Cutler Hammer, Div of Eaton Corp S752 Application Note

10
10
18
Solid-State Soft Start Motor Controller and Starter
Application Note
Contents
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
About This Guide . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Basic Motor and Soft Start Theory
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
AC Motors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
AC Motor Types . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Induction Motors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Enclosures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Ventilation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Control of AC Motors . . . . . . . . . . . . . . . . . . . . . . . . . 3
Soft Start Basics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Soft Start Applications . . . . . . . . . . . . . . . . . . . . . . . . 5
Other Reduced Voltage Starting Methods . . . . . . . . 5
Basic Mechanics
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Torque . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Calculating Torque . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Calculating Horsepower . . . . . . . . . . . . . . . . . . . . . . . 7
Inertia . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Calculations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Cylinders . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Pulley/Gear . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
2
WK
Reflected to the Motor Shaft . . . . . . . . . . . . . . . 8
Speed Reducer Selection . . . . . . . . . . . . . . . . . . . . . . 9
Gear Reducer Selection . . . . . . . . . . . . . . . . . . . . . . . 9
Gear Reducer — Overhung Load . . . . . . . . . . . . . . . . 9
Other Gear Issues . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Controllers and Starters, Theory and Application
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Benefits of Using Soft Start Controllers and
Starters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Basic Principles of Soft Start Controllers and
Starters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Load Characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Typical Soft Start Adjustments . . . . . . . . . . . . . . . . . 11
Motor Application Considerations . . . . . . . . . . . . . . 12
Installation Compatibility . . . . . . . . . . . . . . . . . . . . . . 12
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
. . . . . . . . . . . . . . . . 2
. . . . 10
Load Types and Characteristics
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Load Types . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Other Functional Considerations . . . . . . . . . . . . . . . 13
Typical Load Torque . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Controller and Starter Selection
Selection Considerations . . . . . . . . . . . . . . . . . . . . . . 15
Selecting a Soft Start for a Machine . . . . . . . . . . . . . 15
Measuring Machine Torque . . . . . . . . . . . . . . . . . . . . 16
Soft Start Application Questions . . . . . . . . . . . . . . . . 16
Soft Starter Application Data Worksheet . . . . . . . . . 17
Formulae, Conversions and Tables
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
How to Calculate Torque . . . . . . . . . . . . . . . . . . . . . . 18
How to Calculate Horsepower . . . . . . . . . . . . . . . . . . 18
How to Calculate Surface Speed . . . . . . . . . . . . . . . . 18
How to Calculate Horsepower for Pumps . . . . . . . . 18
How to Calculate Horsepower for Fans and
Blowers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
How to Calculate Horsepower for Conveyors . . . . . 18
How to Calculate Accelerating Torque . . . . . . . . . . . 18
How to Calculate Maximum Motor Torque . . . . . . . 19
How to Calculate WK How to Calculate Equivalent WK
Electrical Formulae . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Induction Motor Formulae . . . . . . . . . . . . . . . . . . . . . 20
Tables of Conversions and Abbreviations . . . . . . . . 20
Glossary
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
. . . . . . . . . . . . . . . . . . . 12
. . . . . . . . . . . . . . . . . . 15
. . . . . . . . . . . . . . . . 18
2
. . . . . . . . . . . . . . . . . . . . . . . . 19
2
at Motor Shaft . . 19
AP03902001E For more information visit: www.EatonElectrical.com
Application Note
Page 2
Introduction
About This Guide
The following material is intended to acquaint the user with the theory and operation of solid-state soft start motor controllers and starters. This material will enable the user to better select the controller or starter and take into consideration the parameters nec­essary for proper application to a given load.
The reference material provided is for the convenience of the user. It is taken from current handbooks and stan­dards such as NEC, NEMA, IEEE and others. It is intended as reference material for standard applications and may not cover all actual and special applications. Experienced factory application engineers are available to assist users in the application of motor controllers and starters for most motor loads. Specific ratings and external signals used for control and logic are the user’s responsibility.
The user must determine the final suitability and acceptability for con­trollers and starters used on specific equipment.
Basic Motor and Soft Start Theory
Introduction
A solid-state soft start controller or starter controls the starting torque and current of an AC motor electronically.
