Cutler Hammer, Div of Eaton Corp S811 Users Manual

IT
. S811 Soft Starter
User Manual
November 2006 — Revision 6 Supersedes June 2006 — Revision 5
IT
. S811 Soft Starter User Manual
November 2006
Important Notice – Please Read
The product discussed in this literature is subject to terms and conditions outlined in Eaton Electrical Inc. selling policies. The sole source governing the rights and remedies of any purchaser of this equipment is the relevant Eaton Electrical Inc. selling policy.
NO WARRANTIES, EXPRESS OR IMPLIED, INCLUDING WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE OR MERCHANTABILITY, OR WARRANTIES ARISING FROM COURSE OF DEALING OR USAGE OF TRADE, ARE MADE REGARDING THE INFORMATION, RECOMMENDATIONS AND DESCRIPTIONS CONTAINED HEREIN. In no event will Eaton Electrical Inc. be responsible to the purchaser or user in contract, in tort (including negligence), strict liability or otherwise for any special, indirect, incidental or consequential damage or loss whatsoever, including but not limited to damage or loss of use of equipment, plant or power system, cost of capital, loss of power, additional expenses in the use of existing power facilities, or claims against the purchaser or user by its customers resulting from the use of the information, recommendations and descriptions contained herein.
The information contained in this manual is subject to change without notice.
Cover Photo: The Cutler-Hammer
®
Intelligent Technologies ( IT. ) Soft Starter
MN03902002E
For more information visit: www.EatonElectrical.com
i
IT
. S811 Soft Starter User Manual
Table of Contents
LIST OF FIGURES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . iv
LIST OF TABLES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . v
SAFETY
The Meaning of Safety Statements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . vii
IT. Soft Starter Safety Statements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . viii
Dangers, Warnings, Cautions and Notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ix
CHAPTER 1 — OVERVIEW
General Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1
General Appearance Notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2
CHAPTER 2 — RECEIPT/UNPACKING
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1
Unpacking. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1
Storage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1
CHAPTER 3 — INSTALLATION
Mounting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1
Power Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-9
Control Wiring Inputs. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-14
CHAPTER 4 — SPECIFICATIONS
Environmental . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1
Physical . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1
CE Conformance. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-2
Short Circuit Ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-3
CHAPTER 5 — FUNCTIONAL DESCRIPTION
Power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-1
Control. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-1
Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-4
QCPort Network Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-4
CHAPTER 6 — CONFIGURATION
Programming the S811 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-1
S801 to S811 Comparison . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-2
CHAPTER 7 — SETUP AND STARTING
Before You Begin . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-1
Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-1
CHAPTER 8 — TROUBLESHOOTING
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-1
Before You Begin to Troubleshoot . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-1
Define the Problem . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-2
Fault Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-6
CHAPTER 9 — PARTS AND SERVICE
Renewal Parts. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-1
Service. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-1
November 2006
ii
For more information visit: www.EatonElectrical.com
MN03902002E
IT
November 2006
Table of Contents, Continued
APPENDIX A — PARAMETERS
Parameter List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-1
APPENDIX B — PROTECTION
Thermal Overload . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-1
Overload Trip Curves . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-3
S811 and Motor Protection Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-4
APPENDIX C — RATINGS, COOLING AND POWER LOSSES FOR A LINE CONNECTED MOTOR
Horsepower and kW Ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C-1
Cooling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C-8
Power Losses. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C-8
APPENDIX D — RATINGS, COOLING AND POWER LOSSES FOR AN INSIDE-THE-DELTA CONNECTED MOTOR
Horsepower and kW Ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . D-1
Cooling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . D-8
Power Losses. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . D-8
APPENDIX E — MOTOR/APPLICATION CONSIDERATIONS
Using MOVs. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . E-1
Squirrel Cage Motor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . E-1
Wye-Delta Motor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . E-2
Part Winding Motor. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . E-2
Dual Voltage Motor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . E-2
Multi-Speed Motor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . E-2
Other Winding Configurations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . E-3
Power Factor Correction Capacitors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . E-3
APPENDIX F — SPECIAL FUNCTION OPTIONS
Pump Control Option . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . F-1
Extended Ramp Option. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . F-2
APPENDIX G — USER INTERFACE — DIM
Modes of Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . G-2
Button Operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . G-3
Areas of the Screen. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . G-5
Parameter Navigation/Editing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . G-8
Access Level (Password) Operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . G-11
Fault Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . G-12
DIM System Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . G-13
DIM Setup Parameter Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . G-14
APPENDIX H — QCPORT NETWORK
QCPort Communication Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . H-1
Networks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .H-3
Auto and Hand/Local Modes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . H-5
APPENDIX I — QCPORT PARAMETER DESCRIPTIONS
Data Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . I-1
Configuration Parameters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . I-6
. S811 Soft Starter User Manual
MN03902002E
For more information visit: www.EatonElectrical.com
iii
. S811 Soft Starter User Manual
List of Figures
Figure 1-1: The Cutler-Hammer Intelligent Technologies ( IT. ) S811 Soft Starter . . . . . . 1-2
Figure 3-1: Warning Tag . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-3
Figure 3-2: Power Wiring Alternatives . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-4
Figure 3-3: N Frame (65 mm) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-5
Figure 3-4: R Frame (110 mm) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-5
Figure 3-5: T Frame (200 mm) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-6
Figure 3-6: U Frame (200 mm) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-6
Figure 3-7: V Frame (290 mm) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-7
Figure 3-8: EMA91 Digital Interface Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-7
Figure 3-9: Line Connected Soft Starter Power Wiring Diagram . . . . . . . . . . . . . . . . . . . 3-10
Figure 3-10: Delta Connected Soft Starter Power Wiring Diagram
for a 6-Lead Motor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-11
Figure 3-11: Delta Connected Soft Starter Power Wiring Diagram
for a 12-Lead Low Voltage Motor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-11
Figure 3-12: Delta Connected Soft Starter Power Wiring Diagram
for a 12-Lead High Voltage Motor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-11
Figure 3-13: V Frame Shown with Terminal Cover Removed
and EML30 Lug Kit Installed on Load Side . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-13
Figure 3-14: Terminal Block . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-14
Figure 3-15: Basic Connection Diagram for 24V DC 3-Wire Pushbutton
STOP/START/JOG/RESET and 24V DC Fault/Ready and Bypass Indication . . . . . . . 3-16
Figure 3-16: Basic Connection Diagram for 24V DC 2-Wire Switch
HAND/OFF/AUTO/RESET and 24V DC Fault/Ready and Bypass Indication . . . . . . . 3-17
Figure 3-17: Basic Connection Diagram for Use of DIM Control Only . . . . . . . . . . . . . . 3-17
Figure 3-18: 24V DC Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-22
Figure 3-19: 120V AC Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-22
Figure 3-20: 24V DC Control with Edge Sensing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-24
Figure 5-1: Line Connected Soft Starter SCRs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-1
Figure 5-2: Ramp Start . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-2
Figure 5-3: Current Limit Start . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-3
Figure 5-4: Soft Stop . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-3
Figure 6-1: Digital Interface Module (DIM) — Display Mode . . . . . . . . . . . . . . . . . . . . . . 6-1
Figure 6-2: Digital Interface Module (DIM) — Parameter Edit Mode . . . . . . . . . . . . . . . . 6-2
Figure 8-1: Start Command Troubleshooting Flowchart . . . . . . . . . . . . . . . . . . . . . . . . . 8-2
Figure 8-2: Main Troubleshooting Flowchart #1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-4
Figure A-1: Navigation Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-1
Figure B-1: Overload Trip Curves . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-3
Figure F-1: IT. Soft Starter DIM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . F-1
Figure F-2: Pump Start Ramp and Soft Pump Stop . . . . . . . . . . . . . . . . . . . . . . . . . . . . . F-2
Figure G-1: DIM (Digital Interface Module) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . G-1
Figure G-2: Display Mode LCD . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . G-2
Figure G-3: Parameter Edit Mode LCD . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . G-2
Figure G-4: Fault Mode LCD . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . G-2
Figure G-5: Soft Key Functions Above Soft Keys . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . G-3
Figure G-6: Predefined Keys . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . G-4
Figure G-7: Status Bar on LCD . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . G-5
Figure G-8: Device Connection (User Display Only) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . G-5
Figure G-9: Connection Status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . G-5
Figure G-10: Mode of Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . G-6
Figure G-11: Connection Destination . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . G-7
Figure G-12: HAND/AUTO Status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . G-7
IT
November 2006
iv
For more information visit: www.EatonElectrical.com
MN03902002E
IT
November 2006
List of Figures, Continued
Figure G-13: Motor Control Status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . G-7
Figure G-14: Bar Indicates Menu Position . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . G-8
Figure G-15: Bar Indicates Item Position . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . G-8
Figure G-16: Bar Indicates Edited Value . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . G-9
Figure G-17: Use MORE to Highlight Element . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . G-10
Figure G-18: Setting Access Level . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . G-11
Figure G-19: Changing Passwords . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . G-12
Figure G-20: Fault Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . G-12
Figure H-1: QCP Network Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . H-2
Figure H-2: Two-Wire QCPort System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . H-3
Figure H-3: Three-Wire QCPort System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . H-4
Figure H-4: S811 Motor Control Byte . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . H-6
List of Tables
. S811 Soft Starter User Manual
Table 3-1: Required Mounting Hardware . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-8
Table 3-2: Weight Support Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-8
Table 3-3: Line and Load Power Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-12
Table 3-4: 12-Pin Terminal Block Wiring Capacity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-14
Table 3-5: S811 Terminal Block Control Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-15
Table 3-6: 24V DC Power Supply Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-18
Table 3-7: 24V DC Power Supplies . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-19
Table 4-1: Environmental Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1
Table 4-2: Weight . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1
Table 4-3: Agency Standards and Certifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1
Table 4-4: EMC Immunity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-2
Table 4-5: Short Circuit Ratings. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-3
Table 6-1: S801 to S811 Setup Cross-Reference . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-2
Table 8-1: Start Command Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-3
Table 8-2: Troubleshooting – Status LED OFF . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-5
Table 8-3: Troubleshooting – Status LED GREEN . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-5
Table 8-4: Troubleshooting Fault Table . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-6
Table 8-5: Resetting the S811 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-8
Table 9-1: DIM – Digital Interface Module Renewal Parts. . . . . . . . . . . . . . . . . . . . . . . . . . 9-1
Table A-1: Monitoring — Menu 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-2
Table A-2: Diagnostics — Menu 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-3
Table A-3: Soft Start Confg — Menu 3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-4
Table A-4: Overload Config — Menu 4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-5
Table A-5: Protection Setup — Menu 5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-6
Table A-6: Network Setup — Menu 6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-7
Table A-7: Network Status — Menu 7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-8
Table A-8: LCD DIM Setup Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-9
Table B-1: Overload — Adjustment Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-1
Table B-2: Thermal Motor Overload Times . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-2
Table B-3: Motor Parameters Required for Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-4
Table B-4: Instantaneous Over Current Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-4
Table B-5: Motor Stall Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-4
Table B-6: SCR Over Current Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-4
Table B-7: Motor Jam Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-5
Table B-8: Motor Over Current Settings. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-5
Table B-9: Motor Under Load Settings. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-5
Table B-10: Current Imbalance Settings. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-5
MN03902002E
For more information visit: www.EatonElectrical.com
v
. S811 Soft Starter User Manual
List of Tables, Continued
Table B-11: Phase Loss Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-6
Table B-12: Motor Voltage Phase Reversal Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-6
Table B-13: Voltage Imbalance Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-6
Table B-14: Under Voltage Settings. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-7
Table B-15: Over Voltage Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-7
Table B-16: Fault Generation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-7
Table B-17: S811 Protection Faults . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-8
Table C-1: 15 Second Ramp, 4 Starts per Hour, 300% Current Limit @ 40°C . . . . . . . . . C-1
Table C-2: 25 Second Ramp, 4 Starts per Hour, 300% Current Limit @ 40°C . . . . . . . . . C-2
Table C-3: 15 Second Ramp, 4 Starts per Hour, 300% Current Limit @ 50°C . . . . . . . . . C-3
Table C-4: 50 Second Ramp, 2 Starts per Hour, 300% Current Limit @ 50°C . . . . . . . . . C-4
Table C-5: 15 Second Ramp, 4 Starts per Hour, 450% Current Limit @ 40°C . . . . . . . . . C-5
Table C-6: 30 Second Ramp, 4 Starts per Hour, 450% Current Limit @ 40°C . . . . . . . . . C-6
Table C-7: > 30 Second Ramp, > 4 Starts per Hour or >300% Current Limit . . . . . . . . . . C-7
Table C-8: Maximum Power Loss . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C-8
Table D-1: 15 Second Ramp, 4 Starts per Hour, 300% Current Limit @ 40°C Ambient . D-1 Table D-2: 25 Second Ramp, 4 Starts per Hour, 300% Current Limit @ 40°C Ambient . D-2 Table D-3: 15 Second Ramp, 4 Starts per Hour, 300% Current Limit @ 50°C Ambient . D-3 Table D-4: 50 Second Ramp, 2 Starts per Hour, 300% Current Limit @ 50°C Ambient . D-4 Table D-5: 15 Second Ramp, 4 Starts per Hour, 450% Current Limit @ 40°C Ambient . D-5 Table D-6: 30 Second Ramp, 4 Starts per Hour, 450% Current Limit @ 40°C Ambient . D-6
Table D-7: Severe Duty Inside-the-Delta Ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . D-7
Table D-8: Maximum Power Loss . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . D-8
Table E-1: MOV Kit Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . E-1
Table G-1: Access Levels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . G-11
Table G-2: Reconfiguring All Devices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . G-13
Table G-3: LCD DIM Setup Menu Access . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . G-14
IT
November 2006
vi
For more information visit: www.EatonElectrical.com
MN03902002E
November 2006
Peligro
Advertencia
Precaución
!
Aviso
Safety
Eaton’s electrical business has made every effort to provide you with the safest motor starters on the market. However, we wish to point out how to safely operate and troubleshoot your starter.
The Meaning of Safety Statements
You will find various types of safety information on the following pages and on the labels attached to the equipment. This section explains their meaning.
The Safety Alert Symbol means ATTENTION! BECOME ALERT! YOUR SAFETY IS INVOLVED!
!
Le symbole d’alerte signifie ATTENTION ! SOYEZ VIGILANT ! VOTRE SECURITE EST EN JEU !
!
IT
. S811 Soft Starter User Manual
El símbolo de alerta de seguridad significa ¡ATENCIÓN! ¡ESTÉ ALERTA! ¡SU SEGURIDAD ESTÁ EN JUEGO!
!
Danger Danger
Danger means that failure to follow the safety statement result in serious personal injury, death, or substantial property damage.
Warning Avertissement
Warning means that failure to follow the safety statement result in serious personal injury, death, or substantial property damage.
Caution
!
Caution means that failure to follow the safety statement result in minor or moderate personal injury or property damage.
will
could
may
Danger signifie que l’inobservation de l’énoncé de sécurité des blessures corporelles graves, la mort ou des dégâts matériels substantiels.
Avertissement signifie que l’inobservation de l’énoncé de sécurité blessures corporelles graves, la mort ou des dégâts matériels substantiels.
Attention signifie que l’inobservation de l’énoncé de sécurité blessures corporelles mineures ou modérés ou des dégâts matériels.
pourrait
Attention
!
peut
entraîner des
entraînera
entraîner des
Peligro significa que si no se respeta la indicación de seguridad, se
producirán
graves, la muerte o daño considerable a la propiedad.
Advertencia significa que si no se respeta la indicación de seguridad se lesiones personales graves, la muerte o daños considerables a la propiedad.
Precaución significa que si no se respeta la indicación de seguridad, se lesiones personales menores o moderadas, o daños a la propiedad.
lesiones personales
pueden
pueden
producir
producir
MN03902002E
Notice Avis
Notice means that failure to follow these instructions cause damage to the equipment or cause it to operate improperly.
could
For more information visit: www.EatonElectrical.com
Avis signifie que l’inobservation de ses instructions entraîner des dégâts à ou le mauvais fonctionnement de l’équipement.
pourrait
Aviso significa que si no se siguen estas instrucciones, se
pueden
o provocar que funcione de manera incorrecta.
producir daños al equipo
vii
. S811 Soft Starter User Manual
. Soft Starter Safety Statements
IT
IT
November 2006
The following safety statements relate to the installation, operation and troubleshooting of Cutler-Hammer
®
Motor Starters.
Notice Avis Aviso
Make sure you read and understand the procedures in this manual before you attempt to operate or set up the equipment.
Bien lire et comprendre les procédures contenues dans ce manuel avant de tenter le fonctionnement ou la mise en place de l’équipement.
Asegúrese de leer y entender los procedimientos en este manual
antes de intentar operar o
configurar el equipo.
Warning Avertissement Advertencia
This instruction manual should be used for proper installation, setup and operation of the starter. Improperly installing and maintaining this product can result in serious personal injury or property damage. Before attempting installation, setup or operation, read and understand all of this manual.
Ce manuel d’instructions doit être utilisé pour l’installation, mise en place et opération réglés d’un démarreur. La mauvaise installation et entretien de ses produits pourraient entraîner des blessures corporelles graves ou des dommages matériels. Avant de tenter l’installation ou l’entretien, bien lire et comprendre ce manuel en entier.
Este manual de instrucciones debe utilizarse para la correcta instalación, configuración y operación del arrancador. La instalación o el mantenimiento inadecuado de este producto puede ocasionar serias lesiones personales o daños al material. Antes de intentar la instalación, la configuración o la operación lea y entienda todo el manual.
Danger High Voltage Danger Haute Tension Peligro alto voltaje
There can be line voltage potential at the motor load terminals even with the starter in the OFF state. This is due to the possible leakage across the thyristors. Unit does not provide galvanic isolation. Always disconnect input power before servicing the starter or motor.
Notice Avis Aviso
Power factor capacitors: Do not connect power factor correcting capacitors to the load side of the starter. They will cause the starter to fail. If capacitors are used, they must be connected to the line side of the starter, as far upstream as possible.
Il peut exister une tension de ligne potentielle aux bornes de charge du moteur bien que le démarreur soit dans en état d’arrêt. Cela s’explique du fait de fuites possibles à travers les redresseurs au silicium. Le produit ne fournit pas l’isolement galvanique. Toujours débrancher l’alimentation avant de travailler sur le démarreur ou le moteur.
Condensateurs de compensation : Ne pas raccorder ces appareils au côté charge du démarreur. Cela entraînera la défaillance du démarreur. Si des condensateurs sont utilisés, ils doivent être raccorder au côté ligne du démarreur, aussi loin amont que possible.
Aun con el motor desactivado, puede haber voltaje de línea en los terminales de la carga del motor. Esto se debe a una posible fuga a través de los tiristores. La unidad no brinda aislamiento galvánico. Desconecte siempre la alimentación antes de trabajar sobre el arrancador o el motor.
Capacitores correctores del factor de potencia: No conecte estos capacitores del lado de la carga del arrancador. Esto ocasionará la falla de este último. Si se usan capacitores, deben conectarse del lado de la línea del arrancador, tan lejos de la entrada como sea posible.
viii
For more information visit: www.EatonElectrical.com
MN03902002E
November 2006
Peligro alto voltaje
Peligro alto voltaje
Dangers, Warnings, Cautions and Notes
Dangers
Danger High Voltage Danger Haute Tension
IT
. S811 Soft Starter User Manual
Hazardous voltage can cause electric shock and burns. To avoid shock hazard, disconnect all power to the controller, motor or other control devices before any work is performed on this equipment. Failure to do so will result in personal injury, death or substantial property damage.
Do not apply a disconnect device on the output of the Starter unless a means to turn off the soft starter when disconnect switch is open is utilized. Opening disconnect while the Soft Starter is operating may cause a malfunction. Closing disconnect switch while the Soft Starter is operating will result in a soft starter failure and potential equipment damage and personnel hazard.
IT.
Soft
IT.
IT.
Une tension électrique dangereuse peut causer des chocs électriques et des brûlures. Pour éviter des chocs électriques, débrancher l’alimentation du contrôleur, du moteur ou des autres appareils de contrôle avant d’y effectuer du travail. L’inobservation de ces instructions entraînera des blessures corporelles graves, la mort ou des dégâts matériels substantiels.
Ne pas appliquer un appareil de sectionnement sur la sortie du démarreur progressif qu’un moyen d’éteindre le démarreur progressif quand l’interrupteur de sectionnement est ouvert soit utilisé. Le fait d’ouvrir l’interrupteur de sectionnement pendant le fonctionnement du démarreur progressif défaillance. Le fait d’éteindre l’interrupteur de sectionnement pendant le fonctionnement du démarreur progressif entraînera la défaillance du démarreur progressif et des dégâts à l’équipement ou risque au personnel.
IT.
peut entraîner une
IT.
à moins
IT.
Voltajes peligrosos que pueden causar descargas eléctricas y quemaduras. Para evitar descargas eléctricas, desconecte la alimentación del controlador, del motor u otros dispositivos de control antes de efectuar cualquier trabajo en el equipo. El incumplimiento de estas medidas ocasionará lesiones personales, la muerte o daños importantes al material.
No aplique un dispositivo de desconexión a la salida del arrancador IT. Soft Starter a menos que se utilice un medio para apagar el arrancador cuando el interruptor de desconexión está abierto. La apertura del interruptor de desconexión mientras el arrancador IT. está operando puede ocasionar un funcionamiento incorrecto. El cierre del interruptor de desconexión mientras el arrancador IT. está operando producirá una falla de dicho arrancador, como también potenciales daños a los equipos y riesgo para el personal.
MN03902002E
Danger High Voltage Danger Haute Tension
Hazardous voltage can cause electric shock and burns. Always disconnect power before proceeding with any work on this product.
For more information visit: www.EatonElectrical.com
Une tension électrique dangereuse peut causer des chocs électriques et des brûlures. Il faut toujours débrancher l’alimentation électrique avant de travailler sur ce produit.
Voltajes peligrosos que pueden causar descargas eléctricas y quemaduras. Siempre desconecte la energía eléctrica antes de efectuar cualquier trabajo en el equipo.
ix
. S811 Soft Starter User Manual
Dangers, continued
Danger High Voltage Danger Haute Tension Peligro alto voltaje
November 2006
IT
Warnings
The S811 has the ability to respond to commands from an automated network controller. Consequently the soft starter may start unexpectedly in response to these commands. To insure the safety of personnel and equipment, always remove power before accessing the electrical and/or mechanical equipment.
