Crestron GLS-ODT-C-500/1000/2000

DUAL-TECHNOLOGY CEILING MOUNTED

OCCUPANCY SENSOR

Operations & Installation Guide

FCC Compliance Statement:

This device complies with part 15 and part 18 of the FCC rules. Operation is subject to the following two conditions: (1) This device must not cause harmful interference, and (2) This device must accept any interference received, including interference that may cause undesired operation.

Further Inquiries

If you cannot locate specific information or have questions after reviewing this guide, please take advantage of Crestron's award winning customer service team by calling Crestron at 1-888-CRESTRON [1-888-273-7876].

You can also log onto the online help section of the Crestron website (www.crestron.com/onlinehelp) to ask questions about Crestron products. First-time users will need to establish a user account to fully benefit from all available features.

Future Updates

As Crestron improves functions, adds new features and extends the capabilities of the GLS-ODT-C units, additional information may be made available as manual updates. These updates are solely electronic and serve as intermediary supplements prior to the release of a complete technical documentation revision.

Check the Crestron website periodically for manual update availability and its relevance. Updates are identified as an “Addendum” in the Download column.

Crestron Electronics, Inc.

Operations & Installation Guide-DOC. 6769A

15 Volvo Drive Rockleigh, NJ 07647

(2023016)

Tel: 888.CRESTRON

12.08

Fax: 201.767.7576

Specifications subject to

www.crestron.com

change without notice.

 

 

 

 

WARNINGS, CAUTIONS & NOTES

WARNING: To avoid fire, shock, or death; turn off power at circuit breaker or fuse and test that power is off before wiring!

CAUTION: Insufficient power can lead to unpredictable results or damage to the equipment. Please use the Crestron Power Calculator to help calculate how much power is needed for the system. (www.crestron.com/calculators).

NOTES: Observe the following points regarding sensor installation.

To be installed and/or used in accordance with appropriate electrical codes and regulations.

If you are unsure about any part of these instructions, consult a qualified electrician.

Sensors must be mounted on a vibration free surface.

All sensors must be mounted at least 6 feet away from air vents.

Do not mount sensors closer than 10 feet from each other.

Do not touch the inner surface of the lens. Clean outer surface with a damp cloth only.

NETWORK WIRING

When wiring the Cresnet® network, consider the following:

Use Crestron Certified Wire.

Use Crestron power supplies for Crestron equipment.

Provide sufficient power to the system.

PREPARING AND CONNECTING WIRES

Strip the ends of the wires approximately 1/2”. Use care to avoid nicking the conductors. Twist together

the ends of the wires that share a connection and tin the twisted connection. Apply solder only to the

ends of the twisted wires. Avoid tinning too far up the wires or the end becomes brittle.

DESCRIPTION

The Occupancy Sensor is a low-voltage infrared and ultrasonic sensor that works with the GLS-SIM (or other compatible interface) to automatically control lighting. The exact behavior of the sensor can be configured via software, but the sensor is typically used to turn lights on when a room or area is occupied, and to shut them off when the room or area is vacated. The sensor continually analyzes and adjusts to changing conditions. The sensor uses the latest microprocessor-based technology which permits it to continually adjust and optimize its performance. The combination of ultrasonic (doppler shift) motion detection, which gives maximum sensitivity, and infrared motion detection, which gives higher false triggering immunity, yields a sensor with excellent performance.

Model/Feature Basics

Model No.

Description

Current

Operating

 

Suggested

Consumption

Frequency

Coverage

Mounting Location

GLS-ODT-C-500

1-Way Dual-Technology

30mA

40KHz

500 sq. ft

Mount in corner/

over doorway

 

 

 

 

 

GLS-ODT-C-1000

2-Way Dual-Technology

40mA

40KHz

1000 sq. ft.

Mount in center

of room/area

 

 

 

 

 

GLS-ODT-C-2000

2-Way Dual-Technology

32mA

32KHz

2000 sq. ft.

