Specifications for the CHV-TSTATEX are listed in the following table.
CHV-TSTATEX Specifications
SPECIFICATION DETAILS
Wireless
RF Transceiver
Range (typical)
Gateway
Display
Measurement Range Ambient Temperature -10º to 110º F (-23º to 43º C)
Display Limits -9º to 99º F (-9º to 43º C)
Temperature Tolerance Over Full Range ±1º F (±0.5º C)
At Room Temperatures ±1º F (+0.4/-0.2º C)
Setpoint Range Heat only setpoint 38º to 89º F (3º to 32º C)
Cool only setpoint
Relay Rating 1 Amp @ 40 Volts DC or 24 Volts AC (nominal)
Environmental
Temperature -10º to 110º F (-23º to 43º C)
Humidity 10% to 90% RH (non-condensing)
Power Requirements
24V
Battery
2-way RF, 2.4 GHz ISM Channels 11-26 (2400
to 2483.6 MHz), IEEE 802.15.4 compliant
150 ft (46 m) indoor, 250 ft (76 m) outdoor;
Subject to site-specific conditions; range is
increased by adding additional devices or
CLW-RFEXP-EX wireless expander (sold
separately)
Requires a CEN-RFGW-EX RF gateway or
MC3 3-Series Control System™ (both sold
separately)
Backlit LCD with two large seven-segment
digits, two small seven-segment digits, 14
dedicated symbols;
Displays ambient temperature, set point,
system mode, fan setting, call activity, low
battery, RF or control system communication
errors, firmware download progress, setup
parameter/function and value
59º to 99º F (15º to 37º C) or
38º to 99º F (3º to 37º C) extended cool mode
enabled
0.24 Watts (10 mA @ 24 Volts AC) supplied by
heating or cooling system
Two AA batteries, estimated one year normal
operation
Dimensions
Height 4.50 in (115 mm)
Width 5.53 in (141 mm)
Depth 1.03 in (26 mm)
Weight 6.7 oz (190 g)
Available Models
CHV-TSTATEX-A-T infiNET EX Thermostat, Matte Almond
CHV-TSTATEX-B-T infiNET EX Thermostat, Matte Black
CHV-TSTATEX-W-T infiNET EX Thermostat, Matte White
Available Accessories
CEN-RFGW-EX infiNET EX Wireless Gateway
Version 4.001.1012 or later
Version 1.000.018 or later
Injection molded plastic, surface-mountable to
the front of a horizontally oriented single-gang
electrical box.
C2N-RTHS Temperature and Humidity Sensor, Cresnet
CHV-RSS Remote Slab Sensor
CHV-RTHS
3
Remote Temperature and Humidity Sensor
CHV-RTS Remote Temperature Sensor
MC3 3-Series Control System
1. The latest software versions can be obtained from the Crestron Web site. Refer to the NOTE
following these footnotes.
2. Crestron 2-Series control systems include the AV2 and PRO2. Consult the latest Crestron Product
Catalog for a complete list of 2-Series control systems.
3. The humidity function will not be reported to the CHV-TSTATEX.
NOTE: Crestron software and any files on the website are for authorized Crestron
dealers and Crestron Authorized Independent Programmers (CAIP) only. New users
may be required to register to obtain access to certain areas of the site (including the
Cycles through available system modes:
OFF, HEAT, AUX HEAT ONLY (for
heatpump or dual-fuel systems only), AUTO
and COOL.
Toggles fan setting between FAN AUTO and
FAN ON.
Raises the setpoint.
Crestron CHV-TSTATEX infiNET EX™ Thermostat
Connectors, Controls & Indicators (Continued)
# CONNECTORS,
DESCRIPTION
CONTROLS &
INDICATORS
4
5 LCD DISPLAY
6 HVAC (4) Two-position terminal blocks
7 HVAC (4) Two-position terminal blocks.
Lowers the setpoint.
Displays ambient temperature, set point,
system mode, fan setting, call activity, low
battery, RF or control system communication
errors, firmware download progress, setup
parameter/function and value.
Every CHV-TSTATEX communicating via RF with a Crestron control system
through a CEN-RFGW-EX wireless gateway requires a unique RF ID. The RF ID is
a two-digit hexadecimal number that can range from 03 to FF. The RF ID of the unit,
set using Crestron Toolbox™, must match the RF ID specified in the SIMPL
Windows program.
Supplied Hardware
The hardware supplied with the CHV-TSTATEX is listed in the following table.