Danger High Voltage Danger Haute Tension Peligro alto voltaje
Do not work on energized equipment unless absolutely required. If troubleshooting procedure requires equipment to be energized, all work must be performed by properly qualified personnel, following appropriate safety practices and precautionary measures.
Le S811 à la capacité de répondre aux commandes d’un contrôleur de réseau automatisé. Donc le démarreur progressif peut démarrer soudainement en réponse à ces commandes. Pour s’assurer la sécurité du personnel et de l’équipement, toujours débrancher l’alimentation avant d’accéder à l’équipement électrique et/ou mécanique.
Ne pas travailler sur d’équipement sous tension sauf si c’est absolument nécessaire. Si des méthodes de dépannage exigent que l’équipement soit sous tension, tout travail doit être faire par du personnel qualifié, suivant des pratiques de sécurité et des mesures de précaution appropriées.
El S811 tiene la capacidad de responder a comandos de un controlador de red automatizado. Por lo tanto, el arrancador suave podría arrancar de improviso en respuesta a estos comandos. Para garantizar la seguridad del personal y del equipo, siempre desconecte la energía antes de acceder al equipo eléctrico o mecánico.
No trabaje en equipos en funcionamiento, a menos que sea absolutamente necesario. Si un procedimiento de solución de problemas requiere que el equipo permanezca encendido, todo el trabajo lo debe realizar personal adecuadamente calificado, respetando las prácticas de seguridad y las medidas preventivas correspondientes.
Warning Avertissement Advertencia
After mounting the unit, remove and discard the lifting eye and packaging bolts before continuing with the installation process.
Warning Avertissement Advertencia
Make sure you read and understand all of the safety statements in the safety section of this manual before you begin troubleshooting.
Après que l’appareil sera supporté, enlever et jeter les œillets de levage et les boulons de l’emballage avant de poursuivre l’installation.
S’assurer de bien lire et comprendre les énoncés de sécurité dans le passage de sécurité de ce manuel avant de commencer le dépannage.
Después de montar la unidad, retire y elimine la argolla de izada y los pernos de embalaje antes de continuar con el proceso de instalación.
Antes de comenzar a solucionar problemas, asegúrese de leer y comprender todas las indicaciones de seguridad que aparecen en la sección de seguridad de este manual.
x
For more information visit: www.EatonElectrical.com
MN03902002E
November 2006
Precaución
!
Precaución
!
Precaución
!
Cautions
IT. S811 Soft Starter User Manual
Caution
!
The S811V soft starter weighs approximately 100 Lbs. (45 kg). To prevent personal injury or equipment damage, use proper lifting equipment (such as a floor crane) to safely lift and install the soft starter. A lifting eye is provided at the line end of the soft starter.
Caution
!
Only apply 24V DC to the terminal block unless specified otherwise in this manual. All control wiring is 22 – 12 AWG (0.33 – 2.5 mm this caution could result in severe damage to the controller.
Never megger a motor while it is connected to the IT. Soft Starter. Disconnect the leads at the IT. Soft Starter before meggering the motor.
2
). Failure to follow
Caution
!
Attention
!
Le démarreur progressif S811V pèse environ 45 kg (100 livres). Pour éviter des blessures corporelles ou des dégâts matériels, utiliser une machine de levage appropriée (comme une grue d’atelier) pour soulever et installer le démarreur progressif sans encombre. Un œillet de levage est prévu au côté ligne du démarreur progressif.
Attention
!
Appliquer seulement 24V CC à la barrette à bornes sauf ce manuel offre d’avis contraire. Tout le câblage de commande est de calibre 0,33 – 2,5 mm AWG). L’inobservation de cet énoncé pourrait entraîner des dégâts matériels au contrôleur.
Attention
!
Ne jamais régler un moteur alors qu’il est branché au démarreur progressif IT. Débrancher les fils au démarreur progressif IT. Avant de régler le moteur.
2
(22 – 12
El arrancador suave S811V pesa aproximadamente 45 kg (100 lb.). Para evitar que se produzcan lesiones personales o daños al equipo, use el equipo para elevar adecuado (como un brazo de elevación) a fin de levantar e instalar con seguridad el arrancador suave. Se proporciona una argolla de izada en el extremo de del arrancador suave.
Aplique sólo 24 V CC al bloque de terminales, a menos que se especifique lo contrario en este manual. Todo el cableado de control es de 0.33 – 2.5 mm (22 – 12 AWG). Si no respeta esta precaución, se pueden producir daños graves al controlador.
Nunca efectúe pruebas del motor con un megóhmetro mientras esté conectado al arrancador Soft Starter IT. Desconecte los cables en el arrancador IT. antes de usar el megóhmetro.
2
MN03902002E
For more information visit: www.EatonElectrical.com
xi
IT. S811 Soft Starter User Manual
Notes
Notice Avis Aviso
November 2006
The S811V Soft Starter includes mounting hardware (8 1/4-20 x
1.5 Allen hex head cap screws and special washers). Do not substitute for this hardware. See Figure 3-7 on Page 3-7 for panel hole locations. Applicable codes or standards must be considered before locating and mounting the soft starter. The four special rectangular/rounded washers must be used on the two innermost mounting holes on both the line and load side of the soft starter.
Le démarreur progressif S811V inclut des matériels de support (vis à tête hexagonale 8-1/4-20 x 1,5 et des rondelles spéciales). Ne substituer pas pour ces matériels. Consulter la Figure 3-7 de la Page 3-7 pour les locations des trous dans le panneau. Tenir compte des normes et des codes existants avant de localiser et de monter le démarreur progressif. Les quatre rondelles rectangulaires/ circulaires spéciales doivent être utiliser aux deux trous de support les plus intérieurs sur le côté ligne et le côté charge du démarreur progressif.
El arrancador suave S811V incluye piezas metálicas de montaje (tornillos Allen de cabeza hexagonal de 8 1/4-20 x
1.5 y arandelas especiales). No las sustituya. Consulte la
Figura 3-7 que aparece en la página 3-7 para conocer las
ubicaciones de los orificios del panel. Antes de ubicar y montar el arrancador suave, se deben considerar los códigos o las normas pertinentes. Las cuatro arandelas rectangulares/ redondas especiales se deben usar en los dos orificios de montaje que se encuentren más al interior, en los lados de línea y de carga del arrancador suave.
xii For more information visit: www.EatonElectrical.com
MN03902002E
November 2006
Chapter 1 — Overview
General Introduction
The Cutler-Hammer® Intelligent Technologies S811 IT. Soft Starter from Eaton’s electrical business is an electronic, self-contained, panel- or enclosure-mounted motor soft-starting device. It is intended to provide three-phase induction motors with a smooth start, both mechanically and electrically. The S811 Soft Starters utilize six SCRs connected in a full wave power bridge. Varying the SCR conduction period controls the voltage applied to the motor. This in turn controls the torque developed by the motor. After the motor reaches speed, contacts are closed to bypass the SCRs.
The S811 has built-in communications capabilities through Cutler-Hammer QC (Quick Connect) Port. The S811 Soft Starter utilizes a DIM (Digital Interface Module) that allows the user to configure the device and read system parameters. The DIM includes an easy-to-read LCD display and keypad to scroll through the menus. The DIM allows the user to modify control parameters, enable or disable protections, set communication variables, monitor system parameters such as line voltages and currents and access the fault queue.
The S811 is designed to fulfill the industrial service requirements for applications such as Chillers, Pumps and Machine Tools that require less than 85% of the motor’s rated starting torque for worst case starting condition.
IT. S811 Soft Starter User Manual
The S811 meets all relevant specifications set forth by NEMA ICS 1, ICS 2 and ICS 5, UL 508, IEC 60947-4-2, CE and CSA.
This user manual covers everything you need to know in order to install, set up, operate, troubleshoot and maintain the S811.
However, no publication can take into account every possible situation. If you require further assistance with any aspect of this product, or a particular application, please contact us.
For contact information, please see Chapter 9.
MN03902002E
For more information visit: www.EatonElectrical.com
1-1
IT. S811 Soft Starter User Manual
General Appearance Notes
November 2006
Digital Interface
Module (DIM)
Load Output
Line Input
Mounting Slots
Base
QC Port CH0 Network Address Switch
Detachable 12-Pin Locking Control Terminal Block
Figure 1-1: The Cutler-Hammer Intelligent Technologies (IT.) S811 Soft Starter
1-2 For more information visit: www.EatonElectrical.com
MN03902002E
November 2006
Chapter 2 — Receipt/Unpacking
General
Upon receipt of the unit, verify that the catalog number and unit options stated on the shipping container match those stated on the order/purchase form.
Inspect the equipment upon delivery. Report any crate or carton damage to the carrier prior to accepting the delivery. Have this information noted on the freight bill. Eaton is not responsible for damage incurred in shipping.
Unpacking
Remove all packing material from the unit. Be sure to remove all packing material from lug locations. Also, make sure no packing material blocks the airflow near the fans. For V frame units, verify mounting hardware has been included with shipment.
Check the unit for any signs of shipping damage. If damage is found after unpacking, report it to the freight company. Retain the packaging materials for carrier to review.
Verify that the unit’s catalog number and options match those stated on the order/purchase form.
IT. S811 Soft Starter User Manual
Storage
It is recommended that the unit be stored in its original shipping box/crate until it is to be installed.
The unit should be stored in a location where:
The ambient temperature is -58°F – 158°F (-50°C – 70°C)
The relative humidity is 0% – 95%, non-condensing
The environment is dry, clean and non-corrosive
The unit will not be subjected to high shock or vibration conditions
MN03902002E
For more information visit: www.EatonElectrical.com
2-1
November 2006
Advertencia
Precaución
!
Chapter 3 — Installation
Mounting
Models S811N, S811R and S811T
The S811 is easy to mount. It does not require any special tools. To aid you with panel layout, refer to the dimension drawings in Figures 3-3 through 3-7 of
this manual. Drill and tap holes per mounting hole location as shown. To mount the unit, use all the hardware specified in Table 3-1 on Page 3-8. Tighten to the
torque specified. The T frame S811 is supplied with a lifting eye mounted on the center phase of the line end of
the device. This will aid in mounting the unit.
Warning Avertissement
IT. S811 Soft Starter User Manual
After mounting the unit, remove and discard the lifting eye and packaging bolts before continuing with the installation process.
Model S811V10
IMPORTANT: For model S811V10xxx, see additional installation requirements noted on Page 3-4.
The S811V soft starter weighs approximately 100 Lbs. (45 kg). To prevent personal injury or equipment damage, use proper lifting equipment (such as a floor crane) to safely lift and install the soft starter. A lifting eye is provided at the line end of the soft starter.
Caution
!
Après que l’appareil sera supporté, enlever et jeter les œillets de levage et les boulons de l’emballage avant de poursuivre l’installation.
Attention
!
Le démarreur progressif S811V pèse environ 45kg (100 livres). Pour éviter des blessures corporelles ou des dégâts matériels, utiliser une machine de levage appropriée (comme une grue d’atelier) pour soulever et installer le démarreur progressif sans encombre. Un œillet de levage est prévu au côté ligne du démarreur progressif.
Después de montar la unidad, retire y elimine la argolla de izada y los pernos de embalaje antes de continuar con el proceso de instalación.
El arrancador suave S811V pesa aproximadamente 45 kg (100 lb.). Para evitar que se produzcan lesiones personales o daños al equipo, use el equipo para elevar adecuado (como un brazo de elevación) a fin de levantar e instalar con seguridad el arrancador suave. Se proporciona una argolla de izada en el extremo de del arrancador suave.
MN03902002E
For more information visit: www.EatonElectrical.com
3-1
IT. S811 Soft Starter User Manual
Notice Avis Aviso
November 2006
The S811V soft starter includes mounting hardware (8 1/4-20 x
1.5 Allen hex head cap screws and special washers). Do not substitute for this hardware. See Figure 3-7 on Page 3-7 for panel hole locations. Applicable codes or standards must be considered before locating and mounting the soft starter. The four special rectangular/rounded washers must be used on the two innermost mounting holes on both the line and load side of the soft starter.
Le démarreur progressif S811V inclut des matériels de support (vis à tête hexagonale 8-1/4-20 x 1,5 et des rondelles spéciales). Ne substituer pas pour ces matériels. Consulter la Figure 3-7 de la Page 3-7 pour les locations des trous dans le panneau. Tenir compte des normes et des codes existants avant de localiser et de monter le démarreur progressif. Les quatre rondelles rectangulaires/ circulaires spéciales doivent être utiliser aux deux trous de support les plus intérieurs sur le côté ligne et le côté charge du démarreur progressif.
El arrancador suave S811V incluye piezas metálicas de montaje (tornillos Allen de cabeza hexagonal de 8 1/4-20 x
1.5 y arandelas especiales). No las sustituya. Consulte la
Figura 3-7 que aparece en la página 3-7 para conocer las
ubicaciones de los orificios del panel. Antes de ubicar y montar el arrancador suave, se deben considerar los códigos o las normas pertinentes. Las cuatro arandelas rectangulares/ redondas especiales se deben usar en los dos orificios de montaje que se encuentren más al interior, en los lados de línea y de carga del arrancador suave.
Drill and tap the eight mounting holes. Thread the two lower middle screws (with special flat washer and lockwasher) into the panel before lifting the soft starter. These two screws will assist in mounting. Special mounting hardware is included with the soft starter. Hardware supplied must be used.
Hook lifting equipment to the soft starter lifting eye. If you are using a crane, minimize the chain length between the boom and the soft starter. Make sure that the back of the soft starter is oriented to the panel-mounting surface. Make sure that the lifting equipment hook is fully engaged with the soft starter lifting eye before lifting.
Slowly lift the soft starter to about 2 in. (5 cm) above the mounting location. Then move it back against the mounting panel. Carefully lower the soft starter onto the two mounting screws. Make sure the screws align with the slots on the load end of the soft starter, and that the two washers are between the soft starter base and the screw head.
Install and tighten the remaining six mounting screws, washers and lockwashers. Then tighten the two lower middle screws. Tighten all eight screws to 50 Lb-in (5.6 N•m). Disengage and remove the lifting equipment.
Warning Avertissement Advertencia
After mounting the unit, remove and discard the lifting eye and packaging bolts before continuing with the installation process.
Après que l’appareil sera supporté, enlever et jeter les œillets de levage et les boulons de l’emballage avant de poursuivre l’installation.
Después de montar la unidad, retire y elimine la argolla de izada y los pernos de embalaje antes de continuar con el proceso de instalación.
3-2 For more information visit: www.EatonElectrical.com
MN03902002E
November 2006
WARNING
AVERTISSEMENT
REMO VE LIFTING EYE
BEFO REWIRING
NOT AN ELECTRICAL
CONNECTION
CAN CAUSESEVERE IN JURY,
DEATH, OR DAMAGE
EQUIPMENT
RETIRER L’OEI LLET DE
LEVAGE AVAN T DE CÂBLE
PAS UNE CONNEXION
´
E
PEUT CAUSERDES BLESSURES
DOMMAGES Á L’ QUIPEMENT
LECTRIQUE
GRAVES, LA MORT OU DES
´
E
IT. S811 Soft Starter User Manual
R
Figure 3-1: Warning Tag
MN03902002E
For more information visit: www.EatonElectrical.com
3-3
IT. S811 Soft Starter User Manual
S811V10xxx Installation Requirements
1. Install the device in a minimum enclosure size 30 ft3.
2. Two (2) forced air ventilation fans with a min. 500 ft3/min, at a location for “air in” — bottom right or left corner and “air out” — opposite upper right or left corner.
3. RD circuit breaker.
4. For power wiring: Use four (4) 500 MCM cables for each phase between RD circuit breaker and Soft Starter.
OPTIONAL: Two (2) 3" x 1/4" bus with a 1/4" spacer per terminal. Note: See Figure 3-2 for alternative layouts.
5. Line and load service entrance wiring must not cross in the enclosure.
12"
Minimum
Distance
RD
Circuit
Breaker
S811V10xxx
IT.
Soft Starter
Line Service
(4) 350
MCM/Terminal
(4) 500 MCM or
(2) 3 x 1/4" Bus
with 1/4"
Space/Terminal
Line Service
(4) 350
MCM/Terminal
RD
Circuit
Breaker
Isolation
Contactor
S811V10xxx
IT.
Soft Starter
6"
Minimum
Distance
6"
Minimum
Distance
November 2006
Figure 3-2: Power Wiring Alternatives
3-4 For more information visit: www.EatonElectrical.com
MN03902002E
November 2006
Dimensions
IT. S811 Soft Starter User Manual
6.87
(1 74 .5 )
1.97
(50.0)
.22 (5.5)
Typ. 4 Places
3.54
(90.0)
6.47
(164.4)
7.38
(187.4)
Figure 3-3: N Frame (65 mm)
Approximate Dimensions in Inches (mm)
6.66
(169.2)
2.66
(67.6)
(111.3)
4.38
3.46
(88.0)
5.35
(135.9)
7.44
(189.0)
MN03902002E
.27 (6.8)
Typ. 4 Places
7.92
(201.2)
Figure 3-4: R Frame (110 mm)
Approximate Dimensions in Inches (mm)
For more information visit: www.EatonElectrical.com
3.49
(88.5)
5.53
(140.5)
3-5
IT. S811 Soft Starter User Manual
6.39
(162.4)
11. 77
12.71
(299.0)
(322.9)
Slots
Figure 3-5: T Frame (200 mm)
Approximate Dimensions in Inches (mm)
2.95
(75.0)
Slots
7.67
(194.8)
5.91
(150.0)
Slots
November 2006
5.40
(137.2)
.28 (7.1)
Slots Typ.
6 Places
11.77 (299.0) Mounting
12.72
(323.1)
.47
(11.9)
5.20 (132.0) Mounting
C
L
Mounting Slots
for M6 (1/4) Screws
(Up to 6 Quantity)
7.08
(179.9)
5.20 (132.0)
Pole Centers
C
L
7.73
(196.3)
Figure 3-6: U Frame (200 mm)
Approximate Dimensions in Inches (mm)
3-6 For more information visit: www.EatonElectrical.com
MN03902002E
November 2006
IT. S811 Soft Starter User Manual
15.63
(397.0)
.26 (6.5) Dia. Typ. 4 Places
9.84
(250.0)
3.74
(95.0)
7.35
(186.6)
.27 (6.7) Dia.
Typ. 4 Places
Figure 3-7: V Frame (290 mm)
Approximate Dimensions in Inches (mm)
15.16
(385.0)
Slots
16.57
(420.8)
11.05
(280.6)
1.83
(46.4)
1.77
(45.0)
.91
(23.2)
.49
(12.5)
.31
(8.0)
2.91
(74.0)
.29
(7.5)
.41
(10.5)
Figure 3-8: EMA91 Digital Interface Module
Approximate Dimensions in Inches (mm)
3.08
(78.3)
.89
(22.5)
2.68
(68.0)
MN03902002E
For more information visit: www.EatonElectrical.com
3-7
IT. S811 Soft Starter User Manual
Required Mounting Hardware
Table 3-1: Required Mounting Hardware
Frame Size Screw Size Washer Size
Quantity Required
November 2006
Torque Required
N #10 – 32 x 0.5 Standard #10 Lockwasher and
R 1/4 – 20 x 0.625 Standard 1/4 Lockwasher and
T & U 1/4 – 20 x 0.625 Standard 1/4 Lockwasher and
V 1/4 – 20 x 1.5
Grade 8 Allen head hex cap screws
Included with V Frame Units
Weight Support Requirements
Table 3-2: Weight Support Requirements
Frame Size Weight of Unit
N 5.8 Lbs. (2.6 Kg) R 10.5 Lbs. (4.8 Kg) T & U 48 Lbs. (21.8 Kg) with lugs
41 Lbs. (18.6 Kg) without lugs
V 103 Lbs. (46.8 Kg) with lugs
91 Lbs. (41.4 Kg) without lugs
Flat Washer
Flat Washer
Flat Washer Quantity: 4
ID: 0.270 OD: 0.495 – 0.505 Max. 0.055 Thick
Quantity: 4 Special Washer
4 15 Lb-in
(1.7 N•m)
4 25 Lb-in
(2.8 N•m)
6 30 Lb-in
(3.4 N•m)
8 50 Lb-in
(5.6 N•m)
3-8 For more information visit: www.EatonElectrical.com
MN03902002E
November 2006
Peligro alto voltaje
Power Wiring
Using the wiring diagrams in Figures 3-93-12, 3-15, 3-16 and 3-17 and Table 3-3 below as guides, connect the line, Motor, and Power Supply wiring in accordance with appropriate local and national codes.
Note: To provide optimum motor protection the Line and Motor power wiring should be
Safety Notices
IT. S811 Soft Starter User Manual
tightly bundled and run perpendicular to the orientation of the S811.
Danger High Voltage Danger Haute Tension
Hazardous voltage can cause electric shock and burns. To avoid shock hazard, disconnect all power to the controller, motor or other control devices before any work is performed on this equipment. Failure to do so will result in personal injury, death or substantial property damage.
Do not apply a disconnect device on the output of the IT. Soft Starter unless a means to turn off the soft starter when disconnect switch is open is utilized. Opening disconnect while the IT. Soft Starter is operating may cause a malfunction. Closing disconnect switch while the IT. Soft Starter is operating will result in a soft starter failure and potential equipment damage and personnel hazard.
Une tension électrique dangereuse peut causer des chocs électriques et des brûlures. Pour éviter des chocs électriques, débrancher l’alimentation du contrôleur, du moteur ou des autres appareils de contrôle avant d’y effectuer du travail. L’inobservation de ces instructions entraînera des blessures corporelles graves, la mort ou des dégâts matériels substantiels.
Ne pas appliquer un appareil de sectionnement sur la sortie du démarreur progressif IT. à moins qu’un moyen d’éteindre le démarreur progressif quand l’interrupteur de sectionnement est ouvert soit utilisé. Le fait d’ouvrir l’interrupteur de sectionnement pendant le fonctionnement du démarreur progressif IT. peut entraîner une défaillance. Le fait d’éteindre l’interrupteur de sectionnement pendant le fonctionnement du démarreur progressif IT. entraînera la défaillance du démarreur progressif et des dégâts à l’équipement ou risque au personnel.