Mount in center

of room/area

 

 

 

 

 

 

 

 

 

 

 

INSTALLATION INSTRUCTIONS

These instructions include three typical installation options (A, B, and C). Choose one that best suits your needs. Other methods may be possible but they are not described here.

Parts Supplied

 

Sensor (1)

Threaded Rod (1) and Hex nut (1)

#8-32 x 1/2” screw (2)

Half Mask (1)

#8-32 x 1-1/2” screw (2)

360º Perforated Mask (1)

#8x32 Washer and Nut (2)

Plastic Washer (1)

Tools/Equipment Required (not supplied)

Phillips Screwdriver

Electrical Tape

Pliers

Pencil

Diagonal Cutters

 

Option A. Drop Ceiling Installation Using Supplied Threaded Rod

1.Select the location for mounting the sensor and proper masking for your application. (Refer to Mounting/Masking Location Diagram).

2.Use the supplied threaded rod or other means to make a hole (1/2" to 1") in the ceiling tile just large enough to pass the shaft of the threaded rod through.

3.Insert the sensor wires through the flared end of the threaded rod. Position the threaded rod to the base of the sensor.

4.Insert the flared end of the threaded rod into the opening in the bottom of the sensor and twist to lock into place.

5.Push the wires into the hole in the ceiling tile and insert the threaded rod until the sensor is flush with the tile.

6.Insert wires through the hole in the included washer, then place the washer over the rod and secure in position using the included hex nut.

7.Connect low voltage wires from the GLS-SIM or other Crestron® device as shown in the wiring diagram. Twist strands of each lead tightly and, with circuit conductors, push firmly into appropriate wire connector. Screw connectors on clockwise making sure that no bare conductor shows below the wire connectors. Secure each connector with electrical tape.

8.Rotate the sensor to the desired orientation. Note that the sensor base and backcover are keyed. To lock the device in place, ensure that the arrows are not aligned.

9.Restore power at circuit breaker or fuse. INSTALLATION IS COMPLETE.

Mounting to Drop Ceiling Using Threaded Rod

Low-Voltage Wires

 

Drop Ceiling

 

 

1" thick maximum

Nut

GLS-SIM (Optional)

 

Washer

 

Threaded Rod

NOTE: Wires routed through the Threaded Rod

OPTION B. Drop Ceiling Installation Using Screws

NOTE: You may use the mounting screws, nuts and washers included, or screws in combination with commercially available wall anchors.

1.Select the location for mounting of the sensor and proper masking for your application (Refer to Mounting/Masking Location Diagram).

2.Make a hole in the ceiling tile large enough to pass the wire connections and wire nuts through (approximately 1" diameter).

3.Remove the back cover of the sensor. Hold the back cover and body of the sensor and rotate until the two arrows line up, and pull them apart.

4.Install back cover of the ceiling sensor to the wallboard or drop ceiling using the included screws, nuts and washers, or screws in combination with commercially available wall anchors.

OPTION B. Drop Ceiling Installation Using Screws (Cont’d)

5.Connect low voltage wires from the GLS-SIM or other Crestron device as shown in the wiring diagram. Twist strands of each lead tightly and, with circuit conductors, push firmly into appropriate wire connector. Screw connectors on clockwise making sure that no bare conductor shows below the wire connectors. Secure each connector with electrical tape.

6.Push wire connections through the center hole of the back cover and into the ceiling.

7.Secure the sensor body to the back cover by aligning the arrows. Lock it by turning the sensor such that the arrows do not line up.

8.Rotate the sensor to the desired orientation.

9.Restore power at the circuit breaker or fuse. INSTALLATION IS COMPLETE.

Mounting to Drop Ceiling Using Screws

Low-Voltage Wires

 

Nut (2 places)

 

Washer (2 places)

Wallboard

 

Ceiling

Sensor

 

Back Cover

 

Mounting Screws

 

(2 places)

 

Keylock Arrow

Back Cover open center to route Low-Voltage Wires

Mounting Screw

Back Cover internal surface shown

Sensor Base

Back Cover shown mounted

on ceiling with screws

Sensor Front Cover

 

OPTION C. Back Box or Surface Mount Raceway Installation

1.Select the location for mounting of the sensor and proper masking for your application (Refer to Mounting/Masking Location Diagram).

