Crestron electronic Power Switching User Manual

CRESTRON GREEN LIGHT™ Power Switching

Introduction

CRESTRON GREEN LIGHT power switching cabinets come pre-configured with GLXP modules already installed. The cabinets only require installation and wiring of feed and load circuits.

Industry Compliance

The cabinet and modules are Listed to applicable UL Standards and requirements by Underwriters Laboratories Inc.

Application

CRESTRON GREEN LIGHT Power Switching Cabinets in a Typical Lighting Application
(E227280 (cabinet) and E103692 (modules))
Crestron Electronics, Inc. Installation Guide – DOC. 6672B
15 Volvo Drive Rockleigh, NJ 07647 (2020570) Tel: 888.CRESTRON 10.08 Fax: 201.767.7576 Specifications subject to www.crestron.com change without notice.
Power Switching CRESTRON GREEN LIGHT™

Physical Description

This section shows the exterior and interior dimensions of the CRESTRON GREEN LIGHT cabinet.
External Dimensions of CRESTRON GREEN LIGHT Power Switching Cabinets
20"
(508 mm)
H2
H1
H3
1
2
2
(64 mm)
"
15"
(381 mm)
5
Ø
16
(8 mm)
5
Ø
(16 mm)
"
"
8
OPTIONAL DOOR
(169 mm)
TECHNICAL KNOCKOUTS, 50 TOTAL
3
(FOR
4
TYPICAL TOP & BO T TOM
" (19 mm) &
1
" (13 mm) CONDUIT)
2
KNOCKOUT
3
(FOR
" (19 MM) CONDUIT)
4
TYPICAL BOTH SI D ES
5
6
"
8
7
Ø
16
(12 mm)
"
External Dimensions of CRESTRON GREEN LIGHT Power Switching Cabinets
DIMENSION 12 Breaker 30 Breaker 42 Breaker 42 Breaker (Short)
H1
H2
H3
37 1/2” 953 mm) 70” (1.8 m) 90” (2.3 m) 78 15/16” (2 m)
3” (77 mm) 3 5/8” (93 mm) 3 5/8” (93 mm) 3 5/8” (93 mm)
32 7/8” (836 mm) 59 3/8“ (1.5 m) 79 3/8” (2.0 m) 66" (1.7 m)
2 CRESTRON GREEN LIGHT Power Switching Installation Guide – DOC. 6672B
CRESTRON GREEN LIGHT™ Power Switching
Interior Dimensions of CRESTRON GREEN LIGHT Cabinets (120/208 VAC, left; 277/480 VAC, right)
H1
(207 mm)
1
6
"
4
(159 mm)
7
1
1
"
8
8
(48 mm)
8
"
7
1
"
8
(48 mm)
H1
7
"
3
8
(99 mm)
8"
(204 mm)
2"
(51 mm)
2"
(51 mm)
Interior Dimensions of CRESTRON GREEN LIGHT Cabinets
120 Service 277 Service
DIMENSION 12 Breaker 30 Breaker 42 Breaker 12 Breaker 30 Breaker 42 Breaker
H1
8 3/4”
(223 mm)
15 1/8”
(385 mm)
18 1/8”
(461 mm)
Installation Guide – DOC. 6672B CRESTRON GREEN LIGHT Power Switching 3
7 1/16”
(180 mm)
12 1/16”
(310 mm)
15 1/16”
(383 mm)
Power Switching CRESTRON GREEN LIGHT™

Installation

Observe the following when installing the cabinet:
The cabinet must be mounted by a licensed electrician in accordance with all national and local codes.
Refer to the diagram below for specific requirements.
The cabinet is designed for surface mounting on a wall.
Cabinets are intended for indoor use only.
The ambient temperature range should be 32°F to 104°F (0°C to 40°C). The relative humidity should range
from 10% to 90% (non-condensing). Allow adequate clearance in front of the cover for servicing.
Mounting Location
WALL
MAXIMUM HEIGHT OF
HIGHEST BREAKER
(FROM GROUND)
6'-7"
(2.01 m)
3'
(0.9 m)
MINIMUM REQUIRED
CLEARANCE
4 CRESTRON GREEN LIGHT Power Switching Installation Guide – DOC. 6672B
CRESTRON GREEN LIGHT™ Power Switching

