2.2
Power Defense Molded Case Circuit Breakers—Frame Size 1
Molded Case Circuit Breakers
Power Defense Molded Case Circuit Breakers
2
2
2
2
2
2
2
2
2
2
2
Power Defense Molded Case Circuit Breakers—Frame Size 1
Product Description
2
Frame Size 1 covers a range
of 15 A through 125 A with
2
fixed-fixed thermal-magnetic
trip units. PD-1 is available
2
in 1-, 2-, 3- and 4-pole
configurations, with the
2
4-pole configuration available
with no protection on the
2
neutral pole, or fully protected.
Application Description
Frame Size 1 can be used to
meet a wide range of circuit
protection and power
distribution needs, including
current limiting applications.
PD-1 is a cable-in / cable-out
MCCB.
Frame Size 1 breakers are
available in multiple ratings
from 15 A through 125 A.
They are of a modular design
with field installable
accessories and terminals,
which may also be factory
installed.
Standards and Certifications
Power Defense breakers are
designed and tested to meet
stringent requirements for:
Frame Size 1 covers a range of 15 A through 125 A using thermal-magnetic trip units.
It is available in configurations of single-pole, 2-pole, 3-pole and 4-pole.
C = 18 kA at 480 V
F = 25 kA at 480 V
G = 35 kA at 480 V
K = 50 kA at 480 V
M= 65 kA at 480 V
Trip Unit
Type Options
TFF = Fixed Thermal /
Fixed Magnetic
VFF = 50 °C Fixed
Thermal / Fixed
Magnetic
(non UL)
Standard Terminal
Options
N = No terminals
J = Line and load terminals
K = Line only terminals
L = Load only terminals
Continuous
Current Ratings
0015 =15 A
0020 =20 A
0025 =25 A
0030 =30 A
0035 =35 A
0040 =40 A
0045 =45 A
0050 =50 A
0060 =60 A
0070 =70 A
0080 =80 A
0090 =90 A
0100 = 100 A
0110 = 110 A
0125 = 125 A
Product Series
PD = Power Defense
PD G 13 M0125 TFFJ
G = UL/CSA/IEC/CCC1 =13 =3-pole
4 = 4-pole (100% N)
0 = 4-pole (0% N)
C = 10 kA at 600Y/347 V
F = 14 kA at 600Y/347 V
G = 18 kA at 600Y/347 V
K = 22 kA at 600Y/347 V
M= 25 kA at 600Y/347 V
N = 30 kA at 600Y/347 V
P = 35 kA at 600Y/347 V
TFF = Fixed Thermal /
Fixed Magnetic
VFF = 50 °C Fixed
Thermal / Fixed
Magnetic
(non UL)
N = No terminals
J = Line and load terminals
K = Line only terminals
L = Load only terminals
0015 =15 A
0020 = 20 A
0025 =25 A
0030 =30 A
0035 =35 A
0040 =40 A
0045 =45 A
0050 =50 A
0060 =60 A
0070 =70 A
0080 =80 A
0090 =90 A
0100 = 100 A
0110 = 110 A
0125 = 125 A
PD
Molded Case Circuit Breakers (Three- and Four-Pole) with Thermal-Magnetic Trip Units—Globally Rated
G = UL/CSA/IEC/CCC1 =13 =3-pole
4 = 4-pole
G = 35 kA at 480 V
M= 65 kA at 480 V
KNS = Molded Case
Switch
N = No terminals
J = Line and load terminals
K = Line only terminals
L = Load only terminals
0125 = 125 A PD
Molded Case Switches—Globally Rated
3
Interrupting
Ratings
2
C = 10 kA at 600Y/347 V
F = 14 kA at 600Y/347 V
G = 18 kA at 600Y/347 V
K = 22 kA at 600Y/347 V
M= 25 kA at 600Y/347 V
C = 18 kA at 480 V
F = 25 kA at 480 V
G = 35 kA at 480 V
K = 50 kA at 480 V
M= 65 kA at 480 V
N = 85 kA at 480 V
P = 100 kA at 480 V
G = 18 kA at 600Y/347 V
M= 25 kA at 600Y/347 V
2.2
Power Defense—Frame Size 1 (15–125 A)
2
This information is presented as a tool to develop catalog numbers
for selecting Power Defense circuit breakers and trip units.