They can be used in almost any application such as:
commercial – HVAC fans and pumps
general industrial – fans, pumps, conveyors, material handling and processing equipment
others – forest products, mining, metals and printing
The guide provides the basics required to evaluate motor controller and starter application needs.
Effective: February 2005
Solid-State Soft Start Motor Controller and Starter
AC Motor Types
AC motors can be divided into two main types: Induction and Synchro­nous. In this guide we will only cover the use of a three-phase induction motor and soft starter device, although in some cases a soft starter device may be used with a single-phase motor.
Induction Motors
The induction motor is the simplest and most rugged of all electric motors. The typical varieties are the standard induction motor and the wound rotor motor.
Three-Phase
The three-phase induction motor is divided into four classifications according to NEMA. (Note that there are IEC design standards which differ somewhat from the NEMA versions.) The classification or design, is deter­mined by the locked rotor torque and current, breakdown torque, pull-up torque and the percent slip. The speed-torque curve and characteristics of each design are given below. These characteristics apply for operation from fixed frequency and voltage as normally supplied from commercial utility power sources at 60 Hz.
Design A motors have a slightly
higher breakdown, and lower start­ing torque than Design B motors. The slip is usually 3 to 5% or less. The major difference between the Design A and Design B motor is that the starting current is limited on the Design B, but not on the Design A. Design A motors are applied to the same applications as Design B motors. Design A motors may be used with solid-state soft start devices.
%
Rated
Tor qu e
300
200
Breakdown
(Maximum)
To rq ue
Design B motors are general pur-
pose type motors and account for the largest share of the induction motors sold. The slip of a Design B motor is approximately 3 to 5% or less. Design B motors are used on applications where starting torque requirements are low such as gen­eral industry, fans, blowers and cen­trifugal pumps and compressors. Design B motors are often used with solid-state soft start devices.
%
Rated
Tor qu e
300
200
100
0
020406080100
% Rated Speed
Figure 2. Design B Polyphase Motor
Design C motors have a high start-
ing torque with a normal starting current and low slip. The Design C motor is usually used where break­away loads are high at starting, but are normally run at rated full load, and are not subject to high overload demands after running speed has been reached. The slip of the Design C motor is 5% or less. Design C motors are often used where high starting torques under loaded condi­tions are required including crush­ers, agitators, reciprocating pumps and high friction conveyors. Care must be exercised when using a Design C motor with a soft start con­troller or starter to assure that the application starting torque and time to start requirements can be met.
%
Rated
Tor qu e
300
AC Motors
Cutler-Hammer and starters operate with standard motors. In most cases, an existing motor sized for another method of soft start, can be directly applied. For new installations the user must understand the nature of the application in terms of the load characteristic requirements and the motor capability when used with a soft start controller or starter.
®
soft start controllers
100
0
02040
% Rated Speed
Figure 1. Design A Polyphase Motor
For more information visit: www.EatonElectrical.com
60 80
100
200
100
0
020406080100
% Rated Speed
Figure 3. Design C Polyphase Motor
AP03902001E
Design D motors have high slip,
high starting torque, low starting current and low full load speed. Because of the high amount of slip, the speed will vary if fluctuating loads are encountered. The slip of this type of motor is approximately 5 to 13%. Design D motors are used on applications with high peak loads with flywheels like punch presses, shears, hoists, oil well pumps and extractors. Care must be exercised when using a Design D motor with a soft start controller or starter, since the limitation of the starting torque or increase of the starting time may cause thermal concerns for the motor and soft start.
%
Rated
Tor que
300
200
100
0
020406080
% Rated Speed
Figure 4. Design D Polyphase Motor
100
Wound Rotor Motors
The wound rotor motor allows control­lable speed and torque compared to the conventional induction motor. Wound rotor motors are generally started with a secondary resistance in the rotor. As the resistance is reduced, the motor will come up to speed. Thus the motor can develop substantial torque while limiting the locked rotor current. The secondary resistance can be designed for continuous service to dissipate the heat produced by contin­uous operation at reduced speed and frequent start/stops or acceleration of a large inertia load. This external resis­tance gives the motor a characteristic that results in a large drop in rpm for a small change in load. Reduced speed typically can be provided down to approximately 50% of rated speed, although at a very low efficiency.