Wiring

NOTE: All wiring must be installed in accordance with all local and national electrical codes. NOTE: Refer to the torque settings specified on pages 6, 7 and 8.
CRESTRON GREEN LIGHT cabinets are shipped with GLXP modules installed and prewired to the branch circuit breakers. The following must be performed after installation:
Connect incoming feed conductors to the breaker panel (section A of the following diagram)
Connect load wiring to GLXP module outputs (section B of the following diagram)
Connect control wiring (section C of the followi ng diagram)
FEED:
3-PHASE 4-WIRE
TO LOADS:
2W + GND 16A (MAX)
A
B
CLASS 2
WIRING ONLY
C
CLASS 2 WIRING ONLY
Installation Guide – DOC. 6672B CRESTRON GREEN LIGHT Power Switching 5
Power Switching CRESTRON GREEN LIGHT™

Feed Wiring (Section A)

Feed Wiring for MLO (left) and MCB (right) Applications
Refer to the following table for information on wiring the feed to the panel.
Feed Wire Information
120 Volt Models
TERMINAL CONNECTOR MAX
WIRE RANGE
Neutral and Main Lugs
Neutral Bus 14-10 AWG(CU) or
WARNING: Failure to properly tighten lugs may result in poor electrical connection and overheating of the terminals.
10-2/0 AWG (CU) or 6-2/0 AWG (AL)
6 - 300 kcmil (CU or AL)
12-10 AWG (AL) 8 AWG (CU or AL)
6-4 AWG (CU or AL)
Use copper or aluminum conductors only – rated 75°C.
TORQUE Max
Current
15 lb-ft (20.3 Nm)
21 lb-ft (28.5 Nm) 20 lb-in (2.3 Nm) 25 lb-in (2.8 Nm) 35 lb-in (4.0 Nm)
225
Amps
CONNECTOR MAX
WIRE RANGE
6-350 kcmil (CU or AL) 1/0-750 kcmil (CU or AL)
14-6 AWG (CU or AL) 14-2/0 AWG (CU or AL)
277 Volt Models
TORQUE Max
275-300 lb-in (31.1-33.9 Nm)
24-35 lb-in (2.7-4.0 Nm) 40-50 lb-in (4.5-5.6 Nm)
Current
250
Amps
6 CRESTRON GREEN LIGHT Power Switching Installation Guide – DOC. 6672B
CRESTRON GREEN LIGHT™ Power Switching

Load Wiring (Section B)

CAUTION: Bypass jumpers are provided on each output to allow testing and to protect the module during installation. The jumper shorts the L and SW terminals so that the load circuit is energized when the branch breaker is on. Do not remove the bypass jumper until all feed and load wiring has been completed, and the circuits have been tested for electrical faults.
NOTE: Use copper conductors only – rated 75°C.
Wire Gauge and Torque Values
TERMINAL CONNECTOR MAX WIRE RANGE TORQUE STRIP LENGTH
LOAD OUTPUTS 14-10 AWG 4.43 lb-in
DIM CONTROL (GLXP-DIMFLV8 only)
GROUND BAR 14-10 AWG 35 lb-in
GROUND LUG 14-4 AWG 45-25 lb-in
28-12 AWG 4.43 lb-in
(0.5 Nm)
(0.5 Nm)
(4.0 Nm)
(5.1-2.8 Nm)
1. Each output has a label with the number of the controlling circuit breaker printed on it. With the
corresponding circuit breaker turned off, connect the controlled circuit (LOAD) wires to the output per the markings on the module as shown in the following diagrams. Terminals for load wiring accept one 10 – 14 AWG wire.
5/16” (8 mm)
5/16” (8 mm)
5/16” (8 mm)
3/4" (19 mm)
Load Wiring for GLXP-SW10, GLXP-SW16, GLXP-HSW8, GLXP-HSW12, and GLXP-DIMFLV8 (Jumper Installed)
1
NEUTRAL BUS
L
CIRCUIT BREAKER (20A MAX)
TO NEUTRAL BUS (PREWIRED)*
TO BRANCH BREAKER (PREWIRED)
JUMPER (PREWIRED)
TO LOAD
N
TO LOADS
L
1.2000
2
3
4
* A NEUTRAL connection is only present on OUTPUT 1.
Installation Guide – DOC. 6672B CRESTRON GREEN LIGHT Power Switching 7
Power Switching CRESTRON GREEN LIGHT™
The GLXP-DIMFLV8 also requires wiring the terminals for 0-10 VDC control wire. Refer to the following diagram when connecting the dimmable ballast. Each control wire terminal accepts one 12 – 28 AWG wire.
0-10 VDC Control Wiring for GLXP-DIMFLV8 Only
TO + ON 4-WIRE LOADS (PURPLE)
TO - ON 4-WIRE LOADS (GRAY)
2. Test the circuit for electrical faults by turning on each circuit breaker, checking that the breakers do not
trip, and that power is delivered to the proper loads.
3. Turn off the circuit breaker(s) and remove all jumpers.
4. Turn on the circuit breakers.