2
Molded Case Circuit Breakers (Single- and Two-Pole) with Thermal-Magnetic Trip Units—Globally Rated
Catalog numbers shown are for a single side of a 3-pole breaker.
For 2- and 4-pole options, replace the X3 with X2 or X4, respectively.
Example: PDG1X3T125 becomes PDG1X2T125 for two-pole.
Note: Wire capacity is based on standard imperial wire sizes; metric sizes provided in table
are a direct conversion to demonstrate maximum capacity, not to denote metric wire sizes.
Control Wire Tabs
Use
15–125 A12GCWTK
Note: Control wire tabs can be installed with terminals listed above.
Alarm and auxiliary switches
are plug-and-play accessories
designed to be field
2
installable. However, Eaton
also offers the service of field
2
installation in our factories.
2
Breaker catalog numbers
with alarm and auxiliary
switch combinations require
a complete 20-digit catalog
number, adding the alarm and
auxiliary switch functionality
in digits 15–16 and adhering
to the following conditions
and tables:
2
Alarm and Auxiliary Switch—Field Installation Kits
2
2
Alarm SwitchNone—
2
2
2
Alarm and Auxiliary Switch Factory Installation (Digits 15–16)
2
Alarm SwitchNone
2
2
Notes
1
2
2-pole PD-1 breakers have an accessory pocket compatible with indicating accessory options only.
2
All options come with pigtail terminations.
Auxiliary SwitchCatalog Number
Three-PoleNone1NO/1NC (1 Form C)2NO/2NC (2 Form C)
1NO/1NC (1 Form C)
2NO/2NC (2 Form C)
Auxiliary SwitchBreaker Catalog Number (Digit 15–16 Suffix)
Three-PoleNone1NO/1NC (1 Form C)2NO/2NC (2 Form C)
1NO/1NC (1 Form C)
2NO/2NC (2 Form C)
ALM1M1BEPKAUXALRMEPK—
ALM2M2BEPK——
NNACA1
BCCC—
B1——
2
l
Digit 15 denotes the type
of accessory(-ies) installed
and the terminal types
l
Digit 16 denotes number of
switches installed
l
If no other accessories are
selected, use NNNN for
the final 4 digits of the
catalog number
Power Defense Molded Case Circuit Breakers—Frame Size 2
Power Defense Molded Cas e Circ uit Breakers
2.2
Contents
DescriptionPage
Power Defense Molded Case Circuit Breakers
Power Defense Molded Case Circuit Breakers—Frame Size 2
Product Description
Frame Size 2 covers a range
of 15 A through 225 A with a
complete offering of trip units,
including PXR electronic trip
units and fixed-fixed thermalmagnetic trip units.
Application Description
Frame Size 2 can be used
to meet a wide range of
circuit protection and power
distribution needs, including
ground fault protection and
current limiting options. PXR
trip units in PD-2 provide all
levels of protection, including
energy metering with
multiple communication
schemes, breaker health
indication, and zone selective
interlocking with visual
indication.
Features and Benefits
Frame Size 2 breakers are
available in multiple ratings
from 15 A through 225 A.
They are configured with a
trip unit from the factory.
Accessories are modular in
design to allow for field
installation or factory
configuration. PXR trip units
are available with advanced
features to provide
customers unparalleled
situational awareness of
their electrical system.
Frame Size 2 covers a range of 15 A through 225 A using electronic trip units or thermal-magnetic
trip units. It is available in configurations of single-pole, 2-pole, 3-pole and 4-pole.
2
Interrupting Ratings (2-, 3- and 4-Pole)
Catalog Designator
2
ANSI (UL/CSA)kA rmskA rmskA rmskA rmskA rmskA rms
2
240 Vac
480 Vac
2
600 Vac
2
250 Vdc
2
IEC
2
240 Vac353555558585100100150100200150
380–415 Vac
2
440 Vac
480 Vac
2
525 Vac
660–690 Vac——8 4 105105105105
2
2
2
2
2
2
2
2
2
2
2
250 Vdc
Interrupting Ratings (Single-Pole)
Catalog Designator
ANSI (UL/CSA)
277 Vac
347 Vac
125 Vdc
IEC
240 Vac2525363650507070857010070
125 Vdc
Notes
1
UL current limiting for 3- and 4-pole breakers.
2
DC ratings available in thermal-magnetic breakers only. 250 Vdc is achieved using 2-poles in series.
