Cutler Hammer, Div of Eaton Corp PowerXL Series VFD Communications Guide

PowerXL Series VFD
Communication manual
Effective June 2018 Supersedes October 2017
PowerXL Series VFD
SAFETY
Before commencing the installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . xiii
Definitions and symbols . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . xiv
Warnings and cautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . xiv
Motor and equipment safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . xvii
POWERXL SERIES OVERVIEW
How to use this manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
Receiving and inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
Real time clock battery activation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
Rating label . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
General information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
OPTION CARD SLOTS
Option Card Slots . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
Installing PowerXL Series option board . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
Control wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
EMC directive . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
Control cable grounding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
MODBUS RTU ON-BOARD COMMUNICATIONS
Modbus RTU specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
Commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
Modbus communication standards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
MODBUS TCP ON-BOARD COMMUNICATIONS
Modbus/TCP specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16
Hardware specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16
Commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .18
Modbus communication standards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25
ETHERNET/IP ON-BOARD COMMUNICATIONS
EtherNet/IP specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .31
Hardware specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .32
EtherNet/IP overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .34
Commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .36
PLC programming . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .39
BACNET MS/TP—ON-BOARD COMMUNICATION
BACnet MS/TP connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .68
Commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .71
BACnet overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .73
iv
POWERXL SERIES VFD MN040010EN—June 2018 www.eaton.com
Contents, continued
PROFIBUS-DP EXTERNAL COMMUNICATION CARDS
PROFIBUS-DP external communication cards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .80
PROFIBUS specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .81
Hardware specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .81
PROFIBUS cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .82
Commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .83
PROFIBUS—PowerXL Series . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .85
PROFIBUS overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .88
CANOPEN EXTERNAL COMMUNICATION CARDS
CANopen technical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .99
CANopen cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .99
CANopen bus termination . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .100
Hardware specification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101
Commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 102
CANopen overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .104
Network management (NMT) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .106
Drive profile state machine . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .108
Device profile parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .109
Object directory . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 115
PowerXL Series VFD
DEVICENET EXTERNAL COMMUNICATION CARDS
DeviceNet technical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .121
DeviceNet board LED status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .123
Commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .124
DeviceNet Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .126
SMARTWIRE-DT EXTERNAL COMMUNICATION CARDS
SmartWire-DT external communication cards . . . . . . . . . . . . . . . . . . . . . . . . . . . . .147
SmartWire-DT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .148
Hardware specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .148
SmartWire-DT cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .150
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .152
Commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .153
SmartWire-DT parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .154
SmartWire-DT – PowerXL Series . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .157
Cyclic Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .158
SmartWire-DT diagnostics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .163
BACNET IP ON-BOARD COMMUNICATION
BACnet on-board communication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .164
Prepare for use through Ethernet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .165
BACnet parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 174
BACnet overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 174
POWERXL SERIES VFD MN040010EN—June 2018 www.eaton.com
v
PowerXL Series VFD
Contents, continued
APPENDIX A—PARAMETER ID LIST
Parameter descriptions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .178
APPENDIX B—PROCESS DATA VALUES
Process data OUT (slave master) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .222
Process data IN (master
slave) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .222
APPENDIX C—FAULT CODES
Fault codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .224
APPENDIX D—POWERXL RECOMMENDED SECURE HARDENING GUIDELINES
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .226
References . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .228
List of Figures
Figure 1. RTC battery connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
Figure 2. Rating label (DG1) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
Figure 3. Rating label (DH1) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
Figure 4. PowerXL Series control board location . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
Figure 5. Count . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
Figure 5. PowerXL Series control board location . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
Figure 6. Control cable grounding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
Figure 7. Connection diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
Figure 8. Terminal wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
Figure 9. Termination resistor and shielding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
Figure 10. DG1 keypad navigation to RS-485 menu . . . . . . . . . . . . . . . . . . . . . . . . . . .7
Figure 11. DH1 keypad navigation to RS-485 menu . . . . . . . . . . . . . . . . . . . . . . . . . . .8
Figure 12. The basic structure of a modbus frame . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
Figure 13. Module and network status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17
Figure 14. CAT-5e cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .18
Figure 15. DG1 keypad navigation to ethernet comm settings . . . . . . . . . . . . . . . . .18
Figure 16. DH1 keypad navigation to ethernet comm settings . . . . . . . . . . . . . . . . .19
Figure 17. DG1 Static IP mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .21
Figure 18. DH1 Static IP mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22
Figure 19. DG1 Static IP address . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .23
Figure 20. DH1 Static IP address . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24
Figure 21. Module and network status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .33
Figure 25. DG1 Static IP mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .37
Figure 26. Static IP address . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .38
Figure 27. State transition diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .58
Figure 28. Principal example diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .68
Figure 29. Stripping the cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .69
Figure 30. RS-485 Cable strip (Aluminum Shield) . . . . . . . . . . . . . . . . . . . . . . . . . . . .69
Figure 31. Drive terminals (BACnet) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .69
vi
POWERXL SERIES VFD MN040010EN—June 2018 www.eaton.com
List of Figures, continued
Figure 32. Serial ground . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .69
Figure 33. RS-485 Bus termination setup. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .70
Figure 34. BACnet bus termination . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .70
Figure 35. PowerXL DG1 BACnet MSTP parameter navigation . . . . . . . . . . . . . . . . .71
Figure 36. PowerXL DH1 BACnet MSTP parameter navigation . . . . . . . . . . . . . . . . .72
Figure 37. Fault tracing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .79
Figure 38. Com1 PROFIBUS card layout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .81
Figure 39. Com1 PROFIBUS DB9 adapter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .82
Figure 40. PROFIBUS parameter menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .83
Figure 41. PROFIdrive . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .88
Figure 42. Application class . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .89
Figure 43. General state diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .94
Figure 44. CANopen bus termination . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .100
Figure 45. CANopen hardware . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101
Figure 46. CANopen parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .102
Figure 47. NMT state machine . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .106
Figure 48. Internal state machine . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .108
Figure 49. Device profile . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .120
Figure 50. Trunk lines or drop lines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .122
Figure 51. DeviceNet hardware . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .122
Figure 52. Module and network status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .124
Figure 53. DeviceNet parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .125
Figure 54. Network state machine . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .135
Figure 55. SmartWire-DT “DXG-NET-SWD-IP20” module details . . . . . . . . . . . . . .148
Figure 56. SmartWire-DT “DXG-NET-SWD-IP54” module details . . . . . . . . . . . . . .148
Figure 57. 8 core flat cable and pin assignment . . . . . . . . . . . . . . . . . . . . . . . . . . . .149
Figure 58. 5 core round cable and pin assignment . . . . . . . . . . . . . . . . . . . . . . . . .149
Figure 59. External device plug SWD4-8SF2-5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . .150
Figure 60. Connection of SmartWire-DT module to PowerXL DG1 Drive . . . . . . . .151
Figure 61. Mounting of SmartWire-DT
“DXG-NET-SWD-IP20” module on PowerXL DG1 Drive . . . . . . . . . . . . . . . . . . . .152
Figure 62. Connection of flat cable with
SmartWire-DT “DXG-NET-SWD-IP20” module . . . . . . . . . . . . . . . . . . . . . . . . . . . .152
Figure 63. Mounting of SmartWire-DT
“DXG-NET-SWD-IP54” module on PowerXL DG1 Drive . . . . . . . . . . . . . . . . . . . .152
Figure 64. Connection of round cable with
SmartWire-DT “DXG-NET-SWD-IP54” module . . . . . . . . . . . . . . . . . . . . . . . . . . . .152
Figure 67. Recommended wire lengths . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .153
Figure 68. SmartWire-DT parameter menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .154
Figure 69. Principle example diagram of BACnet . . . . . . . . . . . . . . . . . . . . . . . . . . .164
Figure 70. CAT-5e cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .166
Figure 71. DH1 keypad navigation to ethernet comm settings . . . . . . . . . . . . . . . .167
Figure 72. DH1 Static IP mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .169
