All rights, including those of translation, reserved.
No part of this manual may be reproduced, stored in a retrieval system, or transmitted in any
form or by any means, whether electronic, mechanical, photocopying, micro-filming,
recording, or otherwise, without the prior written permission of Eaton Industries GmbH, Bonn.
and
product
names
are
trademarks or registered trademarks of their respective
Subjecttoalteration.
DANGER!
Dangerous ElectricalVoltage!
Before starting with the installation
l Installationrequires qualified electrician
l Disconnectthe power supply of the device.
l Secure against retriggering
l Verify isolationfrom thesupply
l Groundandshort-circuit
l Cover or enclose any
neighboringlive parts.
l Follow the engineering instructions (IL) of the device
concerned.
l Only suitably qualified personnel inaccordance with
EN 50110-1/-2 (VDE 0105 part 100) may work on this
device/system.
l Beforeinstallationandbeforetouchingthe device
ensure that you are freeof electrostatic charge.
l Thefunctional earth (FE) must be connected tothe
protective earth (PE) or to theequipotential bonding.
Thesystem installer is responsiblefor implementing
this connection.
l Connectingcables andsignallines should be
installed so that inductive or capacitive interference
does not impair the automation functions.
l Installautomation devices and relatedoperatingele-
ments in sucha way thatthey are wellprotected
against unintentionaloperation.
l Suitablesafety hardware and software measures
shouldbe implemented for the I/O interfaceso that a
lineor wire breakageon the signal sidedoes not result in undefinedstates in the automation devices.
l Deviations of the mains voltage from the nominal
value must not exceed the tolerancelimits given in
the specifications, otherwise this may result in malfunctionandhazardous states.
l Emergency-Stop devices complying with IEC/EN
60204-1 must be effective inall operatingmodes of
the automation devices. Unlatching the emergency
stop devices must notresult inan automatic restart.
l Built-in devices for enclosures or cabinets must only
be run and operated in an installed state; desktop
devices andportable devices only whenthe housing
is closed.
l Measures shouldbe taken toensure the proper
restartingof programs interruptedafter a voltage dip
or outage. This should not result indangerous operating states even for a short time. If necessary, emergency stop devices should be implemented.
l Wherever faults in the automation system may
cause damage topersons or property, externalmeasures must be implemented toensure asafe operating statein the event ofa fault or malfunction (for
example,by means of separate limit switches, mechanicalinterlocks, etc.).
I
Table of Contents
easyE4 Manual1
Imprint2
Beforestarting withthe installation3
Table of Contents1
0.1About this manual13
0.1.1List of revisions13
0.1.2Target group14
0.1.3Legal disclaimer15
0.1.4Short designations16
0.1.5Writingconventions17
0.1.5.1Warning labels17
0.1.5.2Documents with additional information18
1.easyE4 control relays description19
1.1Use as intended19
1.2Function19
1.2.1Features20
1.3Device models - versions and part nos.22
1.3.1Basic features22
1.3.2Base device versions23
1.3.3I/O expansion versions EASY-E4-...-...E124
1.3.3.1Overview of available easyE4 devices25
1.4Accessory devices27
1.5What the different parts of the part number mean27
Alphabetical index693
List of Figures704
Glossary715
12
easyE4 04/19 MN050009 EN
0.1 About this manual
0.1 About this manual
This manualcontains all the information youwill need in order to use the easyE4 safely
andeffectively.
TheManual easyE4 manualis considered an integral part ofthe devices and must
always be readily availablein the device's close proximity so that users have access
to it.
As an integratedpart, the easySoft 7 Help groups together the relevant sections in the
easySoft 7.
This Manual describes all of thedevices' lifecyclestages: transportation,installation,
commissioning, operation,maintenance, storage, and disposal.
It assumes you have electrical engineering knowledgeand skills.
Make sure to always use thelatest documentationfor your device.