3
First rating listed is for thermal-magnetic breakers, second rating is for breakers with PXR electronic trip units.
F = 25 kA at 277 V
G = 35 kA at 277 V
K = 50 kA at 277 V
M= 65 kA at 277 V
N =
85 kA at 277 V
1
P = 100 kA at
277 V
1
F = 14 kA at 347 V
G = 18 kA at 347 V
K = 22 kA at 347 V
M= 25 kA at 347 V
N =
30 kA at
347
V
1
P =
35 kA at
347
V
1
Trip Unit
Type Options
TFF = Fixed thermal /
Fixed magnetic
VFF = 50 °C Fixed thermal /
Fixed magnetic
(non UL)
Standard Terminal
Options
N = No terminals
J = Line and load terminals
K = Line only terminals
L = Load only terminals
Continuous
Current Ratings
0015 = 15 A
0020 = 20 A
0025 = 25 A
0030 = 30 A
0035 = 35 A
0040 = 40 A
0045 = 45 A
0050 = 50 A
0060 = 60 A
0070 = 70 A
0080 = 80 A
0090 = 90 A
0100 = 100 A
0110 = 110 A
0125 = 125 A
0150 = 150 A
F = 25 kA at 480 V
G = 35 kA at 480 V
K = 50 kA at 480 V
M= 65 kA at 480 V
N = 85 kA at 480 V
P = 100 kA at 480 V
F = 14 kA at 600 V
G = 18 kA at 600 V
K = 22 kA at 600 V
M= 25 kA at 600 V
N = 30 kA at 600 V
P = 35 kA at 600 V
TFF = Fixed thermal /
Fixed magnetic
VFF = 50 °C Fixed thermal /
Fixed magnetic
(non UL)
N = No terminals
J = Line and load terminals
K = Line only terminals
L = Load only terminals
0015 = 15 A
0020 = 20 A
0025 = 25 A
0030 = 30 A
0035 = 35 A
0040 = 40 A
0045 = 45 A
0050 = 50 A
0060 = 60 A
0070 = 70 A
0080 = 80 A
0090 = 90 A
0100 = 100 A
0110 = 110 A
0125 = 125 A
0150 = 150 A
0175 = 175 A
0200 = 200 A
0225 = 225 A
PD
PD G 21 M0150 TFFJ
Certifications/
Standards
G = UL/CSA/IEC/CCC
Molded Case Circuit Breakers (Two-, Three- and Four-Pole) with Thermal-Magnetic Trip Units—Globally Rated
G = UL/CSA/IEC/CCC
Power Defense Molded Cas e Circ uit Breakers
2.2
Power Defense—Frame Size 2 (15–225 A)
This information is presented as a tool to develop catalog numbers
for selecting Power Defense circuit breakers and trip units.
Molded Case Circuit Breakers (Single-Pole) with Thermal-Magnetic Trip Units (TMTU)—Globally Rated
2
2
2
2
2
2
2
2
2
2
2
2
2
2
Note
1
N and P ratings available for 15–30 A on single-pole breakers.
F = 35 kA at 240 V
G = 65 kA at 240 V
K = 85 kA at 240 V
M= 100 kA at 240 V
N = 150 kA at 240 V
P = 200 kA at 240 V
Trip Unit
Type Options
TFF = Fixed thermal /
Fixed magnetic
VFF = 50 °C Fixed thermal /
Fixed magnetic
(non UL)
Standard Terminal
Options
N = No terminals
J = Line and load terminals
K = Line only terminals
L = Load only terminals
Continuous
Current Ratings
0015 = 15 A
0020 = 20 A
0025 = 25 A
0030 = 30 A
0035 = 35 A
0040 = 40 A
0045 = 45 A
0050 = 50 A
0060 = 60 A
0070 = 70 A
0080 = 80 A
0090 = 90 A
0100 = 100 A
0110 = 110 A
0125 = 125 A
0150 = 150 A
0175 = 175 A
0200 = 200 A
0225 = 225 A
Product Series
PD = Power Defense
2 =22 = 2-pole
3 = 3-pole
4 = 4-pole
G = 35 kA at 480 V
M= 65 kA at 480 V
G = 18 kA at 600 V
M= 35 kA at 600 V
KNS = Molded Case SwitchN = No terminals
J = Line and load terminals
K = Line only terminals
L = Load only terminals
0100 = 100 A
0150 = 150 A
0225 = 225 A
PD
PD D 23 M0225 TFFJ
Certifications/
Standards
D = UL/CSA
Molded Case Switches—Globally Rated
1
G = UL/CSA/IEC/CCC
2 =23 = 3-pole
4 = 4-pole
(programmable N)
F = 25 kA at 480 V
G = 35 kA at 480 V
K = 50 kA at 480 V
M= 65 kA at 480 V
N = 85 kA at 480 V
P = 100 kA at 480 V
F = 14 kA at 600 V
G = 18 kA at 600 V
K = 22 kA at 600 V
