N = 65 mm
R = 110 mm
T = 200 mm
U = 200 mm
V = 290 mm
Ampere Rating
37 = 37A
66 = 66A
10 = 105A
13 = 135A
18 = 180A
24 = 240A
30 = 304A
36 = 360A
42 = 420A
50 = 500A
3
65 = 650A
72 = 720A
85 = 850A
10 = 1000A
S = Standard soft starter
(configurable for
edge or level control)
D = Inside-the-delta
L = Extended ramp start
W = Without DIM
Number of Poles
3 = Three-pole device
Options
N = No options
P = Pump control
V = 690V option (Frame
T18 through V85)
4
S = Soft Starter
811 = Non-combination
soft starter
S811 Open Soft Starters
1
Notes
1
All units require a 24 Vdc power supply found on catalog Page V6-T1-107, or equivalent.
2
3
4
T-, U- and V-Frames require lug kits found on Page V6-T1-107.
U-Frame 500A unit does not have IEC certification.
Not available in U-Frame.
Reduced Voltage Motor Starters
S811
Solid-State Starters
1.2
Product Selection
Standard Duty Ratings
Starting Method
Soft start300%30 sec.350°C
Full voltage500%10 sec.350°C
Wye-delta350%20 sec.350°C
80% RVAT480%20 sec.250°C
65% RVAT390%20 sec.350°C
50% RVAT300%20 sec.450°C
Motor applications and
customer needs come in
many different varieties.
With the standard and severe
duty rating tables, we have
attempted to provide
Ramp Current
% of FLA
guidelines on what the soft
starter is capable of.
If the application falls under
these categories, you can
use these charts. For other
applications, or when a
Standard Duty—15 Second Ramp, 4 Starts per Hour, 300% Current Limit at 40°C
For Pump Option, replace character 8 with “P” and also, see Pa ge V 6-T 1-108.
Notes
1
2
3
230V380–400V 440V
690V is available only from T18 thru V85. Not available on U-Frames.
500A rating does not have IEC certification.
For more information on optimum performance of the 1000A Frame Size V S811, see Appendix E of MN03902002E.
Ramp Time
SecondsStarts per Hour
question arises, consult
with your local Eaton
representative or call our
Technical Resource Center.
200V230V460V575–690V
1.0SF1.15SF1.0SF1.15SF1.0SF1.15SF1.0SF1.15SF
Ambient
Temperature
1
1
1
1
1
1
1
1
1
1
1
Catalog
Number
1
1
1
1
1
1
1
1
1
2
1
1
1
1
1
3
1
1
1
1
1
1
1.2
S811
Reduced Voltage Motor Starters
Solid-State Starters
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Standard Duty—25 Second Ramp, 4 Starts per Hour, 300% Current Limit at 40°C
For Pump Option, replace character 8 with “P” and also, see Pa ge V 6-T 1-108.
Notes
1
2
3
230V380–400V 440V
690V is available only from T18 thru V85. Not available on U-Frames.
500A rating does not have IEC certification.
For more information on optimum performance of the 1000A Frame Size V S811, see Appendix E of MN03902002E.
200V230V460V575–690V
1.0SF1.15SF1.0SF1.15SF1.0SF1.15SF1.0SF1.15SF
1
Catalog
Number
1
1
1
1
1
1
1
1
1
1
2
1
1
1
1
3
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.2
S811
Reduced Voltage Motor Starters
Solid-State Starters
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Standard Duty—50 Second Ramp, 2 Starts per Hour, 300% Current Limit at 50°C
For Pump Option, replace character 8 with “P” and also, see Pa ge V 6-T 1-108.
Notes
1
2
230V380–400V 440V
690V is available only from T18 thru V85. Not available on U-Frames.
For more information on optimum performance of the 1000A Frame Size V S811, see Appendix E of MN03902002E.
200V230V460V575–690V
1.0SF1.15SF1.0SF1.15SF1.0SF1.15SF1.0SF1.15SF
1
Catalog
Number
1
1
1
1
1
1
1
1
1
1
1
1
1
1
2
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.2
S811
Reduced Voltage Motor Starters
Solid-State Starters
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Standard Duty—30 Second Ramp, 4 Starts per Hour, 450% Current Limit at 40°C
690V is available only from T18 thru V85. Not available on U-Frames.
