Cutler Hammer, Div of Eaton Corp PSS10E Installation Guide

Instructional Leafl et IL00912009E
Effective December 2009
Instructions for installing 10 and 25 watt, 24 Vdc power
WARNING!
HAZARD OF BURN OR ELECTRICAL SHOCK. TO AVOID SHOCK HAZARD, DISCONNECT ALL POWER BEFORE ANY FUNCTIONS ARE PERFORMED ON THIS EQUIPMENT.
+ + – –
Load
AVERTISSEMENT!
RISQUE DE BRULURE OU DE CHOC ELECTRIQUE. POUR EVITER TOUT CHOC ELECTRIQUE, COUPLER L’ALIMENTATION DE CET EQUIPEMENT AVANT D’Y EFFECTUER DES TRAVAUX.
Installation
The PSS10X and PSS25X Power Supplies can be DIN rail or panel mounted. The unit is designed to reach a crow-bar current and safely shut itself down when a sec­ondary side short circuit is encountered. The unit will recover automatically when the short circuit is removed.
ote: N When wiring the system, ensure all power is removed before beginning the installation.
L1
L2
Primary
Figure 1.
Input wiring requirements
The PSS10E and PSS25E are single-phase input units. They have a wide ranging input from 100–240 Vac. Both can be wired with the (L1) terminal to line volt­age. The (L2) line should be wired to Neutral and the center terminal wired to the Ground. See Figure 1.
The PSS10F and PSS25F are 380–480 Vac single-phase input power supplies. The units should be wired to the line voltage. The top terminals are wired to the Ground. See Figure 2.
CPT
100 Vac
or 240 Vac
Output
Instructional Leafl et IL00912009E
Effective December 2009
Breaker
Starter
+
+ – –
380–480 Vac
L1
L2
Load
Figure 2.
Output wiring requirements
All units have two output connections (two +, two –) for ease of wiring. The two outputs are tied together and are not elec­trically isolated.
The power supplies are not designed to operate in parallel and no provisions have been made for load sharing.
Table 1.
Output Specifications
Catalog Number
PSS10E PSS10F PSS25E PSS25F
Output voltage nominal 24 Vdc 24 Vdc 24 Vdc 24 Vdc
Voltage regulation ±10% ±10% ±10% ±10%
Steady-state wattage 10W 10W 25W 25W
Outrush wattage (nominal) 20W 20W 165W 165W
Outrush holdup time (msecs)
Eaton Corporation
Electrical Sector 1111 Superior Ave. Cleveland, OH 44114 United States 877-ETN-CARE (877-386-2273) Eaton.com
© 2009 Eaton Corporation All Rights Reserved Printed in China Publication No. IL00912009E / Z9047 December 2009
PowerChain Management is a registered trademark of Eaton Corporation.
All other trademarks are property of their respective owners.
Loading...