Cutler Hammer, Div of Eaton Corp Molded Case Circuit Breakers Catalog Supplement

2.2
Power Defense Molded Case Circuit Breakers—Frame Size 1
Molded Case Circuit Breakers
Power Defense Molded Case Circuit Breakers
2
2
2
2
2
2
2
2
2
2
2
Power Defense Molded Case Circuit Breakers—Frame Size 1
Product Description
2
Frame Size 1 covers a range of 15 A through 125 A with
2
fixed-fixed thermal-magnetic trip units. PD-1 is available
2
in 1-, 2-, 3- and 4-pole configurations, with the
2
4-pole configuration available with no protection on the
2
neutral pole, or fully protected.
Application Description
Frame Size 1 can be used to meet a wide range of circuit protection and power distribution needs, including current limiting applications. PD-1 is a cable-in / cable-out MCCB.
Contents
Power Defense Molded Case Circuit Breakers
Frame Size 1 (15–125 A)
Catalog Number / Product Selection . . . . . . V4-T2-23
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . V4-T2-26
Dimensions and Weights. . . . . . . . . . . . . . . V4-T2-28
Frame Size 2 (15–225 A) . . . . . . . . . . . . . . . . . . . . V4-T2-29
Frame Size 3 (45–600 A) . . . . . . . . . . . . . . . . . . . . V4-T2-42
Frame Size 4 (300–800 A) . . . . . . . . . . . . . . . . . . . V4-T2-57
Frame Size 5 (320–1200 A) . . . . . . . . . . . . . . . . . . V4-T2-70
Frame Size 6 (700–2500 A) . . . . . . . . . . . . . . . . . . V4-T2-79
Motor Circuit Protectors (3–600 A) . . . . . . . . . . . . V4-T2-87
Motor Protection Circuit Breakers (15–600 A) . . . V4-T2-98
Terminals, Lugs and Connectors . . . . . . . . . . . . . V4-T2-104
Communications and Software. . . . . . . . . . . . . . . V4-T2-127
Special Applications . . . . . . . . . . . . . . . . . . . . . . . V4-T2-129
Features and Benefits
Frame Size 1 breakers are available in multiple ratings from 15 A through 125 A. They are of a modular design with field installable accessories and terminals, which may also be factory installed.
Standards and Certifications
Power Defense breakers are designed and tested to meet stringent requirements for:
l
UL
l
CSA
l
IEC (CE)
l
CB (CCC)
2
2
2
2
2
2
2
2
2
2
2
2
2
2
V4-T2-22 Volume 4—Circuit Protection CA08100005E—March 2020
Molded Case Circuit Breakers
Power Defense Molded Cas e Circ uit Breakers
2.2
Catalog Number / Product Selection
Power Defense—Frame Size 1 (15–125 A)
Frame Size 1 covers a range of 15 A through 125 A using thermal-magnetic trip units. It is available in configurations of single-pole, 2-pole, 3-pole and 4-pole.
Interrupting Ratings (2-, 3- and 4-Pole)
Catalog Designator
ANSI (UL/CSA) kA rms kA rms kA rms kA rms kA rms kA rms kA rms
240 Vac 25 35 65 85 100 150 200
480 Vac
600Y/347 Vac
3
250 Vdc
IEC
240 Vac 25 25 35 35 55 55 85 85 100 100 150 150 200 200
380–415 Vac
3
250 Vdc
Interrupting Ratings (Single-Pole)
ANSI (UL/CSA)
120 Vac 35 100 200
240 Vac
277 Vac
347 Vac
125 Vdc
IEC
240 Vac 25 25 35 35 55 55 85 85 100 100
125 Vdc
Notes
1
UL current limiting.
2
Available in 3- and 4-pole configurations only.
3
Must use 2 poles in series for 250 Vdc.
CFGKM
18 25 35 50 65 85 100
10 14 18 22 25 30 35
10 22 22 35 35 42 42
l
20 20 25 25 36 36 50 50 70 50 70 70 100 100
10 10 22 22 22 22 35 35 35 35 42 42 42 42
CFGKM
kA rms kA rms kA rms kA rms kA rms
25 35 65 85 100
18 25 35 50 65
10 14 18 22 25
10 22 22 35 35
l
10 10 22 22 22 22 35 35 35 35
l
cu
l
cu
l
cs
l
cs
l
cu
l
cu
l
cs
l
cs
l
cu
l
cu
l
cs
l
cs
l
cu
cu
cs
l
cs
1
l
l
l
cu
cu
cs
l
cs
12
N
l
l
cu
cs
12
P
l
l
cu
2
2
2
2
2
2
2
cs
2
2
2
2
2
2
2
2
2
2
2
Volume 4—Circuit Protection CA08100005E—March 2020 V4-T2-23
2
2
2
2
2
2
2
2
2
2
2
2
Molded Case Circuit Breakers
Certifications/
Standards
G = UL/CSA/IEC/CCC
Frame
Size
1 =1
Pole
Options
1 =1-pole 2 = 2-pole
Interrupting
Ratings
1
C = 18 kA at 480 V F = 25 kA at 480 V G = 35 kA at 480 V K = 50 kA at 480 V M= 65 kA at 480 V
Trip Unit
Type Options
TFF = Fixed Thermal /
Fixed Magnetic
VFF = 50 °C Fixed
Thermal / Fixed Magnetic (non UL)
Standard Terminal
Options
N = No terminals J = Line and load terminals K = Line only terminals L = Load only terminals
Continuous
Current Ratings
0015 =15 A 0020 =20 A 0025 =25 A 0030 =30 A 0035 =35 A 0040 =40 A 0045 =45 A 0050 =50 A 0060 =60 A 0070 =70 A 0080 =80 A 0090 =90 A 0100 = 100 A 0110 = 110 A 0125 = 125 A
Product Series
PD = Power Defense
PD G 1 3 M 0125 TFF J
G = UL/CSA/IEC/CCC 1 =1 3 =3-pole
4 = 4-pole (100% N) 0 = 4-pole (0% N)
C = 10 kA at 600Y/347 V F = 14 kA at 600Y/347 V G = 18 kA at 600Y/347 V K = 22 kA at 600Y/347 V M= 25 kA at 600Y/347 V N = 30 kA at 600Y/347 V P = 35 kA at 600Y/347 V
TFF = Fixed Thermal /
Fixed Magnetic
VFF = 50 °C Fixed
Thermal / Fixed Magnetic (non UL)
N = No terminals J = Line and load terminals K = Line only terminals L = Load only terminals
0015 =15 A 0020 = 20 A 0025 =25 A 0030 =30 A 0035 =35 A 0040 =40 A 0045 =45 A 0050 =50 A 0060 =60 A 0070 =70 A 0080 =80 A 0090 =90 A 0100 = 100 A 0110 = 110 A 0125 = 125 A
PD
Molded Case Circuit Breakers (Three- and Four-Pole) with Thermal-Magnetic Trip Units—Globally Rated
G = UL/CSA/IEC/CCC 1 =1 3 =3-pole
4 = 4-pole
G = 35 kA at 480 V M= 65 kA at 480 V
KNS = Molded Case
Switch
N = No terminals J = Line and load terminals K = Line only terminals L = Load only terminals
0125 = 125 A PD
Molded Case Switches—Globally Rated
3
Interrupting
Ratings
2
C = 10 kA at 600Y/347 V F = 14 kA at 600Y/347 V G = 18 kA at 600Y/347 V K = 22 kA at 600Y/347 V M= 25 kA at 600Y/347 V
C = 18 kA at 480 V F = 25 kA at 480 V G = 35 kA at 480 V K = 50 kA at 480 V M= 65 kA at 480 V N = 85 kA at 480 V P = 100 kA at 480 V
G = 18 kA at 600Y/347 V M= 25 kA at 600Y/347 V
2.2
Power Defense—Frame Size 1 (15–125 A)
2
This information is presented as a tool to develop catalog numbers for selecting Power Defense circuit breakers and trip units.
2
Molded Case Circuit Breakers (Single- and Two-Pole) with Thermal-Magnetic Trip Units—Globally Rated
2
2
2
2
2
2
2
2
2
Power Defense Molded Case Circuit Breakers
2
2
2
2
2
2
2
2
2
2
2
2
2
Notes
1
Ratings at 277 Vac for single-pole.
2
2
Ratings at 347 Vac for single-pole.
3
Molded case switch may open above 1250 A.
2
2
2
2
2
V4-T2-24 Volume 4—Circuit Protection CA08100005E—March 2020
Molded Case Circuit Breakers
Power Defense Molded Cas e Circ uit Breakers
2.2
Terminals—Frame Size 1
Catalog numbers shown are for a single side of a 3-pole breaker. For 2- and 4-pole options, replace the X3 with X2 or X4, respectively. Example: PDG1X3T125 becomes PDG1X2T125 for two-pole.
Te r m i n a l T y p e s
PDG1X3T125 PDG1X3TA125 PDG1X3TA1256W PDG1X3TA1253W PDG1X3TS125 GCWTK
Note: Pictures are for reference only.
Te r m i n a l s
2
Maximum Breaker Amperes
Standard Terminals
125 Steel Al or Cu B, C 1 14-3/0 2.08–85 PDG1X3T125 J K L 15–125
Alternate Terminals
125 Aluminum Cu/Al B, C 1 14-1/0 2.08–53.5 PDG1X3TA125 T U V 15–125
Multi-wire Terminals
125 Aluminum Cu/Al B, C 6 14-6 2.08–13.3 PDG1X3TA1256W Terminal shield G 15–125
125 Aluminum Cu/Al B, C 3 14-2 2.08–33.6 PDG1X3TA1253W Terminal shield H 15–125
End Cap Kit/Screw Terminals
—— ——— — — PDG1X3TS125 S D E 15–125
Note: Wire capacity is based on standard imperial wire sizes; metric sizes provided in table are a direct conversion to demonstrate maximum capacity, not to denote metric wire sizes.
Control Wire Tabs
Use
15–125 A 12 GCWTK
Note: Control wire tabs can be installed with terminals listed above.
Terminal Body Type
Wire Ty pe
Package Quantity
Wire Class
Number of Conductors per Phase
Catalog Number
AWG Range per Conductor
Metric (mm Range per Conductor
)
3-Pole Catalog Number
Included Accessories
Digit 14 Designation Line and
Load
Line Only
Load Only
Standard on Amperes
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
Volume 4—Circuit Protection CA08100005E—March 2020 V4-T2-25
2
2
2
2
2
2
2
2
Molded Case Circuit Breakers
2.2
Accessories
2
Internal Accessory Configurations—Frame Size 1
2
3- and 4-Pole Circuit Breakers
2
2
2
Tripping Accessory Options
2
None None
2
2
Qty: 1
2
2
2
Qty: 1
Power Defense Molded Case Circuit Breakers
Indicating Accessory Options
1 Make/1 Break Alarm Switch
2 Make/2 Break Alarm Switch
1A/1B Auxiliary Switch
2A/2B Auxiliary Switch
1A/1B Alarm,1A/1B Auxiliary Combination
1
2
Alarm and Auxiliary Switches
2
Alarm and auxiliary switches are plug-and-play accessories designed to be field
2
installable. However, Eaton also offers the service of field
2
installation in our factories.
