Cutler Hammer, Div of Eaton Corp PSG480E Technical Data

Input (AC)
Output (DC)
Certification and Standards
Safety and Protection
surge
max
TECHNICAL DATA FOR PSG480E
Mains buffering at nominal load (typ.) > 20 ms @ 115 VAC & 230 VAC Turn-on time < 1 sec. Internal fuse F 10 AH / 250 V Recommended backup fuse 10 A or 16 A Power circuit-breaker characteristic B Leakage current < 1 mA
Nominal output voltage UN / tolerance 24 VDC ± 2 % Adjustment range of the voltage 22-28 VDC Nominal current 20 A Derating above +50 °C 2.5 % / K. Startup with capacitive loads Max. 10,000 µF Max. power dissipation idling / nominal load approx. 72 W Efficiency (at 400V AC and nominal values) > 86 % typical Residual ripple/ peak switching (20 MHz) (at nominal values) < 50 mV / < 240 mVpp Parallel operation With oring diode
General Data
Type of housing Aluminium (Al5052) Signals Green LED DC OK MTBF > 300,000 hrs. Dimensions (L x W x H) 121 mm x 160 mm x 115 mm Weight 1.8 kg Connection method Screw connection Stripping length 7 mm or use suitable lug to crimp Operating temperature -20 °C to +75 °C (> 50°C derating) Storage temperature -25 °C to +85 °C Humidity at +25 °C, no condensation < 95 % RH Vibration (operating)
Pollution degree 2 Climatic class 3K3 according to EN 60721
IL00912004E
No damage &
10 to 150 Hz, 0.35 mm acc. 50 m / s², single amplitude (5 G max.) for 90 min. in each X, Y & Z directions, in acc. with IEC 68-2-6
I2t
rating of all l/P devices shall not exceed their rating
Electrical equipments of machines IEC60204-1 (over voltage category III) Electronic equipment for use in electrical power installations EN50178 / IEC62103 Safety entry low voltage PELV (EN60204), SELV (EN60950) Electrical safety (of information technology equipment) EN60950-1 (GS-mark),
Industrial control equipment UL / C-UL listed to UL508 and CSA C22.2 No. 107.1-01
Protection against electric shock DIN57100-410 CE In conformance with EMC directive 2004/108/EC and low voltage
ITE EN55022,EN61000-3-2,EN61000-3-3, EN55024 Industrial EN55011 Limitation of mains harmonic currents EN61000-3-2
RoHS Compliant Yes
Transient surge voltage protection VARISTOR Current limitation at short-circuits approx. I Surge voltage protection against internal surge voltages Yes Isolation voltage: Input / output (type test/routine test) Input / PE (type test/routine test) Output / PE (type test/routine test) Protection degree IPX0 Safety class Class I with PE connection Shock (in all directions) 30 G (300 m/s²) in all directions according to IEC 68-2-27
UL/C-UL recognized to UL60950-1, CSA C22.2 No. 60950-1, CB scheme to IEC60950-1, cCSAus to UL60950-1 and CSA C22.2 No. 60950-1 (file no.181564)
CSA to CSA C22.2 No.107.1-01 (file no.181564)
directive 2006/95/EC.
= 150 % of Po
4 kVAC / 3 kVAC
1.5 kVAC / 1.5 kVAC
1.5 kVAC / 500 VAC
typically