Control Wiring (Section C)

The bottom of the cabinet contains Cresnet® connections for interfacing to the rest of the Crestron® control system. It also provides an override input which can be tied to devices such as the GLS-PLS-120/277 phase-loss sensor, or other devices that provide a dry contact closure (manual switch, fire alarm relay, etc.).
NOTE: Interface connectors for NET (x2), POWER (x1), and OVERRIDE (x1) ports are pr ovided.
Wire Gauge and Torque Values
TERMINAL CONNECTOR MAX
WIRE RANGE
NET 12 AWG POWER 26-12 AWG OVERRIDE 26-12 AWG
TORQUE STRIP
LENGTH
4.43 lb-in (0.5 Nm)
4.43 lb-in (0.5 Nm)
4.43 lb-in (0.5 Nm)
1/4”
(6 mm)
1/4”
(6 mm)
1/4”
(6 mm)
8 CRESTRON GREEN LIGHT Power Switching Installation Guide – DOC. 6672B
CRESTRON GREEN LIGHT™ Power Switching
Connector Wiring
RED
BLUE
WHITE
TO CONTROL SYSTEM AND
NET:
OTHER CRESNET DEVICES
BLACK
POWER:
24 VDC JUMPERED FROM NET
PORT or EXTERNAL SUPPLY. PROVIDES CRESNET POWER
TO THE MODULES
OTHER DEVICES RECEIVING
OVERRIDE: FROM DEVICE PROVIDING CONTACT CLOSURE & TO
OVERRIDE SIGNAL
NET Port Wiring
When wiring the supplied NET connectors for connection to a Crestron control system or other device on the Cresnet network, use Crestron certified wire such as CRESNET-NP or CRESNET-P.
To ensure optimum performance over the full range of your installation topology, use Crestron certified wire. Failure to do so may incur additional charges if support is required to identify performance deficiencies because of using improper wire.
When daisy-chaining connections between NET ports, strip the ends of the wires carefully to avoid nicking the conductors. Twist together the ends of the wires that share a pin on the network connector, insert the connection into the Cresnet connector, and tighten the retaining screw. Repeat the procedure for the other three conductors.
POWER Port Wiring
Low voltage (24 VDC) power must be supplied to the modules either internally via devices connected to the NET port or externally via a Cresnet power supply connected to the POWER port.
To power the modules internally from line power, install a jumper from the INT pin on the supplied POWER connector to the EXT pin on the POWER connector as shown in the following diagram.
Providing Cresnet Power Internally
When a lighting module is powered from line power, the module’s PWR LED will illuminate.
Installation Guide – DOC. 6672B CRESTRON GREEN LIGHT Power Switching 9
Power Switching CRESTRON GREEN LIGHT™
To power the modules externally from a Cresnet 24 VDC power supply, connect the external power supply to the EXT and G pins on the POWER supplied connector as shown in the following diagram.
Providing Cresnet Power Externally
CRESTRON 24 VDC
POWER SUPPLY
G 24
When properly connected and receiving 24 VDC power externally, the green LED next to the MODULES port will light.
When a lighting module is powered from a Cresnet power supply in the absence of line power, the module’s PWR LED will flash.
OVERRIDE Port Wiring
Low-voltage input devices such as the Crestron GLS-PLS-120/277 phase-loss sensor or any device that provides a dry contact closure can be connected to the supplied OVERRIDE connector on the bottom of the cabinet.
10 CRESTRON GREEN LIGHT Power Switching Installation Guide – DOC. 6672B
CRESTRON GREEN LIGHT™ Power Switching