2
Breaker catalog numbers with alarm and auxiliary switch combinations require a complete 20-digit catalog number, adding the alarm and auxiliary switch functionality in digits 15–16 and adhering to the following conditions and tables:
2
Alarm and Auxiliary Switch—Field Installation Kits
2
2
Alarm Switch None
2
2
2
Alarm and Auxiliary Switch Factory Installation (Digits 15–16)
2
Alarm Switch None
2
2
Notes
1
2
2-pole PD-1 breakers have an accessory pocket compatible with indicating accessory options only.
2
All options come with pigtail terminations.
Auxiliary Switch Catalog Number
Three-Pole None 1NO/1NC (1 Form C) 2NO/2NC (2 Form C)
1NO/1NC (1 Form C)
2NO/2NC (2 Form C)
Auxiliary Switch Breaker Catalog Number (Digit 15–16 Suffix) Three-Pole None 1NO/1NC (1 Form C) 2NO/2NC (2 Form C)
1NO/1NC (1 Form C)
2NO/2NC (2 Form C)
ALM1M1BEPK AUXALRMEPK
ALM2M2BEPK ——
NN AC A1
BC CC
B1 ——
2
l
Digit 15 denotes the type of accessory(-ies) installed and the terminal types
l
Digit 16 denotes number of switches installed
l
If no other accessories are selected, use NNNN for the final 4 digits of the catalog number
2
AUX1A1BPK AUX2A2BPK
2
2
2
2
V4-T2-26 Volume 4—Circuit Protection CA08100005E—March 2020
Molded Case Circuit Breakers
Power Defense Molded Cas e Circ uit Breakers
2.2
Tripping Accessories—Frame Size 1
Shunt Trips Undervoltage Releases
Pigtail (29 in / 0.75 m)
12 Vdc SH SNT012CPK
24 Vac/Vdc SN SNT024CPK
48–60 Vdc SNT4860CPK
110–125 Vdc SNT125DPK
250 Vdc SNT250DPK
48–60 Vac SNT4860CPK
110–240 Vac SNT120CPK
380–600 Vac SNT480CPK
Handle Mechanisms—Frame Size 1
Universal Direct Rotary Handle Mechanism Variable Depth Rotary Handle Mechanism
Description
With interlock EHMCCBI EHMCCRI
Without interlock EHMCCB EHMCCR
Flex Shaft Handle Mechanism
Cable Length (ft)
2 PDG1XFS02 PDG1XFS02HP PDG1XFS02X PDG1XFS02HPX
3 PDG1XFS03 PDG1XFS03HP PDG1XFS03X PDG1XFS03HPX
4 PDG1XFS04 PDG1XFS04HP PDG1XFS04X PDG1XFS04HPX
5 PDG1XFS05 PDG1XFS05HP PDG1XFS05X PDG1XFS05HPX
6 PDG1XFS06 PDG1XFS06HP PDG1XFS06X PDG1XFS06HPX
7 PDG1XFS07 PDG1XFS07HP PDG1XFS07X PDG1XFS07HPX
8 PDG1XFS08 PDG1XFS08HP PDG1XFS08X PDG1XFS08HPX
9 PDG1XFS09 PDG1XFS09HP PDG1XFS09X PDG1XFS09HPX
10 PDG1XFS10 PDG1XFS10HP PDG1XFS10X PDG1XFS10HPX
Flex Shaft Handle Auxiliary Switch
Description Catalog Number
1A/1B, Early Break AUX1EBFSEG
Breaker Catalog Number Digit 17-18 Suffix Catalog NumberVoltage
NEMA 1/12 Black Handle Catalog Number
Metal Handle, NEMA 1/3R/12 Catalog Number
NEMA 1/12 Red Handle Catalog Number
High Performance Handle, NEMA 1/3R/12 Catalog Number
Metal Handle, NEMA 4/4X Catalog Number
Pigtail (29 in / 0.75 m)
24 Vdc UG UVR024DPK
48 Vdc UJ UVR048DPK
60 Vdc UK UVR048DPK
125 Vdc UVR125DPK
250 Vdc UM UVR250DPK
24 Vac UF UVR024APK
48 Vac UVR048APK
60 Vac UVR048APK
125 Vac UVR120APK
240 Vac UB UVR240APK
480 Vac UVR480APK
525 Vac UD UVR600APK
600 Vac UE UVR600APK
Description Catalog Number
Standard lockable handle with mechanism (black and gray) NEMA 1/3R/12/4/4X
Emergency lockable handle with mechanism (red and yellow) NEMA 1/3R/12/4/4X
Mechanism only EHMVDB
12-in (307 mm) handle mechanism shaft PDG12XHMS307
20-in (507 mm) handle mechanism shaft PDG12XHMS507
Standard NFPA79-compliant shaft handle (black and gray) PDG12XHM79S
Emergency NFPA79-compliant shaft handle (red and yellow) PDG12XHM79E
High Performance Handle, NEMA 4/4X Catalog Number
Breaker Catalog Number Digit 17-18 Suffix Catalog NumberVoltage
PDG1XHMDS
PDG1XHMDE
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
Volume 4—Circuit Protection CA08100005E—March 2020 V4-T2-27
2
2
2.2
Molded Case Circuit Breakers
Power Defense Molded Case Circuit Breakers
Accessories—Frame Size 1
2
External Accessories
2
Description Fit Type Catalog Number
Padlockable handle lock, Snap-on Center PDG1XPLKSNAP
2
Padlockable handle lock hasp Top PDG1XPLKT
Padlockable handle lock hasp, OFF only Top PDG1XPLKTOFF
2
Padlockable handle block On handle PDG1XPHB
2
Padlockable handle block, OFF only On handle PDG1XPHBOFF
2
Walking beam interlock Three-pole PDG1XWBI3P
2
Slide bar interlock Field EFSBI
Electrical operator 110–240 Vac/Vdc MOPEG240C
2
2
Plug-in adapter, breaker and base Three-pole PAD3E
2
Plug-in block interlock replacement kit Field PIILEG
Wohner bus bar adapter Field top EG-BUS-T
2
Terminal covers Three-pole PDG1XTC3P
2
2
Interphase barriers 2 barriers PDG1XIB3P
2
DIN Rail Mounting
Description Catalog Number
2
DIN rail adapter; single-pole PDG1XDIN1P
2
Din rail adapter; two-, three- or four-pole PDG1XDIN234P
DIN rail adapter; three- or four-pole PDG1XDIN34P
2
Metal DIN rail adapter, three-pole PDG1XDINM3P
2
Base Mounting Hardware
Description Catalog Number
2
Single-pole metric 8703C80G11
2
Two-, three-, four-pole metric 8703C80G08
Single-pole English 8703C80G12
2
Two-, three-, four-pole English BMHE
Note: Base mounting hardware is included with a circuit breaker or
2
molded case switch.
Right PDG1XPLKROFF
Four-pole PDG1XWBI4P
24/48 Vdc MOPEG48D
Four-pole PAD4E
Field bottom EG-BUS-B
Four-pole PDG1XTC4P
2
Dimensions and Weights—Frame Size 1
Approximate Dimensions in Inches (mm)
Number of Poles Width Height Depth
1 1.0 (25.4) 5.5 (139.7) 2.99 (76.0)
2 2.0 (50.8) 5.5 (139.7) 2.99 (76.0)
3 3.0 (76.2) 5.5 (139.7) 2.99 (76.0)
4 4.0 (101.6) 5.5 (139.7) 2.99 (76.0)
Approximate Shipping Weight in lb (kg)
Breaker Type 1-Pole 2-Pole 3-Pole 4-Pole
PDG1 125 A 0.85 (0.39) 1.57 (0.71) 2.3 (1.04) 2.84 (1.29)
2
2
2
2
2
2
2
V4-T2-28 Volume 4—Circuit Protection CA08100005E—March 2020
Molded Case Circuit Breakers
Power Defense Molded Case Circuit Breakers—Frame Size 2
Power Defense Molded Cas e Circ uit Breakers
2.2
Contents
Description Page
Power Defense Molded Case Circuit Breakers
Power Defense Molded Case Circuit Breakers—Frame Size 2
Product Description
Frame Size 2 covers a range of 15 A through 225 A with a complete offering of trip units, including PXR electronic trip units and fixed-fixed thermal­magnetic trip units.
Application Description
Frame Size 2 can be used to meet a wide range of circuit protection and power distribution needs, including ground fault protection and current limiting options. PXR trip units in PD-2 provide all levels of protection, including energy metering with multiple communication schemes, breaker health indication, and zone selective interlocking with visual indication.
Features and Benefits
Frame Size 2 breakers are available in multiple ratings from 15 A through 225 A. They are configured with a trip unit from the factory. Accessories are modular in design to allow for field installation or factory configuration. PXR trip units are available with advanced features to provide customers unparalleled situational awareness of their electrical system.
Frame Size 1 (15–125 A) . . . . . . . . . . . . . . . . . . . V4-T2-22
Frame Size 2 (15–225 A)
Catalog Number / Product Selection . . . . . . V4-T2-30
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . V4-T2-35
Dimensions and Weights . . . . . . . . . . . . . . . V4-T2-41
Frame Size 3 (45–600 A) . . . . . . . . . . . . . . . . . . . V4-T2-42
Frame Size 4 (300–800 A) . . . . . . . . . . . . . . . . . . V4-T2-57
Frame Size 5 (320–1200 A) . . . . . . . . . . . . . . . . . V4-T2-70
Frame Size 6 (700–2500 A) . . . . . . . . . . . . . . . . . V4-T2-79
Motor Circuit Protectors (3–600 A) . . . . . . . . . . . V4-T2-87
Motor Protection Circuit Breakers (15–600 A). . . V4-T2-98
Terminals, Lugs and Connectors . . . . . . . . . . . . V4-T2-104
Communications and Software . . . . . . . . . . . . . . V4-T2-127
Special Applications. . . . . . . . . . . . . . . . . . . . . . . V4-T2-129
Standards and Certifications
Power Defense breakers are designed and tested to meet stringent requirements for:
l
UL
l
CSA
l
IEC (CE)
l
CB (CCC)
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
Volume 4—Circuit Protection CA08100005E—March 2020 V4-T2-29
Molded Case Circuit Breakers
2.2
Catalog Number / Product Selection
2
Power Defense—Frame Size 2 (15–225 A)
2
Frame Size 2 covers a range of 15 A through 225 A using electronic trip units or thermal-magnetic trip units. It is available in configurations of single-pole, 2-pole, 3-pole and 4-pole.
2
Interrupting Ratings (2-, 3- and 4-Pole)
Catalog Designator
2
ANSI (UL/CSA) kA rms kA rms kA rms kA rms kA rms kA rms
2
240 Vac
480 Vac
2
600 Vac
2
250 Vdc
2
IEC
2
240 Vac 35 35 55 55 85 85 100 100 150 100 200 150
380–415 Vac
2
440 Vac
480 Vac
2
525 Vac
660–690 Vac —8 4 10 510510 5105
2
2
2
2
2
2
2
2
2
2
2
250 Vdc
Interrupting Ratings (Single-Pole)
Catalog Designator
ANSI (UL/CSA)
277 Vac
347 Vac
125 Vdc
IEC
240 Vac 25 25 36 36 50 50 70 70 85 70 100 70
125 Vdc
Notes
1
UL current limiting for 3- and 4-pole breakers.
2
DC ratings available in thermal-magnetic breakers only. 250 Vdc is achieved using 2-poles in series.
3
First rating listed is for thermal-magnetic breakers, second rating is for breakers with PXR electronic trip units.
