Crestron electronic CLS-EXP-DIMU User Manual

Page 1
CLS-EXP-DIMU

Functional Summary

The CLS-EXP-DIMU enables the expansion of the Crestron iLux™ Integrated Lighting System (CLS-C6 series) and other Crestron lighting dimmers to allow dimming of both forward and reverse phase type loads. Supported loads include electronic low-voltage, magnetic low-voltage, incandescent, neon/cold cathode, or 2-wire dimmable fluorescent. A single model supports 120, 230, or 277 Volt loads up to 16 Amps.
The CLS-EXP-DIMU simplifies installation by auto­detecting the dimmable load type connected to it and selecting the appropriate dimming mode to control that load. Reverse phase (trailing edge) dimming supports incandescent and electronic low-voltage load types, while forward phase (leading edge) dimming handles magnetic low-voltage, neon, and other inductive load types.
Any output channel of the iLux system can be used to control the CLS-EXP-DIMU to dim a fully loaded circuit. It is also compatible with CLW-Series and select CLX-Series lighting control modules. The metal enclosure is designed for mounting to a vertical surface and can be installed in a space used for environmental air as defined in NEC Article 30 0.22(C). Conduit knockouts are provided on the bottom and lower sides. All connections are made via screw terminals behind the front cover.
Works with Crestron iLux (CLS-C6 series),
DIN-1DIMU4, CLW1 Series, and CLX Series dimmers
Emulates the characteristics of the dimmer that is
controlling it
Up to five Expansion Modules can be connected
to a single dimmer output
Supports 120, 230, and 277 Volt ELV, MLV,
NCC, incandescent, and 2-wire dimmable fluorescent loads
Auto-selects for forward or reverse phase
Can be installed in an air-handling space2
Includes threshold adjustment for setting
minimum fluorescent dimming level
Built-in air gap relay at the output
Surface mount design
1. CLW-Series devices must have a dedicated neutral.
2. As defined in NEC Article 300.22(C).
1
in-wall dimmers
CLS-EXP-DIMU Physical View

Specifications

CLS-EXP-DIMU Specifications
SPECIFICATION DETAILS
Load Ratings Output Channels Load Rating Minimum Load
at 120 Volts at 230 Volts at 277 Volts
Load Types
Maximum Modules per Dimmer Output
Input Voltages Line Power Control Input
Electrical Terminals Captive screw type;
1 16 Amps
15 Watts 25 Watts 30 Watts
Electronic Low Voltage, Incandescent, Neon/Cold Cathode, Magnetic Low Voltage, 2-Wire Dimmable Fluorescent (Advance Mark 10 Powerline equivalent)
5
120 to 277 Volts AC, 50/60 Hz 120 or 230 Volts AC, 50/60 Hz,
phase independent of line power and load, presents 25 Watts load to the controlling device
Accommodates two 22-12 AWG (0.34-4.0 mm2) wires
®
or
(Continued on following page.)
Crestron Electronics, Inc. Installation Guide – DOC. 6682B
15 Volvo Drive Rockleigh, NJ 07647 (2020684) Tel: 888.CRESTRON 02.09 Fax: 201.767.7576 Specifications subject to www.crestron.com change without notice.
Page 2
iLux™ Expansion Module Crestron CLS-EXP-DIMU
CLS-EXP-DIMU Specifications (continued)
SPECIFICATION DETAILS
Enclosure Surface mount module with (2)
Environmental Temperature Humidity
Heat Dissipation
integral mounting flanges, galvanized steel w/gray matte powder coat front panel, extruded aluminum heat sink, ½” and ¾” conduit knockouts provided on bottom and lower left & right sides
32° to 104°F (0° to 40°C) 10% to 90% RH
(non-condensing) 200 BTU/Hr at maximum load
(Continued on following column.)
CLS-EXP-DIMU Specifications (continued)
SPECIFICATION DETAILS
Dimensions Height Width Depth Weight
Compatible Control Devices
CLS(I)-C6 Series CLW-DIM Series CLW-DIMXRF Series CLX(I)-1DIM4
CLX-1DIM8
CLX(I)-2DIM2
CLX(I)-2DIM8
DIN-1DIMU4
8.82 in (22.40 cm)
6.39 in (16.23 cm)
3.18 in (8.08 cm)
3.34 lbs (1.52 kg)
iLux Integrated Lighting System Wall Dimmers infiNet™ Wall Dimmers Four Channel Dimmer Module,
Single Feed Eight Channel Dimmer Module,
Single Feed Two Channel Dimmer Module,
Two Feeds Eight Channel Dimmer Module,
Two Feeds DIN Rail Universal Dimmer

