C-TEC CFP702-4, CFP704-4, CFP708E-4, CFP708-4 Installation Instructions

Application Note 0005.0
ESCAPE ACCESS
How to put a CFP Panel into Walk T e s t Mo de
To put a CFP fire panel into walk test mode:
1. First, you must remove the panel lid to access the PCB (see Fig. 1).
button
ZONE LEDs
NEXT OPTION
button
ENABLE/DISABLE
button
PROGRAMMING
2. At the bottom of the PCB, press the ACCESS LEVEL THREE FUNCTIONS button until the programming TEST LED flashes (see Fig. 2).
ACCESS LEVEL THREE
FUNCTIONS button
TEST LED
LEDs
3. Press the NEXT OPTION button and ZONE1 LED will illuminate but will flash out of sync with
4. If you want to put multiple zones into test repeat step 3.
Approved Document No. DFU0000702 Rev 1 Page 1 of 2
the programming TEST LED. To put zone 1 into a test condition press the ENABLE/DISABLE button and you will now see both ZONE1 LED and programming TEST LED flash in sync.
Application Note 0005.0
5. To finalise your programming you must press ESCAPE ACCESS button and now you will see for any zones in test the ZONE LEDs flashing in sync with the general T EST LED (see Fig. 3).
ZONE LEDs
TEST LED
6. To take zones out of the test condition repeat steps 2 and 3, making sure this time the ZONE LED and the programming TEST LED flash out of sync.
7. Finally, press the ESCAPE ACCESS button and the panel returns to normal condition.
Page 2 of 2 Approved Document No. DFU0000702 Rev 1