M= 25 kA at 600 V
N = 25 kA at 600 V
P = 25 kA at 600 V
B2N =PXR 10 LSI
E##
2
=PXR 20
D##
2
=PXR 20D
P##
2
=PXR 25
N = No terminals
J = Line and load terminals
K = Line only terminals
L = Load only terminals
0060 = 60 A
0100 = 100 A
0150 = 150 A
0225 = 225 A
PD
Molded Case Circuit Breakers with Power Xpert Release Electronic Trip Units (ETU)—Globally Rated
G = UL/CSA/IEC/CCC
2 =23 = 3-pole
4 = 4-pole
F = 25 kA at 480 V
G = 35 kA at 480 V
K = 50 kA at 480 V
M= 65 kA at 480 V
N = 85 kA at 480 V
P = 100 kA at 480 V
F = 14 kA at 600 V
G = 18 kA at 600 V
K = 22 kA at 600 V
M= 25 kA at 600 V
N = 25 kA at 600 V
P = 25 kA at 600 V
B2N = PXR 10 LSI
E##
2
=PXR 20
D##
2
=PXR 20D
P##
2
=PXR 25
J = Line and load terminals
W= Optional line and load
terminals
0060 =60 A
0100 =100 A
0150 =150 A
0225 =225 A
PD
Molded Case Circuit Breakers with Power Xpert Release Electronic Trip Units (ETU)—100% UL Rated
F = UL/CSA/IEC/CCC
(100% UL Rated)
2.2
Power Defense—Frame Size 2 (15–225 A)
2
This information is presented as a tool to develop catalog numbers
for selecting Power Defense circuit breakers and trip units.
2
Molded Case Circuit Breakers with TMTU—UL/CSA Rated to 240 Vac
2
2
2
2
2
Power Defense Molded Case Circuit Breakers
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
Notes
1
Molded case switch may open above 1800 A.
2
See tables and descriptions on Page V4-T2-33 for protection type (#
Note: Wire capacity is based on standard imperial wire sizes; metric sizes provided in table
2
are a direct conversion to demonstrate maximum capacity, not to denote metric wire sizes.
Notes
1
2
2
2
2
The “Breaker Frame” column provides information on the ampere ratings for which the terminal may be used (field installation);
in some cases the range is limited by proper fit of the terminal onto the breaker conductor.
The column “Standard on Amperes” provides information on what terminal is used during factory configuration
per Digit 14 of the breaker catalog number. The two may not match.
2
Factory standard terminals and non-aluminum terminals for 100 A and below are the same terminals.
3
PDF2 225 A breakers with Digit 14 designation of “J” are equipped with PDG2X3TA225K terminals.
PDF2 150 A breakers with Digit 14 designation of “J” are equipped with PDG2X3TA225 terminals.
4
Breaker loses UL when fitted with rear-fed terminals or rear connectors.
Power Defense breakers
have designated positions for
2
alarm and auxiliary switches
in the right-pole accessory
cavity. For Frame 2, the two
2
left-most positions are used
for alarm switches, and the
2
two right-most locations are
used for auxiliary switches.
2
2
2
Pigtail (29 in / 0.75 m) Contact Blocks for Alarm and Auxiliary Switch Functionality
2
Catalog NumberPDGXAAPDGXABPDGXAC
Typ eForm A / NOForm B / NCForm C / NO-NC
2
2
Screw Terminal Contact Blocks for Alarm and Auxiliary Switch Functionality
Catalog NumberPDGXXAPDGXXBPDGXXA + PDGXXB
2
Typ eForm A / NOForm B / NCFor NO-NC, use two separate
2
Power Defense Molded Case Circuit Breakers
Power Defense breakers
have secondary covers for
ease of field installation of
accessories, including alarm
and auxiliary switches.
contact blocks
Power Defense alarm and
auxiliary switches are
available in contact blocks, in
Form A (NO), Form B (NC)
and Form C (NO-NC) types.
