Crompton Instruments 798 Series Catalog Page

2002
Transformers
Moulded Case Current Transformers
798 Series Relaying and Metering
Application: Metering or relaying Frequency: 50-400 Hz Installation Class: 0.6 KV. BIL. 10 KV. Full
Continuous Current Rating Factor: 1.33 at 30°C ambient and
1.0 at 55°C ambient
Burdens:
ANSI 0.9 power factor meter burdens
Manufactured to meet the requirements of UL 1244 and revisions
Flexible leads are UL 1015 105° CSA approved, #16 AWG, 24" long
Non-standard lengh to be specifed
Terminals are brass studs No. 8-32 UNC
with one flat washer, lockwasher and regular nut
UL Recognized
ABS Approved
Catalogue Number Current Relay ANSI Accuracy Classification Weight
(without mounting Rating Class Metering Class at 60Hz (lb)
brackets) BO.1 B0.2 B0.5 B0.9 B1.8
* * U-PKLS 100:5 1.2 2.4 - - - 2.5 * * U-PZLS 150:5 0.6 1.2 - - - 5.0 * * U-RLLS 200:5 0.6 0.6 1.2 - - 12.5 * * U-RSLS 250:5 0.3 0.3 1.2 - - 12.5 * * U-RXLS 300:5 0.3 0.3 0.6 1.2 2.4 25.0 * * U-SCLS 400:5 0.3 0.3 0.3 0.6 1.2 50.0 * * U-SFLS 500:5 0.3 0.3 0.3 0.6 1.2 50.0 * * U-SJLS 600:5 0.3 0.3 0.3 0.6 0.6 50.0 * * U-SMLS 750:5 0.3 0.3 0.6 0.6 1.2 50.0 * * U-SNLS 800:5 0.3 0.3 0.3 0.3 0.3 75.0 * * U-SSLS 1000:5 0.3 0.3 0.3 0.3 0.3 100.0 * * U-SULS 1200:5 0.3 0.3 0.3 0.3 0.3 125.0 * * U-TCLS 1500:5 0.3 0.3 0.3 0.3 0.3 160.0 * * U-TELS 1600:5 0.3 0.3 0.3 0.3 0.3 175.0 * * U-TMLS 2000:5 0.3 0.3 0.3 0.3 0.3 210.0
Approximate weight 3.5lbs. Other ratios available on request. Order mounting bracket kit separately option code MH. ie: 798-941U-TMLS-MH
** NOTE: When ordering, prefix Cat. No with model designation required. i.e 798-941U-PKLS. NOTE: Model 798 is identical in physical dimensions to GE type JCH-0 and Westinghousen ELC.
Compare the much superior electrical accuracies, burden capabilities and higher ratios available.
Model 798-941 * *
Specifications
Ordering Information
Dimensions (inches)
Loading...