 ................................................................................................. 27
4. Outdoor Unit..............................................................................................28
Part 4 Functions and Control......................................................... 31
1. Functions for CTXS, FTXS, CDXS, FDXS, FVXS Series .........................32
1.1 Temperature Control .................................................................................. 32
1.2 Frequency Principle.................................................................................... 32
1.3 Airflow Direction Control (CTXS, FTXS, FVXS Series) .............................. 34
1.4 Fan Speed Control for Indoor Unit ............................................................. 37
1.5 Program Dry Operation .............................................................................. 38
1.6 Automatic Operation................................................................................... 39
1.7 Thermostat Control..................................................................................... 40
1.8 NIGHT SET Mode ...................................................................................... 41
1.9 ECONO Operation ..................................................................................... 41
1.10 INTELLIGENT EYE Operation (CTXS, FTXS Series) ................................ 42
1.11 Inverter POWERFUL Operation ................................................................. 43
1.12 Clock Setting .............................................................................................. 44
1.13 WEEKLY TIMER Operation (CTXS, FTXS, FVXS Series)......................... 45
1.14 Other Functions.......................................................................................... 51
2. Functions for FFQ Series ..........................................................................52
2.1 Drain Pump Control .................................................................................... 52
2.2 Thermostat Sensor in Remote Controller................................................... 54
SiUS121602E
iii Table of Contents
2.3 Freeze Prevention Control ......................................................................... 56
2.4 Hot Start Control (In Heating Operation Only)............................................ 57
3. Control Specification .................................................................................58
3.1 Thermistor Functions.................................................................................. 58
3.2 Mode Hierarchy .......................................................................................... 60
3.3 Frequency Control ...................................................................................... 61
3.4 Controls at Mode Changing/Start-up.......................................................... 63
3.5 Discharge Pipe Temperature Control......................................................... 64
3.6 Input Current Control .................................................................................. 65
3.7 Freeze-up Protection Control ..................................................................... 66
3.8 Heating Peak-cut Control ........................................................................... 66
3.9 Outdoor Fan Control................................................................................... 67
3.10 Liquid Compression Protection Function.................................................... 67
3.11 Defrost Control ........................................................................................... 68
3.12 Low Hz High Pressure Limit ....................................................................... 69
3.13 Electronic Expansion Valve Control ........................................................... 70
3.14 Malfunctions ............................................................................................... 75
Part 5 Remote Controller ...............................................................76
1. CTXS, FTXS Series ..................................................................................77
2. CDXS, FDXS Series .................................................................................79
3. FVXS Series..............................................................................................81
4. FFQ Series................................................................................................83
4.1 <BRC1E71> Wired Remote Controller....................................................... 83
4.2 <BRC1E72/73> Wired Remote Controller.................................................. 88
4.3 <BRC7E830> Wireless Remote Controller ................................................ 94
Part 6 Service Diagnosis................................................................ 95
1. General Problem Symptoms and Check Items .........................................97
2. Troubleshooting with LED .........................................................................98
2.1 Indoor Unit.................................................................................................. 98
2.2 Outdoor Unit ............................................................................................... 99
3. Service Diagnosis ...................................................................................100
3.1 CTXS, FTXS, CDXS, FDXS, FVXS Series .............................................. 100
3.2 FFQ Series ............................................................................................... 106
4. Code Indication on Remote Controller....................................................112
4.1 CTXS, FTXS, CDXS, FDXS, FVXS Series .............................................. 112
4.2 FFQ Series ............................................................................................... 112
4.3 Outdoor Unit ............................................................................................. 113
5. Troubleshooting for CTXS, FTXS, CDXS, FDXS, FVXS Series ............. 114
5.1 Indoor Unit PCB Abnormality ................................................................... 114
5.2 Freeze-up Protection Control/Heating Peak-cut Control .......................... 116
5.3 Fan Motor or Related Abnormality ........................................................... 117
5.4 Thermistor or Related Abnormality........................................................... 121
5.5 Signal Transmission Error (Between Indoor Unit and Outdoor Unit)........ 122
5.6 Unspecified Voltage (Between Indoor Unit and Outdoor Unit) ................. 124
SiUS121602E
Table of Contents iv
6. Troubleshooting for FFQ Series..............................................................125
6.1 Indoor Unit PCB Abnormality ................................................................... 125
6.2 Drain Level Control System Abnormality.................................................. 126
6.3 Fan Motor (AC Motor) or Related Abnormality ......................................... 127
6.4 Drain System Abnormality........................................................................ 128
6.5 Thermistor or Related Abnormality........................................................... 129
6.6 Remote Controller Thermistor Abnormality .............................................. 130
6.7 Signal Transmission Error
(Between Indoor Unit and Remote Controller) ......................................... 131
6.8 Signal Transmission Error
(Between MAIN Remote Controller and SUB Remote Controller) ........... 132
6.9 Field Setting Abnormality ......................................................................... 133
7. Troubleshooting for Outdoor Unit............................................................134
7.1 Refrigerant Shortage ................................................................................ 134
7.2 Low-voltage Detection or Over-voltage Detection.................................... 136
7.3 Wiring Error Check Unexecuted ............................................................... 138
7.4 Unspecified Voltage (Between Indoor Unit and Outdoor Unit)/
Anti-icing Control in Other Rooms............................................................ 139
7.5 Anti-icing Control for Indoor Unit .............................................................. 140
7.6 Outdoor Unit PCB Abnormality................................................................. 142
7.7 OL Activation (Compressor Overload) ..................................................... 143
7.8 Compressor Lock ..................................................................................... 145
7.9 DC Fan Lock ............................................................................................ 146
7.10 Input Overcurrent Detection ..................................................................... 147
7.11 Four Way Valve Abnormality.................................................................... 148
7.12 Discharge Pipe Temperature Control....................................................... 150
7.13 High Pressure Control in Cooling ............................................................. 151
7.14 Compressor Sensor System Abnormality ................................................ 152
7.15 Position Sensor Abnormality .................................................................... 154
7.16 CT or Related Abnormality ....................................................................... 156
7.17 Thermistor or Related Abnormality (Outdoor Unit) ................................... 158
7.18 Electrical Box Temperature Rise .............................................................. 160
7.19 Radiation Fin Temperature Rise .............................................................. 161
7.20 Output Overcurrent Detection .................................................................. 162
8. Check ......................................................................................................164
8.1 Thermistor Resistance Check .................................................................. 164
8.2 Indoor Fan Motor Connector Check ......................................................... 165
8.3 Hall IC Check ........................................................................................... 165
8.4 Power Supply Waveform Check............................................................... 166
8.5 Electronic Expansion Valve Check........................................................... 167
8.6 Four Way Valve Performance Check ....................................................... 168
8.7 Inverter Unit Refrigerant System Check................................................... 168
8.8 Inverter Analyzer Check ........................................................................... 169
8.9 Rotation Pulse Check on the Outdoor Unit PCB ...................................... 170
8.10 Installation Condition Check ..................................................................... 171
8.11 Discharge Pressure Check....................................................................... 171
8.12 Outdoor Fan System Check ..................................................................... 172
8.13 Main Circuit Short Check.......................................................................... 172
8.14 Capacitor Voltage Check.......................................................................... 173
SiUS121602E
v Table of Contents
8.15 Power Module Check ............................................................................... 174
Part 7 Trial Operation and Field Settings.................................... 175
1. Pump Down Operation............................................................................176
2. Wiring Error Check Function...................................................................177
3. Trial Operation ........................................................................................179
3.1 CTXS, FTXS, CDXS, FDXS, FVXS Series .............................................. 179
3.2 FFQ Series ............................................................................................... 181
4. Field Settings ..........................................................................................183
4.1 Outdoor Unit ............................................................................................. 183
4.2 CTXS, FTXS, CDXS, FDXS, FVXS Series .............................................. 185
4.3 FFQ Series ............................................................................................... 190
5. Silicone Grease on Power Transistor / Diode Bridge..............................197
Part 8 Appendix............................................................................198
1. Piping Diagrams......................................................................................199
1.1 Indoor Unit................................................................................................ 199
1.2 Outdoor Unit ............................................................................................. 201
2. Wiring Diagrams......................................................................................202
2.1 Indoor Unit................................................................................................ 202
2.2 Outdoor Unit ............................................................................................. 207
SiUS121602E Safety Cautions
vi
1. Safety Cautions
Be sure to read the following safety cautions before conducting repair work. After the repair work is complete, be sure to conduct a test operation to ensure that the equipment operates normally, and explain the cautions for operating the product to the customer.
