Culligan AQUA-CLEER BXL Series, AQUA-CLEER BXL PLUS Series Installation And Operating Instructions Manual

Page 1
MG10 R/O WATER FILTRATION SYSTEM
Rev. D 1/24/01
DCO#1521
Installation
and
Operating
Instructions
AQUA-CLEER
®
SERIES BXL and BXL PLUS
WATER TREATMENT SYSTEMS MODELS FROM JUNE 2000
©2001 Culligan International Company
Printed in USA
Page 2
Attention Culligan Customer:
MG10 R/O WATER FILTRATION SYSTEM
Your local independently operated Culligan dealer employs trained service and maintenance personnel who are experienced in the installation, function and repair of Culligan equipment. This publication is written specifically for these individuals and is intended for their use.
We encourage Culligan users to learn about Culligan products, but we believe that product knowledge is best obtained by consulting with your Culligan dealer. Untrained individuals who use this manual assume the risk of any resulting property damage or personal injury.
WARNING - Prior to servicing equipment, disconnect power supply to prevent electrical shock.
CAUTION: Do not use with water that is microbiologically
unsafe or of unknown quality without adequate disinfection before or after the system.
WARNING: IF INCORRECTLY INST ALLED, OPERA TED OR
MAINT AINED, THIS PRODUCT CAN CAUSE SEVERE INJURY . THOSE WHO INSTALL, OPERATE, OR MAINTAIN THIS PRODUCT SHOULD BE TRAINED IN ITS PROPER USE, WARNED OF ITS DANGERS, AND SHOULD READ THE ENTIRE MANUAL BEFORE A TTEMPTING TO INST ALL, OPERA TE, OR MAINT AIN THIS PRODUCT .
Page 3
Installation
MG10 R/O WATER FILTRATION SYSTEM
and
Operating
Instructions
AQUA-CLEER
®
SERIES BXL and BXL PLUS
WATER TREATMENT SYSTEMS MODELS FROM JUNE 2000
Table of Contents
Introduction ............................................................... 2
Specifications ........................................................... 5
Installation................................................................. 6
Operation .................................................................14
Service and Maintenance .........................................16
Parts List .................................................................24
Electrical Schematic ................................................31
Wiring Diagram ........................................................33
Page
Page 4
Introduction
MG10 R/O WATER FILTRATION SYSTEM
Culligan® Aqua-Cleer® Series BXL and BXL Plus reverse osmosis systems are designed to meet the needs of applications for high quality water. This manual contains important information about the unit, including informa­tion needed for installation, operating, and maintenance procedures. A troubleshooting section provides a guide for quick and accurate problem solving.
In order for the water treatment system to continue to provide high quality water, a thorough understanding of the system and its operation is required. Review this manual before making any attempt to install, operate or service the system. Installation or maintenance done on this system by an untrained service person can cause major equipment or property damage.
This publication is based on information available when approved for printing. Continuing design refinements could cause changes that may not be included in this publication.
SAFE PRACTICES
Throughout this manual there are paragraphs set off by special headings.
NOTICE: Notice is used to emphasize installation, operation or maintenance information which is important, but does not present any hazard.
Example: NOTICE: The nipple must extend no more than 1 inch above the cover plate.
CAUTION: Caution is used when failure to follow directions could result in damage to equipment or
property. Example:
CAUTION: Disassembly while under water pressure can result in flooding.
WARNING: Warning is used to indicate a hazard which could cause injury or death if ignored. Example:
WARNING! ELECTRICAL SHOCK HAZARD! UNPLUG THE UNIT BEFORE REMOVING THE TIMER MECHANISM OR COVER PLA TES!
The CAUTION and WARNING paragraphs are not meant to cover all possible conditions and situations that may occur. It must be understood that common sense, caution, and careful attention are conditions which cannot be built into the equipment. These MUST be supplied by the personnel installing, operating or maintaining the system.
Be sure to check and follow the applicable plumbing codes and ordinances when installing this equipment. Local codes may prohibit the discharge of acid or caustic solutions to drain. An extra solution tank should be used to neutralize the solution before discharging to drain.
Use protective clothing and proper face or eye protection equipment when handling chemicals or power tools.
SERIAL NUMBERS
The Culligan Series BXL system has two serial number labels, one for the entire plumbing assembly and one for the RO module assembly. The plumbing assembly serial number label is located on the top right-side of the panel. The RO module serial number is located on the modules. Do not remove or destroy these serial number labels. They must be referenced for warranty parts replacement.
REVERSE OSMOSIS
In order to understand reverse osmosis, we must first define osmosis. Osmosis is the passage of a liquid through a semi-permeable membrane. A semi-permeable membrane is a membrane which allows one component of a solution
2 AQUA-CLEER SERIES BXL AND BXL PLUS
Page 5
to pass through it and not the others. In osmosis, there is a tendency for a liquid to go from an area of less
MG10 R/O WATER FILTRATION SYSTEM
concentration to an area of more concentration through a semi-permeable membrane. Figure 1 shows the osmotic process.
If pressure is applied to the concentrated solution, reverse osmosis will take place. The pressure causes a flow through the semi-permeable membrane into the dilute solution. The semi-permeable membrane acts as a barrier to ions and does not allow them to pass through into the dilute solution. When applied to water, this means that the product water has a reduced total dissolved solids (TDS) content as a result of the passage of water molecules through the membrane while the mineral ions are rejected. (Figure 2)
Note: Numbers used in these examples may not reflect those of your unit.