Voltajes peligrosos que pueden causar descargas eléctricas y quemaduras. Para evitar descargas eléctricas, desconecte la alimentación del controlador, del motor u otros dispositivos de control antes de efectuar cualquier trabajo en el equipo. El incumplimiento de estas medidas ocasionará lesiones personales, la muerte o daños importantes al material.
No aplique un dispositivo de desconexión a la salida del arrancador IT. Soft Starter a menos que se utilice un medio para apagar el arrancador cuando el interruptor de desconexión está abierto. La apertura del interruptor de desconexión mientras el arrancador IT. está operando puede ocasionar un funcionamiento incorrecto. El cierre del interruptor de desconexión mientras el arrancador IT. está operando producirá una falla de dicho arrancador, como también potenciales daños a los equipos y riesgo para el personal.
MN03902002E
Note: Short circuit protection must be applied on the line side of the soft starter. The S811 can be wired in both line connected and inside-the-delta connected configurations.
If a line configuration is desired then the three-phase line feeding and the three main motor leads should be connected for normal across-the-line starting as shown in Figure 3-9. For inside-the-delta connected configurations be sure to consult Figures 3-10, 3-11 and 3-12.
Note: Only soft starters with catalog numbers S811xxxxxD may be connected in an inside­the-delta configuration. Refer to the motor nameplate for correct wiring information. Contact
Eaton if a special motor wiring requirement exists before wiring your starter.
For more information visit: www.EatonElectrical.com
3-9
IT. S811 Soft Starter User Manual
By factory default, the S811 is to be connected with an ABC phase rotation on the incoming power wiring. If the motor turns in the incorrect direction upon energization, exchange two phases at the motor terminal box or at the output terminals of the soft starter. Changing the input wiring will cause a voltage phase reversal trip.
If the input phase sequence to the S811 must be ACB, the incoming phase sequence protection will need to be set to ACB. Setting ACB as the incoming phase sequence causes the ABC incoming phase sequence to cause a voltage phase reversal trip.
IMPORTANT: The reversing contactor must never be switched while the soft starter is operating. In order to gain the full benefit of the S811 with a reversing contactor, the S811 needs to be OFF when switching the direction. The soft starter settings must account for catching a motor spinning in the opposite direction upon soft restarts. The time required for slowing the motor to a stop and then ramping up to speed in the opposite direction adds to the overall starting time. This will also impact the overload protection setting.
See the Motor/Application Considerations in Appendix E of this manual for information on typical motor winding configurations.
November 2006
1L1 3L2
S811
2T1 4T2 6T3
5L3
M
3
˜
Figure 3-9: Line Connected Soft Starter Power Wiring Diagram
3-10 For more information visit: www.EatonElectrical.com
MN03902002E
November 2006
IT. S811 Soft Starter User Manual
Supply
S811
1L13L25
2T14T26
L1S L2S
L3
T3
L3S
T5 T4 T6
Motor
T2
T3
T1
L3
L2
L2
T4
L1
T1
T2
T1
T2
T5
L3
T3 T3
T6
L1
Figure 3-10: Inside-the-Delta Connected Soft Starter Power Wiring Diagram
for a 6-Lead Motor
S811
1L13L25
2T14T26
L3
T3
Supply
L1S L2S
L3S
T11
T5
T3 T9
T10T4T12
T6
Motor
T2
T1
T8
T7
L3
L2
L1
Low Voltage
L2
T10
12-Lead
T8
T4
T7
T11
T2
T2
T1
T1
T5
L3
T3
T3
T6
L1
T9
T12
Figure 3-11: Inside-the-Delta Connected Soft Starter Power Wiring Diagram
for a 12-Lead Low Voltage Motor
S811
1L13L25
2T14T26
T3
L3
Supply
L1S L2S
L3S
T11
T3
T10 T12
Motor
T8 T5
T2
T7 T4
T6 T9
T1
L3
L2
L1
12-Lead
High Voltage
T5
T2
L2
T10
T7
T4
T2
T1
T1
T8
T11
L3
T3 T3
T6 T9
T12
L1
MN03902002E
Figure 3-12: Inside-the-Delta Connected Soft Starter Power Wiring Diagram
for a 12-Lead High Voltage Motor
For more information visit: www.EatonElectrical.com
3-11
IT. S811 Soft Starter User Manual
Line and Load power wiring data is shown in Table 3-3.
Table 3-3: Line and Load Power Wiring
Frame Size Lug Kit Options
Number of Conductors Lug Type
Wire Sizes Cu 75°C Only
Torque Requirements
November 2006
Number of Kits Required
N Supplied
Standard with Box Lugs
1 Box Lug 2 AWG 50 Lb-in (5.6 N•m) N/A
4 – 6 AWG 45 Lb-in (5.0 N•m) 8 AWG 40 Lb-in (4.5 N•m) 10 – 14 AWG 35 Lb-in (4.0 N•m)
R Supplied
Standard with Box Lugs
1 Box Lug 14 – 8 AWG
(2.5 – 10 mm 6 – 4 AWG
(16 – 25 mm 3 – 3/0 AWG
(27 – 95 mm
T & U EML22 2 4 – 1/0 MCM
(21.2 – 53.5 mm
EML23 1 4/0 – 500 MCM
(107 – 240 mm
EML24 2
4/0 – 500 MCM
(107 – 240 mm
EML25 1 2/0 – 300 MCM
(70 – 150 mm
EML26 2 2/0 – 300 MCM
(70 – 150 mm
V EML28 2
4/0 – 500 MCM
(107 – 240 mm
EML30 4
4/0 – 500 MCM
(107 – 240 mm
EML32 6

4/0 – 500 MCM
(107 – 240 mm
EML33 4 2/0
Requires special lug cover. Check with Eaton for availability.
CSA approved 350 MCM – 500 MCM
300 MCM
(70
150 mm
90 – 100 Lb-in
2
)
(10.1 – 11.3 N•m)
2
)
2
)
250 Lb-in (28.3 N•m) 2
2
)
250 Lb-in (28.3 N•m)
2
)
250 Lb-in (28.3 N•m)
2
)
225 Lb-in (25.5 N•m)
2
)
225 Lb-in (25.5 N•m)
2
)
250 Lb-in (28.3 N•m) 2
2
)
250 Lb-in (28.3 N•m)
2
)
250 Lb-in (28.3 N•m)
2
)
225 Lb-in (25.5 N•m)
2
)
N/A
3-12 For more information visit: www.EatonElectrical.com
MN03902002E
November 2006
Peligro alto voltaje
Lugs for T, U and V Frame
T, U and V frame units are supplied standard without lugs. If lugs are needed, they can be ordered through your local Eaton distributor. Each lug kit contains three lugs, mounting hardware, and instructions for use on either line or load side of the IT. Soft Starter. Catalog numbers and wire ranges for lug kits are listed in the table above.
Lug Installation
IT. S811 Soft Starter User Manual
Danger High Voltage Danger Haute Tension
Hazardous voltage can cause electric shock and burns. Always disconnect power before proceeding with any work on this product.
Une tension électrique dangereuse peut causer des chocs électriques et des brûlures. Il faut toujours débrancher l’alimentation électrique avant de travailler sur ce produit.
Voltajes peligrosos que pueden causar descargas eléctricas y quemaduras. Siempre desconecte la energía eléctrica antes de efectuar cualquier trabajo en el equipo.
Note: For additional motor and system protection, a Metal Oxide Varistor (MOV) may be
installed on the line side of the unit. An MOV can also be installed on the load side of the Soft Starter if additional protection is desired. Generally, it is more common to use a MOV on the line side. Refer to the instructions provided with the MOV kit.
1. For T, U and V Frame Soft Starters, remove line and load terminal covers by removing the screws that hold each cover (and the MOV, if installed) onto the unit.
Note: For N and R Frame Soft Starters, it is not necessary to remove the covers in order
to wire the device. Proceed to step 3.
2. After screws are removed, slide covers off of unit. Set the covers and screws aside.
3. Position lugs and install lug mounting screws according to instructions provided with the kit. Tighten lug mounting screws provided with the kit to 120 Lb-in (13.6 N•m).
4. Wire the appropriate line and load conductors to the IT. Soft Starter (as required by NEC and local codes based on the device rating).
5. Torque bolts as directed by Table 3-3 on Page 3-12 of this manual.
MN03902002E
Figure 3-13: V Frame Shown with Terminal Cover Removed
and EML30 Lug Kit Installed on Load Side
For more information visit: www.EatonElectrical.com
3-13
IT. S811 Soft Starter User Manual
6. Slide the line and load covers back into place on the soft starter.
7. Reinstall the cover screws through the cover and the MOV, if installed.
8. Insert two outer cover screws through cover.
9. Align cover and torque all cover screws to 5 Lb-in (0.6 N•m). Do not overtighten screws.
Control Wiring Inputs
Control wiring is connected to the S811 by a 12-pin terminal block located at the front of the unit. Using the wiring diagrams in Figures 3-15, 3-16 and 3-17 and Tables 3-4 and 3-5 as guides, connect the control wiring as required for your application.
November 2006
Caution
!
Only apply 24V DC to the terminal block unless specified otherwise in this manual. All control wiring is 22 – 12 AWG (0.33 – 2.5 mm this caution could result in severe damage to the controller.
2
). Failure to follow
Appliquer seulement 24V CC à la barrette à bornes sauf ce manuel offre d’avis contraire. Tout le câblage de commande est de calibre 0,33 – 2,5 mm AWG). L’inobservation de cet énoncé pourrait entraîner des dégâts matériels au contrôleur.
Attention
!
2
(22 – 12
Precaución
!
Aplique sólo 24 V CC al bloque de terminales, a menos que se especifique lo contrario en este manual. Todo el cableado de control es de 0.33 – 2.5 mm (22 – 12 AWG). Si no respeta esta precaución, se pueden producir daños graves al controlador.
2
Figure 3-14: Terminal Block
Table 3-4 provides the 12-pin terminal block wiring capacity and torque requirements for the
control wiring.
Table 3-4: 12-Pin Terminal Block Wiring Capacity
Wire Size
22 – 14 AWG (0.33 – 2.5 mm
12 AWG (4.0 mm
2
)
Number of Conductors
2
)
2 3.5 Lb-in (0.4 N•m)
1 3.5 Lb-in (0.4 N•m)
Torque Requirements
3-14 For more information visit: www.EatonElectrical.com
MN03902002E
November 2006
Input Descriptions
IT. S811 Soft Starter User Manual
The IT. Soft Starter has the following control inputs:
Table 3-5: S811 Terminal Block Control Wiring
Terminal Block
Name
Circuit Common
Power + 24V DC nominal
Permissive P Hardwired
Input 1 1 START 24V DC only
Input 2 2 JOG 24V DC only
Input 3 3 HAND/AUTO 24V DC only
Input 4 4 Fault RESET 24V DC only Input 4 is Fault RESET. Energizing this
Relay1 Form A NO Contact
Form C Common
Relay2 Form C NC Contact
Relay2 Form C NO Contact
Designation (Pin)
- Negative Power supply connections:
13 Common 3 Amps, @ 230V 14 NO De-
95 Common Form C Common
96 NC De-
98 NO De-
Factory Default Input Connections
– Connect power supply negative to pin
“–” and to system ground – Connect +24V DC output to pin “+” Note: To avoid voltage drop during bypass contactor inrush, a minimum of 14 AWG wire should be used between the power supply and the “+” and “–” inputs at the S811 terminal block.
Pin “P”, permissive, must be energized (+24V DC) to enable operation of the unit. If power is removed from the permissive circuit at any time, the unit will begin a STOP command. If a soft stop is selected, the soft stop will begin and run to time­out.
Applying 24V DC to Input 1 while P is energized will initiate a START. As shipped from the factory this input is “level” sensitive.
Input 2 is JOG. Applying 24V DC to this input while P is energized will initiate a JOG.
Input 3 is HAND. Energizing this input will select the terminal block as the source of motor control. It must be energized to enable the terminal block to START or JOG the motor.
input will reset a fault only after the fault condition has been corrected.
NO Form A contact: As shipped from the factory this programmable contact closes when the starter’s bypass contactor is energized. It will remain closed until a STOP is initiated. The motor may continue to run even after the STOP is initiated until the stop ramp has been completed.
Form C contacts: As shipped from the factory these programmable contacts will change status when a Fault occurs.
STOP
energized
energized
energized
(see 24V DC Power Supply Requirements section for sizing of power supply)
24V DC only (maintained input)
(momentary input)
(momentary input)
Must be maintained for control from the terminal block
AC/24V DC
for 96 and 98 3 Amps, @ 230V
AC/24V DC
3 Amps, @ 230V AC/24V DC
MN03902002E
For more information visit: www.EatonElectrical.com
3-15
IT. S811 Soft Starter User Manual
Typical Control Wiring Diagrams
Each diagram illustrates a typical wiring scheme for the options described. The terminal block represents the soft starter. The additional Cutler-Hammer items shown on the diagrams are not included, but they may be purchased from Eaton.
(See Note 1)
Power Supply
+
24V DC
E-Stop
November 2006
Inputs
24V DC Only
_
24V DC
Jog
Permissive
-
+
P
1
+24V
Start
32 4 13 14 95 96 98
Reset
Internal
Contacts
Jumper
+24V to 3
Stop
Start
(See Note 3)
Jog
Reset
In Bypass
Ready Fault
Optional 24V DC Pilot Lights
(See Note 2)
Maintained
Momentary
Figure 3-15: Basic Connection Diagram for 24V DC 3-Wire Pushbutton
STOP/START/JOG/RESET and 24V DC Fault/Ready and Bypass Indication
3-16 For more information visit: www.EatonElectrical.com
MN03902002E
November 2006
(See Note 1)
Power Supply
+
24V DC
E-Stop
IT. S811 Soft Starter User Manual
Inputs
24V DC Only
_
24V DC
Not Used
Permissive
-
+
P
1
+24V
Start
32 4 13 14 95 96 98
Reset
Internal
Contacts
Jumper
+24V to 3
Hand
OFF
Auto
(See Note 3)
Optional 24V DC Pilot Lights
(See Note 2)
Remote Contact
Reset
In Bypass
Ready Fault
Jumper
Maintained
Momentary
Figure 3-16: Basic Connection Diagram for 24V DC 2-Wire Switch HAND/OFF/AUTO/RESET
and 24V DC Fault/Ready and Bypass Indication
Inputs
24V DC Only
_
24V DC
Permissive
Not Used
Not Used
Not Used
-
+
P
1
32 4 13 14 95 96 98
Not Used
Internal
Contacts
(See Note 1)
Power Supply
+
24V DC
E-Stop
MN03902002E
Jumper
+24V to P
Maintained
Figure 3-17: Basic Connection Diagram for Use of DIM Control Only
For more information visit: www.EatonElectrical.com
3-17
IT. S811 Soft Starter User Manual
Notes:
1. A minimum wire of 14 AWG (2.5 mm2) should be used between the power supply and the 24V DC + and - terminals.
2. See Using an Auxiliary Relay section below if it is desired to use a relay instead of an indicating lamp for terminals 13, 14, 95, 96 and 98.
3. If an isolation or reversing contactor is used upstream of the S811, Eaton recommends that the user choose the level sensing option.
Each diagram illustrates a typical wiring scheme for the options described. The terminal block represents the soft starter. The additional Cutler-Hammer items shown on the diagrams are not included, but can be purchased from Eaton.
24V DC Control Power Supply
The S811 Soft Starter requires 24V DC control power. The sealed in and inrush characteristics of the S811 Soft Starter are summarized in Table 3-6:
Table 3-6: 24V DC Power Supply Requirements
Soft Starter Frame
November 2006
Sealed Inrush
Watts Amps Watts Amps Duration (ms)
S811N 25 1.0 240 10 150 S811R 25 1.0 240 10 150 S811T 25 1.0 240 10 150 S811U 25 1.0 240 10 150 S811V 25 1.4 240 10 150
For applications where one starter is used with one power supply, the power supply selected must be equal to or greater than both the sealed in and inrush requirements of the starter.
Max Steady State for the Power Supply Sealed In Power of the Starter
Outrush for the Power Supply Inrush Power of the Starter
Multiple starters can be used with one power supply. If the application requires the starters to start at the same time, the power supply must be sized for the sum of the sealed in and inrush power for each starter.
Max Steady State for the Power Supply Sum of the Sealed In Power of all the Starters
Outrush for the Power Supply Sum of the Inrush Power of all the Starters
Multiple starters are typically not commanded to start at the same time. If the application requires the starters not be commanded to start at the same time (>150 ms between start commands), the required power is the sum of the largest inrush power, plus the sealed in power of the running starters. Worst case from a power supply standpoint is the largest inrush starter commanded to start while all the other starters are running.
3-18 For more information visit: www.EatonElectrical.com
MN03902002E
November 2006
Precaución
!
IT. S811 Soft Starter User Manual
Formulas to calculate power supply requirements are as follows:
Definitions:
SI = Sum of Seal Incurrent LS = Largest Seal Incurrent LI = Largest Inrush Needed TS = Total Seal Incurrent Needed LO = Largest Outrush Needed
TS = (SI - LS) LO = TS + LI
Max Steady State for the Power Supply SI
Outrush for the Power Supply LO
The voltage on the S811 + and – control terminals must not exceed 30V DC to prevent hardware damage. The S811 will shut down and issue low control voltage fault at control voltages less than 17V DC. The fault will reset at control voltages greater than 18V DC. The Cutler-Hammer control power supplies listed in Table 3-7 are recommended.
Table 3-7: 24V DC Power Supplies
Catalog Number
Continuous Peak
Input Voltage VACWatts Amps Amps
PSS55A 55 2.3 10.0 90 – 140 PSS55B 55 2.3 10.0 180 – 260 PSS55C 55 2.3 10.0 360 – 500 PSS160E 160 6.5 13.0 90 – 260 PSS160C 160 6.5 13.0 360 – 500 PSS300E 300 12.5 20.0 90 – 260 PSS600C 600 25.0 50.0 360 – 500
Control Wiring Application Notes
Caution
!
Only apply 24V DC to the terminal block unless specified otherwise in this manual. All control wiring is 22 – 12 AWG (0.33 – 2.5 mm this caution could result in severe damage to the controller.
2
). Failure to follow
1. Connect DC common (negative) to terminal -, using a minimum wire of 14 AWG (2.5 mm
2. Connect +24V DC positive to terminal +, using a minimum wire of 14 AWG (2.5 mm2).
3. Terminal P (permissive circuit) — Must be energized at +24V DC to enable operation of all S811 soft starters. For all units, if power is removed from the permissive circuit at any time, the unit will initiate a stop sequence, including a soft-stop if enabled.
Attention
!
Appliquer seulement 24V CC à la barrette à bornes sauf ce manuel offre d’avis contraire. Tout le câblage de commande est de calibre 0,33 – 2,5 mm AWG). L’inobservation de cet énoncé pourrait entraîner des dégâts matériels au contrôleur.
2
(22 – 12
Aplique sólo 24 V CC al bloque de terminales, a menos que se especifique lo contrario en este manual. Todo el cableado de control es de 0.33 – 2.5 mm (22 – 12 AWG). Si no respeta esta precaución, se pueden producir daños graves al controlador.
2
2
).
MN03902002E
For more information visit: www.EatonElectrical.com
3-19
IT. S811 Soft Starter User Manual
Note: With level sensing control, if +24V DC is removed from the permissive circuit at
any time, the unit will initiate a stop and restart when +24V DC is reapplied to terminal P if:
a) +24V DC is still available on pin 1 (to start from Terminal Block, Input #3 must
b) the device shows a green status light (not faulted). If the starter has faulted and
See the Edge and Level Sensing sections below for more details. If the AUTO
Reset Mode setting is used, CAUTION must be exercised to assure that any restart occurs in a safe manner.
4. Terminal 1 (Start mode) — If terminal P is at +24V DC, momentary application of +24V DC to terminal 1 will initiate a start sequence for all S811 soft starters.
Edge Sensing
Edge sensing is set with the Start Control parameter. Edge sensing requires +24V DC power be momentarily applied to pin 1 (with terminal P
at +24V DC) to initiate a start under all conditions. After a stop or fault occurs, the +24V DC must be removed, then reapplied to pin 1 before another start can occur. This control configuration should be used when restarting of the motor after a fault or stop must be supervised manually or as a part of a control scheme. The cycling of +24V DC power to terminal 1 before starting is required regardless of the setting of the Reset Mode parameter.
November 2006
also be enabled),
the fault condition clears then if the Reset Mode parameter is set to AUTO on Digital Interface Module (DIM), the starter will restart.
Level Sensing
Level sensing is set with the Start Control parameter. Level sensing will enable a motor to restart after a fault is cleared without cycling
+24V DC power to terminal 1 as long as:
Terminal P is supplied with +24V DC (to start from Terminal Block, Input #3 must
also be enabled),
The Reset Mode parameter is set to AUTO,
All faults have been reset.
This control configuration should be used where it is desirable to restart a motor after a fault without additional manual or automatic control. An example of this condition would be on a remote pumping station where it is desirable to automatically restart a pump after a power outage without operator intervention.
In the AUTO RESET MODE, CAUTION must be exercised to assure that any restart occurs in a safe manner.
3-20 For more information visit: www.EatonElectrical.com
MN03902002E
November 2006
IT. S811 Soft Starter User Manual
5. Terminal 2 (Jog mode) — If +24V DC power is applied to this terminal while terminal P is at +24V DC, the soft starter will operate in the jog mode as long as +24V DC is on terminal 2 and no faults occur. In jog mode, the soft starter will operate only on the thyristors and the bypass contactors will not close.
6. Terminal 3 (HAND/AUTO setting) — Input 3 selects the terminal block as a source of motor control. It must be energized to enable the terminal block to START or JOG the motor.
7. Terminal 4 (Reset) — Application of +24V DC power will reset the soft starter after all fault conditions are cleared. If the AUTO Reset Mode setting is used with level control CAUTION must be exercised to assure that any restart occurs in a safe manner. See Edge and Level sensing on Page 3-20.