Form A and Form B contacts
take one position in the
breaker accessory cavity, and
Form C contacts take two
positions in the cavity.
Identical contact blocks are
used for the alarm and
auxiliary switch functions.
Frame 2 breakers with
electronic trip units are
automatically configured with
a factory-installed Form C
auxiliary contact block
because the right-pole
accessory cavity is not
available for field
modification. Trip position can
also be communicated via
communications and the PXR
programmable relays.
2
Push-In Clamp Contact Blocks for Alarm and Auxiliary Switch Functionality
2
Catalog NumberPDGXUAPDGXUBPDGXUC
Typ eForm A / NOForm B / NCForm C / NO-NC
2
2
Pigtail (118 in / 3.0 m) Contact Blocks for Alarm and Auxiliary Switch Functionality
Catalog NumberPDGXDAPDGXDBPDGXDC
2
Typ eForm A / NOForm B / NCForm C / NO-NC
2
Alarm Switch for Use with PXR Electronic Trip Units
2
Catalog NumberPDG2XALMBCPDG2XALMEC
2
Typ eForm C / NO-NCForm C / NO-NC
Termination0.75 m pigtail3.0 m pigtail
2
Note
1
2
2
Frame 2 breakers with electronic trip units do not allow access to the right accessory pocket
but are automatically configured with a factory installed Form C / NO-NC auxiliary switch.
These alarm switches can be field or factory installed in the left accessory pocket in place of a shunt trip or UVR.
Factory Installation of Alarm and Auxiliary Switches—Frame Size 2
Alarm and auxiliary switches
are plug-and-play accessories
designed to be field
installable. However, Eaton
also offers installation service
in our factories.
Breaker catalog numbers
with alarm and auxiliary
switch combinations require
a complete 20-digit catalog
number, adding the alarm and
auxiliary switch functionality
in digits 15–16 and adhering
to the following conditions
and tables:
l
Digit 15 denotes the type
of accessory(-ies) installed
and the terminal types
Pigtails—29 in / 0.75 m (A, B, C)
Alarm SwitchNone
1NO
1NC
1
1NO/1NC
2NO
2NC
l
Switches may be
requested for alarm only,
auxiliary only or a
combination of the two
l
Digit 16 denotes the
number and type (NO, NC)
of switches installed
l
For Eaton factory
installation, the same type
of terminals (i.e. all pigtail
0.75 m, all screw, etc.) and
same style of contact block
(i.e., all 1NO/1NC, all 2NC,
etc.) must be used in a
factory configuration
If no other accessories are
selected, use NNNN for
the final 4 digits of the
catalog number
l
Frame 2 breakers with
electronic trip units do not
allow access to the right
accessory pocket but are
automatically configured
with a factory installed
1NO/1NC auxiliary switch.
A bell alarm accessory is
available for separate
installation in the left
accessory pocket.
Note: Though factory
configuration options are limited,
combinations of auxiliary
switches and alarms using
differing terminals and contact
block styles are still available
through field installation. Please
see full auxiliary switch and alarm
catalog numbers to order.
Single-pole breakers can be equipped with a 1NO/1NC alarm switch that must be factory installed; use suffix BC in digits 15–16.
No other internal accessories are available for single-pole breakers.
Factory Installation of Alarm Switch for Use with PXR Electronic Trip Units
2
Pigtails—29 in / 0.75 m Pigtails—118 in / 3.0 m
2
2
Auxiliary switchNoneNN
2
2
Tripping Accessories—Frame Size 2
2
Power Defense breakers have designated positions for shunt trips and undervoltage releases
(UVRs) in the left pole accessory cavity. Each breaker has space for one tripping accessory only.
2
Power Defense breaker have secondary covers for ease of field installation of tripping accessories.
Shunt Trips
2
VoltageScrew TerminalsPigtail (29 in / 0.75 m)Pigtail (118 in / 3.0 m)
Shunt trips and under voltage
releases (UVRs) are plug-andplay accessories designed to
be field installable. However,
Eaton also offers the service
of installation in our factories.