Figure 73. DH1 Static IP address . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .170
Figure 74. Fault tracing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .178
PowerXL Series VFD
POWERXL SERIES VFD MN040010EN—June 2018 www.eaton.com
vii
PowerXL Series VFD
List of Tables
Table 1. Common abbreviations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
Table 2. Wire sizes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
Table 3. Control wiring requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
Table 4. PowerXL Series—drive option boards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
Table 5. PowerXL Series drives protocols . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
Table 6. Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
Table 7. Communications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
Table 8. Modbus RTU . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
Table 9. Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10
Table 10. Request to read coils . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10
Table 11. Request to read discrete inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Table 12. Request to read holding registers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10
Table 13. Request to read input registers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10
Table 14. Request to read exception status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
Table 15. Read diagnostics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
Table 16. Request to write single coil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
Table 17. Request to write single register . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Table 18. Write coils 19–28 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
Table 19. Request to write holding registers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Table 20. Index table . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12
Table 21. Process data slave Table 22. Process data master
Table 23. Fieldbus basic input table . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13
Table 24. FB control word . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13
Table 25. Fieldbus basic output table . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
Table 26. FB Status Word Bit Descriptions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
Table 27. FB general status word . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
Table 28. Process data OUT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
Table 29. Process data IN . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
Table 30. Modbus/TCP technical data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16
Table 31. Ethernet LED description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16
Table 32. Module status LED description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17
Table 33. Network status LED description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17
Table 34. EtherNet/IP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19
Table 35. EtherNet/IP / Modbus TCP—P20.3, continued . . . . . . . . . . . . . . . . . . . . . .20
Table 36. Request to read coils . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25
Table 37. Request to read discrete inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25
Table 38. Request to read holding registers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25
Table 39. Request to read input registers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25
Table 40. Request to read exception status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25
Table 41. Read diagnostics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25
Table 42. Request to write single coil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .26
Table 43. Request to write single register . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .26
master (max. 22 bytes) . . . . . . . . . . . . . . . . . . . . . .12
slave (max. 22 bytes) . . . . . . . . . . . . . . . . . . . . . .12
viii
POWERXL SERIES VFD MN040010EN—June 2018 www.eaton.com
List of Tables, continued
Table 44. Write coils 19–28 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .26
Table 45. Write holding registers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .26
Table 46. Index table . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .26
Table 47. Process data slave Table 48. Process data master
Table 49. Fieldbus basic input table . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .27
Table 50. Table 55. FB control word . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .28
Table 51. Table 57. Fieldbus basic output table . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .29
Table 52. Table 59. FB status word bit descriptions . . . . . . . . . . . . . . . . . . . . . . . . . .29
Table 53. Table 60. FB general status word . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .29
Table 54. Process data OUT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .30
Table 55. Process data IN . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .30
Table 56. EtherNet/IP technical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .31
Table 57. Ethernet LED description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .32
Table 58. Module status LED description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .33
Table 59. Network status LED description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .33
Table 60. EtherNet/IP network settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .35
Table 61. List of object classes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .49
Table 62. Services supported by object classes . . . . . . . . . . . . . . . . . . . . . . . . . . . . .50
Table 63. Elementary data types . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .50
Table 64. Constructed data types . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .50
Table 65. Different types of resets supported by the identity object . . . . . . . . . . . . .50
Table 66. Identity object . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .51
Table 67. Connection manager object . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .52
Table 68. TCP/IP interface object . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .53
Table 69. Ethernet link object . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .54
Table 70. Assembly Object . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .55
Table 71. Motor data object . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .56
Table 72. Control supervisor object . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .57
Table 73. Motor data object . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .59
Table 74. Vendor specific objects . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .60
Table 75. Instance 20 (Output) length = 4 bytes . . . . . . . . . . . . . . . . . . . . . . . . . . . .61
Table 76. Instance 21 (Output) length = 4 bytes . . . . . . . . . . . . . . . . . . . . . . . . . . . .61
Table 77. Instance 23 (Output) length = 6 bytes . . . . . . . . . . . . . . . . . . . . . . . . . . . . .61
Table 78. Instance 25 (Output) length = 6 bytes . . . . . . . . . . . . . . . . . . . . . . . . . . . .61
Table 79. Instance 101 (Output) length = 8 bytes . . . . . . . . . . . . . . . . . . . . . . . . . . .62
Table 80. Instance 111 (Output) length = 20 bytes . . . . . . . . . . . . . . . . . . . . . . . . . . .63
Table 81. Instance 70 (Input) length = 4 bytes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .64
Table 82. Instance 71 (Input) length = 4 bytes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .64
Table 83. Instance 73 (Input) length = 6 bytes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .65
Table 84. Instance 75 (Input) length = 6 bytes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .65
Table 85. Instance 107 (Input) length = 8 bytes . . . . . . . . . . . . . . . . . . . . . . . . . . . . .65
Table 86. Instance 117 (input). EIP drive status length = 34 bytes. . . . . . . . . . . . . . .66
master (max. 22 bytes) . . . . . . . . . . . . . . . . . . . . . .27
slave (max. 22 bytes) . . . . . . . . . . . . . . . . . . . . . .27
PowerXL Series VFD
POWERXL SERIES VFD MN040010EN—June 2018 www.eaton.com
ix
PowerXL Series VFD
List of Tables, continued
Table 87. Instance 127 (Input). EIP drive status length = 20 bytes . . . . . . . . . . . . . . .67
Table 88. Instance 128 (Input). EIP drive status length = 20 bytes . . . . . . . . . . . . . .67
Table 89. BACnet MS/TP technical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .68
Table 90. BACnet MS/TP Parameter Table . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .72
Table 91. Supported object types and properties summary . . . . . . . . . . . . . . . . . . . .74
Table 92. Binary value object instance summary . . . . . . . . . . . . . . . . . . . . . . . . . . . .77
Table 93. Analog value object instance summary . . . . . . . . . . . . . . . . . . . . . . . . . . .78
Table 94. Analog Input object instance summary . . . . . . . . . . . . . . . . . . . . . . . . . . .78
Table 95. Multi state object instance summary . . . . . . . . . . . . . . . . . . . . . . . . . . . . .79
Table 96. Analog Input object instance summary . . . . . . . . . . . . . . . . . . . . . . . . . . .79
Table 97. PROFIBUS technical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .80
Table 98. Line length. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .80
Table 99. PROFIBUS LEDs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .81
Table 100. Connector and pin assignment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .82
Table 101. PROFIBUS cable connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .82
Table 102. Recommended cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .82
Table 103. PROFIBUS parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .86
Table 104. Binary bits and corresponding outputs . . . . . . . . . . . . . . . . . . . . . . . . . . .87
Table 105. Bypass mode process data modules . . . . . . . . . . . . . . . . . . . . . . . . . . . .87
Table 106. Fieldbus basic output table . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .87
Table 107. Application class . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .89
Table 108. PROFIdrive control word 1—STW1 message examples . . . . . . . . . . . . . .90
Table 109. Control word (STW1) message examples . . . . . . . . . . . . . . . . . . . . . . . . .92
Table 110. Application status word PROFIdrive . . . . . . . . . . . . . . . . . . . . . . . . . . . . .92
Table 111. References . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .93
Table 112. PROFIBUS option Card . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .95
Table 113. Standard telegram 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .95
Table 114. Words and Double Words . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .96
Table 115. Base mode parameter request . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .96
Table 116. Base model response . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .96
Table 117. Field coding. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .97
Table 118. CANopen connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .99
Table 119. Communications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .99
Table 120. Environment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .99
Table 121. Practical bus length . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .99
Table 122. Power LED (D1) Red LED . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101
Table 123. CANopen board status LED (D10) (Red LED) . . . . . . . . . . . . . . . . . . . . . 101
Table 124. CANopen module status—Error LED (D2-Red LED) . . . . . . . . . . . . . . . . 101
Table 125. CANopen module status—Run LED (D2-Green LED) . . . . . . . . . . . . . . . 101
Table 126. CANopen parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 103
Table 127. Message Frame . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .104
Table 128. Predefined connection set . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .105
Table 129. Start remote node message . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .107
Table 130. Stop remote node message . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 107
x
POWERXL SERIES VFD MN040010EN—June 2018 www.eaton.com