Manual easyE4
MN050009_EN
0.1.1 List of revisions
Thelatest versionof this documentation,as well as additional references, is available
for download on the Internet.
http://www.eaton.eu/doc
Please send any comments, recommendations, or suggestions regarding this document to: AfterSalesEGBonn@eaton.com
Thefollowing significant amendments have been introduced since previous issues:
Real-time clock characteristic curve
Sample program
article no. MEMORY-SUD-A1
AC-... and EASY-E4-DC-4PE1;
added AC, AV, PM, and RE
function blocks
time response, micro SD card
✓
✓
✓
easyE4 04/19 MN050009 EN
13
0.1.3 Legal disclaimer
0.1 About this manual
All the information in this manual has been prepared tothe best of our knowledgeand in
accordancewith thestate of the art. However, this does notexcludethe possibility of
therebeing errors or inaccuracies. We assume noliability for thecorrectness andcompleteness of this information. Inparticular, this informationdoes not guarantee any particular properties.
Do not use the easyE4 before reading and understanding this manual.
It is assumed that the user of this manual is thoroughly familiar with the information
found in the manuals for incorporatingthe controlrelay into automation processes.
Hazards posed by the controlrelay cannot beruledout if thesafety instructions arenot
observed –especially if thecontrol relay is installedand commissioned by inadequately
qualified personnel or if it is usedimproperly. Eaton assumes no liability for any damages resultingfrom cases suchas these.
Theuse of sample programs andof theeasySoft 7 programming softwareis subject to
the following instructions andrules ofuse:
1. The program examples provided were createdto the best of our knowledgeand
belief andin accordance withthe currentstate-of-the-art. The program
examples provided were created to thebest of our knowledgeandbelief and in
accordancewith thecurrentstate-of-the-art. However, errors cannot betotally
excluded,andthe example programs do not cover allfunctionblocks and applications thatare available for thecontrol relays.
2. Electrical engineering skills and know-how are required in order tobe ableto program and commission controlrelays. An incorrectly wiredor incorrectly configured control relay will pose aproperty damagerisk and aninjury hazard when
active components such as motors and pressure cylinders are being driven.
3. When using the providedsample programs andgenerating aprogram with
SWDeasySoft 7, the user has the soleresponsibility to observe the following:
l All relevant rules andpractices for preparing circuit diagrams for the circuit
relays as specifiedin the latest documents for these relays.
l All occupational health and safety andaccident preventiondirectives, stand-
ards, and regulations applicable tothe commissioning,circuit diagram creation for, and use of the control relays for your plannedapplication, in
particular those imposedbyemployers' liability insurance associations
(Berufsgenossenschaften).
l Acknowledgedrule of technology andstate ofscience.
l All other general due diligence regarding the prevention of damages tolife
andphysical conditionof persons as well as materialdamage.
easyE4 04/19 MN050009 EN
15
0.1 About this manual
0.1.4 Short designations
4. The manufacturer cannot accept any liability for any damages thatare caused
by customers not usingthe program examples provided in accordancewith the
conditions of use specifiedhere under points 1 to 3.
Thefollowing general terms are used throughout this manual:
Short designationExplanation
easyE4Entire series, used to refer to all the devices in the product family
EASY-E4-...Used to refer to the devices in the series
EASY-E4-...-12...CX1Base devices from the product family with diagnostic LEDs
EASY-E4-...-12...C1Base devices from the product family with an LCD display and a keypad
Expansions
EASY-E4-...-...E1
All input and output expansions as devices in the product family
For the exact designationfor your easyE4, please refer tothe inscription on
the device.
16
easyE4 04/19 MN050009 EN
1. easyE4 control relays description
1.2 Function
1.2.1 Features
l Logic gates
l Time and counter functions
l Time switchfunctions
l Arithmeticfunctions
l PID controllers
l Control relays with 16-character x 6-line LCD display (128 x 96 pixels) and keypad
available.
l Function expansions canbe implemented withinsertable microSD cards
l Integratedoperatingsystem, canbe loaded
l Built-in Ethernet interface
l Requires little space; can be usedin an upright positionas well
l Device construction for mounting rails
l Programminglanguages: Ladder diagram (LD), Function Block Diagram (FBD),
Structured Text (ST),and easy Device Programming (EDP) on device and in
easySoft 7
easyE4 base devices combinethe functions of a controlrelay and an input device inone
singleunit
TheEthernet port makes it possible to integratethe base device into a network.
This allows thedesignof systems using high-speed controllers with decentralized intel-
ligence.
There is ladder diagram languageversion called easy Device Programming (EDP) that
you can use to put together acircuit diagram on the device.
In the case ofdevices witha display, you can enter the program as a circuitdiagram directly on the deviceby using the corresponding buttons. Youcanalso program it on your
computer with the easySoft 7 programming software program (this optioncan also be
used for base devices without a display).