These motors are sometimes used (in large horsepower ratings) in slip recovery systems. In these systems the external (secondary) resistance element is replaced with a solid-state circuit to convert the rotor slip energy to useful AC power. These motors can be used with a soft starter in some applications. The use is dependent
Solid-State Soft Start Motor Controller and Starter
upon why the motor’s secondary resis­tance was selected and how the use of the soft starter will impact the load requirements. If the rotor resistance was selected to be stepped through various sizes to provide a gentle start, a soft starter can likely be used. If the resistor is just a single value and was selected to give high starting torque, the use of a soft starter might not allow the same level of torque to be generated. The application require­ments must be determined.
Enclosures
The basic protective enclosures for AC motors are: open dripproof (ODP), totally enclosed fan cooled (TEFC), totally enclosed non-ventilated (TENV) and totally enclosed air over (TEAO). Other special enclosures available include: pipe-ventilated, weather pro­tected, water cooled and explosion proof.
Ventilation
The system for ventilating motors depends on the type of motor enclo­sure as mentioned previously and described below:
ODP (Open Dripproof) – The ODP
motor is ventilated (cooled) by means of a shaft mounted internal fan which drives air through the open ends of the motor and dis­charges it out the sides. These motors are often supplied as protected, fully-guarded or splash-proof.
TEFC (Totally Enclosed Fan Cooled)
– This type of motor is cooled by air passing over the outer frame of the motor. The air is supplied by a shaft mounted fan opposite the shaft end of motor.
TENV (Totally Enclosed Non-
Ventilated)
a shaft mounted internal fan used to circulate air within the motor to pre­vent hot spots. No external fan or air is supplied. These are suitable for very dirty and contaminant laden environments that would clog most exposed cooling fans. These motors dissipate their heat through their frames and are thus oversized com­pared to other enclosure types. They are generally available only in smaller hp ratings (up to 7-1/2 hp).
– This type of motor has
Application Note
Effective: February 2005 Page 3
TEAO (Totally Enclosed Air Over)
This type of motor is cooled by externally provided air blowing over the frame. The air may be supplied by an integrally mounted blower and motor or from a separate source. This type of ventilation provides constant cooling under all operating conditions.
Special Enclosures – The Pipe-
Ventilated motor is available for either an open or totally enclosed type of enclosure and is used in very dirty environments. Ventilating air (supplied by the User) enters and exits the motor through inlet and outlet ducts or pipes. The air is cir­culated by means either integral or external to the motor.
The Weather-Protected motor uses an open type enclosure for ventila­tion. The motor is constructed to minimize the entrance of rain, snow and airborne particles to the electri­cal parts of the motor. External air can be circulated through the motor for cooling.
Totally Enclosed Air-to-Air and Totally Enclosed Water-to-Air cooled enclosures are normally used on high horsepower motors that gener­ate large amounts of heat. A heat exchanger is used for both types to remove the heat generated by the motor. An AC motor driven blower circulates air through the windings and heat exchanger tubes. The heat in the heat exchanger is removed by either an external air system (air-to­air) or water provided by the user (water-to-air cooled).
Explosion Proof motors are designed to operate in hazardous environments such as explosive vapors, coal or grain dust and other classified areas. These are selected on the basis of the appropriate Class, Group, and Division of haz­ard, as defined by the National Elec­trical Code (NEC).
Control of AC Motors
The most common control of an AC motor is by using a motor starter. This device connects the motor to the com­mercial AC power line. It is rated to operate with the typical high starting (inrush) current that occurs when a motor is directly connected to the util­ity line. A motor starter also contains a protective device known as a motor overload. This device is designed to protect the motor from continued overloads and stalling due to exces­sive machine loads on starting or jam­ming when operating.
AP03902001E For more information visit: www.EatonElectrical.com
Application Note
Page 4
With the above method of control, AC motors will operate as described by their NEMA (or IEC) characteristics for their design type on industrial AC power. This includes a prescribed overload capability, regulation due to slip, starting inrush current and start­ing (locked rotor) torque. The load on the driven machine determines the acceleration time and motor load (or overload).
Special control hardware is available to modify some of the above charac­teristics. Part winding, autotrans­former and wye-delta motor starters will reduce the inrush current when starting an AC motor. But using these devices does not provide for a soft controlled stepless start.
Solid-state soft start motor controllers and starters have the ability to control the starting characteristics to match the application requirements, such as acceleration and deceleration time, starting and overload current and motor torque. In addition, motor protection may be provided for a number of potential damaging circum­stances by the soft starter (a soft start controller does not provide any motor protection).