Power Defense Molded Case Circuit Breakers
F G K
35 65 85 100 150 200
25 35 50 65 85 100
14 18 22 25 30 / 25
10 10 10 22 22 22
l
cu
25 25 36 36 50 50 70 53 70 70 100 70
25 20 30 22.5 35 35 50 40 70 50 100 65
20 20 25 20 35 22.5 50 30 65 40 65 40
18 15 / 13 320 15 / 13 330 / 25 315 / 13 330 / 25 315 / 13 330 / 25 315 / 13 335 / 25 318 / 13
10 10 10 10 10 10 22 22 22 22 22 22
F G K M N P
kA rms kA rms kA rms kA rms kA rms kA rms
25 35 50 65 85 100
14 18 22 25 30 35
10 10 10 22 22 22
l
cu
10 10 10 10 10 10 22 22 22 22 22 22
l
cs
l
cs
l
cu
l
cu
l
cs
l
cs
1
l
cu
l
cu
l
cs
l
cs
1
M
l
cu
l
cu
l
cs
l
cs
1
N
3
l
cu
l
cu
l
cs
l
cs
1
P
35 / 25
l
cu
l
cu
3
l
cs
3
l
cs
2
2
2
2
2
2
2
2
2
2
V4-T2-30 Volume 4—Circuit Protection CA08100005E—March 2020
Molded Case Circuit Breakers
Frame
Size
2 =2
Pole
Options
1 = 1-pole
Interrupting
Ratings
F = 25 kA at 277 V G = 35 kA at 277 V K = 50 kA at 277 V M= 65 kA at 277 V N =
85 kA at 277 V
1
P = 100 kA at
277 V
1
F = 14 kA at 347 V G = 18 kA at 347 V K = 22 kA at 347 V M= 25 kA at 347 V N =
30 kA at
347
V
1
P =
35 kA at
347
V
1
Trip Unit
Type Options
TFF = Fixed thermal /
Fixed magnetic
VFF = 50 °C Fixed thermal /
Fixed magnetic (non UL)
Standard Terminal
Options
N = No terminals J = Line and load terminals K = Line only terminals L = Load only terminals
Continuous
Current Ratings
0015 = 15 A 0020 = 20 A 0025 = 25 A 0030 = 30 A 0035 = 35 A 0040 = 40 A 0045 = 45 A 0050 = 50 A 0060 = 60 A 0070 = 70 A 0080 = 80 A 0090 = 90 A 0100 = 100 A 0110 = 110 A 0125 = 125 A 0150 = 150 A
Product Series
PD = Power Defense
2 =2 2 = 2-pole
3 = 3-pole 4 = 4-pole (100% N) 0 = 4-pole (0% N) 6 = 4-pole (60% N)
F = 25 kA at 480 V G = 35 kA at 480 V K = 50 kA at 480 V M= 65 kA at 480 V N = 85 kA at 480 V P = 100 kA at 480 V
F = 14 kA at 600 V G = 18 kA at 600 V K = 22 kA at 600 V M= 25 kA at 600 V N = 30 kA at 600 V P = 35 kA at 600 V
TFF = Fixed thermal /
Fixed magnetic
VFF = 50 °C Fixed thermal /
Fixed magnetic (non UL)
N = No terminals J = Line and load terminals K = Line only terminals L = Load only terminals
0015 = 15 A 0020 = 20 A 0025 = 25 A 0030 = 30 A 0035 = 35 A 0040 = 40 A 0045 = 45 A 0050 = 50 A 0060 = 60 A 0070 = 70 A 0080 = 80 A 0090 = 90 A 0100 = 100 A 0110 = 110 A 0125 = 125 A 0150 = 150 A 0175 = 175 A 0200 = 200 A 0225 = 225 A
PD
PD G 2 1 M 0150 TFF J
Certifications/
Standards
G = UL/CSA/IEC/CCC
Molded Case Circuit Breakers (Two-, Three- and Four-Pole) with Thermal-Magnetic Trip Units—Globally Rated
G = UL/CSA/IEC/CCC
Power Defense Molded Cas e Circ uit Breakers
2.2
Power Defense—Frame Size 2 (15–225 A)
This information is presented as a tool to develop catalog numbers for selecting Power Defense circuit breakers and trip units.
Molded Case Circuit Breakers (Single-Pole) with Thermal-Magnetic Trip Units (TMTU)—Globally Rated
2
2
2
2
2
2
2
2
2
2
2
2
2
2
Note
1
N and P ratings available for 15–30 A on single-pole breakers.
Volume 4—Circuit Protection CA08100005E—March 2020 V4-T2-31
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
Molded Case Circuit Breakers
Frame
Size
2 =2
Pole
Options
2 = 2-pole 3 = 3-pole
Interrupting
Ratings
F = 35 kA at 240 V G = 65 kA at 240 V K = 85 kA at 240 V M= 100 kA at 240 V N = 150 kA at 240 V P = 200 kA at 240 V
Trip Unit
Type Options
TFF = Fixed thermal /
Fixed magnetic
VFF = 50 °C Fixed thermal /
Fixed magnetic (non UL)
Standard Terminal
Options
N = No terminals J = Line and load terminals K = Line only terminals L = Load only terminals
Continuous
Current Ratings
0015 = 15 A 0020 = 20 A 0025 = 25 A 0030 = 30 A 0035 = 35 A 0040 = 40 A 0045 = 45 A 0050 = 50 A 0060 = 60 A 0070 = 70 A 0080 = 80 A 0090 = 90 A 0100 = 100 A 0110 = 110 A 0125 = 125 A 0150 = 150 A 0175 = 175 A 0200 = 200 A 0225 = 225 A
Product Series
PD = Power Defense
2 =2 2 = 2-pole
3 = 3-pole 4 = 4-pole
G = 35 kA at 480 V M= 65 kA at 480 V
G = 18 kA at 600 V M= 35 kA at 600 V
KNS = Molded Case Switch N = No terminals
J = Line and load terminals K = Line only terminals L = Load only terminals
0100 = 100 A 0150 = 150 A 0225 = 225 A
PD
PD D 2 3 M 0225 TFF J
Certifications/
Standards
D = UL/CSA
Molded Case Switches—Globally Rated
1
G = UL/CSA/IEC/CCC
2 =2 3 = 3-pole
4 = 4-pole
(programmable N)
F = 25 kA at 480 V G = 35 kA at 480 V K = 50 kA at 480 V M= 65 kA at 480 V N = 85 kA at 480 V P = 100 kA at 480 V
F = 14 kA at 600 V G = 18 kA at 600 V K = 22 kA at 600 V M= 25 kA at 600 V N = 25 kA at 600 V P = 25 kA at 600 V
B2N =PXR 10 LSI E##
2
=PXR 20
D##
2
=PXR 20D
P##
2
=PXR 25
N = No terminals J = Line and load terminals K = Line only terminals L = Load only terminals
0060 = 60 A 0100 = 100 A 0150 = 150 A 0225 = 225 A
PD
Molded Case Circuit Breakers with Power Xpert Release Electronic Trip Units (ETU)—Globally Rated
G = UL/CSA/IEC/CCC
2 =2 3 = 3-pole
4 = 4-pole
F = 25 kA at 480 V G = 35 kA at 480 V K = 50 kA at 480 V M= 65 kA at 480 V N = 85 kA at 480 V P = 100 kA at 480 V
F = 14 kA at 600 V G = 18 kA at 600 V K = 22 kA at 600 V M= 25 kA at 600 V N = 25 kA at 600 V P = 25 kA at 600 V
B2N = PXR 10 LSI E##
2
=PXR 20
D##
2
=PXR 20D
P##
2
=PXR 25
J = Line and load terminals W= Optional line and load
terminals
0060 =60 A 0100 =100 A 0150 =150 A 0225 =225 A
PD
Molded Case Circuit Breakers with Power Xpert Release Electronic Trip Units (ETU)—100% UL Rated
F = UL/CSA/IEC/CCC
(100% UL Rated)
2.2
Power Defense—Frame Size 2 (15–225 A)
2
This information is presented as a tool to develop catalog numbers for selecting Power Defense circuit breakers and trip units.
2
Molded Case Circuit Breakers with TMTU—UL/CSA Rated to 240 Vac
2
2
2
2
2
Power Defense Molded Case Circuit Breakers
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
Notes
1
Molded case switch may open above 1800 A.
2
See tables and descriptions on Page V4-T2-33 for protection type (#
V4-T2-32 Volume 4—Circuit Protection CA08100005E—March 2020
) and available configured options (#
(1)
).
(2)
Molded Case Circuit Breakers
Power Defense Molded Cas e Circ uit Breakers
2.2
Power Xpert Release (PXR) Trip Unit Options—Frame Size 2
Power Xpert Release (PXR) Trip Unit Options
#
PXR ETU
PXR 10 B
PXR 20 E
PXR 20D D
PXR 25 P
—Protection Type #
(1)
LSI LSIG
2 N ————————
2 NRMZ C WX ——
3 RMZCWX——
23 ——M ——W DY
23 ——M ——W DY
—Available Configured Options
(2)
— — — —
Relays — — —
Description of PXR Configured Options
1
Relays
—Form A contacts
(rated for 240 Vac, 1 A)
l
2 available if Modbus RTU is not used; 1 available when used in conjunction with Modbus RTU
l
Interface: 3 wires (ALM1, ALM2, ALM Common)
l
Programmable to indicate breaker conditions
l
Available as field-installable option if not pre-configured (catalog number PDG2XRELAYS)
2
Modbus 1—Modbus RTU directly from breaker
l
Interface: 3 wires (MODBA, MODBB, MODBG)
l
No additional modules required
l
Available as field-installable option if not pre-configured (catalog number
PDG2XMODRTUREL)
ZSI—Zone Selective
Interlocking
l
Includes ability to turn ON and OFF
l
Interface: 3 wires (Zin, Zout, Zcomm)
l
No additional modules required
Relays Modbus — —
2
Relays — ZSI —
Relays — — CAM
Relays Modbus ZSI —
CAM—CAM Link Connection (requires a CAM module per breaker)
l
Interface: 5 wires (refer to CAM IL for details)
l
Communications Adapter Modules available for Modbus TCP and PROFIBUS
Relays — ZSI CAM
Relays Modbus — CAM
Auxiliary Power
l
Connection included with all PXR 20, 20D and 25 trip units
l
Required for communications, relays and metering accuracy
l
24 Vdc, 0.5 A
l
Interface: 2 wires (Aux +24 V, Aux 0 V)
Relays Modbus ZSI CAM
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
Available Continuous Current (l
Option Setting
PXR 10, PXR 20 1 15 A 32 A 50 A 80 A
2 16 A 35 A 60 A 90 A
3 20 A 40 A 63 A 100 A
4 25 A 50 A 70 A 110 A
5 30 A 60 A 80 A 125 A
6 35 A 63 A 90 A 150 A
7 40 A 70 A 100 A 160 A
8 45 A 80 A 110 A 175 A
9 50 A 90 A 125 A 200 A
10 = l
n
PXR 20D, PXR 25 Programmable from minimum to maximum values in 1 A increments.
Notes
1
Relays and/or Modbus RTU in PD-2 uses accessory pocket, therefore UVR and shunt trip use is not possible.
2
PD-2 can only be equipped with one field-installable communication option (PDG2XMODRTUREL or PDG2XRELAYS).