Supplied Hardware for the CHV-TSTATEX
DESCRIPTION PART
NUMBER
Screws, Zinc, Phillips, Pan Head, #06-32 x 1” 2007251 2
Batteries, AA, Alkaline 2001050 2
QUANTITY
Installation
NOTE: Installers should have a strong working knowledge of HVAC systems.
The location of the thermostat can affect its performance and efficiency. Install the
thermostat away from direct sunlight, drafts, doorways, skylights and windows. Also
make sure the thermostat is conveniently located for control access and setup.
Thermostats should be mounted 60 inches (1.6 meters) above the finished floor
(HVAC industry standard). Do not mount on an exterior wall.
The following tools/hardware are required for installation.
• Standard single-gang electrical box, mounted horizontally (not supplied)
• Phillips screwdriver (not supplied)
• Two 1-inch pan head Phillips screws (supplied)
• Two AA batteries (supplied)
Use the following procedure to install the CHV-TSTATEX in a standard,
single-gang electrical box (refer to illustration on the following page):
1. Separate thermostat front plate from back plate (you may need to exert force
when removing the front plate).
2. Turn HVAC system power OFF.
3. Feed HVAC wiring from the electrical box through the hole in the center of
the back plate so it can be connected to the proper terminals on the
CHV-TSTATEX after the thermostat is mounted.
4. Make sure unit is correctly oriented and place it in the electrical box.
CAUTION: Excess wire pinched between the CHV-TSTATEX and electrical box
could cause a short circuit. Make sure that all excess wire is completely inside the
electrical box and not between the box and the CHV-TSTATEX.
NOTE: To ensure accurate temperature readings, avoid drafts in the back of the unit
by plugging the wire hole with insulation.
5. Attach the CHV-TSTATEX back plate to the electrical box using the two
supplied #06-32 x 1” pan head screws.
6. Attach the face plate.
7. Insert batteries and attach the battery compartment cover.
8. Turn HVAC system power ON.
CAUTION: Replace all batteries in the device at the same time Mixing old and new
batteries in the device may result in battery leakage and equipment damage.
NOTE: Crestron has provided small slots on either side of the battery cover,
designed to allow a flathead screwdriver to be inserted to assist in removal.
1. Install two AA batteries (supplied) in the battery compartment.
2. Locate the DIP switches inside the unit and configure th e following
parameters:
DIP Switch Settings
Left Switch
# DESCRIPTION ON OFF
4 System Type Heat/Cool Heat Pump
3 Heat Pump Mode Aux Heat Dual Fuel
2 Cool/HP Stages 1 2
1 Heat Stages 1 2
Right Switch
# DESCRIPTION ON OFF
4 Fan In Heat Disabled Enabled
3 Change Over Outputs Disabled Enabled
2 Cool SP Range Normal Extended
1 N/A N/A N/A
By default, the CHV-TSTATEX is configured to be powered by two AA alkaline
batteries. To extend battery life, the device also receives power from the HVAC
system by drawing a small amount of current through the heat or cool terminals. This
is known as Steal Power mode.
To enable this feature, locate the POWER slide switch inside the unit and slide it to
STEAL (This is the default factory setting on the CHV-TSTATEX).
POWER Slide Switch
NOTE: Steal Power mode will not draw enough current to cause the external heat
or cool relays to close. More specifically, when the unit is not making a call for heat,
it will draw power through the RH and W terminals. When the unit is making a call
for heat, it will draw power through the RC and Y terminals. (This will not work if
the thermostat has been wired for a cool only application.). The CHV-TSTATEX
must be wired for heat control in order to take advantage of Steal Power mode.
NOTE: In Steal Power mode, even when an auxiliary power source is available, the
unit will continue to enter a communications sleep state, waking every 30 seconds or
one minute (based on the infiNET EX Sleep Time setting) to exchange data with the
control system. Refer to “Remote Operation” on page 26 for details.
NOTE:Steal Power mode may cause problems with some types of HVAC systems,
such as indicating a false heat or cool call. If this occurs, do not use Steal Power
mode.
If the thermostat will be wired so that 24 Volts AC will always be present on the 24C
terminal, slide the POWER DIP switch to 24VAC. No batteries will be required in
this mode (except during initial setup),
NOTE: When the unit detects 24 VAC is present, it will no longer “sleep”, meaning
it will offer real-time communication with the control system.
NOTE: When the unit is powered from a constant 24 VAC supply, there may be a
slight discrepancy between the ambient temperature displayed on the thermostat and
the actual room temperature. This discrepancy will also be seen when switching from
STEAL to 24VAC. This is normal and the discrepancy will disappear within
approximately 10 minutes.