8. Terminals 13 and 14 (Programmable) — At default setting, relay contacts for use up to 230V AC or 24V DC provide bypass contactor status. The contact closes upon bypass and will remain closed until a stop is initiated or a fault occurs. The motor and load may continue to rotate after a stop is initiated if soft stop is being used or if the load inertia is high. See Using an Auxiliary Relay section below for additional contact interface information.
9. Terminals 95, 96 and 98 (Programmable) — At default setting, relay contacts for use up to 230V AC or 24V DC provide fault or ready status indication. See Page 3-15 for a description of their operation.
Connecting a New or Replacement DIM
When 24V DC is first applied to terminals + and -, the S811 will send commands to the DIM to reconfigure its communication, and the S811 will send a reset to the DIM after configuration is done (this process takes approximately 20 seconds).
Using an Auxiliary Relay
The IT. Soft Starter contains one Form A and one Form C set of auxiliary contacts to indicate its status. A contact between terminals 13 and 14 indicates when the IT. is in bypass (unless it has been programmed to indicate another status). The contacts between terminals 95 and 96 and 95 and 98 indicate the IT. is in a normal or tripped state (unless it has been programmed to indicate another status). Often these contacts are used as shown in Figures 3-15, 3-16 and 3-17 with indicating lamps. In some installations the user may wish to use an electromagnetic relay for indication of the status at a remote location for use by a programmable controller (PLC), or in a 230V AC or 24V DC control circuit.
If the IT. Soft Starter is subject to mechanical shock during operation, it is possible that these contacts may momentarily open, causing nuisance fault tripping of down stream devices. When used with an indicating lamp, a momentary contact opening would not be observed. In order to assure proper application, it is suggested that the following recommendations be followed:
MN03902002E
For more information visit: www.EatonElectrical.com
3-21
IT. S811 Soft Starter User Manual
PLC Interface — It is suggested that a 20 mS delay be programmed to assure the contact status before a change of status is indicated. The application and the environmental issues will determine the exact requirements.
24V DC Control — When a relay is used in conjunction with an electronic control, it is highly recommended that a noise suppression/snubber diode be placed across the relay coil as shown in Figure 3-18. This diode offers two benefits. First, the suppression of any electrical noise generated when the relay coil is de-energized. Second, the diode delays the opening of the relay slightly as it dissipates the energy stored in the relay coil. This delay is often long enough to compensate for the potential effects of a mechanical shock opening the control contact. A typical suppression diode is a 1N4001.
November 2006
24V DC Supply
13
R
14
+
95
R
96
R
98
Bypass
Ready
Fault
Figure 3-18: 24V DC Control
120V AC Control — When a relay is used in conjunction with an electronic control, it is highly
recommended that a noise suppressor be used across the relay coil. In the case of an AC coil, the noise suppressor is made up of a series connected resistor and capacitor as shown in Figure 3-19. Usually the delay in the relay opening is very small, so if the system is subject to shock, a delay should be added in the external control before the contact change of state is recognized. The resistor is rated 100 ohms at 0.5 watts. The capacitor is 0.25 µF at 250V AC.
120V AC
Supply
13
R
14
+
95
R
96
R
98
Bypass
Ready
Fault
Figure 3-19: 120V AC Control
Using a Supplemental Line Contactor
In some installations, it may be necessary to use an electromagnetic contactor in series with the soft starter. In this case, it is recommended that the contactor be placed on the load side of the soft starter. The contactor must be closed prior to starting the soft starter and remain closed until the Soft Starter has been stopped to ensure proper soft starter and system operation.
3-22 For more information visit: www.EatonElectrical.com
MN03902002E
November 2006
IT. S811 Soft Starter User Manual
If an electromagnetic contactor is used on the line side of the soft starter, additional control circuitry must be supplied by the user when using edge control to ensure the line power is supplied to the soft starter before control power (24V DC) is applied. If this sequence is not followed, the soft starter will fault on either a phase loss or zero voltage-crossing fault. This control scheme is illustrated in Figure 3-20.
If it is desired to place an electromagnetic contactor on the line side of the soft starter, when using level control, no additional control circuitry is required. A start can be completed when the line power is supplied to the unit after the control power (24V DC), providing the Reset Mode parameter is set to AUTO and the unit has a green light status with +24V DC on pin 1.
If the AUTO Reset Mode setting is used, CAUTION must be exercised to assure that any restart occurs in the safe manner.
MN03902002E
For more information visit: www.EatonElectrical.com
3-23
IT. S811 Soft Starter User Manual
November 2006
120V AC
24V DC
Line Connected
480V AC
Mains
Inside-the-Delta Connected
L1
Field AC
Mains
L2
L3
STOP
(On Delay -6 Seconds)
(Isolation Contactor)
X
Fusible Disconnect
Circuit Breaker
or Terminal Block
(Side Adder #1)
T
STAR T
X
X
T
Soft-Starter
24V
PP
1
Auto­Reset = ON
L1
L2
L3
L1
L2
L3
Isolation
Contactor
T1
T2
T3
T1
T2
T3
Motor
T6
Inside-the-Delta Connected (Optional for Frame Sizes S811T S811V)
L1
Field AC
Mains
L2
L3
Fusible Disconnect
Circuit Breaker
or Terminal Block
Figure 3-20: 24V DC Control with Edge Sensing
3-24 For more information visit: www.EatonElectrical.com
L1
T1
L2
T2
L3
T3
Isolation
Contactor
T4
T5
T1
T2
T3
Motor
T6
T4
T5
MN03902002E
November 2006
Chapter 4 — Specifications
Environmental
Table 4-1: Environmental Specifications
Item Specification
Temperature Range —
Operating Storage
Elevation Up to 6,600 ft. (2000m). Above
Humidity Functional to 95% non-condensing Operating Orientation Any Pollution Degree IEC 60947-1 3 Shock Resistance 15g in any direction Vibration Resistance 3g in any direction
IT. S811 Soft Starter User Manual
-40°F – 122°F (-40°C – 50°C)
-58°F – 158°F (-50°C – 70°C)
6,600 ft. (2000m), derate 0.5% per 330 ft. (100m)
Physical
Table 4-2: Weight
Frame Size Weight of Unit
N 5.8 Lbs. (2.6 Kg) R 10.5 Lbs. (4.8 Kg) T & U 48 Lbs. (21.8 Kg) with lugs
41 Lbs. (18.6 Kg) without lugs
V 103 Lbs. (46.8 Kg) with lugs
91 Lbs. (41.4 Kg) without lugs
Table 4-3: Agency Standards and Certifications
Standard Certifications
UL UL 508 CSA CSA 22.2 – 14 – 1995 IEC 60947-4-2 CE See Table 4-4
MN03902002E
For more information visit: www.EatonElectrical.com
4-1
IT. S811 Soft Starter User Manual
CE Conformance
Table 4-4: EMC Immunity
Immunity Severity Level
November 2006
Electrostatic Discharge IEC 61000-4-2
Electromagnetic Field IEC 61000-4-3
Fast Transient Bursts IEC 61000-4-4
1.2/50 µS – 8/20 µS Surges IEC 61000-4-5
Conducted RF IEC 61000-4-6
50 Hz Magnetic Field IEC 61000-4-8
Voltage dips Interrupt IEC 61000-4-11
Emissions
Radiated EN 55011, Class A Conducted EN 55011, Class A
4 kV contact discharge 8 kV air discharge
10 V/m 80 – 1000 MHz 2 angles
2 kV, 5 kHz rep, 2 min intervals
2 kV Line to earth 1 kV Line to Line 1 minute intervals
10 V rms .15 – 80 MHz
N/A
30% dip @10 mS 60% dip @100 mS 100% interrupt @5 S
1. The 24V DC power supply must be grounded.
2. Add ferrite, Fair-Rite #0444173551 to DC Power Leads and Control I/O Leads (all through one ferrite) at S811 with two passes through ferrite of the DC Power Leads, and a single pass through ferrite of the I/O Control Leads.
3. Add ferrite, Fair-Rite #0443167251 to Load Leads at S811 with two passes through ferrite.
4-2 For more information visit: www.EatonElectrical.com
MN03902002E
November 2006
Short Circuit Ratings
Table 4-5: Short Circuit Ratings
Soft Starter Frame Size
N 10 kA 10 kA 10 kA — R 10 kA 10 kA 10 kA — T 18 kA 18 kA 18 kA U 30 kA 30 kA 30 kA — V 42 kA 42 kA 42 kA
Catalog No. S811T__V3S devices are UL Listed and suitable for use on a circuit capable of delivering not more than 18 kA symmetrical amperes, 690 volts maximum, when protected by a Ferraz-Shawmut Amp-Trap Form 101 (Cat. No. A70QS800-4) 800 Amp, 700 Volt Semiconductor Protection Fuse.
Catalog No. S811V__V3S devices are UL Listed and suitable for use on a circuit capable of delivering not more than 42 kA 690 volts maximum, when protected by a Ferraz-Shawmut Type PSC (Cat. No. A070URD73I1600) 1600 Amp, 700 Volt Semiconductor Protection Fuse.
Catalog No. S811T__V3S devices tested per IEC 60947-4-2 to Type 1 Short Circuit Withstand Requirements to 18 kA, 690 volts with Cutler-Hammer Cat. No. NW3800T33W 800 Amp 690 Volt circuit breaker.
Catalog No. S811V__V3S devices tested per IEC 60947-4-2 to Type 1 Short Circuit Withstand Requirements to 42 kA, 690 volts with Cutler-Hammer Cat. No. RW420T33W 2 kA 690 Volt circuit breaker.
IT. S811 Soft Starter User Manual
Three-Phase Short Circuit Rating
240V 480V 600V 690V
 
 
Note: Short circuit protection must be applied on the line side of the soft starter.
MN03902002E
For more information visit: www.EatonElectrical.com
4-3
November 2006
Chapter 5 — Functional Description
Power
The S811 Soft Starter controls the voltage applied to a three-phase induction motor in order to control the starting torque and provide a smooth starting characteristic. Within the soft starter are three power poles, each of which includes a set of anti-parallel SCRs (thyristors) in parallel with a contact. During a start, the conduction periods of the SCRs are continuously adjusted to apply a gradually increasing voltage to the motor, resulting in gradually increasing torque and a smooth start. As the motor reaches its rated speed, the power pole contacts are closed, bypassing the SCRs for the most efficient operation.
IT. S811 Soft Starter User Manual
Control
T3
T2
T1
Motor
3-Phase
AC Line Voltage
L3
L2
L1
Figure 5-1: Line Connected Soft Starter SCRs
For each start, the length of time the SCRs are conducting current as well as the magnitude of that current determine how hot the SCRs will get. Between successive starts the SCRs must cool down to avoid exceeding their thermal limits. Appendices C and D (Ratings, Cooling and Power Losses) gives the S811’s application ratings for various starting conditions. Staying within these specified limits should avoid over temperature trips.
When the S811 control circuit senses that the internal temperature has increased above a preset value, internal fans are tuned on to assist in cooling. To maximize fan life the fans are only turned on when needed. Further discussion of fan operation can be found in Appendices C and D.
The software contained in the S811 IT. Soft Starter is the heart of the product. This software allows you to control nearly every aspect of the soft starter’s functionality. In this section, various features and protection options are described.
MN03902002E
Note: In the following descriptions the S811 Parameter Names are shown in italics. You will
find a complete listing of these parameters in Appendix A.
Note that the motor current measurements made with a standard meter may not be correct because of the non-sinusoidal nature of the current during starting. The S811 is designed to accurately measure these currents so that the current displayed by the S811’s Digital Interface Module (DIM) is correct.
For more information visit: www.EatonElectrical.com
5-1
IT. S811 Soft Starter User Manual
Starting Options
The following starting choices are available in the S811 IT. Soft Starter:
Voltage Ramp Start
This is the most commonly used mode of soft starting. Starting at an initial value set by the Initial Torque parameter, the voltage applied to the motor is gradually increased at a rate that will reach rated voltage at time tr, set by the Soft Start Time parameter. As the voltage increases the motor develops torque that accelerates the load toward full speed. When the S811 senses that the motor has come up to speed, it quickly completes the voltage ramp and closes the bypass contactor. See Figure 5-2.
It should be noted that a lightly loaded motor takes less torque, and thus lower voltage and time, to accelerate to full speed. For this case the S811 will go into bypass before the ramp reaches full voltage. In other words, the S811 will go into bypass before the Soft Start Time has elapsed.
Kick Start To rq
100%
Voltage
Ramp
Bypass Bypass
Rated
Voltage
100%
November 2006
Torque
Initial
To rq ue
Soft Start Time
Kick Start Time
Start Run
Time (Seconds)
t
r
Speed
Start Run
Time (Seconds)
Figure 5-2: Ramp Start
Kick Start — The Kick Start feature works in both the Voltage Ramp Start and Current Limit
Start modes. By momentarily applying a pulse of current to the motor, it provides an initial boost in torque to overcome the static friction common in some applications. The level of torque boost is set by the Kick Start Torq parameter and the duration of the “kick” is set by the Kick Start Time. Setting the Kick Start Time to 0 disables this feature.
5-2 For more information visit: www.EatonElectrical.com
MN03902002E
November 2006
IT. S811 Soft Starter User Manual
Current Limit Start
This mode is typically used when it is necessary to limit the maximum current during start-up due to line power limitations or other considerations. During a Current Limit Start the S811 applies a constant voltage to the motor, resulting in limited current flowing through the motor’s windings. The level of current is set by the Initial Torque parameter. See Figure 5-3.
Note: Current Limit Starts are not recommended on variable torque load applications like
fans and pumps.
Kick
Start
To rq
Initial
To rq ue
100%
Current
Soft Start Time
Kick Start Time
Start Run
Bypass Bypass
100%
Speed
Start Run
Time (Seconds) Time (Seconds)
Figure 5-3: Current Limit Start
Soft Stop — This feature is used for applications that require a controlled extended stop. It is
designed for high frictional loads that tend to stop suddenly when voltage to the motor is removed. During Soft Stop the voltage is gradually reduced to zero in the time set by the Soft
Stop Time parameter. See Figure 5-4.
Note: The Soft Stop mode is not an electronic brake function and will not stop a motor any
faster than it would normally take to coast to a stop under load.
MN03902002E
Coast to Stop
100%
Speed
Run Soft Stop
Time (Seconds)
(Speed)
Soft Stop Ramp
(Voltage)
Soft
Stop Time
Figure 5-4: Soft Stop
Pump Start/Stop (Optional) — This pump control option is described in Appendix F.
For more information visit: www.EatonElectrical.com
5-3
IT. S811 Soft Starter User Manual
Protection
Thermal Overload
The IT. S811 Soft Starter features an electronic motor overload protection feature. It is designed to protect the motor and power wiring against overheating caused by operating at excessive current levels for extended periods of time.
Entering the motor’s full load current rating, using the Overld Trip FLA parameter programs the overload. The Overld Trip FLA is settable from 32% to 100% of the S811’s rated current.
The overload’s trip class is set using the Ovrld Trip Class parameter. Additional details on the Thermal Overload can be found in Appendix B.
S811 and Motor Protection
In addition to motor overload protection, the S811 has many programmable features designed to protect the motor as well as the soft starter itself.
Incoming Line Phase Reversal, Loss, Imbalance, Over Voltage, and Under Voltage trips
Three Overcurrent trips
Stall and Jam trips
November 2006
For troubleshooting purpose trips are recorded, as they occur, in the S811’s Device Status, Fault List and Fault Queue.
QCPort Network Control
The S811 has two QCPort communications ports, Local (CH1) and Remote Network (CH0).
Local Control (HAND)
S811 Local Control usually consists of the terminal block and one DIM connected to the Local Port (CH1). Additional DIMs, QCPort Cover Controls, as well as other QCPort devices can be connected to the Local Port and used as input devices to control the operation of the S811. Each device sends a Motor Control byte to the S811 which logically combines them and responds appropriately.
Remote Network (AUTO)
The S811 will switch to AUTO control whenever all local control devices have released (de-energized) their LOCAL control signal. When the S811 is in AUTO control it is ready to respond to motor control commands issued through the Remote Network (CH0). Typically an industrial automation fieldbus is connected to the Remote Network port via one of the many network adapters (gateways) available from Eaton.
For further discussion of the network ports, refer to Appendix H.
5-4 For more information visit: www.EatonElectrical.com
MN03902002E
November 2006
Chapter 6 — Configuration
Programming the S811
A Digital Interface Module (DIM) is used to configure all models of the IT. S811 Soft Starter.
The Status Bar at the top of the display indicates the operating and communicating
status of the S811 and DIM.
The three Soft Key Functions at the bottom of the display indicate the functions of the
Soft Keys (pushbuttons) directly below them. The Soft Key Functions will change as you navigate through the different menus of the DIM.
The center of the display shows the value of the selected S811 parameter. The default
display at power-up is “3 ø Line Currents”.
Figure 6-1 shows how the S811’s parameters are organized within the menu structure.
Navigating through the menus down to the parameters is straightforward if you understand a few basic concepts.
1. The Escape Key (ESC) moves you from the User Display to the Parameter Edit Screen.
IT. S811 Soft Starter User Manual
2. The PREV and NEXT soft keys (Figure 6-2) scroll from menu to menu (left and right).
3. The far right soft key will allow you to take action (Enter, Edit, More, Send, …) to “drill down” into the menu or parameter.
4. When you enter a menu, the Previous and Next soft keys scroll from parameter to parameter (up and down) in that menu.
5. The Escape Key backs you out of the current parameter or menu.
ONLN SS OXFDO1 H STOP 3 Line Currents
XXXX L1 Amp XXXX L1 Amp XXXX L1 Amp
JOG RESET H->A
ESC
Status Bar
Soft Key Functions
Soft Keys
Predefined Keys
Figure 6-1: Digital Interface Module (DIM) — Display Mode
MN03902002E
For more information visit: www.EatonElectrical.com
6-1
IT. S811 Soft Starter User Manual
November 2006
Figure 6-2: Digital Interface Module (DIM) — Parameter Edit Mode
For a more complete description of the DIM, refer to Appendix G.
S801 to S811 Comparison
If you are familiar with the adjustments of the S801 Soft Starter, Table 6-1 provides you with a cross-reference between the CIM potentiometer and switch adjustments and the corresponding S811 parameters found in the Configuration and Protection menus of the S811’s Digital Interface Module (DIM).
Table 6-1: S801 to S811 Setup Cross-Reference
Description S801 CIM
Configuration Menu
Overload setting
OL Trip Class Trip Class Ovrld Trip Class 5, 10, 20 and 30 Kick Start
Torque Kick Start Time tk Kick Start Time Sec Sets the duration of the Kick Start Initial Voltage
Ramp Torque Current Limit
Torque
Voltage Start Ramp Time
ONLN SS OXFDO1 H STOP
Monitoring
PREV
NEXT ENTER
ESC
Status Bar
Soft Key Functions
Soft Keys
Predefined Keys
S811 DIM Parameter Units Comment
FLA Overld Trip FLA Amps Set for motor’s nameplate rated
current assuming a 1.15 Service Factor motor. See Appendix C for other Service Factor motors.
T1 Kick Start Torq % rated torque Sets the initial breakaway torque to
overcome static friction loads.
T2 Initial Torque % rated pull-
out torque
T2 Initial Torque % rated pull-
out current
Sets the initial voltage (torque) of the Voltage Ramp Start.
Sets the constant current (torque) applied to the motor throughout its acceleration to full speed.
tr Soft Start Time Sec Sets the time to ramp up to rated
voltage (torque). If the motor is not up to speed at the end of the ramp, the S811 will trip on a Stall Fault. Note: Lightly loaded motors will reach full speed, and the bypass contactor will close, before tr elapses.
6-2 For more information visit: www.EatonElectrical.com
MN03902002E
November 2006
Table 6-1: S801 to S811 Setup Cross-Reference, continued
Description S801 CIM
Configuration Menu, continued
Current Limit
tr Soft Start Time Sec Sets the time at which the S811
Start Time
Stop Ramp
ts Soft Stop Time Sec
Tim e
Pump Stop
ts Pump Stop
Time (option)
Protections Menu
Overload Overload Ovld Fault Jam Jam Jam Fault Stall Stall Stall Fault Phase Loss Ph. Loss Phase Loss
Phase
Phase Imb
Imbalance Phase
Ph. Rev Phase Rev Fault See also Phase Sequence Sequence Reversal
Fault Reset Man/Auto
Reset Special
Function Ramp / Current
Ramp Start Start Method Limit Start
Option — Configuration Menu
Option S811 DIM
Edge/Level Start Input
S811 DIM Parameter Units Comment
Sec Sets the time to ramp down the
Tim e
Fault
Fault
Reset Mode
Default
parameter
Start Control Level Sets whether the Start input at the
IT. S811 Soft Starter User Manual
expects the motor to be up to speed. When tr elapses the S811 checks for a stall condition.
Sets the time to linearly ramp down from rated voltage to zero. The rate at which the motor slows is dependent on the load. Not functional on S811s with Pump Option if start method is Pump Start.
speed of the motor to zero. Not functional on standard S811s. S811s purchased with the pump stop option must set the DIM Start Method to Pump Start to activate the Pump Stop option.
terminal block responds only when it sees a transition from 0 to +24V DC (edge) or anytime 24V DC is present (level)
MN03902002E
For more information visit: www.EatonElectrical.com
6-3
November 2006
Chapter 7 — Setup and Starting
Before You Begin
Be Aware of the Following:
1. Terminal P must have 24V DC applied to ENABLE starts.
2. The P and Hand inputs must be energized (24V DC) to enable starting of the Soft Starter from the terminal block.
3. To Start: Apply 24V DC to Input 1 while the P input is energized.
4. To initiate a Stop remove the P input.
5. For 2-wire control, jumper P and Input 1 together.
6. After an Overload Trip, the S811 Soft Starter cannot be restarted until the prescribed cool-down time has elapsed. Cycling power does not reset the timer. If 24V DC power is removed, the soft starter will remember the remaining time and will resume the cool­down timing when power is again reapplied.
7. On frames R, T, U and V when the S811 goes into bypass, a sound similar to contactor chatter can be heard. This sound is the result of multiple contactors closing one after the other in a very short period. It is normal operation intended to reduce the surge current requirements of your power supply.