For example,you can:
l ConnectN/O and N/C contacts inseries andin parallel
l Connectoutput relays and markers.
l Define outputs as coils, impulse relays, rising
or falling edge-triggered relays or as latching relays.
l ...
Youcan use the function blocks to run arithmeticfunctions, comparevalues, count up,
count down, etc. All thefunctionblocks available are provided in a list
20
→ Section"Functionblocks", page 180
If you wish towire a easyE4 device via your PC, i.e. create a circuit diagram, use the
easySoft 7
Make sure to take advantage of theEATON onlinecatalog. Enter "easy" intothe search
box and the catalog will take youdirectly to the correspondingproduct groupin the
Automation,Controlandvisualizationsection.
http://www.eaton.eu/ecat
easyE4 control relays
l Featuring screw terminals and areal-time clock (RTC)
l Canbe expanded withI/O expansions from theeasyE4 series
l Canbe networked using the correspondingEthernet port
1. easyE4 control relays description
1.3 Device models - versions and part nos.
Article no. and type
197211 - EASY-E4-UC-12RC1
197212 - EASY-E4-UC-12RCX1
197213 - EASY-E4-DC-12TC1
197214 - EASY-E4-DC-12TCX1
197215 - EASY-E4-AC-12RC1
97216 - EASY-E4-AC-12RCX1
Description
Base device with display;
12/24 VDC, 24 VAC;
digital inputs: 8, of which 4 can be used as analog inputs;
digital outputs: 4 relay outputs
Base device with diagnostic LED;
12/24 VDC, 24 VAC;
digital inputs: 8, of which 4 can be used as analog inputs;
digital outputs: 4 relay outputs
Base device with display;
24 VDC;
digital inputs: 8, of which 4 can be used as analog inputs;
digital outputs: 4 transistor outputs
Base device with diagnostic LED;
24 VDC;
digital inputs: 8, of which 4 can be used as analog inputs;
digital outputs: 4 transistor outputs
Base device with display;
100 – 240 VAC, 100 – 240 VDC;
digital inputs: 8; digital outputs: 4 relay outputs
Base device with diagnostic LED;
100 – 240 VAC, 100 – 240 VDC;
digital inputs: 8; digital outputs: 4 relay outputs
easyE4 04/19 MN050009 EN
25
1. easyE4 control relays description
1.3 Device models - versions and part nos.
I/O expansion for easyE4 control relays
l Featuring screw terminals
l Canbe networked using the correspondingEthernet port
Article no. and type
197217 - EASY-E4-UC-8RE1
197218 - EASY-E4-UC-16RE1
197219 - EASY-E4-DC-8TE1
197220 - EASY-E4-DC-16TE1
197221 - EASY-E4-AC-8RE1
197222 - EASY-E4-AC-16RE1
197223 - EASY-E4-DC-6AE1
197224 - EASY-E4-DC-4PE1
Description
12/24 V DC, 24 V AC,
digital inputs: 4,
digital output: 4 relays
12/24 V DC, 24 V AC,
digital inputs: 8,
digital output: 8 relays
24 V DC,
digital inputs: 4,
digital output: 4 transistors
24 V DC,
digital inputs: 8,
digital output: 8 transistors
100 - 240 V AC, 100 - 240 V DC, digital inputs: 4,
digital output: 4 relays,
100 - 240 V AC, 100 - 240 V DC, digital inputs: 8,
digital output: 8 relays
24 V DC,
analog inputs: 4,
analog outputs: 2
with temperature measuring
Pt100, Pt1000 or Ni1000
24 VDC;
analog inputs: 4;
outputs: None
26
easyE4 04/19 MN050009 EN
1.4 Accessory devices
1. easyE4 control relays description
1.4 Accessory devices
In additionto I/O expansions, thereare additional accessories available for easyE4
base devices.
NOTICE
Only use original accessories.
Order accessories throughyour supplier or throughthe EATON
onlinecatalog
www.eaton.eu/ecat
Example:
Article no. and typeDescription
191087 - MEMORY-SDU-A1microSD
2 GB memory card with adapter, I Grade, without an operating system
Consists of three (3) connectors and three (3) end covers for the easyE4 series
between the control relay and input/output expansions
1.5 What the different parts of the part number mean
Thepart number includes information that specifies the version and model of thespecific device beingused.