Caution Items The caution items are classified into Warning and Caution. The Warning items are
especially important since death or serious injury can result if they are not followed closely. The
Caution items can also lead to serious accidents under some conditions if they are not
followed. Therefore, be sure to observe all the safety caution items described below.
Pictograms This symbol indicates an item for which caution must be exercised.
The pictogram shows the item to which attention must be paid.
This symbol indicates a prohibited action.
The prohibited item or action is shown in the illustration or near the symbol.
This symbol indicates an action that must be taken, or an instruction.
The instruction is shown in the illustration or near the symbol.
1.1 Warnings and Cautions Regarding Safety of Workers
Warning
Do not store equipment in a room with fire sources (e.g., naked flames, gas appliances, electric heaters).
Be sure to disconnect the power cable from the socket before disassembling equipment for repair.
Working on equipment that is connected to the power supply may cause an electrical shock. If it is necessary to supply power to the equipment to conduct the repair or inspect the circuits, do not touch any electrically charged sections of the equipment.
If refrigerant gas is discharged during repair work, do not touch the discharged refrigerant gas.
Refrigerant gas may cause frostbite.
When disconnecting the suction or discharge pipe of the compressor at the welded section, evacuate the refrigerant gas completely at a well-ventilated place first.
If there is gas remaining inside the compressor, the refrigerant gas or refrigerating machine oil discharges when the pipe is disconnected, and it may cause injury.
If refrigerant gas leaks during repair work, ventilate the area.
Refrigerant gas may generate toxic gases when it contacts flames.
Be sure to discharge the capacitor completely before conducting repair work.
The step-up capacitor supplies high-voltage electricity to the electrical components of the outdoor unit. A charged capacitor may cause an electrical shock.
Safety Cautions SiUS121602E
vii
Do not turn the air conditioner on or off by plugging in or unplugging the power cable.
Plugging in or unplugging the power cable to operate the equipment may cause an electrical shock or fire.
Be sure to wear a safety helmet, gloves, and a safety belt when working in a high place (more than 2 m).
Insufficient safety measures may cause a fall.
In case of R-32 / R-410A refrigerant models, be sure to use pipes, flare nuts and tools intended for the exclusive use with the R-32 / R-410A refrigerant.
The use of materials for R-22 refrigerant models may cause a serious accident, such as a damage of refrigerant cycle or equipment failure.
Do not mix air or gas other than the specified refrigerant (R-32 / R-410A / R-
22) in the refrigerant system.
If air enters the refrigerant system, an excessively high pressure results, causing equipment damage and injury.
Warning
Caution
Do not repair electrical components with wet hands.
Working on the equipment with wet hands may cause an electrical shock.
Do not clean the air conditioner with water.
Washing the unit with water may cause an electrical shock.
Be sure to provide an earth / grounding when repairing the equipment in a humid or wet place, to avoid electrical shocks.
Be sure to turn off the power switch and unplug the power cable when cleaning the equipment.
The internal fan rotates at a high speed, and may cause injury.
Be sure to conduct repair work with appropriate tools.
The use of inappropriate tools may cause injury.
Be sure to check that the refrigerating cycle section has cooled down enough before conducting repair work.
Working on the unit when the refrigerating cycle section is hot may cause burns.
SiUS121602E Safety Cautions
viii
1.2 Warnings and Cautions Regarding Safety of Users
Conduct welding work in a well-ventilated place.
Using a welder in an enclosed room may cause oxygen deficiency.
Caution
Warning
Do not store the equipment in a room with fire sources (e.g., naked flames, gas appliances, electric heaters).
Be sure to use parts listed in the service parts list of the applicable model and appropriate tools to conduct repair work. Never attempt to modify the equipment.
The use of inappropriate parts or tools may cause an electrical shock, excessive heat generation or fire.
If the power cable and lead wires are scratched or have deteriorated, be sure to replace them.
Damaged cable and wires may cause an electrical shock, excessive heat generation or fire.
Do not use a joined power cable or extension cable, or share the same power outlet with other electrical appliances, since it may cause an electrical shock, excessive heat generation or fire.
Be sure to use an exclusive power circuit for the equipment, and follow the local technical standards related to the electrical equipment, the internal wiring regulations, and the instruction manual for installation when conducting electrical work.
Insufficient power circuit capacity and improper electrical work may cause an electrical shock or fire.
Be sure to use the specified cable for wiring between the indoor and outdoor units.
Make the connections securely and route the cable properly so that there is no force pulling the cable at the connection terminals. Improper connections may cause excessive heat generation or fire.
When wiring between the indoor and outdoor units, make sure that the terminal cover does not lift off or dismount because of the cable.
If the cover is not mounted properly, the terminal connection section may cause an electrical shock, excessive heat generation or fire.
Do not damage or modify the power cable.
Damaged or modified power cables may cause an electrical shock or fire. Placing heavy items on the power cable, or heating or pulling the power cable may damage it.
Safety Cautions SiUS121602E
ix
Do not mix air or gas other than the specified refrigerant (R-32 / R-410A / R-
22) in the refrigerant system.
If air enters the refrigerant system, an excessively high pressure results, causing equipment damage and injury.
If the refrigerant gas leaks, be sure to locate the leaking point and repair it before charging the refrigerant. After charging the refrigerant, make sure that there is no leak.
If the leaking point cannot be located and the repair work must be stopped, be sure to pump-down, and close the service valve, to prevent refrigerant gas from leaking into the room. Refrigerant gas itself is harmless, but it may generate toxic gases when it contacts flames, such as those from fan type and other heaters, stoves and ranges.
When relocating the equipment, make sure that the new installation site has sufficient strength to withstand the weight of the equipment.
If the installation site does not have sufficient strength or the installation work is not conducted securely, the equipment may fall and cause injury.
Check to make sure that the power cable plug is not dirty or loose, then insert the plug into a power outlet securely.
If the plug is dusty or has a loose connection, it may cause an electrical shock or fire.
When replacing the coin battery in the remote controller, be sure to dispose of the old battery to prevent children from swallowing it.
If a child swallows the coin battery, see a doctor immediately.
Warning
Caution
Installation of a leakage breaker is necessary in some cases depending on the conditions of the installation site, to prevent electrical shocks.
Do not install the equipment in a place where there is a possibility of combustible gas leaks.
If combustible gas leaks and remains around the unit, it may cause a fire.
Check to see if parts and wires are mounted and connected properly, and if connections at the soldered or crimped terminals are secure.
Improper installation and connections may cause excessive heat generation, fire or an electrical shock.
If the installation platform or frame has corroded, replace it.
A corroded installation platform or frame may cause the unit to fall, resulting in injury.
SiUS121602E Safety Cautions
x
Check the earth / grounding, and repair it if the equipment is not properly earthed / grounded.
Improper earth / grounding may cause an electrical shock.
Be sure to measure insulation resistance after the repair, and make sure that the resistance is 1 M or higher.
Faulty insulation may cause an electrical shock.
Be sure to check the drainage of the indoor unit after the repair.
Faulty drainage may cause water to enter the room and wet the furniture and floor.
Do not tilt the unit when removing it.
The water inside the unit may spill and wet the furniture and floor.
Caution
Icons Used SiUS121602E
xi
2. Icons Used
The following icons are used to attract the attention of the reader to specific information.
Icon Type of
Information
Description
Warning
Warning A Warning is used when there is danger of personal injury.