IT. S811 Soft Starter User Manual
Setup
8. To Jog: apply 24V DC to input 2, (terminal P must also have 24V applied). To stop remove 24V DC from input 2.
9. In jog, the unit will follow the normal start ramp as long as terminal 2 is at 24V DC.
10. Jog operates the same as a normal start, except that the bypass contactors will not close and the soft stop is not functional.
11. Jog is only intended for short term jogging of the motor and not for long term two-wire control.
After all power and control connections have been made and you have read and understood the different operating modes and protection features (Chapter 5) of the soft starter, it is time to program it for your application. The following procedure will take you through the setup of the S811 to match it to your motor and application, “bumping” the motor to verify correct direction of rotation, and tuning of the selected operating mode. After this procedure has been completed, it is suggested that you review the Protection Options of the S811 (Appendix B) and select the appropriate ones for your application. All Protection Options are shipped from the factory “enabled”.
As shipped from the factory, the S811 Soft Starter’s default configuration is sufficient for basic operation but may require some configuration to “tune” it for your application. The following procedure assumes you understand how to “navigate” through the S811’s parameter menu using the Digital Interface Module (DIM) and that the S811 is in its Factory (Out-of-Box) state. Refer to Appendix G of this manual for a detailed explanation of DIM operation.
MN03902002E
For more information visit: www.EatonElectrical.com
7-1
IT. S811 Soft Starter User Manual
Initial Configuration:
1. It is suggested that the S811 Soft Starter be configured before applying the line voltage. Before applying the Line voltage, apply 24V DC to the + and - connections of the S811’s terminal block. “Eaton Cutler-Hammer” will be displayed by the DIM while the S811 is powering up. When power-up is complete the DIM should be displaying “3 Ø Line Currents”.
Note: If anything else is displayed, go to Chapter 8, Troubleshooting, for information on
getting the S811 back to a known state.
2. Using the DIM, review the parameter settings in the “Soft Start Confg”, “Overload Config”, and “Protection Setup” menus. Parameter navigation and menus are located in Appendix A and G. The following setup procedures will use the factory default settings unless changed by you.
3. In the Overload Config menu, set the Overld Trip FLA parameter to the motor’s nameplate rated current. This setting assumes the motor has a 1.15 Service Factor.
4. Set Ovrld Trip Class parameter for the desired overload trip characteristic (curve).
5. In the Protection Setup menu set the Motor Rated Volt parameter to the motor’s operating voltage.
November 2006
6. If auto fault reset is required, set the Reset Mode parameter in the Soft Start Confg menu to Auto (and Start Control to Level (default)). NOTE: Auto Reset is intended for unattended installations where there is no danger to personnel or other equipment when the motor starts without warning. If Auto Reset is enabled, CAUTION must be exercised to assure that any restart occurs in a safe manner.
7. Apply the Mains voltage and verify that no fault is present. If a fault is indicated, display the Diagnostics menu’s Device Status parameter to determine the source of the fault. Each fault is described on Page 8-6.
a. A Phase Reversal Fault is a likely candidate on new installations. It can be remedied
by either changing the Phase Sequence parameter from ABC to ACB in the Protection Setup menu or removing Mains power and switching the incoming line connections at L1 and L2 of the S811.
8. Quickly Jog (bump) the motor just enough to verify that the direction of rotation is correct. If it is not, remove all power to the S811 and the motor and swap two of the motor’s winding connections.
9. Based on the desired starting mode, Voltage Ramp or Current Limit, complete the configuration of your S811 using the Soft Start Confg menu:
a. Voltage Ramp Start Configuration
i. Initial parameter settings:
Start Method = Voltage Ramp. Initial Torque = 50% Soft Start Time = 60 sec Kick Start Torq = 0% (fans and pumps), 75% (high breakaway loads) Kick Start Time = 0 sec (fans and pumps), 1 sec (high breakaway loads) Soft Stop Time = 60 sec
7-2 For more information visit: www.EatonElectrical.com
MN03902002E
November 2006
Peligro alto voltaje
IT. S811 Soft Starter User Manual
ii. Start the motor and determine the worst case starting conditions. Adjust Initial
Torque for smooth start without hesitation. Rotation should begin within 2 seconds.
iii. If Stall Faults occur at the end of the ramp time, increase Initial Torque, Kick
Start Torq & Time and/or Soft Start Time to get into bypass before the Soft Start Time elapses. Also, verify that the motor is not overloaded.
iv. Adjust the Soft Stop Time for the desired stopping time.
b. Current Limit Start Configuration
v. Initial settings:
Start Method = Current Limit Initial Torque = 50% Soft Start Time = 120 sec Kick Start Torq = 0% Kick Start Time = 0 sec (disabled) Soft Stop Time = 60 sec
vi. Start the motor and determine the worst case starting conditions. Adjust Initial
Torque for smooth start without hesitation. Rotation should begin within 2
seconds and the motor should smoothly accelerate to full speed.
vii. If Stall Faults occur, increase Initial Torque and/or Soft Start Time to get into
bypass before the Soft Start Time elapses. Also, verify that the motor is not overloaded.
viii. After suitable performance has been achieved, determine the starting time to
bypass and set Soft Start Time at 1.25 times this time. For example, if it takes 10 seconds to accelerate the motor and go into bypass, set the Soft Start Time for
12.5 seconds.
ix. Adjust the Soft Stop Time for the desired stopping time.
10. Review the Protection Options of the S811 and configure the appropriate ones for your application. Refer to Table A-5 on Page A-6 for the list of parameters used in configuring the protections features on your S811 Soft Starter. These parameters are located in the Protections menu of the DIM.
11. The S811 can be operated from a remote automated network. For network configuration details refer to Appendix H of this manual.
Danger High Voltage Danger Haute Tension
The S811 has the ability to respond to commands from an automated network controller. Consequently the soft starter may start unexpectedly in response to these commands. To insure the safety of personnel and equipment, always remove power before accessing the electrical and/or mechanical equipment.
Le S811 à la capacité de répondre aux commandes d’un contrôleur de réseau automatisé. Donc le démarreur progressif peut démarrer soudainement en réponse à ces commandes. Pour s’assurer la sécurité du personnel et de l’équipement, toujours débrancher l’alimentation avant d’accéder à l’équipement électrique et/ou mécanique.
El S811 tiene la capacidad de responder a comandos de un controlador de red automatizado. Por lo tanto, el arrancador suave podría arrancar de improviso en respuesta a estos comandos. Para garantizar la seguridad del personal y del equipo, siempre desconecte la energía antes de acceder al equipo eléctrico o mecánico.
MN03902002E
For more information visit: www.EatonElectrical.com
7-3
IT. S811 Soft Starter User Manual
12. Refer to Appendix H of this manual for additional details on each of the S811’s software parameters.
13. For additional support contact Customer Support.
November 2006
7-4 For more information visit: www.EatonElectrical.com
MN03902002E
November 2006
Advertencia
Peligro alto voltaje
Chapter 8 — Troubleshooting
General
In this section of the manual, we present a procedure you can follow to diagnose a problem with your S811.
While many potential situations are outlined in this section, it is possible you may run into a problem that is not covered here. If you have worked through the following troubleshooting procedure and find that you require further assistance, please contact Eaton.
Please have the following information ready when you call:
Order No. (if available): Catalog Number: Style Number: Serial Number:
Before You Begin to Troubleshoot
IT. S811 Soft Starter User Manual
Warning Avertissement
Make sure you read and understand the procedures in this manual before you attempt to operate or set up the equipment.
Bien lire et comprendre les procédures contenues dans ce manuel avant de tenter le fonctionnement ou la mise en place de l’équipement.
Asegúrese de leer y entender los procedimientos en este manual antes de intentar operar o configurar el equipo.
Danger High Voltage Danger Haute Tension
Do not work on energized equipment unless absolutely required. If troubleshooting procedure requires equipment to be energized, all work must be performed by properly qualified personnel, following appropriate safety practices and precautionary measures.
Ne pas travailler sur d’équipement sous tension sauf si c’est absolument nécessaire. Si des méthodes de dépannage exigent que l’équipement soit sous tension, tout travail doit être faire par du personnel qualifié, suivant des pratiques de sécurité et des mesures de précaution appropriées.
No trabaje en equipos en funcionamiento, a menos que sea absolutamente necesario. Si un procedimiento de solución de problemas requiere que el equipo permanezca encendido, todo el trabajo lo debe realizar personal adecuadamente calificado, respetando las prácticas de seguridad y las medidas preventivas correspondientes.
We highly recommend that you read this entire section of the manual before you begin to troubleshoot the IT. Soft Starter.
You may want to obtain the following equipment to aid you in troubleshooting:
Multimeter
MN03902002E
Clamp-on ammeter
Always assume the S811 has high voltage applied and take proper precautions while troubleshooting the soft starter and associated equipment. Read all precautions at the front of this manual before starting the troubleshooting process.
For more information visit: www.EatonElectrical.com
8-1
IT. S811 Soft Starter User Manual
The S811 Soft Starter can not be started until all faults have been reset. If a fault condition persists, fault reset is not possible and the Status LED remains red. Also, a local start requires that the start source (DIM, terminal block, Cover Control or other similar device) be in HAND mode (L bit in Motor Control Byte = 1). Pressing the START button on the DIM automatically puts that device in HAND.
Define the Problem
1. The S811 Soft Starter fails to respond in any way to a start command. Look at the front panel of the S811 Soft Starter and determine the state of the LEDs. The following troubleshooting flowcharts will walk the troubleshooter through each step and suggest probable solutions to each problem.
Start
No Yes
Are any LEDs lit?
November 2006
a. Check the 24V Power Supply
What color is
the status LED?
Red
b. Check the Fault in Device Status and Attempt to Clear
End
Green
c. Determine Source of Start
Figure 8-1: Start Command Troubleshooting Flowchart
a. Check the 24V DC power supply for proper operation. Is the 24V power supply
connected to the proper power source? Measure the 24V DC at the output terminals and on the soft starter input terminals. Check the screw terminal connections and polarity of the wiring. See Troubleshooting — Status LED OFF, Table 8-2.
8-2 For more information visit: www.EatonElectrical.com
MN03902002E
November 2006
IT. S811 Soft Starter User Manual
b. With the status LED red, the device will not start. Attempt to reset the S811 Soft
Starter by pressing the S811’s recessed RESET button for one second or pressing the RESET soft key in the Display Mode screen of the DIM. If the LED remains red, use the DIM to determine the fault code and go to the Troubleshooting Fault Table, Table 8-4, to find the corrective action for each fault code.
c. The LED is green and the S811 Soft Starter is ready to start. Find the Start source in
Table 8-1 to determine the appropriate corrective action. Verify that the “P” input terminal is at 24V DC. Then try to start the S811 using the DIM.
Table 8-1: Start Command Troubleshooting
Start Source Attempted Suggested Corrective Action
DIM • Verify the “P” (Permissive) input terminal is at 24V DC, either hard
wired or wired through a normally closed STOP button.
• Verify no other motor control device is preventing a start by clearing its permissive bit. Disconnect any other QCPort device that may prevent a start and purge
them from the S811’s device list. This takes these
devices out of the system and simplifies troubleshooting.
Connector Terminal Block • Verify the “P” input terminal is at 24V DC when the start is attempted.
• Verify the “3” input terminal is at 24V DC when start is attempted.
• Verify 24V is applied to the “1” input terminal when the start is attempted.
• If the Start Control parameter is set to Edge, verify the “1” input terminal sees a transition from 0V to 24V after all faults have been reset and the above conditions have been verified.
• Verify no other motor control device is holding its permissive at 0. If it is, force its permissive = 1 or temporarily remove it from the S811 and
Other QCPort Motor Control Node
purge
• Remove all external QCPort devices, purge device list and attempt a start from the DIM. If the start is not
it from the S811’s device list.
them from the S811’s
successful, see DIM category above. Once that start is successful, reattach QCPort device(s) and retry start.
Fieldbus (DeviceNet, Profibus, etc.)
• Determine if the S811 can be started locally using the DIM.
• Verify that the S811 was in AUTO when the fieldbus start was attempted (all motor control devices having their L bits = 0).
• Verify no other motor control device is holding its permissive at 0. If it is, force its permissive = 1 or temporarily remove it from the S811 and
purge
Unplugging any source of motor control from QCPort will require that it be “purged” from the S811’s motor control command device list (press and hold the S811’s recessed RESET button for six seconds).
it from the S811’s device list.
MN03902002E
2. The S811 Soft Starter trips during starting and never reaches bypass. Use the DIM to determine the Device Status fault code and go to the Troubleshooting Fault Table, Table 8-4, to find the corrective action for each fault code.
3. The S811 Soft Starter trips during running operation while bypass contactors are engaged. Use the DIM to determine the Device Status fault code and go to the Troubleshooting Fault Table to find the corrective action for each fault code.
4. The S811 Soft Starter trips after the stop is commanded. Use the DIM to determine the Device Status fault code and go to the Troubleshooting Fault Table to find the corrective action for each fault code.
5. The S811 Soft Starter stops sooner than expected during a soft stop. If the Soft Stop Time is set too long for the motor loading, the motor will begin to stall when delaying SCR firing reduces the voltage. The S811 Soft Starter will detect this stalling and end the stop immediately and not set any faults.
For more information visit: www.EatonElectrical.com
8-3
IT. S811 Soft Starter User Manual
November 2006
Start
Consult
“Status LED OFF
Table, Ta ble 8-2
What is the
condition of the
STATU S LED?
Green
Consult
ì Status LED GREEN
Table, Ta ble 8-3
Ye s
indicate a
Ye
Did the
No
Consult
Is the S811 continually
resetting?
No
s
No Yes
RedOff
Does the DIM
"Device Status"
fault code?
Depress either
RESET Button
fault clear?
Fault Table
Is Channel 0
connected
to a network?
Ye s
Disconnect Channel
0 from the Network
Does the
resetting stop?
Ye s
Reset the Node ID,
Baud Rate, and
Mode on Channel 0.
Consult Resetting
the S811 Tabl e
No
No
Is the DIM
connected and
Communicating
to the S811?
No
Cycle S811 24V DC
Control Power
After 30 seconds,
did the DIM
reconnect to the
S811?
Ye s
Go to Start
End
Figure 8-2: Main Troubleshooting Flowchart #1
Ye s
No
Call Eaton
Support
8-4 For more information visit: www.EatonElectrical.com
MN03902002E
November 2006
IT. S811 Soft Starter User Manual
Table 8-2: Troubleshooting – Status LED OFF
Symptom/Indication Possible Problem Possible Solution
All LEDs never illuminate The terminal block screws are not
Status LED never illuminates but CH0 and CH1 LEDs are actively flashing
Status LED and CH1 LED never illuminate, CH0 LED is constantly illuminated
CH0, CH1 LEDs never illuminate, Status LED illuminates
secure, not connected to proper terminals, reversed polarity. Possible Control Board failure.
Status LED is defective. S811 can operate properly with a
Communications Firmware failure. Possible fatal device failure.
LED failure, communication failure on the Port.
Check control wiring. Verify the S811 24V DC power is present on the terminal block, the polarity is correct, and all terminals are tight. Possible fatal device failure.
non-operational LED. Use DIM to observe the fault status of the S811. Possible fatal device failure.
S811 may still operate properly with a non-operational LED. Possible fatal device failure.
Table 8-3: Troubleshooting – Status LED GREEN
Symptom/Indication Possible Problem Possible Solution
Status LED green but S811 is not responding to Start from field wiring
Status LED green but S811 is not responding to Start from field wiring
Status LED green but S811 is not responding to Start from field wiring, DIM or network
Terminal block Hand input is low. Check control wiring. To assert local
24V is not being applied to the field wiring Start, Jog or Permissive terminal.
A network device or field wiring is holding permissive low.
control apply a constant 24V to the terminal block Hand input terminal 3.
Verify if the soft starter is configured for Level sensitive or Edge sensitive field wiring.
• If commanding Start or Jog with Level Sensitive Inputs: Check field wiring. Make sure terminal P, terminal 1, and terminal 3 have 24V applied.
• If commanding Start with Edge Sensitive inputs: Make sure terminal 1 cycles from low to high while P and terminal 3 remain high.
Make the field wiring permissive on the S811 and any cover controls are at 24V. Verify all hand control devices are sending permissive. A 0V permissive on any motor control device will inhibit a start or stop a running motor.
MN03902002E
For more information visit: www.EatonElectrical.com
8-5
IT. S811 Soft Starter User Manual
Fault Codes
Table 8-4: Troubleshooting Fault Table
Fault Code Possible Problem Possible Solution
1 Firmware Incompatibility or Hardware failure. Call Eaton support. 3 Internal Communications Fault –
Communications to DSP have been interrupted. Possible electrical noise or hardware failure.
4 Low Control Voltage Fault – The external 24V
power supply voltage is dropping below the minimum required to control the motor.
5 Power Pole Over Temperature Fault – The S811
has detected the internal SCR temperature is excessive. Operating environment above specified maximum temperature, ventilation holes blocked, fans are not operational, starts per hour exceed specifications, sensor failure on circuit board, bypass contactor(s) failed to close.
6 Phase Loss Fault – Extreme phase imbalance
condition. Incoming phase disconnected, blown fuse.
7 Phase Imbalance Fault – The imbalance of the
incoming phases exceeds the trip threshold.
9 Under Load Fault – Current supplied to the
motor is below trip threshold. Linkage or belt driven by motor is broken, a clutch or other load engagement device is not operating, the motor is not loaded to the trip current.
10 Over Current Fault – only active in bypass if the
Jam Fault is disabled. Current exceeds the fault threshold.
11 Jam Fault – While in bypass an obstruction has
slowed or stalled the motor resulting in extreme motor current.
13 Bypass Failure Fault – S811 detected that the
internal bypass contact(s) did not close. Possibly opened due to excessive shock or 24V DC control voltage sag (insufficient voltage to maintain contact closure).
November 2006
Try a 24V DC control voltage power cycle to attempt to clear problem. Verify that the S811 is properly grounded. Call Eaton support if the problem persists.
Use recommended 24V power supplies with enough current sourcing capability to close contactors. Verify correct wire size used to connect power supply to S811. (See power supply specification for more details.) Verify connections are secure.
Ventilate to specified maximum temperatures, clear obstructions, verify fans are operational, verify control system is not exceeding the specified maximum starts per hour.
Repair broken connection, replace fuse.
Correct imbalance problem with mains. Increase the xx Imbalance Fault xx parameters or disable the fault if the other issues cannot be resolved. Make sure your system can tolerate the imbalance.
Repair/replace broken belts, linkage, or clutch, and/or increase load. Reduce Low I Trip % FLA to an acceptable value (0% will disable).
Disconnect power from S811 and any other equipment. Remove obstruction in motor drive train. Verify S811 is properly sized for the application.
Disconnect power from S811 and any other equipment and remove obstruction. Jam Fault can be disabled if trips occur during normal operation. Over Current Fault will provide protection at a higher current threshold.
Verify control power and wire size meets specifications. Reduce shock or vibration. Call Eaton support if the problem persists.
8-6 For more information visit: www.EatonElectrical.com
MN03902002E
November 2006
Table 8-4: Troubleshooting Fault Table, continued
Fault Code Possible Problem Possible Solution
14 Overload Fault – Motor has been overloaded
for an extended period of time.
18 Instantaneous Over Current Fault – Starting
current excessive. Load too great.
32 Internal NV Memory Fault – Internal memory
error.
36 Communications Loss Stop Fault –
Communications to a remote network controller was lost while motor was running. Device was disconnected or the connection broken.
38 Temperature Sensor Fault – Temperature
sensor or interconnection failure.
39 Internal CPU Fault – Firmware Incompatibility
or Hardware failure.
42 Under Voltage Fault – Incoming AC line voltage
below trip threshold. Device connected to incorrect mains supply voltage.
43 Over Voltage Fault – Incoming AC line voltage
above trip threshold. Device connected to incorrect mains supply voltage.
44 Motor Voltage Phase Reversal Fault – incoming
line phase rotation sequence opposite of device setting.
55 Motor Control Command Device Missing Fault
– A motor control command device (DIM, Cover Control, or similar device) was removed.
56 Internal Communications Fault 2 – The motor
was stopped because of an internal communications error. Possible electrical noise or hardware failure.
Reduce the motor’s load. Verify the Overld Trip FLA and/or Ovrld Trip Class if the overloads are infrequent and are set to match the motor and system. Note: Exceeding nameplate ratings will shorten equipment life. If fault happens during motor start: verify the control system is not exceeding the specified maximum starts per hour. Increase the initial torque to bring the motor up to speed faster.
Reduce starting load, increase soft starter capacity (be sure model ratings can handle current demands). Call Eaton support for application assistance.
Call Eaton support.
Reattach network controller, replace connection cable. Call Eaton support if the problem persists.
Call Eaton support. Fault can be disabled, but S811 will not be protected against failures caused by excessive internal temperatures.
Call Eaton support.
Connect to correct supply voltage. Verify Motor Rated Volt is set to correct value. It may be necessary to reduce this setting for soft mains.
Connect to correct supply voltage. Verify Motor Rated Volt is set to correct value. It may be necessary to increase this setting for high mains.
Set Phase Sequence to match incoming sequence. If motor is turning in wrong direction swap two motor connection leads. If mains leads need to be changed, swap incoming leads and set Phase Sequence to match incoming sequence. If an upstream reverser is used, disable Phase Rev Fault.
Re-attach motor control command device and reset the fault. If the motor command device is to be permanently removed, purge it from the S811’s motor control command device list (press and hold the recessed RESET button on the front of the S811 for six seconds). The STATUS LED will change to amber when the action has started and any detached motor control device has been removed from the S811’s list.
Try a 24V DC control voltage power cycle to attempt to clear problem. Verify the S811 is properly grounded. Call Eaton support if the problem persists.
IT. S811 Soft Starter User Manual
MN03902002E
For more information visit: www.EatonElectrical.com
8-7
IT. S811 Soft Starter User Manual
Table 8-4: Troubleshooting Fault Table, continued
Fault Code Possible Problem Possible Solution
57 Internal Program Memory Fault – one or more
internal memory locations have been corrupted.