Soft Start Basics
Why do we want to use a reduced volt­age soft starter?
The first reason is to limit the inrush current that a motor draws from the utility when it is first started. This is a concern because the large starting cur­rent may cause the line voltage to dip, impacting other loads which are sensi­tive to low voltages. There may also be a concern if the utility limits the peak current which can be drawn or charges for exceeding the limit.
The second is reduced mechanical system stress. When the large inrush current occurs, there are significant magnetic forces created in the motor windings. These cause some parts of the winding to be attracted to each other and other parts repulsed. This mechanical shock can damage the winding insulation leading to early fail­ure. The mechanical shock of the high torques produced with the large start­ing current can cause failure of system elements such as the motor shaft, belt­ing, gear box, drive train and damage to fragile product.
Effective: February 2005
Solid-State Soft Start Motor Controller and Starter
Current
600
Figure 5. Motor Current vs. Speed
This graph shows the impact of using a soft start. For this motor, the initial current when it is started is 600 per­cent, or six times the motor’s full load current rating. The soft starter can be set to reduce this current, for example in this case to 300 percent. This limits the inrush current on the utility line.
Tor qu e
300
200
100
Figure 6. Motor Torque vs. Speed
As a result of the reduction in current, the motor’s ability to generate torque is also reduced. The upper curve shows the same motor started across the line. The initial torque is about 180 percent with a peak torque of over 300 percent. With the soft start limiting the current, the torque speed curve is reduced, reducing mechanical stress.
The torque available from the motor at reduced current is equal to the locked rotor or starting torque, times the square of the reduced current divided by the locked rotor current. Thus if we reduce the current from 600 percent to 300 percent, the torque varies as the square of this reduction. The torque is thus reduced to 25 percent of the across the line starting torque.
How Does Torque Vary?
Where:
T T I
1
I
2
V V
Full Voltage Starter
%
Solid-State Starter
0
Speed RPM
%
Full Voltage
%
%
0
T2T
= Torque at recued current/voltage
2
= torque at locked rotor current
1
= Locked rotor current
Starter
Solid-State Starter
Speed RPM
2
I
2

T
=
----
1

I
1
V
2

------
1

V
1
2
= Reduced current = Full voltage
1
= Reduced voltage
2
100
100
%
%
Some soft starters control voltage instead of current. The torque avail­able varies proportionately with the square of the ratio of the reduced voltage to the normal line voltage.
When the operator depresses the START button, the soft starter logic issues an ON command to the power module, causing the SCRs to turn on and gently increase the voltage across the motor terminals, or the current into the motor based on the adjust­ments made to the soft start logic. When the SCRs are fully on, the motor reaches full voltage.
A block diagram of a typical soft start starter would look like
L1
3-Phase
Power
Supply
Control
Power
Stop
L2
L3
Reset
Start
Figure 7 .
Control Logic
• Current limit
• Running overload protection
• Phase loss protection
• Undervoltage protection
• Energy saver control
Motor
Figure 7. Typical Block Diagram
This solid-state starter utilizes six full current rated SCRs as its power devices. The logic circuit monitors three-phase input voltage, three-phase output voltage, and the three output currents. From these inputs it can pro­vide starting current limitation, run­ning overcurrent protection, phase loss and undervoltage protection.
This starter interfaces with standard control circuits.
In some products a bypass contactor may be closed to provide higher oper­ating efficiency after the SCRs are fully
Figure 8 is a single-phase leg of the
on. soft starter with the SCRs turning on and becoming the current path for power to flow from the utility to the motor.
A
Motor
Figure 8. SCRs as Current Path
For more information visit: www.EatonElectrical.com
AP03902001E
Solid-State Soft Start Motor Controller and Starter
Application Note
Effective: February 2005 Page 5
After the motor has come up to speed, the bypass contactor closes and it becomes the current path for the motor.
A
Motor
Figure 9. Bypass Contactor as Path
At this time the SCRs no longer con­duct any current.
Bypass operation eliminates the SCR losses once the motor is up to speed, resulting in significantly lower heat generation. Soft starters with internal run bypass mode are typically much smaller and lighter than devices with­out run bypass.
Soft Start Applications
We would like to identify problems that can be solved by the use of a soft starter. One challenge is that it can be difficult for the user to recognize a problem as a problem. Frequently the problem is mistaken for a normal operational or maintenance issue.