Wiring the CHV-TSTATEX to the HVAC System
Make the necessary connections as called out in the illustrations that follow. A flat
head screwdriver (not supplied) is required to attach the control wires from the
HVAC system. Apply power after all connections have been made.
The illustrations on the following pages show examples for connection to various
types of HVAC systems. If your system does not match any of the systems described
below, contact Crestron Technical Support for assistance.
The following describes the most common setup requirements. For full details on all
setup options, refer to “Advanced Setup” which starts on page 19.
Place the CHV-TSTATEX in the Setup mode by doing the following:
1. Press and hold the FAN button.
2. While the FAN button is being held, press and hold the
simultaneously.
3. Hold all three buttons for five seconds, after which the unit will enter Setup
mode. The display shows the Temperature Scale function (FC).
Use or to choose the temperature units: F (Fahrenheit), C1 (setpoint in whole
degrees Celsius) or C2 (setpoint in half degrees Celsius).
and buttons
Joining an infiNET EX Network
Before a CHV-TSTATEX can be used on an infiNET EX network, it must first join
an infiNET EX network by being acquired by an infiNET EX gateway (e.g.,
CEN-RFGW-EX).
NOTE: A CHV-TSTATEX can be acquired by only one gateway.
To acquire a CHV-TSTATEX, perform the following:
1. Put the CEN-RFGW-EX into Acquire mode, from the unit itself or from
Crestron Toolbox, as described in the latest revision of the CEN-RFGW-EX
Operations & Installation Guide (Doc. 6706), which is available from the
Crestron Web site (
www.crestron.com/manuals).
NOTE: In an environment where multiple gateways are installed, only one gateway
should be in the Acquire mode at a time.
2. Ensure the unit is in Setup mode (refer to “Basic Thermostat Setup” above or
“Setup Mode” which starts on page 19) and that Acquire mode (AC) is selected.
4. Press MODE until the “Start infiNET EX Acquire” function is displayed (AC).
5. Press
shows flashing “—” (in progress). When finished, the display shows “00”
(finished, found gateway) or “E#” (finished, could not find gateway), where #
represents an error code.
6. Once all devices have been acquired, take the CEN-RFGW-EX out of Acquire
mode. Press FAN on the thermostat to exit Setup mode.
until the “infiNET EX ID (RF ID)” function is displayed (id).
and to choose the infiNET EX ID.
or on the CHV-TSTATEX to start the acquire process: The display
infiNET EX™ Thermostat Crestron CHV-TSTATEX
NOTE: The acquire process can take up to 15 seconds. The acquire process cannot
be aborted.
NOTE: “E1” indicates that search time has expired and no gateway was found.
“E1” indicates the RF channel is set to “0” (disabled). To enable the RF channel,
refer to “Start infiNET EX Acquire” in “Setup Mode Parameters/Functions” which
starts on page 20.
Leaving an infiNET EX Network
To leave a network, press and hold the FAN, and buttons simultaneously for
five seconds. Press MODE until the unacquire function is displayed (UA). Press
on the CHV-TSTATEX to start the unacquire process. Once completed, press
or
FAN on the thermostat to exit Setup mode.
Verifying Communication Status
To verify communication status, enter the Setup mode as described in “Basic
Thermostat Setup” on page 17. Press MODE until the “CC” function is displayed.
Press or on the CHV-TSTATEX to verify the communication status.
Confirm desired power
connection and S2
position setting.
None, consider
replacement of unit.
Replace unit when
feasible.
Perform general RF
debugging to improve
communications.
Run acquire operations if
communication is needed.
Run acquire operations if
communication is needed.
Perform general RF
debugging to improve
communications
Set when the capacity is below approximately 10%
and the device needs battery power (i.e. not using
24VAC mode).
Set when constant 24VAC is detected but the
internal bus voltage does not meet run threshold.
This can happen when 24VAC is available but S2
is set to power-steal. This is not an error but warns
that better performance may be achieved by
changing S2 position.
Set when timing parameters for display operation
cannot be met. Device may be usable but proper
display operation cannot be guaranteed.
Set when internal NV memory usage has
exceeded its rated life. Device will continue to
operate but data retention may be in question.
Link quality to gateway is poor and may indicate
communications problems that can impact timely
data exchange or battery life.
Device cannot address a gateway. This may
simply mean the device has not been acquired
yet.
Device is not joined to a ZigBee network. This may
simply mean the device has not been acquired
yet.
Network link to gateway is not desirable.
Communication may work ok but is subject to
many hops that will impact communication speed
and battery life.