) Settings on PXR Electronic Trip Units
r
Catalog Number Selection and Maximum Setting (ln) 0060
60 A
60 A 100 A 150 A 225 A
0100
100 A
0150
150 A
0225
225 A
2
2
2
2
2
2
2
2
2
2
2
2
2
Volume 4—Circuit Protection CA08100005E—March 2020 V4-T2-33
Molded Case Circuit Breakers
Screw
Washer
Collar
Conductor
Nut
Conductor
Extrusion
Clip
Collar
Conductor
Collar
Washer
Screw
Screw
Wire Clamp
Conductor
Control Wire Tabs
Use
Package Qty.
Catalog Number
15–150 A 12 FCWTK
175–225 A 12 FCWTK225
2.2
Terminals—Frame Size 2
2
Catalog numbers shown are for a single side of a 3-pole breaker. For 2- and 4-pole options, replace the X3 with X2 or X4, respectively.
2
Example: PDG2X3T100 becomes PDG2X2T100 for 2-pole
Te r m i n a l T y p e s
2
2
Power Defense Molded Case Circuit Breakers
2
2
2
PDG2X3T100 PDG2X3T150
2
Note: Pictures are for reference only.
2
Te r m i n a l s
Maximum
2
Breaker Amperes
2
Standard Terminals
100 15–100 Steel Cu/Al B, C 1 14–1/0 2.08–53.5 PDG2X3T100
2
225 60–225 Aluminum Cu/Al B, C 1 4–4/0 21.2 —107 PDG2X3TA225
2
Alternate Terminals
50 15–50 Aluminum Cu/Al B, C 1 14–4 2.08–21.2 PDG2X3TA50 T U V 15–50
2
100 60–100 Aluminum Cu/Al B, C 1 14–1/0 2.08–53.5 PDG2X3TA100 T U V 60–100
150 60–150 Aluminum Cu/Al B, C 1 14–4/0 2.08–107 PDG2X3TA150 T U V 110–150
2
225 175–225 Aluminum Cu/Al B, C 1 6–300 13.3–152 PDG2X3TA225K
Non-standard Terminals
2
100 15–100 Steel Cu/Al B, C 1 14–1/0 2.08–53.5 PDG2X3T100
2
150 60–150 Stainless
2
225 60–225 Copper Cu B, C 1 4–4/0 21.2 —107 PDG2X3T225 W Y Z 175–225
Multi-wire Terminals
2
225 150–225 Aluminum Cu/Al B, C 6 14–6 2.08–13.3 PDG2X3TA2256W Terminal shield G 15–225
225 150–225 Aluminum Cu/Al B, C 3 14–2 2.08–33.6 PDG2X3TA2253W Terminal shield H 15–225
2
Rear Fed Terminals
150 60–150 Aluminum Cu/Al B, C 1 14–4/0 2.08–107 PDG2X3TA150RF Terminal shield 15–150
2
225 60–225 Aluminum Cu/Al B, C 1 6–300 13.3–152 PDG2X3TA225RF Terminal shield 175–225
2
Box Terminal
20 15–20 Steel Cu/Al B, C 1 14–10 2.08–5.26 PDG2X3T20 15–20
2
Rear Connectors
225 PDG2X3T225RC R 15–25
2
End Cap Kits/Screw Terminals
225 PDG2X3TS225 S D E 15–25
2
Note: Wire capacity is based on standard imperial wire sizes; metric sizes provided in table
2
are a direct conversion to demonstrate maximum capacity, not to denote metric wire sizes.
Notes
1
2
2
2
2
The “Breaker Frame” column provides information on the ampere ratings for which the terminal may be used (field installation); in some cases the range is limited by proper fit of the terminal onto the breaker conductor. The column “Standard on Amperes” provides information on what terminal is used during factory configuration per Digit 14 of the breaker catalog number. The two may not match.
2
Factory standard terminals and non-aluminum terminals for 100 A and below are the same terminals.
3
PDF2 225 A breakers with Digit 14 designation of “J” are equipped with PDG2X3TA225K terminals. PDF2 150 A breakers with Digit 14 designation of “J” are equipped with PDG2X3TA225 terminals.
4
Breaker loses UL when fitted with rear-fed terminals or rear connectors.
PDG2X3TA225 PDG2X3TA150 PDG2X3T225
1
4
Terminal Body Type
Steel
4
Breaker Frame
Collar
Wire Class
Washer
Screw
Number of Conductors per Phase
AWG/kcmil Range per Conductor
Metric (mm Range per Conductor
PDG2X3TA2253W
2
)
3-Pole Catalog Number
PDG2X3TA150RF PDG2X3TA225RF
Included Accessories
2
3
3
Terminal shield T U V 175–225
2
PDG2X3T20 PDG2X3TS225
Digit 14 Designation Line and
Load
J K L 15–100
J K L 110–225
W Y Z 15–100
Line Only
Conductor
PDG2X3TA50 PDG2X3TA100 PDG2X3TA225K PDG2X3TA2256W
Wire Typ e
Cu B, C 1 4–4/0 21.2 —107 PDG2X3T150 W Y Z 110–150
Load Only
Standard on Amperes
V4-T2-34 Volume 4—Circuit Protection CA08100005E—March 2020
Molded Case Circuit Breakers
Power Defense Molded Cas e Circ uit Breakers
2.2
Accessories
Internal Accessory Configurations—Frame Size 2
Thermal-Magnetic Circuit Breakers
3-Pole Circuit Breakers 4-Pole Circuit Breakers
Tripping Accessory Options
None None None None None None
Shunt Trip 1NO (1 space) 1NO (1 space) Shunt Trip 1NO (1 space) 1NO (1 space)
UVR 2NC (2 spaces) 2NC (2 spaces) UVR 2NC (2 spaces) 2NC (2 spaces)
Electronic Circuit Breakers
3-Pole Circuit Breakers 4-Pole Circuit Breakers
Alarm (2 Spaces) Options
1NC (1 space) 1NC (1 space) 1NC (1 space) 1NC (1 space)
1NO/1NC (2 spaces) 1NO/1NC (2 spaces) 1NO/1NC (2 spaces) 1NO/1NC (2 spaces)
2NO (2 spaces) 2NO (2 spaces) 2NO (2 spaces) 2NO (2 spaces)
Aux (2 Spaces) Options
12
Tripping Accessory Options
Alarm (2 Spaces) Options
Aux (4 Spaces) Options
2CO (4 spaces)
4NO (4 spaces)
4NC (4 spaces)
2
2
2
2
2
2
2
2
2
2
2
2
2
2
Tripping Accessory Options
None None 1NO/1NC
Shunt Trip Shunt Trip 1NO/1NC
UVR UVR 1NO/1NC
Bell alarm (1NO/1NC–Form C)
Qty: 1 Programmable relay with Modbus RTU
Qty: 2 Programmable relays Qty: 2 Programmable relays
Notes
1
2-pole PD-2 breakers have an accessory pocket compatible with indicating accessory options only.
2
Single-pole PD-2 breakers may be equipped with a Form C bell alarm as a factory installation only. Use “BC” as a suffix code in digits 15–16.
3
Qty: 1 1NO/1NC (Form C) auxiliary contact is automatically factory installed for all Frame 2 Power Defense breakers with electronic trip units.
Alarm Options
Aux Options
Tripping Accessory Options
3
None None 1NO/1NC
Bell alarm (1NO/1NC–Form C)
Qty: 1 Programmable relay with Modbus RTU
Alarm
Options
Aux (2 Spaces) Options
1NO/1NC
1NO/1NC
1NO/1NC
3
3
+ 1NO (1 space)
3
+ 1NC (1 space)
3
+ 1NO/1NC (2 spaces)
3
+ 2NO (2 spaces)
3
+ 2NC (2 spaces)
2
2
2
2
2
2
2
2
2
2
2
2
2
2
Volume 4—Circuit Protection CA08100005E—March 2020 V4-T2-35
2
2
Molded Case Circuit Breakers
2.2
Alarm and Auxiliary Contact Blocks—Frame Size 2
2
Power Defense breakers have designated positions for
2
alarm and auxiliary switches in the right-pole accessory cavity. For Frame 2, the two
2
left-most positions are used for alarm switches, and the
2
two right-most locations are used for auxiliary switches.
2
2
2
Pigtail (29 in / 0.75 m) Contact Blocks for Alarm and Auxiliary Switch Functionality
2
Catalog Number PDGXAA PDGXAB PDGXAC
Typ e Form A / NO Form B / NC Form C / NO-NC
2
2
Screw Terminal Contact Blocks for Alarm and Auxiliary Switch Functionality
Catalog Number PDGXXA PDGXXB PDGXXA + PDGXXB
2
Typ e Form A / NO Form B / NC For NO-NC, use two separate
2
Power Defense Molded Case Circuit Breakers
Power Defense breakers have secondary covers for ease of field installation of accessories, including alarm and auxiliary switches.
contact blocks
Power Defense alarm and auxiliary switches are available in contact blocks, in Form A (NO), Form B (NC) and Form C (NO-NC) types. Form A and Form B contacts take one position in the breaker accessory cavity, and Form C contacts take two positions in the cavity. Identical contact blocks are used for the alarm and auxiliary switch functions.
Frame 2 breakers with electronic trip units are automatically configured with a factory-installed Form C auxiliary contact block because the right-pole accessory cavity is not available for field modification. Trip position can also be communicated via communications and the PXR programmable relays.
2
Push-In Clamp Contact Blocks for Alarm and Auxiliary Switch Functionality
2
Catalog Number PDGXUA PDGXUB PDGXUC
Typ e Form A / NO Form B / NC Form C / NO-NC
2
2
Pigtail (118 in / 3.0 m) Contact Blocks for Alarm and Auxiliary Switch Functionality
Catalog Number PDGXDA PDGXDB PDGXDC
2
Typ e Form A / NO Form B / NC Form C / NO-NC
2
Alarm Switch for Use with PXR Electronic Trip Units
2
Catalog Number PDG2XALMBC PDG2XALMEC
2
Typ e Form C / NO-NC Form C / NO-NC
Termination 0.75 m pigtail 3.0 m pigtail
2
Note
1
2
2
Frame 2 breakers with electronic trip units do not allow access to the right accessory pocket but are automatically configured with a factory installed Form C / NO-NC auxiliary switch. These alarm switches can be field or factory installed in the left accessory pocket in place of a shunt trip or UVR.
1
2
2
2
2
2
2
2
V4-T2-36 Volume 4—Circuit Protection CA08100005E—March 2020
Molded Case Circuit Breakers
Power Defense Molded Cas e Circ uit Breakers
2.2
Factory Installation of Alarm and Auxiliary Switches—Frame Size 2
Alarm and auxiliary switches are plug-and-play accessories designed to be field installable. However, Eaton also offers installation service in our factories.
Breaker catalog numbers with alarm and auxiliary switch combinations require a complete 20-digit catalog number, adding the alarm and auxiliary switch functionality in digits 15–16 and adhering to the following conditions and tables:
l
Digit 15 denotes the type of accessory(-ies) installed and the terminal types
Pigtails—29 in / 0.75 m (A, B, C)
Alarm Switch None
1NO
1NC
1
1NO/1NC
2NO
2NC
l
Switches may be requested for alarm only, auxiliary only or a combination of the two
l
Digit 16 denotes the number and type (NO, NC) of switches installed
l
For Eaton factory installation, the same type of terminals (i.e. all pigtail
0.75 m, all screw, etc.) and same style of contact block (i.e., all 1NO/1NC, all 2NC, etc.) must be used in a factory configuration
Auxiliary Switch Three-Pole Four-Pole None 1NO 1NC 1NO/1NC 2NO 2NC 2NO/2NC 4NO 4NC
NN AA AB AC AD AE A1 A2 A3
BA CA
BB CB
BC CC C1
BD CD C2
BE CE C3
l
If no other accessories are selected, use NNNN for the final 4 digits of the catalog number
l
Frame 2 breakers with electronic trip units do not allow access to the right accessory pocket but are automatically configured with a factory installed 1NO/1NC auxiliary switch. A bell alarm accessory is available for separate installation in the left accessory pocket.
