Transformers
Moulded Case Current Transformers
790 Series Relaying and Metering
Model 790-941 * *
Application: For relaying and metering
Frequency: 25 - 400 Hz
Installation Class: 600 Volts
Impulse Level: 10 kV Full Wave
Continuous Thermal Current
Rating Factor: 1.33 at 30°C ambient and
1.0 at 55°C ambient
• Manufactured to meet the requirements
of UL 1244 and revisions
• Non-standard lengh to be specifed
• Terminals are brass studs No. 8-32 UNC
with one flat washer, lockwasher and
regular nut
• UL Recognized
• ABS Approved
Catalogue Number Current Relay ANSI Accuracy Classification Weight
(without mounting Rating Class Metering Class at 60Hz (lb)
brackets) BO.1 B0.2 B0.5 B1.0 B2.0
790-941U-RLLS *200:5 C10 1.2 1.2 2.4 9.2
790-941U-RXLS *300:5 C10 0.6 0.6 1.2 2.4 9.2
790-941U-SCLS *400:5 C20 0.3 0.3 0.6 1.2 2.4 9.3
790-941U-SFLS *500:5 C20 0.3 0.3 0.6 1.2 2.4 9.4
790-941U-SJLS *600:5 C20 0.3 0.3 0.3 0.6 1.2 9.5
790-941U-SNLS *800:5 C20 0.3 0.3 0.3 0.6 1.2 9.7
790-941U-SSLS 1000:5 C50 0.3 0.3 0.3 0.6 0.6 9.9
790-941U-SULS 1200:5 C50 0.3 0.3 0.3 0.6 0.6 8.6
790-941U-TCLS 1500:5 C50 0.3 0.3 0.3 0.3 0.3 8.6
790-941U-TELS 1600:5 C50 0.3 0.3 0.3 0.3 0.3 8.7
790-941U-TMLS 2000:5 C50 0.3 0.3 0.3 0.3 0.3 9.1
790-941U-TULS 2500:5 C50 0.3 0.3 0.3 0.3 0.3 9.6
790-941U-UALS 3000:5 C50 0.3 0.3 0.3 0.3 0.6 10.1
Ordering mounting bracket kit separately option code MH. ie: 790-941U-UALS-MH
* NOTE: Completely interchangable with GE JAH-0.
Model 791 available with increased burden capability and with same overall dimensions except the width
increases to 2.88"
Specifications
Ordering Information
Dimensions (inches)

Transformers
Moulded Case Current Transformers
792 Series Relaying and Metering
Application: For relaying and metering
Frequency: 25-400 Hz
Installation Class: 600 Volts
Impulse Level: 10 Kv, Full Wave
Continuous Thermal Current
Rating Factor: 1.33 at 30°C ambient and
1.0 at 55°C ambient
• Manufactured to meet the requirements
of UL 1244 and revisions
• Terminals are brass studs No. 8-32 UNC
with one flat washer, lockwasher and
regular nut
• UL Recognized
• ABS Approved
Catalogue Number Current Relay ANSI Accuracy Classification Weight
(without mounting Rating Class Metering Class at 60Hz (lb)
brackets) BO.1 B0.2 B0.5 B1.0 B2.0
* * U-RLLS 200:5 C10 1.2 2.4 10.0
* * U-RXLS 300:5 C10 0.6 1.2 2.4 10.0
* * U-SCLS 400:5 C20 0.6 1.2 1.2 2.4 9.3
* * U-SFLS 500:5 C20 0.3 0.6 0.6 1.2 2.4 10.2
* * U-SJLS 600:5 C20 0.3 0.3 0.3 0.6 1.2 10.3
* * U-SNLS 800:5 C20 0.3 0.3 0.3 0.6 1.2 10.5
* * U-SSLS *1000:5 C50 0.3 0.3 0.3 0.3 0.6 10.7
* * U-SULS *1200:5 C50 0.3 0.3 0.3 0.3 0.6 10.9
* * U-TCLS *1500:5 C50 0.3 0.3 0.3 0.3 0.3 11.2
* * U-TELS 1600:5 C50 0.3 0.3 0.3 0.3 0.3 11.2
* * U-TMLS *2000:5 C50 0.3 0.3 0.3 0.3 0.3 9.8
* * U-TULS *2500:5 C50 0.3 0.3 0.3 0.3 0.3 10.4
* * U-UALS *3000:5 C50 0.3 0.3 0.3 0.3 0.3 10.9
* * U-UELS *4000:5 C50 0.3 0.3 0.3 0.3 0.3 11.7
Ordering mounting bracket kit separately option code MH. ie: 792-941U-UELS-MH
* NOTE: Completely interchangable with GE JAH-0.
