DIN-rail digital meter for single
and three-phase electrical systems
Introduction
This unit measures and displays the characteristics of single-phase
two-wire, three-phase tree-wire and three-phase four-wire supplies,
including voltage, frequency, current, power and real and reactive
energy, imported and exported.
For more in-depth operating instructions, please refer to the full
manual that is available on the Crompton Instruments website, at
www.crompton-instruments.com.
Measurement
In measurement mode, the buttons control the displayed
measurement as follows:
Selects the Voltage and Frequency display screens.
Successive operations of the button select voltage,
frequency and %THD (Total Harmonic Distortion).
In Set-up mode, this is the ‘Back’ button.
Setup Menu Structure
Change password
nnnn – 4-digit number, default ‘0000’.
Supply system
3-phase 3-wire or 4-wire or single phase.
CT Set the value of the CT primary in use
nnnn – 4-digit number, 0001 to 9999.
dIT - Demand Integration Time
This is the period in minutes over which the current and power
readings are integrated for maximum demand measurement.
Options are: Off, 5, 8, 10, 15, 20, 30 and 60 minutes.
RSETResets cumulative Energy and/or Demand
measurements to zero.
COMS Communication parameters for RS485 interface:
FMT – Format:
Modb Modbus protocol,
Baud rate 2400/4800/9600/19200/38400
Parity none/odd/even
Stop bits 1 (1 or 2 if parity is None)
Network address nnn – 3-digit number, 1 to 247
Order: Norm/Rev – Indicates Modbus word order.
N2Johnson Controls (JC) N2 protocol,
Network address nnn – 3-digit number, 1 to 255.
Rly - Relay pulse output
kWh/kVArh (Active/reactive) Import or Export
Rate 0.001/0.01/0.1/1/10/100/1k/10k kWh or kVArh per pulse
Pulse width 200/100/60 ms.
NRGy - Energy
Unit/kilo/Mega units selection
1% limit on/off. If on, power values <1% of range max. will not
be included in energy measurements (prevents ‘creep’).
Test
Display on – all elements on to check display
dISTG – Display toggle. Each element is turned on and off
Phase sequence (V123 I123).
SOFT
Displays firmware version and build numbers.
Menu Option Selection
1. Use the (up) and (down) keys to select the required
item from the menu. Selection does not roll over between
bottom and top of list.
Selects the Current display screens. Successive
operations select phase and neutral (3ph4w) currents,
max. demanded currents and current %THD.
In Set-up mode, this is the ‘Up’ button.
Selects the Instantaneous Power screens. Successive
operations select power (W, VAr & VA), max.
demanded power and power factor.
In Set-up mode, this is the ‘Down’ button.
Selects the Energy display screens. Successive
operations select imported/exported Wh and Varh.
Display can indicate up to 9999999·9.
Running man symbol flashes as data accumulates.
1% symbol shows that power values of <1% of range
maximum will be included in energy readings.
In Set-up mode, this is the ‘Enter’ button.
Display shows the units of measurements in use for each range.
Energy units can be set via set-up screens; other units are set
automatically.
A Demand Reset resets maximum demand readings to zero.
Setting up
To enter set-up mode, firmly press the and buttons
simultaneously and hold for 5 seconds, until the password screen
appears. Setting up is password-protected so you must enter the
correct password (default ‘0000’) before proceeding. If an incorrect
password is entered, the display reverts to measurement mode.
To exit setting-up mode, press
measurement screen is restored or hold
simultaneously for 5 seconds.
repeatedly until the
and buttons
2. Press
3. If an item flashes, then it can be adjusted by the
and
e.g.
4. Having selected an option from the current menu layer, press
5. Having completed a parameter setting, press
a higher menu level. The SET indicator will be removed and
you will be able to use the
menu selection.
6. On completion of all setting-up, press
measurement screen is restored.
to confirm the selection.
(down) keys. If not, there may be a further layer,
Comms - Baud rate, before adjustment is possible. Press
to select the lower layer.
to confirm your selection. The SET indicator will appear.