Note: Though factory configuration options are limited, combinations of auxiliary switches and alarms using differing terminals and contact block styles are still available through field installation. Please see full auxiliary switch and alarm catalog numbers to order.
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
Screw Terminals (X, Y, Z)
Auxiliary Switch Three-Pole Four-Pole None 1NO 1NC 1NO/1NC 2NO 2NC 2NO/2NC 4NO 4NC
Alarm Switch None
1NO
1NC
1NO/1NC
2NO
2NC
Push-In Clamps (U, V, W)
Alarm Switch None
1NO
1NC
1NO/1NC
2NO
2NC
Note
1
Single-pole breakers can be equipped with a 1NO/1NC alarm switch that must be factory installed; use suffix BC in digits 15–16. No other internal accessories are available for single-pole breakers.
NN XA XB XC XD XE X1 X2 X3
YA ZA
YB ZB
YC ZC Z1
YD ZD Z2
YE ZE Z3
Auxiliary Switch Three-Pole Four-Pole None 1NO 1NC 1NO/1NC 2NO 2NC 2NO/2NC 4NO 4NC
NN UA UB UC UD UE U1 U2 U3
VA WA
VB WB
VC WC W1
VD WD W2
VE WE W3
2
2
2
2
2
2
2
2
2
2
2
2
2
2
Volume 4—Circuit Protection CA08100005E—March 2020 V4-T2-37
2
Molded Case Circuit Breakers
2.2
Pigtails—118 in / 3.0 m (D, E, F)
2
2
Alarm Switch None
2
2
2
2
Factory Installation of Alarm Switch for Use with PXR Electronic Trip Units
2
Pigtails—29 in / 0.75 m Pigtails—118 in / 3.0 m
2
2
Auxiliary switch None NN
2
2
Tripping Accessories—Frame Size 2
2
Power Defense breakers have designated positions for shunt trips and undervoltage releases (UVRs) in the left pole accessory cavity. Each breaker has space for one tripping accessory only.
2
Power Defense breaker have secondary covers for ease of field installation of tripping accessories.
Shunt Trips
2
Voltage Screw Terminals Pigtail (29 in / 0.75 m) Pigtail (118 in / 3.0 m)
2
12 Vdc PDG2XST12DCT PDG2XST12DCS PDG2XST12DCR
48 Vdc PDG2XST48DCT PDG2XST48DCS PDG2XST48DCR
2
60 Vdc PDG2XST60DCT PDG2XST60DCS PDG2XST60DCR
24 Vac/Vdc PDG2XST24ACDCT PDG2XST24ACDCS PDG2XST24ACDCR
2
110-130 Vac/125 Vdc PDG2XST130ACDCT PDG2XST130ACDCS PDG2XST130ACDCR
2
200-240 Vac/250 Vdc PDG2XST250ACDCT PDG2XST250ACDCS PDG2XST250ACDCR
380-440 Vac PDG2XST440ACT PDG2XST440ACS PDG2XST440ACR
2
480-525 Vac PDG2XST525ACT PDG2XST525ACS PDG2XST525ACR
600 Vac PDG2XST600ACT PDG2XST600ACS PDG2XST600ACR
2
Power Defense Molded Case Circuit Breakers
Auxiliary Switch Three-Pole Four-Pole None 1NO 1NC 1NO/1NC 2NO 2NC 2NO/2NC 4NO 4NC
NN DA DB DC DD DE D1 D2 D3
1NO
1NC
1NO/1NC
2NO
2NC
1NO/1NC CC
EA FA
EB FB
EC FC F1
ED FD F2
EE FE F3
Auxiliary Switch Three-Pole None 1NO/1NC
1
AC
1
Alarm switch None NN
Auxiliary Switch Three-Pole None 1NO/1NC
1
1NO/1NC FC
DC
Undervoltage Releases (UVRs)
2
Voltage Screw Terminals Pigtail (29 in / 0.75 m) Pigtail (118 in / 3.0 m)
2
12 Vdc PDG2XUV12DCV PDG2XUV12DCU PDG2XUV12DCW
24 Vdc PDG2XUV24DCV PDG2XUV24DCU PDG2XUV24DCW
2
48 Vdc PDG2XUV48DCV PDG2XUV48DCU PDG2XUV48DCW
60 Vdc PDG2XUV60DCV PDG2XUV60DCU PDG2XUV60DCW
2
125 Vdc PDG2XUV125DCV PDG2XUV125DCU PDG2XUV125DCW
250 Vdc PDG2XUV250DCV PDG2XUV250DCU PDG2XUV250DCW
2
24 Vac PDG2XUV24ACV PDG2XUV24ACU PDG2XUV24ACW
2
130 Vac PDG2XUV130ACV PDG2XUV130ACU PDG2XUV130ACW
240 Vac PDG2XUV240ACV PDG2XUV240ACU PDG2XUV240ACW
2
440 Vac PDG2XUV440ACV PDG2XUV440ACU PDG2XUV440ACW
525 Vac PDG2XUV525ACV PDG2XUV525ACU PDG2XUV525ACW
2
600 Vac PDG2XUV600ACV PDG2XUV600ACU PDG2XUV600ACW
2
Note
1
1NO/1NC (AC) is always included in breakers with PXR trip units;
2
no selection or selection of NN in Digits 15–16 will result in AC.
V4-T2-38 Volume 4—Circuit Protection CA08100005E—March 2020
Molded Case Circuit Breakers
Power Defense Molded Cas e Circ uit Breakers
2.2
Factory Installed Tripping Accessories—Frame Size 2
Shunt trips and under voltage releases (UVRs) are plug-and­play accessories designed to be field installable. However, Eaton also offers the service of installation in our factories.
Shunt Trips
Voltage Screw Terminals Pigtail (29 in / 0.75 m) Pigtail (118 in / 3.0 m)
12 Vdc TH SH RH
48 Vdc TJ SJ RJ
60 Vdc TK SK RK
24 Vac/Vdc TN SN RN
110–130 Vac/125 Vdc TP SP RP
200–240 Vac/250 Vdc TR SR RR
380–440 Vac TC SC RC
480–525 Vac TD SD RD
600 Vac TE SE RE
Undervoltage Releases (UVRs)
Voltage Screw Terminals Pigtail (29 in / 0.75 m) Pigtail (118 in / 3.0 m)
12 Vdc VH UH WH
24 Vdc VG UG WG
48 Vdc VJ UJ WJ
60 Vdc VK UK WK
125 Vdc VL UL WL
250 Vdc VM UM WM
24 Vac VF UF WF
130 Vac VA UA WA
240 Vac VB UB WB
440 Vac VC UC WC
525 Vac VD UD WD
600 Vac VE UE WE
Note: Use suffix US for 18 Vdc when using Time Delay UVR.
Breaker catalog numbers with shunt trips or UVRs require a complete 20-digit catalog number, adding the tripping accessory functionality in digits 17 and 18 and adhering to the following conditions and tables.
l
Digit 17 denotes the type of accessory installed and the terminal type
l
Digit 18 denotes the voltage of the accessory
l
If no accessories are selected, use NNNN for the final 4 digits of the catalog number
l
Each breaker has space for one shunt trip or UVR tripping accessory only
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
Volume 4—Circuit Protection CA08100005E—March 2020 V4-T2-39
2
2
2
2
2
2
2
2
Molded Case Circuit Breakers
2.2
Handle Mechanisms—Frame Size 2
2
Direct Rotary Handle Mechanism
2
Description
2
Standard lockable handle and mechanism PDG2XHMCS HA
Standard lockable handle and mechanism with door interlock PDG2XHMCSN HB
2
Standard lockable handle and mechanism with mechanical padlock PDG2XHMCSP HC
Standard lockable handle and mechanism with door interlock and
2
mechanical padlock
Emergency lockable handle and mechanism PDG2XHMCE H1
2
Emergency lockable handle and mechanism with door interlock PDG2XHMCEN H2
Emergency lockable handle and mechanism with mechanical padlock PDG2XHMCEP H3
2
Emergency lockable handle and mechanism with door interlock and mechanical padlock
2
2
Variable Depth Rotary Handle Mechanism 1
2
Description
Standard lockable handle and mechanism PDG2XHMDS DA
2
Standard lockable handle and mechanism with mechanical padlock PDG2XHMDSP DC
Emergency lockable handle and mechanism PDG2XHMDE D1
2
Emergency lockable handle and mechanism with mechanical padlock PDG2XHMDEP D3
2
12 in (307 mm) handle mechanism shaft PDG12XHMS307
20 in (507 mm) handle mechanism shaft PDG12XHMS507
2
Standard NFPA79-compliant shaft handle PDG12XHM79S
Emergency NFPA79-compliant shaft handle PDG12XHM79E
2
Power Defense Molded Case Circuit Breakers
1
NEMA 1/12 Catalog Number
PDG2XHMCSNP HE
PDG2XHMCENP H5
NEMA 1/3R/12/4/4X Catalog Number
Factory Installed Digits 19–20
Factory Installed Digits 19–20
2
Flex Shaft Handle Mechanism
Metal Handle,
2
Cable Length (ft)
2 PDG2XFS02 PDG2XFS02HP PDG2XFS02X PDG2XFS02HPX
2
3 PDG2XFS03 PDG2XFS03HP PDG2XFS03X PDG2XFS03HPX
2
4 PDG2XFS04 PDG2XFS04HP PDG2XFS04X PDG2XFS04HPX
5 PDG2XFS05 PDG2XFS05HP PDG2XFS05X PDG2XFS05HPX
2
6 PDG2XFS06 PDG2XFS06HP PDG2XFS06X PDG2XFS06HPX
7 PDG2XFS07 PDG2XFS07HP PDG2XFS07X PDG2XFS07HPX
2
8 PDG2XFS08 PDG2XFS08HP PDG2XFS08X PDG2XFS08HPX
2
9 PDG2XFS09 PDG2XFS09HP PDG2XFS09X PDG2XFS09HPX
10 PDG2XFS10 PDG2XFS10HP PDG2XFS10X PDG2XFS10HPX
2
Note
1
2
Standard handles are black and gray; Emergency handles are red and yellow.