ThePart number can be foundat the front of theeasyE4.
Table 2: Part number for screw terminal devices
easy-E4 - .C- .....- x1(P)
Power
rating
Type of
supply
voltage
Number
of inputs/outputs
Type of output
R-Relay
T-Transistor
A-Analog
P-Temperature
E-Expansion
CX-Base device with LED diagnostics
C-Base device with display
and buttons
1-Version
P-Model with push-in terminals instead of screw terminals
easyE4 04/19 MN050009 EN
27
1. easyE4 control relays description
1.6 Nameplate
1.6 Nameplate
Thedevicecan be identifiedby checking the nameplate on its side.
This nameplate includes thefollowing information:
l Manufacturer
l Version
l Operational voltage
l Heat dissipationinformation
l Type approval and certification marks andinformation
l Information relevant toUL listing
In additionto thedevice's part number and MAC address, theQR code in the front also
contains additional information:
l Serial number
l Production Date
1.7 Support
To get fast and effective support, make sure to always
provideCustomer Servicewith thefollowing information:
l Part number
l Information from the QR code
l Ambientconditions at the locationof use
l Fuse or other protective element used to protectthe device
l Supply voltage conditions
l If applicable, easySoft 7 build No., version
28
easyE4 04/19 MN050009 EN
1.9 Programming software easySoft 7
easyE4 control relays are designed tobe programmed with the easySoft 7 programming software program. This program was developedspecifically for this series
of devices, andmakes it possible toquickly, conveniently, and easily integrateavailable
functions intoa circuit diagram anduse theresult as a controlprogram.
Theprogram is available free ofcharge. However, you willneeda software license in
order to beableto use all of its functions.
easySoft 7 can also beused to:
l Test your circuit diagram by simulating the power flow (offline test).
l Transfer your circuit diagram to aconnected and operational easyE4 base device.
l Monitor the power flow andview operand states after transferring the circuit dia-
gram (online test)
l Print out your circuit diagram so thatyou candocument it indetail
1. easyE4 control relays description
1.9 Programming software easySoft 7
In addition, theprogram makes it possiblefor you to use apassword toprotect your projects and,accordingly, your know-how.
TheeasySoft 7 Helpis an integral part of easySoft 7 andis designed tohelp you use the
programming software.
Tutorials
For helpfulvideos that explain how to use specific functions, please visit theproduct
page at http://www.eaton.eu/easy.
Application examples
Support has provided anumber of applications that areavailable for download as ZIP
files from the Software DownloadCenter.
These examples come with a task description,the circuit diagram, and the easySoft 7
project (in the EDP and LD programming languages as of this writing).
easyE4 04/19 MN050009 EN
31
1. easyE4 control relays description
1.10 Safety regulations
1.10.2.5 Prerequisites for proper operation
In order for thedeviceto beableto meetthe contractually stipulated terms, thefollowingmust be observed:
l Only qualifiedpersonnel should be allowedto work with thedevice.
l Thepersonnel workingwith thedevicemust have readandunderstood all doc-
uments for the device and must follow all the instructions inthem.
l Therequired ambient conditions must be met.
l Maintenance work must be carriedout correctly.
We assume noliability for damages, consequential damages, and/or accidents caused
by thefollowing:
l Failureto follow any applicableoccupational health and safety rules, standards,
and/or regulations
l Device failures or function disturbances
l Improper use and/or handling
l Not following the instructions or observing the information in the documentation for
the device
l Alterations, changes, and repairs to thedevice
Make sure to readthe → "Legaldisclaimer", page 15.
34
easyE4 04/19 MN050009 EN
1. easyE4 control relays description
1.11 Engineering
1.11 Engineering
TheeasyE4 series makes it possible to combine multiplevoltagevariants. Each easyE4
base devicecan be wiredwith up to 11 EASY-E4-...-...E1 expansions withdifferent
power supplies.