58 SCR Not Firing Fault – SCR is not conducting
when gated. Incoming phase lost. Special application – undersized or high impedance motor, SCR malfunctioning, circuitry damaged by megger testing.
59 Shorted SCR fault – SCR is shorted from over
current abuse, bypass contactor welded shut, application/configuration issues.
60 SCR Over Current Fault – Excessive SCR
Current prior to bypass. Only active when Stall Fault is disabled. Motor should be up to speed prior to bypass.
61 Mains AC Voltage Loss Fault – fuses blown,
disconnect open, or breaker tripped.
63 Motor Stall Fault – S811 could not engage the
bypass contactors at the end of the motor start time because the start current was too high. Motor did not reach full speed during the start time.
64 Voltage Zero Cross Lost Fault – Mains lost,
phase L1 or L3 lost.
November 2006
Cycle 24V DC power to the S811. Call Eaton support if fault persists.
Re-apply lost phase. Review S811 application. Call Eaton support if problem persists.
Call Eaton support if problem persists.
Increase Soft Start Time and/or Initial Torque. Reduce starting load. Verify S811 is properly sized.
Replace fuses, close disconnect, or reset breaker.
Lengthen Soft Start Time and/or increase Initial Torque. Loads that are heavily loaded during a start such as fans will often need an initial torque setting much greater than the factory default.
Restore mains or lost phases. Call Eaton support if problem persists.
Table 8-5: Resetting the S811
#1 Place all DIP switches on the front cover of the S811 in the OFF position #2 Using the table below, toggle (ON-OFF) the indicated switch 5 times to perform the desired Reset #3 After the reset is complete, set the DIP switches back to the desired QCPort Node ID (1-63)
Switch “1” Factory Reset (Reset to default Factory (Out-of-Box) state)
Switch “2” Switch “4” Commission Reset (Reset Mode and Baud Rate only) Switch “8” Network Config Reset (Reset Node ID, Baud and Mode only)
Application Configuration Reset (Resets all application parameters to defaults. Leaves QCP network parameters unchanged.)
8-8 For more information visit: www.EatonElectrical.com
MN03902002E
November 2006
Chapter 9 — Parts and Service
Renewal Parts
Table 9-1: DIM – Digital Interface Module Renewal Parts
Description Catalog Number
DIM for S811 Soft Starter EMA91 12-Pin Locking Terminal Block EMA75L
Service
For additional information on this product, please call our Customer Support Center at: 1-800-356-1243 or visit our web site at: www.EatonElectrical.com.
For technical assistance, please contact the Technical Resource Center at (800) 809-2772. Service and repair is available from Eaton or several factory authorized regional service
centers. Please contact Eaton’s Product Integrity Center at (800) 345-0434 for the location nearest to you.
IT. S811 Soft Starter User Manual
For field service or start-up assistance 24 hours a day, 7 days a week, please call (800) 498-2678.
MN03902002E
For more information visit: www.EatonElectrical.com
9-1
November 2006
Appendix A — Parameters
Parameter List
User
Display Mode
ONLN SS OXFDO1 H STOP 3 Line Currents
XXXX L1 Amp XXXX L1 Amp XXXX L1 Amp
JOG RESET H->A
IT. S811 Soft Starter User Manual
ESC
ESC
ONLN SS OXFDO1 H STOP
Monitoring
PREV NEXT ENTER
ESC
ENTER
ESC
Parameter
List
ONLN SS OXFDO1 H STOP
Diagnostics
PREV NEXT ENTER
ESC
ENTER
ESC
Parameter
List
THEN
ONLN SS OXFDO1 H STOP
Soft Start Confg
PREV NEXT ENTER
ESC
ENTER
ESC
Parameter
List
PREVNEXT
OR OR
ESC
ONLN SS OXFDO1 H STOP
Overload Config
PREV NEXT ENTER
ESC
ENTER
ESC
Parameter
List
ONLN SS OXFDO1 H STOP
Protection Setup
PREV NEXT ENTER
ESC
ENTER
Parameter
List
ONLN SS OXFDO1 H STOP
Network Setup
ESC
ESC
Parameter Edit Mode
Figure A-1: Navigation Overview
PREV NEXT ENTER
ENTER
ESC
Parameter
List
ONLN SS OXFDO1 H STOP
Network Status
PREV NEXT ENTER
ESC
ENTER
ESC
Parameter
List
ONLN SS OXFDO1 H STOP
LCD DIM Setup
PREV NEXT ENTER
ESC
ENTER
ESC
Parameter
List
MN03902002E
For more information visit: www.EatonElectrical.com
A-1
IT. S811 Soft Starter User Manual
Monitoring Menu
Table A-1: Monitoring — Menu 1
November 2006
To
User Display Mode
ESC
ONLN SS OXFDO1 H STOP
Monitoring
PREV NEXT NEXTENTER
ESC
ENTER
ESC
To
Diagnostics
Menu
Parameter Units Access Level
1 3Ø Line Currents Amps 0 2 3Ø Pole Voltages Vol ts 0 3 Thermal Memory %0 4 Current as % FLA %0 5 Pole Temp °C °C 0 6 DC Cntrl Voltage Vol ts 0 7 Device Temp °C °C 0 8 Start Count Starts 0 9 3Ø Pole Currents Amps 0 10 Ave Pole Current Amps 0 11 Ave Line Current Amps 0
Note: The button under the PREV Soft Key moves up one line.
PREV
NEXT
The button under the NEXT Soft Key moves down one line.
Note: See Appendix I for data parameter descriptions.
A-2 For more information visit: www.EatonElectrical.com
MN03902002E
November 2006
Diagnostics Menu
To
Monitoring
Menu
Table A-2: Diagnostics — Menu 2
Parameter Units Access Level
To
User Display Mode
ESC
ONLN SS OXFDO1 H STOP
Diagnostics
PREVPREV NEXT NEXTENTER
ESC
ENTER
ESC
IT. S811 Soft Starter User Manual
To
Soft Start
Confg Menu
1 Device Status 0 2 Fault/Warn List 0 3 Fault/Warn Queue 0 4 Motor Fault Bits 3 5 Motor Status 0 6 Motor Control 3 7 Breaker Status 3
Note: The button under the PREV Soft Key moves up one line.
PREV
NEXT
The button under the NEXT Soft Key moves down one line.
Note: See Appendix I for data parameter descriptions.
MN03902002E
For more information visit: www.EatonElectrical.com
A-3
IT. S811 Soft Starter User Manual
Soft Start Config Menu
Table A-3: Soft Start Confg — Menu 3
Parameter Units Min Max Default
To
Diagnostics
Menu
To
User Display Mode
ESC
ONLN SS OXFDO1 H STOP
Soft Start Confg
PREVPREV NEXT NEXTENTER
ESC
ENTER
ESC
To
Overload
Config
Menu
November 2006
Access Level
1 Start Method 0302 2 Soft Start Time Sec 0.5 180 20 1 3 Initial Torque % 0 100 45 1 4 Pump Stop Time Sec 5 120 10 1 5 Soft Stop Time Sec 0 60 0 1 6 Kick Start Time Sec0201 7 Kick Start Torq % 0 100 0 1 8 Start Control 0112 9 Reset Mode 0102 10 Relay1 Config 0522 11 Relay2 Config 0502
Note: The button under the PREV Soft Key moves up one line.
PREV
NEXT
The button under the NEXT Soft Key moves down one line.
Note: See Appendix I for data parameter descriptions.
A-4 For more information visit: www.EatonElectrical.com
MN03902002E
November 2006
Overload Config Menu
Table A-4: Overload Config — Menu 4
IT. S811 Soft Starter User Manual
To
User Display Mode
ESC
ONLN SS OXFDO1 H STOP
Overload Config
To
Soft Start
Confg
Menu
PREVPREV NEXT NEXTENTER
ESC
ENTER
ESC
Parameter Units Min Max Default
To
Protection
Setup Menu
Access Level
1 Overld Trip FLA Amps 12 1000 21 2 2 Ovrld Trip Class 5 30202 3 Overload Fault 0112 4 Ovld On Start Sec0112
Note: The button under the PREV Soft Key moves up one line.
PREV
NEXT
The button under the NEXT Soft Key moves down one line.
Note: See Appendix I for data parameter descriptions.
MN03902002E
For more information visit: www.EatonElectrical.com
A-5
IT. S811 Soft Starter User Manual
Protection Setup Menu
Table A-5: Protection Setup — Menu 5
Parameter Units Min Max Default
To
Overload
Config
Menu
To
User Display Mode
ESC
ONLN SS OXFDO1 H STOP
Protection Setup
PREVPREV NEXT NEXTENTER
ESC
ENTER
ESC
To
Network
Setup Menu
November 2006
Access Level
1 Phase Sequence 0102 2 Phase Rev Fault 0102 3 Motor Rated Volt Volts 115 600 480 2 4 Low Volt Trip 0112 5 Low Volt Level % 1 99 90 2 6 Low Volt Trip Dly Sec 1 60 3 2 7 Hi Volt Trip 0112 8 Hi Volt Level % 101 120 110 2 9 Hi Volt Trip Dly Sec 1 60 3 2 10 V Imbal Trip Lev % 1 100 6 2 11 V Imbal Trip Dly Sec 1 60 0.5 2 12 Phase Loss Fault 0112 13 Phase Loss % Trp % 1 100 80 2 14 Phase Loss Trip Dly Sec 1 60 0.5 2 15 Low I Trip % FLA % 0 100 6 2 16 Phase Imb Fault 0112 17 I Imbal Trip Lev % 1 100 40 2 18 I Imbal Trip Dly Sec 1 60 0.5 2 19 SCR Short Fault 0112 20 SCR Conduct Fault 0112 21 Jam Fault 0112 22 Stall Fault 0112 23 Temp Sense Fault 0112
Note: The button under the PREV Soft Key moves up one line.
PREV
NEXT
The button under the NEXT Soft Key moves down one line.
Note: See Appendix I for data parameter descriptions.
A-6 For more information visit: www.EatonElectrical.com
MN03902002E
November 2006
Network Setup Menu
Table A-6: Network Setup — Menu 6
IT. S811 Soft Starter User Manual
To
User Display Mode
ESC
ONLN SS OXFDO1 H STOP
Network Setup
To
Protection
Setup Menu
PREVPREV NEXT NEXTENTER
ESC
ENTER
ESC
Parameter Units Min Max Default
To
Network
Status
Menu
Access Level
1 Language Select 1 2 Comm Loss Action 0703 3 Mot Ctrl Timeout mSec 2000 3 4 Trans MC Timeout mSec
2000 3 5 Term Resistor 0113 6 Baud Rate 06 3 7 Device Mode 04 3 8 Production Intvl mSec 3 9 Consumpt Intvl mSec 3 10 Production List 3 11 Consumption List 3
A 0 setting will disable this feature until the next factory reset.
Note: The button under the PREV Soft Key moves up one line.
PREV
NEXT
The button under the NEXT Soft Key moves down one line.
Note: See Appendix I for data parameter descriptions.
MN03902002E
For more information visit: www.EatonElectrical.com
A-7
IT. S811 Soft Starter User Manual
Network Status Menu
Table A-7: Network Status — Menu 7
To
User Display Mode
ESC
ONLN SS OXFDO1 H STOP
Network Status
To
Network
Setup Menu
PREVPREV NEXT NEXTENTER
ESC
ENTER
ESC
To
LCD DIM
Setup Menu
Parameter Access Level
November 2006
1 Firmware Version 0 2 Hardware Version 0 3 QCP Fault Status 3 4 Node ID 3 5 Device ID Tag 3 6 Slave Address 3 7 Production Dest 3 8 Device Identity 3 9 Config CRC 0 10 Parameter List 3 11 Language List 3
Note: The button under the PREV Soft Key moves up one line.
PREV
NEXT
The button under the NEXT Soft Key moves down one line.
Note: See Appendix I for data parameter descriptions.
A-8 For more information visit: www.EatonElectrical.com
MN03902002E
November 2006
LCD DIM Setup Menu
Table A-8: LCD DIM Setup Menu
IT. S811 Soft Starter User Manual
To
User Display Mode
ESC
ONLN SS OXFDO1 H STOP
LCD DIM Setup
To
Network
Status Menu
Parameter Units Min Max Default
PREVPREV NEXT ENTER
ESC
ENTER
ESC
Access Level
1 Access Level 20 2 Password 0 3 Access Timeout Secs 0 600 600 3 4 User Var 1 100 3 5 User Var 1 Scale 13 6 User Var 1 Desc 3 7 User Var 1 Units 3 8 User Var 2 03 9 User Var 2 Scale 13 10 User Var 2 Desc 3 11 User Var 2 Units 3 12 Backlight Level 30 13 Backlight Time Secs 0 300 0 0 14 Screen Contrast 15 0 15 Scan For Devices 2 16 Identify Node 0 17 Start Discovery 2 18 Reset-Soft 2 19 Reset-Factory 3 20 Reset-App Cfg 2 21 Reset-App Fault 2
MN03902002E
Note: Contact Factory for more information on DIM Setup Parameters.
For more information visit: www.EatonElectrical.com
A-9
IT. S811 Soft Starter User Manual
Table 6-5: LCD DIM Setup Menu, continued
Parameter Units Min Max Default
22 Reset-Commission 2 23 Clear Fault Que 0 24 Get Register 2 25 Set Register 3 26 Run Delay Secs 0.3 3 27 Transient Source Disabled 3 28 Refresh Rate mSec 250 3 29 Firmware Version 0 30 Term Resistor Enabled 1 31 Inactive Timeout Secs 0 32 Fault Disp Time Secs 0 30 0 2 33 Production Data 3 34 Consumption Data 3 35 Status 3 36 App Status 0 37 Motor Control 2 38 Motor Status 2 39 Device Temp °C 0 40 Device Identity 2 41 Config CRC 2 42 Node ID 0 43 Device Mode 3 44 Baud Rate 3 45 Production Dest 2 46 Device ID Tag LCD DIM 0 47 Production Intvl mSec 100 3 48 Consumpt Intvl mSec 2000 3 49 Language List 00 50 Language Select 00
Do not set less than 10 seconds. Except: 0 setting disables timeout.
Note: The button under the PREV Soft Key moves up one line.
PREV
November 2006
Access Level
65535 0 2
NEXT
The button under the NEXT Soft Key moves down one line.
Note: Contact Factory for more information on DIM Setup Parameters.
A-10 For more information visit: www.EatonElectrical.com
MN03902002E
November 2006
Appendix B — Protection
Thermal Overload
The IT. Soft Starter features an electronic motor overload protection feature. This is intended to protect the motor and power wiring against overheating caused by excessive current for extended periods of time.
Note: Short circuit protection must be applied on the line side of the soft starter.
Entering the motor full load current rating, using the Overld Trip FLA parameter programs trip current. It is programmable from 32% – 100% of the unit’s rated current.
Table B-1: Overload — Adjustment Settings
Frame Size
N S811N37xxx 11 – 37 19 – 65
R S811R10xxx 32 – 105 55 – 182
T S811T18xxx 56 – 180 97 – 311
U S811U36xxx 112 – 360 193 – 623
V S811V36xxx 112 – 360 193 – 623
Rating does not have IEC certification.
See Application Notes, Appendix E.
Catalog Number
S811N66xxx 20 – 66 35 – 114
S811R13xxx 42 – 135 73 – 234
S811T24xxx 75 – 240 130 – 415 S811T30xxx 95 – 304 164 – 526
S811U42xxx 131 – 420 227 – 727
S811U50xxx
S811V42xxx 131 – 420 227 – 727 S811V50xxx 156 – 500 270 – 865 S811V65xxx 203 – 650 352 – 1125 S811V72xxx 225 – 720 389 – 1246 S811V85xxx 265 – 850 458 – 1471
S811V10xxx
IT. S811 Soft Starter User Manual
FLA Current Range for a Line Connection
156 – 500 270 – 865
320 – 1000 554 – 1730
FLA Current Range for an Inside-the-Delta Connection
MN03902002E
Note: Overload Trip FLA parameter is settable to any point within its range.
For more information visit: www.EatonElectrical.com
B-1
IT. S811 Soft Starter User Manual
The thermal overload is designed to protect the motor from overheating caused by excessive current. If the motor is overloaded, the current drawn rises and heats the motor. The FLA sets the trip threshold and the trip class (5 to 30) is set with the Ovrld Trip Class parameter.
If the device trips on a thermal overload, an internal timer is started which inhibits a reset for three minutes. After this timer expires, the device may be reset and the thermal fault is cleared. At this point another internal timer is started, this timer is 26 x 3 or 48 minutes. If another trip occurs before this timer expires, the reset inhibit time is increased to 6 minutes.
Once the trip level reaches 3, it will take 144 minutes to go back to level 2, then 96 minutes to get back to level 1. To get from level 3 to a reset thermal overload at level 1, it takes 240 minutes without a trip. A reset thermal overload at level 1 means the next thermal overload trip will have a 3-minute reset inhibit as in Table B-2.
Table B-2: Thermal Motor Overload Times
Trip Level
1 3 minutes — 2 6 minutes 96 minutes 3 9 minutes 144 minutes
Total 240 minutes to reset to level 1.
Reset Inhibit Time
Cycling power on the device will NOT clear the thermal trip. The thermal memory and the reset inhibit time are saved to the non-volatile memory. These values are reloaded when the device boots and the timer is restarted at the full reset time. This means if the 3-minute inhibit timer has been running two minutes, cycling power will require the user to wait the full three minutes before a reset can clear the overload fault.
November 2006
Reset Time to Previous Trip Level
If the device is shut down when the overload fault is tripped, the temperature is also saved to the non-volatile memory. If the device is left to cool and then powered, the temperature read from the sensor is compared to the saved temperature. If the current temperature is 87% or less of the saved temperature, a full thermal memory reset is initiated.
B-2 For more information visit: www.EatonElectrical.com
MN03902002E
November 2006
Overload Trip Curves
10000.0
1000.0
IT. S811 Soft Starter User Manual
115%
Class 5 Class 10 Class 20 Class 30
100.0
Time (Seconds)
10.0
1.0
Class 30
Class 10
Class 5
0
100 200 300 400 500 600 700 800
Percent FLA
Class 20
900
MN03902002E
Figure B-1: Overload Trip Curves
For more information visit: www.EatonElectrical.com
B-3
IT. S811 Soft Starter User Manual
S811 and Motor Protection Features
The S811 implements the following protection features. Each protection feature is individually configured and enabled by the user. Some of the features are designed to protect the motor and others are for internal protection of the S811. A summary can be found in Table B-17.
Motor Parameters
One or more of the motor protection features need the following motor parameters. The user must input these values prior to enabling protection.
Table B-3: Motor Parameters Required for Protection
Setting DIM Parameter Range Step Default
Rated Voltage (RMS Line-to-Line) Motor Rated
Phase Sequence Phase
Instantaneous Over Current
When the bypass contactors are not engaged, the S811 monitors the maximum RMS value of the three phase currents. The unit will trip with an instantaneous over current fault if the maximum value exceeds six times the catalog FLA setting for 1.5 seconds. This internal protection mechanism is most useful for protecting the S811 from starting motor too large for its ratings.
November 2006
115 – 690 1 volt 480 volts
Vol t
{ABC, ACB} N/A ABC
Sequence
Table B-4: Instantaneous Over Current Settings
Trip DIM Parameter Set Point Default
Trip Threshold Not User Settable 6x catalog FLA N/A Trip Delay Not User Settable 1.5 Seconds N/A
Motor Stall
The S811 monitors the maximum RMS value of the three phase currents. The unit will trip with a motor stall fault if the stall fault is enabled and the maximum RMS value exceeds two times the FLA setting when the start time setting expires.
Table B-5: Motor Stall Settings
Trip DIM Parameter Set Point Default
Trip Enable Stall Fault {On, Off} On Trip Threshold Not User Settable 2x FLA N/A
SCR Over Current
The SCR over current trip is only active if the stall fault trip is disabled. The S811 monitors the maximum RMS value of the three phase currents. The unit will trip with a SCR over current fault if the stall fault is disabled and the maximum RMS value exceeds three times the FLA setting when the start time setting expires.
Table B-6: SCR Over Current Settings
Trip DIM Parameter Set Point Default
Trip Threshold Not User Settable 3x FLA N/A
B-4 For more information visit: www.EatonElectrical.com
MN03902002E
November 2006
Motor Jam
Motor Over Current
IT. S811 Soft Starter User Manual
When the bypass contactors are closed, the S811 monitors the maximum RMS value of the three phase currents. The unit will trip with a motor jam fault if the jam trip is enabled and the maximum RMS value exceeds three times the FLA setting for 1.5 seconds.
Table B-7: Motor Jam Settings
Trip DIM Parameter Set Point Default
Trip Enable Jam Fault {On, Off} On Trip Threshold Not User Settable 3x FLA N/A Trip Delay Not User Settable 1.5 Seconds N/A
The motor over current trip is active only if the jam fault trip is disabled. When the bypass contactors are closed, the S811 monitors the maximum RMS value of the three phase currents. The unit will trip with a motor over current fault if the maximum RMS value exceeds four times the catalog FLA for the class dependent trip delay.
Table B-8: Motor Over Current Settings
Trip DIM Parameter Set Point Default
Trip Threshold Not User Settable 4x Catalog FLA N/A Trip Delay
– Class ≤ 5 – Class 10 – Class 20 – Class 30
Not User Settable
2.0 seconds
N/A
4.0 seconds
6.0 seconds
8.0 seconds
Motor Under Load
When the bypass contactors are closed, the S811 monitors the average value of the three phase currents as a percent of FLA. The unit will trip with a motor under load fault if the percent FLA value falls below the trip threshold for greater than two seconds.
Table B-9: Motor Under Load Settings
Trip DIM Parameter Set Point Step Default
Trip Threshold Low I Trip % FLA 1 – 100% 1% 6% Trip Delay Not User Settable 2.0 Seconds N/A N/A
Phase Imbalance — Current
NEMA defined current imbalance is calculated using the following equation:
Percent Imbalance = 100 * (max deviation from average / average)
The S811 monitors the current imbalance when the motor is running. The unit will trip with a motor phase imbalance fault if the current imbalance trip is enabled, the percent imbalance exceeds the trip threshold for the trip delay and the current is greater than the FLA trip setting.