Industry Compliance

This product is Listed to applicable UL Standards and requirements by Underwriters Laboratories Inc. These devices have been additionally evaluated to UL 2043, The Standard for Fire Test for Heat and Visible Smoke Release for Discrete Products and Their Accessories Installed in Air-Handling Spaces.
(E103692)
As of the date of manufacture, the CLS-EXP-DIMU has been tested and found to comply with specifications for CE marking.
NOTE: This device complies with part 15 of the FCC rules. Operation is subject to the following two conditions: (1) this device may not cause harmful interference and (2) this device must accept any interference received, including interference that may cause undesired operation.
This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses and can radiate radio frequency energy and if not installed and used in accordance with the instructions, may cause harmful interference to radio comm unications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures:
Reorient or relocate the receiving antenna. Increase the separation between the equipment and receiver. Connect the equipment into an outlet on a circuit different from that to which the receiver is connected. Consult the dealer or an experienced radio/TV technician for help.
2 iLux™ Expansion Module: CLS-EXP-DIMU Installation Guide – DOC. 6682B
Page 3
Crestron CLS-EXP-DIMU iLux™ Expansion Module

Application

The following diagram shows several CLS-EXP-DIMU modules in a typical application.
CLS-EXP-DIMU Modules in a Lighting Application
Installation Guide – DOC. 6682B iLux Expansion Module: CLS-EXP-DIMU 3
Page 4
iLux™ Expansion Module Crestron CLS-EXP-DIMU
Connectors, Controls & Indicators

Physical Description

This section provides information on the connections, controls and indicators available on the CLS-EXP-DIMU.
CLS-EXP-DIMU Overall Dimensions
1.56 in
(3.96 cm)
3.18 in
(8.08 cm)
3.07 in
(7.80 cm)
2.02 in
(5.21 cm)
8.82 in
(22.40 cm)
4.99 in
(12.67 cm)
(16.23 cm)
(14.71 cm)
6.39 in
5.79 in Ø 0.19 in
(Ø 0.48 cm)
(21.11 cm)
7.31 in
(18.57 cm)
0.50 in
(1.27 cm)
Ø 0.25 in
(Ø 0.64 cm)
8.31 in
# CONNECTORS,
CONTROLS &
INDICATORS
1 FLUORESCENT
OFF THRESHOLD
(1) Recessed screwdriver­adjustable trim pot, adjusts minimum brightness level. Covered by removable cap.
2 PHASE LED (1) Yellow LED behind front
panel; illuminates when operating in Reverse Phase mode.
3 STATUS LED (1) Red LED behind front
panel; illuminates when load output is on.
4 POWER LED (1) Green LED behind front
panel; indicates power is applied to the HOT terminal.
5 S2
21
ON
(1) Two-position DIP switch behind front panel; used to select the zero cross detection filter.
For more information, refer to “Zero Cross Detection Filter” on page 6.
6 S1
ON
(1) Two-position DIP switch behind front panel; used to
12
select dimming mode. For more information, refer to
“Dimming Mode” on page 6.
DESCRIPTION
1.64 in
(4.17 cm)
1.64 in
(4.17 cm)
CLS-EXP-DIMU (cover removed)
1
7
2 3
8 9
12
4 5 6
S2
PHASE
POWER
STATUS
S1
ON
ON
12 21
10 11
7 CTRL (1) Captive screw terminal, for
control input from CLS-Series, CLW-Series* dimmers, CLX-DIM (all versions), or other Crestron incandescent dimmers.
8 NEUT (INPUT) (1) Captive screw terminal, for
neutral connection for control input.
9 DIM OUT (1) Captive screw terminal for
dimmed output to the load.
10 HOT (1) Captive screw terminal, for
line power input.
11 NEUT (OUTPUT) (1) Captive screw terminal,
neutral connection for line power input and load.
12 GROUND (1) Chassis ground bus bar.
* CLW-Series device must have a dedicated neutral.
4 Terminal Block & Module: CLTI- & CLXI-2DIM8 Installation Guide – DOC. 6682B
Page 5
Crestron CLS-EXP-DIMU iLux™ Expansion Module

Hardware Hookup

Setup

Important Notes

Read before installation.
Permits: An electrical permit shall be obtained
prior to each installation.
Codes: Install in accordance with all local and
national electrical codes.
Wiring: Use 75°C copper wire only.
Not suitable for Hazardous/Classified areas.

