iLux
™
Integrated Lighting Systems w/infiNET
™
Introduction
Features and Functions
The iLux™ units, CLS-C6RF and CLS-C6MRF, are wallmounted complete integrated lighting systems that can
function as standalone devices and/or be part of a Crestron®
solution total control system network (Cresnet®). The units
are functionally identical except that the CLS-C6MRF
includes a built-in motion sensor.
CLS-C6MRF with Cover Open, Shown in Almond
Each unit provides automated control of up to six channels
of lighting loads, including incandescent, magnetic lowvoltage, neon/cold cathode, and two-wire dimmable
fluorescent. Each unit also provides automated control of up
to six groups of shade and drape controllers for motorized
window treatments, screens, and lifts.
Front panel operation provides manual control of lighting
loads and shade groups as well as access to up to sixteen
scenes (lighting level/shade position combinations).
A built-in IR receiver allows for wireless operation using an
optional infrared remote generating standard RC5
commands; a built-in motion detector (CLS-C6MRF only)
enables automated control based on room occupancy.
Up to 16 Crestron keypads (sold separately) can be used
with each unit for control of rooms that have several
entrances or work areas. Each unit also supports up to eight
additional CLS-C6RF units, enabling systems of up to 54
lighting channels and 54 shade groups.
The CLS-C6RF employs Crestron's infiNET technology to
enable a wireless link to a 2-Series control system. A single
C2N-MNETGW gateway connected to the control system
enables 2-way wireless communications between the iLux
system and the central control system, allowing iLux's
functions to be controlled from touchpanels, RF wireless
remotes, and even computers.
Each unit is available in three colors: almond, black, or
white. The letter at the end of the product name, ‘A’, ‘B’, or
‘W’, denotes the color (e.g., a CLS-C6MRFA is an almond
unit).
Specifications
Following are specifications for the iLux units.
CLS-C6RF & CLS-C6MRF Specifications
SPECIFICATION
Power Requirements Line Power, 120 VAC, 60Hz
Load Ratings1
Max load per channel
Min load per channel
Max load per unit
Note that if the unit is fed from an arc fault circuit interrupter
(required if controlling loads in a bedroom), the maximum total
load is 1000 W/VA
Load Types1 Incandescent, magnetic low
IR Receiver For use with Crestron IR
RF Wireless
RF Transceiver
Range (typical)
Gateway
Motion Detector
(CLS-C6MRF only)
Type
Range
Default MNET ID 1F
Control System Update Files
2-Series Control System
Firmware CLS-C6.v1.0.upg or later
800 W/VA
(6.6 Amps @ 120 VAC),
Expandable via Expansion
Modules (sold separately)
15 W/VA
(0.125 Amps @ 120 VAC)
1920 W/VA
(16 Amps @ 120 VAC)
voltage, neon/cold cathode,
dimmable 2-wire fluorescent,
and non-dim lighting
(also: electronic low voltage,
3-wire and 4-wire fluorescent,
High-Inrush Switching,
277V via expansion modules;
sold separately)
remote (sold separately).
2-way RF, 2.4 GHz ISM
Channels 11-26 (2400 to
2483.6 MHz), IEEE 802.15.4
compliant
150 feet indoor, 250 feet
outdoor; subject to site-specific
conditions; range is increased
by adding additional devices or
C2N-MNETRPT repeater;
Requires a C2N-MNETGW RF
gateway
Infrared
20 to 30 feet at 4-foot elevation
2, 3
Version 2.004.CUZ or later
(Continued on following page)
DETAILS
and
Crestron Electronics, Inc. Installation Guide – DOC. 6416A
15 Volvo Drive Rockleigh, NJ 07647 (2013966)
Tel: 888.CRESTRON 06.08
Fax: 201.767.7576 Specifications subject to
www.crestron.com change without notice.
iLux™ Integrated Lighting Systems w/infiNET
™
CLS-C6RF & CLS-C6MRF Specifications (Continued)
SPECIFICATION
Environmental Temperature 32° to 104°F (0° to 40°C)
Humidity 10% to 90% RH
Overall Dimensions:
Height
Width
Depth
Weight 22.8 oz (646.37 g)
1. Additional load types can be controlled and load ratings can be increased via
optional CLS-EXP expansion modules. Refer to the Crestron website
http://www.crestron.com/
2. The latest software versions can be obtained from the Crestron website. Refer to
the NOTE following these footnotes.
3. Crestron 2-Series control systems include the AV2 and PRO2. Consult the latest
Crestron Product Catalog for a complete list of 2-Series control systems.
for details.
(non-condensing)
4.48 in (11.38 cm)
8.89 in (22.58 cm)
2.47 in (6.25 cm) for CLS-C6
2.60 in (6.61 cm) for CLS-C6M
DETAILS
NOTE: Crestron software and any files on the website are
for Authorized Crestron dealers and Crestron Authorized
Independent Programmers (CAIP) only. New users may be
required to register to obtain access to certain areas of the
site (including the FTP site)
Physical Description
The following illustration shows the overall dimensions for
the CLS-C6RF and CLS-C6MRF.
CLS-C6MRF Overall Dimensions
Important Notes
Read before installation.
• Codes: Install in accordance with all local and
national electrical codes.
• Wiring: Use copper wire only. For supply
connections, use wires rated for at least 75°C.
• Lighting Load Types: incandescent, magnetic
low voltage, neon/cold cathode, dimmable
2-wire fluorescent, and non-dim lighting
(also: electronic low voltage, 3-wire and 4-wire
fluorescent, and 277V via expansion modules; sold
separately).
• Temperature: The iLux units are designed for use
where temperatures are between 32° to 104°F
(0° to 40°C).
• Wallboxes: The iLux units mount in standard
4-gang wallboxes; 3.5 inches deep, minimum.
• Make certain that power is turned off, and
ensure that there is at least 4.5 inches of open
space above and below the electrical box location
to permit heat dissipation.
Installation
WARNING: Turn off power at the distribution panel
circuit breaker. Installing with power on can result in
serious personal injury and damage to the device.
Industry Compliance
This product is Listed to applicable UL Standards and
requirements by Underwriters Laboratories Inc.
(E103692)
NOTE: This device complies with part 15 of the FCC
rules. Operation is subject to the following two conditions:
(1) this device may not cause harmful interference, and (2)
this device must accept any interference received, including
interference that may cause undesired operation.
CAUTION: To reduce the risk of overheating and possible
damage to other equipment, do not install to control a
receptacle or a motor-operated appliance.
NOTE: The CLS-C6RF units require a neutral wire for
operation. If no neutral is present, contact a licensed
electrician for installation.
The following tools/hardware are required for installation.
• A 4-gang electrical box (not supplied), 3.5 inches
deep, minimum.
• Phillips torque screwdriver (not supplied)
• Four 7/8-inch pan head Phillips screws (supplied)
If the planned configuration includes connection to shade
controllers, keypads, and/or a Crestron 2-Series control
system, the following items are also required. Refer to the
latest version of the Crestron CLS-C6RF iLux Integrated
Lighting System w/infiNET Operations Guide (Doc. 6418)
for detailed configuration options.
• Cresnet network cable(s) (not supplied)
• Terminal block connector(s) (two supplied)
2 • iLux™ Integrated Lighting Systems w/infiNET™: CLS-C6RF & CLS-C6MRF Installation Guide – DOC. 6416A