List of Tables, continued
Table 131. Enter pre-operational message . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .107
Table 132. Reset node message . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .107
Table 133. Reset communication message . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 107
Table 134. Device profile parameters index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .109
Table 135. 0x6040 control word . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 110
Table 136. 0x6041 status word . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 111
Table 137. Process data (PDO) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 112
Table 138. Fixed control word . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 113
Table 139. Fixed status word . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 114
Table 140. Object directory index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 115
Table 141. Service data (SDO) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 117
Table 142. Process data application mapping index . . . . . . . . . . . . . . . . . . . . . . . . .118
Table 143. DeviceNet connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .121
Table 144. Communications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .121
Table 145. Environment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .121
Table 146. DeviceNet power LED (D1) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .123
Table 147. DeviceNet Board status LED (D10) . . . . . . . . . . . . . . . . . . . . . . . . . . . . .123
Table 148. The MS and NS LED (D2) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .123
Table 149. Module status LED description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .124
Table 150. Network status LED description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .124
Table 151. DeviceNet parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .126
Table 152. Instance 20 (Output) length = 4 bytes . . . . . . . . . . . . . . . . . . . . . . . . . .127
Table 153. Instance 21 (Output) length = 4 bytes . . . . . . . . . . . . . . . . . . . . . . . . . .127
Table 154. Instance 23 (Output) length = 6 bytes . . . . . . . . . . . . . . . . . . . . . . . . . .127
Table 155. Instance 25 (Output) length = 6 bytes . . . . . . . . . . . . . . . . . . . . . . . . . .127
Table 156. Instance 101 (Output) length = 8 bytes . . . . . . . . . . . . . . . . . . . . . . . . . .128
Table 157. Instance 111 (Output) length = 20 bytes . . . . . . . . . . . . . . . . . . . . . . . . .129
Table 158. Instance 70 (Input) length = 4 bytes . . . . . . . . . . . . . . . . . . . . . . . . . . . .130
Table 159. Instance 71 (Input) length = 4 bytes . . . . . . . . . . . . . . . . . . . . . . . . . . . .130
Table 160. Instance 73 (Input) length = 6 bytes . . . . . . . . . . . . . . . . . . . . . . . . . . . .131
Table 161. Instance 75 (Input) length = 6 bytes . . . . . . . . . . . . . . . . . . . . . . . . . . . .131
Table 162. Instance 107 (Input) length = 8 bytes . . . . . . . . . . . . . . . . . . . . . . . . . . .132
Table 163. Instance 117 (Input). EIP drive status length = 34 bytes . . . . . . . . . . . .133
Table 164. Instance 127 (Input). EIP Drive status length = 20 bytes . . . . . . . . . . . .134
Table 165. List of object classes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .135
Table 166. List of services . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .136
Table 167. List of data types . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .136
Table 168. Reset service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .137
Table 169. Identity Object, Class 0x01 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .137
Table 170. Bit definitions for status instance attribute of identity object . . . . . . . . .138
Table 171. Values for extended device status field
(Bits 4–7) in status instance attribute . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .138
Table 172. Connection object, class 0x05 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .139
Table 173. DeviceNet object, class 0x03 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .140
PowerXL Series VFD
POWERXL SERIES VFD MN040010EN—June 2018 www.eaton.com
xi
PowerXL Series VFD
List of Tables, continued
Table 174. Assembly object, class 0x04 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .141
Table 175. Motor data object, class 0x28 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .142
Table 176. Control supervisor object, class 0x29 . . . . . . . . . . . . . . . . . . . . . . . . . . .143
Table 177. AC/DC drive object, class 0x2A . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .144
Table 178. Vendor parameters object, class 0xA0, 0xA1, 0xA2, 0xA3, ---- 0xBB . . .145
Table 179. Base device information object . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .146
Table 180. SmartWire-DT technical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .147
Table 181. Line length . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 147
Table 182. SmartWire-DT Diagnostic LED . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .148
Table 183. Recommendation for 8 core flat cable . . . . . . . . . . . . . . . . . . . . . . . . . . 150
Table 184. Recommendation for 5 core round cable . . . . . . . . . . . . . . . . . . . . . . . .150
Table 185. Firmware versions of SmartWire-DT gateways. . . . . . . . . . . . . . . . . . . .150
Table 186. Compatible field bus description files . . . . . . . . . . . . . . . . . . . . . . . . . . .150
Table 187. Recommended cable lengths . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .153
Table 188. SmartWire-DT parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .155
Table 189. Cyclic profile data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .158
Table 190. Profile 1: input bytes 0 and 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .158
Table 191. Profile 1: Output bytes 0 and 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .159
Table 192. Profile 2: Input bytes 0 to 4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .159
Table 193. Profile 2: Output bytes 0 and 4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .161
Table 194. References table for setpoint/actual speed . . . . . . . . . . . . . . . . . . . . . . .162
Table 195. Diagnostic alarms of the PowerXL DG1 variable frequency drive . . . . . .163
Table 196. BACnet/IP Protocol . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .164
Table 197. EtherNet/IP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .167
Table 198. BACnet/IP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 171
Table 199. BACnet/IP parameter descriptions . . . . . . . . . . . . . . . . . . . . . . . . . . . . .172
Table 200. Supported object types and properties summary . . . . . . . . . . . . . . . . .173
Table 201. Binary value object instance summary . . . . . . . . . . . . . . . . . . . . . . . . . . 175
Table 202. Analog value object instance summary . . . . . . . . . . . . . . . . . . . . . . . . .176
Table 203. Analog input object instance summary . . . . . . . . . . . . . . . . . . . . . . . . . .177
Table 204. Multi state object instance summary . . . . . . . . . . . . . . . . . . . . . . . . . . .177
Table 205. DG1 Parameter ID list . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .179
Table 206. DH1 Parameter ID list . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .205
Table 207. Process data OUT (slave master) . . . . . . . . . . . . . . . . . . . . . . . . . . . .222
Table 208. Process data IN (master slave) for all applications . . . . . . . . . . . . . .222
Table 209. Fault code list . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .224
Table 210. PowerXL—secure configuration guidelines . . . . . . . . . . . . . . . . . . . . . . .226
xii
POWERXL SERIES VFD MN040010EN—June 2018 www.eaton.com
Safety
WARNING! DANGEROUS ELECTRICAL VOLTAGE!
Before commencing the installation
Disconnect the power supply of the device
Ensure that devices cannot be accidentally restarted
Verify isolation from the supply
Earth and short circuit the device
Cover or enclose any adjacent live components
Only suitably qualified personnel in accordance with EN50110-1/-2 (VDE 0105 Part 100) may work on this device/system
Before installation and before touching the device ensure that you are free of electrostatic charge
The functional earth (FE, PES) must be connected to the protective earth (PE) or the potential equalization. The system installer is responsible for implementing thisconnection
Connecting cables and signal lines should be installed so that inductive or capacitive interference does not impair the automation functions
Install automation devices and related operating elements in such a way that they are well protected against unintentional operation
Suitable safety hardware and software measures should be implemented for the I/O interface so that an open circuit on the signal side does not result in undefined states in the automation devices
Ensure a reliable electrical isolation of the extra-low voltage of the 24V supply. Only use power supply units complying with IEC 60364-4-41 (VDE 0100 Part 410) or HD384.4.41 S2
Deviations of the input voltage from the rated value must not exceed the tolerance limits given in the specifications, otherwise this may cause malfunction and dangerous operation
Emergency stop devices complying with IEC/EN 60204-1 must be effective in all operating modes of the automation devices. Unlatching the emergency-stop devices must not cause a restart
Devices that are designed for mounting in housings or control cabinets must only be operated and controlled after they have been installed and with the housing closed. Desktop or portable units must only be operated and controlled in enclosed housings
Measures should be taken to ensure the proper restart of programs interrupted after a voltage DIP or failure. This should not cause dangerous operating states even for a short time. If necessary, emergency-stop devices should be implemented
PowerXL Series VFD
Wherever faults in the automation system may cause injury or material damage, external measures must be implemented to ensure a safe operating state in the event of a fault or malfunction (for example, by means of separate limit switches, mechanical interlocks, and so on)
Depending on their degree of protection, adjustable frequency drives may contain live bright metal parts, moving or rotating components, or hot surfaces during and immediately after operation
Removal of the required covers, improper installation, or incorrect operation of motor or adjustable frequency drive may cause the failure of the device and may lead to serious injury or damage
The applicable national accident prevention and safety regulations apply to all work carried out on live adjustable frequency drives
The electrical installation must be carried out in accordance with the relevant regulations (for example, with regard to cable cross sections, fuses, PE)
Transport, installation, commissioning, and maintenance work must be carried out only by qualified personnel (IEC 60364, HD 384 and national occupational safetyregulations)
Installations containing adjustable frequency drives must be provided with additional monitoring and protective devices in accordance with the applicable safety regulations. Modifications to the variable frequency drives using the operating software are permitted
All covers and doors must be kept closed duringoperation
To reduce hazards for people or equipment, the user must include in the machine design measures that restrict the consequences of a malfunction or failure of the drive (increased motor speed or sudden standstill of motor). These measures include:
Other independent devices for monitoring safety-related
variables (speed, travel, end positions, and so on)
Electrical or non-electrical system-wide measures
(electrical or mechanical interlocks)
Never touch live parts or cable connections of
the adjustable frequency drive after it has been disconnected from the power supply. Due to the charge in the capacitors, these parts may still be live after disconnection. Fit appropriate warning signs
POWERXL SERIES VFD MN040010EN—June 2018 www.eaton.com
xiii
PowerXL Series VFD
Read this manual thoroughly and make sure you understand the procedures before you attempt to install, set up, operate or carry out any maintenance work on this variable frequency drive.
