Daewoo DPB-280LH User Manual

Service Manual
FLOOR STANDING AIR CONDITIONER
Model: DPB-280LH
DAEWOO ELECTRONICS CO., LTD. OVERSEAS SERVICE DEFT.
CONTENTS
1. Installation Guide...........................................................................................2
3. Outline..........................................................................................................6
4. Operation.....................................................................................................8
5. Circuit Diagram...........................................................................................18
6. Refrigerant Cycle.........................................................................................35
7. Trouble Shooting..........................................................................................36
8. Exploded Diagram ......................................................................................43
Contents
2
1. INSTALLATION GUIDE
1
INSTALLATION PLACE
Indoor unit Outdoor unit
Secure enough space from the neighboring objects as shown below. This is required to operate the unit efficiently.
• Flat and strong place in the room
• No obstacles in front of air in/out grille
• Easy place to connect drain hose to outside of room
• Easy place to connect copper tube with outdoor unit
• Secure enough distance from neighboring objects as shown below.
• Secure enough distance from neighboring objects as shown below.
• A place no reach of direct ray of sun (if necessary, shield the light)
• No obstacles in front of air in/out grille
• A place having a drain out-let
• Easy place to connect copper tube with indoor unit
• Secure enough distance from neighboring objects as shown below.
100cm
5cm
10cm
50cm
10cm
50cm
(Indoor unit) (Outdoor unit)
Lquid
Gas
3/8 5/8
A
12~12.4
18.6~19
B
9.52
15.88
Unit: mm
Nominal diameter
Flare specification
Lquid
Gas
3/8 5/8
Unit: mm
Torque 300Kg cm 500Kg cm
Torque
B
CAUTION : Do not hang the outdoor unit on the wall of building, in case of falling, it may cause a serious trouble and damage.
2
SPACE TO INSTALL
Specification and method of copper tube
Connection method of copper tube is to make connection with flare nut at the end of the copper tube with a flare tool.
3
3
INSTALLATION OF INDOOR UNIT
1) Drain hose should maintain downward slope to outside of room.
2) Indoor unit should be fixed firmly with the bracket to avoid falling down. The bracket has several holes to fix the unit any direction needed (fore/back/right/left)
1) Cushion rubbers absorb vibration of outdoor unit
2) The unit must be grounded for safety in accordance with local
electrical codes. (Grounding resistance should be under 100 ohms)
2
1
1
2
CAUTION
Use designated diameter and thickness of tube.
Connect all tube as short as possible and fix firmly.
Less than 3M of the difference of height between indoor
and outdoor unit is desirable.
Fill up more refrigerant if the connection tube is longer than 5M (50g/M).
(The refrigerant volume filled from the factory is suitable for 5M connection)
Be careful not to let in any dust or motes into the tube
when the tube passes the wall.
When insulating the connection, use foam rubber or
equivalent.
(Connecting method)
4
INSTALLATION OF OUTDOOR UNIT
5
REFRIGERANT TUBE CONNECTION
IDU TERMINAL BLOCK
321YN L
ODU TERMINAL BLOCK
321YN L
220V/50Hz
4
6
ELECTRICAL WIRING
SIGNAL LINE SIGNAL LINE SIGNAL LINE
SIGNAL LINE MAIN POWER (INDOOR) MAIN POWER (INDOOR) MAIN POWER (INDOOR)
MAIN POWER (OUTDOOR) MAIN POWER (OUTDOOR) MAIN POWER (OUTDOOR)
(Specification of harness)
3 2 1 Y
N
L
N
L
Spec
1.25mm
2
1.25mm
2
1.25mm
2
1.25mm
2
1.25mm
2
1.25mm
2
1.25mm
2
2.0mm
2
2.0mm
2
2.0mm
2
Color
BLUE
BLACK
RED BROWN BROWN
YEL/GRN
RED(or BLUE)
BLACK
YEL/GRN
WHITE
CAUTION
Be sure to use designated wires and make it as short as possible
Use an exclusive power supply for the air conditioner
Use an electricity leakage interrupter having suitable capacity.
Grounding resistance should be under 100 ohms and the grounding wire should be connected firmly to the
terminal of out door unit.
Wire connection of indoor and outdoor unit
When connecting wires of indoor and outdoor unit, the numbers of terminal block and terminals of connecting wires should match exactly as shown below.
Terminals of connecting wires should be fixed firmly using wire fixing tool to the same direction of terminal board.