It is the intent of this section to help to determine solutions, using soft starters for both new and retrofit installations.
Typical problems can be categorized as mechanical, motor, starting equip­ment, inrush current, or fragile product related.
Typical mechanical problems are: stretching, squealing or breaking of drive belts; breakage of gear boxes; cou­plings wearing out prematurely; shaft breakage within the drive train; and, water hammer in hydraulic systems.
To get an idea of the effect of starting torque on the mechanical system, lets consider an automobile. If you were to put the transmission in neutral and quickly press the accelerator to the floor, you would feel the car reacting to the sudden increase in motor torque as it rotates slightly in response to the torque being developed by the engine. This same type of effect is what causes these mechanical problems, except that the torque levels may be consider­ably greater than those experienced with an automobile.
Motor problems include: motor insula­tion deterioration or premature wind­ing failure due to the mechanical stresses put on the winding during starting, or the high temperatures imposed by high starting currents; mechanical stresses on the system such as foundation bolts or mounting failures, bearing lock-up and failure, and motor shaft cracking and break­age; coupling failures; and, excessive energy losses due to duty cycle or fre­quent start/stop operation.
Benefits of Using Soft Start Starters:
Controlled starting – Limited start-
ing current, reduction of power line disturbance on starting, lower power demand on starting.
Controlled acceleration – Soft start,
adjustable acceleration based on time or load, reduced motor size for pure inertial load acceleration.
Adjustable torque limiting – Protects
machinery from damage, protects process or product.
Controlled stopping – Soft slow
down, timed stopping, fast reversal with much less stress on AC motor than plug reverse.
Typical Fixed Speed Applications:
Conveyors, belts, chains, screws,
bulk material, packaged material
Fans, blowers, compressors, pumps
Machine tools, grinders, lathes,
stamping presses
Custom machinery, labelers, pack-
aging machines, bottle washers, wire drawing, textiles, etc.
Extruders
Process machinery, kilns, grinders,
blenders, agitators. See the section on load types for particular evalua­tion of specific loads.
Other Reduced Voltage Starting Methods
There are several reduced voltage starting methods that predate solid­state soft start motor controllers and starters. Table 1 illustrates these meth- ods and their typical applications.
AP03902001E For more information visit: www.EatonElectrical.com
Application Note
Page 6 Effective: February 2005
Solid-State Soft Start Motor Controller and Starter
Table 1. Comparison of Electromechanical Soft Starters
Type of Starter
Autotrans­former8065
Primary Resistor
Part Winding
Wye Delta 100 33 33 Open
Starting Characteristics in Percent of Full
Transition Extra
Voltage Values
% Line Voltage at Motor
50
% Motor Locked Rotor Amps
64 42 25
% of Motor Locked Rotor Torque
64 42 25
Closed No
65 65 42 Closed Yes
100 65 48 Closed Yes (but very
(Closed available for about 30% price adder)
Acceleration Steps Available
uncommon)
No
Advantages Disadvantages Applications
Provides highest
torque per ampere of line current
3 different starting
torques available through
In lower horsepower
ratings is most expensive design
Low power factor
Large physical size
Blowers Pumps Compressors Conveyors
autotransformer taps
Suitable for relatively
long starting periods
Motor current is
greater than line current during starting
Smooth acceleration –
motor voltage increases with speed
High power factor
during start
Less expensive than
autotransformer starter in lower horsepower ratings
Available with as
Low torque efficiency
Resistors give off heat
Starting time in excess
of 5 seconds requires expensive resistors
Difficult to change
starting torques under varying conditions
Belt and gear drives Conveyors Textile machines
many as 5 accelerating points
Least expensive
reduced voltage starter
Most dual voltage
motors can be started part winding on lower voltage
Small physical size
Unsuited for high
inertia, long starting time loads
Requires special motor
design for voltage higher than 230 volts
Motor will not start if
the torque demanded
Reciprocating compressors Pumps Blowers Fans
by the load exceeds that developed by the motor when the first half of the motor is energized
First step of
acceleration must not exceed 5 seconds or else motor will overheat
Suitable for high
inertia, long acceleration loads
High torque efficiency
Ideal for especially
stringent inrush restrictions
Ideal for frequent
Requires special motor
Low starting torque
During open transition
there is a high momentary inrush when the delta contactor is closed
Centrifugal compressors Centrifuges
starts
For more information visit: www.EatonElectrical.com AP03902001E
Solid-State Soft Start Motor Controller and Starter
Application Note
Effective: February 2005 Page 7
Basic Mechanics
Introduction
In order to apply a soft start properly, certain mechanical parameters must be taken into consideration. This sec­tion explains what these parameters are and how to calculate or measure them.
