Cutler Hammer, Div of Eaton Corp PSG120E Technical Data

Input (AC
)
Output (DC)
Certification and Standards
Safety and Protection
surge
m
ax
TECHNICAL DATA FOR PSG120E
Nominal input voltage 100-240 VAC Voltage range 85-264 VAC (DC input range 120-375 VDC) Frequency 47-63 Hz (0 Hz @ DC input) Nominal current 1.4 A @ 115 VAC, 0.8 A @ 230 VAC Inrush current limitation. I2t (+25 °C) typ. < 80 A @ 115 VAC Mains buffering at nominal load (typ.) > 35 ms @ 115 VAC, > 70 ms @ 230 VAC Turn-on time < 1 sec. Internal fuse T 3.15 AH / 250 V Recommended backup fuse 6 A, 10 A or 16 A Power circuit-breaker characteristic B Leakage current < 1 mA
Nominal output voltage UN / tolerance 24 VDC ± 2 % Adjustment range of the voltage 22-28 VDC Nominal current 5 A Derating above +50 °C 2.5 % / K. Startup with capacitive loads Max. 10,000 µF Max. power dissipation idling / nominal load approx. 22.5 W Efficiency (at 400V AC and nominal values) > 84 % typical Residual ripple/ peak switching (20 MHz) (at nominal values) < 50 mV / < 240 mVpp Parallel operation With oring diode
General Data
Type of housing Aluminium (Al5052) Signals Green LED DC OK MTBF > 800,000 hrs. Dimensions (L x W x H)
Weight 0.54 kg Connection method Screw connection Stripping length 7 mm or use suitable lug to crimp Operating temperature -20 °C to +75°C (> 50°C derating) Storage temperature -25 °C to +85 °C Humidity at +25 °C, no condensation < 95 % RH Vibration (operating)
Pollution degree 2 Climatic class 3K3 according to EN 60721
IL00912002E
121 mm x 50 mm x 118. 2 mm
10 to 150 Hz, 0.35 mm acc. 50 m / s², single amplitude (5 G max.) for 90 min. in each X, Y & Z directions, in acc. with IEC 68-2-6
Electrical equipments of machines IEC60204-1 (over voltage category III) Electronic equipment for use in electrical power installations EN 50178 / IEC62103 Safety entry low voltage PELV (EN 60204), SELV (EN 60950) Electrical safety (of information technology equipment) EN60950-1 (GS-mark),
Industrial control equipment UL / C-UL listed to UL508 and CSA C22.2 No.107.1-01
Protection against electric shock DIN 57100-410 CE In conformance with EMC directive 2004/108/EC and low
ITE EN55022, EN61000-3-2, EN61000-3-3, EN55024 Industrial EN55011 Limitation of mains harmonic currents EN61000-3-2
RoHS Compliant Yes
Transient surge voltage protection VARISTOR Current limitation at short-circuits approx. I Surge voltage protection against internal surge voltages Yes Isolation voltage: Input / output (type test/routine test) Input / PE (type test/routine test) Output / PE (type test/routine test) Protection degree IPX0 Safety class Class I with PE connection Shock (in all directions) 30 G (300 m/s²) in all directions according to IEC 68-2-27
UL/C-UL recognized to UL60950-1, CSA C22.2 No.60950-1, CB scheme to IEC60950-1, cCSAus to UL60950-1 and CSA C22.2 No.60950-1 (file no.181564)
CSA to CSA C22.2 No.107.1-01 (file no.181564)
voltage directive 2006/95/EC
= 150 % of Po
4 kVAC / 3 kVAC
1.5 kVAC / 1.5 kVAC
1.5 kVAC / 500 VAC
typically
Loading...