(up)
to return to
and keys for further
repeatedly until the
Number Entry Procedure
When setting up the unit, some screens require the entering of a
number. In particular, on entry to the setting up section, a
password must be entered. Digits are set individually, from left to
right. The procedure is as follows:
1. The current digit to be set flashes and is set using the
(up) and (down) keys.
2. Press to confirm each digit setting. The SET indicator
appears after the last digit has been set.
3. After setting the last digit, press to exit the number
setting routine. The SET indicator will be removed.
Installation
Warnings
• During normal operation, voltages hazardous to life may
be present at some of the terminals of this unit.
Installation and servicing should be performed only by
qualified, properly trained personnel abiding by local
regulations. Ensure all supplies are de-energised before
attempting connection or other procedures.
• Terminals should not be user accessible after installation
and external installation provisions must be sufficient to
prevent hazards under fault conditions.
• This unit is not intended to function as part of a system
providing the sole means of fault protection - good
engineering practice dictates that any critical function be
protected by at least two independent and diverse
means.
• The unit does not have internal fuses therefore external
fuses must be used for protection and safety under fault
conditions.
• Never open-circuit the secondary winding of an
energised current transformer.
• This product should only be operated with the CT
secondary connections earthed.
• If this equipment is used in a manner not specified by the
manufacturer, protection provided by the equipment may
be impaired.
Caution: Risk of
Electric Shock
Case Dimensions:
Width 71·3 mm, Depth 57·5 mm, Length 90·5 mm
Length including fixing tag 93·5 mm.
The unit is intended for mounting on a standard DIN rail. Avoid
mounting the unit where there is excessive vibration; in excessive
direct sunlight; or outside a reasonably stable ambient temperature
of -10 to +55°C.
Safety
The unit is designed in accordance with BS EN 61010-1:2001
(IEC 61010-1:2001) – Permanently connected use, Normal
condition. Installation category III, pollution degree 2, basic
insulation for rated voltage. Measurement Category III.
EMC Installation Requirements
Whilst this unit complies with all relevant EU EMC (electro-magnetic
compatibility) regulations, any additional precautions necessary to
provide proper operation of this and adjacent equipment will be
installation dependent and so the following can only be general
guidance:
• Avoid routing wiring to this unit alongside cables and products
that are, or could be, a source of interference.
• The auxiliary supply to the unit should not be subject to
excessive interference. In some cases, a supply line filter may
be required.
• To protect the product against incorrect operation or permanent
damage, surge transients must be controlled. It is good EMC
practice to suppress transients and surges at the source. The
unit has been designed to automatically recover from typical
transients; however in extreme circumstances it may be
necessary to temporarily disconnect the auxiliary supply for a
period of greater than 5 seconds to restore correct operation.
• Screened communication leads are recommended and may be
required. These and other connecting leads may require the
fitting of RF suppression components, such as ferrite absorbers,
line filters etc., if RF fields cause problems.
• It is good practice to install sensitive electronic instruments that
are performing critical functions in EMC enclosures that protect
against electrical interference causing a disturbance in function.
Wiring
Input connections are made to screw clamp terminals. Choice of
cable should meet local regulations for the operating voltage and
current.
The current inputs of these products are designed for
connection into systems via current transformers only.
All negative current inputs are commoned inside the unit and
grounding should be at one point only. To minimise measurement
errors, the CTs should be grounded as shown in the wiring
diagram.
CT secondaries must be grounded in accordance with local
regulations. It is desirable to make provision for shorting links to be
made across CTs to permit easy replacement of a unit should this
ever be necessary.
Additional considerations for three wire systems
The neutral terminal (terminal N) is indirectly connected to the
voltage input terminals (terminals L1, L2, L3). When connected to
a three wire system the neutral terminal will adopt a potential
somewhere between the remaining lines.
If external wiring is connected to the neutral terminal it must be
connected to either the neutral line or earth (ground) to avoid the
possibility of electric shock from the neutral terminal.
Fusing
This unit must be fitted with external fuses in voltage and auxiliary
supply lines. Voltage input lines must be fused with a quick blow
fuse 1A maximum. Auxiliary supply lines must be fused with a slow
blow fuse rated 1A maximum. Choose fuses of a type and with a
breaking capacity appropriate to the supply and in accordance with
local regulations.
