Dacor HICT365BG Planning Guide

HICT305, HICT365
Heritage
Electric Induction Cooktops
®
Doc #: PGH-HICT.01 Revised 22 May 2018 Page 1 of 4
All tolerances: ±¹/₁₆” (±1.6 mm), unless otherwise stated.
PLANNING
GUIDE
WARNING
• Follow local codes/ordinances during planning and installation. (Contact the local building department for details.)
• The cooktop must be installed per its installation instructions. Dacor is not responsible for product damage/failure due to faulty installation.
HICT Electrical-Supply Requirements (reference only)
Total Connected Load* Dedicated Circuit Required
46.7 Amp. (11.2 kW) 240V, 60 Hz.; 3-Wire** 50 Amp.
* See the product-data label for current, exact specifications. ** Two 120V hot (L1 and L2), plus one ground (use all-copper wires in all lines)
• Chassis depth is ½” wider and deeper at the base of the glass cooking surface.
• The cooking surface overhangs the chassis by ¾” (1.9 cm) on all sides.
All specications subject to change without notice. www.dacor.com Ph. 800.793.0093
HICT305, HICT365
Heritage
Electric Induction Cooktops
• To reduce risk of burn injury from reaching over a hot cooktop, avoid storage in overhead cabinetry, or install a range hood.
• Locate the junction box within reach of the 48” (122 cm) power conduit attached to the bottom-right rear of the chassis. The junction box and chassis bottom should be easily accessible for service/inspection.
• To properly vent smoke/fumes and prevent injury, installing a range hood is strongly recommended. The hood should overhang the entire cooktop surface and project outward at least 5” beyond the bottom of overhead cabinets.
• Always consult the countertop manufacturer for specific installation instructions/requirements.
The countertop opening must accept the cooktop chassis’ squared corners.
• Installation may need to include fire­retardant material, which bears the mark:
UNDERWRITERS LABORATORIES INC.
CLASSIFIED
MINERAL AND FIBER BOARDS.
SURFACE BURNING CHARACTERISTICS
This mark is followed by flame-spread and smoke ratings, which are shown as “FHC (Flame Spread)/(Smoke Developed).” Material with “0” flame-spread rating are flame retardant. Local codes may allow other flame-spread ratings.
• If the cooktop chassis is completely enclosed, allow ventilation of at least 18 sq. inches into the enclosure.
®
Cabinet Cutout Dimensions
Page 2 of 4
All tolerances: ±¹/₁₆” (±1.6 mm), unless otherwise stated.
PLANNING
GUIDE
Cabinet Clearances
Model A B
HICT305 30” (76.2 cm) 28 ¾” (73.0 cm)
HICT365 36” (91.4 cm) 34 ¾” (88.3 cm)
Callout Description
30” min. clearance from cooktop surface and bottom of unprotected wood
1
or metal cabinet
Distance to combustible side wall (either side): 2 ¼” (5.7 cm) min. from
2
edge of cooktop surface.
If cooktop side of upper cabinetry is over 2 ¼” (5.7 cm) to the left/right of
3
the cooktop edge, Specification 3 does not apply.
1 ” (2.9 cm) min. to combustible surface at rear; ” (1.9 cm) min. to non-
4
Under-Counter Clearance
All specications subject to change without notice. www.dacor.com Ph. 800.793.0093
combustible surface at rear.
Ensure internal space allows proper under-cabinet ventilation for cooktop
5
chassis. (See Under-Counter Clearance at left.)