Definitions and symbols
WARNING
This symbol indicates high voltage. It calls your attention to items or operations that could be dangerous to you and other persons operating this equipment. Read the message and follow the instructions carefully.
This symbol is the “Safety Alert Symbol.” It occurs with either of two signal words: CAUTION or WARNING, as described below.
WARNING
Indicates a potentially hazardous situation which, if not avoided, can result in serious injury or death.
CAUTION
Indicates a potentially hazardous situation which, if not avoided, can result in minor to moderate injury, or serious damage to the product. The situation described in the CAUTION may, if not avoided, lead to serious results. Important safety measures are described in CAUTION (as well as WARNING).
Hazardous high voltage
WARNING
Motor control equipment and electronic controllers are connected to hazardous line voltages. When servicing drives and electronic controllers, there may be exposed components with housings or protrusions at or above line potential. Extreme care should be taken to protect against shock.
Stand on an insulating pad and make it a habit to use only one hand when checking components
Always work with another person in case an emergency occurs
Disconnect power before checking controllers or performing maintenance
Be sure equipment is properly earthed
Wear safety glasses whenever working on electronic controllers or rotating machinery
WARNING
The components in the drive’s power section remain energized after the supply voltage has been switched off. After disconnecting the supply, wait at least five minutes before removing the cover to allow the intermediate circuit capacitors to discharge.
Pay attention to hazard warnings!
DANGER 5 MIN
WARNING
Electric shock hazard—risk of injuries! Carry out wiring work only if the unit is de-energized.
WARNING
Do not perform any modifications on the AC drive when it is connected to mains.
Warnings and cautions
WARNING
Be sure to ground the unit following the instructions in this manual. Ungrounded units may cause electric shock and/or fire.
WARNING
This equipment should only be installed, adjusted, and serviced by qualified electrical maintenance personnel familiar with the construction and operation of this type of equipment and the hazards involved. Failure to observe this precaution could result in death or severeinjury.
WARNING
Components within the drive are live when it is connected to power. Contact with this voltage is extremely dangerous and may cause death or severeinjury.
WARNING
Line terminals (L1, L2, L3), motor terminals (U, V, W) and the DC link/brake resistor terminals (DC–, DC+/ R+, R–) are live when the drive is connected to power, even if the motor is not running. Contact with this voltage is extremely dangerous and may cause death or severeinjury.
xiv
POWERXL SERIES VFD MN040010EN—June 2018 www.eaton.com
PowerXL Series VFD
WARNING
Even though the control I/O-terminals are isolated from line voltage, the relay outputs and other I/O-terminals may have dangerous voltage present even when the drive is disconnected from power. Contact with this voltage is extremely dangerous and may cause death or severe injury.
WARNING
This equipment has a large capacitive leakage current during operation, which can cause enclosure parts to be above ground potential. Proper grounding, as described in this manual, is required. Failure to observe this precaution could result in death or severe injury.
WARNING
Before applying power to this drive, make sure that the front and cable covers are closed and fastened to prevent exposure to potential electrical fault conditions. Failure to observe this precaution could result in death or severe injury.
WARNING
An upstream disconnect/protective device must be provided as required by the National Electric Code
®
(NEC
). Failure to follow this precaution may result in
death or severe injury.
®
WARNING
This drive can cause a DC current in the protective earthing conductor. Where a residual current-operated protective (RCD) or monitoring (RCM) device is used for protection in case of direct or indirect contact, only an RCD or RCM of Type B is allowed on the supply side of this product.
WARNING
Carry out wiring work only after the drive has been correctly mounted and secured.
WARNING
The opening of the branch-circuit protective device may be an indication that a fault current has been interrupted. To reduce the risk of fire or electric shock, current-carrying parts and other components of the controller should be examined and replaced if damaged. If burnout of the current element of an overload relay occurs, the complete overload relay must be replaced.
WARNING
Operation of this equipment requires detailed installation and operation instructions provided in the Installation/Operation manual intended for use with this product.
WARNING
Before servicing the drive:
Disconnect all power to the drive, including external control power that may be present
Place a “DO NOT TURN ON” label on the disconnect device
Lock the disconnect device in the open position
Failure to follow these instructions will result in death or serious injury.
WARNING
The drive outputs (U, V, W) must not be connected to the input voltage or the utility line power as severe damage to the device may occur and there may be a risk of fire.
WARNING
The heat sink and/or outer enclosure may reach a high temperature.
Pay attention to hazard warnings!
WARNING
Before opening the drive covers:
Disconnect all power to the drive, including external control power that may be present
Wait a minimum of five minutes after all the lights on the keypad are off. This allows time for the DC bus capacitors to discharge
A hazard voltage may still remain in the DC bus capacitors even if the power has been turned off. Confirm that the capacitors have fully discharged by measuring their voltage using a multimeter set to measure the DC voltage
Failure to follow these precautions may cause death or severe injury.
POWERXL SERIES VFD MN040010EN—June 2018 www.eaton.com
Hot Surface—Risk of Burn. DO NOT TOUCH!
CAUTION
Any electrical or mechanical modification to this drive without prior written consent of manufacturer will void all warranties and may result in a safety hazard in addition and voiding of the UL
®
listing.
CAUTION
Install this drive on flame-resistant material such as a steel plate to reduce the risk of fire.
xv
PowerXL Series VFD
CAUTION
Install this drive on a perpendicular surface that is able to support the weight of the drive and is not subject to vibration, to lessen the risk of the drive falling and being damaged and/or causing personal injury.
CAUTION
Prevent foreign material such as wire clippings or metal shavings from entering the drive enclosure, as this may cause arcing damage and fire.
CAUTION
Install this drive in a well-ventilated room that is not subject to temperature extremes, high humidity, or condensation, and avoid locations that are directly exposed to sunlight, or have high concentrations of dust, corrosive gas, explosive gas, inflammable gas, grinding fluid mist, etc. Improper installation may result in a fire hazard.
CAUTION
When selecting the cable cross-section, take the voltage drop under load conditions into account. The consideration of other standards is the responsibility of the user.
The user is responsible for compliance with all international and national electrical standards in force concerning protective grounding of all equipment.
CAUTION
The specified minimum PE conductor cross-sections in this manual must be maintained.
Touch current in this equipment exceeds 3.5 mA (AC). The minimum size of the protective earthing conductor shall comply with the requirements of EN 61800-5-1 and/or the local safety regulations.
CAUTION
Touch currents in this frequency inverter are greater than 3.5mA (AC). According to product standard IEC/EN 61800-5-1, an additional equipment grounding conductor of the same cross-sectional area as the original protective earthing conductor must be connected, or the cross-section of the equipment grounding conductor must be at least 10mm2Cu. Drive requires that only copper conductor should be used.
CAUTION
Debounced inputs may not be used in the safety circuit diagram. If you are connecting multiple motors on one drive, you must design the contactors for the individual motors according to utilization category AC-3.
Selecting the motor contactor is done according to the rated operational current of the motor to be connected.
CAUTION
Debounced inputs may not be used in the safety circuit diagram. A changeover between the drive and the input supply must take place in a voltage-free state.
CAUTION
Debounced inputs may not be used in the safety circuit diagram. Fire hazard!
Only use cables, protective switches, and contactors that feature the indicated permissible nominal current value.
CAUTION
Before connecting the drive to AC mains make sure that the EMC protection class settings of the drive are appropriately made according to instructions in this manual.
If the drive is to be used in a floating distribution network, remove screws at MOV and EMC
Disconnect the internal EMC filter when installing the drive on an IT system (an ungrounded power system or a high-resistance-grounded [over 30 ohm] power system), otherwise the system will be connected to ground potential through the EMC filter capacitors. This may cause danger, or damage the drive
Disconnect the internal EMC filter when installing the drive on a corner grounded TN system, otherwise the drive will be damaged
Note: When the internal EMC filter is disconnected, the
drive might be not EMC compatible.
Do not attempt to install or remove the MOV or EMC screws while power is applied to the drive’s input terminals.
CAUTION
Debounced inputs may not be used in the safety circuit diagram. Residual current circuit breakers (RCD) are only to be installed between the AC power supply network and thedrive.
xvi
POWERXL SERIES VFD MN040010EN—June 2018 www.eaton.com
Motor and equipment safety
PowerXL Series VFD
CAUTION
Do not perform any meggar or voltage withstand tests on any part of the drive or its components. Improper testing may result in damage.
CAUTION
Prior to any tests or measurements of the motor or the motor cable, disconnect the motor cable at the drive output terminals (U, V, W) to avoid damaging the drive during motor or cable testing.