Torque
Torque is the action of a force produc­ing or tending to produce rotation. Unlike work (which only occurs during movement) torque may exist even though no movement or rotation occurs.
Torque consists of a force (Lb.) acting upon a length of a lever arm (Ft.). The product of these two factors produces the term lb-ft, which is the unit of mea­surement for torque (see Figure 10). Mathematically, it is expressed as:
Torque (lb-ft) = Force (Lbs.) x Distance (Ft.)
Example:
Torque = Force x Distance Torque = 50 Lbs. x 1 Ft. Torque = 50 lb-ft
Because most power transmission is based upon rotating elements, torque is important as a measurement of the effort required to produce work.
Force
Lever Arm – 1 Ft.
Figure 10. Calculating Torque
Calculating Torque
Acceleration Torque Required for Rotating Motion
Some machines must be accelerated to a given speed in a certain period of time. The torque rating of the motor may have to be increased to accom­plish this objective. The following equation may be used to calculate the average torque required to accelerate a known inertia (WK must be added to all the other torque requirements of the machine when determining the motor’s required peak torque output.
2
). This torque
50 Lbs.
2
WK
xdN
-------------------------
T
=
308t
Where:
T = Acceleration Torque (lb-ft)
2
= Total system inertia (lb-ft2) that
WK the motor must accelerate. This value includes motor rotor, speed reducer and load.
dN = Change in speed required (rpm)
t = Time to accelerate total system load (seconds)
Note: The number substituted for (WK2) in this equation must be in units of lb-ft
The same formula can also be rear­ranged to determine the minimum acceleration time of a given system, or if a motor can accomplish the desired change in speed within the required time period.
Rearranged Equation:
2
xdN
WK
-------------------------=
t
308T
2
.
Calculating Horsepower
Note: The following equations for calculat­ing horsepower are to be used for estimat­ing purposes only. These equations do not include any allowance for machine friction, windage or other factors. These factors must be considered when selecting a motor for an application. Once the machine torque is determined, the required horsepower is calculated using the formula:
TxN
hp
-------------= 5250
Where:
hp = Horsepower
T = Torque (lb-ft)
N = Speed of motor at rated load (rpm)
If the calculated horsepower falls between standard available motor ratings, select the higher available horsepower rating. It is good practice to allow some margin when selecting the motor horsepower. Also note that the motor’s torque output is reduced during a soft start. The load require­ments must be related to the soft starter settings.
For many applications, it is possible to calculate the horsepower required without actually measuring the torque. The following equations will be helpful:
Conveyors
hp = (Vertical)
hp = (Horizontal
Where:
F/W = force/weight in Lbs. V = Velocity in feet per minute Coef. = Coefficient of friction
F / W (lbs) x V (fpm)
33,000 x Efficiency
F / W (lbs) x V (fpm) x Coef
)
33,000 x Efficiency
Fans and Blowers
hp =
cfm x Pressure (psi)
33,000 x Efficiency of Fan
hp =
cfm x Pressure (lb-ft
2
)
229 x Efficiency of Fan
cfm x (Inches of Water Gauge)
hp =
6356 x (Efficiency of Fan)
Pumps
gpm x Head (ft.) x (Specific Gravity)
hp =
Where:
psi = pounds per square inch cfm = cubic feet per minute gpm = gallons per minute Specific gravity of water = 1.0 1 cubic foot per second = 448 gpm 1 psi = a head of 2.309 ft. for water
weighing 62.36 lbs. per cu. ft. at 62°F.
Efficiency of fan or pump = %/100
Displacement pump efficiency: Displacement pumps vary between 85 and 90% efficiency depending on size of pumps.