1.11.0.1 Length of input cables
Severe interference can cause asignal 1 on theinputs withouta proper signal being
applied. Observe therefore the following maximum cablelengths:
Base device inputs I1–I6
l 40 m for AC supply voltages; 100 m for DC supply voltages
Base device inputs I7–I8
l 100 m for AC supply voltages; 100 m for DC supply voltages
Expansion device inputs
l 40 m for AC supply voltages; 100 m for DC supply voltages
In addition, thefollowingapplies to base devices andexpansion devices:
With longer cables, connect a diode (e.g.1N4007) with aminimum reverse voltage of1
kV anda let-through current of 1 A in series to the device inputs. Ensure that the diode
is pointing tothe input; otherwise the device will not be able to detect the 1 state.
38
easyE4 04/19 MN050009 EN
1. easyE4 control relays description
1.11 Engineering
Input signal voltagerange
l Off signal: 0 to 40 V.
l On signal:79 to 264 V
Input current
l I1 to I8: 0.5 mA/0.25 mA at 230 V/115 V.
In addition, thefollowingapplies to AC expansiondevices:
With longer cables, connect a diode (e.g.1N4007) with aminimum reverse voltage of1
kV anda let-through current of 1 A in series to the device inputs. Ensure that the diode
is pointing tothe input; otherwise the device will not be able to detect the 1 state.
easyE4 04/19 MN050009 EN
41
1. easyE4 control relays description
1.11 Engineering
42
easyE4 04/19 MN050009 EN
2. Installation
2.2 Unpacking and checking the equipment supplied
2.2 Unpacking and checking the equipment supplied
Check the easyE4's packaging for transit damage.
Carefully remove the packaging in order toavoid damaging the device.
Check the packagecontents for visibletransit damage.
Use the information in Installation instructions to make surethat the contents are
complete.
Keepthe original packagingso that youwill beableto use it in the
futureif you needto transport or ship the device.
Make sure to also keepthe documents enclosedwith thedevice
and/or togive them to the end customer.
1. Take thebase device's endcover and install it on the right sideof the last expansion.
There willbe the following electricalisolation at the localexpansionconnection
between the base device and the expansiondevice:
l Basic isolation 400 V AC (+10 %).
l Safeisolation 240 V AC (+10 %).
Basic device and expansionunitcan be provided with differentpower supplies.
easyE4 04/19 MN050009 EN
51
2. Installation
2.4 Connection terminals
Table 4: AC phase assignment
EASY-E4-AC-...
EASY-E4-AC-...
-12RC1, -12RCX1
16RE1
-8RE1
LN I1-I8I1-I4I5 - I 8
L1
L1L1L1
N
L1L1L1L2
L1L1L1L3
L2
L2L2L2
L2L2L2L1
N
L2L2L2L3
L3
L3L3L3
N
L3L3L3L1
L3L3L3L2
58
easyE4 04/19 MN050009 EN
2. Installation
2.4 Connection terminals
Project view
Figure 27: "Expansion parameter" tab
Thetemperature sensor connections determinewhich inputs willbe used. Upto four different RTD sensors of type Pt100, Pt1000, or Ni1000 with anindividual temperature
rangecan beconnected to eachEASY-E4-DC-4PE1 expansiondevice.
Inputs that do not have a sensor connectedto them will be"undefined."
By default, all inputs will beundefined andaccordingly will be switched off.
Thetemperature ranges for theEASY-E4-DC-4PE1 dependon the selectedsensor.
Values will be represented as a signed decimal with the following resolution (withthe
specifics dependingon the selectedformat):
Look
Sensor
style
Temperature
value
in °C
Indicated value at selected representation
Degrees Celsius °CDegrees Fahrenheit °F
Nonlinear
value
1/1011/101
Pt100,
Pt1000
Pt100,
Pt1000
Pt100,
Pt1000
Ni1000-50 up to +100-500 up to
Ni1000-50 up to +250-500 up to
-100 up to +200-1000 up to
2000
-100 up to +400-1000 up to
4000
-100 up to +800-1000 up to
8000
1000
2500
-100 up to
+200
-100 up to
+400
-100 up to
+800
-50 up to +100 -580 up to
-50 up to +250 -580 up to
-1480 up to
+3920
-1480 up to
+7520
-1480 up to
+14720
+2120
+4820
-148 up to
+392
-148 up to
+752
-148 to +14720 – 4095
-148 up to
+212
-148 up to
+482
0 - 4095
0 – 4095
0 – 4095
0 – 4095
68
easyE4 04/19 MN050009 EN
2. Installation
2.4 Connection terminals
Theselected scalingand update settings will apply toall the temperature inputs in the
corresponding module.