Model only: Functionally interchangeable with Westinghouse CLA-10 (5.5"); CLA-10 (8.25") please request
Information on Model 794.
Model 793 available with increased burden capability and with same overall dimensions except the width
increases to 2.87".
Model 792-941 * *
Specifications
Ordering Information
Dimensions (inches)

Transformers
Moulded Case Current Transformers
797 Series Relaying and Metering
Model 797-940 * *
Model 797-941 * *
Application: For relaying and metering
Frequency: 50-400 Hz
Installation Class: 0.6 KV. BIL. 10 KV
Continuous Thermal Current
Rating Factor: 1.33 at 30°C ambient and
1.0 at 55°C ambient
Burdens:
ANSI 0.9 power factor meter burdens
• Manufactured to meet the requirements of
UL 1244 and revisions
• Flexible leads are UL 1015 105°C CSA
approved, #16 AWG, 24" long
• Non-standard lengh to be specifed
• Terminals are brass studs No. 8-32 UNC
with one flat washer, lockwasher and
regular nut
• UL Recognized
• ABS Approved
Multi-ratios available on request. Order mounting bracket kit separately option code MH. ie: 797-941U-UELS-MH
** NOTE: When ordering, prefix Cat. No with model designation required. I.e 797-940U-RLLS or 797-941U-RLLS.
Catalogue Number Current ANSI Accuracy Classification VA for Weight
(without mounting Rating Metering Class at 60Hz 1% Class (lb)
brackets) BO.1 B0.2 B0.5 B0.9 B1.8
* * U-RLLS 200:5 1.2 1.2 - - - 5.0 3.03
* * U-RSLS 250:5 0.6 1.2 - - - 5.0 3.07
* * U-RXLS 300:5 0.6 0.6 1.2 2.4 - 12.5 3.10
* * U-SCLS 400:5 0.3 0.6 1.2 1.2 2.4 25.0 3.17
* * U-SFLS 500:5 0.3 0.3 0.6 1.2 2.4 25.0 3.24
* * U-SJLS 600:5 0.3 0.3 0.6 0.6 1.2 25.0 3.31
* * U-SMLS 750:5 0.3 0.3 0.3 0.3 0.6 40.0 3.30
* * U-SNLS 800:5 0.3 0.3 0.3 0.3 0.6 50.0 3.32
* * U-SSLS 1000:5 0.3 0.3 0.3 0.3 0.6 75.0 3.43
* * U-SULS 1200:5 0.3 0.3 0.3 0.3 0.6 100.0 3.54
* * U-TCLS 1500:5 0.3 0.3 0.3 0.3 0.6 80.0 2.47
* * U-TELS 1600:5 0.3 0.3 0.3 0.3 0.6 90.0 2.53
* * U-TMLS 2000:5 0.3 0.3 0.3 0.3 0.3 105.0 2.79
* * U-TULS 2500:5 0.3 0.3 0.3 0.3 0.3 130.0 2.80
* * U-UALS 3000:5 0.3 0.3 0.3 0.3 0.3 165.0 3.14
* * U-UCLS 3500:5 0.3 0.3 0.3 0.3 0.3 190.0 3.48
* * U-UELS 4000:5 0.3 0.3 0.3 0.3 0.3 215.0 3.39
Specifications
Dimensions (inches)
Ordering Information