After the CHV-TSTATEX is installed, it is necessary to set it up for a particular
heating/cooling system. Please note that some of the setup parameters listed below
will not always be available. Refer to “Setup Mode Parameters/Functions”, which
starts on page 20 for details.
Place the CHV-TSTATEX in the Setup mode by doing the following:
1. Press and hold the FAN button.
2. While the FAN button is being held, press and hold the
simultaneously.
3. Hold all three buttons for five seconds, after which the unit will enter Setup
mode.
Once in Setup mode, the display will indicate the currently selected setup
parameter/function. Press and release the MODE button quickly (must be released
within one second) to change to the next parameter/function in the list.
NOTE: Holding the MODE button for more than one second will reset the
currently selected parameter/function to its default value.
When setting parameters (such as when choosing between Fahrenheit or Celsius
display), pressing the
change occurs when button is released.
When a function is selected (such as when starting an infiNET EX acquire), pressing
either
or will execute the function.
To exit from Setup mode, press the FAN button on the CHV-TSTATEX.
CHV-TSTATEX LCD Display (Setup Mode)
Indicates Current Setup
Parameter/Function
Skips to Next Setup
Parameter/Function
and buttons
or button will increment or decrement the value. Value
Indicates Current Value for
selected Setup Parameter
MODE
Adjust Current Setup
Exits Setup Mode
FAN
Parameter/Function Value
NOTE: When the CHV-TSTATEX is in Setup mode the large seven-segment
displays will show the current setup parameter/function. The small seven-segment
displays will show the current value for the selected setup parameter, if applicable, or
it will display “—” when a function is selected. All other display elements will be
hidden (refer to “LCD Display” which starts on page 26).
NOTE: While in Setup mode, a period of one minute with no button activity will
cause the CHV-TSTATEX to revert to standard operation, unless a function (such as
an infiNET EX acquire) is executing.
Setup Mode Parameters/Functions
The following table shows the available setup parameters/functions.
Setup Mode Parameters/Functions
PARAMETER/
FUNCTION
Temperature Scale FC F, C1 or C2 F
Backlight Timeout bL
Auto mode AU
Auto Dead Band
(will only appear when
Auto mode is enabled)
Temperature Offset to
Heat Anticipator HA 1 – 6 3
Cool Anticipator CA 1 – 6 3
Heat pump Balance
Point
(will only appear for
Heat pump and DualFuel Heat pump
systems)
CODE VALID VALUES
1 – 4 seconds or
disabled (--)
Disabled (--),
Dual setpoint (d) or
Single setpoint (S)
db
Hb
2 – 4 (for Fahrenheit)
or 1 – 3 (for Celsius)
-9 to +9 (for
Fahrenheit) or
-5 to +5 (for Celsius)
16 to 90 (for
Fahrenheit) or
-9 to 32 (for Celsius)
or Disabled (--)
DEFAULT
4 seconds
--
2
0
--
VALUE
NOTES
Sets units to use for temperature
display (Fahrenheit or Celsius).
When using Celsius temperature
scale, C2 allows the setpoint to be
adjusted in 0.5ºC steps.
Sets the number of seconds the
backlight will remain lit after a
button press.
Used to enable Auto mode with
single or dual setpoint operation.
Used to set minimum separation
between heat and cool setpoints
(with dual setpoints) or maximum
drift before system latches alternate
mode (with single setpoint).
Permits recalibration of room
temperature sensor. This is the
number of degrees added to or
subtracted from the actual
temperature. This adjustment
changes the actual regulation
temperature, not just the display.
Lower setting results in more
frequent cycles and faster response
(tighter regulation). Higher setting
results in less frequent cycles and
slower response (looser regulation).
The default value should suffice in
nearly all installations.
Lower setting results in more
frequent cycles and faster response
(tighter regulation). Higher setting
results in less frequent cycles and
slower response (looser regulation).
The default value should suffice in
nearly all installations.
Heat pump systems have
performance restrictions based on
outdoor temperature. This setting is
the minimum outdoor temperature
at which the heat pump (or dual-fuel
heat pump) system will run.