CAUTION
Do not touch any components on the circuit boards. Static voltage discharge may damage the components.
CAUTION
Before starting the motor, check that the motor is mounted properly and aligned with the driven equipment. Ensure that starting the motor will not cause personal injury or damage equipment connected to the motor.
CAUTION
Set the maximum motor speed (frequency) in the drive according to the requirements of the motor and the equipment connected to it. Incorrect maximum frequency settings can cause motor or equipment damage and personal injury.
CAUTION
Before reversing the motor rotation direction, ensure that this will not cause personal injury or equipment damage.
CAUTION
Make sure that no power correction capacitors are connected to the drive output or the motor terminals to prevent drive malfunction and potential damage.
CAUTION
Make sure that the drive output terminals (U, V, W) are not connected to the utility line power as severe damage to the drive may occur.
CAUTION
When the control terminals of two or more drive units are connected in parallel, the auxiliary voltage for these control connections must be taken from a single source which can either be one of the units or an external supply.
CAUTION
The drive will start up automatically after an input voltage interruption if the external run command is on.
CAUTION
Do not control the motor with the disconnecting device (disconnecting means); instead, use the control panel start and stop keys and, or commands via the I/O board of the drive. The maximum allowed number of charging cycles of the DC capacitors (i.e. power-ups by applying power) is five in ten minutes.
CAUTION
Improper drive operation:
If the drive is not turned on for a long period, the performance of its electrolytic capacitors will be reduced
If it is stopped for a prolonged period, turn the drive on at least every six months for at least 5 hours to restore the performance of the capacitors, and then check its operation. It is recommended that the drive is not connected directly to the line voltage. The voltage should be increased gradually using an adjustable AC source
Failure to follow these instructions can result in injury and/or equipment damage.
POWERXL SERIES VFD MN040010EN—June 2018 www.eaton.com
xvii
PowerXL Series VFD
Sécurité
AVERTISSEMENT ! TENSION ÉLECTRIQUE DANGEREUSE !
Avant de commencer l’installation
Débrancher l’alimentation de l’appareil
S’assurer que les dispositifs ne peuvent pas être accidentellement redémarrés
Vérifier l’isolement de l’alimentation
Mettre l’appareil à la terre et le protéger contre les courts-circuits
Couvrir ou enfermer tout composant sous tension adjacent
Seul le personnel qualifié conformément à la norme EN 50110-1/-2 (VDE 0105 Partie 100) peut travailler sur cet appareil/ce système
Avant l’installation et avant de toucher l’appareil, s’assurer de ne porter aucune charge électrostatique
La terre fonctionnelle (FE, PSE) doit être raccordée à la terre de protection (PE) ou la compensation de potentiel. L’installateur du système a la responsabilité d’assurer cette connexion
Les câbles de connexion et les lignes de signal doivent être installés de façon à ce que les interférences capacitives ou inductives ne compromettent pas les fonctions d’automatisation
Installer les appareils d’automatisation et les éléments de fonctionnement associés de manière à ce qu’ils soient bien protégés contre tout fonctionnement accidentel
Des dispositifs de sécurité matériels et logiciels appropriés doivent être utilisés en rapport avec l’interface des E/S afin qu’un circuit ouvert sur le côté signal ne résulte pas en états indéfinis dans les dispositifs d’automatisation
Assurer une isolation électrique fiable sur le côté tension extra basse de l’alimentation 24 V. Utiliser uniquement des blocs d’alimentation conformes à la norme CEI 60364-4-41 (VDE 0100, partie 410) ou HD384.4.41 S2
Les écarts entre la tension d’entrée et la tension nominale ne doivent pas dépasser les limites de tolérance indiquées dans les spécifications, au risque de provoquer un mauvais fonctionnement et une utilisation dangereuse du système
Les dispositifs d’arrêt d’urgence conformes à la norme CEI/EN 60204-1 doivent être efficace dans tous les modes de fonctionnement des dispositifs d’automatisation. Le déverrouillage des dispositifs d’arrêt d’urgence ne doit pas entraîner un redémarrage
Les dispositifs conçus pour un montage dans des boîtiers ou armoires de commande ne doivent être utilisés et contrôlés qu’après avoir été installés et avec le boîtier fermé. Les unités de bureau ou portatives ne doivent être utilisées et contrôlées que dans leurs boîtiers fermés
Des mesures doivent être prises pour assurer un bon redémarrage des programmes interrompus après une chute ou une panne de tension. Ceci ne doit pas causer des états de fonctionnement dangereux, même pour un court laps de temps. Si nécessaire, des dispositifs d’arrêt d’urgence doivent être utilisés
Quand des défaillances du système d’automatisation peuvent entraîner des blessures ou des dommages matériels, des mesures externes doivent être appliquées pour assurer un état de fonctionnement sans danger en cas de panne ou de mauvais fonctionnement (par exemple au moyen de disjoncteurs séparés, de verrouillages mécaniques, etc.)
En fonction de leur degré de protection, les entraînements à fréquence variable peuvent contenir des pièces métalliques sous tension, des composants rotatifs ou en mouvement et des surfaces brûlantes, pendant le fonctionnement et immédiatement après l’arrêt
Le retrait des protections requises, une installation incorrecte ou un mauvais fonctionnement du moteur ou de l’entraînement à fréquence variable peuvent causer la défaillance de l’appareil et entraîner des blessures graves et des dommages importants
La réglementation nationale applicable en matière de sécurité et de prévention des accidents s’applique à tous les travaux effectués sur les entraînements à fréquence variable sous tension
L’installation électrique doit être effectuée conformément aux réglementations applicables (par exemple, en ce qui concerne les sections transversales des câbles, les fusibles, la mise à la terre de protection)
Le transport, l’installation, la mise en service et les travaux de maintenance doivent être effectués uniquement par un personnel qualifié (IEC 60364, HD 384 et règles de sécurité du travail)
Les installations contenant des entraînements à fréquence variable doivent être équipées de dispositifs de surveillance et de protection, conformément aux réglementations applicables en matière de sécurité. Les modifications des entraînements à fréquence variable réalisées à l’aide du logiciel d’exploitation sont autorisées
Toutes les protections et les portes doivent être maintenues fermées pendant le fonctionnement
xviii
POWERXL SERIES VFD MN040010EN—June 2018 www.eaton.com
Pour réduire les risques d’accidents et de dommages matériels, l’utilisateur doit inclure dans la conception de la machine des mesures limitant les conséquences de panne ou de mauvais fonctionnement de l’entraînement (augmentation de la vitesse ou arrêt soudain du moteur). Ces mesures comprennent :
Autres dispositifs indépendants de surveillance des
variables en rapport avec la sécurité (vitesse, voyages, positions d’extrémité, etc.)
Mesures électriques ou non électriques appliquées à
l’ensemble du système (verrouillages électriques ou mécaniques)
Ne jamais toucher les pièces sous tension ni les
connexions des câbles de l’entraînement à fréquence variable après leur déconnexion de l’alimentation. En raison de la charge dans les condensateurs, ces pièces peuvent être encore sous tension après la déconnexion. Installer les panneaux d’avertissement appropriés
Lire ce manuel en entier et s’assurer de bien comprendre les procédures avant de tenter d’installer, de configurer, d’utiliser et d’effectuer tout travail d’entretien sur cet entraînement à fréquence variable.
PowerXL Series VFD
Haute tension dangereuse
AVERTISSEMENT
L’équipement de contrôle du moteur et les contrôleurs électroniques sont branchés sur des tensions secteur dangereuses. Lors de l’entretien des entraînements et des contrôleurs électroniques, il peut y avoirdes composants exposés avec des boîtiers ou des protubérances au niveau du potentiel du réseau ou au-dessus. Toutes les précautions doivent être prises pour se protéger contre les chocs électriques.
Se tenir sur un tapis isolant et prendre l’habitude de n’utiliser qu’une seule main pour vérifier les composants
Toujours travailler avec une autre personne lorsqu’une situation d’urgence se produit
Débrancher l’alimentation avant de vérifier les contrôleurs ou d’effectuer des travaux d’entretien
S’assurer que l’équipement est correctement relié à la terre
Porter des lunettes de sécurité lors des travaux sur les contrôleurs électroniques ou les machines rotatives
Dé nitions et symboles
AVERTISSEMENT
Ce symbole indique une haute tension. Il attire l’attention sur les éléments ou les opérations qui pourraient être dangereux pour les personnes utilisant cet équipement. Lire attentivement le message et suivre attentivement les instructions.
Ce symbole est le « symbole d’alerte de sécurité ». Ilaccompagne les deux termes d’avertissement suivants: MISE EN GARDE ou AVERTISSEMENT, comme décrit ci-dessous.