A suitable switch or circuit breaker should be included in the
installation. It should be positioned so as to be easy to operate, in
close proximity to the equipment, and clearly identified as the
disconnecting device.
Earth/Ground Connections
For safety reasons, current transformer secondary connections
should be grounded in accordance with local regulations. Under no
circumstances should this product be operated without this earth
connection.
Maintenance
In normal use, little maintenance is needed. As appropriate for
service conditions, isolate from electrical power, inspect the unit
and remove any dust or other foreign material present. Periodically
check all connections for freedom from corrosion and screw
tightness, particularly if vibration is present.
The front of the case should be wiped with a dry cloth only. Use
minimal pressure, especially over the viewing window area. If
necessary wipe the rear case with a dry cloth. If a cleaning agent is
necessary, isopropyl alcohol is the only recommended agent and
should be used sparingly. Water should not be used. If the rear
case exterior or terminals should be contaminated accidentally with
water, the unit must be thoroughly dried before further service.
Should it be suspected that water might have entered the unit,
factory inspection and refurbishment is recommended.
In the unlikely event of a repair being necessary, it is recommended
that the unit be returned to the factory or nearest Crompton
Instruments/Tyco Electronics service centre.
Specification
Measured Parameters
The unit can monitor and display the following parameters of a
single phase, 3-phase 3-wire or 3-phase 4-wire supply:
Voltage and Frequency
Phase to neutral voltages 100 to 289V a.c. (not for 3p3w)
Voltages between phases 173 to 500V a.c. (3p only)
Frequency in Hz
Percentage total voltage harmonic distortion (THD%) for
each phase to N (not for 3p3w supplies)
Percentage voltage THD% between phases (3p only)
Current
Current on each phase – 1 to 9999A range, set by external
current transformer(s) (CTs)
Neutral current (calculated) (3p4w supplies only)
Maximum demand currents on each phase, since the last
demand reset
Maximum neutral demand current, since the last demand
reset (3p4w supplies only)
Current THD% for each phase
Power and Power Factor
Instantaneous power: Power 0 to 3600 MW Reactive Power 0 to 3600 MVAr Volt-amps 0 to 3600 MVA
Maximum demanded power since last Demand reset
Power factor
Energy Measurements
Imported energy 0 to 9999999·9 Wh, kWh or MWh
Exported energy 0 to 9999999·9 Wh, kWh or MWh
Imported reactive energy 0 to 9999999·9 VArh, kVArh or MVArh
Exported reactive energy 0 to 9999999·9 VAhr, kVArh or MVArh
Measured Inputs
Voltage inputs through 4-way fixed connector with 2·5mm2
stranded wire capacity. 3-Phase 3- & 4-wire, and Single-phase 2wire. Line frequency measured from L1 voltage or L3 voltage.
Three current inputs (six physical terminals) with 2·5mm2 stranded
wire capacity for connection of external CTs. Nominal rated input
current 5A a.c. rms.
Range of Use
Voltage 5 to 120% of Range Maximum
Current 1 to 120% of nominal
Power factor 1 to 0, leading or lagging
Active power 1 to 144% of nominal, 3600 MW maximum
Apparent power 1 to 144% of nominal, 3600 MVA maximum
Power is only registered when voltage and current are within their
respective range of use.
Power factor is only indicated when the measured VA is over 3% of
range maximum.
(below 5% of range maximum voltage, current
indication may only be approximate)
Accuracy
Voltage 0·5% of range maximum
Current 0·5% of nominal
Neutral current 4% of nominal (calculated)
Frequency 0·2% of mid-frequency
Power factor 1% of unity (0.01)
Active power (W) ±1% of range maximum
Reactive power (VAr) ±1% of range maximum
Apparent power (VA) ±1% of range maximum
Active energy (Wh) Class 1 IEC 62053-21 section 4.6
Reactive energy (VARh) ±1% of range maximum
st
Total harmonic distortion 1% up to 31
Temperature co-efficient, typ. Voltage and current = 0·013%/°C
Response time to step input 1s, typical, to >99% of final
Error change due to variation
of an influence quantity in the
manner described in Section
6 of IEC 688:1992
Error in measurement when a
measurand is within its
measuring range, but outside
its reference range
30% THD the error in this reading
may increase to 1·5% for the
higher harmonics)
Active energy = 0·018%/°C
reading, at 50 Hz.