Aux-Heat Balance
Point
(will only appear for
Heat pump type
systems)
Interstage Differential
(will only appear for
Heat pump systems)
Heat pump/AUX or any
2-stage system
configuration
(will only appear for
Heat pump type
systems)
Remote sensors Sn i, r, ir i
Check Firmware
Version
InfiNET-EX ID
(RF ID)
infiNET EX Sleep Time SL Short (S) or Long (L) L
Start infiNET EX
Acquire
CODE VALID VALUES
Ab
dF
AS 1 – 6 6
rE
id 01 and 03 – FE 01
AC
16 to 90 (for
Fahrenheit) or
-9 to 32 (for Celsius)
or Disabled (--)
05 to 80 (tenths of a
degree Fahrenheit),
adjustable in 5 tenths
degree increments or
05 to 45 (tenths of a
degree Celsius),
adjustable in 5 tenths
degree increments
Firmware version is
displayed in xx.yy.zz
format. “—“ can also
be displayed
Not started (--)
In progress
(flashing --)
Finished, found GW
(00)
Finished, could not
find GW (E#, where
# represents an error
code)
DEFAULT
VALUE
--
20 (F) or
10 (C)
--
N/A
NOTES
Aux heat operation is locked out
when outdoor temperature exceeds
the Aux Heat Balance Point. Dualfuel systems do not allow both the
heat pump and the aux to run at the
same time.
Heat pump systems can allow both
the heat pump and aux to run at the
same time. This sets the ambient
temperature threshold to trigger aux
heat in addition to the heat pump.
Accumulated staging threshold
index sets how aggressively staging
is performed in response to
extended system calls. Index 6
effectively disables accumulated
staging effects.
i – internal sensor only
(When no remote sensor is
detected, only this option is
available)
r – remote sensor only
(Only available when a remote
sensor has been detected)
ir – average internal and remote
sensors
When firmware version is not yet
shown, display will be “—“. Each
press of the
cycle to the next portion of the
version number.
Sets the infiNET EX ID. SIMPL
Windows restricts infiNET EX
devices to an ID range of 03 – 20.
Indicates thermostat update rate.
Setting for fewer updates (“L”) will
conserve battery power.
Used to acquire the device to a
gateway.
”E0” indicates that search time has
expired and no gateway was found.
”E1” indicates the infiNET EX RF
Channel is set to “0” (disabled).
Perform Aux Heat Call
Test (Toggle)
(will appear only on
Heat pump and DualFuel Heat pump
systems)
Perform Fan Call Test
(Toggle)
Perform Self Test St
CODE VALID VALUES
CC
Fd
H
C
A
F
Not started (--)
In progress
(flashing --)
Finished, success
(00)
Finished, failed (E#,
where # represents
an error code)
Error (E# - where #
is a number from 0 to
7)
No problems (00)
Not started (--)
Estimated remaining
battery life (0 – 99)
Not started (--)
In progress (blank or
flashing --)
Finished (00)
Button not held long
enough (Er)
Not started/Heat call
off (--)
Heat call on (on)
(also, “H” icon will
turn on)
Not started/Cool call
off (--)
Cool call on (on)
(also, “C” icon will
turn on)
Not started/Aux call
off (--)
Aux call on (on)
(also, “A” icon will
turn on)
Not started/Fan call
off (--)
Fan call on (on)
(also, “F” icon will
turn on)
Not started (--)
In progress
(flashing --)
Finished, self test ok
(00)
Finished, self test
failed (E#, where #
represents an error
code)
DEFAULT
VALUE
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
NOTES
Used to remove gateway
information from the device, so it
will no longer communicate with the
current gateway.
”E1” indicates that there is no
previous gateway information (i.e.
the gateway may already have
been unacquired).
Displays error codes for any
problems found, or 00 for no
problems.
Gives estimated remaining battery
life in percent.
Restores all setup parameters to
their default settings. To prevent
accidentally performing this action,
you must press and hold either the
or button for three seconds
for this function to execute.
Will test the heat call output.
Bypasses short-cycle timers. Useful
for technician system testing. Note
that calling the heat may activate
other relays in the thermostat as
required, such as the fan output for
heat pump or dual-fuel types.
Will test the cool call output.
Bypasses short-cycle timers. Useful
for technician system testing. Note
that calling the cooling may activate
other relays in the thermostat as
required, such as the fan output.
Same as above, for testing aux
heat output.
Same as above, for fan. Note that
only the fan relay can be activated
for a fan call test.
For assistance, please contact the
Crestron customer service team by
calling Crestron at
1-888-CRESTRON
(1-888-273-7876).
The MODE button on the CHV-TSTATEX will cycle the unit through all available
system modes in the following order: Off, Heat, Emergency Heat (for heat pump and
dual-fuel systems), Cool and Auto (if enabled in Setup).
The system mode will change upon release of the MODE button and the selected
mode will become operational five seconds after the mode has been entered.
Off Mode
In Off mode, all HVAC systems are disabled.
