Cutler Hammer, Div of Eaton Corp S801 Technical Specifications

Reduced Voltage Motor Starters Solid-State Starters
April 2007
Standards and Certifications
IEC 947 compliant
CSA Certification
Technical Data and Specifications
Table 27. Specifications— IT. Soft Starter
Soft Starter (Partial Catalog Number)
Max. Current Capacity 37 66 105 135 180 240 304 360 420 500 360 420 500 650 720 850 1000
Dimensions
Width in Inches (mm) 2.60 (66.0) 4.37 (111.0) 7.65 (194.4) 7.73 (196.3) 11.03 (280.2) Height in Inches (mm) 7.38 (187.4) 7.92 (201.1) 12.71 (322.9) 12.72 (323.1) 16.57 (420.8) Depth in Inches (mm) 6.63 (168.4) 7.03 (178.6) 6.69 (169.8) 7.08 (179.9) 7.23 (183.7) Weight in lbs. (kg) 5.8 (2.6) 10.5 (4.8) 48 (21.8) w/Lugs
General Information
Bypass Mechanical Lifespan 10M Insulating Voltage Ui 660V Ramp Time Range .5 – 180 Seconds (.5 – 360 Seconds Extended Ramp) Resistance to Vibration 3g Resistance to Shock 15g
Electrical Information
Operating Voltage 200 – 600V Operating Frequency 47 – 63 Hz Overload Setting 30 – 100% Trip Class 5, 10, 20, & 30
Cabling Capacity (IEC 947)
Number of Conductors 1 1 1 or 2 1 or 2 2, 4 or 6 Wire Sizes 14 – 2 14 – 4/0 4 AWG to 500 MCM 4 AWG to 500 MCM 2/0 to 500 MCM Type of Connectors Box Lug Add-On Lug Kit
Control Wiring (12-Pin)
Wire Sizes in AWG 22 – 14 Number of Conductors
(Stranded) Torque Requirements
in lb-in Solid, Stranded or Flexible Max.
Size in mm
2
Control Power Requirements
Voltage Range (24V ± 10%) 21.6 – 26.4 Steady State Current Amps 1.0 1.0 1.0 1.0 1.4 Inrush Current Amps 10 10 10 10 10 Ripple 1%
Relays (1) Class A and C
Voltage AC — maximum 240 Voltage DC — maximum 120 Amps — maximum 3
Environment
Temperature — Operating -30 – 50°C (No derating) Consult factory for operation > 50° C Temperature — Storage -50 – 70°C Altitude <2000 Meters — Consult factory for operation > 2000m Humidity <95% Non-condensing Operating Position Any Pollution degree IEC947-1 3 Impulse withstand Voltage
IEC947-4-1
U-Frame 500 Amp unit does not have IEC Certification.
UR Recognized Product.
S801 N37
S801 N66
S801 R10
Type S801, Intelligent Technologies (IT.) Soft Starters
cUL
CE marked
Listed (File # E202571)
US
S801
S801
R13
S801
T18
T24
41 (18.6) w/o Lugs
S801 T30
S801
S801
U36
U42
48 (21.8) w/Lugs
41 (18.6) w/o Lugs
2
(or one AWG 12)
3.5
3.31
6000V
S801 U50
S801 V36
S801 V42
S801
S801
V50
V65
103 (46.8) w/Lugs
91 (41.4) w/o Lugs
S801 V72
S801 V85
S801 V10
13
CA03902005E For more information visit: www.eaton.com
Loading...