Thescalingandthe unit (Celsius, Fahrenheit) can be selectedfor inputs T1 throughT4. If
no scaling is specified, the corresponding raw value willbe given witha 12-bit resolution(dimensionless, 0 – 4095).
Readingscaling: The scaling
Update - Sampling time for all inputs being used:
l 250 ms (no averaging)
l 1 s (averaging over 4 measuring cycles)
l 2.5 s (averagingover 10 measuring cycles)
l 10 s (averaging over 40 measuringcycles)
As soon as the device is switched on, the temperature willbe measured and transmitted by all active sensors. However, thereading will not beaveraged untilafter the
set samplingtime.
Theexpansionmodulefeatures a DIAG output for function monitoring and diagnostic
purposes. This means that each temperature input can be individually mappedto an
operandwithin arangeof ID25 to ID96.
Designation Event
DIAGGeneral diagnostic indicating that a diagnostic event is present
DIAG 1Configured measuring range exceeded at at least one temperature input, or connection cable dis-
continuity
DIAG 2Configured measuring range fallen below at at least one temperature input, or a short-circuit has
Every easyE4 base device features an Ethernet port.
This Ethernet port is aCat 5 port.
Make sure to use compatiblestandard RJ45 Ethernet cables only.
TheEthernet port on the base device serves as a communication interface.
TheEthernet controllers support transfer rates of 10Mbit/s and 100Mbit/s.
Figure 32: RJ-45 socket, 8-pole
If you integratethe EASY-E4-...into an Ethernet network, you
will needto connect the functional earth to thecorresponding
terminal.
To commission the communications between the EASY-E4-... controlrelay and the
deviceto which the Ethernet cable is connected, follow the description for theconnected device.
easyE4 04/19 MN050009 EN
75
2.6 Programming software license
Theprogrammingsoftware (version 7 and higher) is available for download.
Please note that easyE4 devices can only beprogrammed with easySoft 7.
TheeasySoft 7 programming software program is available for free. However, you will
need tobuy a softwarelicense inorder to beable touse allof the software's functions.
Onceyou purchase asoftware license, you willreceive a license product certificate
thatyou canthenuse to request a license key online.This license key can be usedto
unlock all ofthe software's functions.
Installationrequirements
2. Installation
2.6 Programming software license
Youcan order an easySoft 7 programming software license throughyour
supplier or throughthe EATONonlinecatalogEASYSOFT-SWLIC, article
no.197226.
http://www.eaton.eu/ecat
l An easySoft 7 version
l A PC that meets allsystem requirements and for whichthe person installing the
software has administrator privileges
l A 24-digit license key
If a validkey is not entered duringinstallation, the softwarewill
be installedin demo mode.
This means thatthe softwarewill befully installed, but withthe
following limitations:
l Youwill not beableto loadany programs onto a connected
device(no online function)
l There willnot be any cardmanager functions availablefor
the microSD memory card
However, you will still be able to simulateprograms.
Youcan always add alicense key later on.
easyE4 04/19 MN050009 EN
77
2. Installation
2.6 Programming software license
2.6.1 System requirements
HardwareSoftware
l Recommendedminimum resolution of
1280 x 1024 pixels
l Min.250 MB of free space on the hard
drive
2.6.2 Licensing
Whenyou purchase an EASYSOFT-SWLIC (order No. 197226), you will be purchasing a
license product certificatefor easySoft 7.
This license product certificate will include a 36-digit certificate number
thatyou canuse to request a24-digit license key online.
One of thefollowing operatingsystems:
l Windows 7 (32 + 64 Bit) >=SP1,
l Windows 8/8.1 (32 + 64 Bit) or
l Windows 10 (32 + 64 Bit)
Duringthe installationprocess, you will beasked for the 24-digitlicense
key for your easySoft 7. If you do not enter alicense key, theprogram will
be installedin demo mode.
Youcan add alicense key at a later point if necessary.
78
Figure 35: License product certificate
easyE4 04/19 MN050009 EN
2.6.2.1 Getting a license key
2. Installation
2.6 Programming software license
To get a license key with your license product certificate,follow the instructions at:
http://www.eaton-automation.com/license
Figure 36: Input screen for the license product certificate No.