FIG. 1 FIG. 2
REJECTION AND RECOVERY
Feed water entering the system is split into two streams, a product stream and a concentrate stream (Figure 3).
During the process of reverse osmosis, some of the water has its dissolved solids content reduced by approximately 96%. This high quality product water is sent to service.
FIG. 3
The rest of the feed water contains the total dissolved solids removed from the product water, in addition to the total dissolved solids already present in the feed water. This concentrate water is sent to drain.
The amount of total dissolved solids rejected by the system is expressed as a percentage. A 90% rejection means that 90% of the total dissolved solids have been removed from the feed water by the system. To calculate the percent rejection, use the following equation:
(Feed TDS - Product TDS)
Feed TDS
x 100 = % Rejection
where Feed TDS is the total dissolved solids content of the water going into the system, and Product TDS is the total dissolved solids content of the high quality product water.
Example - If the Feed TDS is 600 ppm and the Product TDS is 24 ppm.
(600 - 24)
The amount of high quality water recovered for use as a percentage of the water fed into the reverse osmosis system is called percent recovery . Use the following equation to calculate percent recovery:
Product Water Flow Rate
Feed Water Flow Rate
x 100 = 96% Rejection
600
x 100 = % Recovery
INTRODUCTION 3
Page 6
NOTICE: The feed water flow rate is equal to the product water flow rate plus the concentrate water flow rate,
MG10 R/O WATER FILTRATION SYSTEM
both of which are easily measured.
Example - If the product flow rate is 0.7 gallons per minute and the concentrate flow rate is 0.55 gallons per minute,
0.7
x 100 = 56% Recovery
(0.7 + 0.55)
CAUTION: An understanding of rejection/recovery percentages is essential for
monitoring and evaluating the performance or condition of the reverse osmosis system. DO NOT operate the system before becoming familiar with these concepts.
FEED WATER LIMITS
Before starting the installation, verify that the feed water meets the limits shown in T able 1, and that a water softener is used for pretreatment.
TABLE 1 - FEED WATER LIMITS
Property Minimum Maximum
Turbidity (NTU) 0.0 1.0 pH* 6 11 Chlorine (ppm) 0.0 0.1 Total Dissolved Solids (ppm) 50 2500 Temperature (°F) 33 100 Silt Density Index 0.0 5.0 Iron (ppm) 0.0 1.0
* Short term cleaning is acceptable for pH ranges between 2.0 and 12.0. Additional treatment is required when chloramines are present and the pH levels exceed 9.0.
NOTICE: In some applications, a water softener is not required. Consult the independently operated Culligan
dealer for further information on these special applications.
4 AQUA-CLEER SERIES BXL AND BXL PLUS
Page 7
SERIES BXL/BXL PLUS SPECIFICATIONS
MG10 R/O WATER FILTRATION SYSTEM
B-2XL B-3XL B-4XL
Dimensional, Pump Assembly
Width - in [mm] 32 [813] Depth - in [mm] 13 [330] Height - in [mm] 11 [280]
Dimensional, Module Assembly
Width - in [mm] 42 [1067] Depth - in [mm] 6 [153] Height - in [mm] 17 [432]
Unit Connections
Inlet (Tube) 0.5" Product (Tube) 0.375" Concentrate (Tube) 0.188"
Electrical
Motor Horsepower (hp) [kW] 3/4 [1.08] Power Requirement (VAC/Hz/phase) 115/60/1 Full Load Current (amp) 9.0
Specifications
Hydraulic-Prefilter
Housing Quantity 1 Cartridge Quantity 1 Cartridge Size - (in) [mm] 10 [254] Cartridge Rating (micron) 5
Hydraulic - RO
RO Housing Quantity 2 3 4 RO Element Quantity 2 3 4 RO Element Length in [mm] 40 40 40 Product Flow gpm [L/min]* 0.80 [3.03] 1.17 [4.43] 1.53 [5.79] Concentrate Flow gpm [L/min]* 0.80 [3.03] 1.17 [4.43] 1.53 [5.79] Operating Weight lb [kg] 75 [34] 84 [38] 93 [42]
Recovery (%)*
Design 50 50 50 Minimum 40 40 40
Maximum Feed Pressure psig [kPa] 250 [1723] Maximum Product Pressure psig [kPa] 40 [275] Maximum Temperature °F [°C] 100 [38]
Inlet Pressure
Minimum, dynamic psig [kPa] 20 [138] Maximum, dynamic psig [kPa] 75 [517] Maximum, static psig [kPa] 100 [689]
Required Inlet Feed Flow gpm [L/min] 1.60 [6.06] 2.34 [8.86] 3.05 [11.54] Pump Flow @ 225 psi gpm [L/min] 4.0 [15.1] 4.0 [15.1] 4.0 [15.1] Salt Rejection, Min. Initial (%) 98 98 98
*Approximate initial product flow is based on properly pretreated feed water of 600 ppm TDS as NaCl, 77°F temperature, 225 psig applied pressure, and silt density index below 3 supplying water to atmosphere. Productivity will vary depending on other feed water conditions.
SPECIFICATIONS 5