For more information on optimum performance of the 1000A Frame Size V S811, see Appendix E of MN03902002E.
Ramp Time
SecondsStarts per Hour
300%. Example: 35-second
ramp, 5 starts per hour,
350% current limit at 40°C
ambient.
200V230V460V575–690V
1.0SF1.15SF1.0SF1.15SF1.0SF1.15SF1.0SF1.15SF
Ambient
Temperature
1
1
1
1
1
1
1
1
1
1
Catalog
Number
1
1
1
1
1
1
1
1
1
1
1
1
1
2
1
1
1
1
1
1
1
1
1.2
S811
Inside-the-Delta Standard Duty Ratings
1
Inside-the-Delta Standard Duty—15 Second Ramp, 4 Starts per Hour,
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
300% Current Limit at 40°C Ambient
Max.
Continuous
Motor Line
Current
Frame Size N
6510 18.518.51515151540305050S811N37N3D
114 18.5 30 37 30253030756010075S811N66N3D
Frame Size R
182 30 55 59 50406050125100150125S811R10N3D
234 40 63 80 60507560150125200150S811R13N3D
Frame Size T
311519011010075100100250200250250S811T18N3D
41575110147125100125125300250300300S811T24N3D
52690160185150125150150400300400400S811T30N3D
Frame Size U
623110185220200150250200450400550450S811U36N3D
727129220257250200300250550450700550S811U42N3D
865150257300250250300250600550750700S811U50N3D
Frame Size V
623110185220200150250200450400550450S811V36N3D
727129220257250200300250550450700550S811V42N3D
865150257300250250300250600550750700S811V50N3D
1125200355425400300400300750700900750S811V65N3D
1246— — — ————————S811V72N3D
1471— — — ————————S811V85N3D
—— — — ————————S811V10N3D
Notes
1
2
3
Reduced Voltage Motor Starters
Solid-State Starters
Three-Phase Motor
kW Rating (50 Hz)hp Rating (60 Hz)
200V230V460V575V
230V380–400V 440V
15 sec. start, 300% inrush, 40°C, 1 start every 15 minutes. If these start parameters are exceeded, please refer to 290 mm V-Frame, 865A inside-the-delta starter.
U-Frame 500A unit does not have IEC certification.
For more information on optimum performance of the 1000A Frame Size V S811, see Appendix E of MN03902002E.
1.0SF1.15SF1.0SF1.15SF1.0SF1.15SF1.0SF1.15SF
Catalog
Number
12
3
1
1
1
1
1
1
1
1
1
1
1
Reduced Voltage Motor Starters
S811
Solid-State Starters
1.2
Inside-the-Delta Standard Duty—25 Second Ramp, 4 Starts per Hour,
300% Current Limit at 40°C Ambient
Max.
Continuous
Motor Line
Current
Frame Size N
589 15 18.51510151540305040S811N37N3D
108 15 30 33 30253030606010075S811N66N3D
Frame Size R
164 25 45 55 50405050125100125125S811R10N3D
206 33 63 63 60506050125125150150S811R13N3D
Frame Size T
257 45 80 90 75607560150150250200S811T18N3D
36563110132100100125100250250300250S811T24N3D
47780147160125125150125300300400400S811T30N3D
Frame Size U
55490160185150125200150400300450400S811U36N3D
646110200220200150250200500400550450S811U42N3D
796140250280250200250250550500700600S811U50N3D
Frame Size V
55490160185150125200150400300450400S811V36N3D
646110200220200150250200500400550450S811V42N3D
796140250280250200250250550500700600S811V50N3D
1055185315375400250300300800700900750S811V65N3D
1176200375445—300400300900800900900S811V72N3D
1358— — — ————————S811V85N3D
—— — — ————————S811V10N3D
Notes
1
15 sec. start, 300% inrush, 40°C, 1 start every 15 minutes. If these start parameters are exceeded, please refer to 290 mm V-Frame, 796A inside-the-delta starter.
2
U-Frame 500A unit does not have IEC certification.
3
For more information on optimum performance of the 1000A Frame Size V S811, see Appendix E of MN03902002E.