(Diagram of wire connection)
5
2. SPECIFICATIONS
MODEL
DPB-280LH
ITEM
Function COOLING HEATING Class T Power 220~240V/ 50Hz Capacity W 8,200 8,200
Btu/h 28,000 28,000
Dehumidification l/h - -
Running Current A 14 14 Power Input W 2,800 2,800 Starting Current A ­Type Scroll Model ZR36K3-PFJ-501 Capacitor 50µF/370V AC
Indoor Unit Outdoor Unit Type Sirocco Propeller fan Capacitor 5µF/400V AC 8µF/370V AC Motor Model Number DE112 A2935BA010 Control Capillary Charge Q'ty g 2,000 Type Flare OD
(Liquid/Suction)
in(mm) 3/8 (9.52mm) 5/8 (15.88mm) Dimensions (W x H x D) mm 500 x 1,830 x 350 872 x 675 x 325 Net Weight kg 40 66
Electrical
Data
Compressor
Fan
Refrigerant
(R-22)
Connection
DPB-280LH
4
5
2
7 6
1
3
6
3. OUTLINE
1
INDOOR UNIT
DPB-280LH
No Part Name Quantity Description Remarks
1 Connecting Hole 3 ø60X100 (Left, Right, Back) 2 Evaporator 1 Heat Exchanger 3 Suction Grille 1 Air Inlet 4 Discharge Grille 1 Air outlet 5 Fan Blower 1 Sirocco Type 6 Joint (Gas) 1 OD ø15.88mm 7 Joint (Liquid) 1 OD ø9.52mm
7
2
OUTDOOR UNIT
DPB-280LH
No Part Name Quantity Description Remarks
1 Service Valve (Liquid) 1 OD ø9.52mm Flare Type 2 Service Valve (Gas) 1 OD ø15.88mm Flare Type 3 Service Door 1 4 Fan Guard 1 Fan Protector 5 Fan Blower 1 Propeller type 6 Condenser 1 Heat Exchanger 7 Fan motor 1 Foor propeller fan 8 Compressor 1 Depend on Models 9 Earth Bolt 1 Ground
10 Connection Hole 1 Power & Control wire
8
1
PARTS OF NAME AND FUNCTION
Indoor Unit
4. OPERATION
MAIN CONTROLS/ REMOTE SENSOR
LCD REMOTE CONTROLLER
- Operative distance is within 7m from the indoor unit.
- Use toward to the remote sensor
AIR OUT
- According to the operation mode, it is opened/closed automatically.
AIR IN
- It is to suck warm air.
- There is an air filter inside this grille.
The method to open the air suction grille Pull the upper side of grille with both hands.
MODE
SLEEP
ON/OFF
TIMER
ENTER/
CANCEL
FAN SPEED
TURBO/MILD
A U
T O
F A N
D I R
. F A N
D IR
.
9
ROOM TEMPERATURE / DESIRED TEMPERATURE INDICATOR
- It displays current room temperature and desired room temperature.
FAN MODE INDICATOR
AUTO MODE INDICATOR
TIMER/SLEEP INDICA T OR
ECONOMY MODE INDICA T OR
MODE BUTTON
ECONOMY MODE BUTTON
ON/OFF BUTTON
- Whenever you push this button. It repeats on -> off -> on -> off.
AUTO F AN SPEED INDICATOR
FAN SPEED INDICATOR
COOL MODE INDICA T OR
QUICK MODE
INDICA T OR
HEA T MODE
INDICA T OR (ONLY HEAT PUMP MODEL)
MILD MODE INDICA T OR
DEHUMIDIFIER MODE INDICA T OR
FAN SPEED BUTT ON
- AUTO -> LOW -> MIDDLE -> HIGH -> NATURAL
TEMPERA TURE BUTT ONS
- Each time you push this button, temperature goes up by 1˚C.
- Each time you push this button, temperature falls by 1˚C.
10
Outdoor Unit
OUTDOOR UNIT AIR IN
- If there is any obstacle in front of the grille, the efficiency of the unit can be lowered.
OUTDOOR UNIT AIR OUT
SERVICE VALVES(GAS TUBE)
SERVICE VALVES(LIQUID TUBE)
CAUTION
Do not install the outdoor unit on unstable place like outside wall of building or outside of balcony. In case of falling, it may cause serious trouble and damage.
11
Name of Each Button
2
REMOTE CONTROLLER
MODE
SLEEP
ON/OFF
TIMER
ENTER/ CANCEL
FAN SPEED
TURBO/MILD
Display
Displays information pertaining to unit.
TURBO/MILD
Press to be more silent and comfortable room condition
TIMER ENTER/CANCEL Button
Press to enter a timer setting or to cancel timer setting
TIMER ON/OFF Button
Press to set the unit off or on time. (0.5, 1, 1.5, 2, 2.5, 3, 4, 5, 6, 8, 10, 12, 16, 20, 24hr)
MODE Button
Press to cycle through the modes (Auto/Quick/Cool/Fan/Dehumidifier/ Heat)
SLEEP Button
Press to set the unit for the sleep mode.
