Crompton Instruments 76 Data Sheet

Model 76
Window Diameter 3.00"
Application:
With ammeters, wattmeters and cross current conpensation.
Frequency:
50-400Hz
600 Volts, 10kV BIL full wave
• Flexible leads are UL 1015 105°C, CSA approved #16 AWG, 24” long
• Non-standard length to be specified
• Terminals are brass studs No. 8-32 UNC with one flat washer, lockwasher and regular nut
• SFT case styles also available as SFL with leads
• Approximate weight: 0.9 lb
Catalogue Current Ratio Accuracy Burden Number at 60Hz VA at 60Hz
76**–201 200:5 ± 1% 5.0 76**–251 250:5 ± 1% 5.0 76**–301 300:5 ± 1% 6.0 76**–401 400:5 ± 1% 10.0 76**–501 500:5 ± 1% 10.0 76**–601 600:5 ± 1% 10.0 76**–751 750:5 ± 1% 10.0 76**–801 800:5 ± 1% 12.5 76**–102 1000:5 ± 1% 12.5 76**–122 1200:5 ± 1% 12.5 76**–152 1500:5 ± 1% 12.5 76**–162 1600:5 ± 1% 12.5 76**–202 2000:5 ± 1% 15.0
14
76SFT
76RL
Approvals
CSA 223647
UL 257877
Loading...