Three-Phase Motor
kW Rating (50 Hz)hp Rating (60 Hz)
200V230V460V575V
230V380–400V 440V
1.0SF1.15SF1.0SF1.15SF1.0SF1.15SF1.0SF1.15SF
Catalog
Number
12
3
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.2
S811
Reduced Voltage Motor Starters
Solid-State Starters
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Inside-the-Delta Standard Duty—15 Second Ramp, 4 Starts per Hour,
300% Current Limit at 50°C Ambient
Max.
Continuous
Motor Line
Current
Frame Size N
589 15 18.51510151540305040S811N37N3D
108 15 30 33 30253030606010075S811N66N3D
Frame Size R
164 25 45 55 50405050125100125125S811R10N3D
206 33 63 63 60506060125125150150S811R13N3D
Frame Size T
257 45 80 90 75607575150150250200S811T18N3D
36563110132100100125100250250300250S811T24N3D
47780147160125125150125300300400400S811T30N3D
Frame Size U
55490160185150125200150400300450400S811U36N3D
646110200220200150250200450400550450S811U42N3D
796140250280250200250250550450700600S811U50N3D
Frame Size V
55490160185150125200150400300450400S811V36N3D
646110200220200150250200450400550450S811V42N3D
796140250280250200250250550450700600S811V50N3D
1055185315375400250300300750700900750S811V65N3D
1176200375445————————S811V72N3D
1358257450500————————S811V85N3D
—— — — ————————S811V10N3D
Notes
1
U-Frame 500A unit does not have IEC certification.
2
For more information on optimum performance of the 1000A Frame Size V S811, see Appendix E of MN03902002E.
Three-Phase Motor
kW Rating (50 Hz)hp Rating (60 Hz)
200V230V460V575V
230V380–400V 440V
1.0SF1.15SF1.0SF1.15SF1.0SF1.15SF1.0SF1.15SF
Catalog
Number
1
2
1
1
1
1
1
1
1
1
1
1
1
1
Reduced Voltage Motor Starters
S811
Solid-State Starters
1.2
Inside-the-Delta Standard Duty—50 Second Ramp, 2 Starts per Hour,
300% Current Limit at 50°C Ambient
Three-Phase Motor
Max.
Continuous
Motor Line
Current
Frame Size N
365.510117-1/27-1/27-1/27-1/225152525S811N37N3D
73 11 18.522 1515251550406050S811N66N3D
Frame Size R
10315 30 33 2525302560607575S811R10N3D
1382240454030504010075125100S811R13N3D
Frame Size T
19933596350506050125125150150S811T18N3D
25745809075607575150150250200S811T24N3D
3245510011010075100100250200300250S811T30N3D
Frame Size U
48580150160125125150125300300400400S811U36N3D
580100180200150150200150400300550450S811U42N3D
646110200220200150250200450400550450S811U50N3D
Frame Size V
48580150160125125150125300300400400S811V36N3D
580100180200150150200150400300550450S811V42N3D
646110200220200150250200450400550450S811V50N3D
727129220257250200250250550500700550S811V65N3D
816147257295250250300250600550750700S811V72N3D
1021180315375300250300300750600900750S811V85N3D
————————————S811V10N3D
Notes
1
U-Frame 500A unit does not have IEC certification.
2
For more information on optimum performance of the 1000A Frame Size V S811, see Appendix E of MN03902002E.
kW Rating (50 Hz)hp Rating (60 Hz)
200V230V460V575V
230V380–400V 440V
1.0SF1.15SF1.0SF1.15SF1.0SF1.15SF1.0SF1.15SF
Catalog
Number
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
2
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.2
S811
Reduced Voltage Motor Starters
Solid-State Starters
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Inside-the-Delta Standard Duty—15 Second Ramp, 4 Starts per Hour,
450% Current Limit at 40°C Ambient
Three-Phase Motor
Max.