Testing

Manual Control

A lighting module can be manually controlled from its front panel.
GLXP-SW and GLXP-HSW Modules:
The state of each output can be manually controlled from the front panel. To toggle the output between off and on, tap the appr opriate ON/OFF button. The corresponding LED
illuminates and the output state is shown on the NET ID display (“oF” for off, “On” for on) for two seconds after the button is released.
NOTE: The control system program may change the settings if the Override mode is not enabled.
GLXP-DIMFLV8 Modules:
The lighting level of each of the outputs can be manually controlled from the front panel. To toggle the light between off and 100% (on), tap an output’s ON/OFF button. The corresponding LED
illuminates and the output level is shown on the NET ID display (“oF” for off, “On” for on) for two seconds after the button is released.
To ramp the lighting level up or down (until it reaches a limit), press and hold the output’s ON/OFF button. To change the ramp direction, release the output’s ON/OFF button, then press and hold it again. The corresponding LED illuminates and the output level is shown on the NET ID display as a percentage (01-99) for two seconds after the button is released.
NOTE: The control system program may change the settings if the Override mode is not enabled.

Override Mode

The Override mode overrides the control system program and sets all of the output states to the stored override values. For instructions on saving override setti ngs, refer to “Save Override Settings” below.
To enable Override mode, press and release the OVR button. The OVR LED flashes slowly.
NOTE: If the Override mode was enabled from an external device (i.e. a contact closure is present on the OVERRIDE terminals), the OVR LED will flash quickly. Pressing the OVR button has no effect.
To disable Override mode, press the OVR button again. The OVR LED extinguishes and the outputs return to the states set by the control system program.
NOTE: If override states have not been stored, the factory default override state is all loads on.

Save Override Settings

The state of each output can be saved as an override setting, which can be automatically recalled when the Override mode is enabled.
NOTE: The control system program has a setting that can prevent locally saving the override state. If this setting is enabled, the display shows “Er” when trying to save override states. For more information, refer to the SIMPL Windows help file.
To save the state of all of the outputs as an override setting, press and hold the OVR button for three seconds. The OVR LED blinks to indicate the new override settings have been stored.
Installation Guide – DOC. 6672B CRESTRON GREEN LIGHT Power Switching 11
Power Switching CRESTRON GREEN LIGHT™

System Operation and Commissioning

This cabinet has been designed as a component of a programmed Crestron system. System commissioning by an authorized Crestron representative
Once the cabinet has been wired and the modules have been tested, contact Crestron at 1-888-CRESTRON [1-888-273-7876] to schedule commissioning.
must be performed to ensure system operation.
12 CRESTRON GREEN LIGHT Power Switching Installation Guide – DOC. 6672B
CRESTRON GREEN LIGHT™ Power Switching

Problem Solving

Troubleshooting

The following table provides corrective action for possible trouble situations. If further assistance is required, please contact a Crestron customer service representative.
Troubleshooting
TROUBLE POSSIBLE CAUSE(S) CORRECTIVE ACTION
Module(s) does not function.
Module’s PWR LED is flashing.
Unit cannot be taken out of Override mode
Fluorescent lamps stay at minimum intensity (0-10V dimmable fluorescents only).
Fluorescent lamps stay at maximum intensity (0-10V dimmable fluorescents only).
Power not delivered to the module.
System commissioning not complete.
AC power not present on L1.
Short (contact closure) exists between G and OVR terminals on any of the OVERRIDE terminals present at bottom of the cabinet.
+ or - wires are reversed or shorted.
+ or - wires are not connected.
If the module is powered internally, verify that the circuit breaker connected to the first channel on the module is on and delivering power to the module.
If module is powered externally, verify that the POWER port is correctly wired and receiving power.
Arrange for system commissioning.
Check that the branch breaker feeding L1 has not tripped. Note that unit will continue to function, but will draw power from the backup Cresnet power supply.
Determine the reason for the short. Remove or remedy the short (e.g. GLS-PLS-120/277 phase­loss sensor may not have been installed properly, or actual phase-loss has been detected).
Verify polarity of + and - wires at ballasts and GLXP-DIMFLV8.
Verify polarity of + and - wires at ballasts and GLXP-DIMFLV8.