Shunt Trips
VoltageScrew TerminalsPigtail (29 in / 0.75 m)Pigtail (118 in / 3.0 m)
12 VdcTHSHRH
48 VdcTJSJRJ
60 VdcTKSKRK
24 Vac/VdcTNSNRN
110–130 Vac/125 VdcTPSPRP
200–240 Vac/250 VdcTRSRRR
380–440 VacTCSCRC
480–525 VacTDSDRD
600 VacTESERE
Undervoltage Releases (UVRs)
VoltageScrew TerminalsPigtail (29 in / 0.75 m)Pigtail (118 in / 3.0 m)
12 VdcVHUHWH
24 VdcVGUGWG
48 VdcVJUJWJ
60 VdcVKUKWK
125 VdcVLULWL
250 VdcVMUMWM
24 VacVFUFWF
130 VacVAUAWA
240 VacVBUBWB
440 VacVCUCWC
525 VacVDUDWD
600 VacVEUEWE
Note: Use suffix US for 18 Vdc when using Time Delay UVR.
Breaker catalog numbers
with shunt trips or UVRs
require a complete 20-digit
catalog number, adding
the tripping accessory
functionality in digits 17 and
18 and adhering to the
following conditions and
tables.
l
Digit 17 denotes the type
of accessory installed and
the terminal type
l
Digit 18 denotes the
voltage of the accessory
l
If no accessories are
selected, use NNNN for
the final 4 digits of the
catalog number
l
Each breaker has space for
one shunt trip or UVR
tripping accessory only
Power Defense Molded Case Circuit Breakers—Frame Size 3
Molded Case Circuit Breakers
Power Defense Molded Case Circuit Breakers
2
2
2
2
2
2
2
2
2
2
2
Power Defense Molded Case Circuit Breakers—Frame Size 3
Product Description
2
Frame Size 3 covers a range
of 45 A through 600 A with a
2
complete offering of trip
units, including PXR
2
electronic trip units and fixedadjustable thermal-magnetic
2
trip units. PD-3 is available in
two versions, with 400 A and
2
600 A constructions to
optimize performance in
multiple applications.
2
2
2
Application Description
Frame Size 3 can be used to
meet a wide range of circuit
protection and power
distribution needs, including
ground fault protection,
current limiting, 100% UL
ratings, and high
instantaneous settings for
selective coordination. PXR
trip units in PD-3 provide all
levels of protection, including
energy metering with
multiple communication
schemes, breaker health
indication, and arc flash
reduction options.
Frame Size 3 breakers are
modular and available as
complete breakers from the
factory, or as modular
components, including
frames, trip units,
accessories and terminals to
provide flexibility for
customers. PXR trip units are
available with advanced
features to provide
customers unparalleled
situational awareness of their
electrical system.
Standards and Certifications
Power Defense breakers are
designed and tested to meet
stringent requirements for:
Frame Size 3 covers a range of 45 A through 600 A using electronic trip units, and 100 A through
600 A using thermal-magnetic trip units. It is available in configurations of 2-pole, 3-pole and
4-pole, with the 2-pole being in the same physical size of a 3-pole variant. Frame 3 has two unique
constructions: one for 400 A and a second one for 600 A. The 600 A construction provides a unique
capability to be used at 400 A and below in critical coordination applications where a high level fixed
instantaneous is required. This is accomplished by using a letter H in the 7th digit of the catalog
number, as shown below.
Interrupting Ratings
Catalog Designator
ANSI (UL/CSA)kA rmskA rmskA rmskA rmskA rmskA rms
240 Vac
480 Vac
600 Vac
23
250 Vdc
IEC
240 Vac353555558585100100150100200150
380–415 Vac
440 Vac
480 Vac
525 Vac
660–690 Vac
23
250 Vdc
Notes
1
UL current limiting. M interrupting rating only current limiting for the 400 A construction breakers.
2
DC ratings available in thermal-magnetic breakers only. 250 Vdc is achieved using two poles in series.
3
First rating listed is for 400 A frame, second rating is for 600 A frame.