Installation

The CLS-EXP-DIMU can be installed vertically on a wall and can also be installed in a space used for environmental air as defined in NEC Article 30 0.22(C). Refer to the following diagram when installing a CLS-EXP-DIMU module.
Module Installation
MOUNTING SURFACE
CLS-EXP-DIMU MODULE
MOUNTING SCREW, #8, QTY 4 TOTAL (NOT SUPPLIED)
WARNING: RISK OF SERIOUS PERSONAL INJURY. Turn off power at the circuit breaker(s) prior to
installation. Installing with power on can result in serious personal injury and damage to the device.
1. Use a #2 Philips screwdriver to remove the cover
screws as shown in the following diagram and remove the cover.
Remove Cover Screws
COVER SCREWS
(x4)
2. Depending on the module’s application, select the
appropriate configuration from one of the wiring diagrams on the next page and connect the CLS-C6 and load(s) as shown.
To ensure proper ventilation:
The device must be installed vertically on a vertical
surface. NOTE: To prevent potential heat damage to
drywall, do not mount the CLS-EXP-DIMU directly onto drywall. Mount a piece of ½” (minimum) thick plywood between the CLS-EXP-DIMU and the drywall.
Install device with 6 inches (152 mm) of clearance
from the top and bottom of the device.
Do not connect wires of differing gauge to a
single terminal.
Wires should be stripped to 7/16” (11 mm)
Tighten terminal screws to 7 in-lbs (0.79 Nm)
NOTE: Dimmers controlling one or more CLS-EXP-DIMU modules must not be wired to control any other type of load.
NOTE: When using a CLW-Series wall dimmer, the wall dimmer must be wired with a dedicated neutral wire.
NOTE: While these diagrams show a CLS-C6 as the controlling source, other Crestron products such as CLW-Series wall dimmers (Cresnet infiNET™), DIN-1DIMU4, and CLX-Seri es dimming modules can be used as well. Please refer to the specific dimmer’s Installation Guide for detailed information.
®
and
Installation Guide – DOC. 6682B iLux™ Expansion Module: CLS-EXP-DIMU 5
Page 6
iLux™ Expansion Module Crestron CLS-EXP-DIMU
CLS-EXP-DIMU Wiring with Dual Feeds
HOT
(120 to 277 VAC)
NEUTRAL
HOT
(120 (230) VAC)
NEUTRAL
LOAD 3 LOAD 2
LOAD 1 HOT NEUTRAL
CLS(I)-C6
CLS-EXP-DIMU
HOT
DIM OUT
NEUTRAL
CONTROL
NEUTRAL
Multiple CLS-EXP-DIMU Modules
HOT
(120 to 277 VAC)
NEUTRAL
HOT
(120 to 277 VAC)
NEUTRAL
HOT
(120 (230) VAC)
NEUTRAL
LOAD 3 LOAD 2
LOAD 1
HOT NEUTRAL
CLS(I)-C6
CLS-EXP-DIMU
HOT
DIM OUT
NEUTRAL
CONTROL
CLS-EXP-DIMU
HOT
DIM OUT
NEUTRAL
CONTROL
NEUTRAL
NEUTRAL
3. Apply power to the line/load and turn on the
controlling device. The power indicator LED will light indicating that power is supplied to the module.
NEUTRAL
DIM OUT
NEUTRAL
DIM OUT
NEUTRAL
DIM OUT
Lighting
Loads
Lighting
Loads
Lighting
Loads
The dimming mode can be changed by adjusting the S1 DIP switches as detailed in the following table.
Switch Settings for S1 DIP Switch
SW. 1 SW. 2 DIMMING MODE LOAD TYPES
Off Off Auto Detect
(Default, recommended)
On Off Reverse Phase Incandescent,
On On Forward Phase Magnetic Low
All
Electronic Low Voltage
Voltage, Neon/CC, 2-wire dimmable Fluorescent