Caution
Caution A Caution is used when there is danger that the reader, through
incorrect manipulation, may damage equipment, lose data, get an unexpected result or have to restart (part of) a procedure.
Note:
Note A Note provides information that is not indispensable, but may
nevertheless be valuable to the reader, such as tips and tricks.
Reference A Reference guides the reader to other places in this binder or in
this manual, where he/she will find additional information on a specific topic.
SiUS121602E
List of Functions 1
Part 1
List of Functions
1. Functions.....................................................................................................2
Functions SiUS121602E
2 List of Functions
1. Functions
Category Functions
CTXS07LVJU
FTXS09/12/15/18LVJU
Category Functions
CTXS07LVJU
FTXS09/12/15/18LVJU
Basic Functions
Inverter (with inverter power control)
zz
Health & Cleanliness
Air-purifying filter
Operation limit for cooling (°CDB) Photocatalytic deodorizing filter
Operation limit for cooling (°FDB)
Air-purifying filter with photocatalytic deodorizing function
——
Operation limit for heating (°CWB)
Operation limit for heating (°FWB)
Titanium apatite photocatalytic air-purifying filter
zz
PAM control
Compressor Oval scroll compressor Longlife filter (option)
Swing compressor Air filter (prefilter)
zz
Rotary compressor Wipe-clean flat panel
zz
Reluctance DC motor Washable grille
Comfortable Airflow
Power-airflow flap (horizontal blade) Filter cleaning indicator
Power-airflow dual flaps
zz
Good-sleep cooling operation
Power-airflow diffuser Timer WEEKLY TIMER operation
zz
Wide-angle louvers (vertical blades)
zz
24-hour ON/OFF TIMER
zz
Auto-swing (up and down)
zz
NIGHT SET mode
zz
Auto-swing (right and left)
zz
Worry Free (Reliability & Durability)
Auto-restart (after power failure)
zz
3-D airflow
zz
Self-diagnosis (R/C, LED)
zz
COMFORT AIRFLOW operation
zz
Wiring error check function
Comfort Control
Auto fan speed
zz
Anti-corrosion treatment of outdoor heat exchanger
——
Indoor unit quiet operation
zz
NIGHT QUIET mode (automatic) Flexibility Multi-split / split type compatible indoor
unit
z
OUTDOOR UNIT QUIET operation (manual)
zz
Flexible power supply correspondence
INTELLIGENT EYE operation
zz
High ceiling application
Quick warming function Chargeless
Hot-start function
zz
Either side drain (right or left)
zz
Automatic defrosting Power selection
Operation Automatic operation
zz
°F/°C changeover R/C temperature display (factory setting: °F)
zz
Program dry function
zz
Fan only
zz
Remote Control
5-room centralized controller (option)
zz
Lifestyle Convenience
New POWERFUL operation (non-inverter)
——
Remote control adaptor (normal open pulse contact) (option)
zz
Inverter POWERFUL operation
zz
Remote control adaptor (normal open contact) (option)
zz
Priority-room setting
COOL/HEAT mode lock DIII-NET compatible (adaptor) (option)
zz
HOME LEAVE operation Remote
Controller
Wireless
zz
ECONO operation
zz
Wired (option)
zz
Indoor unit ON/OFF button
zz
Signal receiving sign
zz
R/C with back light
zz
Temperature display
Note:
z
: Available
— : Not available
SiUS121602E Functions
List of Functions 3
Category Functions
FDXS09/12LVJU
CDXS15/18LVJU
Category Functions
FDXS09/12LVJU
CDXS15/18LVJU
Basic Functions
Inverter (with inverter power control)
zz
Health & Cleanliness
Air-purifying filter
Operation limit for cooling (°CDB) Photocatalytic deodorizing filter
Operation limit for cooling (°FDB)
Air-purifying filter with photocatalytic deodorizing function
——
Operation limit for heating (°CWB)
Operation limit for heating (°FWB)
Titanium apatite photocatalytic air-purifying filter
——
PAM control
Compressor Oval scroll compressor Longlife filter (option)
Swing compressor Air filter (prefilter)
zz
Rotary compressor Wipe-clean flat panel
Reluctance DC motor Washable grille
Comfortable Airflow
Power-airflow flap (horizontal blade) Filter cleaning indicator
Power-airflow dual flaps Good-sleep cooling operation
Power-airflow diffuser Timer WEEKLY TIMER operation
Wide-angle louvers (vertical blades) 24-hour ON/OFF TIMER
zz
Auto-swing (up and down) NIGHT SET mode
zz
Auto-swing (right and left) Worry Free
(Reliability & Durability)
Auto-restart (after power failure)
zz
3-D airflow Self-diagnosis (R/C, LED)
zz
COMFORT AIRFLOW operation Wiring error check function
Comfort Control
Auto fan speed
zz
Anti-corrosion treatment of outdoor heat exchanger
——
Indoor unit quiet operation
zz
NIGHT QUIET mode (automatic) Flexibility Multi-split / split type compatible indoor
unit
z
— OUTDOOR UNIT QUIET operation (manual)
zz
Flexible power supply correspondence
INTELLIGENT EYE operation High ceiling application
Quick warming function Chargeless
Hot-start function
zz
Either side drain (right or left)
Automatic defrosting Power selection
Operation Automatic operation
zz
°F/°C changeover R/C temperature display (factory setting: °F)
zz
Program dry function
zz
Fan only
zz
Remote Control
5-room centralized controller (option)
zz
Lifestyle Convenience
New POWERFUL operation (non-inverter)
——
Remote control adaptor (normal open pulse contact) (option)
zz
Inverter POWERFUL operation
zz
Remote control adaptor (normal open contact) (option)
zz
Priority-room setting
COOL/HEAT mode lock DIII-NET compatible (adaptor) (option)
zz
HOME LEAVE operation Remote
Controller
Wireless (option)
zz
ECONO operation
zz
Wired (option)
zz
Indoor unit ON/OFF button
zz
Signal receiving sign
zz
R/C with back light
zz
Temperature display
Note:
z
: Available
— : Not available
Functions SiUS121602E
4 List of Functions
Category Functions
FVXS09/12/15/18NVJU
Category Functions
FVXS09/12/15/18NVJU
Basic Functions
Inverter (with inverter power control)
z
Health & Cleanliness
Air-purifying filter
Operation limit for cooling (°CDB) Photocatalytic deodorizing filter
Operation limit for cooling (°FDB)
Air-purifying filter with photocatalytic deodorizing function
— Operation limit for heating (°CWB)
Operation limit for heating (°FWB)
Titanium apatite photocatalytic air-purifying filter
z
PAM control
Compressor Oval scroll compressor Longlife filter (option)
Swing compressor Air filter (prefilter)
z
Rotary compressor Wipe-clean flat panel
z
Reluctance DC motor Washable grille
Comfortable Airflow
Power-airflow flap (horizontal blade) Filter cleaning indicator