Centrifugal pump efficiency (at design point):
500 to 1000 gal. per min. = 70 to 75% 1000 to 1500 gal. per min. = 75 to 80% Larger than 1500 gal. per min. =
80 to 85%
3960 x (Efficiency of Pump)
AP03902001E For more information visit: www.EatonElectrical.com
Application Note
Page 8 Effective: February 2005
Solid-State Soft Start Motor Controller and Starter
Inertia
Inertia is a measure of a body’s resis­tance to changes in velocity, whether the body is at rest or moving at a con­stant velocity. The velocity can be either linear or rotational.
2
The moment of Inertia (WK
) is the product of the weight (W) of an object and the square of the radius of gyra-
2
tion (K
). The radius of gyration is a measure of how the mass of the object is distributed about the axis or rota­tion. Because of the distribution of mass, a small diameter cylindrical part has a much lower inertia than a large diameter part.
The inertia calculations for typical shapes follow.
WK2 or WR
2
WR2 refers to the inertia of a rotating member that was calculated by assuming the weight of the object was concentrated around its rim at a distance R (radius) from the center.
2
refers to the inertia of a rotating
WK member that was calculated by assuming the weight of the object was concentrated at some smaller radius, K (termed the radius of gyration). To determine the WK
2
of a part, the
weight is normally required.
Calculations
When performing calculations, be con­sistent with the formulae and units used. Common mistakes are substitut­ing inches for feet, etc.
Cylinders
D
L
Figure 11. Solid Cylinder
Equations:
2
WK
= .000681 x p x L x (D)
4
D1D
2
L
Figure 12. Hollow Cylinder
Equations:
2
WK
= .000681 x p x L (D
4
- D1 4)
2
Where:
2
= inertia of a cylinder (lb-ft2)
WK p = density of cylinder material in lb-in (see density chart below)
= inside diameter of cylinder
D
1
(inches)
= outside diameter of cylinder
D
2
(inches) L = Length of cylinder (inches)
Table 2. Common Material Densities (p)
Aluminum Brass Cast Iron Steel Rubber Paper
0.0977
0.3110
0.2816
0.2816
0.0341
0.0250 to 0.0420
Pulley/Gear
To calculate the inertia of a pulley or gear, divide up the piece (shown in Figure 13) as shown in Figure 14. Using the same equation for calculat­ing hollow cylinders, perform the cal­culations of each separate part and add them together for a total inertia.
End View
2
and WK
1
Note: WK
inertia calculations.
Figure 13. Complete Pulley/Gear
2
are the separate
2
3"
2.5"
Side View
3" 2"
1.375"
Motor
Shaft
In this example the pulley is made of steel. We will divide it up to calculate as shown.
3"
2.5"
3"
Figure 14. Pulley/Gear Components
3
WK
2
1
Equations:
2
= .000681 x p x L (D
WK
4
2
Calculations:
2
= .000681 x 0.2816 x 3 x
WK
1
4
– 2.54)
(3
= .0241 lb-ft
2
WK
= .000681 x 0.2816 x 2 x
2
(2.5
= .0136 lb-ft
Total Inertia = WK
2
4
– 1.3754)
2
2
+ WK
1
.0136
= .0377 lb-ft
2
WK2 Reflected to the Motor Shaft
In most mechanical systems not all the moving parts operate at the same speed. If speeds of the various parts have a continuous fixed relationship to the motor speed, the equation can be used to convert all of the various inertia values to an equivalent WK applied to the motor shaft.
WK2 of Rotating Parts
2
WK
---------------­DR()
2
N
--------­N
Equivalent WK2 = WK2
Where:
2
= inertia of the moving part
WK N = speed of the moving part (rpm)
= speed of the driving motor (rpm)
N
M
When using speed reducers, and the machine inertia is reflected back to the motor shaft, the equivalent inertia is equal to the machine inertia divided by the square of the drive reduction ratio.
2
Equivalent WK
=
2"
1.375"
2
WK
2
- D1 4)
2
= .0241 +
2
2
M
2
For more information visit: www.EatonElectrical.com AP03902001E
Solid-State Soft Start Motor Controller and Starter
Application Note
Effective: February 2005 Page 9
Where:
DR = drive reduction ratio =
Input
1 hp
3 lb-ft
1750 RPM
Reducer
N
---------
Output
(Less Efficiency)
76.5 lb-ft
57.5 Rpm
Gear
(30:1)
M
N
1 hp
Figure 15. Gear Reducer Characteristics
WK2 of Linear Motion
Not all driven systems involve rotating motion. The equivalent WK
2
of linearly moving parts can also be reduced to the motor shaft speed as follows:
2
WV()
2
=
Equivalent WK
-----------------------------
39.5 NM()
2
Where:
W = weight of load (Lbs.) V = linear velocity of rack and load or
conveyor and load (fpm) = speed of the driving motor (rpm)
N
M
This equation can only be used where the linear speed bears a continuous fixed relationship to the motor speed, such as a conveyor.