AVERTISSEMENT
Indique une situation potentiellement dangereuse qui, si elle n’est pas évitée, peut entraîner des blessures graves ou la mort.
MISE EN GARDE
Indique une situation potentiellement dangereuse qui, si elle n’est pas évitée, peut entraîner des blessures légères à modérées et d’importants dégâts matériels. La situation décrite dans la MISE EN GARDE peut, si elle n’est pas évitée, entraîner des conséquences graves. Des mesures de sécurité importantes sont décrites dans les MISES EN GARDE (ainsi que dans les AVERTISSEMENTS).
AVERTISSEMENT
Les composants de la section d’alimentation de l’entraînement restent sous tension après la coupure de la tension d’alimentation. Après la déconnexion de l’alimentation, attendre au moins cinq minutes avant de retirer le couvercle pour permettre la décharge des condensateurs du circuit intermédiaire.
Prêter attention aux avertissements signalant des dangers !
DANGER 5 MIN
AVERTISSEMENT
Risque de choc électrique - risque de blessures ! Effectuer le câblage uniquement si l’unité n’est plus sous tension.
AVERTISSEMENT
Ne pas effectuer de modifications sur l’entraînement CA lorsqu’il est connecté à l’alimentation secteur.
POWERXL SERIES VFD MN040010EN—June 2018 www.eaton.com
xix
PowerXL Series VFD
Avertissements et mises en garde
AVERTISSEMENT
S’assurer de mettre l’appareil à la terre en suivant les instructions de ce manuel. Les unités non mises à la terre peuvent causer des chocs électriques et des incendies.
AVERTISSEMENT
Cet équipement ne doit être installé, réglé et entretenu que par un personnel d’entretien électrique qualifié connaissant la construction et le fonctionnement de ce type d’équipement, ainsi que les risques encourus. Le non-respect de cette précaution peut entraîner la mort ou des blessures graves.
AVERTISSEMENT
Les composants à l’intérieur de l’entraînement sont sous tension lorsque l’entraînement est branché à l’alimentation. Le contact avec cette tension est extrêmement dangereux et peut causer la mort ou des blessures graves.
AVERTISSEMENT
Les bornes de phase (L1, L2, L3), les bornes du moteur (U, V, W) et les bornes de résistance de liaison CC/ frein (DC-, DC+ /R+, R-) sont sous tension lorsque l’entraînement est branché à l’alimentation, même si le moteur ne tourne pas. Le contact avec cette tension est extrêmement dangereux et peut causer la mort ou des blessures graves.
AVERTISSEMENT
Même si les bornes E/S de commande sont isolées de la tension secteur, les sorties de relais et les autres bornes E/S peuvent présenter une tension dangereuse même lorsque l’entraînement est débranché. Le contact avec cette tension est extrêmement dangereux et peut causer la mort ou des blessures graves.
AVERTISSEMENT
Cet équipement a un grand courant de fuite capacitif pendant le fonctionnement, ce qui peut mettre les pièces du boîtier à un niveau supérieur au potentiel de terre. Une mise à la terre appropriée, telle que décrite dans ce manuel, est nécessaire. Le non-respect de cette précaution peut entraîner la mort ou des blessures graves.
AVERTISSEMENT
Avant de mettre l’entraînement sous tension, s’assurer que les protections avant et des câbles sont fermées et attachées pour empêcher l’exposition à d’éventuelles défaillances électriques. Le non-respect de cette précaution peut entraîner la mort ou des blessures graves.
AVERTISSEMENT
Un dispositif de protection/déconnexion en amont doit être fourni, tel que requis par le code électrique national (NEC peutentraîner la mort ou des blessures graves.
®
). Le non-respect de cette précaution
AVERTISSEMENT
Cet entraînement peut causer un courant CC dans le conducteur de mise à la terre de protection. Lorsqu’un dispositif de protection ou de surveillance à courant résiduel est utilisé pour la protection en cas de contact direct ou indirect, seul un dispositif de type B est autorisé sur le côté alimentation de ce produit.
AVERTISSEMENT
Ne travailler sur le câblage qu’après que l’entraînement a été correctement monté et attaché.
AVERTISSEMENT
Avant d’ouvrir les couvercles de l’entraînement :
Débrancher toute l’alimentation allant à l’entraîne­ment, y compris l’alimentation de commande externe pouvant être présente
Attendre un minimum de cinq minutes après l’extinction de tous les voyants du clavier. Cela permet aux condensateurs de bus CC de se décharger
Une tension dangereuse peut rester dans les condensateurs de bus CC même si l’alimentation a été coupée. Confirmer que les condensateurs sont entièrement déchargés en mesurant la tension à l’aide d’un multimètre réglé pour mesurer la tension CC
Le non-respect de cette précaution peut entraîner la mort ou des blessures graves.
AVERTISSEMENT
L’ouverture du dispositif de protection du circuit de dérivation peut indiquer que le courant de défaut a été interrompu. Pour réduire le risque d’incendie ou de choc électrique, les pièces porteuses de courant et les autres composants du contrôleur doivent être examinés et remplacés s’ils sont endommagés. Si l’élément de courant d’un relais de surcharge a grillé, le relais de surcharge doit être intégralement remplacé.
AVERTISSEMENT
Le fonctionnement de cet équipement nécessite le respect des instructions d’installation et de fonctionnement détaillées fournies dans le manuel d’installation/de fonctionnement destiné à être utilisé avec ce produit.
xx
POWERXL SERIES VFD MN040010EN—June 2018 www.eaton.com
PowerXL Series VFD
AVERTISSEMENT
Avant de procéder à l’entretien de l’entraînement :
Débrancher toute l’alimentation allant à l’entraîne­ment, y compris l’alimentation de commande externe pouvant être présente
Placer une étiquette « NE PAS UTILISER » sur le dispositif de déconnexion
Verrouiller le dispositif de déconnexion en position ouverte
Le non-respect de ces instructions peut entraîner la mort ou des blessures graves.
AVERTISSEMENT
Les sorties de l’entraînement (U, V, W) ne doivent pas être connectées à la tension d’entrée ni à l’alimentation secteur, car ceci pourrait gravement endommager l’appareil et causer un incendie.
AVERTISSEMENT
Le dissipateur de chaleur et/ou le boîtier externe peuvent atteindre une température élevée.
Prêter attention aux avertissements signalant des dangers !
Surface brûlante - Risque de brûlure. NE PAS TOUCHER !
MISE EN GARDE
Empêcher la pénétration de corps étrangers, tels que morceaux de fils et copeaux métalliques, dans le boîtier de l’entraînement, car ceci pourrait provoquer la formation d’un arc électrique et un incendie.
MISE EN GARDE
Installer cet entraînement dans une pièce bien aérée non soumise à des températures extrêmes, à une forte humidité ou à la condensation. Éviter les endroits directement exposés au soleil ou présentant de fortes concentrations de poussières, des gaz corrosifs, des gaz explosifs, des gaz inflammables, ou des vapeurs de liquide de meulage, etc. Une installation inadéquate peut entraîner un risque d’incendie.
MISE EN GARDE
Lors de la sélection de la section transversale des câbles, prendre en compte la chute de tension dans des conditions de charge. La prise en compte d’autres paramètres relève de la responsabilité de l’utilisateur.
Il relève de la responsabilité de l’utilisateur de respecter toutes les normes électriques nationales et internationales en vigueur concernant la mise à la terre de protection de l’ensemble de l’équipement.
MISE EN GARDE
Les spécifications minimum relatives aux sections transversales des conducteurs de terre de protection indiquées dans ce manuel doivent être respectées.
MISE EN GARDE
Toute modification électrique ou mécanique de cet entraînement sans consentement écrit préalable fabricar annule toutes les garanties, peut entraîner un danger pour lasécurité et annuler l’homologation UL
®
.
MISE EN GARDE
Installer cet entraînement sur une matière résistante aux flammes, telle qu’une plaque d’acier, pour réduire les risques d’incendie.
MISE EN GARDE
Installer cet entraînement sur une surface perpendiculaire capable de supporter le poids de l’entraînement et non soumise à des vibrations afin de diminuer les risques de chute et de dommage de l’entraînement, ainsi que les risques de blessures.
Le courant de fuite de cet équipement dépasse 3,5 mA (CA). La taille minimum du conducteur de la mise à la terre de protection doit être conforme aux exigences de la norme EN 61800-5-1 et/ou aux réglementations de sécurité locales.