Table B-10: Current Imbalance Settings
Trip DIM Parameter Set Point Step Default
Trip Enable Phase Imb Fault {On, Off} N/A On Trip Threshold I Imbal Trip Lev 1 – 100% 1% 40% Trip Delay I Imbal Dly 0.0 – 60.0
Seconds
0.1 Second 0.5 Second
MN03902002E
For more information visit: www.EatonElectrical.com
B-5
IT. S811 Soft Starter User Manual
Phase Loss
NEMA defined current imbalance is calculated using the following equation:
Percent Imbalance = 100 * (max deviation from average / average)
The S811 monitors the current imbalance when the motor is running. Phase loss is an extreme case of current imbalance. The unit will trip with a motor phase loss fault if the phase loss trip is enabled, the percent imbalance exceeds the trip threshold for the trip delay and current increases above FLA trip setting.
Table B-11: Phase Loss Settings
Trip DIM Parameter Set Point Step Default
Trip Enable Phase Loss Fault {On, Off} N/A On Trip Threshold Phase Loss % Trp 1 – 100% 1% 80% Trip Delay Phase Loss Dly 0.0 – 60.0
Motor Voltage Phase Reversal
The S811 monitors the phase voltages to determine the incoming phase sequence (ABC or ACB). If the monitored sequence differs from the Incoming Phase Sequence parameter setting, a motor phase reversal fault is issued. The phase reversal trip will need to be disabled when using an upstream reverser.
November 2006
0.1 Second 0.5 Second
Seconds
Table B-12: Motor Voltage Phase Reversal Settings
Trip DIM Parameter Step Default
Trip Enable Phase Rev Fault {On, Off} On
Phase Imbalance — Voltage
NEMA defined voltage imbalance is calculated using the following equation:
Percent Imbalance = 100 * (max deviation from average / average)
The S811 monitors the voltage imbalance when the motor is off and checks the value just prior to starting to determine if a fault shall be issued. The unit will trip with a motor phase imbalance fault if the phase imbalance trip is enabled and the percent imbalance has exceeded the trip threshold for the trip delay.
Table B-13: Voltage Imbalance Settings
Trip DIM Parameter Set Point Step Default
Trip Enable Phase Imb Fault {On, Off} N/A On Trip Threshold V Imbal Trip Lev 1 – 100% 1% 6% Trip Delay V Imbal Dly 0.0 – 60.0
Seconds
0.1 Second 0.5 Second
B-6 For more information visit: www.EatonElectrical.com
MN03902002E
November 2006
Under Voltage
Over Voltage
IT. S811 Soft Starter User Manual
The S811 monitors the minimum RMS value of the three phase voltages. The unit will trip with a motor under voltage fault if the under voltage trip is enabled and the minimum RMS value drops below the trip threshold for the trip delay. Note that the S811 will not generate an under voltage trip when the motor is starting.
Table B-14: Under Voltage Settings
Trip DIM Parameter Set Point Step Default
Trip Enable Low Volt Trip {On, Off} N/A On Trip Threshold Low Volt Level 1 – 99% Rated 1% 90% Trip Delay Low Volt Trip Dly 0.0 – 60.0
Seconds
0.1 Second 3.0 Second
The S811 monitors the maximum RMS value of the three phase voltages. The unit will trip with a motor over voltage fault if the over voltage trip is enabled and the maximum RMS value rises above the trip threshold for the trip delay.
Table B-15: Over Voltage Settings
Trip DIM Parameter Set Point Step Default
Trip Enable Hi Volt Trip {On, Off} N/A On Trip Threshold Hi Volt Level 101 – 120
%Rated
Trip Delay Hi Volt Trp Dly 0.0 – 60.0
Seconds
1 % 110%
0.1 Second 3.0 Second
Mains Faults
If a start is commanded and voltage mains are not present or are not in a safe range for the S811 to attempt a start, a fault will be generate according to the following table.
Table B-16: Fault Generation
Fault Condition
Mains Loss Average RMS of three phase voltages is less than 80 volts Motor Under Voltage Minimum phase RMS voltage is less than 80 volts Motor Over Voltage Maximum phase RMS voltage is greater than 800 volts
MN03902002E
For more information visit: www.EatonElectrical.com
B-7
IT. S811 Soft Starter User Manual
November 2006
Table B-17: S811 Protection Faults
Fault Active Trip DIM Parameter Set Point Step Default
#18 Inst Over Current
#63 Motor Stall End of start time
#60 SCR Over Current
#11 Motor Jam Bypass engaged Enable Jam Fault {On, Off} N/A On
#10 Motor Over Current
#9 Motor Under Load
#7 Current Imbalance
#6 Phase Loss Motor energized Enable Phase Loss Fault {On, Off} N/A On
#44 Phase Reversal
#7 Voltage Imbalance
#42 Under V
#43 Over Voltage Motor energized Enable Hi Volt Trip {On, Off} N/A On
#61 Mains Loss When start is
#42 Mains Low When start is
#43 Mains High When start is
oltage Bypass engaged Enable Low Volt Trip {On, Off} N/A On
On SCRs Threshold Not User Settable 6x FLA N/A N/A
Delay Not User Settable 1.5 Seconds N/A N/A
setting End of start time
setting (stall disabled)
Bypass engaged (Jam Disabled)
Bypass engaged Threshold Low I Trip % FLA 1 – 100% 1% 6%
Motor energized Enable Phase Imb Fault {On, Off} N/A On
Mains Present; when monitored sequence differs from Incoming Phase Sequence parameter
When start is attempted
attempted
attempted
attempted
Enable Stall Fault {On, Off} N/A On Threshold Not User Settable 2x FLA N/A N/A Threshold Not User Settable 3x FLA N/A N/A
Threshold Not User Settable 3x FLA N/A N/A Delay Not User Settable 1.5 Seconds N/A N/A Threshold Not User Settable 4x Catalog FLA N/A N/A Delay Class
5 – 10 – 20 – 30
Delay Not User Settable 2.0 seconds N/A N/A
Threshold I Imbal Trip Lev 1 – 100% 1% 40% Delay I Imbal Dly 0.0 – 60.0
Threshold Phase Loss % Trp 1 – 100% 1% 80% Delay Phase Loss Dly 0.0 – 60.0
Enable Phase Rev Fault {On, Off} N/A On
Enable Phase Imb Fault {On, Off} N/A On Threshold V Imbal Trip Lev 1 – 100% 1% 6% Delay V Imbal Dly 0.0 – 60.0
Threshold Low Volt Level 1 – 99% Rated 1% 90% Delay Low Volt Trip Dly 0.0 – 60.0
Threshold Hi Volt Level 101 – 120
Delay Hi Volt Trp Dly 0.0 – 60.0
Threshold Not User Settable 80 volts N/A N/A
Threshold Not User Settable 80 volts N/A N/A
Threshold Not User Settable 800 volts N/A N/A
Not User Settable
2.0 seconds
4.0 seconds
6.0 seconds
8.0 seconds
Seconds
Seconds
Seconds
Seconds
%Rated
Seconds
N/A N/A
0.1 Second
0.1 Second
0.1 Second
0.1 Second
1 % 110%
0.1 Second
0.5 Second
0.5 Second
0.5 Second
3.0 Second
3.0 Second
B-8 For more information visit: www.EatonElectrical.com
MN03902002E
IT. S811 Soft Starter User Manual
November 2006
Appendix C — Ratings, Cooling and Power Losses for a Line Connected Motor
Horsepower and kW Ratings
Standard Duty Ratings
Table C-1: 15 Second Ramp, 4 Starts per Hour, 300% Current Limit @ 40°C
Three-Phase Motors kW Rating (50 Hz) hp Rating (60 Hz)
Max. Current
230V
380 – 400V 440V
Frame Size N
37 10 18.5 18.5 10 10 10 10 25 20 30 30 S811N37xxx 66 18.530372015 2020 5040 6050S811N66xxx
Frame Size R
105 30 55 59 30 25 40 30 75 60 100 75 S811R10xxx 135 40 63 80 40 30 50 40 100 75 125 100 S811R13xxx
Frame Size T
180 51 90 110 60 50 60 60 150 125 150 150 S811T18xxx 240 75 110 147 75 60 75 75 200 150 200 200 S811T24xxx 304 90 160 185 100 75 100 100 250 200 300 250 S811T30xxx
Frame Size U
360 110 185 220 125 100 150 125 300 250 350 300 S811U36xxx 420 129 220 257 150 125 175 150 350 300 450 350 S811U42xxx 500 150 257 300 150 150 200 150 400 350 500 450 S811U50xxx
Frame Size V
360 110 185 220 125 100 150 125 300 250 350 300 S811V36xxx 420 129 220 257 150 125 175 150 350 300 450 350 S811V42xxx 500 150 257 300 150 150 200 150 400 350 500 450 S811V50xxx 650 200 355 425 250 200 250 200 500 450 600 500 S811V65xxx 720 220 400 450 300 250 600 500 700 600 S811V72xxx 850 257 475 500 350 300 700 600 900 700 S811V85xxx
1000 277 525 50 400 350 800 700 900 800 S811V10xxx
See Application Notes, Appendix E.
500A rating does not have IEC certification.
200V 230V 460V 575 – 690V
1.0SF 1.15SF 1.0SF 1.15SF 1.0SF 1.15SF 1.0SF 1.15SF
Catalog Number
MN03902002E
For more information visit: www.EatonElectrical.com
C-1
IT. S811 Soft Starter User Manual
November 2006
Table C-2: 25 Second Ramp, 4 Starts per Hour, 300% Current Limit @ 40°C
Three-Phase Motors kW Rating (50 Hz) hp Rating (60 Hz)
Max. Current
230V
380 – 400V 440V
Frame Size N
34 9 15 18.5 10 7-1/2 10 10 25 20 30 25 S811N37xxx 63 15 30 33 20 15 20 20 40 40 60 50 S811N66xxx
Frame Size R
96 25 45 55 30 25 30 30 75 60 75 75 S811R10xxx
120 33 63 63 40 30 40 40 75 75 100 100 S811R13xxx
Frame Size T
150 45 80 90 50 40 50 50 100 100 150 125 S811T18xxx 215 63 110 132 60 60 75 60 150 150 200 150 S811T24xxx 278 80 147 160 75 75 100 75 200 200 250 250 S811T30xxx
Frame Size U
320 90 160 185 100 75 125 100 250 200 300 250 S811U36xxx 380 110 200 220 125 100 150 125 300 250 350 300 S811U42xxx 460 140 250 280 150 125 150 150 350 300 450 400 S811U50xxx
Frame Size V
320 90 160 185 100 75 125 100 250 200 300 250 S811V36xxx 380 110 200 220 125 100 150 125 300 250 350 300 S811V42xxx 460 140 250 280 150 125 150 150 350 300 450 400 S811V50xxx 610 185 315 375 250 150 200 200 500 450 600 500 S811V65xxx 680 200 375 445 200 250 200 600 500 700 600 S811V72xxx 810 250 450 500 300 300 700 600 900 700 S811V85xxx 890 290 510 560 400 350 700 600 900 700 S811V10xxx
See Application Notes, Appendix E.
500A rating does not have IEC certification.
200V 230V 460V 575 – 690V
1.0SF 1.15SF 1.0SF 1.15SF 1.0SF 1.15SF 1.0SF 1.15SF
Catalog Number
C-2 For more information visit: www.EatonElectrical.com
MN03902002E
IT. S811 Soft Starter User Manual
November 2006
Table C-3: 15 Second Ramp, 4 Starts per Hour, 300% Current Limit @ 50°C
Three-Phase Motors kW Rating (50 Hz) hp Rating (60 Hz)
Max. Current
230V
380 – 400V 440V
Frame Size N
34 9 15 18.5 10 7-1/2 10 10 25 20 30 25 S811N37xxx 63 15 30 33 20 15 20 20 40 40 60 50 S811N66xxx
Frame Size R
96 25 45 55 30 25 30 30 75 60 75 75 S811R10xxx
120 33 63 63 40 30 40 40 75 75 100 100 S811R13xxx
Frame Size T
150 45 80 90 50 40 50 50 100 100 150 125 S811T18xxx 215 63 110 132 60 60 75 60 150 150 200 150 S811T24xxx 278 80 147 160 75 75 100 75 200 200 250 250 S811T30xxx
Frame Size U
320 90 160 185 100 75 125 100 250 200 300 250 S811U36xxx 380 110 200 220 125 100 150 125 300 250 350 300 S811U42xxx 460 140 250 280 150 125 150 150 350 300 450 400 S811U50xxx
Frame Size V
320 90 160 185 100 75 125 100 250 200 300 250 S811V36xxx 380 110 200 220 125 100 150 125 300 250 350 300 S811V42xxx 460 140 250 280 150 125 150 150 350 300 450 400 S811V50xxx 610 185 315 375 250 150 200 200 500 450 600 500 S811V65xxx 680 200 375 445 200 250 200 600 500 700 600 S811V72xxx 830 257 450 500 300 300 700 600 900 700 S811V85xxx 960 302 510 540 350 300 800 700 900 800 S811V10xxx
See Application Notes, Appendix E.
500A rating does not have IEC certification.
200V 230V 460V 575 – 690V
1.0SF 1.15SF 1.0SF 1.15SF 1.0SF 1.15SF 1.0SF 1.15SF
Catalog Number
MN03902002E
For more information visit: www.EatonElectrical.com
C-3
IT. S811 Soft Starter User Manual
November 2006
Table C-4: 50 Second Ramp, 2 Starts per Hour, 300% Current Limit @ 50°C
Three-Phase Motors kW Rating (50 Hz) hp Rating (60 Hz)
Max. Current
230V
380 – 400V 440V
Frame Size N
21 5.5 10 11 5 5 5 5 15 10 15 15 S811N37xxx 42 1118.5221010 1510 3025 4030S811N66xxx
Frame Size R
60 15 30 33 15 15 20 15 40 40 50 50 S811R10xxx 80 22 40 45 25 20 30 25 60 50 75 60 S811R13xxx
Frame Size T
115 33 59 63 30 30 40 30 75 75 100 100 S811T18xxx 150 45 80 90 50 40 50 50 100 100 150 125 S811T24xxx 192 55 100 110 60 50 60 60 150 125 200 150 S811T30xxx
Frame Size U
280 80 150 160 75 75 100 75 200 200 250 250 S811U36xxx 340 110 180 200 100 100 125 100 250 200 350 300 S811U42xxx 380 110 200 220 125 100 150 125 300 250 350 300 S811U50xxx
Frame Size V
280 80 150 160 75 75 100 75 200 200 250 250 S811V36xxx 340 110 180 200 100 100 125 100 250 200 350 300 S811V42xxx 380 110 200 220 125 100 150 125 300 250 350 300 S811V50xxx 420 129 220 257 150 125 150 150 350 300 450 350 S811V65xxx 480 147 257 295 150 150 200 150 400 350 500 450 S811V72xxx 590 180 315 375 200 150 200 200 500 400 600 500 S811V85xxx 650 205 370 415 250 200 250 200 500 450 600 500 S811V10xxx
See Application Notes, Appendix E.
500A rating does not have IEC certification.
200V 230V 460V 575 – 690V
1.0SF 1.15SF 1.0SF 1.15SF 1.0SF 1.15SF 1.0SF 1.15SF
Catalog Number
C-4 For more information visit: www.EatonElectrical.com
MN03902002E
IT. S811 Soft Starter User Manual
November 2006
Table C-5: 15 Second Ramp, 4 Starts per Hour, 450% Current Limit @ 40°C
Three-Phase Motors kW Rating (50 Hz) hp Rating (60 Hz)
Max. Current
230V
380 – 400V 440V
Frame Size N
29 7.5 12.5 15 49 12.522251510 1515 3030 4040S811N66xxx
Frame Size R
73 18.537402020 2520 5040 6060S811R10xxx 94 25 45 55 30 25 30 30 60 60 75 75 S811R13xxx
Frame Size T
155 45 80 90 50 40 60 50 100 100 150 125 S811T18xxx 219 63 110 132 60 60 75 60 150 150 200 150 S811T24xxx 280 80 150 160 75 75 100 75 200 200 250 250 S811T30xxx
Frame Size U
345 100 185 200 100 100 125 100 250 200 350 300 S811U36xxx 405 110 200 250 125 100 150 125 300 250 400 350 S811U42xxx
Frame Size V
345 100 185 200 100 100 125 100 250 200 350 300 S811V36xxx 405 110 200 250 125 100 150 125 300 250 400 350 S811V42xxx 465 140 250 280 150 125 150 150 350 300 450 400 S811V50xxx 530 160 280 335 150 150 200 150 450 350 500 450 S811V65xxx 590 180 315 375 200 150 200 500 400 600 500 S811V72xxx 651 200 355 425 600 450 700 600 S811V85xxx 754 220 400 465 600 500 800 700 S811V10xxx
See Application Notes, Appendix E.
200V 230V 460V 575 – 690V
1.0SF 1.15SF 1.0SF 1.15SF 1.0SF 1.15SF 1.0SF 1.15SF
7-1/2 7-1/2
10
7-1/2
20 15 25 20 S811N37xxx
Catalog Number
MN03902002E
For more information visit: www.EatonElectrical.com
C-5
IT. S811 Soft Starter User Manual
November 2006
Table C-6: 30 Second Ramp, 4 Starts per Hour, 450% Current Limit @ 40°C
Three-Phase Motors kW Rating (50 Hz) hp Rating (60 Hz)
Max. Current
230V
380 – 400V 440V
Frame Size N
21 5.5 10 12.5 5 5 5 5 15 10 15 15 S811N37xxx 40 1118.5221010 1010 3025 3030S811N66xxx
Frame Size R
55 15 25 30 15 15 20 15 40 30 50 40 S811R10xxx 75 22 37 45 20 20 25 20 50 50 60 60 S811R13xxx
Frame Size T
151 45 80 90 50 40 50 50 100 100 150 125 S811T18xxx 215 63 110 132 60 60 75 60 150 150 200 150 S811T24xxx 264 80 140 160 75 75 100 75 200 150 250 200 S811T30xxx
Frame Size U
300 90 160 185 100 75 100 100 200 200 300 250 S811U36xxx 340 100 180 200 100 100 125 100 250 200 350 300 S811U42xxx
Frame Size V
300 90 160 185 100 75 100 100 200 200 300 250 S811V36xxx 340 100 180 200 100 100 125 100 250 200 350 300 S811V42xxx 380 110 200 220 125 100 150 125 300 250 350 300 S811V50xxx 420 129 220 257 150 125 150 150 350 300 450 350 S811V65xxx 460 140 250 280 150 125 150 150 350 300 450 400 S811V72xxx 500 150 257 300 150 150 200 150 400 350 500 450 S811V85xxx 560 160 277 325 200 150 250 200 500 400 600 500 S811V10xxx
See Application Notes, Appendix E.
200V 230V 460V 575 – 690V
1.0SF 1.15SF 1.0SF 1.15SF 1.0SF 1.15SF 1.0SF 1.15SF
Catalog Number
C-6 For more information visit: www.EatonElectrical.com
MN03902002E
IT. S811 Soft Starter User Manual
November 2006
Severe Duty Ratings
Table C-7: > 30 Second Ramp, > 4 Starts per Hour or >300% Current Limit
Three-Phase Motors kW Rating (50 Hz) hp Rating (60 Hz)
Max. Current
230V
380 – 400V 440V
200V 230V 460V 575 – 690V
1.0SF 1.15SF 1.0SF 1.15SF 1.0SF 1.15SF 1.0SF 1.15SF
Catalog Number
Frame Size N
22 5.5 10 11 5 5
7-1/2
515102015S811N37xxx
42 1118.5221010 1510 3025 4030S811N66xxx
Frame Size R
65 15 30 33 15 15 20 15 50 40 50 50 S811R10xxx 80 22 40 45 25 20 30 25 60 50 75 60 S811R13xxx
Frame Size T
115 33 59 63 30 30 40 30 75 75 100 100 S811T18xxx 150 45 80 90 50 40 50 50 100 100 150 125 S811T24xxx 192 55 100 110 60 50 75 60 150 125 200 150 S811T30xxx
Frame Size U
240 75 110 147 75 60 75 75 200 150 200 200 S811U36xxx 305 90 160 185 100 75 100 100 250 200 300 250 S811U42xxx
Frame Size V
240 75 110 147 75 60 75 75 200 150 200 200 S811V36xxx 305 90 160 185 100 75 100 100 250 200 300 250 S811V42xxx 365 110 185 220 125 100 150 125 300 250 350 300 S811V50xxx 420 129 220 257 150 125 150 150 350 300 450 350 S811V65xxx 480 147 257 295 150 150 200 150 400 350 500 450 S811V72xxx 525 160 280 335 150 150 200 150 450 350 500 450 S811V85xxx 575 172 303 370 200 150 250 200 500 450 600 500 S811V10xxx
See Application Notes, Appendix E.
Severe Duty Ratings are defined as any combination of parameters that exceed the Standard Duty Ratings where the ramp time is over 30 seconds, the number of starts per hour exceeds 4, or the current limit set is over 300%. Example: 35-Second Ramp, 5 Starts per Hour, 350% Current Limit @ 40°C Ambient.
MN03902002E
For more information visit: www.EatonElectrical.com
C-7
IT. S811 Soft Starter User Manual
Cooling
Microcontroller controlled fans are used to cool the IT. Soft Starter. The fans are turned on when the temperature of any of the thermal sensors exceeds preset value. Once the fans are started, they will not go off until the temperature goes below the off set point for 10 minutes.
The fans will also be turned on whenever the IT. is started, stopped or jogged. The fans will remain on for 10 minutes to assure the SCRs are adequately cooled prior to the next start.
If a temperature is sensed above a second preset level, a Pole Over-Temperature Fault will occur. This fault cannot be reset until the temperature returns to a safe level.
Note: The fans will only operate if 24V DC is applied to the + and – terminals. Cycling power
during the 10 minute timeout after a start, stop or jog will reset the fans to off.
Power Losses
The following table lists the maximum power loss for each IT. Soft Starter when it is operating in the across-the-line mode with its bypass contactor pulled in. These losses should be used in conjunction with the losses of another cabinet mounted device to determine the enclosure size and any cooling requirements.