Further Inquiries

If you cannot locate specific information or have questions after reviewing this guide, please take advantage of Crestron's award winning customer service team by calling Crestron at 1-888-CRESTRON [1-888-273-7876].
You can also log onto the online help section of the Crestron website ( questions about Crestron products. First-time users will need to establish a user accoun t to fully benefit from all available features.
Installation Guide – DOC. 6672B CRESTRON GREEN LIGHT Power Switching 13
www.crestron.com/onlinehelp) to ask
Power Switching CRESTRON GREEN LIGHT™

Appendix A: Setting Module Net IDs

The following procedure will normally be performed by an authorized Crestron representative as part of the System Commissioning phase. For system wiri ng and basic te sti n g as desc ri bed on pages 5 and 11, it is not necessary to perform this step. Only perform this step if instructed by an authorized Crestron representative, or when replacing modules on a system that have already been commissioned (in the latter case the Net ID should be set to match the Net ID of the module being replaced).
The Net ID of each module in the cabinet can be changed from the front panel of each module. The Net IDs of each module in the system must be unique.
To set the Net ID using the front panel:
1. Press the recessed SETUP button to enter the Setup mode. The SETUP LED illuminates.
2. As shown in the following diagram, press the left button under the NET ID display to chang e th e left digit
of the Net ID or press the right button under the NET ID display to change the right digit of the Net ID number.
Changing the Net ID
3. When the desired Net ID is displayed, press the SETUP button to exit the Setup mode. The SETUP LED
extinguishes.
If the SETUP button is not pressed, the Setup mode will time out after one minute activity and the Net ID will revert back to its original value.
14 CRESTRON GREEN LIGHT Power Switching Installation Guide – DOC. 6672B
CRESTRON GREEN LIGHT™ Power Switching

Appendix B: Module Specifications

Specifications for the GLXP modules are listed in the following table.
GLXP Module Specifications
SPECIFICATION GLXP-SW10 GLXP-SW16 GLXP-HSW8 GLXP-HSW12 GLXP-DIMFLV8
Description
Number of Outputs Cresnet Power
Usage* Input Voltage 100 – 277 VAC
Supported Load Types
Maximum Load Lighting Motor
Environmental Temperature
Humidity
Heat Dissipation
10 Channel
Switch Module
10 16 8 12 8
5 Watts 5 Watts 5 Watts 5 Watts 5 Watts
50/60 Hz
Incandescent, Magnetic Low Voltage, Electronic Low Voltage, Neon/Cold Cathode, Fluorescent Ballast, HID, Motor
16 A per output
1 HP @ 120V
2 HP @ 230/277V
32º to 104º F
(0º to 40º C)
10% to 90% RH
(non-condensing)
10 BTU/Hr
16 Channel
Switch Module
100 – 277 VAC
50/60 Hz
Incandescent, Magnetic Low Voltage, Electronic Low Voltage, Neon/Cold Cathode, Fluorescent Ballast, HID, Motor
16 A per output
1 HP @ 120V
2 HP @ 230/277V
32º to 104º F
(0º to 40º C)
10% to 90% RH
(non-condensing)
10 BTU/Hr
8 Channel High-
Inrush Switch
Module
100 – 277 VAC
50/60 Hz
Incandescent, Magnetic Low Voltage, Electronic Low Voltage, Neon/Cold Cathode, Fluorescent Ballast, HID, Motor
16 A per output
½ HP @ 120V 1 HP @ 230V,
1 HP @ 277V
32º to 104º F
(0º to 40º C)
10% to 90% RH
(non-condensing)
10 BTU/Hr
12 Channel High-
Inrush Switch
Module
100 – 277 VAC
50/60 Hz
Incandescent, Magnetic Low Voltage, Electronic Low Voltage, Neon/Cold Cathode, Fluorescent Ballast, HID, Motor
16 A per output
½ HP @ 120V 1 HP @ 230V,
1 HP @ 277V
32º to 104º F
(0º to 40º C)
10% to 90% RH
(non-condensing)
10 BTU/Hr
8 Channel 0-10V
Fluorescent
Dimmer Module
100 – 277 VAC
50/60 Hz
Dimmable Loads:
0-10 VDC dimmable fluorescent ballasts (i.e. Advance Mark 7 or other ballasts that comply with the specifications for control by DC voltage in ANSI C82.11:2002 and IEC60929:2006)
Non-Dim Loads: Incandescent, HID, magnetic low voltage (MLV), electronic low voltage (ELV), neon/cold cathode, and fluorescent ballasts, motor
16 A per output
½ HP @ 120V 1 HP @ 230V,
1 HP @ 277V
32º to 104º F
(0º to 40º C)
10% to 90% RH
(non-condensing)
10 BTU/Hr
* Power usage will be zero whenever AC power is present on circuit 1 on the module. Use of Cresnet power is optional.
Installation Guide – DOC. 6672B CRESTRON GREEN LIGHT Power Switching 15
Power Switching CRESTRON GREEN LIGHT™