MISE EN GARDE
Les courants de fuite de ce convertisseur de fréquence sont supérieures à 3,5 mA (CA). Conformément à la norme CEI/EN 61800-5-1, un conducteur de mise à la terre de l’équipement supplémentaire possédant la même superficie de coupe transversale que le conducteur de mise à la terre de protection d’origine doit être branché, ou la section transversale du conducteur de mise à la terre de l’équipement doit être d’au moins 10 mm2 Cu. Seul un conducteur en cuivre doit être utilisé avec cet entraînement.
MISE EN GARDE
Les entrées anti-rebond ne sont pas permises dans le schéma du circuit de sécurité. Des disjoncteurs de courant résiduel (RCD) ne peuvent être installés qu’entre le réseau de courant alternatif et l’entraînement.
POWERXL SERIES VFD MN040010EN—June 2018 www.eaton.com
xxi
PowerXL Series VFD
MISE EN GARDE
Les entrées anti-rebond ne sont pas permises dans le schéma du circuit de sécurité. Si plusieurs moteurs sont connectés à un entraînement, des contacteurs doivent être conçus pour les moteurs individuels conformément à la catégorie d’utilisation AC-3.
Sélectionner du contacteur du moteur en fonction du courant de fonctionnement nominal du moteur à connecter.
MISE EN GARDE
Les entrées anti-rebond ne sont pas permises dans le schéma du circuit de sécurité. Une commutation entre l’entraînement et l’alimentation d’entrée doit avoir lieu dans un état sans tension.
MISE EN GARDE
Les entrées anti-rebond ne sont pas permises dans le schéma du circuit de sécurité. Risque d’incendie !
Utiliser uniquement des câbles, des interrupteurs de protection et des contacteurs indiquant le courant nominal permis.
MISE EN GARDE
Avant de connecter l’entraînement à l’alimentation secteur CA, s’assurer que les réglages de la classe de protection CEM sont correctement effectués selon les instructions de ce manuel.
Si l’entraînement doit être utilisé dans un réseau de distri­bution flottant, retirer les vis au niveau des VOM et CEM. Voir « Installation dans un réseau à une phase connectée à la terre (corner-grounded)
Débrancher le filtre CEM interne lors de l’installation de l’entraînement sur un réseau IT (système d’alimentation non mis à la terre ou système d’alimentation électrique mis à la terre haute résistance [plus de 30 ohms]) pour ne pas que le système soit connecté au potentiel de terre via les condensateurs du filtre CEM. Ceci peut être une cause de dangers ou endommager l’entraînement
Débrancher le filtre CEM interne lors de l’installation de l’entraînement sur un système TN à une phase connectée à la terre pour ne pas endommager l’entraînement
Note: Lorsque le filtre CEM interne est débranché,
l’entraînement peut ne pas être conforme aux normes de compatibilité électromagnétique.
Ne pas tenter d’installer ou de retirer les vis des VOM et CEM lorsque l’alimentation est appliquée aux bornes d’entrée de l’entraînement
Sécurité du moteur et de l’équipement
MISE EN GARDE
N’effectuer aucun test de résistance de tension ou au mégohmmètre sur toute partie de l’entraînement ou de ses composants. Un test inadéquat peut entraîner des dommages.
MISE EN GARDE
Avant tout test ou mesure du moteur ou du câble du moteur, débrancher le câble du moteur au niveau des bornes de sortie de l’entraînement (U, V, W) pour éviter d’endommager ce dernier lors des tests.
MISE EN GARDE
Ne toucher aucun composant sur les cartes de circuit. Les décharges d’électricité statique peuvent endommager les composants.
MISE EN GARDE
Avant de mettre le moteur en marche, vérifier qu’il est correctement monté et aligné avec l’équipement entraîné. S’assurer que le démarrage du moteur ne risque pas de provoquer des blessures ou d’endommager l’équipement connecté au moteur.
MISE EN GARDE
Régler la vitesse maximale du moteur (fréquence) dans l’entraînement conformément aux exigences du moteur et de l’équipement qui lui est connecté. Des réglages de fréquence maximum incorrects peuvent endommager le moteur ou l’équipement et causer des blessures.
MISE EN GARDE
Avant d’inverser le sens de rotation du moteur, veiller à ce que cela ne risque pas de provoquer des blessures ou des dommages matériels.
MISE EN GARDE
S’assurer qu’aucun condensateur de correction de puissance n’est connecté à la sortie de l’entraînement ou aux bornes du moteur pour éviter un mauvais fonctionnement de l’entraînement et des dommages potentiels.
MISE EN GARDE
S’assurer que les bornes de sortie de l’entraînement (U, V, W) ne sont pas connectées à l’alimentation secteur, ce qui pourrait causer de graves dommages à l’entraînement.
xxii
POWERXL SERIES VFD MN040010EN—June 2018 www.eaton.com
PowerXL Series VFD
MISE EN GARDE
Lorsque les bornes de commande de deux ou plusieurs unités d’entraînement sont raccordées en parallèle, la tension auxiliaire de ces connexions de commande doit être fournie par une source unique, qui peut être soit l’une des unités, soit une alimentation externe.
MISE EN GARDE
L’entraînement démarre automatiquement après une interruption de la tension d’entrée si la commande de démarrage externe est active.
MISE EN GARDE
Ne pas commander le moteur avec le dispositif de déconnexion ; à la place, utiliser les touches de marche et d’arrêt du tableau de contrôle ou les commandes du tableau des E/S de l’entraînement. Le nombre de cycles de charge maximum permis des condensateurs CC (c’est-à-dire les mises sous tension par application de puissance) est de cinq en dix minutes.
MISE EN GARDE
Fonctionnement incorrect de l’entraînement :
Si l’entraînement n’est pas mis en marche pendant une longue période, la performance de ses condensateurs électrolytiques sera réduite
S’il est arrêté pour une période prolongée, le mettre en marche au moins tous les six mois pendant au moins 5heures pour restaurer la performance des condensateurs, puis vérifier son fonctionnement. Il est recommandé de ne pas brancher l’entraînement directement sur la tension secteur. La tension doit être augmentée progressivement en utilisant une source CA réglable
Le non-respect de ces instructions peut entraîner des blessures ou des dégâts matériels.
POWERXL SERIES VFD MN040010EN—June 2018 www.eaton.com
xxiii
Sécurité du moteur et de l’équipement
xxiv
POWERXL SERIES VFD MN040010EN—June 2018 www.eaton.com
PowerXL Series Overview
PowerXL Series Overview
This series overview describes the purpose and contents of this manual, the receiving inspection recommendations and the PowerXL Series Open Drive catalog numbering system.
How to use this manual
The purpose of this manual is to provide you with information necessary to install, set and customize parameters, start up, troubleshoot and maintain the PowerXL Series Variable Frequency Drive (VFD). To provide for safe installation and operation of the equipment, read the safety guidelines at the beginning of this manual and follow the procedures outlined in the following chapters before connecting power to the PowerXL Series VFD. Keep this operating manual handy and distribute to all users, technicians and maintenance personnel for reference.
Receiving and inspection
The PowerXL Series VFD has met a stringent series of factory quality requirements before shipment. It is possible that packaging or equipment damage may have occurred during shipment. After receiving your PowerXL Series VFD, please check for the following:
Check to make sure that the package includes the Instruction Leaflet, Quick Start Guide, and accessory packet. The accessory packet includes:
Rubber grommets
Control cable grounding clamps
Additional grounding screw
Real time clock battery activation
To activate the real time clock (RTC) functionality in the PowerXL Series VFD, the RTC battery (already mounted inthe drive) must be connected to the control board.
Simply remove the primary drive cover, locate the RTC battery directly below the keypad, and connect the white 2-wire connector to the receptacle on the control board.
Figure 1. RTC battery connection
Inspect the unit to ensure it was not damaged during shipment.
Make sure that the part number indicated on the nameplate corresponds with the catalog number on your order.
If shipping damage has occurred, please contact and file a claim with the carrier involved immediately.
If the delivery does not correspond to your order, please contact your Eaton Electrical representative.
ote: N Do not destroy the packing. The template printed on
the protective cardboard can be used for marking the mounting points of the PowerXL VFD on the wall or in a cabinet.
Table 1. Common abbreviations
Abbreviation Definition
CT Constant torque with high overload rating (150%)
VT Variable torque with low overload rating (110%)
I
H
I
L
RTC Real Time Clock
VFD Variable Frequency Drive
High Overload (150%)
Low Overload (110%)
POWERXL SERIES VFD MN040010EN—June 2018 www.eaton.com
1
PowerXL Series Overview
Rating label
Figure 2. Rating label (DG1)
Contains
EAN Code
Contains
NAED Code
Contains SN, PN, Type, Date
Figure 3. Rating label (DH1)
Contains
EAN Code
Contains
NAED Code
Contains SN, PN, Type, Date
Date Code: 20131118
General information
The PowerXL Series drives provide a wide selection of option boards to increase the number and type of control inputs and outputs (I/O) and communication interfaces to provide the versatility required for today’s demanding motor control applications.