Continuous
Motor Line
Current
Frame Size N
47 7.5 12.515 1010151030254030S811N37N3D
83 12.522 25 2515252550506060S811N66N3D
Frame Size R
12618.537 40 303040307560100100S811R10N3D
16225455550405050100100125125S811R13N3D
Frame Size T
266458090756010075150150250200S811T18N3D
37963110132100100125100250250300250S811T24N3D
48580150160125125150125300300400400S811T30N3D
Frame Size U
580100185200150150200150400300550450S811U36N3D
695110200250200150250200450400600550S811U42N3D
798140250280250200250250550450700600S811U50N3D
Frame Size V
580100185200150150200150400300550450S811V36N3D
695110200250200150250200450400600550S811V42N3D
798140250280250200250250550450700600S811V50N3D
908160280335250250300250700550750700S811V65N3D
1021— — — ————————S811V72N3D
1125— — — ————————S811V85N3D
Note
1
U-Frame 500A unit does not have IEC certification.
kW Rating (50 Hz)hp Rating (60 Hz)
200V230V460V575V
230V380–400V 440V
1.0SF1.15SF1.0SF1.15SF1.0SF1.15SF1.0SF1.15SF
Catalog
Number
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Reduced Voltage Motor Starters
S811
Solid-State Starters
1.2
Inside-the-Delta Standard Duty—30 Second Ramp, 4 Starts per Hour,
450% Current Limit at 40°C Ambient
Three-Phase Motor
Max.
Continuous
Motor Line
Current
Frame Size N
365.51012.57-1/27-1/27-1/27-1/225152525S811N37N3D
69 11 18.522 1515151550405050S811N66N3D
Frame Size R
961525302525302560507560S811R10N3D
13022 37 45 303040307575100100S811R13N3D
Frame Size T
25745809075607575150150250200S811T18N3D
36563110132100100125100250250300250S811T24N3D
44880140160125125150125300250400300S811T30N3D
Frame Size U
50390160185150125150150300300450400S811U36N3D
580100180200150150200150400300550450S811U42N3D
646110200220200150250200450400550450S811U50N3D
Frame Size V
50390160185150125150150300300450400S811V36N3D
580100180200150150200150400300550450S811V42N3D
646110200220200150250200450400550450S811V50N3D
727129220257250200250250550450700550S811V65N3D
796— — — ————————S811V72N3D
865— — — ————————S811V85N3D
Note
1
U-Frame 500A unit does not have IEC certification.
kW Rating (50 Hz)hp Rating (60 Hz)
200V230V460V575V
230V380–400V 440V
1.0SF1.15SF1.0SF1.15SF1.0SF1.15SF1.0SF1.15SF
Catalog
Number
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.2
S811
Inside-the-Delta Severe Duty Ratings
1
Severe duty ratings are
defined as any combination of
1
parameters that exceed the
standard duty ratings where
the ramp time is over 30
1
seconds, the number of
starts per hour exceeds 4, or
1
the current limit set is over
300%.
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Reduced Voltage Motor Starters
Solid-State Starters
Example: 35-second ramp,
5 starts per hour 350%
current limit at 40°C ambient.
Inside-the-Delta Severe Duty
Three-Phase Motor
Max.
Continuous
Motor Line
Current
Frame Size N
395.510117-1/27-1/2107-1/225153025S811N37N3D
731118.5221515251550406050S811N66N3D
Frame Size R
11115 30 33 2525302575607575S811R10N3D
13822 40 45 4030504010075120100S811R13N3D
Frame Size T
19933 59 63 50506050125125150150S811T18N3D
25745 80 90 75607575150150250200S811T24N3D
3245510011010075100100250200300250S811T30N3D
Frame Size U
41575110147125100125125300250300300S811U36N3D
52690160185150120150150400300450400S811U42N3D
623110185220200150250200450400550450S811U50N3D
Frame Size V
41575110147125100125125300250300300S811V36N3D
52690160185150120150150400300450400S811V42N3D
623110185220200150250200450400550450S811V50N3D
727129220257250200250250550450700550S811V65N3D
816147257295250250300250600550750700S811V72N3D
908160280335250250300250700550750700S811V85N3D
—— — — ————————S811V10N3D
Notes
1
U-Frame 500A unit does not have IEC certification.
2
For more information on optimum performance of the 1000A Frame Size V S811, see Appendix E of MN03902002E.
kW Rating (50 Hz)hp Rating (60 Hz)
200V230V460V575V
230V380–400V 440V
1.0SF1.15SF1.0SF1.15SF1.0SF1.15SF1.0SF1.15SF
Catalog
Number
1
2
1
1
1
1
1
1
1