Zero Cross Detection Filter

The CLS-EXP-DIMU performs filtering to compensate for noise on the incoming AC line. This filtering is useful for eliminating flickering of the load caused by line noise. If necessary, this filtering can be disabled.
Disabling the zero cross detection filter should not be necessary, and is not recommended unless suggested by a Crestron technical support representative.
WARNING: RISK OF SERIOUS PERSONAL INJURY. Turn off power at the circuit breaker(s) prior to
changing any switch settings. Changing settings with power on can result in serious personal injury and damage to the device.
4. Replace the cover and cover screws.

Dimming Mode

The CLS-EXP-DIMU is capable of automatically detecting the attached load type, and setting itself for forward-phase (leading edge) or reverse-phase (trailing edge) dimming accordingly. In addition, the unit can be forced to perform forward- or reverse-phase dimming by overriding the automatic detection.
Disabling the Auto Detect mode should not be necessary, and is not recommended unless suggested by a Crestron technical support representative.
WARNING: RISK OF SERIOUS PERSONAL INJURY. Turn off power at the circuit breaker(s) prior to
changing any switch settings. Changing settings with power on can result in serious personal injury and damage to the device.
The function of the zero cross detection filter is set using the S2 DIP switch. Refer to the following table when setting the zero cross detection filter.
Switch Settings for S2 DIP Switch
SW. 1 SW. 2 DESCRIPTION
Off Off Enable zero cross detection filter
(Default, recommended). Provides maximum filtering under various line noise conditions.
On Off Disable zero cross detection filter.
Allows rapid tracking of the AC line. Suitable when using generators for AC line power.

Set the Minimum Dimming Level

Certain types of loads can flicker when dimmed too low. Adjust the FLUORESCENT OFF THRESHOLD to prevent the CLS-EXP-DIMU from attempting to dim the load below a certain level. To adjust:
1. Remove the cap from the FLUORESCENT OFF
THRESHOLD adjustment from the inside of the cover (requires removal of cover as shown on previous page).
6 iLux™ Expansion Module: CLS-EXP-DIMU Installation Guide – DOC. 6682B
Page 7
Crestron CLS-EXP-DIMU iLux™ Expansion Module
2. Using a flat-head screwdriver, turn the
FLUORESCENT OFF THRESHOLD
adjustment counter-clockwise until it stops.
3. Set the CLS-C6 so that the light output is on but is
below the desired minimum level.
4. Turn the FLUORESCENT OFF THRESHOLD
adjustment clockwise until the light output is at the desired minimum level.
5. Replace the cap.

Problem Solving

Troubleshooting

The following table provides corrective action for possible trouble situations. If further assistance is required, please contact a Crestron customer service representative.
CLS-EXP-DIMU Troubleshooting
TROUBLE POSSIBLE
Load does not turn on.
Load turns on and off, but will not dim.
Lights do not dim properly.
CAUSE(S)
Controller is not working.
No power applied to HOT terminal.
Controlling unit is either not a dimmer, or has been set to non­dim.
FLUORESCENT OFF THRESHOLD has
been set too high. Using an incompatible dimmer.
CORRECTIVE
ACTION
Make sure the controller is powered on, and is one of the compatible dimmers listed in “Specifications” on page 1.
Check circuit breaker. Check that green POWER LED on inside of unit is lit.
Verify that dimmer is compatible with the CLS-EXP-DIMU (refer to “Specifications” on page 1). Verify that the controlling channel has not been programmed as non-dim. Refer to “Set the Minimum Dimming Level” on page 6.
Make sure that the dimmer is one of those listed in “Specifications” on page 1.
CLS-EXP-DIMU Troubleshooting (continued)
TROUBLE POSSIBLE
Audible noise while dimming.
Lights flicker when at certain dimming levels.
Lights cannot be dimmed below a certain level.
CAUSE(S)
Load is being dimmed in wrong mode.
Large incandescent load.
Some types of loads cannot be dimmed below a certain level.
FLUORESCENT OFF THRESHOLD has
been set too high.
CORRECTIVE
ACTION
Refer to the list of load types in the table at the top of page 6. Check the PHASE LED to ensure that the load is being dimmed in the proper way for the attached load type. If the unit is set to Auto, and the improper mode is being used, follow the instructions on page 6 to override the Auto setting and force the unit to the proper mode. Some incandescent loads can make noise when dimmed due to the size of the filament. Try a different lamp manufacturer. Refer to “Set the Minimum Dimming Level” on page 6.
Refer to “Set the Minimum Dimming Level” on page 6.

