Cutler Hammer, Div of Eaton Corp S811 General Product Line Information

1.2
Type S811, Soft Starters with DIM
ESC
ONLN SS OXFDO1 H STOP
Monitoring
PREV NEXT ENTER
Reduced Voltage Motor Starters
Solid-State Starters
1
1
1
1
1
1
1
1
1
1
1
Type S811, Soft Starters with DIM
Product Description
1
Eaton’s S811 offers all the popular features of the
1
S801, but adds enhanced functionality with the new
1
DIM (Digital Interface Module), communications,
1
metering, monitoring and diagnostics capabilities.
1
Eaton’s line of S811 reduced voltage soft starters is very
1
compact, multi-functional, easy to install and easy to set
1
operating parameters. Designed to control the acceleration and deceleration
1
of three-phase motors up to 690V, the line is available
1
from 11–1000A.
The S811 is designed to be a
1
complete package combining the silicon controlled
1
rectifiers (SCRs), bypass contactor and overload in
1
one, very compact unit. The S811 is available as a
1
component for panel mounting, in motor control centers or in enclosed control
1
(NEMA Type 1, 3R, 4, 4X, 7/9 and 12).
1
1
1
Application Description
Designed to control the acceleration and deceleration of three-phase motors, the S811 soft starter uses SCRs to control the voltage to soft start and soft stop the motor. After the motor is started, internal run bypass contactors close, resulting in the motor running directly across-the-line. The built-in solid-state overload protects the motor from overload conditions with sophisticated algorithms that model true motor heating, resulting in better motor protection and fewer nuisance trips. Advanced protective and diagnostic features reduce downtime.
A voltage ramp start or current limit start is available. Kick start is available in either starting mode. The soft stop option allows for a ramp stop time that is longer than the coast to stop time. The pump control option provides a smooth transition for starting and stopping a motor and eliminating the “water­hammer” effect that can damage pipes, valves and pumps.
Contents
Description Page
Type S811, Soft Starters with DIM
Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . V6-T1-86
Features and Benefits . . . . . . . . . . . . . . . . . . . V6-T1-89
Standards and Certifications . . . . . . . . . . . . . . V6-T1-92
Instructional Leaflets . . . . . . . . . . . . . . . . . . . . V6-T1-92
Catalog Number Selection . . . . . . . . . . . . . . . . V6-T1-92
Product Selection . . . . . . . . . . . . . . . . . . . . . . . V6-T1-93
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . V6-T1-107
Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . V6- T1-108
Technical Data and Specifications . . . . . . . . . . V6-T1-109
Wiring Diagrams . . . . . . . . . . . . . . . . . . . . . . . V6-T1-113
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . V6-T1-114
The S811 offers an impressive array of advanced protective features. Not only are the protective features selectable, but many offer variable settings and adjustable time delays to ride through system discrepancies.
The S811 has an easy to use Digital Interface Module (DIM) that allows the user to configure the device and to read system parameters and monitor system values. The DIM includes an LCD display and keypad to scroll through the various menus. The DIM allows the user to modify control parameters, enable or disable protections, set communication variables, monitor system parameters such as line voltages and currents, and access the fault queue.
The DIM can be removed from the S811 and remote mounted. Kits are available to door mount the DIM, enabling users to safely configure, commission, monitor and troubleshoot the system at the electrical panel without opening the enclosure door. This will help eliminate the possibility of an arc flash incident.
Digital Interface Module (DIM)
1
1
Reduced Voltage Motor Starters
Fieldbus
DIM
Network Adapter
(Gateway)
Terminator
and
Power Tap
DIN Rail
Communications
Backplane
24 Vdc Power Supply
+
10
S811 Soft Starter
Solid-State Starters
1.2
Communications
The S811 has built-in communication capabilities through Eaton’s QC (Quick Connect) Port. QCPort™ enables the soft starter to be connected to a variety of networks, including DeviceNet™, EtherNet/Modbus, EtherNet/ IP and PROFIBUS. The advantage of QCPort is that multiple control components can be connected to one Eaton D77D gateway.
Communications Reference
Description
DeviceNet network adapter D77D-DNA
EtherNet Modbus network adapter D77D-EMA
EtherNet/IP network adapter D77D-EIP
PROFIBUS network adapter D77D-PNA
Terminator and power tap D77E-QPLR
DIN rail communications backplane, 7-position D77E-BP7
DIN rail communications backplane, 12-position D77E-BP12
85–264 Vac input, 24 Vdc output PSG240E
360–575 Vac input, 24 Vdc output PSG240F
The gateway concentrates data from the devices into a single node. Configuration is simple—a single press of the gateway’s Auto Configuration button sets the system up for default operation. This automatically configures the I/O assemblies to the QCPort system devices. The data from these devices are then assembled into single input and output messages
Part Number
The S811 communication parameters can be configured with the DIM or through the Fieldbus using CH Studio Component Manager. Advanced communication configuration settings provide the system integrator with powerful tools to facilitate system optimization
S811 Connection