Heat Mode
In Heat mode, the thermostat uses the heating system to maintain the setpoint
temperature.
AUX Heat Mode
In Aux Heat mode, the thermostat uses only the auxiliary heat output on heat pump
or dual-fuel systems to maintain the setpoint temperature.
NOTE:Aux Heat mode can only be accessed when heat/cool type has been set to
“Heat pump” or “Dual-Fuel Heat pump”. This setting can be useful when the heat
pump is being serviced or when there is an unexpected problem with it. The display
will flash the “flame” icon when the system is in Aux Heat mode.
Cool Mode
In Cool mode, the thermostat uses the cooling system to maintain the setpoint
temperature.
Auto Mode
In Auto mode, the thermostat allows the system to switch between Heat and Cool
automatically as needed to maintain the setpoint temperature. By default, the
CHV-TSTATEX has been configured with Auto mode disabled, meaning it is not
available from the thermostat itself or via another interface such as a touch screen.
In order to enable Auto mode, you must enter Setup mode and change the “AU”
setting from “--” to either “d” (dual setpoint) or “S” (single setpoint). Refer to “Setup
Mode” which starts on page 19 for details.
Once Auto mode has been enabled, you can access it from the CHV-TSTATEX
controls as follows:
1. Press the MODE button until both the flame
appear in the display. This indicates Auto mode is now active.
2. Use the
depend on whether you are using single or dual setpoints.
a. In dual setpoint Auto mode, the first press of the
and buttons to adjust the setpoint. Actual operation will
second press if the first press simply turned on the backlight) will cause
either the flame
or snowflake icon to flash rapidly. This
and snowflake icons
or buttons (or
infiNET EX™ Thermostat Crestron CHV-TSTATEX
indicates which setpoint will be adjusted by subsequent presses of the
or buttons. To adjust or view the alternate setpoint, press the
MODE button while the icon is flashing. This will cause the alternate
icon to flash and now the
The flashing icon will time out after five seconds of no button activity.
b. In single setpoint Auto mode, use the buttons to adjust the setpoint as
usual.
Dual Setpoint Auto Mode (“AU” = “d” in Setup Mode)
In dual setpoint Auto mode, separate heat and cool setpoints are used. When the
ambient temperature drops below the heat setpoint, the unit will call for heat to
maintain the heat setpoint. When the ambient temperature rises above the heat
setpoint, the unit will not call for cooling until the temperature exceeds the cool
setpoint. When the ambient temperature drops below the cool setpoint, the unit will
not call for heating until the temperature is below the heat setpoint.
When dual setpoint Auto mode has been enabled, the Auto Dead Band is used to
maintain a minimum separation between the heat and cool setpoints. If this
separation is violated by a setpoint adjustment, the other setpoint will be
automatically adjusted.
and buttons will adjust that setpoint.
For example, if the heat setpoint is at 68 degrees, the cool setpoint is at 72 degrees
and the Auto Dead Band is set to 4 degrees, if you lower the cool setpoint to 71
degrees, the heat setpoint will automatically be adjusted to 67 degrees to maintain
the 4 degree Auto Dead Band separation.
In dual setpoint Auto mode, the CHV-TSTATEX display will indicate whichever
setpoint is closer to the ambient temperature. Both the heat and cool setpoints can be
viewed simultaneously using a touch screen.
Single Setpoint Auto Mode (“AU” = “S” in Setup Mode)
In single setpoint Auto mode, a single setpoint is used for regulation at all times,
regardless of whether the system is heating or cooling. The Auto Dead Band (“db”)
setup parameter is used to determine when to switch between heating and cooling.
For example, if the setpoint is at 70 degrees and the Auto Dead Band is set to 2
degrees, if the system is cooling, it will not start heating until the ambient
temperature drops below 68 degrees (setpoint – Auto Dead Band). Once the unit has
switched to heating, it will not resume cooling until the ambient temperature rises
above 72 degrees (setpoint + Auto Dead Band).
A larger value for the Auto Dead Band setting will result in less cycling between
heating and cooling but can result in large temperature swings during the course of
the day. Smaller values for the Auto Dead Band setting will result in tighter
temperature regulation but more frequent cycling between heating and cooling.
NOTE: When using a single setpoint, the CHV-TSTATEX has a 20-minute change
limiter to prevent system toggling.
Fan
The FAN button toggles the fan setting between fan AUTO and fan ON. When set to
AUTO, a fan call will be made whenever the system makes a cool call or when the
system makes a heat call or auxiliary heat call (if the DIP switch is set to “Enabled”).
When set to ON the fan will always run.