NEMA 1/3R/12 Catalog Number
High Performance Handle, NEMA 1/3R/12 Catalog Number
Metal Handle, NEMA 4/4X Catalog Number
2
2
2
2
2
High Performance Handle, NEMA 4/4X Catalog Number
2
V4-T2-40 Volume 4—Circuit Protection CA08100005E—March 2020
Molded Case Circuit Breakers
Power Defense Molded Cas e Circ uit Breakers
2.2
Accessories—Frame Size 2
External Accessories
Description Fit Type Catalog Number
Padlockable hasp Top PDG2XPLKT L4
Left side PDG2XPLKL L5
Right side PDG2XPLKR L6
Snap on PDG2XPLKSNAP L0
Padlockable hasp OFF only Top PDG2XPLKTOFF L1
Left side PDG2XPLKLOFF L2
Right side PDG2XPLKROFF L3
Padlockable handle block On handle PDG2XPHB
1
Kirk lock provision
Walking beam interlock
23
Electrical operator 24 Vdc PDG2XROP24DC RG
Plug-in breaker base only Three-pole PDG2XPIBB3P225A
Plug-in breaker parts kit Three-pole PDG2XPIBK3P225A
Terminal covers Two-pole PDG2XTC2P
Interphase barriers Single-pole PDG2XIB
Finger protection Three-pole PDG2XFP3P
60A–100 A residual current neutral sensor
150A–225 A residual current neutral sensor
60A–100 A residual current neutral sensor
150A–225 A residual current neutral sensor
Service entrance barrier kit
Top PDG2XKLKPTFF L7
Two-, three-, and four-pole
48–60 Vdc PDG2XROP60DC RJ or RK
125 Vdc PDG2XROP125DC RL
250 Vdc PDG2XROP250DC RM
110–130 Vac PDG2XROP130AC RA
200–240 Vac PDG2XROP240AC RB
380–440 Vac PDG2XROP440AC RC
Four-pole PDG2XPIBB4P225A
Four-pole PDG2XPIBK4P225A
Three-pole PDG2XTC3P
Four-pole PDG2XTC4P
Three-pole PDG2XIB3P
Four-pole PDG2XIB4P
Four-pole PDG2XFP4P
Cable type PDG2XNCTD0100
Cable type PDG2XNCTD0225
Bus bar type PDG2XNCTB0100
Bus bar type PDG2XNCTB0225
Three-pole PRLSEBPD2
PDG2XWBI234P
Factory Installed Digits 19–20
Base Mounting Hardware
Description Catalog Number
Single-pole metric 4218B80G09
Two -pol e me tri c 4218B80G11
Three-, four-pole metric BMH1M
Single-pole English 624B375G01
Two-pole English 4218B80G01
Three-, four-pole English BMH1
Note: Base mounting hardware is included with a circuit breaker or molded case switch.
Dimensions and Weights—Frame Size 2
Approximate Dimensions in Inches (mm)
Number of Poles Width Height Depth
1 1.38 (35.1) 6.00 (152.4) 3.50 (88.9)
2 2.75 (69.9) 6.00 (152.4) 3.50 (88.9)
3 4.12 (104.6) 6.00 (152.4) 3.50 (88.9)
4 5.49 (139.5) 6.00 (152.4) 3.50 (88.9)
Approximate Shipping Weight in lb (kg)
Breaker Type 1-Pole 2-Pole 3-Pole 4-Pole
PDG2 225 A 2.00 (0.91) 3.00 (1.36) 4.21 (1.82) 5.69 (2.46)
Notes
1
Provision only. For use with Type FF Kirk keylock (sold separately). Bolt projection in withdrawn position is 0 in (0 mm).
2
Breaker must be ordered with walking beam interlock ready modification from plant (factory suffix WB).
3
Requires two breakers.
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
Volume 4—Circuit Protection CA08100005E—March 2020 V4-T2-41
2
2
2
2
2
2.2
Power Defense Molded Case Circuit Breakers—Frame Size 3
Molded Case Circuit Breakers
Power Defense Molded Case Circuit Breakers
2
2
2
2
2
2
2
2
2
2
2
Power Defense Molded Case Circuit Breakers—Frame Size 3
Product Description
2
Frame Size 3 covers a range of 45 A through 600 A with a
2
complete offering of trip units, including PXR
2
electronic trip units and fixed­adjustable thermal-magnetic
2
trip units. PD-3 is available in two versions, with 400 A and
2
600 A constructions to optimize performance in multiple applications.
2
2
2
Application Description
Frame Size 3 can be used to meet a wide range of circuit protection and power distribution needs, including ground fault protection, current limiting, 100% UL ratings, and high instantaneous settings for selective coordination. PXR trip units in PD-3 provide all levels of protection, including energy metering with multiple communication schemes, breaker health indication, and arc flash reduction options.
Contents
Power Defense Molded Case Circuit Breakers
Frame Size 1 (15–125 A) . . . . . . . . . . . . . . . . . . . . V4-T2-22
Frame Size 2 (15–225 A) . . . . . . . . . . . . . . . . . . . . V4-T2-29
Frame Size 3 (45–600 A)
Catalog Number / Product Selection . . . . . . V4-T2-43
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . V4-T2-51
Dimensions and Weights. . . . . . . . . . . . . . . V4-T2-56
Frame Size 4 (300–800 A) . . . . . . . . . . . . . . . . . . . V4-T2-57
Frame Size 5 (320–1200 A) . . . . . . . . . . . . . . . . . . V4-T2-70
Frame Size 6 (700–2500 A) . . . . . . . . . . . . . . . . . . V4-T2-79
Motor Circuit Protectors (3–600 A) . . . . . . . . . . . . V4-T2-87
Motor Protection Circuit Breakers (15–600 A) . . . V4-T2-98
Terminals, Lugs and Connectors . . . . . . . . . . . . . V4-T2-104
Communications and Software. . . . . . . . . . . . . . . V4-T2-127
Special Applications . . . . . . . . . . . . . . . . . . . . . . . V4-T2-129
Features and Benefits
Frame Size 3 breakers are modular and available as complete breakers from the factory, or as modular components, including frames, trip units, accessories and terminals to provide flexibility for customers. PXR trip units are available with advanced features to provide customers unparalleled situational awareness of their electrical system.
Standards and Certifications
Power Defense breakers are designed and tested to meet stringent requirements for:
l
UL
l
CSA
l
IEC (CE)
l
CB (CCC)
2
2
2
2
2
2
2
2
2
2
2
V4-T2-42 Volume 4—Circuit Protection CA08100005E—March 2020
Molded Case Circuit Breakers
Power Defense Molded Cas e Circ uit Breakers
2.2
Catalog Number / Product Selection
Power Defense—Frame Size 3 (45–600 A)
Frame Size 3 covers a range of 45 A through 600 A using electronic trip units, and 100 A through 600 A using thermal-magnetic trip units. It is available in configurations of 2-pole, 3-pole and 4-pole, with the 2-pole being in the same physical size of a 3-pole variant. Frame 3 has two unique constructions: one for 400 A and a second one for 600 A. The 600 A construction provides a unique capability to be used at 400 A and below in critical coordination applications where a high level fixed instantaneous is required. This is accomplished by using a letter H in the 7th digit of the catalog number, as shown below.
Interrupting Ratings
Catalog Designator
ANSI (UL/CSA) kA rms kA rms kA rms kA rms kA rms kA rms
240 Vac
480 Vac
600 Vac
23
250 Vdc
IEC
240 Vac 35 35 55 55 85 85 100 100 150 100 200 150
380–415 Vac
440 Vac
480 Vac
525 Vac
660–690 Vac
23
250 Vdc
Notes
1
UL current limiting. M interrupting rating only current limiting for the 400 A construction breakers.
2
DC ratings available in thermal-magnetic breakers only. 250 Vdc is achieved using two poles in series.
3
First rating listed is for 400 A frame, second rating is for 600 A frame.
FGKM 1N
35 65 85 100 150 200
25 35 50 65 85 100
14 18 25 35 50 65
10 / 22 10 / 22 10 / 22 22 / 42 22 / 42 22 / 42
l
cu
25 25 36 36 50 50 70 53 70 70 100 70
25 20 30 22.5 35 35 50 40 70 50 100 50
20 20 25 20 35 22.5 50 30 65 40 85 40
18 5207.525 10 30 15 35 25 40 25
—8 4 10 5157.520 10 20 10
10 / 22 10 / 22 10 / 22 10 / 22 10 / 22 10 / 22 22 / 42 22 / 42 22 / 42 22 / 42 22 / 42 22 / 42
l
cs
l
cu
l
cs
l
cu
l
cs
l
cu
l
cs
1
l
cu
l
cs
1
P
l
cu
l
2
2
2
2
2
2
2
2
2
cs
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
Volume 4—Circuit Protection CA08100005E—March 2020 V4-T2-43
Molded Case Circuit Breakers
Frame
Size
3 =3
Pole
Options
2 =2-pole
1
3 =3-pole 4 = 4-pole (100% N) 0 = 4-pole (0% N) 6 = 4-pole (60% N)
Interrupting
Ratings
F = 25 kA at 480 V G = 35 kA at 480 V K = 50 kA at 480 V M= 65 kA at 480 V N = 85 kA at 480 V P = 100 kA at 480 V
F = 14 kA at 600 V G = 18 kA at 600 V K = 25 kA at 600 V M= 35 kA at 600 V N = 50 kA at 600 V P = 65 kA at 600 V
Trip Unit
Type Options
TFA = Fixed thermal /
Adjustable magnetic
VFA = 50 °C Fixed thermal /
Adjustable magnetic (non UL)
Standard Terminal
Options
N = No terminals J = Line and load terminals K = Line only terminals L = Load only terminals
Continuous
Current Ratings
0100 = 100 A
2
0125 = 125 A
2
0150 = 150 A 0175 = 175 A 0200 = 200 A 0225 = 225 A 0250 = 250 A H250 = 250 A
3
0300 = 300 A H300 = 300 A
3
0350 = 350 A H350 = 350 A
3
0400 = 400 A H400 = 400 A
3
0500 = 500 A 0600 = 600 A
Product Series
PD = Power Defense
3 =3 3 =3-pole
4 = 4-pole (100% N) 0 = 4-pole (0% N) 6 = 4-pole (60% N)
F = 25 kA at 480 V G = 35 kA at 480 V K = 50 kA at 480 V M= 65 kA at 480 V
F = 14 kA at 600 V G = 18 kA at 600 V K = 25 kA at 600 V M= 35 kA at 600 V
TFA = Fixed thermal /
Adjustable magnetic
N = No terminals J = Line and load terminals K = Line only terminals L = Load only terminals
H250 = 250 A
3
H300 = 300 A
3
H350 = 350 A
3
H400 = 400 A
3
0500 = 500 A 0600 = 600 A
PD
3 =3
2 =2-pole
1
3 =3-pole
F = 35 kA at 240 V G = 65 kA at 240 V K = 85 kA at 240 V M= 100 kA at 240 V N = 150 kA at 240 V P = 200 kA at 240 V
TFA = Fixed thermal /
Adjustable magnetic
VFA = 50 °C Fixed thermal /
Adjustable magnetic (non UL)
N = No terminals J = Line and load terminals K = Line only terminals L = Load only terminals
0100 = 100 A 0125 = 125 A 0150 = 150 A 0175 = 175 A 0200 = 200 A 0225 = 225 A 0250 = 250 A 0300 = 300 A 0350 = 350 A 0400 = 400 A 0500 = 500 A 0600 = 600 A
PD
PD G 3 3 M 0400 TFA J
Certifications/
Standards
G = UL/CSA/IEC/CCC
Molded Case Circuit Breakers with TMTU—Globally Rated (100% UL Rated)
Molded Case Circuit Breakers with TMTU—UL/CSA Rated to 240 Vac
F = UL/CSA/IEC/CCC
(100% UL Rated)
D = UL/CSA
G = UL/CSA/IEC/CCC 3 =3 3 =3-pole
4 = 4-pole (100% N)
G = 35 kA at 480 V M= 65 kA at 480 V
G = 18 kA at 600 V M= 35 kA at 600 V
KNS = Molded case switch
N = No terminals J = Line and load terminals K = Line only terminals L = Load only terminals
0400 = 400 A 0600 = 600 A
PD
Molded Case Switches 4—Globally Rated
2.2
Molded Case Circuit Breaker
2
This information is presented as a tool to develop catalog numbers for selecting Power Defense circuit breakers and trip units.