Onceyou enter the36-digit certificate number from your license product certificate, a
dialogbox will appear. For your own security, enter the owner information into this dialogbox.
Onceyou enter all your information,a 24-digit license key will be sentto thee-mail
address you provided.
Thee-mail willcontainthe following information:
l License type:SW-EASYSOFT
l License product certificatenumber:7-digit number for your certificate
l License key: Automatically generated24-digitcode
l Information regarding the owner's registration
The24-digitlicense key is requested duringthe installationprocess.
easyE4 04/19 MN050009 EN
79
2. Installation
2.6 Programming software license
2.6.3 Adding a license key later on
If you installed the demo versionof easySoft 7, youcanadd a valid license key later on
in order to unlock the full version.
Go toeasySoft 7 the? menu and click onLicense.
A dialogbox for entering the license key will appear.
Figure 37: License dialog box
Now enter the24-digit license key
thatyou received by e-mail.
80
easyE4 04/19 MN050009 EN
2.6.4 Software updates and hardware changes
Onceyou have licensed the programming software,you candownload the latest
easySoft 7 version from the EatonDownloadCenter - Software and installit – the
license information willremain.
If you changehardware,use your license key and redeem it again.
easySoft 7 can check whether there are any updates for the version installed. This
requires for the PCto have anactive Internet connection.
Menu?
2. Installation
2.6 Programming software license
Figure 38: Options in ? menu
easyE4 04/19 MN050009 EN
81
2. Installation
2.6 Programming software license
2.6.5 Installation instructions
Beforestarting withthe installation, close all open applications.
To install easySoft 7, you will need to have local admin privileges for your system.
Download
Download the full version of the easySoft 7 program from the Software Download
Center.
Select the "Software" category, thenthe easySoft 7 software, thenthe product version, and finally your language.
Click on the product version you want in order todownload it.
Download Center - Software
http://www.eaton.eu/software
Save the installationpackage file on your PC.
Installation
Duringthe installationprocess, you will beasked for the 24-digit
license key for your easySoft 7. Ifyou donot enter alicense key,
the program willbe installed indemo mode.
Youcan add alicense key later onif necessary.
Follow the on screen instructions of the installationpackage.
Figure 39: Step 1
82
easyE4 04/19 MN050009 EN
2.6 Programming software license
Figure 40: Step 2 License agreement
Youcan also print out theterms of use in their entirety.
2. Installation
Figure 41: Step 3 License key
To install the full version of the software,enter your 24-digitlicense key here.
If a validlicense key is notentered duringinstallation, the softwarewill be
installed in demo mode.
Youcan add alicense key later on– please refer to→ Section"Addinga
license key later on", page 80.
Figure 42: Step 4 Destination folder
Shows thepath where theprogram files willbe stored.
easyE4 04/19 MN050009 EN
83
2. Installation
2.6 Programming software license
Youcan click on Browse...to set adifferent storage locationwhere you want the
easySoft 7 programming softwareprogram to beinstalled.
Figure 43: Step 4.1 Changing the destination folder
Figure 44: Step 4.2 Creating your own destination folder
Figure 45: Step 6 Starting the installation
A confirmation prompt willappear.
Theinstallationwill start as soon as you confirm this prompt.
Figure 48: easySoft 7 icon depending on the screen resolution
easyE4 04/19 MN050009 EN
85
2. Installation
2.6 Programming software license
86
easyE4 04/19 MN050009 EN
3. Commissioning
3.3 Switch on
3.3 Switch on
Beforeswitching the device on, check the power supplies, inputs, outputs, and any
expansion devices and Ethernet connections tomake sure thatthey are properly connected.
3.3.1 Startup behavior of easyE4 control relays with LED indicators
If there is no program, the control relay will start in STOP mode.
These devices without a display and controls feature 2 LEDs that indicate the stateof
the Ethernet port and the devicestatus.
If there is an executable program on the easyE4 controlrelays, the device will start in
RUN mode.
In additionto having avalid program on the control relay,
please make sure that there are noperipheral faults that will
lead toSTOP mode.
Device models without a display feature LED indicators inthe front:
l 1. POW/RUN
l 2. ETHERNET (base devices only)
Figure 49: LED indicators on EASY-E4-...-12...CX1
LED POW/RUN base device
ThePOW/RUN LED indicates thestate ofthe POWpower supply as well as the STOP
or RUN state.