Table C-8: Maximum Power Loss
Frame Size
Catalog Number
Current Range for a Line Connection
November 2006
Across-the-Line­Losses (Watts)
N S811N37xxx 11 – 37 30
S811N66xxx 20 – 66 33
R S811R10xxx 32 – 105 47
S811R13xxx 42 – 135 55
T S811T18xxx 56 – 180 37
S811T24xxx 75 – 240 40 S811T30xxx 95 – 304 45
U S811U36xxx 112 – 360 76
S811U42xxx 131 – 420 92
S811U50xxx 156 – 500
V S811V36xxx 112 – 360 56
S811V42xxx 131 – 420 64 S811V50xxx 156 – 500 78 S811V65xxx 203 – 650 109 S811V72xxx 225 – 720 127 S811V85xxx 265 – 850 164 S811V10xxx 310 – 1000 215
500A rating does not have IEC certification.
116
C-8 For more information visit: www.EatonElectrical.com
MN03902002E
IT. S811 Soft Starter User Manual
November 2006
Appendix D — Ratings, Cooling and Power Losses for an Inside-the-Delta Connected Motor
Horsepower and kW Ratings
Inside-the-Delta Standard Duty Ratings
Table D-1: 15 Second Ramp, 4 Starts per Hour, 300% Current Limit @ 40°C Ambient
Three-Phase Motor
Max. Continuous Motor Line Current
Frame Size N
65
114
Frame Size R
182 234
Frame Size T
311 415 526
Frame Size U
623 727 865
Frame Size V
623 727
865 1125 1246 1471 —
Does not have IEC certification.
kW Rating (50 Hertz) hp Rating (60 Hertz)
200V 230V 460V 575V
1.0SF 1.15SF 1.0SF 1.15SF 1.0SF 1.15SF 1.0SF 1.15SF
59 80
30
50 60
100 125 150
200 250 250
200 250 250 400 — — —
15 25
40 50
75 100 125
150 200 250
150 200 250 300 — — —
15 30
60 75
100 125 150
250 300 300
250 300 300 400 — — —
230V
10
18.5
30 40
51 75 90
110 129 150
110 129 150 200 — — —
380 – 400V 440V
18.53018.53715
55 63
90 110 160
185 220 257
185 220 257 355 — — —
110 147 185
220 257 300
220 257 300 425 — — —
15 30
5060125
100 125 150
200 250 250
200 250 250 300 — — —
40 75
150
250 300 400
450 550 600
450 550 600 750 — — —
30 6050100
100 125
200 250 300
400 450 550
400 450 550 700 — — —
150 200
250 300 400
550 700 750
550 700 750 900 — — —
Catalog Number
5075S811N37xxD
S811N66xxD
125 150
250 300 400
450 550 700
450 550 700 750 — — —
S811R10xxD S811R13xxD
S811T18xxD S811T24xxD S811T30xxD
S811U36xxD S811U42xxD S811U50xxD
S811V36xxD S811V42xxD S811V50xxD S811V65xxD S811V72xxD S811V85xxD S811V10xxD
MN03902002E
For more information visit: www.EatonElectrical.com
D-1
IT. S811 Soft Starter User Manual
Table D-2: 25 Second Ramp, 4 Starts per Hour, 300% Current Limit @ 40°C Ambient
Three-Phase Motor
Max. Continuous Motor Line Current
Frame Size N
58
108
Frame Size R
164 206
Frame Size T
257 365 477
Frame Size U
554 646 796
Frame Size V
554 646
796 1055 1176 1358 —
Does not have IEC certification.
kW Rating (50 Hertz) hp Rating (60 Hertz)
200V 230V 460V 575V
1.0SF 1.15SF 1.0SF 1.15SF 1.0SF 1.15SF 1.0SF 1.15SF
18.53315 30
55 63
90
50 60
75
100 125
150 200 250
150 200 250 400 — — —
10 25
40 50
60 100 125
125 150 200
125 150 200 250 300 — —
15 30
50 60
75 125 150
200 250 250
200 250 250 300 400 — —
230V
9
15
25 33
45 63 80
90 110 140
90 110 140 185 200 — —
380 – 400V 440V
15 30
45 63
80 110 147
160 200 250
160 200 250 315 375 — —
132 160
185 220 280
185 220 280 375 445 — —
15 30
5050125
60 100 125
150 200 250
150 200 250 300 300 — —
40 60
125
150 250 300
400 500 550
400 500 550 800 900 — —
30 6050100
100 125
150 250 300
300 400 500
300 400 500 700 800 — —
125 150
250 300 400
450 550 700
450 550 700 900 900 — —
40 75
125 150
200 250 400
400 450 600
400 450 600 750 900 — —
November 2006
Catalog Number
S811N37xxD S811N66xxD
S811R10xxD S811R13xxD
S811T18xxD S811T24xxD S811T30xxD
S811U36xxD S811U42xxD S811U50xxD
S811V36xxD S811V42xxD S811V50xxD S811V65xxD S811V72xxD S811V85xxD S811V10xxD
D-2 For more information visit: www.EatonElectrical.com
MN03902002E
IT. S811 Soft Starter User Manual
November 2006
Table D-3: 15 Second Ramp, 4 Starts per Hour, 300% Current Limit @ 50°C Ambient
Three-Phase Motor
Max. Continuous Motor Line Current
Frame Size N
58
108
Frame Size R
164 206
Frame Size T
257 365 477
Frame Size U
554 646 796
Frame Size V
554 646
796 1055 1176 1358 —
Does not have IEC certification.
kW Rating (50 Hertz) hp Rating (60 Hertz)
200V 230V 460V 575V
1.0SF 1.15SF 1.0SF 1.15SF 1.0SF 1.15SF 1.0SF 1.15SF
18.53315 30
55 63
90
50 60
75
100 125
150 200 250
150 200 250 400 — — —
10 25
40 50
60 100 125
125 150 200
125 150 200 250 — — —
15 30
50 60
75 125 150
200 250 250
200 250 250 300 — — —
230V
9
15
25 33
45 63 80
90 110 140
90 110 140 185 200 257 —
380 – 400V 440V
15 30
45 63
80 110 147
160 200 250
160 200 250 315 375 450 —
132 160
185 220 280
185 220 280 375 445 500 —
15 30
5060125
75 100 125
150 200 250
150 200 250 300 — — —
40 60
125
150 250 300
400 450 550
400 450 550 750 — — —
30 6050100
100 125
150 250 300
300 400 450
300 400 450 700 — — —
125 150
250 300 400
450 550 700
450 550 700 900 — — —
Catalog Number
4075S811N37xxD
S811N66xxD
125 150
200 250 400
400 450 600
400 450 600 750 — — —
S811R10xxD S811R13xxD
S811T18xxD S811T24xxD S811T30xxD
S811U36xxD S811U42xxD S811U50xxD
S811V36xxD S811V42xxD S811V50xxD S811V65xxD S811V72xxD S811V85xxD S811V10xxD
MN03902002E
For more information visit: www.EatonElectrical.com
D-3
IT. S811 Soft Starter User Manual
Table D-4: 50 Second Ramp, 2 Starts per Hour, 300% Current Limit @ 50°C Ambient
Three-Phase Motor
Max. Continuous Motor Line Current
Frame Size N
36 73
Frame Size R
103 138
Frame Size T
199 257 324
Frame Size U
485 580 646
Frame Size V
485 580 646 727
816 1021 —
Does not have IEC certification.
kW Rating (50 Hertz) hp Rating (60 Hertz)
200V 230V 460V 575V
1.0SF 1.15SF 1.0SF 1.15SF 1.0SF 1.15SF 1.0SF 1.15SF
7-1/2157-1/2157-1/2257-1/21525
230V
5.51110
380 – 400V 440V
18.51122
15 22
33 45 55
80 100 110
80 100 110 129 147 180 —
30 40
59 80
100
150 180 200
150 180 200 220 257 315 —
33 45
63 90
110
160 200 220
160 200 220 257 295 375 —
25 40
50 75
100
125 150 200
125 150 200 250 250 300 —
25 30
50 60 75
125 150 150
125 150 150 200 250 250 —
100
150 200 250
150 200 250 250 300 300 —
30 50
60 75
25 40
50 75
100
125 150 200
125 150 200 250 250 300 —
50
60
100
125 150 250
300 400 450
300 400 450 550 600 750 —
15 40
25 60
60 757512575100
125 150 200
300 300 400
300 300 400 500 550 600 —
150 250 300
400 550 550
400 550 550 700 750 900 —
November 2006
Catalog Number
2550S811N37xxD
S811N66xxD
S811R10xxD S811R13xxD
150 200 250
400 450 450
400 450 450 550 700 750 —
S811T18xxD S811T24xxD S811T30xxD
S811U36xxD S811U42xxD S811U50xxD
S811V36xxD S811V42xxD S811V50xxD S811V65xxD S811V72xxD S811V85xxD S811V10xxD
D-4 For more information visit: www.EatonElectrical.com
MN03902002E
IT. S811 Soft Starter User Manual
November 2006
Table D-5: 15 Second Ramp, 4 Starts per Hour, 450% Current Limit @ 40°C Ambient
Three-Phase Motor
Max. Continuous Motor Line Current
Frame Size N
47 83
Frame Size R
126 162
Frame Size T
266 379 485
Frame Size U
580 695 798
Frame Size V
580 695 798
908 1021 1125
Does not have IEC certification.
kW Rating (50 Hertz) hp Rating (60 Hertz)
200V 230V 460V 575V
1.0SF 1.15SF 1.0SF 1.15SF 1.0SF 1.15SF 1.0SF 1.15SF
25
40 55
90
10 25
30 50
75 100 125
150 200 250
150 200 250 250 — —
10 15
30 40
60 100 125
150 150 200
150 150 200 250 — —
15 25
40 50
100 125 150
200 250 250
200 250 250 300 — —
230V
7.5
12.5
18.52537
45 63 80
100 110 140
100 110 140 160 — —
380 – 400V 440V
12.52215
45
80 110 150
185 200 250
185 200 250 280 — —
132 160
200 250 280
200 250 280 335 — —
10 25
30 50
75 100 125
150 200 250
150 200 250 250 — —
30 50
25 50
75
10060100
150 250 300
400 450 550
400 450 550 700 — —
150 250 300
300 400 450
300 400 450 550 — —
40 60
100 125
250 300 400
550 600 700
550 600 700 750 — —
Catalog Number
3060S811N37xxD
S811N66xxD
100 125
200 250 400
450 550 600
450 550 600 700 — —
S811R10xxD S811R13xxD
S811T18xxD S811T24xxD S811T30xxD
S811U36xxD S811U42xxD S811U50xxD
S811V36xxD S811V42xxD S811V50xxD S811V65xxD S811V72xxD S811V85xxD
MN03902002E
For more information visit: www.EatonElectrical.com
D-5
IT. S811 Soft Starter User Manual
Table D-6: 30 Second Ramp, 4 Starts per Hour, 450% Current Limit @ 40°C Ambient
Three-Phase Motor
Max. Continuous Motor Line Current
Frame Size N
36 69
Frame Size R
96
130
Frame Size T
257 365 448
Frame Size U
503 580 646
Frame Size V
503 580 646 727 796 865
Does not have IEC certification.
kW Rating (50 Hertz) hp Rating (60 Hertz)
200V 230V 460V 575V
1.0SF 1.15SF 1.0SF 1.15SF 1.0SF 1.15SF 1.0SF 1.15SF
12.5
7-1/2157-1/2157-1/2157-1/21525
22
30 45
90
25 30
75 100 125
150 150 200
150 150 200 250 — —
25 30
60 100 125
125 150 150
125 150 150 200 — —
125 150
150 200 250
150 200 250 250 — —
230V
5.51110
15 22
45 63 80
90 100 110
90 100 110 129 — —
380 – 400V 440V
18.5
25 37
80 110 140
160 180 200
160 180 200 220 — —
132 160
185 200 220
185 200 220 257 — —
30 40
75
25 30
75 100 125
150 150 200
150 150 200 250 — —
50
60 75
150 250 300
300 400 450
300 400 450 550 — —
15 40
25 50
50 757510060100
150 250 250
300 300 400
300 300 400 450 — —
250 300 400
450 550 550
450 550 550 700 — —
November 2006
Catalog Number
2550S811N37xxD
S811N66xxD
S811R10xxD S811R13xxD
200 250 300
400 450 450
400 450 450 550 — —
S811T18xxD S811T24xxD S811T30xxD
S811U36xxD S811U42xxD S811U50xxD
S811V36xxD S811V42xxD S811V50xxD S811V65xxD S811V72xxD S811V85xxD
D-6 For more information visit: www.EatonElectrical.com
MN03902002E
November 2006
Inside-the-Delta Severe Duty Ratings
Table D-7: Severe Duty Inside-the-Delta Ratings
Three-Phase Motor
Max. Continuous Motor Line Current
Frame Size N
39 73
Frame Size R
111 138
Frame Size T
199 257 324
Frame Size U
415 526 623
Frame Size V
415 526 623 727 816 908 —
kW Rating (50 Hertz) hp Rating (60 Hertz)
200V 230V 460V 575V
1.0SF 1.15SF 1.0SF 1.15SF 1.0SF 1.15SF 1.0SF 1.15SF
7-1/2157-1/21510
230V
5.51110
380 – 400V 440V
18.51122
15 22
33 45 55
75 90
110
75
90 110 129 147 160 —
30 40
59 80
100
110 160 185
110 160 185 220 257 280 —
33 45
63 90
110
147 185 220
147 185 220 257 295 335 —
25 40
50 75
100
125 150 200
125 150 200 250 250 250 —
25 30
50 60 75
100 120 150
100 120 150 200 250 250 —
25
30 50
60 75
100
125 150 250
125 150 250 250 300 300 —
7-1/21525
25 40
50 75
100
125 150 200
125 150 200 250 250 250 —
50
75
100
125 150 250
300 400 450
300 400 450 550 600 700 —
IT. S811 Soft Starter User Manual
15 40
60 757512075100
125 150 200
250 300 400
250 300 400 450 550 550 —
30 60
150 250 300
300 450 550
300 450 550 700 750 750 —
Catalog Number
2550S811N37xxD
S811N66xxD
S811R10xxD S811R13xxD
150 200 250
300 400 450
300 400 450 550 700 700 —
S811T18xxD S811T24xxD S811T30xxD
S811U36xxD S811U42xxD S811U50xxD
S811V36xxD S811V42xxD S811V50xxD S811V65xxD S811V72xxD S811V85xxD S811V10xxD
Does not have IEC certification.
Severe Duty Ratings are defined as any combination of parameters that exceed the Standard Duty Ratings where the ramp time is over 30 seconds, the number of starts per hour exceeds 4, or the current limit set is over 300%. Example: 35-Second Ramp, 5 Starts per Hour, 350% Current Limit @ 40°C Ambient.
MN03902002E
For more information visit: www.EatonElectrical.com
D-7
IT. S811 Soft Starter User Manual
Cooling
Microcontroller controlled fans are used to cool the IT. Soft Starter. The fans are turned on when the temperature of any of the thermal sensors exceeds preset value. Once the fans are started, they will not go off until the temperature goes below the off set point for 10 minutes.
The fans will also be turned on whenever the IT. is started, stopped or jogged. The fans will remain on for 10 minutes to assure the SCRs are adequately cooled prior to the next start.
If a temperature is sensed above a second preset level, a Pole Over-Temperature Fault will occur. This fault cannot be reset until the temperature returns to a safe level.
Note: The fans will only operate if 24V DC is applied to the + and – terminals. Cycling power
during the 10 minute timeout after a start, stop or jog will reset the fans to off.
Power Losses
The following table lists the maximum power loss for each IT. Soft Starter when it is operating in the across-the-line mode with its bypass contactor pulled in. These losses should be used in conjunction with the losses of another cabinet mounted device to determine the enclosure size and any cooling requirements.
Table D-8: Maximum Power Loss
Frame Size
Catalog Number
Current Range for an Inside-the-Delta Connection
November 2006
Across-the-Line­Losses (Watts)
N S811N37xxD 19 – 65 30
S811N66xxD 35 – 114 33
R S811R10xxD 55 – 182 47
S811R13xxD 73 – 234 55
T S811T18xxD 97 – 311 37
S811T24xxD 130 – 415 40 S811T30xxD 164 – 526 45
U S811U36xxD 193 – 623 76
S811U42xxD 227 – 727 92 S811U50xxD 270 – 865 116
V S811V36xxD 193 – 623 56
S811V42xxD 227 – 727 64 S811V50xxD 270 – 865 78 S811V65xxD 352 – 1125 109 S811V72xxD 389 – 1246 127 S811V85xxD 458 – 1471 164
D-8 For more information visit: www.EatonElectrical.com
MN03902002E
November 2006
Appendix E — Motor/Application Considerations
Using MOVs
Most utility power systems experience periodic transient voltages. Line or power factor correction capacitor switching, nearby lightning strikes, utility supply faults, or a user starting or shutting down a large load such as a motor can cause these voltages. The IT. Soft Starter has been designed to handle transient voltages of up to 4 kV lasting up to 20 µS.
If transient voltages of greater magnitude or longer duration than the standard withstand capability are expected, a protective module must be installed. The protective module contains metal oxide varistors (MOVs). MOVs are devices that remain in a passive state until a transient voltage occurs. Under the transient condition, the MOV turns on and holds the peak line voltage down to a level less than the IT. transient voltage rating. When the transient clears, the MOV returns to a passive state.
Eaton offers two MOV option kits:
Table E-1: MOV Kit Options
Catalog Number Description
IT. S811 Soft Starter User Manual
EMS38 600V (max) MOV for S811N and S811R Soft Start
EMS39 600V (max) MOV for S811T and S811V Soft Start EMS41 690V (max) MOV for S811T, V35 and S811V, V35
The EMS38 is panel mounted, while the EMS39 and EMS41 are mounted directly on the IT. Soft Starter.
In situations where an MOV must be used, the installer may choose to apply a different transient absorption device, but it must be equivalent to the EMS38, EMS39 or EMS41. These MOVs may also be used on the load side of the soft starter where long cables connect the motor to the soft starter or where the cables are located outdoors.
Squirrel Cage Motor
This is the most common application. The motor is configured with three motor leads available. In this case, wire the motor to the soft starter with one lead per phase, observing proper
phase rotation. An in-sight disconnect means should be installed, per code requirements.
(side mounted)
MN03902002E
For more information visit: www.EatonElectrical.com
E-1
IT. S811 Soft Starter User Manual
Wye-Delta Motor
The wye-delta motor is a traditional way of achieving a reduced voltage start using regular contactors and starters. In this method, the motor is constructed with all six leads brought out to connect the unit in a wye configuration. This allows about 58% of the current (33% starting torque) to be applied during start-up. A timer is used to control the circuit and switch to the delta configuration as the unit approaches full speed.
In this case, wire the six-lead motor in a standard delta configuration. The soft starter is then used to control the voltage and motor torque without the need for additional circuitry. An in­sight disconnect means should be installed, per local code. The IT. Soft Starter must be wired into the three-phase line feeding the three main motor input leads as would be done for normal across-the-line starting. It must not be wired internally between motor windings in
an inside-the-delta configuration. If an inside-the-delta starting configuration is desired, please contact Eaton for details about our inside-the-delta soft starters, designated S811xxxxxD.
Part Winding Motor
The part winding motor is another design created to help achieve a soft start to the load. A part winding motor is constructed of two separate (but parallel) windings. When using a traditional starter, the first winding would receive full voltage. This winding supplies as much as 400% of the motors FLA; about 45% starting torque in a delta configuration for motor start­up. After a timed delay, full voltage is applied to the second winding. The second winding acts in parallel with the first to provide for normal running current. Part winding motors are available in both a wye and delta configuration, dependent upon the manufacturer. Refer to the motor nameplate for the correct wiring information. In this case, wire the two windings in parallel. The soft starter is then used to control the current applied to the motor. An in-sight disconnect means should be installed, per code requirements.
November 2006
Dual Voltage Motor
A dual voltage motor should be wired into the appropriate configuration for the line voltage it is being applied to. Refer to the motor nameplate for the correct wiring information. The soft starter must be selected for the appropriate line voltage.
Multi-Speed Motor
Some motors have multiple windings to allow operation at different base speeds. The multiple speeds are sometimes utilized for soft starting and other times for a process requirement of the machine to which it is attached. If only one speed is required, the motor should be wired for that speed. If multiple speeds are required, the appropriate contactors will need to be connected to the output of the Soft Starter. The contactors must be in the selected speed position before the soft starter is started. The motor must be stopped and the soft starter turned off before the speed selection contactors are changed.
E-2 For more information visit: www.EatonElectrical.com
MN03902002E
November 2006
Precaución
!
Other Winding Configurations
Motors with other winding configurations, designed for specific characteristics, should be wired in a fashion consistent with their intended use. The motor nameplate contains information on the available configurations. The motor winding configuration chosen must be appropriate for the available line voltage. The soft starter must also be selected on the basis of the configuration chosen.
Power Factor Correction Capacitors
Power factor correction capacitors should be installed on the line side of the soft starter. It is recommended that at least 10 feet of cable be between the capacitor and the soft starter. The power factor correction capacitors can be switched with a separate contactor. NEMA ICS2­1988 Part 2-210.81.01 provides recommendations for when a separate contactor should be used to switch the power factor correction capacitor including high inertia loads, reversing motors, frequently jogged motors and multi-speed motors.
It is not recommended that the power factor correction capacitors be used on the load side of the soft starter. If used on the load side, the overload relay will measure the combination of capacitor and motor current causing the overload relay to not function correctly.
IT. S811 Soft Starter User Manual
Caution
!
Never megger a motor while it is connected to the IT. Soft Starter. Disconnect the leads at the IT. Soft Starter before meggering the motor.
Attention
!
Ne jamais régler un moteur alors qu’il est branché au démarreur progressif IT. Débrancher les fils au démarreur progressif IT. Avant de régler le moteur.
Nunca efectúe pruebas del motor con un megóhmetro mientras esté conectado al arrancador Soft Starter IT. Desconecte los cables en el arrancador IT. antes de usar el megóhmetro.
MN03902002E
For more information visit: www.EatonElectrical.com
E-3
Loading...