Power-airflow dual flaps Good-sleep cooling operation
Power-airflow diffuser Timer WEEKLY TIMER operation
z
Wide-angle louvers (vertical blades)
z
24-hour ON/OFF TIMER
z
Auto-swing (up and down)
z
NIGHT SET mode
z
Auto-swing (right and left) Worry Free
(Reliability & Durability)
Auto-restart (after power failure)
z
3-D airflow Self-diagnosis (R/C, LED)
z
COMFORT AIRFLOW operation Wiring error check function
Comfort Control
Auto fan speed
z
Anti-corrosion treatment of outdoor heat exchanger
— Indoor unit quiet operation
z
NIGHT QUIET mode (automatic) Flexibility Multi-split / split type compatible indoor unit
OUTDOOR UNIT QUIET operation (manual)
z
Flexible power supply correspondence
INTELLIGENT EYE operation High ceiling application
Quick warming function Chargeless
Hot-start function
z
Either side drain (right or left)
Automatic defrosting Power selection
Operation Automatic operation
z
°F/°C changeover R/C temperature display (factory setting: °F)
z
Program dry function
z
Fan only
z
Remote Control
5-room centralized controller (option)
z
Lifestyle Convenience
New POWERFUL operation (non-inverter)
Remote control adaptor (normal open pulse contact) (option)
z
Inverter POWERFUL operation
z
Remote control adaptor (normal open contact) (option)
z
Priority-room setting
COOL/HEAT mode lock DIII-NET compatible (adaptor) (option)
z
HOME LEAVE operation Remote
Controller
Wireless
z
ECONO operation
z
Wired (option)
Indoor unit ON/OFF button
z
Signal receiving sign
z
R/C with back light
z
Temperature display
Note:
z
: Available
— : Not available
SiUS121602E Functions
List of Functions 5
Category Functions
FFQ09/12/15/18LVJU
Category Functions
FFQ09/12/15/18LVJU
Basic Functions
Inverter (with inverter power control)
z
Health & Cleanliness
Air-purifying filter
Operation limit for cooling (°CDB) Photocatalytic deodorizing filter
Operation limit for cooling (°FDB)
Air-purifying filter with photocatalytic deodorizing function
— Operation limit for heating (°CWB)
Operation limit for heating (°FWB)
Titanium apatite photocatalytic air-purifying filter
— PAM control
Compressor Oval scroll compressor Longlife filter (option)
z
Swing compressor Air filter (prefilter)
Rotary compressor Wipe-clean flat panel
Reluctance DC motor Washable grille
z
Comfortable Airflow
Power-airflow flap (horizontal blade) Filter cleaning indicator
z
Power-airflow dual flaps Good-sleep cooling operation
Power-airflow diffuser Timer WEEKLY TIMER operation
z
2
Wide-angle louvers (vertical blades) 24-hour ON/OFF TIMER
Auto-swing (up and down)
z
72-hour ON/OFF TIMER
z
1
Auto-swing (right and left) NIGHT SET mode
3-D airflow Worry Free
(Reliability & Durability)
Auto-restart (after power failure)
z
COMFORT AIRFLOW operation Self-diagnosis (R/C, LED)
z
Comfort Control
Auto fan speed Wiring error check function
Indoor unit quiet operation
Anti-corrosion treatment of outdoor heat exchanger
— NIGHT QUIET mode (automatic)
OUTDOOR UNIT QUIET operation (manual) Flexibility Multi-split / split type compatible indoor unit
INTELLIGENT EYE operation Flexible power supply correspondence
Quick warming function High ceiling application
Hot-start function
z
Chargeless
Automatic defrosting Either side drain (right or left)
Operation Automatic operation
z
Power selection
Program dry function
z
°F/°C changeover R/C temperature display (factory setting: °F)
z
2
Fan only
z
Lifestyle Convenience
New POWERFUL operation (non-inverter)
Remote Control
5-room centralized controller (option)
Remote control adaptor (normal open pulse contact) (option)
— Inverter POWERFUL operation
Priority-room setting
Remote control adaptor (normal open contact) (option)
— COOL/HEAT mode lock
HOME LEAVE operation DIII-NET compatible (adaptor) (option)
z
ECONO operation Remote
Controller
Wireless (option)
z
Indoor unit ON/OFF button
z
1 Wired (option)
z
Signal receiving sign
z
1
R/C with back light
z
2
Temperature display
Note:
z
: Available
— : Not available
1: With wireless remote controller
2: With wired remote controller
Functions SiUS121602E
6 List of Functions
Category Functions
2MXL18QMVJU
3MXL24QMVJU
Category Functions
2MXL18QMVJU
3MXL24QMVJU
Basic Functions
Inverter (with inverter power control) zzHealth &
Cleanliness
Air-purifying filter
Operation limit for cooling (°CDB)
–10
~ 46
–10
~ 46
Photocatalytic deodorizing filter
Operation limit for cooling (°FDB)
14 ~
114.8
14 ~
114.8
Air-purifying filter with photocatalytic deodorizing function
——
Operation limit for heating (°CWB)
–25 ~
15.6
–25 ~
15.6
Titanium apatite photocatalytic air-purifying filter
——
Operation limit for heating (°FWB)
–13~ 60–13~
60
Longlife filter (option)
Air filter (prefilter)
PAM control
zz
Wipe-clean flat panel
Standby electricity saving Washable grille
Compressor Oval scroll compressor Filter cleaning indicator
Swing compressor
zz
Good-sleep cooling operation
Rotary compressor Timer WEEKLY TIMER operation
Reluctance DC motor
zz
24-hour ON/OFF timer
Comfortable Airflow
Power-airflow flap (horizontal blade) NIGHT SET mode
Power-airflow dual flaps Worry Free
(Reliability & Durability)
Auto-restart (after power failure)
Power-airflow diffuser Self-diagnosis (R/C, LED)
zz
Wide-angle louvers (vertical blades) Wiring error check function
zz
Auto-swing (up and down)
Anti-corrosion treatment of outdoor heat exchanger
zz
Auto-swing (right and left)
3-D airflow Flexibility
Multi-split / split type compatible indoor unit
——
COMFORT AIRFLOW operation
Comfort Control
Auto fan speed Flexible power supply correspondence
Indoor unit quiet operation High ceiling application
NIGHT QUIET mode (automatic)
zz
Chargeless
98.4 ft
(30 m)
131.2 ft
(40 m)
OUTDOOR UNIT QUIET operation (manual)
zz
Either side drain (right or left)
INTELLIGENT EYE operation Power selection
Quick warming function
zz
°F/°C changeover R/C temperature display (factory setting: °F)
——
Hot-start function
Automatic defrosting
zz
Remote Control
5-room centralized controller (option)
Operation Automatic operation
Remote control adaptor (normal open pulse contact) (option)
——
Program dry function
Fan only Remote control adaptor
(normal open contact) (option)
—— Lifestyle Convenience
New POWERFUL operation (non-inverter)
——
DIII-NET compatible (adaptor) (option)
Inverter POWERFUL operation Remote
Controller
Wireless
Priority-room setting
zz
Wired (option)
COOL/HEAT mode lock