2.Refer to the suggested mounting option illustrations below.

Mounting to Octagon Back Box Installed Flush to Drop Ceiling

Octagon Back Box 4" x 1 1/2" deep

GLS-SIM (Optional)

Drop Ceiling

Wires

Low-Voltage

#8-32 Screws (2 places)

Mounting to Round Fixture with Raceway for Wallboard Ceiling Installation

Wire Mold Back Cover

Back Cover Screws (4 places)

Wire Mold Round Fixture

(for raceway mount)

GLS-SIM (Optional)

Low-Voltage Wires

Mounting Screws

(4 places)

Wallboard Ceiling

Wire Mold Raceway (use applicable fittings)

MOUNTING/MASKING LOCATION DIAGRAM

The supplied masks mount in the sensor front cover. The half mask is supplied pre-mounted to demonstrate the mounting method. The perforated mask has twelve 30º removable segments that allow you to mask particular areas to prevent undesireable triggers from affecteng the sensor operation. The following illustrations provide typical application examples.

Mask

Masking is not required in a corner

mounting application. The sensor traffic can not see hallway traffic.

TYPICAL APPLICATION DIAGRAMS

Up to Three

in Crestron Parallel

2-Series Control Cresnet® GLS-SIM Processor or

CLS-C6

GLS-ODT-C-500/1000/2000

Crestron

Cresnet®

 

 

 

 

2-Series Control

 

DIN-IO8

 

 

 

Processor

 

 

 

 

 

 

 

GLS-ODT-C-500/1000/2000

WIRING DIAGRAMS

Connecting Sensors to the GLS-SIM

All wires from sensor to GLS-SIM must be 24 AWG, minimum.

*

Blue*

*

Blue

Blue

Black

Black

Black

(cap off)

 

 

Gray*

 

Sensor

 

Sensor

 

Sensor

 

 

 

 

#3

 

#2

 

#1

 

 

 

 

Red (optional)

Red

(optional)

Red

 

GLS-SIM

 

 

 

 

 

 

 

 

––– NET––– –SENSOR–

 

 

*To incorporate the internal photocell, connect

 

 

24 Y Z G

 

 

gray wire to GLS -SIM and cap off blue wire

 

 

24 1 2 G

 

 

from sensor.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

To Control

 

 

 

 

 

 

Use CRESNET-P or

System

 

 

 

 

 

 

CRESNET-NP wire only

 

Connecting Sensors to the DIN-IO8 or Equivalent**

 

 

 

Blue*

 

 

 

 

 

 

 

 

 

 

 

G 1

2 3 4

G 1 2 3 4

 

 

 

 

 

 

––– I/O –––

 

 

 

 

Gray*

(cap off)

 

DIN-IO8

 

 

 

 

 

 

 

 

 

Black

Sensor

 

 

 

 

 

 

 

 

 

––– NET –––

 

 

 

 

#1

 

 

 

 

Red

 

24 Y

Z G

24 Y Z G

 

 

 

 

 

 

 

 

 

 

 

 

 

 

To Control

 

 

 

 

 

 

Use CRESNET-P or

System

 

 

 

 

 

 

 

 

**The following Crestron devices may be used to

 

 

CRESNET-NP wire only

 

 

 

 

 

 

 

integrate the sensors into a Cresnet system by

NOTE: The same Crestron power supply MUST be used to

following the schematic shown here:

 

power both the sensors and the interface device (e.g., DIN-IO8).

DIN-IO8 DIN-AP2

PAC2

PRO2

Otherwise, there is a risk of damage to the interface device.

 

 

 

 

 

AV2

CP2E

MP2E

CNXIO16

*To incorporate the internal photocell, connect the gray wire to

Any Crestron product with Versiports

the DIN-IO8 (or other interface device) and cap off the blue wire

from the sensor.

 

 