F = 25 kA at 480 V
G = 35 kA at 480 V
K = 50 kA at 480 V
M= 65 kA at 480 V
F = 14 kA at 600 V
G = 18 kA at 600 V
K = 25 kA at 600 V
M= 35 kA at 600 V
TFA = Fixed thermal /
Adjustable magnetic
N = No terminals
J = Line and load terminals
K = Line only terminals
L = Load only terminals
H250 = 250 A
3
H300 = 300 A
3
H350 = 350 A
3
H400 = 400 A
3
0500 = 500 A
0600 = 600 A
PD
3 =3
2 =2-pole
1
3 =3-pole
F = 35 kA at 240 V
G = 65 kA at 240 V
K = 85 kA at 240 V
M= 100 kA at 240 V
N = 150 kA at 240 V
P = 200 kA at 240 V
TFA = Fixed thermal /
Adjustable magnetic
VFA = 50 °C Fixed thermal /
Adjustable magnetic
(non UL)
N = No terminals
J = Line and load terminals
K = Line only terminals
L = Load only terminals
0100 = 100 A
0125 = 125 A
0150 = 150 A
0175 = 175 A
0200 = 200 A
0225 = 225 A
0250 = 250 A
0300 = 300 A
0350 = 350 A
0400 = 400 A
0500 = 500 A
0600 = 600 A
PD
PD G 33 M0400 TFAJ
Certifications/
Standards
G = UL/CSA/IEC/CCC
Molded Case Circuit Breakers with TMTU—Globally Rated (100% UL Rated)
Molded Case Circuit Breakers with TMTU—UL/CSA Rated to 240 Vac
F = UL/CSA/IEC/CCC
(100% UL Rated)
D = UL/CSA
G = UL/CSA/IEC/CCC3 =33 =3-pole
4 = 4-pole (100% N)
G = 35 kA at 480 V
M= 65 kA at 480 V
G = 18 kA at 600 V
M= 35 kA at 600 V
KNS = Molded case switch
N = No terminals
J = Line and load terminals
K = Line only terminals
L = Load only terminals
0400 = 400 A
0600 = 600 A
PD
Molded Case Switches 4—Globally Rated
2.2
Molded Case Circuit Breaker
2
This information is presented as a tool to develop catalog numbers
for selecting Power Defense circuit breakers and trip units.
2
Molded Case Circuit Breaker with Thermal-Magnetic Trip Units (TMTU)—Globally Rated
2
2
2
2
2
2
Power Defense Molded Case Circuit Breakers
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
Notes
2
1
All PD-3 2-pole breakers are physically the same size as a 3-pole frame with the outer poles used for electrical connections.
2
2
2
Not available in 4-pole 60% neutral protection.
3
High override (600 A frame).
4
Molded case switches may open above 4000 A for the 400 A frame, and above 6300 A for the 600 A frame.
F = 25 kA at 480 V
G = 35 kA at 480 V
K = 50 kA at 480 V
M= 65 kA at 480 V
N = 85 kA at 480 V
P = 100 kA at 480 V
F = 14 kA at 600 V
G = 18 kA at 600 V
K = 25 kA at 600 V
M= 35 kA at 600 V
N = 50 kA at 600 V
P = 65 kA at 600 V
Trip Unit
Type Options
FNN = Frame only
Standard Terminal
Options
N = No terminals
Continuous
Current Ratings
0400 = 400 A
0600 = 600 A
Product Series
PD = Power Defense
PD G 33 M0400 FNNN
F = UL/CSA/IEC/CCC
(100% UL Rated)
3 =33 = 3-pole
4 = 4-pole
F = 25 kA at 480 V
G = 35 kA at 480 V
K = 50 kA at 480 V
M= 65 kA at 480 V
F = 14 kA at 600 V
G = 18 kA at 600 V
K = 25 kA at 600 V
M= 35 kA at 600 V
FNN = Frame onlyN = No terminals0400 = 400 A
0600 = 600 A
PD
Frame Only—Globally Rated (100% UL Rated)
2.2
Globally Rated Frame Only
2
PD-3 thermal-magnetic and electronic breakers may also be purchased as separate frames, trip units, terminals and
accessories for field configuration of a final breaker. Each Frame Only device is marked with interrupting ratings and a
2
maximum continuous current rating; each trip unit is also marked with a maximum continuous current rating, which must
not exceed that of the frame. Additionally, 100% UL Rated frames are marked as such on the Frame Only device.
2
Frame Only—Globally Rated
2
2
2
2
2
2
2
2
Power Defense Molded Case Circuit Breakers
2
2
2
2
2
2
Note
2
1
2
2
2
2
2
2
2
2
2
2
All PD-3 2-pole breakers are physically the same size as a 3-pole frame with the outer poles used for electrical connections.