zz
HOME LEAVE operation
ECONO operation
Indoor unit ON/OFF button
Signal receiving sign
R/C with back light
Temperature display
Note:
z
: Available
— : Not available
SiUS121602E
Specifications 7
Part 2
Specifications
1. Indoor Unit...................................................................................................8
2. Outdoor Unit..............................................................................................13
Indoor Unit SiUS121602E
8 Specifications
1. Indoor Unit
60 Hz, 208 - 230 V
Model
CTXS07LVJU
Cooling Heating
Rated Capacity 7 kBtu/h Class Front Panel Color Whit e
Airflow Rate
H
cfm
(m³/min)
332 (9.4) 350 (9.9) M 261 (7.4) 290 (8.2) L 194 (5.5) 233 (6.6) SL 145 (4.1) 219 (6.2)
Fan
Type Cross Flow Fan Motor Output W 23 Speed Steps 5 Steps, Quiet, Auto
Air Direction Control Right, Left, Horizontal, Downward Air Filter Removable, Washable, Mildew Proof Running Current (Rated) A 0.09 - 0.08 0.11 - 0.10 Power Consumption (Rated) W 18 - 18 21 - 21 Power Factor (Rated) % 96.2 - 97.8 91.8 - 91.3 Temperature Control Microcomputer Control Dimensions (H × W × D) in. (mm) 11-5/8 × 31-1/2 × 8-7/16 (295 × 800 × 215) Packaged Dimensions (H × W × D) in. (mm) 10-13/16 × 34-1/4 × 14-7/16 (274 × 870 × 366) Weight (Mass) Lbs (kg) 20 (9) Gross Weight (Gross Mass) Lbs (kg) 29 (13) Sound Pressure
Level
H / M / L / SL dB(A) 38 / 32 / 25 / 22 38 / 33 / 28 / 25
Sound Power Level dB 54 54 Heat Insulation Both Liquid and Gas Pipes
Piping Connections
Liquid in. (mm) φ
1/4 (φ 6.4)
Gas i n. ( mm) φ 3/8 (φ 9.5) Drain in. (mm) φ 5/8 (φ 16.0)
Drawing No. 3D075490
Model
FTXS09LVJU FTXS12LVJU
Cooling Heating Cooling Heating
Rated Capacity 9 kBtu/h Class 12 kBtu/h Class Front Panel Color White White
Airflow Rate
H
cfm
(m³/min)
381 (10.8) 420 (11.9) 403 (11.4) 438 (12.4) M 279 (7.9) 321 (9.1) 307 (8.7) 335 (9.5) L 194 (5.5) 233 (6.6) 205 (5.8) 240 (6.8) SL 145 (4.1) 219 (6.2) 155 (4.4) 212 (6.0)
Fan
Type Cross Flow Fan Cross Flow Fan Motor Output W 23 23 Speed Steps 5 Steps, Quiet, Auto 5 Steps, Quiet, Auto
Air Direction Control Right, Left, Horizontal, Downward Right, Left, Horizontal, Downward Air Filter Removable, Washable, Mildew Proof Removable, Washable, Mildew Proof Running Current (Rated) A 0.09 - 0.08 0.11 - 0.10 0.13 - 0.12 0.14 - 0.13 Power Consumption (Rated) W 18 - 18 21 - 21 26 - 26 28 - 28 Power Factor (Rated) % 96.2 - 97.8 91.8 - 91.3 96.2 - 94.2 96.2 - 93.6 Temperature Control Microcomputer Control Microcomputer Control Dimensions (H × W × D) in. (mm) 11-5/8 × 31-1/2 × 8-7/16 (295 × 800 × 215) 11-5/8 × 31-1/2 × 8-7/16 (295 × 800 × 215) Packaged Dimensions (H × W × D) in. (mm) 10-13/16 × 34-1/4 × 14-7/16 (274 × 870 × 366) 10-13/16 × 34-1/4 × 14-7/16 (274 × 870 × 366) Weight (Mass) Lbs (kg) 20 (9) 22 (10) Gross Weight (Gross Mass) Lbs (kg) 29 (13) 31 (14) Sound Pressure
Level
H / M / L / SL dB(A) 41 / 33 / 25 / 22 42 / 35 / 28 / 25 45 / 37 / 29 / 23 45 / 39 / 29 / 26
Sound Power Level dB 57 58 61 61 Heat Insulation Both Liquid and Gas Pipes Both Liquid and Gas Pipes
Piping Connections
Liquid in. (mm) φ 1/4 (φ 6.4) φ 1/4 (φ 6.4) Gas i n. ( mm) φ 3/8 (φ 9.5) φ 3/8 (φ 9.5) Drain in. (mm) φ 5/8 (φ 16.0) φ 5/8 (φ 16.0)
Drawing No. 3D075491 3D075492
Conversion Formulae
kcal/h = kW × 860
Btu/h = kW × 3412
cfm = m³/min × 35.3
SiUS121602E Indoor Unit
Specifications 9
60 Hz, 208 - 230 V
Model
FTXS15LVJU FTXS18LVJU
Cooling Heating Cooling Heating
Rated Capacity 15 kBtu/h Class 18 kBtu/h Class Front Panel Color White White
Airflow Rate
H
cfm
(m³/min)
568 (16.1) 593 (16.8) 583 (16.5) 625 (17.7) M 477 (13.5) 505 (14.3) 484 (13.7) 526 (14.9) L 385 (10.9) 417 (11.8) 385 (10.9) 431 (12.2) SL 360 (10.2) 371 (10.5) 360 (10.2) 399 (11.3)
Fan
Type Cross Flow Fan Cross Flow Fan Motor Output W 48 48 Speed Steps 5 Steps, Quiet, Auto 5 Steps, Quiet, Auto
Air Direction Control Right, Left, Horizontal, Downward Right, Left, Horizontal, Downward Air Filter Removable, Washable, Mildew Proof Removable, Washable, Mildew Proof Running Current (Rated) A 0.31 - 0.29 0.31 - 0.29 0.32 - 0.30 0.32 - 0.30 Power Consumption (Rated) W 38 - 38 38 - 38 38 - 38 38 - 38 Power Factor (Rated) % 58.9 - 57.0 58.9 - 57.0 57.1 - 55.1 57.1 - 55.1 Temperature Control Microcomputer Control Microcomputer Control Dimensions (H × W × D) in. (mm) 13-3/8 × 41-5/16 × 9-3/4 (340 × 1,050 × 248) 13-3/8 × 41-5/16 × 9-3/4 (340 × 1,050 × 248) Packaged Dimensions (H × W × D) in. (mm) 13 × 45-11/16 × 16-7/8 (331 × 1,160 × 429) 13 × 45-11/16 × 16-7/8 (331 × 1,160 × 429) Weight (Mass) Lbs (kg) 31 (14) 31 (14) Gross Weight (Gross Mass) Lbs (kg) 44 (20) 44 (20) Sound Pressure
Level
H / M / L / SL dB(A) 45 / 40 / 35 / 32 43 / 38 / 33 / 30 46 / 41 / 36 / 33 45 / 40 / 35 / 32
Sound Power Level dB 61 59 62 61 Heat Insulation Both Liquid and Gas Pipes Both Liquid and Gas Pipes
Piping Connections
Liquid in. (mm) φ 1/4 (φ 6.4) φ 1/4 (φ 6.4) Gas i n. ( mm) φ 1/2 (φ 12.7) φ 1/2 (φ 12.7) Drain in. (mm) φ 5/8 (φ 16.0) φ 5/8 (φ 16.0)
Drawing No. 3D075043 3D075044
Model
FDXS09LVJU FDXS12LVJU
Cooling Heating Cooling Heating
Rated Capacity 9 kBtu/h Class 12 kBtu/h Class External Static Pressure inAq (Pa) 0.12 (30) 0.12 (30)
Airflow Rate
H
cfm
(m³/min)
305 (8.6) 305 (8.6) 305 (8.6) 305 (8.6) M 280 (7.9) 280 (7.9) 280 (7.9) 280 (7.9) L 260 (7.4) 260 (7.4) 260 (7.4) 260 (7.4) SL 235 (6.7) 235 (6.7) 235 (6.7) 235 (6.7)
Fan
Type Sirocco Fan Sirocco Fan Motor Output W 62 62 Speed Steps 5 Steps, Quiet, Auto 5 Steps, Quiet, Auto
Air Filter Removable, Washable, Mildew Proof Removable, Washable, Mildew Proof Running Current (Rated) A 0.58 - 0.52 0.58 - 0.52 0.58 - 0.52 0.58 - 0.52 Power Consumption (Rated) W 72 - 72 72 - 72 72 - 72 72 - 72 Power Factor (Rated) % 59.7 - 60.2 59.7 - 60.2 59.7 - 60.2 59.7 - 60.2 Temperature Control Microcomputer Control Microcomputer Control Dimensions (H × W × D) in. (mm) 7-7/8 × 27-9/16 × 24-7/16 (200 × 700 × 620) 7-7/8 × 27-9/16 × 24-7/16 (200 × 700 × 620) Packaged Dimensions (H × W × D) in. (mm) 10-13/16 × 36-5/16 × 30-1/4 (274 × 923 × 768) 10-13/16 × 36-5/16 × 30-1/4 (274 × 923 × 768) Weight (Mass) Lbs (kg) 47 (21) 47 (21) Gross Weight (Gross Mass) Lbs (kg) 64 (29) 64 (29) Sound Pressure
Level
H / M / L dB(A) 35 / 33 / 31 35 / 33 / 31 35 / 33 / 31 35 / 33 / 31
Sound Power Level dB 51 51 51 51 Heat Insulation Both Liquid and Gas Pipes Both Liquid and Gas Pipes