2
Molded Case Circuit Breaker with Thermal-Magnetic Trip Units (TMTU)—Globally Rated
2
2
2
2
2
2
Power Defense Molded Case Circuit Breakers
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
Notes
2
1
All PD-3 2-pole breakers are physically the same size as a 3-pole frame with the outer poles used for electrical connections.
2
2
2
Not available in 4-pole 60% neutral protection.
3
High override (600 A frame).
4
Molded case switches may open above 4000 A for the 400 A frame, and above 6300 A for the 600 A frame.
V4-T2-44 Volume 4—Circuit Protection CA08100005E—March 2020
Molded Case Circuit Breakers
Certifications/
Standards
G = UL/CSA/IEC/CCC
Frame
Size
3 =3
Pole
Options
2 = 2-pole
1
3 = 3-pole 4 = 4-pole
(programmable N)
Interrupting
Ratings
F = 25 kA at 480 V G = 35 kA at 480 V K = 50 kA at 480 V M= 65 kA at 480 V N = 85 kA at 480 V P = 100 kA at 480 V
F = 14 kA at 600 V G = 18 kA at 600 V K = 25 kA at 600 V M= 35 kA at 600 V N = 50 kA at 600 V P = 65 kA at 600 V
Trip Unit
Type Options
B2N = PXR 10 LSI E##
2
=PXR 20
D##
2
=PXR 20D
P##
2
=PXR 25
Standard Terminal
Options
N = No terminals J = Line and load terminals K = Line only terminals L = Load only terminals
Continuous
Current Ratings
0125 = 125 A 0250 = 250 A 0400 = 400 A 0600 = 600 A H250 = 250 A High Override
(600 A Frame)
H400 = 400 A High Override
(600 A Frame)
Product Series
PD = Power Defense
PD G 3 3 M 0400 P2M J
F = UL/CSA/IEC/CCC
(100% UL Rated)
3 =3 3 = 3-pole
4 = 4-pole
(programmable N)
F = 25 kA at 480 V G = 35 kA at 480 V K = 50 kA at 480 V M= 65 kA at 480 V
F = 14 kA at 600 V G = 18 kA at 600 V K = 25 kA at 600 V M= 35 kA at 600 V
B2N = PXR 10 LSI E##
2
=PXR 20
D##
2
=PXR 20D
P##
2
=PXR 25
N = No terminals J = Line and load terminals K = Line only terminals L = Load only terminals
0125 = 125 A 0250 = 250 A 0400 = 400 A 0600 = 600 A H250 = 250 A High Override
(600 A Frame)
H400 = 400 A High Override
(600 A Frame)
PD
Molded Case Circuit Breakers with PXR ETU—Globally Rated (100% UL Rated)
Power Defense Molded Cas e Circ uit Breakers
2.2
Molded Case Circuit Breakers with Power Xpert Release (PXR) Electronic Trip Units (ETU)
This information is presented as a tool to develop catalog numbers for selecting Power Defense circuit breakers and trip units.
Molded Case Circuit Breakers with PXR ETU—Globally Rated
2
2
2
2
2
2
2
2
2
2
2
2
2
2
Note
1
All PD-3 2-pole breakers are physically the same size as a 3-pole frame with the outer poles used for electrical connections.
2
See PXR Trip Unit Options table on Page V4-T2-48 for protection type (#
) and available configured options (#
(1)
(2)
).
2
2
2
2
2
2
2
2
2
2
2
2
2
2
Volume 4—Circuit Protection CA08100005E—March 2020 V4-T2-45
2
2
Molded Case Circuit Breakers
Certifications/
Standards
G = UL/CSA/IEC/CCC
Frame
Size
3 =3
Pole
Options
2 = 2-pole
1
3 = 3-pole 4 = 4-pole
Interrupting
Ratings
F = 25 kA at 480 V G = 35 kA at 480 V K = 50 kA at 480 V M= 65 kA at 480 V N = 85 kA at 480 V P = 100 kA at 480 V
F = 14 kA at 600 V G = 18 kA at 600 V K = 25 kA at 600 V M= 35 kA at 600 V N = 50 kA at 600 V P = 65 kA at 600 V
Trip Unit
Type Options
FNN = Frame only
Standard Terminal
Options
N = No terminals
Continuous
Current Ratings
0400 = 400 A 0600 = 600 A
Product Series
PD = Power Defense
PD G 3 3 M 0400 FNN N
F = UL/CSA/IEC/CCC
(100% UL Rated)
3 =3 3 = 3-pole
4 = 4-pole
F = 25 kA at 480 V G = 35 kA at 480 V K = 50 kA at 480 V M= 65 kA at 480 V
F = 14 kA at 600 V G = 18 kA at 600 V K = 25 kA at 600 V M= 35 kA at 600 V
FNN = Frame only N = No terminals0400 = 400 A
0600 = 600 A
PD
Frame Only—Globally Rated (100% UL Rated)
2.2
Globally Rated Frame Only
2
PD-3 thermal-magnetic and electronic breakers may also be purchased as separate frames, trip units, terminals and accessories for field configuration of a final breaker. Each Frame Only device is marked with interrupting ratings and a
2
maximum continuous current rating; each trip unit is also marked with a maximum continuous current rating, which must not exceed that of the frame. Additionally, 100% UL Rated frames are marked as such on the Frame Only device.
2
Frame Only—Globally Rated
2
2
2
2
2
2
2
2
Power Defense Molded Case Circuit Breakers
2
2
2
2
2
2
Note
2
1
2
2
2
2
2
2
2
2
2
2
All PD-3 2-pole breakers are physically the same size as a 3-pole frame with the outer poles used for electrical connections.
2
2
V4-T2-46 Volume 4—Circuit Protection CA08100005E—March 2020
Molded Case Circuit Breakers
Frame
Size
3 =3
Separator
Digit
X = Accessory
Trip Unit
Type Options
TFA = Fixed Thermal /
Adjustable Magnetic
VFA = 50 °C Fixed Thermal /
Adjustable Magnetic (non UL)
Continuous
Current Ratings
0100 = 100 A
1
0125 = 125 A
1
0150 = 150 A 0175 = 175 A 0200 = 200 A 0225 = 225 A 0250 = 250 A 0300 = 300 A 0350 = 350 A 0400 = 400 A 0500 = 500 A 0600 = 600 A H250 = 250 A High Override
(600 A Frame)
H300 = 300 A High Override
(600 A Frame)
H350 = 350 A High Override
(600 A Frame)
H400 = 400 A High Override
(600 A Frame)
Product Series
PD = Power Defense
PD G 3 X TFA 3 0600
Certifications/
Standards
G = UL/CSA/IEC/CCC
Pole
Options
2 = 2-pole 3 = 3-pole 4 = 4-pole (100% N) 0 = 4-pole (0% N) 6 = 4-pole (60% N)
Frame
Size
3 =3
Separator
Digit
X = Accessory
Trip Unit
Type Designator
PXR = Power Xpert Release
Trip Unit
Continuous
Current Ratings
0125 = 125 A 0250 = 250 A 0400 = 400 A 0600 = 600 A H250 = 250 A High Override
(for use in 600 A Frame)
H400 = 400 A High Override
(for use in 600 A Frame)
Product Series
PD = Power Defense
PD G 3 X PXR 3 0600 E2N
Certifications/
Standards
G = UL/CSA/IEC/CCC
Pole
Options
3 = 3-pole 4 = 4-pole
(programmable N)
Trip Unit
Type and Options
B2N = PXR 10 LSI E##
2
=PXR 20
D##
2
=PXR 20D
P##
2
=PXR 25
Power Defense Molded Cas e Circ uit Breakers
2.2
Trip Units
PD-3 thermal-magnetic and electronic breakers may also be purchased as separate frames, trip units, terminals and accessories for field configuration of a final breaker. The 400 A frame must use trip units of ratings 0100–0400, while the 600 A frame must use trip units of ratings 0500, 0600 or designated by H, such as H250. Additionally, for 2-pole breakers using electronic trip units, 3-pole trip units are used. PDG designated trip units are for use with PDG and PDF breaker frames. The 100% rating for PDF (100% UL Rated) is marked on the frame, not the trip unit.
Trip Units Only
This information is presented as a tool to develop catalog numbers for selecting Power Defense circuit breakers and trip units.
Thermal-Magnetic Trip Units
2
2
2
2
2
2
2
2
2
2
2
2
2
2
Power Xpert Release (PXR) Electronic Trip Units
Power Xpert Release (PXR) Electronic Trip Units
Notes
1
Not available in 4-pole 60% neutral protection.
2
See tables and descriptions on Page V4-T2-48 for protection type (#
) and available configured options (#
(1)
Volume 4—Circuit Protection CA08100005E—March 2020 V4-T2-47
).
(2)
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
Molded Case Circuit Breakers
2.2
Power Xpert Release (PXR) Trip Unit Options—Frame Size 3
2
Power Xpert Release (PXR) Trip Unit Options
2
2
PXR ETU
2
PXR 10 B
PXR 20 E
2
PXR 20D D
2
PXR 25 P
2
Descriptions of PXR Configured Options
2
Relays—2 Form A contacts (rated for 240 Vac, 1 A)
2
l
Interface: 3 wires (ALM1,
2
2
2
2
2
ALM2, ALM Common)
l
Programmable to indicate breaker conditions
Modbus—Modbus RTU directly from breaker
l
Interface: MODBB, MODBG)
l
No additional modules required
2
#
LSI LSIG
2 —— — N ————————
2 —— — NR MZ C WX ——
34 5 RMZCWX——
234 5 ——M ——W DY
234 5 ——M ——W DY
3 wires (MODBA,
Power Defense Molded Case Circuit Breakers
—Protection Type #
(1)
LSI with ARMS
LSIG with ARMS
ZSI—Zone Selective Interlocking
l
Interface: 3 wires (Zin, Zout, Zcomm)
l
Includes ability to turn ON and OFF, and indicate signals
CAM—CAM Link connection (requires a CAM module per breaker)
l
Interface: 5 wires (refer to CAM IL for details)
l
Communications Adapter Modules available for Modbus TCP and PROFIBUS
—Available Configured Options
(2)
— — — —
Relays — — —
Relays Modbus — —
Relays — ZSI —
ARMS—Arcflash Reduction Maintenance System, or Maintenance Mode
l
Available as trip unit Protection Type 4 or 5
l
Interface: Switch and LED on face of trip unit (self­powered) and two wires for remote switch enable option (24 Vdc required)
l
A programmable relay will be factory defaulted to remote indication of ARMS
Relays — — CAM
Relays Modbus ZSI —
Relays — ZSI CAM
Auxiliary Power
l
Connection included with all PXR 20, 20D, and 25 trip units
l
Required for communications, relays, and metering accuracy
l
24 Vdc, 0.5 A
l
Interface: 2 wires Aux +24 V, Aux 0 V)
Relays Modbus — CAM
Relays Modbus ZSI CAM
2
Available Continuous Current (l
2
Option Setting
2
PXR 10, PXR 20 1 45 A 90 A 160 A 250 A
2
2
2
2
2
PXR 20D, PXR 25 Programmable from minimum to maximum values in 1 A increments.