The setpoint is the user selectable temperature you want the system to maintain.
The
and buttons will change the current setpoint by one degree F or C (if
Temperature Scale is set to “F” or “C1”) or by one half degree C (if Temperature
Scale is set to “C2”).
NOTE: While the setpoint is being adjusted, if it is set to a half-degree increment,
the integer portion of the number will be displayed and will alternate with “_5” every
quarter second for a period of four seconds after the last adjustment. After four
seconds, only the integer portion of the number will be displayed.
If the or button is held down for two seconds, the unit will enter an auto-repeat
state and the setpoint will adjust rapidly until the button is released or until the upper
(or lower) limit is reached.
Some users will want to have setpoints change automatically based on the day of the
week and the time of day. For example, in the winter they may want to lower the
heat setpoint while they sleep to lower heating costs. To accommodate this, the
CHV-TSTATEX provides a “Scheduled Heat Setpoint” and a “Scheduled Cool
Setpoint” which can be specified by the control system program. This is handled
automatically by the “Crestron CHV-TSTATEX w/5-2 Scheduler” module provided
with the Crestron Database. Refer to the SIMPL Windows help file for details.
For dual setpoint operation, refer to “Auto Mode” which starts on page 23.
Hold
Hold allows the user to adjust the setpoint and will maintain that setpoint until the
unit is taken out of Hold. This means that any change to the scheduled heat or cool
setpoint that occurs while in Hold will be ignored until the unit is taken out of Hold.
Pressing the MODE and FAN buttons simultaneously will cause the unit to enter
Hold if Hold is not yet active and the system mode is Heat, Emergency Heat or Cool.
Pressing the MODE and FAN buttons simultaneously when Hold is active will
cause the unit to exit from Hold and recall either the scheduled heat setpoint or
scheduled cool setpoint as appropriate to the system mode.
If the system is in single setpoint Auto mode, exiting from Hold will recall the
scheduled auto setpoint. If the system is in dual setpoint Auto mode, upon exiting
from Hold, the auto cool setpoint becomes the scheduled cool setpoint and the auto
heat setpoint becomes the scheduled heat setpoint.
Pressing the MODE and FAN buttons simultaneously when the system mode is Off
will have no effect.
When Hold is active, the unit will continue to adjust the current setpoint when the
or
buttons are pressed. The unit will also continue to adjust the current setpoint
when the setp oint signal from the control system changes.
When the system mode changes to Heat or Emergency Heat, the current setpoint will
be set to the scheduled heat setpoint.
When the system mode changes to Cool, the current setpoint will be set to the
As an infiNET EX device, the CHV-TSTATEX can be controlled remotely via a
Crestron control system. Most often, control of the thermostat will be achieved via a
touch screen or Web-based graphical interfa ce. In order to extend battery life, the
thermostat will only communicate with the control system once every 30 seconds or
one minute, based on the infiNET EX Sleep Time setting. Because of this, there will
be a noticeable delay between the time a button is pressed on a touch screen and
when the thermostat reacts to the command. To account for this, the
CHV-TSTATEX modules written by Crestron and provided in the Crestron Database
will mimic the feedback from the thermostat so that the user will see an immediate
response on the touch screen.
Likewise, pressing a local button on the thermostat (for example, setpoint raise or
lower) will not cause an immediate change to the corresponding display on a touch
screen. Instead, the thermostat will wake up shortly after the last button press to send
its updated status to the control system.
If the thermostat is wired to have the optional 24 VAC at the 24C terminal and the
power switch is set for 24V, there will not be a delay in feedback.
Indicates current ambient temperature
Setup mode, indicates current setup
parameter/function.
Display range is limited to –9º to 99ºF (-9º to
43ºC). If the ambient temperature is above
99º, the display will indicate 99º. If the
ambient temperature is below –9º, the
display will indicate –9º.
2
Small seven-segment
digits
Indicates current setpoint (in F or C) in whole
degrees.
While the setpoint is being adjusted, if it is
set to a half-degree increment, the integer
portion of the number will be displayed and
will alternate with “_5” every quarter second
for a period of four seconds after the last
adjustment. After four seconds, only the
integer portion of the number will be
displayed.
In Setup mode, indicates current value for
selected setup parameter.
3 Flame icon
Displayed when the system mode is Heat.
Flashes (on two seconds, off one half
second) when the system mode is Aux Heat
(Emergency Heat).
Displayed with snowflake icon when system
is in Auto mode.
4 Snowflake icon
Displayed when the system mode is Cool.
Displayed with flame icon when system is in
Auto mode.