2 × error allowed for the reference
condition applied in the test.
Error due to temperature variation
as above.
2 × error allowed at the end of the
reference range adjacent to the
section of the measuring range,
where the measurand is currently
operating / being tested.
harmonic (above
Auxiliary Supply
Two-way fixed connector with 2·5mm2 stranded wire capacity.
110 to 400V a.c. 50/60Hz ±10% or 120V to 350V d.c. ±20%.
Consumption < 3W.
Pulse Relay Output
The pulse relay output can be set to generate pulses to represent
imported kWh, exported kWh, imported kVArh or exported kVArh.
The rate cannot be set to a value that could result in more
than 2 pulses per second.
Pulse width 200/100/60 ms.
RS485 Output for Modbus or JC N2 Protocol
For Modbus protocol, the following RS485 communication
parameters can be configured from the Set-up menu:
Baud rate 2400, 4800, 9600, 19200, 38400
Parity none/odd/even
Stop bits 1 or 2
RS485 network address nnn – 3-digit number, 1 to 247
Modbus Word order Shows the word order (Hi/Lo) of the 8-bit
bytes in the Modbus message format. This setting can only be
changed from the Modbus port.
Note that with odd or even parity, Stop Bits are forced to one.
For JC N2 protocol, only the RS485 network address can be
configured. The range of addresses is 1 to 255.
Reference Conditions of Influence Quantities
Influence Quantities are variables that affect measurement errors to
a minor degree. Accuracy is verified under nominal value (within
the specified tolerance) of these conditions.
Ambient temperature 23°C ±1°C
Input waveform 50 or 60Hz ±2%
Input waveform Sinusoidal (distortion factor <0·005)
Auxiliary supply voltage Nominal ±1%
Auxiliary supply frequency Nominal ±1%
Auxiliary supply waveform
(if AC)
Magnetic field of external
origin
Sinusoidal (distortion factor <0·05)
Terrestrial flux
Environment
Operating temperature -10°C to +55°C
Storage temperature -20°C to +70°C
Relative humidity 0 to 90%, non-condensing
Altitude Up to 2000m
Warm up time 1 minute
Vibration 10Hz to 50Hz, IEC 60068-2-6, 2g
Shock 30g in 3 planes
*
Maximum operating and storage temperatures are in the context of
typical daily and seasonal variation.
*
*
Mechanics
DIN rail dimensions 72 x 90 mm (WxH) per DIN 43880
Mounting DIN rail (DIN 43880)
Sealing IP30 (minimum)
Material Self-extinguishing UL 94 V-0
Approval, Certification, and Standards Compliance
RoHS compliant. (Although this class of product is presently
excluded from the RoHS regulations, the unit has been designed
and manufactured in compliance with the RoHS regulations.)
EMC Emissions BS EN 61326, Class A (Industrial)
EMC Immunity BS EN 61326, Class A (Industrial)
Safety BS EN 61010-1:2001
All of the above information, including drawings, illustrations and graphic design, reflects our present understanding and is to the best of our
knowledge and belief correct and reliable. Users, however, should independently evaluate the suitability of each product for the desired application.
Under no circumstances, does this constitute an assurance of any particular quality or performance. Such an assurance is only provided in the
context of our product specifications or explicit contractual arrangements. Our liability for these products is set forth in our standard terms and
conditions of sale. TE Connectivity (logo), TE Connectivity, Tyco Electronics and Integra are trademarks. CROMPTON is a trademark of Crompton
Parkinson Ltd. and is used by TE Connectivity Ltd. under licence. Other trademarks, products or company names mentioned herein may be
trademarks of their respective owners.
Tyco Electronics (UK) Ltd
TE Energy
Freebournes Road, Witham
Essex CM8 3AH
England
Tel: +44 (0) 1376 509509
Fax: +44 (0) 1376 509511