Cutler Hammer, Div of Eaton Corp KD3400 Technical Data

FRED# 296
TD00301003E
MOLDED CASE CIRCUIT BREAKER
APPLICATION ON GROUNDED
B-PHASE SYSTEMS
Occasionally you may have an application that is a delta voltage source with a grounded “B” phase, also known as corner grounded. Eaton Corporation literature states “for all 3 phase delta grounded B phase applications, refer to Eaton Corporation.” Following are sketches of what the voltage source looks like with a breaker applied.
Std. 2 Pole Breaker (Fig 1) 2 or 3 Pole breaker with
Unprotected Ground Phase. Protected Single Phase Load
(Fig 2)
2 Phases Protected 3 Phase Load
Std 3 Pole Breaker (Fig 3) Std 3 Pole Breaker (Fig 4)
Protected Single Phase Load
(Use outside poles when 2 poles of a 3 pole breaker are used)
Sizing a breaker for application in a Grounded B-Phase Delta system is different from sizing a breaker for application in a solidly grounded or low-resistance grounded wye system because the phase to ground interrupting duty requirement of an individual breaker pole is different for each case.
A) In a grounded B-Phase System case, a single-line-to-ground fault occurring
downstream of the breaker must be interrupted by a single pole of the breaker with full line-to-line voltage across that single interrupting pole.
B) In a neutral-grounded wye system, solidly-grounded or low-resistance
grounded; a downstream single-line-to-ground fault must likewise be interrupted by a single pole of the breaker, but in this case with only line-to­neutral voltage across that single interrupting pole.
This is the difference which determines the values of the following application data table:
Protected 3 Phase Load
1 6/22/2009
PHASE TO GROUND INTERRUPTING RATINGS
MOLDED CASE CIRCUIT BREAKERS IN GROUNDED B-PHASE SYSTEMS
INTERRUPTION RATING,
CLASSIC
EB 5 EHB 18 10 FB 18 10 8.6 HFB 65 10 8.6 CA, CAH, HCA * 10 JA, KA 25 15 10 HKA 65 15 10 JB, KB, HKB 18 10 LB, LBB, HLB 25 10 DA 25 LA, LAB, HLA 400A 42 15 10 LA, LAB, HLA 600A 30 10 8.6 LC, HLC 30 10 8.6 LCL 65 MA, HMA 42 12 10
MA, HMA W/CERAMIC ARC CHUTES
MC, HMC 42 12 10 NB, HNB 25 12 NB TRI-PAC 75 NC, HNC 25 12 PB, PC 65 25 20 PB TRI-PAC 100
Series C
GHB, GHC 14 GD 22 8.6
ED, EDH, EDC 10 EHD 14 10 FDB 14 10 10 FD, JD, JDB, KD,LD, LDB, CLD 35 10 10 HFD, HJD, HKD, HLD, CHLD 65 10 10 FDC, JDC, KDC, LDC, CLDC 100 10 10
MDL, CMDL 50 10 10 HMDL, CHMDL 65 10 10 ND, CND 50 14 14 HND, CHND 65 14 14 NDC, CNDC 100 14 14 NDU 150 14 14
240 VAC
42 15 10
kA
480
VAC
600
VAC