C = Copper terminals
F = Frame only
K = High magnetic molded case switch
V = 50°C (thermal-magnetic trip units only)
W = Without terminals
X = Load side terminals only
Y = Line side terminals only
Number
of Poles
2 = 2 poles
3 = 3 poles
4 = 4 poles
Trip Unit Rating/Plug
Ampere Rating
300
350
400
450
500
600
Trip Unit Type
LT = Thermal Magnetic
Suffix
T = Trip unit thermal-magnetic fixed thermal
adjustable magnetic
V = 50°C calibration (thermal-magnetic trip units only)
LT 3 400 T
Circuit Breaker/
Frame Type
LD
HLD
LDC
CLD
CHLD
CLDC
Trip Type
2 = LSI (550 only)
6 = LSIG
7 = LSIA
Suffix
W =Without terminals
Circuit Breaker/
Frame Ampere Rating
125 (Available on Model 1050 only)
250 (Available on Model 1050 only)
400
600
Number
of Poles
3 = 3 poles
Trip Model
T5 = Model 550
T10 = Model 1050
LD 3 125 T5 7 W
Trip Unit Type
LES = Electronic
Number
of Poles
3 = 3 poles
4 = 4 poles
Suffix
P = 100% protected neutral on
four-pole trip unit
Suffix
LS
LSI
LSG
LSIG
Trip Unit
Ampere
Rating
600
LES 3 600 LS P
2.3
Catalog Number Selection
2
This information is presented only as an aid to understanding catalog numbers. It is not to be used to build catalog numbers for circuit
breakers or trip units.
t Response) or Adjustable Short Time (Flat Response)
I – Adjustable Instantaneous Pickup by Setting Short Time Delay Time to Instantaneous
G –Adjustable Ground Fault Pickup with Adjustable Ground Fault Delay (Flat Response)
LSLSILSGLSIGFixedAdjustable
2–8 x I
—
—
—
n
2–8 x I
I–300 ms
—
—
n
2–8 x I
n
—
Varies by frame
0–500 ms
2–8 x I
n
0–300 ms
Varies by frame
0–500 msCatalog Number
Digitrip RMS 310 Rating Plug
(Order as Separate Items)
100% Rated Types CLD, CHLD and CLDC Electronic Circuit Breakers with Interchangeable Trip Units
2
The NEC allows the breaker to be rated at 100% of its frame size in an assembly, provided that 90°C wire is applied at the 75°C
ampacity. All 100% rated circuit breakers have electronic trip units. Order as individual components: breaker frame, trip unit, rating
2
plug and terminals.
2
100% Rated Types CLD, CHLD and CLDC Electronic Circuit Breakers with Interchangeable Trip Units
Type LDB Thermal-Magnetic Circuit Breakers with NonInterchangeable Trip Units
600 Vac Rated, 250 Vdc
Complete Circuit Breaker
Maximum
Continuous
Ampere
Rating
Tw o - P o l e
300LDB2300WLDB2300
350LDB2350WLDB2350
400LDB2400WLDB2400
450LDB2450WLDB2450
500LDB2500WLDB2500
600LDB2600WLDB2600
Three-Pole
300LDB3300WLDB3300
350LDB3350WLDB3350
400LDB3400WLDB3400
450LDB3450WLDB3450
500LDB3500WLDB3500
600LDB3600WLDB3600
Without Line and
Load Terminals
Catalog
Number
1
With Standard Line and
Load Terminals Only
Catalog
Number
Molded Case Switches
Eaton’s molded case
switches are used as
compact switches in
applications requiring high
current switching capabilities.
Molded case switches are
constructed of circuit breaker
Molded Case Switches
600 Vac Maximum, 250 Vdc
Maximum
Continuous
Ampere
Rating
at 40°C
Tw o - P o l e
600LD2600WK2TA603LDK
600LDB2600WK
600HLD2600WK2TA603LDK
Three-Pole
600LD3600WK3TA603LDK
600LDB3600WK
600HLD3600WK3TA603LDK
Four-Pole
600LD4600WK4TA603LDK
600LDB4600WK
600HLD4600WK4TA603LDK
Notes
1
Factory sealed—suitable for reverse feed application.
Molded case switch will trip above 6000 amperes.
Circuit Breaker Only
without Line and Load
Ter mi na ls
Catalog
Number
components and are of the
high instantaneous automatic
type. Molded case switches
are listed in accordance with
Underwriters Laboratories
Standard UL 489.
Digitrip OPTIM Electronic Circuit Breaker with Interchangeable Rating Plug
2
Order as individual components: Breaker Frame (which includes Trip Unit), Rating Plug, Terminals.
2
Digitrip OPTIM 550 Electronic Circuit Breaker with Interchangeable Rating Plug
2
2
2
Maximum
Continuous
2
Ampere
Rating
at 40°C
2
Three-Pole Standard Interrupting Capacity 600 Vac Rated 35 kAIC at 480 Vac
2
125LD3125T52WLD3125T56WLD3125T57W—ORPL125A070
2
2
2
250LD3250T52WLD3250T56WLD3250T57W—ORPL025A125
2
2
2
400LD3400T52WLD3400T56WLD3400T57W200ORPL40A200
2
2
2
2
600LD3600T52WLD3600T56WLD3600T57W300ORPL60A300
2
2
2
Notes
1
Long delay I4t response selection limits short delay time to flat response.
2
2
Zone interlocking, PowerNet, or both features can be added at the factory by adding suffixes ZG, PN or ZGP respectively to above catalog number.
Series C
Circuit Breaker Frame OnlyDigitrip OPTIM Rating Plug Only
L – Adjustable Long Delay Pickup (I
S – Adjustable Short Delay Pickup with Adjustable Short Delay Time (I2t or Flat Response)
I – Adjustable Instantaneous Pickup
G – Adjustable Ground Fault Pickup with Adjustable Ground Fault Time (I
A – Adjustable Ground Fault Alarm with Adjustable Ground Fault Time (I
OPTIM 550
LSILSIGLSIA
Catalog
Number
2
) with Adjustable Long Delay Time (I2t or I4t Response)