Return and Warranty Policies

Merchandise Returns / Repair Service
1. No merchandise may be returned for credit, exchange or service without prior authorization from
CRESTRON. To obtain warranty service for CRESTRON products, contact an authorized CRESTRON dealer. Only authorized CRESTRON dealers may contact the factory and request an RMA (Return Merchandise Authorization) number. Enclose a note specifying the nature of the problem, name and phone number of contact person, RMA number and return address.
2. Products may be returned for credit, exchange or service with a CRESTRON Return Merchandise
Authorization (RMA) number. Authorized returns must be shipped freight prepaid to CRESTRON, 6 Volvo Drive, Rockleigh, N.J. or its authorized subsidiaries, with RMA number clearly marked on the outside of all cartons. Shipments arriving freight collect or without an RMA number shall be subject to refusal. CRESTRON reserves the right in its sole and absolute discretion to charge a 15% restocking fee plus shipping costs on any products returned with an RMA.
3. Return freight charges following repair of items under warranty shall be paid by CRESTRON,
shipping by standard ground carrier. In the event repairs are found to be non-warranty, return freight costs shall be paid by the purchaser.
CRESTRON Limited Warranty
CRESTRON ELECTRONICS, Inc. warrants its products to be free from manufacturing defects in materials and workmanship under normal use for a period of three (3) years from the date of purchase from CRESTRON, with the following exceptions: disk driv es and any other moving or rotating mechanical parts, pan/tilt heads and power supplies are covered for a period of one (1) year; touchscreen display and overlay components are covered for 90 days; batteries and incandescent lamps are not covered.
This warranty extends to products purchased directly from CRESTRON or an authorized CRESTRON dealer. Purchasers should inquire of the dealer regarding the nature and extent of the dealer's warranty, if any.
CRESTRON shall not be liable to honor the terms of this warranty if the product has been used in any application other than that for which it was intended or if it has been subjected to misuse, accidental damage, modification or improper installation procedures. Furthermore, this warranty does not cover any product that has had the serial number altered, defaced or removed.
This warranty shall be the sole and exclusive remedy to the original purchaser. In no event shall CRESTRON be liable for incidental or consequential damages of any kind (property or economic damages inclusive) arising from the sale or use of this equipment. CRESTRON is not liable for any claim made by a third party or made by the purchaser for a third party.
CRESTRON shall, at its option, repair or replace any product found defective, without charge for parts or labor. Repaired or replaced equipment and parts supplied under this warranty shall be covered only by the unexpired portion of the warranty.
Except as expressly set forth in this warranty, CRESTRON makes no other warranties, expressed or implied, nor authorizes any other party to offer any warranty, including any implied warranties of merchantability or fitness for a particular purpose. Any implied warranties that may be imposed by law are limited to the terms of this limited warranty. This warranty statement supersedes all previous warranties.
Trademark Information
All brand names, product names and trademarks are the sole property of their respective owners. Windows is a registered trademark of Microsoft Corporation. Windows95/98/Me/XP/Vista and WindowsNT/2000 are trademarks of Microsoft Corpora tion.
16 CRESTRON GREEN LIGHT Power Switching Installation Guide – DOC. 6672B
Loading...