2
POWERXL SERIES VFD MN040010EN—June 2018 www.eaton.com
Date Code: 20131118
The input and output capability is designed with modularity in mind, comprised of option boards, each having its own input and output configuration. The control unit is designed to accept a total of two boards, the boards provide standard analog and digital inputs and outputs, fieldbus capability, and application specific hardware.
The basic, expander and adapter boards are installed in board slots, which are parts of the control board. The I/O boards are interchangeable between different members of the PowerXL Series drives.
Option Card Slots
The control board is located inside the control unit of the PowerXL Series Drive. There are two slots, labeled A and B, on the control board. The different option boards can be added to any slots. For more information, see “PowerXL Series Option Board Summary.” When the PowerXL Series Drive is assembled at the factory, no option boards are installed in slots A and B. If an incorrect board is plugged into either slot, the board will not work, but there is no danger to personal or for equipment damage.
Figure 5. PowerXL Series control board location
Option Card Slots
Figure 4. PowerXL Series control board location
Fan Power Wire
STO
AI Mode Selection
Control I/O
Terminals
Removable
EMC Screw
Line Ground
Clamp Location
Grounding
Strap Location
Figure 5. Count
Connect DSP Part to Power Board
Keypad
Connect MCU Part
123
ON
ON
1
to Power Board
Battery (Standard)
RJ45 EtherNet/IP, Modbus TCP
Optional Card A
Optional Card B
RS-485 Termination Resistor
Removable MOV Screw
Motor Ground Clamp Location
Grounding Strap Location
Line Side Motor
POWERXL SERIES VFD MN040010EN—June 2018 www.eaton.com
3
Option Card Slots
Installing PowerXL Series option board
Remove Utility line and control power from the drive. Install the option board in one of the slots available on the control board. To insert and remove the board, hold it in a horizontally straight position to avoid twisting the connectorpins.
CAUTION
To prevent board damage, option cards and fieldbus boards must not be installed, removed or replaced while utility line or control power is applied to the drive.
Verify the board fits tightly in the metal clamp and plastic groove. If the board seems to be difficult to install in the slot, you should confirm that you are using one of the allowed slots for the option board.
ote: N Check that the DIP switch settings on the board corre-
spond to your need.
Control wiring
Digital I/O and 24 Vdc can use Stranded Cu or Solid Cu wire as specified below. Analog signal PT100 must use shielded cables. Table 2 shows the wire sizes available. I/O terminals allow for 5.00 mm connectors.
Table 2. Wire sizes
Wire type Wire size Terminal torque
Solid Cu –90 °C 12–28 AWG (0.2~2.5 mm2) 4.5 in-lb (0.5 Nm)
Stranded Cu –90 °C 12–30 AWG (0.2~2.5 mm2) 4.5 in-lb (0.5 Nm)
4
POWERXL SERIES VFD MN040010EN—June 2018 www.eaton.com
Option Card Slots
EMC directive
For the electrical equipment installed in the EMC, directive states that the equipment must not disturb the environment and must be immune to other electromagnetic disturbances in the environment. Table 3 indicates the requirements for the control wiring to meet this directive.
Table 3. Control wiring requirements
Item Directive
Product Safety EMC (at default
settings)
Table 4. PowerXL Series—drive option boards
IEC 61800-2 UL 508C, IEC / EN 61800-5-1 Immunity: EN / IEC 61800-3, 2nd environment Radiated emissions: EN / IEC 61800-3 (Transient Testing
included), 1st environment Conducted emissions: EN / IEC 61800-3 Category C1: is possible with external filter connected to
drive. Please consult factory Category C2: with internal filter maximum of 10m motor
cablelength (FR0: This is obtained with 2 turns on a ferrite core and using metal ground plate)
Category C3: with internal filter maximum of 50m motor cable length (FR0: This is obtained with no ferrite core and metal plate)
Control cable grounding
It is recommended that the shielded cables be grounded as shown in Figure 6. Strip the cable insulation required allowing attachment to the frame with the grounding clamp.
Figure 6. Control cable grounding
DX H –NET
Basic naming
DX = PowerXL Drive
Table 5. PowerXL Series drives protocols
Protocols
Modbus RTU BACnet MSTP EtherNet/IP Modbus TCP PROFIBUS CANopen DeviceNET SmartWire-DT BACnet IP
Series
H = HVAC purpose
PowerXL Series Drives
■■
■■
■■
■■
PROFB
Type
NET = Communication card
EXT = I/O card ACC = Accessory SPR = Spare part KEY = Keypad CBL = Cable
On Board/Option ModuleDG1 DH1
On Board On Board
On Board
On Board
Option Module —Option Module —Option Module —Option Module
On Board
Function
PROFB = PROFIBUS
DEVICENET = DeviceNet
CANopen = CANopen SWD-IP20 = SmartWire IP20 SWD-IP54 = SmartWire IP54
POWERXL SERIES VFD MN040010EN—June 2018 www.eaton.com
5
Modbus RTU On-Board Communications
Modbus RTU On-Board Communications
The drive product can be controlled via Modbus® RTU through the on-board RS-485 terminals.
Figure 7. Connection diagram
The figure shows a typical arrangement with a host computer (master) and any number maximum 31 slaves of frequency inverters. Each frequency inverter has a unique address in the network. This addressing is executed individually for each VFD via the communication parameters.
The electrical connection between master and the slaves connected in parallel are implemented via the serial interface A-B (A = positive, B = negative) with a shielded RS-485 twisted pair cable.
Modbus RTU specifications Communication board connections
Table 6. Connections
Item Description
Interface Data Transfer Method Tra ns fer Cable Electrical Isolation
RS-485, half-duplex Twisted pair (1 pair and shield)
Communications
Table 7. Communications
Item Description
Modbus RTU
Baud Rate Addresses
As described in “Modicon Modbus Protocol Reference Guide” found at. http.//public.modicon.com/
9600,19200,38400,57600,115200 1 to 247
Connections
The RS-485 communication port is connected via the AandB terminals on the drives control board.
Figure 8. Terminal wiring
6
POWERXL SERIES VFD MN040010EN—June 2018 www.eaton.com
Figure 9. Termination resistor and shielding
Commissioning
RS-485 communication parameters
To commission the RS-485 communication board, enter the Keypad menu as described below.
Change the Modbus RTU commissioning parameter values.
Modbus RTU On-Board Communications
Figure 10. DG1 keypad navigation to RS-485 menu
POWERXL SERIES VFD MN040010EN—June 2018 www.eaton.com
7
Modbus RTU On-Board Communications
Figure 11. DH1 keypad navigation to RS-485 menu
In this menu you will be able to scroll through the below settings to setup the communication protocol.
Table 8. Modbus RTU
DG1 code DH1 code Parameter Min. M ax. Unit Defau lt ID Note
P20.3.1.1 P12.3.1.1 RS4 85 comm set 0 586 0 = Modbus RTU
1 = BACnet® MS/TP
2 = SmartWire-DT® P20.3.2.1 P12.3.2.1 Slave address 1 247 1 587 P20.3.2.2 P12.3.2.2 Baud rate 1 584 0 = 9600
1 = 19200
2 = 384 00
3 = 5760 0
4 = 115200 P20.3.2.3 P12.3.2.3 Parit y type 2 585 0 = None, 2 Stop Bits
1 = Odd, 1 Stop Bit
2 = Even, 1 Stop Bit P20.3.2.4 P12.3.2.4 Protocol status 0 588 0 = Initial
1 = Stopped
2 = Operational
3 = Faulted P20.3.2.5 P12.3.2.5 Slave busy 0 589 0 = Not Busy
1 = Busy P20.3.2.6 Parity error 0 590 P20.3.2.7 Slave fault 0 591 P20.3.2.8 Last fault response 0 592 P20.3.2.9 Comm timeout modbus RTU ms 10000 593 P20.3.2.10 P12.3.2.6 Modbus RTU/BACNet Fault
Response
01 025160 = In Fieldbus Control
1 = in all Control
The parameters of every device must be set before connecting to the bus. Each parameter must be the same as the master configuration.
Not available on the PowerXL DH1.
For SmartWire-DT: Before connecting the power supply to both the Drive and PLC, ensure devices
are off before connecting the 8 pin flat cable to prevent damage to the boards.

8
POWERXL SERIES VFD MN040010EN—June 2018 www.eaton.com
Loading...