OffMalfunction or no supply voltage
Green, continuous light Supply voltage OK, RUN mode
Green,
Flashing, 1 Hz
Green,
Flashing, 4 Hz
Supply voltage OK, STOP mode
Fault at one of the expansions,
between the easyE4 device and the EASY-E4-CONNECT1 connector
88
easyE4 04/19 MN050009 EN
3. Commissioning
3.3 Switch on
LED ETHERNET/NET (base device only)
OffNo Ethernet cable connected; supply voltage off
The port is not enabled; the easyE4 device does not have an IP address
Yellow, continuous lightEthernet cable connected
Green, continuous lightThere is an IP address, but the NET has not been configured
Red, continuous lightEthernet conflict or error, e.g.: duplicate IP address, address collision
Green, flashing,
2 flashes, pause, etc.
Green, flashing,
1 flash, pause, etc.
LED POW/RUN status expansion unit
OffMalfunction or no supply voltage
Green, continuous lightSupply voltage OK, address assigned, expansion bus working correctly
Green,
Flashing, 1 Hz
Green,
Flashing, 3 Hz
Green,
Flashing, 10 Hz
Green,
Flashing, 0.5 Hz
NET data flow working; one or more NET stations missing
NET data flow working; all NET stations working
Supply voltage OK, no data exchange with base device
Supply voltage OK, no data exchange with base device,
diagnostic bit will be set, device not working
Device waiting for firmware update
Firmware update active
easyE4 04/19 MN050009 EN
89
3. Commissioning
3.3 Switch on
3.3.2 Startup behavior of easyE4 control relays with a display and keypad
If there is no program, the control relay will start in STOP mode.
All the information on the display willbe shown in English if the device is configured
with its factory settings.
If there is an executable program on the easyE4 controlrelays, the device will start in
RUN mode.
In additionto having avalid program on the control relay,
please make sure that there are noperipheral faults that will
lead toSTOP mode.
easyE4 base device with integrated display
l If there is no splash screenon the memory card
after beingswitched on, the easyE4 base device willshow
the Eatonlogoandthen the status display. This status display provides information on the device's status.
l If there is a splash screen on the memory card
after beingswitched on, the easyE4 device willshow the
splash screen and thenthe status display. This status display provides information on the device's status.
If there is no executable program on the easyE4 controlrelays, the device will start in
STOP mode.
All the information on the display willbe shown in English if the device is configured
with its factory settings. Once the device is ready for operation, the status display will
appear.
Figure 50: Example of status display on display
90
easyE4 04/19 MN050009 EN
3. Commissioning
3.3 Switch on
3.3.4 Status display on easyE4 control relays with display and keypad
After beingswitched on, the easyE4 base device willstart with thestatus display after
the boot logo.
Thestatus display has six lines, with eachone containing 16 characters.
Press the Altbutton toswitch betweendisplays.
Thefirst time you press ALT, the time will be replaced by the date.
Pressing the ALT buttonagain will switch to display 2
RowStatus indicator 1Status indicator 2
1
2
3
4
5
6
Figure 53: Start displays for easyE4 base device in English
Status indicator 1
Line 1The Ethernet status for the base device without LED indicators will be shown for diagnostic purposes
I........Inputs; the number will be shown during activity (1, 2, 3,..,8)
EOFThe Ethernet port is not enabled;
no Ethernet cable connected; supply voltage off
The port is not enabled; the easyE4 device does not have an IP address
ECNEthernet cable connected
EOKThere is an Ethernet IP address, but the NET has not been configured
ENWNET data flow working; all NET stations working
ENMNET data flow working; one or more NET stations missing
EEREthernet conflict or error, e.g.: duplicate IP address, address collision
Line 2Settings in current program
RERetention active
IDebounce active
NTNET stations with NET ID (1 this case)
DCUsed to display the type of power used by the base device (AC or DC)
PP Buttons inactive (-) or active (+)
Line 3Current device setting
WDWeekday
hh:mmDevice time
1xALTDD-MM-YYYDisplays the device date with the configured format
STConfigured startup behavior for the device;
nothing displayed – automatic starting is possible
94
Line 4
qOutputs; the number will be shown during activity (1, 2, 3, etc.)
RUN/STOPCurrent device operating mode
easyE4 04/19 MN050009 EN
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.