Cutler Hammer, Div of Eaton Corp RMS 610, RMS 910 Catalog Page

45-10
Circuit Breakers & Supplementary Protectors 15 – 2500 Amperes for UL, CSA & IEC Applications
August 2006
Frame Sizes JG through LG
45
Multi-Function Electronic Trip Units for All Applications
Digitrip RMS Trip Units
True rms Sensing
Digitrip RMS Trip Units utilize our patented microprocessor-based intelli­gence to provide true rms sensing, permitting increased accuracy and reliable system protection. True rms sensing is not susceptible to nuisance tripping when waveforms containing high harmonic currents are present.
Digitrip RMS 310
Digitrip RMS 310 Electronic Trip Units are available with Cutler-Hammer Circuit Breakers J- and L-Frames 20 through 600 amperes.
Digitrip RMS 310+
Digitrip RMS 310+ Electronic Trip Units are available with Cutler-Hammer Circuit Breakers JG and LG. They are selectable long time delay (t pickup settings (I required. The Digitrip 310+ offers true rms sensing, is front adjustable and has an optional local display of current and cause of trip.
). A rating plug is not
r
LD
) and
RCurve Shaping
When selectively coordinated systems are called for, Digitrip RMS 310 will provide a cost-effective solution for a variety of applications.
The standard Digitrip RMS 310 includes an adjustable short time pickup setting encompassing an I ramp function which provides the basic LS curve shaping function. JG- and LG-Frames have an adjustable long time delay.
JG- and LG-Frames have selectable long time delay (t tings (I
The optional Digitrip RMS 310 provides additional flat response short time delay adjustments on an instantaneous setting to provide LSI curve shaping capability.
Digitrip RMS 310 Trip Units are available with ground fault pickup and flat response ground fault delay which provides the trip unit with full function LSG and LSIG curve shaping flexibility.
Note: Contact factory for availability of ground fault for LG-Frame trip unit.
Digitrip RMS 310 Trip Units can effec­tively coordinate with both sophisti­cated upstream power breakers as well as downstream thermal magnetic breakers…making Digitrip RMS 310 Trip Units the cost-effective reliable choice for selectively coordinated systems.
). A rating plug is not required.
r
) and pickup set-
LD
2
t
Thermal Memory
All Digitrip RMS Trip Units incorporate a long delay. Thermal memory prevents the system from cumulative overheating due to repeated overcurrent events that may occur in quick succession.
Field Testing
A field test kit is available for Digitrip RMS 310 trip units.
Digitrip RMS 610 and 910
RMS 610
Digitrip RMS 610 and 910 Trip Units are available with Cutler-Hammer R-Frame Circuit Breakers 800 through 2500 amperes. Digitrip 610 and 910 Trip Units provide unparalleled system protection with the added convenience of a local display.
Curve Shaping
Digitrip RMS 610 and 910 Trip Units are available with up to nine curve shaping choices achieved by adjusting up to seven switches on the front of the unit for optimum system coordination. Maximum curve shaping flexibility is provided by dependent long and short delay adjustments that are long delay pickup (I depicted on the front of the unit by the blue portion of the time-current curve.
Additional coordination capability can be provided by utilizing the short delay and ground fault zone selective interlocking features available on these trip units.
RMS 910
) based,
r
For more information visit: www.EatonElectrical.com CA08102001E
Circuit Breakers & Supplementary Protectors 15 – 2500 Amperes for UL, CSA & IEC Applications
August 2006
Digitrip RMS Electronic Trip Unit Selection Guide
Table 45-5. Digitrip RMS Electronic Trip Unit Selection Guide
Digitrip RMS 310
Breaker Type
Cutler-Hammer Frame(s) JG-, LG-Frames Ampere Rating 20 – 2500 A Interrupting Rating at 415 V 35, 70, 100 kA
Trip Unit Sensing
rms Sensing Yes
Protection and Coordination
Protection Ordering Options LS, LSG LSI, LSIG
Fixed Rating Plug (I Overtemperature Trip Yes Yes
Long Delay Adjustable Rating Plug (l
Long Delay Setting 0.5 – 1.0 (l Long Delay Time I2t at 6x 10 Seconds Long Delay Thermal Memory Yes Yes High Load Alarm No No
Short Delay Short Delay Setting Var/Frame
Short Delay Time I2t 100 ms No Short Delay Time Flat No I – 300 ms Short Delay Time ZSI No No
Instantaneous Instantaneous Setting No 200 – 800% x (l
Discriminator No No Instantaneous Override Yes Yes
Ground Fault
Ground Fault Setting Var/Frame Ground Fault Delay I2t at .62x No No Ground Fault Delay Flat I – 500 ms Ground Fault ZSI No No Ground Fault Thermal Memory No No
System Diagnostics
Cause of Trip LEDs No No Magnitude of Trip Information No No Remote Signal Contacts No No
System Monitoring
Digital Display No No Current No No Voltage No No Power and Energy No No Power Quality — Harmonics No No Power Factor No No
System Communications
PowerNet No No
Field Testing
Testing Method Test Set Test Set
JG- and LG-Frames have selectable settings instead of a rating plug.
JG-, LG- and NG-Frames have adjustable long delay times of 2 – 24 seconds.
JG/LG: 2X – 14X (In); NG: 2X – 8X (In); RG: 2X – 8X (I 200 – 600% x (I
); 2500 ampere RG-Frame
n
).
n
)
n
)
n
Frame Sizes JG through LG
JG
LG/NG
RG
Ye s Ye s
Ye s Ye s
JG-Frame also has a 14X setting.
Not to exceed 1200 amperes.
JG- and LG-Frames are Instantaneous, 120 ms. NG- and RG-Frames are Instantaneous, 100, 300 and 500 ms.
Note: In= Rating plug rating.
)
n
= Long delay setting.
I
r
0.5 – 1.0 (ln) 10 Seconds
Var/Frame
Var/Frame
I – 500 ms
45-11
)
n
45
CA08102001E For more information visit: www.EatonElectrical.com