0150 = 150 A
0175 = 175 A
0200 = 200 A
0225 = 225 A
0250 = 250 A
0300 = 300 A
0350 = 350 A
0400 = 400 A
0500 = 500 A
0600 = 600 A
H250 = 250 A High Override
0125 = 125 A
0250 = 250 A
0400 = 400 A
0600 = 600 A
H250 = 250 A High Override
(for use in 600 A Frame)
H400 = 400 A High Override
(for use in 600 A Frame)
Product Series
PD = Power Defense
PD G 3X PXR3 0600E2N
Certifications/
Standards
G = UL/CSA/IEC/CCC
Pole
Options
3 = 3-pole
4 = 4-pole
(programmable N)
Trip Unit
Type and Options
B2N = PXR 10 LSI
E##
2
=PXR 20
D##
2
=PXR 20D
P##
2
=PXR 25
Power Defense Molded Cas e Circ uit Breakers
2.2
Trip Units
PD-3 thermal-magnetic and electronic breakers may also be purchased as separate frames, trip units,
terminals and accessories for field configuration of a final breaker. The 400 A frame must use trip units
of ratings 0100–0400, while the 600 A frame must use trip units of ratings 0500, 0600 or designated
by H, such as H250. Additionally, for 2-pole breakers using electronic trip units, 3-pole trip units are
used. PDG designated trip units are for use with PDG and PDF breaker frames. The 100% rating for
PDF (100% UL Rated) is marked on the frame, not the trip unit.
Trip Units Only
This information is presented as a tool to develop catalog numbers
for selecting Power Defense circuit breakers and trip units.
Thermal-Magnetic Trip Units
2
2
2
2
2
2
2
2
2
2
2
2
2
2
Power Xpert Release (PXR) Electronic Trip Units
Power Xpert Release (PXR) Electronic Trip Units
Notes
1
Not available in 4-pole 60% neutral protection.
2
See tables and descriptions on Page V4-T2-48 for protection type (#
Power Defense breakers
have designated positions for
alarm and auxiliary switches
in the right pole accessory
cavity. For Frame 3, the two
left-most positions are used
for alarm switches, and the
two right-most locations are
used for auxiliary switches.
Power Defense breakers
have secondary covers for
ease of field installation of
accessories, including alarm
and auxiliary switches.
Contact Blocks
Pigtail (29 in / 0.75 m) Contact Blocks for
Alarm and Auxiliary Switch Functionality
Catalog NumberPDGXAAPDGXABPDGXAC
Typ eForm A / NOForm B / NCForm C / NO-NC
Power Defense alarm and
auxiliary switches are
available in contact blocks, in
Form A (NO), Form B (NC),
and Form C (NO-NC) types.
Form A and Form B contacts
take one position in the
breaker accessory cavity, and
Form C contacts take two
positions in the cavity.
Identical contact blocks are
used for the alarm and
auxiliary switch functions.
Electronic breakers with
communications options
(Modbus RTU or CAM Link)
lose one alarm switch
position, but are also able to
provide trip position via
communications and the PXR
programmable relays.
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
Tripping
Accessory Options
Shunt TripNoneNone
UVR2NO (2 spaces)2NO (2 spaces)
Notes
1
Frame 3 Power Defense breakers with electronic trip units AND communication only have
access to one alarm space. Breakers with thermal-magnetic trip units or electronic trip units
without communication have access to two alarm spaces.
2
Neutral pole includes two additional auxiliary spaces.
Alarm Options
(2 Spaces)
1NO (1 space)1NO (1 space)
1NC (1 space)1NC (1 space)
1NO/1NC (2 spaces)1NO/1NC (2 spaces)
2NC (2 spaces)2NC (2 spaces)
1
Aux Options
(4 Spaces)
2NO/2NC (4 spaces)
4NO (4 spaces)
4NC (4 spaces)
2
Screw Terminal Contact Blocks for
Alarm and Auxiliary Switch Functionality
Catalog NumberPDGXXAPDGXXBPDGXXA + PDGXXB
Typ eForm A / NOForm B / NCFor NO-NC, use two
Push-In Clamp Contact Blocks for
Alarm and Auxiliary Switch Functionality
Catalog NumberPDGXUAPDGXUBPDGXUC
Typ eForm A / NOForm B / NCForm C / NO-NC
Pigtail (118 in / 3.0 m) Contact Blocks for
Alarm and Auxiliary Switch Functionality