Piping Connections
Liquid in. (mm) φ 1/4 (φ 6.4) φ 1/4 (φ 6.4) Gas i n. ( mm) φ 3/8 (φ 9.5) φ 3/8 (φ 9.5) Drain in. (mm) φ 25/32 (φ 20) φ 25/32 (φ 20)
Drawing No. 3D075493 3D075494
Conversion Formulae
kcal/h = kW × 860
Btu/h = kW × 3412
cfm = m³/min × 35.3
Indoor Unit SiUS121602E
10 Specifications
60 Hz, 208 - 230 V
Model
CDXS15LVJU CDXS18LVJU
Cooling Heating Cooling Heating
Rated Capacity 15 kBtu/h Class 18 kBtu/h Class External Static Pressure inAq (Pa) 0.16 (40) 0.16 (40)
Airflow Rate
H
cfm
(m³/min)
424 (12.0) 424 (12.0) 424 (12.0) 424 (12.0) M 388 (11.0) 388 (11.0) 388 (11.0) 388 (11.0) L 353 (10.0) 353 (10.0) 353 (10.0) 353 (10.0) SL 297 (8.4) 297 (8.4) 297 (8.4) 297 (8.4)
Fan
Type Sirocco Fan Sirocco Fan Motor Output W 130 130 Speed Steps 5 Steps, Quiet, Auto 5 Steps, Quiet, Auto
Air Filter Removable, Washable, Mildew Proof Removable, Washable, Mildew Proof Running Current (Rated) A 0.79 0.79 0.79 0.79 Power Consumption (Rated) W 172 172 172 172 Power Factor (Rated) % 94.4 94.4 94.4 94.4 Temperature Control Microcomputer Control Microcomputer Control Dimensions (H × W × D) in. (mm) 7-7/8 × 35-7/16 × 24-7/16 (200 × 900 × 620) 7-7/8 × 35-7/16 × 24-7/16 (200 × 900 × 620) Packaged Dimensions (H × W × D) in. (mm) 10-1/2 × 43-9/16 × 29-9/16 (266 × 1,106 × 751) 10-1/2 × 43-9/16 × 29-9/16 (266 × 1,106 × 751) Weight (Mass) Lbs (kg) 60 (27) 60 (27) Gross Weight (Gross Mass) Lbs (kg) 75 (34) 75 (34) Sound Pressure
Level
H / M / L / SL dB(A) 37 / 35 / 33 / 31 37 / 35 / 33 / 31 37 / 35 / 33 / 31 37 / 35 / 33 / 31
Heat Insulation Both Liquid and Gas Pipes Both Liquid and Gas Pipes
Piping Connections
Liquid in. (mm) φ 1/4 (φ 6.4) φ 1/4 (φ 6.4) Gas i n. ( mm) φ 1/2 (φ 12.7) φ 1/2 (φ 12.7) Drain in. (mm) VP20 (O.D. φ 1-1/32 (φ 26), I.D. φ 25/32 (φ 20)) VP20 (O.D. φ 1-1/32 (φ 26), I.D. φ 25/32 (φ 20))
Drawing No. C: 3D075721 C: 3D075722
Model
FVXS09NVJU FVXS12NVJU
Cooling Heating Cooling Heating
Rated Capacity 9 kBtu/h Class 12 kBtu/h Class Front Panel Color White White
Airflow Rate
H
cfm
(m³/min)
290 (8.2) 311 (8.8) 300 (8.5) 332 (9.4) M 230 (6.5) 244 (6.9) 237 (6.7) 258 (7.3) L 169 (4.8) 177 (5.0) 173 (4.9) 184 (5.2) SL 145 (4.1) 155 (4.4) 159 (4.5) 166 (4.7)
Fan
Type Turbo Fan Turbo Fan Motor Output W 12.3 13.4 Speed Steps 5 Steps, Quiet, Auto 5 Steps, Quiet, Auto
Air Direction Control Right, Left, Horizontal, Downward Right, Left, Horizontal, Downward Air Filter Removable, Washable, Mildew Proof Removable, Washable, Mildew Proof Running Current (Rated) A — Power Consumption (Rated) W — Power Factor (Rated) % — Temperature Control Microcomputer Control Microcomputer Control Dimensions (H × W × D) in. (mm) 23-5/8 × 27-9/16 × 8-1/4 (600 × 700 × 210) 23-5/8 × 27-9/16 × 8-1/4 (600 × 700 × 210) Packaged Dimensions (H × W × D) in. (mm) 27-3/8 × 30-15/16 × 11 (695 × 786 × 279) 27-3/8 × 30-15/16 × 11 (695 × 786 × 279) Weight (Mass) Lbs (kg) 31 (14) 31 (14) Gross Weight (Gross Mass) Lbs (kg) 40 (18) 40 (18) Sound Pressure
Level
H / M / L / SL dB(A) 38 / 32 / 26 / 23 38 / 32 / 26 / 23 39 / 33 / 27 / 24 39 / 33 / 27 / 24
Heat Insulation Both Liquid and Gas Pipes Both Liquid and Gas Pipes
Piping Connections
Liquid in. (mm) φ 1/4 (φ 6.4) φ 1/4 (φ 6.4) Gas i n. ( mm) φ 3/8 (φ 9.5) φ 3/8 (φ 9.5) Drain in. (mm) φ 13/16 (φ 20.0) φ 13/16 (φ 20.0)
Drawing No. 3D101722 3D101724
Conversion Formulae
kcal/h = kW × 860
Btu/h = kW × 3412
cfm = m³/min × 35.3
SiUS121602E Indoor Unit
Specifications 11
60 Hz, 208 - 230 V
Model
FVXS15NVJU FVXS18NVJU
Cooling Heating Cooling Heating
Rated Capacity 15 kBtu/h Class 18 kBtu/h Class Front Panel Color White White
Airflow Rate
H
cfm
(m³/min)
378 (10.7) 417 (11.8) 378 (10.7) 417 (11.8) M 325 (9.2) 357 (10.1) 325 (9.2) 357 (10.1) L 275 (7.8) 300 (8.5) 275 (7.8) 300 (8.5) SL 233 (6.6) 251 (7.1) 233 (6.6) 251 (7.1)
Fan
Type Turbo Fan Turbo Fan Motor Output W 23.3 23.3 Speed Steps 5 Steps, Quiet, Auto 5 Steps, Quiet, Auto
Air Direction Control Right, Left, Horizontal, Downward Right, Left, Horizontal, Downward Air Filter Removable, Washable, Mildew Proof Removable, Washable, Mildew Proof Running Current (Rated) A — Power Consumption (Rated) W — Power Factor (Rated) % — Temperature Control Microcomputer Control Microcomputer Control Dimensions (H × W × D) in. (mm) 23-5/8 × 27-9/16 × 8-1/4 (600 × 700 × 210) 23-5/8 × 27-9/16 × 8-1/4 (600 × 700 × 210) Packaged Dimensions (H × W × D) in. (mm) 27-3/8 × 30-15/16 × 11 (695 × 786 × 279) 27-3/8 × 30-15/16 × 11 (695 × 786 × 279) Weight (Mass) Lbs (kg) 31 (14) 31 (14) Gross Weight (Gross Mass) Lbs (kg) 40 (18) 40 (18) Sound Pressure
Level
H / M / L / SL dB(A) 44 / 40 / 36 / 32 45 / 40 / 36 / 32 44 / 40 / 36 / 32 45 / 40 / 36 / 32
Heat Insulation Both Liquid and Gas Pipes Both Liquid and Gas Pipes
Piping Connections
Liquid in. (mm) φ 1/4 (φ 6.4) φ 1/4 (φ 6.4) Gas i n. ( mm) φ 1/2 (φ 12.7) φ 1/2 (φ 12.7) Drain in. (mm) φ 13/16 (φ 20.0) φ 13/16 (φ 20.0)
Drawing No. 3D101718 3D094866
Model
FFQ09LVJU FFQ12LVJU
Cooling Heating Cooling Heating
Rated Capacity 9 kBtu/h Class 12 kBtu/h Class
Decoration Panel
Model BYFQ60B3W1 BYFQ60B3W1 Color White White Dimensions (H × W × D) 2-5/32 × 27-9/16 × 27-9/16 (55 × 700 × 700) 2-5/32 × 27-9/16 × 27-9/16 (55 × 700 × 700) Weight (Mass) Lbs (kg) 6 (2.7) 6 (2.7)
Airflow Rate
H
cfm
(m³/min)
318 (9.0) 318 (9.0) 353 (10.0) 353 (10.0)
L 230 (6.5) 230 (6.5) 230 (6.5) 230 (6.5)
Fan
Type Turbo Fan Turbo Fan Motor Output W 55 55 Speed Steps 2 Steps 2 Steps
Air Direction Control Horizontal, Downward Horizontal, Downward Running Current (Rated) A 0.44 0.38 0.47 0.42 Power Consumption (Rated) W 87 76 98 89 Power Factor % 85.8 87.0 91.3 91.8 Temperature Control Microcomputer Control Microcomputer Control Dimensions (H × W × D) in. (mm) 11-1/4 × 22-5/8 × 22-5/8 (285 × 575 × 575) 11-1/4 × 22-5/8 × 22-5/8 (285 × 575 × 575) Packaged Dimensions (H × W × D) in. (mm) 14-9/16 × 27-1/16 × 26-9/16 (370 × 687 × 674) 14-9/16 × 27-1/16 × 26-9/16 (370 × 687 × 674) Weight (Mass) Lbs (kg) 38.6 (17.5) 38.6 (17.5) Gross Weight (Gross Mass) Lbs (kg) 46 (21) 46 (21) Sound Pressure
Level
H / L dB(A) 36.0 / 29.5 36.0 / 29.5 38.5 / 29.0 38.5 / 29.0
Heat Insulation Both Liquid and Gas Pipes Both Liquid and Gas Pipes
Piping Connections
Liquid in. (mm)
φ
1/4
6.4
)
φ
1/4
(
φ
6.4
)
Gas i n. ( mm)
φ
3/8
(
φ
9.5)
φ
3/8
(
φ
9.5)
Drain in. (mm) VP20 (O.D.