2
2 50 A 100 A 175 A 275 A
3 60 A 110 A 200 A 300 A
4 63 A 125 A 225 A 320 A
5 70 A 150 A 250 A 350 A
6 80 A 160 A 275 A 400 A
7 90 A 175 A 300 A 450 A
8 100 A 200 A 320 A 500 A
9 110 A 225 A 350 A 550 A
10 = l
n
) Settings on PXR Electronic Trip Units
r
Catalog Number Selection and Maximum Setting (ln)
0125
125 A
125 A 250 A 400 A 600 A
0250/H250
250 A
0400/H400
400 A
2
2
2
2
2
0600
600 A
2
V4-T2-48 Volume 4—Circuit Protection CA08100005E—March 2020
Molded Case Circuit Breakers
Power Defense Molded Cas e Circ uit Breakers
2.2
Terminals—Frame Size 3
Catalog numbers shown are for a single side of a 3-pole breaker. For 2- and 4-pole options, replace the X3 with X2 or X4, respectively.
Example: PDG3X3TA300 becomes PDG3X2TA300 for two-pole.
Te r m i n a l T y p e s
PDG3X3TA300 PDG3X3TA350 PDG3X3T300 PDG3X3T350 PDG3X3TA350SW
Note: Pictures are for reference only.
Te r m i n a l s
Maximum Breaker Amperes
Standard Terminals
300 400 Aluminum Cu/Al B, C 1 3–350 26.7–177 PDG3X3TA300 J K L 100–225
350 400 Aluminum Cu/Al B, C 1 250–500 127–253 PDG3X3TA350 J K L 250–350
400 400 Aluminum Cu/Al B, C 2 3/0–250 85–127 PDG3X3TA400 Terminal shield J K L 400
400 600 Aluminum Cu/Al B, C 1 500–750 253–380 PDG3X3TA401H Terminal shield J K L H250–H400
630 600 Aluminum Cu/Al B, C 2 2–500 33.6–253 PDG3X3TA630 Terminal shield J K L 450–600
Optional Aluminum Terminals
400 400 Aluminum Cu/Al B, C 1 500–750 253–380 PDG3X3TA402 Terminal shield T U V 100–400
400 400 Aluminum Cu/Al B, C 2 2/0–250 (2) or
400 600 Aluminum Cu/Al B, C 1 3–500 26.7–253 PDG3X3TA400H T U V H250–H400
Optional Copper Terminals
300 400 Copper Cu B, C 1 3–350 26.7–177 PDG3X3T300 W Y Z 100–225
350 400 Copper Cu B, C 1 250–500 127–253 PDG3X3T350 W Y Z 250–350
400 400 Copper Cu B, C 2 3/0–250 85–127 PDG3X3T400 Terminal shield W Y Z 400
400 400 Copper Cu/Al B, C 1 Al: 500–750
400 600 Copper Cu B, C 1 3–500 26.7–253 PDG3X3T400H — ———
400 600 Copper Cu B, C 1 500–750 253–380 PDG3X3T401H Terminal shield W Y Z H250–H400
630 600 Copper Cu B, C 2 2–500 33.6 –253 PDG3X3T630 Terminal shield W Y Z 450–600
StrandAble Terminals
400 400 Aluminum Cu/Al B, C 2 3/0–250 85–127 PDG3X3TA400SW Terminal shield A B C 100–400
350 400 Aluminum Cu/Al B, C 1 250–500 127–253 PDG3X3TA350SW — — ———
630 600 Aluminum Cu/Al B, C 2 2–500 33.6–253 PDG3X3TA630SW Terminal shield A B C H250–600
Breaker Frame
PDG3X3TA400 PDG3X3TA400SW PDG3X3T400 PDG3X3TA400CW PDG3X3T400CW PDG3X3TA401CW PDG3X3TA401
Terminal Body Type
Wire Typ e
PDG3X3TA402 PDG3X3T402 PDG3X3TA401H PDG3X3T401H PDG3X3TA401HCW PDG3X3T401HCW
Number of
Wire
Conductors
Class
per Phase
D, G, H, I, K, M
D, G, H, I, K, M
D, G, H, I, K, M
PDG3X3TA400H PDG3X3T400H
AWG / kcmil Range per Conductor
2/0–500 (1)
Cu: 500 Only
3/0–4/0 85–107
250–350 127–177
2–350 33.6–177
Metric (mm Range per Conductor
67.4–127 (2) or
67.4–253 (1)
PDG3X3T402 Terminal shield —
PDG3X3TA630 PDG3X3T630 PDG3X3TA630SW PDG3X3TA630CW PDG3X3T630CW
2
)
3-Pole Catalog Number
PDG3X3TA401 Terminal shield I O F 100–400
PDG3X3TA4003W PDG3X3TA4006W PDG3X3TA6006W PDG3X3TA6006WSW
Included Accessories
PDG3X3TA400RF PDG3X3TA400HRF PDG3X3TA630RF
Digit 14 Designation Factory
Line and Load
Line Only
Load Only
Config. Ampere Range
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
Volume 4—Circuit Protection CA08100005E—March 2020 V4-T2-49
Molded Case Circuit Breakers
2.2
Terminals—Frame Size 3
2
Terminals, continued
2
Maximum Breaker Amperes
2
Control Wire Aluminum Terminals
2
400 400 Aluminum Cu/Al B, C 2 3/0–250 85–127 PDG3X3TA400CW Terminal shield 1 2 3 100–400
400 400 Aluminum Cu/Al B, C 2 2/0–250 (2) or
2
400 600 Aluminum Cu/Al B, C 1 500–750 253–380 PDG3X3TA401HCW Terminal shield 1 2 3 H250–H400
2
630 600 Aluminum Cu/Al B, C 2 2–500 33.6–253 PDG3X3TA630CW Terminal shield 1 2 3 450–600
Control Wire Copper Terminals
2
400 400 Copper Cu B, C 2 3/0–250 85–127 PDG3X3T400CW Terminal shield 7 8 9 100–400
2
400 600 Copper Cu B, C 1 500–750 253–380 PDG3X3T401HCW Terminal shield 7 8 9 H250–H400
630 600 Copper Cu B, C 2 2–500 33.6–253 PDG3X3T630CW Terminal shield 7 8 9 450–600
2
Multi-wire Terminals
400 400 Aluminum Cu/Al B, C 3 12–2/0 3.31–67.4 PDG3X3TA4003W Terminal shield H 100–400
2
400 400 Aluminum Cu/Al B, C 6 14–3 2.08–26.7 PDG3X3TA4006W Terminal shield G 100–400
600 600 Aluminum Cu/Al B, C 6 14–1/0 2.08–53.5 PDG3X3TA6006W Terminal shield G H250–600
2
StrandAble Multi-wire Terminals
2
600 600 Aluminum Cu/Al B, C 6 12–2/0 PDG3X3TA6006WSW Terminal shield
2
Rear-fed Terminals
2
400 400 Aluminum Cu/Al B, C 1 250–500 127–253 PDG3X3TA400RF
2
400 600 Aluminum Cu/Al B, C 1 2–500 33.6–253 PDG3X3TA400HRF
2
630 600 Aluminum Cu/Al B, C 2 2–500 33.6–253 PDG3X3TA630RF
2
Rear Connectors
400 PDG3X3T400RC R 100–400
2
630 PDG3X3T630RC R 250–600
End Cap Kits/Screw Terminals
2
400 PDG3X3TS400 S D E 100–400
600 PDG3X3TS600 S D E 250–600
2
Note: Wire capacity is based on standard imperial wire sizes; metric sizes provided in table
2
are a direct conversion to demonstrate maximum capacity, not to denote metric wire sizes.
Breaker Frame
Power Defense Molded Case Circuit Breakers
Terminal Body Type
Wire Typ e
Wire Class
D, G, H, I, K, M
Number of Conductors per Phase
AWG / kcmil Range per Conductor
2/0–500 (1)
8–1/0
Metric (mm Range per Conductor
67.4–127 (2) or
67.4–253 (1)
2
)
3-Pole Catalog Number
PDG3X3TA401CW Terminal shield 4 5 6 100–400
1
1
1
Included Accessories
Interphase barriers
Interphase barriers
Interphase barriers
Digit 14 Designation Factory
Line and Load
— ———
— ———
— ———
Line Only
Load Only
Config. Ampere Range
2
Control Wire Tabs
Use
2
100–400 A 12 KCWTK
2
Note
1
2
Terminals not UL Listed.
Package Qty.
Catalog Number
2
2
2
2
2
V4-T2-50 Volume 4—Circuit Protection CA08100005E—March 2020
Molded Case Circuit Breakers
Power Defense Molded Cas e Circ uit Breakers
2.2
Accessories
Internal Accessory Configurations—Frame Size 3
3-Pole Circuit Breakers
Tripping Accessory Options
Shunt Trip None None
UVR 2NO (2 spaces) 2NO (2 spaces)
4-Pole Circuit Breakers
Alarm Options (2 Spaces)
1NO (1 space) 1NO (1 space)
1NC (1 space) 1NC (1 space)
1NO/1NC (2 spaces) 1NO/1NC (2 spaces)
2NC (2 spaces) 2NC (2 spaces)
1
Aux Options (2 Spaces)
Alarm and Auxiliary Contact Blocks—Frame Size 3
Power Defense breakers have designated positions for alarm and auxiliary switches in the right pole accessory cavity. For Frame 3, the two left-most positions are used for alarm switches, and the two right-most locations are used for auxiliary switches.
Power Defense breakers have secondary covers for ease of field installation of accessories, including alarm and auxiliary switches.
Contact Blocks
Pigtail (29 in / 0.75 m) Contact Blocks for Alarm and Auxiliary Switch Functionality
Catalog Number PDGXAA PDGXAB PDGXAC
Typ e Form A / NO Form B / NC Form C / NO-NC
Power Defense alarm and auxiliary switches are available in contact blocks, in Form A (NO), Form B (NC), and Form C (NO-NC) types. Form A and Form B contacts take one position in the breaker accessory cavity, and Form C contacts take two positions in the cavity. Identical contact blocks are used for the alarm and auxiliary switch functions.
Electronic breakers with communications options (Modbus RTU or CAM Link) lose one alarm switch position, but are also able to provide trip position via communications and the PXR programmable relays.
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
Tripping Accessory Options
Shunt Trip None None
UVR 2NO (2 spaces) 2NO (2 spaces)
Notes
1
Frame 3 Power Defense breakers with electronic trip units AND communication only have access to one alarm space. Breakers with thermal-magnetic trip units or electronic trip units without communication have access to two alarm spaces.
2
Neutral pole includes two additional auxiliary spaces.
Alarm Options (2 Spaces)
1NO (1 space) 1NO (1 space)
1NC (1 space) 1NC (1 space)
1NO/1NC (2 spaces) 1NO/1NC (2 spaces)
2NC (2 spaces) 2NC (2 spaces)
1
Aux Options (4 Spaces)
2NO/2NC (4 spaces)
4NO (4 spaces)
4NC (4 spaces)
2
Screw Terminal Contact Blocks for Alarm and Auxiliary Switch Functionality
Catalog Number PDGXXA PDGXXB PDGXXA + PDGXXB
Typ e Form A / NO Form B / NC For NO-NC, use two
Push-In Clamp Contact Blocks for Alarm and Auxiliary Switch Functionality
Catalog Number PDGXUA PDGXUB PDGXUC
Typ e Form A / NO Form B / NC Form C / NO-NC
Pigtail (118 in / 3.0 m) Contact Blocks for Alarm and Auxiliary Switch Functionality
Catalog Number PDGXDA PDGXDB PDGXDC
Typ e Form A / NO Form B / NC Form C / NO-NC
separate contact blocks
2
2
2
2
2
2
2
2
2
2
2
2
2
2
Volume 4—Circuit Protection CA08100005E—March 2020 V4-T2-51
2