Cutler Hammer, Div of Eaton Corp Operator Interface Products Accessories Catalog

Operator Interface Products
Nameplate
Connection Port
Direct Mounting Hole
Input/Output Terminals
HMi Operator Interface
March 2008
Software and Accessories
Accessories
HMIECENT Ethernet Expansion Module
The HMIECENT expansion module adds 10/100 MB Modbus TCP ability when plugged into the expansion slot of a 6", 8" or 10" HMi unit. Up load and download programs and com­municate to other Modbus TCP devices. No need for patch or crossover cables as this module auto-detects and adjusts for proper operation.
48-11
I/O Expansion Modules
The HMIEC0806 and HMIEC1612 are 14 and 28 discrete I/0 expansion modules providing 8 DC inputs and 6 relay out­puts or 16 DC inputs and 12 relay outputs. Plug this module into the available expansion slot on the back of the HMi unit (not available on the 4" model) and it’s ready to use. No need for a separate PLC controller as it is built into the unit. Com­bine operator interface and logic into a single platform — use HMISOFT to build both the ladder logic and OI program.
Figure 48-6. Ethernet Expansion Module — Product Outline
Table 48-10. HMICENT Function Specifications
Item Specifications
Power Supply Voltage DC 5V ±10%, 1A (provided by HMi )
Interfaced Supported RJ-45 with Auto MDI/MDIX
Number of Ports 1 Port
Transmission Method (Standard Conformance)
Transmission Cable Category 5e (TIA/EIA-568-A, TIA/EIA-568-B)
Transmission Speed 10/100 Mbps Auto Detection
Ethernet Protocol ICMP, IP, TCP, UDP, DHCP, Modbus TCP
Noise Immunity ESD (IEC 61131-2,
Connection Port for Ethernet
Direct Mounting Hole
Connection Port for Extension Module
IEEE 802.3, IEEE 802.3u
IEC 61000-4-2): 8 kV Air Discharge EFT (IEC 61131-2, IEC 61000-4-4): Power Line: 2 kV, Communication I/O: 1 kV Damped-Oscillatory Wave: Power Line: 1 kV, Digital I/O: 1 kV RS (IEC 61131-2, IEC 61000-4-3): 26MHz ~ 1GHz, 10V/m
Nameplate
Figure 48-7. I/O Expansion Modules — Product Outline
Table 48-11. I/O Expansion Modules
Catalog Number
HMIEC0806 5V DC
HMIEC1612 16 12 Relay
Input/Output
Power Input Unit Output Unit
Point Type Point Type
supplied by HMi
8 DC Type
Sink or Source
6 Relay
48
CA08102001E For more information visit: www.eaton.com
48-12
48
Operator Interface Products HMi Operator Interface
Software and Accessories
Table 48-12. HMIEC0806/HMIEC1612 Function Specifications
Item Specifications Remark
Control Method Stored program, cyclic
I/O Processing Method Batch I/O (refresh) Immediate refresh command available only
Execution Speed Basic command (30 us) Application command (30 ~ hundreds us)
Program Language Commands + Ladder
Program Capacity 999 Steps Built-in EEPROM
Commands Basic commands: 32
Step Relay (Latched)
Auxiliary Relay
Timer Digital 64 Points T0 ~ T63 (100 ms time base)
Counter General 112 Points C0 ~ C111
Data Register
Pointer P 64 Points P0 ~ P63
Index Register
Constant Decimal K 16 bit: -32768 ~ +32767 32 bit: -2147483648 ~ +2147483647
Self Diagnosis / Protection I/O check, system execution timeout check, invalid command check,
Monitor / Debug Program execution time display, bit / word, device settings
M1000, M1001, M1002, M1003, M1020, M1021, M1022, M1067, M10068, and M1161 are the special auxiliary relays (special M).
General Step Point
General 1024 Points M0 ~ M511, M768 ~ M999, 744 points;
Latched 256 Points M512 ~ M767
Latched 16 Points C112 ~ C127
32 bit 13 Points C235,C236,C237,C238,C241,C242,
General 408 Points D0 ~ D407
Latched 192 Points D408 ~ D599
E / F 2 E, F
Hexadecimal H 16 bit: 0000 ~ FFFF 32 bit: 00000000 ~ FFFFFFFF
scan system
Diagram + SFC
(including the STL commands)
128 Points S0 ~ S127
63 Points T64 ~ T126 (10 ms time base)
1 Points T127 (1 ms time base)
program check and password settings
with I/O of the MPU
Step commands included
Application commands: 59
M1000 ~ M1279, 280 points
C244,C246,C247,C249,C251,C252, C254 (all of them are latched type)
March 2008