φ
1-1/32
26) / I.D.
φ
25/32
20) VP20 (O.D.
φ
1-1/32
(
φ
26) / I.D.
φ
25/32
(
φ
20)
Drawing No. 3D080626A 3D080627A
Conversion Formulae
kcal/h = kW × 860
Btu/h = kW × 3412
cfm = m³/min × 35.3
Indoor Unit SiUS121602E
12 Specifications
60 Hz, 208 - 230 V
Model
FFQ15LVJU FFQ18LVJU
Cooling Heating Cooling Heating
Rated Capacity 15 kBtu/h Class 18 kBtu/h Class
Decoration Panel
Model BYFQ60B3W1 BYFQ60B3W1 Color White White Dimensions (H × W × D) 2-5/32 × 27-9/16 × 27-9/16 (55 × 700 × 700) 2-5/32 × 27-9/16 × 27-9/16 (55 × 700 × 700) Weight (Mass) Lbs (kg) 6 (2.7) 6 (2.7)
Airflow Rate
H
cfm
(m³/min)
424 (12.0) 424 (12.0) 530 (15.0) 530 (15.0) L 283 (8.0) 283 (8.0) 353 (10.0) 353 (10.0)
Fan
Type Turbo Fan Turbo Fan Motor Output W 55 55 Speed Steps 2 Steps 2 Steps
Air Direction Control Horizontal, Downward Horizontal, Downward Running Current (Rated) A 0.57 0.52 0.71 0.65 Power Consumption (Rated) W 112 103 140 130 Power Factor % 86.1 86.0 85.5 86.2 Temperature Control Microcomputer Control Microcomputer Control Dimensions (H × W × D) in. (mm) 11-1/4 × 22-5/8 × 22-5/8 (285 × 575 × 575) 11-1/4 × 22-5/8 × 22-5/8 (285 × 575 × 575) Packaged Dimensions (H × W × D) in. (mm) 14-9/16 × 27-1/16 × 26-9/16 (370 × 687 × 674) 14-9/16 × 27-1/16 × 26-9/16 (370 × 687 × 674) Weight (Mass) Lbs (kg) 38.6 (17.5) 38.6 (17.5) Gross Weight (Gross Mass) Lbs (kg) 46 (21) 46 (21) Sound Pressure
Level
H / L dB(A) 42.5 / 31.5 42.5 / 31.5 46.0 / 37.5 46.0 / 37.5
Heat Insulation Both Liquid and Gas Pipes Both Liquid and Gas Pipes
Piping Connections
Liquid in. (mm)
φ
1/4
6.4
)
φ
1/4
(
φ
6.4
)
Gas i n. ( mm)
φ
1/2
(
φ
12.7)
φ
1/2
(
φ
12.7)
Drain in. (mm) VP20 (O.D.
φ
1-1/32
26) / I.D.
φ
25/32
20) VP20 (O.D.
φ
1-1/32
(
φ
26) / I.D.
φ
25/32
(
φ
20)
Drawing No. 3D080628A 3D080629A
Conversion Formulae
kcal/h = kW × 860
Btu/h = kW × 3412
cfm = m³/min × 35.3
SiUS121602E Outdoor Unit
Specifications 13
2. Outdoor Unit
60 Hz, 208 - 230 V
Notes:
1.Max.: for the combination of CTXS, FTXS series indoor units Min.: for the combination of CDXS, FDXS series indoor units
2. The data are based on the conditions shown in the table below.
Model
2MXL18QMVJU
Cooling Heating
COP
W/W 4.20
EER
Btu/h·W 12.7 — SEER / HSPF 17.0 10.3 Casing Color Ivory White
Compressor
Type Hermetically Sealed Swing Type Model 2YC63AAXD Motor Output W 1,920
Refrigerant Oil
Model FVC50K Charge oz (L) 29.7 (0.9)
Refrigerant
Type R-410A Charge Lbs (kg) 6.17 (2.8)
Airflow Rate
H
cfm
2,150 1,963 M 2,150 1,963 L 1,949 1,006 H
m³/min
60.9 55.6 M 60.9 55.6 L 55.2 28.5
Fan
Type Propeller Motor Output W 51 Running Current A H: 0.32 / M: 0.32 / L: 0.27 H: 0.33 / M: 0.33 / L: 0.07 Power Consumption W H: 62 / M: 62 / L: 54 H: 65 / M: 65 / L: 14
Starting Current A 15.5 Dimension (H × W × D) in. (mm) 28-15/16 × 34-1/4 × 12-5/8 (735 × 870 × 320) Packaged Dimension (H × W × D) in. (mm) 31-7/8 × 41-3/8 × 17-1/2 (810 × 1,050 × 444) Weight (Mass) Lbs (kg) 139 (63) Gross Weight (Gross Mass) Lbs (kg) 155 (71) Sound Pressure Level dB(A) 50 51
Piping Connections
Liquid in. (mm) φ 1/4 × 2 (φ 6.4 × 2) Gas in. (mm) φ 3/8 × 1, φ 1/2 × 1 (φ 9.5 × 1, φ 12.7 × 1) Drain in. (mm) φ 5/8 (φ 15.9)
Heat Insulation Both Liquid and Gas Pipes No. of Wiring Connections 3 for Power Supply, 4 for Interunit Wiring (Including Ground Wiring)
Max. Interunit Piping Length ft (m)
164 (50) (for Total of Each Room)
82 (25) (for One Room)
Amount of Additional Charge of Refrigerant
oz/ft
(g/m)
0.21 (20) (98-7/16 ft (30 m) or more)
Max. Installation Height Difference ft (m)
49-1/4 (15) (between Indoor Unit and Outdoor Unit)
24-5/8 (7.5) (between Indoor Units)
Drawing No. C: 3D101750
Conversion Formulae
kcal/h = kW × 860
Btu/h = kW × 3412
cfm = m³/min × 35.3
Cooling
Indoor ; 80°FDB (26.7°CDB) / 67°FWB (19.4°CWB) Outdoor ; 95°FDB (35°CDB) / 75°FWB (24°CWB)
Heating
Indoor ; 70°FDB (21°CDB) / 60°FWB (15.6°CWB) Outdoor ; 47°FDB (8.3°CDB) / 43°FWB (6°CWB)
Piping Length 24-5/8 ft (7.5 m)
Outdoor Unit SiUS121602E
14 Specifications
60 Hz, 208 - 230 V
Notes:
1.Max.: for the combination of CTXS, FTXS series indoor units Min.: for the combination of CDXS, FDXS series indoor units
