The iLux™ units, CLS-C6RF and CLS-C6MRF, are wall­mounted complete integrated lighting systems that can function as standalone devices and/or be part of a Crestron® solution total control system network (Cresnet®). The units are functionally identical except that the CLS-C6MRF includes a built-in motion sensor.
CLS-C6MRF with Cover Open, Shown in Almond
Each unit provides automated control of up to six channels of lighting loads, including incandescent, magnetic low­voltage, neon/cold cathode, and two-wire dimmable fluorescent. Each unit also provides automated control of up to six groups of shade and drape controllers for motorized window treatments, screens, and lifts.
Front panel operation provides manual control of lighting loads and shade groups as well as access to up to sixteen scenes (lighting level/shade position combinations).
A built-in IR receiver allows for wireless operation using an optional infrared remote generating standard RC5 commands; a built-in motion detector (CLS-C6MRF only) enables automated control based on room occupancy.
Up to 16 Crestron keypads (sold separately) can be used with each unit for control of rooms that have several entrances or work areas. Each unit also supports up to eight additional CLS-C6RF units, enabling systems of up to 54 lighting channels and 54 shade groups.
The CLS-C6RF employs Crestron's infiNET technology to enable a wireless link to a 2-Series control system. A single C2N-MNETGW gateway connected to the control system enables 2-way wireless communications between the iLux system and the central control system, allowing iLux's functions to be controlled from touchpanels, RF wireless remotes, and even computers.
Each unit is available in three colors: almond, black, or white. The letter at the end of the product name, ‘A’, ‘B’, or ‘W’, denotes the color (e.g., a CLS-C6MRFA is an almond unit).

Specifications

Following are specifications for the iLux units.
CLS-C6RF & CLS-C6MRF Specifications
SPECIFICATION
Power Requirements Line Power, 120 VAC, 60Hz
Load Ratings1 Max load per channel
Min load per channel
Max load per unit
Note that if the unit is fed from an arc fault circuit interrupter (required if controlling loads in a bedroom), the maximum total load is 1000 W/VA
Load Types1 Incandescent, magnetic low
IR Receiver For use with Crestron IR
RF Wireless RF Transceiver
Range (typical)
Gateway
Motion Detector (CLS-C6MRF only) Type Range
Default MNET ID 1F
Control System Update Files 2-Series Control System
Firmware CLS-C6.v1.0.upg or later
800 W/VA (6.6 Amps @ 120 VAC), Expandable via Expansion Modules (sold separately)
15 W/VA (0.125 Amps @ 120 VAC)
1920 W/VA (16 Amps @ 120 VAC)
voltage, neon/cold cathode, dimmable 2-wire fluorescent, and non-dim lighting (also: electronic low voltage, 3-wire and 4-wire fluorescent, High-Inrush Switching, 277V via expansion modules; sold separately)
remote (sold separately).
2-way RF, 2.4 GHz ISM Channels 11-26 (2400 to
2483.6 MHz), IEEE 802.15.4 compliant
150 feet indoor, 250 feet outdoor; subject to site-specific conditions; range is increased by adding additional devices or C2N-MNETRPT repeater;
Requires a C2N-MNETGW RF gateway
Infrared 20 to 30 feet at 4-foot elevation
2, 3
Version 2.004.CUZ or later
(Continued on following page)
DETAILS
and
Crestron Electronics, Inc. Installation Guide – DOC. 6416A
15 Volvo Drive Rockleigh, NJ 07647 (2013966) Tel: 888.CRESTRON 06.08 Fax: 201.767.7576 Specifications subject to www.crestron.com change without notice.
iLux™ Integrated Lighting Systems w/infiNET
CLS-C6RF & CLS-C6MRF Specifications (Continued)
SPECIFICATION
Environmental Temperature 32° to 104°F (0° to 40°C)
Humidity 10% to 90% RH
Overall Dimensions: Height
Width Depth
Weight 22.8 oz (646.37 g)
1. Additional load types can be controlled and load ratings can be increased via optional CLS-EXP expansion modules. Refer to the Crestron website
http://www.crestron.com/
2. The latest software versions can be obtained from the Crestron website. Refer to the NOTE following these footnotes.
3. Crestron 2-Series control systems include the AV2 and PRO2. Consult the latest Crestron Product Catalog for a complete list of 2-Series control systems.
for details.
(non-condensing)
4.48 in (11.38 cm)
8.89 in (22.58 cm)
2.47 in (6.25 cm) for CLS-C6
2.60 in (6.61 cm) for CLS-C6M
DETAILS
NOTE: Crestron software and any files on the website are for Authorized Crestron dealers and Crestron Authorized Independent Programmers (CAIP) only. New users may be required to register to obtain access to certain areas of the site (including the FTP site)

Physical Description

The following illustration shows the overall dimensions for the CLS-C6RF and CLS-C6MRF.
CLS-C6MRF Overall Dimensions

Important Notes

Read before installation.
Codes: Install in accordance with all local and national electrical codes.
Wiring: Use copper wire only. For supply connections, use wires rated for at least 75°C.
Lighting Load Types: incandescent, magnetic low voltage, neon/cold cathode, dimmable 2-wire fluorescent, and non-dim lighting (also: electronic low voltage, 3-wire and 4-wire fluorescent, and 277V via expansion modules; sold separately).
Temperature: The iLux units are designed for use where temperatures are between 32° to 104°F (0° to 40°C).
Wallboxes: The iLux units mount in standard 4-gang wallboxes; 3.5 inches deep, minimum.
Make certain that power is turned off, and ensure that there is at least 4.5 inches of open space above and below the electrical box location to permit heat dissipation.

Installation

WARNING: Turn off power at the distribution panel circuit breaker. Installing with power on can result in serious personal injury and damage to the device.

Industry Compliance

This product is Listed to applicable UL Standards and requirements by Underwriters Laboratories Inc.
(E103692)
NOTE: This device complies with part 15 of the FCC rules. Operation is subject to the following two conditions: (1) this device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation.
CAUTION: To reduce the risk of overheating and possible damage to other equipment, do not install to control a receptacle or a motor-operated appliance.
NOTE: The CLS-C6RF units require a neutral wire for operation. If no neutral is present, contact a licensed electrician for installation.
The following tools/hardware are required for installation.
A 4-gang electrical box (not supplied), 3.5 inches deep, minimum.
Phillips torque screwdriver (not supplied)
Four 7/8-inch pan head Phillips screws (supplied)
If the planned configuration includes connection to shade controllers, keypads, and/or a Crestron 2-Series control system, the following items are also required. Refer to the latest version of the Crestron CLS-C6RF iLux Integrated Lighting System w/infiNET Operations Guide (Doc. 6418) for detailed configuration options.
Cresnet network cable(s) (not supplied)
Terminal block connector(s) (two supplied)
2 iLux™ Integrated Lighting Systems w/infiNET™: CLS-C6RF & CLS-C6MRF Installation Guide – DOC. 6416A
Loading...
+ 4 hidden pages