Manual Motor Protection
Manual Motor Protectors—XTPB, XTPR and XTPE
Product Description
Eaton’s new XT family of manual motor protectors (MMPs) features a pushbutton or rotary ON/OFF manual disconnect, Class 10 adjustable bimetallic overload relay and fixed magnetic short-circuit trip capability in one compact unit. Two frame sizes are available: Frame B (45 mm) for motors with FLA ratings up to 32A and Frame D (55 mm) covers motor FLA ratings up to 65A.
Application Description
The XTPB and XTPR MMPs can be used in the following applications.
Motor Protective Circuit Breaker
In many countries outside of the United States and Canada, especially Europe, the MMPs are tested and classified as thermal­magnetic circuit breakers for use in motor branch circuits. This can be an important consideration for all companies who export their equipment and machines internationally. Both the XTPB and XTPR conform to IEC/EN 60947 and have the CE Mark.
Contents
Description Page
Features and Benefits . . . . . . . . . . . . . . . . . . . . . . . . . . 525
Catalog Number Selection . . . . . . . . . . . . . . . . . . . . . . . 525
Reference . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 525
Manual Motor Protectors
The XTPB and XTPR MMPs are UL listed under UL 508 as manual motor protectors. They provide an economical solution for applications requiring simple manual starting and stopping of motors. When used as a manual starter, they are typically installed in an enclosure. Many enclosures are offered as accessories for the MMPs. Separate short­circuit protective devices, such as circuit breakers or fuses, are wired ahead of the MMPs. The short-circuit protective device should be sized per the NEC and should not exceed 400% of the maximum FLA dial setting of the MMP.
Individual Branch Motor Applications
A UL 508 Type E self­protected manual combination starter/motor controller consists of a single device possessing four essential elements: disconnect, short circuit protection, motor controller, and motor overload protection. Some MMPs require use of a lineside adapter for this type of approval. When tested as an official combination by UL, this device takes the place of a fuse-starter or breaker­starter, XT Type E MMPs are self-protected, meaning they do not need additional short circuit protection of a fuse or breaker. Type E devices can also be used with a contactor or other types of UL approved controllers. If tested with a contactor, the combination motor controller becomes a Type F device. See CA08102001E, Control Products Catalog, Tab 34, section 34.1 for XTFC Type F devices.
31
524 Volume 5—Motor Control and Protection CA08100006E—March 2011 www.eaton.com
Motor Protection and Monitoring
Manual Motor Protection
31.3
Features and Benefits
ON/OFF rotary handle with lockout provision
Visible trip indication
Class 10 overload protection
Phase loss sensitivity
Ambient temperature compensation to IEC/EN 60947, VDE 0660
Fixed short-circuit trip— 14 times maximum setting of overload FLA dial
Type 2 coordination per IEC 947
Identification markers standard on starter faceplate
Catalog Number Selection
XT Manual Motor Protectors
Designation
XT = XT IEC power control
PB = Manual motor protector—
PR = Manual motor protector—
PM = Manual motor protector—
PT = Manual transformer
Motor applications from
0.1A to 65A
Built-in heater and magnetic trip elements to protect the motor
Adjustment dial for setting motor FLA
DIN rail mount
Terminal types available:
Screw terminals
Screw (line) and spring cage (load) terminals
Spring cage terminals
XT PR 012 B C1
Type
pushbutton
rotary
magnetic only
protector (high mag.)
Frame B P16 = 0.16A P25 = 0.25A P40 = 0.40A P63 = 0.63A 001 = 1A 1P6 = 1.6A 2P5 = 2.5A 004 = 4A 6P3 = 6.3A 010 = 10A 012 = 12A 016 = 16A 020 = 20A 025 = 25A 032 = 32A
Accessories include:
Current Ratings
Frame D 016 = 16A 025 = 25A 032 = 32A 040 = 40A 050 = 50A 058 = 58A 063 = 63A
Front and side auxiliary contacts
Trip indicating contacts Tamperproof cover for
OLR dial Undervoltage release Shunt trip Through-the-door
operators Enclosures
Three-phase line side connecting links
Frame Size
B = 45 mm D = 55 mm
Standards and Certifications
CE approved
UL listed File No. E245398
UL 508 group motor and Type E compliant
IEC/EN 60947
CSA File 229767, Class 3211-05
DIN VDE 0660 Part 100, Part 101 and Part 102
Trip Class
C1 = Class 10 Blank = Magnetic only (no thermal trip)
31
31
31
31
31
31
31
31
31
31
31
31
31
31
31
31
31
31
31
31
Reference
Refer to Tab 27 of this volume, section 27.1 for additional Product information.
Manual Motor Protectors Tab Section
Product Identification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27.1
Product Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27.1
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27.1
Technical Data and Specifications . . . . . . . . . . . . . . . . . . . 27.1
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27.1