Speed Reducer Selection
The motor should always be coupled to the driven machine by a power transmission that will permit maxi­mum motor rpm at maximum machine speed. The power transmis­sion may be a simple belt-sheave or sprocket-chain arrangement or a compact gear reducer. In most applica­tions requiring speed reductions greater than 5:1, the gear reducer may be the most economical choice.
Gear Reducer Selection
A gear reducer transmits power by an arrangement of various forms of gears. It provides an efficient, positive method to change speed, direction, and torque. This may mean a change of speed with a corresponding change in torque, or a change in output direc­tion or position. A common result is a combination of the above.
The gear reducer serves as a torque amplifier, increasing the torque by a factor proportional to the reducer ratio, less an efficiency factor. See Figure 13.
A 1 hp, 1750 rpm motor has an output torque of 3 lb-ft. If a 30:1 ratio reducer with 85% efficiency is used, the reducer output torque will be 3x30x0.85 = 76.5 lb-ft.
A typical application involves selecting a gear reducer that permits the drive motor to operate at nameplate speed when the driven machine is at maxi­mum speed. The gear reducer should also provide adequate torque to drive the machine.
Application Example
A 1750 rpm motor is selected for a machine which is to operate at 57.5 rpm maximum speed and requires 70 lb-ft of torque.
To find the answer, the following two steps must be accomplished.
1. Determine the required ratio:
Reducer = Ratio
Maximum Motor rpm
Maximum Driven
Machine rpm
1750
Reducer Ratio = = 30.4 or a 30:1
Note: When the calculated reducer ratio is not close to a standard speed reducer ratio, a chain, belt or additional gears with further reduction are necessary (located on the input or output side).
-------------
57.5
ratio
2. Determine the motor torque & horsepower
A 30:1 gear reducer is selected which is capable of supplying 70 lb-ft of out­put torque. Since the machine torque requirement is known, this value is divided by the reduction ratio and an efficiency factor, to arrive at the required motor torque (TM).
TM =
Required torque (lb-ft)
Reducer Ratio x
Efficiency Factory
70
------------------------
TM = = 2.75 lb-ft
30 0.85×
Since a 1 hp, 1750 rpm motor delivers 3 lb-ft of torque, it is chosen for this application along with a 30:1 gear reducer with a minimum of 70 lb-ft output torque.
Where the reduction ratio permits the use of a chain or belt, the same formu­lae are used as with the reducers.
Gear Reducer — Overhung Load
An overhung load (OHL) is defined as dead weight the gear reducer bearings can support on an output shaft at a distance equal to the shaft diameter. This distance is measured from the outside end of the bearing housing along the shaft (see Figure 16). If the acting load is at a point different from the OHL point, it must be converted to the reference point and compared to the manufacturer’s catalog value.
Overhung Load
Reference Points
Side
Thrust
Side
Thrust
Output
Side
Gear
Reducer
Figure 16. Overhung Load
When a gear reducer is driven by a belt, chain or gear drive, or when the gear reducer drives a driven unit through a belt, chain or gear drive, an overhung load (side thrust) is produced. The overhung load must not exceed the rating of the gear reducer as listed by the manufacturer. The magnitude of the overhung load should always be kept to a minimum. Excessive loads could lead to fatigue failure of either the bearing or shaft. The sprocket or pulley should always be located as close to the gear housing as possible.
Increasing the sprocket or pulley diam­eter results in a reduced overhung load. Use the following equation to determine the overhung load:
=2 x Shaft Torque (lb-in) x K
OHL
(lb. )
Diameter (in)
Where:
Diameter is of the sprocket, sheave, pulley or gear.
Note: K is a constant which is:
1.00 for chain drives
1.25 for gears or gear-belt drives
1.50 for V belt drives
2.50 for flat belt drives
Input
Side
AP03902001E For more information visit: www.EatonElectrical.com
Loading...
+ 20 hidden pages