Further Inquiries

If you cannot locate specific information or have questions after reviewing this guide, pl ease t ake advantage of Crestron's award winning customer service team by calling Crestron at 1-888-CRESTRON [1-888-273-7876].
You can also log onto the online help section of the Crestron website ( questions about Crestron products. First-time users will need to establish a user account to fully benefit from all available features.
www.crestron.com/onlinehelp) to ask
(Continued on following column.)
Installation Guide – DOC. 6682B iLux™ Expansion Module: CLS-EXP-DIMU 7
Page 8
iLux™ Expansion Module Crestron CLS-EXP-DIMU

Return and Warranty Policies

Merchandise Returns / Repair Service
1. No merchandise may be retu rned for credit, exchange or service without prior authorization from
CRESTRON. To obtain warranty service for CRESTRON products, contact an authorized CRESTRON dealer. Only authorized CRESTRON dealers may contact the factory and request an RMA (Return Merchandise Authorization) number. Enclose a note specifying the nature of the problem, name and phone number of contact person, RMA number and return address.
2. Products may be returned for credit, exchange or service with a CRESTRON Return Merchandise
Authorization (RMA) number. Authorized returns must be shipped freight prepaid to CRESTRON, 6 Volvo Drive, Rockleigh, N.J. or its authorized subsidiaries, with RMA number clearly marked on the outside of all cartons. Shipments arriving freight collect or without an RMA number shall be subject to refusal. CRESTRON reserves the right in its sole and absolute discretion to charge a 15% restocking fee plus shipping costs on any products returned with an RMA.
3. Return freight charges following repair of items under warranty shall be paid by CRESTRON,
shipping by standard ground carrier. In the event repairs are found to be non-warranty, return freight costs shall be paid by the purchaser.
CRESTRON Limited Warranty
CRESTRON ELECTRONICS, Inc. warrants its products to be free from manufacturing defects in materials and workmanship under normal use for a period of three (3) years from the date of purchase from CRESTRON, with the following exceptions: disk driv es and any other moving or rotating mechanical parts, pan/tilt heads and power supplies are covered for a period of one (1) year; touchscreen display and overlay components are covered for 90 days; batteries and incandescent lamps are not covered.
This warranty extends to products purchased directly from CRESTRON or an authorized CRESTRON dealer. Purchasers should inquire of the dealer regarding the nature and extent of the dealer's warranty, if any.
CRESTRON shall not be liable to honor the terms of this warranty if the product has been used in any application other than that for which it was intended or if it has been subjected to misuse, accidental damage, modification or improper installation procedures. Furthermore, this warranty does not cover any product that has had the serial number altered, defaced or removed.
This warranty shall be the sole and exclusive remedy to the original purchaser. In no event shall CRESTRON be liable for incidental or consequential damages of any kind (property or economic damages inclusive) arising from the sale or use of this equipment. CRESTRON is not liable for any claim made by a third party or made by the purchaser for a third party.
CRESTRON shall, at its option, repair or replace any product found defective, without charge for parts or labor. Repaired or replaced equipment and parts supplied under this warranty shall be covered only by the unexpired portion of the warranty.
Except as expressly set forth in this warranty, CRESTRON makes no other warranties, expressed or implied, nor authorizes any other party to offer any warranty, including any implied warranties of merchantability or fitness for a particular purpose. Any implied warranties that may be imposed by law are limited to the terms of this limited warranty. This warranty statement supersedes all previous warranties.
Trademark Information
All brand names, product names and trademarks are the sole property of their respective owners. Windows is a registered trademark of Microsoft Corporation. Windows95/98/Me/XP/Vista and WindowsNT/2000 are trademarks of Microsoft Corpora tion.
8 iLux™ Expansion Module: CLS-EXP-DIMU Installation Guide – DOC. 6682B
Loading...