FAN DIR. Button
Press to select up/down direction for fan.
FAN DIR. Button
Press to select left/right direction for fan.
ON/OFF Button
Press to turn the unit on or off.
TEMPERATURE Buttons
Press to raise or lower the desired temperature.
FAN SPEED Button
Press to select the fan speed (Auto, High " ", Middle " ", Low " ", Natural).
COVER
Slide down to access most of the remote buttons. Slide down further to access the battery compartment.
AUTO
FAN DIR.
FAN DIR.
12
Replacing Batteries
3
REMOTE CONTROLLER DISPLAY
Slide down the cover to access most of the remote buttons. Slide down further to access the battery compart­ment.
Insert two AAA size Alkaline batteries following the polarity diagram below.
1
2
MODE Indicators (Auto/Quick/Cool/Fan/Dehumidifier/Heat)
Lights to indicate the mode selected.
TIMER Indicators
Lights to indicate the timer function mode.
TEMPERATURE & RESERVATION TIME lndicator
Lights to indicate the temperature or time.
FAN DIRECTION Indicators
Lights to indicate the fan direction.
NATURAL Indicator
Lights to indicate the speeds simulating a breeze.
FAN Indicators
Lights to indicate the fan speed.
AUTO
ON/OFF
TIMER
ENTER/ CANCEL
TURBO/MILD
+
+
13
If you set time in OFF-Timer Mode, the unit will stop at the set time.
If you set time in ON-Timer Mode, the unit will run at the set time.
(1) Range of setting temperature: 18~32°C (2) Setting temperature: Operating temperature of compressor
(3) During the time of test operating, Fan (Indoor, Outdoor) and Compressor is running regardless of room
temperature.
If the Indoor Unit Display receive the signal of Remote Controller, you can hear the signal "beep –" or "beep, beep". (1) In the case of receiving ON/OFF signal-beep“beep” (2) And so on-beep
OFF-Timer
4
DESCRIPTION OF FUNCTIONS
Unit ON
Unit OFF
SET Time
HOUR
ON
OFF
ON-Timer
Unit ON
Unit OFF
SET Time
HOUR
ON
OFF
Control of Room Temperature
Buzzer
COMP (ON)
*RT: ROOM TEMPERATURE DT: DESIRED TEMPERATURE
COMP (OFF)
-1°C0°C (COOLING)
(RT-DT)
COMP (ON)
COMP (OFF)
-1°C0°C (HEATING)
(DT-RT)
+1˚C +1˚C
14
Fan Speed (Indoor Unit)
(1) Motor speed (high speed, middle speed, low speed). (2) Remote controller setting fan speed. (Auto, L, M, H, Natural) (3) Relation of operating mode between fan speed. (legned: X-no relation)
(4) Automatic Operation If the unit is set in 'AUTO' mode, the unit operates automatically according to the room temperature to keep the room temperature comfortable.
0°C
L
M
H
1°C2°C
(RT-DT)
L
H
M
0°C1°C2°C3°C (DT-RT)
(COOLING)
(HEA TING)
FAN ONLY COOL
DEHUMI-
AUTO QUICK HEAT
DIFICATION
H HHLHH H M MMLMH M L LLLLH L
Auto X Auto L Auto H Auto
Natural Natural Natural L Natural H Natural
15
(1) When you are going to sleep, select sleep switch and the unit controls the room to the desired temperature.
(The unit will not operate after 4 hour)
(2) For changing the temperature.
(3) To cancel sleep mode, press the SLEEP button again or press the MODE button once.: the SLEEP
indicator will disappear in the display.
Sleep Mode
0 0.5 1.0 HOUR
(COOLING CYCLE)
DT
+0.5°C
+0.5°C
+0.5°C
0 0.5 1.0 HOUR
(HEATING CYCLE)
DT
0.5°C
0.5°C
0.5°C
Frost Prevention of Indoor Unit
When the unit operates at low ambient temperature, frost may appear on the Evaporator. When the indoor coil temperature is lower than -2°C at the end of 10 minutes of continuous compressor operation from the start, the microcomputer of the unit stops the compressor to protect the unit from the frost. The control procedure for indoor coil freeze protection.
1) The compressor and outdoor fan turn off.
2) Indoor fan operates according to user set speed.
3) The normal operation returns when the indoor coil temperature is higher than 7°C or equal to 7°C.
7°C-2°C
Compressor and Outdoor Fan
OFF
ON
(Indoor coil temperature)
Loading...
+ 35 hidden pages