2. The data are based on the conditions shown in the table below.
Model
3MXL24QMVJU
Cooling Heating
COP
W/W 4. 56
EER
Btu/h·W 12.7 — SEER / HSPF 17.9 12.5 Casing Color Ivory White
Compressor
Type Hermetically Sealed Swing Type Model 2YC63AAXD Motor Output W 1,920
Refrigerant Oil
Model FVC50K Charge oz (L) 29.7 (0.9)
Refrigerant
Type R-410A Charge Lbs (kg) 6.17 (2.8)
Airflow Rate
H
cfm
2,094 1,886 M 2,094 1,780 L 1,977 1,006 H
m³/min
59.3 53.4 M 59.3 50.4 L 56.0 28.5
Fan
Type Propeller Motor Output W 58 Running Current A H: 0.38 / M: 0.38 / L: 0.33 H: 0.38 / M: 0.33 / L: 0.07 Power Consumption W H: 75 / M: 75 / L: 65 H: 75 / M: 65 / L: 14
Starting Current A 17.5 Dimension (H × W × D) in. (mm) 28-15/16 × 34-1/4 × 12-5/8 (735 × 870 × 320) Packaged Dimension (H × W × D) in. (mm) 31-7/8 × 41-3/8 × 17-1/2 (810 × 1,050 × 444) Weight (Mass) Lbs (kg) 140 (63) Gross Weight (Gross Mass) Lbs (kg) 156 (71) Sound Pressure Level dB(A) 52 54
Piping Connections
Liquid in. (mm) φ 1/4 × 3 (φ 6.4 × 3) Gas in. (mm) φ 3/8 × 1, φ 1/2 × 2 (φ 9.5 × 1, φ 12.7 × 2) Drain in. (mm) φ 5/8 (φ 15.9)
Heat Insulation Both Liquid and Gas Pipes No. of Wiring Connections 3 for Power Supply, 4 for Interunit Wiring (Including Ground Wiring)
Max. Interunit Piping Length ft (m)
230 (70) (for Total of Each Room)
82 (25) (for One Room)
Amount of Additional Charge of Refrigerant
oz/ft
(g/m)
0.21 (20) (131-1/4 ft (40 m) or more)
Max. Installation Height Difference ft (m)
49-1/4 (15) (between Indoor Unit and Outdoor Unit)
24-5/8 (7.5) (between Indoor Units)
Drawing No. C: 3D101754
Conversion Formulae
kcal/h = kW × 860
Btu/h = kW × 3412
cfm = m³/min × 35.3
Cooling
Indoor ; 80°FDB (26.7°CDB) / 67°FWB (19.4°CWB) Outdoor ; 95°FDB (35°CDB) / 75°FWB (24°CWB)
Heating
Indoor ; 70°FDB (21°CDB) / 60°FWB (15.6°CWB) Outdoor ; 47°FDB (8.3°CDB) / 43°FWB (6°CWB)
Piping Length 24-5/8 ft (7.5 m)
SiUS121602E
Printed Circuit Board Connector Wiring Diagram 15
Part 3
Printed Circuit Board
Connector Wiring Diagram
1. Indoor Unit.................................................................................................16
1.1 CTXS07LVJU, FTXS09/12LVJU ................................................................ 16
1.2 FTXS15/18LVJU ........................................................................................ 18
1.3 FDXS09/12LVJU, CDXS15/18LVJU .......................................................... 20
1.4 FVXS09/12/15/18NVJU.............................................................................. 22
1.5 FFQ09/12/15/18LVJU ................................................................................ 24
2. Wired Remote Controller...........................................................................25
2.1 BRC1E71 ................................................................................................... 25
2.2 BRC1E72/73 .............................................................................................. 26
3. Wireless Remote Controller ......................................................................27
3.1 BRC7E830 ................................................................................................. 27
4. Outdoor Unit..............................................................................................28
Indoor Unit SiUS121602E
16 Printed Circuit Board Connector Wiring Diagram
1. Indoor Unit
1.1 CTXS07LVJU, FTXS09/12LVJU
Control PCB (PCB1)
Caution Replace the PCB if you accidentally cut a wrong jumper.
Jumpers are necessary for electronic circuit. Improper operation may occur if you cut any of them.
Note: The symbols in the parenthesis are the names on the appropriate wiring diagram.
1) S1 Connector for DC fan motor
2) S21 Connector for centralized control (HA)
3) S25 Connector for INTELLIGENT EYE sensor PCB
4) S32 Indoor heat exchanger thermistor
5) S41 Connector for swing motors
6) S46 Connector for display PCB
7) S47 Connector for signal receiver PCB
8) H1, H2, H3, FG Connector for terminal board
9) JA Address setting jumper
Refer to page 187 for detail.
10)JB Fan speed setting when compressor stops for thermostat OFF
Refer to page 189 for detail.
11)JC Power failure recovery function (auto-restart)
Refer to page 189 for detail.
12)LED A LED for service monitor (green)
13)FU1 (F1U), FU2 (F2U) Fuse (3.15 A, 250 V)
14)V1 Varistor
V1
FU1
S1S41
S21
S47
JB
JA
JC
S46
S25
LED A
FU2
S32
FG
H1H2H3
2P206687-4
SiUS121602E Indoor Unit
Printed Circuit Board Connector Wiring Diagram 17
Signal Receiver PCB (PCB2)
Display PCB (PCB3)
INTELLIGENT EYE Sensor PCB (PCB4)
Note: The symbols in the parenthesis are the names on the appropriate wiring diagram.
1) S48 Connector for control PCB
3P210728-1
S48
1) S49 Connector for control PCB
2) SW1 Forced cooling operation ON/OFF button
3) LED1 (H1P) LED for operation (green)
4) LED2 (H2P) LED for timer (yellow)
5) LED3 (H3P) LED for INTELLIGENT EYE (green)
6) RTH1 (R1T) Room temperature thermistor
3P210728-1
RTH1
SW1
S49
LED3 LED2 LED1
1) S26 Connector for control PCB
3EB86013-1
S26
Indoor Unit SiUS121602E
18 Printed Circuit Board Connector Wiring Diagram
1.2 FTXS15/18LVJU
Control PCB (PCB1)
Caution Replace the PCB if you accidentally cut a wrong jumper.
Jumpers are necessary for electronic circuit. Improper operation may occur if you cut any of them.
Note: The symbols in the parenthesis are the names on the appropriate wiring diagram.
1) S1 Connector for DC fan motor
2) S21 Connector for centralized control (HA)
3) S25 Connector for INTELLIGENT EYE sensor PCB
4) S32 Indoor heat exchanger thermistor
5) S41 Connector for swing motors
6) S46 Connector for display PCB
7) S47 Connector for signal receiver PCB
8) H1, H2, H3, FG Connector for terminal board
9) JA Address setting jumper
Refer to page 187 for detail.
10)JB Fan speed setting when compressor stops for thermostat OFF
Refer to page 189 for detail.
11)JC Power failure recovery function (auto-restart)
Refer to page 189 for detail.
12)LED A LED for service monitor (green)
13)FU1 (F1U), FU2 Fuse (3.15 A, 250 V)
14)V1 Varistor
2P227881-6
FU1
V1
H1
H2FGH3
LED A
S32
S1S41
S46
S25
S47
S21
JB
JA
JC
FU2