Dacor HGPR48CLPH Planning manual

RNRP30G, RNRP36G, RNRP48G
Document # PG05-012
Renaissance 30”, 36” and 48”
Gas Ranges
Cabinet Layout
All maximum and minimum dimensions and clearances shown in the diagrams below must be maintained for safe operation.
The range should be placed away from drafts that may be caused by doors, windows and heating and air conditioning outlets.
Avoid cabinet installations directly above the range. If cabinet storage is to be provided above the range, the risk can be reduced by installing a range hood that projects horizontally a minimum of 5 inches beyond the bottom of the cabinets.
The range may be installed flush to the rear wall. Dacor strongly recommends installing a non-combustible material on the rear wall above the range and up to the vent hood or installation of a backguard.
Any openings in the wall behind the appliance or in the floor underneath it must be sealed.
DIMENSIONS: SEE TABLE ON FOLLOWING PAGE
Cutout tolerances: +1/16” 0” (1.6 mm) unless otherwise stated.
Revised 08/21/15 Page 1/4
PLANNING
GUIDE
The shaded area in the Recommended Cabinet Clearance Dimensions figure shows the recommended locations of the gas inlet and the electrical junction box. For replacement purposes, the location of the existing utilities may be used provided they do not interfere with the sides or rear of the range.
The junction box and gas shut off valve must be located so that the range can be pulled out for service while the appliance remains connected.
An external, manual shut-off valve must be installed between the gas inlet and the range for the purpose of turning on or shutting off gas to the appliance.
The installation must allow for the following:
Access to the gas shut-off valve when the unit is installed.
Access to the remote circuit breaker panel/fuse box, when the range is in place.
The gas supply piping and shut-off valve, and the electrical junction box must be located so they do not interfere with the range when it is installed.
RANGE CUTOUT WITH OPTIONAL
DOWNDRAFT SPACING
(TOP VIEW)
non-combustible rear wall (recommended)
Note 2 Next page
Backsplash
J
3/8" (1.0 cm)
min. for downdraft cap
clearance
H
10" (25.4 cm) min.
to combustible side
walls above the range
(both sides)
All specications subject to change without notice.
G
Phone: (800) 793-0093www.dacor.com
Document # PG05-012
Note 2
F
G
2
Cabinet/countertop depth is at discretion of customer but cabinet face MUST NOT protrude further than rear of front panel, see product dimensions.
3
Consult local code for exact location requirements.
1
Vertical from range grate level to combustible overhead surface; if installing an overhead vent hood, also check hood specifications for minimum required clearances.
4
Vertical from grate level to combustible surface.
Non-combustible
surface along back wall
recommended
10” (25.4 cm) min. to combustible side walls above the range (both sides)
30” (76.2 cm)
min.
1
37 1/2”
(95.3 cm)
max.
13” (33.0 cm)
max.
5
15” (38.1 cm)
min.
4, 5
5
This specification does not apply for cabinets more than a horizontal distance of 10” (25.4 cm) from the edge of the range.
Suggested location of utilities
3
Grate
level
RNRP30G, RNRP36G, RNRP48G
Revised 08/21/15 Page 2/4
Renaissance 30”, 36” and 48”
Gas Ranges
All tolerances +1/16” -0” (+1.6 mm) unless otherwise noted.
CUTOUT DIMENSIONS
Range Model F G H I J
RNRP30G
RNRP36G
36” (91.4 cm) *
30” (76.2 cm) **
42” (106.7 cm) *
36” (91.4 cm) **
RNRP48G 54” (137.2 cm) *
48” (121.9 cm) **
30”
(76.2 cm) **
36”
(91.4 cm) **
48”
(121.9 cm) **
27 1/2”
33 1/2”
(84.8 cm)
43 1/2”
(110.2 cm)
30 1/2”
(77.5 cm)
30 7/8”
(78.4 cm)
29 7/8”
(75.9 cm)
PLANNING
GUIDE
* Recommended **Minimum
MINIMUM CABINET CLEARANCE DIMENSIONS
3 1/2”
(8.9 cm)
3”
(7.6 cm)
3”
(7.6 cm)
All specications subject to change without notice.
Phone: (800) 793-0093www.dacor.com
Loading...
+ 2 hidden pages