5 Fan icon Displayed at all times.
6 AUTO indicator
Displayed when FAN setting is AUTO.
If this is not displayed, FAN is always ON.
7 OFF indicator Displayed when the system mode is Off.
8 HOLD indicator Displayed when the HOLD setting is active.
9 H, C, F & A indicators
H – Displayed whenever a Heat Call is being
made.
C – Displayed whenever a Cool Call is being
made.
F – Displayed whenever a Fan Call is being
made.
A – Displayed whenever an Aux Heat Call is
being made.
1. For heat pump and dual-fuel systems, when you select Emergency Heat mode (by pressing and
releasing the MODE button when system mode is Heat) the display will show “EH” in place of the
ambient temperature for two seconds.
2. When the CHV-TSTATEX detects a low battery condition (approximately one month of battery life
remaining), the display will alternate “Lo” in place of the ambient temperature once per second.
Have a question or comment about Crestron software?
Answers to frequently asked questions (FAQs) can be viewed in the Online Help
section of the Crestron Web site. To post a question or view quest ions you have
submitted to Crestron’s True Blue Support, log in at
First-time users will need to establish a user account.
Earliest Version Software Requirements for the PC
NOTE: Crestron recommends that you use the latest software to take advantage of
the most recently released features. The latest software is available from the Crestron
Web site (
Crestron provides an assortment of Windows® based software tools to develop a
customized system. Use SystemBuilder, D3 Pro or SIMPL Windows to create a
program to control the CHV-TSTATEX. Customers whose focus is on lighting
systems may prefer to use the D3 Pro software since it is designed especially for
creating lighting and environmental system control applications. Customers already
familiar with SIMPL Windows who are including a lighting system as part of an
overall control system project may prefer to continue using SIMPL Windows.
www.crestron.com/software).
www.crestron.com/support.
Programming with Crestron SystemBuilder
SystemBuilder is a comprehensive programming environment. Appropriate for most
systems, it can quickly and easily generate a complete working program including
both control processor logic and touch screen graphics.
Programming with D3 Pro
Crestron’s D3 Pro lighting software provides all the tools necessary to create a
complete Crestron lighting system for residential applications. The lighting system
includes the control system logic program, touch screen projects and keypad
programming, documentation and real-time lighting adjustment capabilities.
As with all Crestron software, D3 Pro provides extensive right-click an d drag-anddrop functionality in addition to convenient keyboard shortcuts for frequently used
functions and commands.
Programming is organized into six system Views of the lighting system, each
providing a moveable toolbox of devices such as interfaces, fixtures and control
modules. You can add a device to your system simply by selecting it from one of the
toolboxes and dragging it to a room. The available toolboxes differ depending on the
View but all Views include a "General" toolbox that allows you to add areas and
rooms at any time.
NOTE: While SIMPL Windows can be used to program the CHV-TSTATEX, it is
recommended to use SystemBuilder for configuring a system.
SIMPL Windows is Crestron’s premier software for programming Crestron control
systems. It is organized into two separate but equally important “Managers”:
Configuration and Program.
Configuration Manager
Configuration Manager is the view where programmers “build” a Crestron control
system by selecting hardware from the Device Library.
1. To incorporate the CHV-TSTATEX into the system:
a. Drag the CEN-RFGW-EX (gateway) from the Wireless Receivers |
Wireless Receivers (RF) folder of the Device Library and drop it in the
System Views.
Locating the CEN-RFGW-EX in the Device Library
b. Drag the CHV-TSTATEX from the Wireless Remotes | Wireless
Remotes (RF) folder of the Device Library and drop it on the
CEN-RFGW-EX.
Locating the CHV-TSTATEX in the Device Library
NOTE: If connecting to the MC3, drag the CHV-TSTATEX directly to the
control system.
The system tree of the control system displays the CHV-TSTATEX in the
appropriate slot(s) with a default RF ID as shown in the following
illustration.
2. If additional CHV-TSTATEX devices are to be added, repeat step 1b for each
device. Each CHV-TSTATEX is assigned a different RF ID number as it is
added.
3. If necessary, double click a device to open the “Device Settings” window and
change the RF ID, as shown in the following illustration.
“Device Settings: Crestron CHV-TSTATEX” Window
Program Manager
NOTE: The ID code specified in the SIMPL Windows pr og ram must match the
RF ID of each unit. Refer to “Identity Code” on page 8.
Program Manager is the view where programmers “program” a Crestron control
system by assigning signals to symbols.
The symbol can be viewed by double clicking on the icon or dragging it into Detail View. Each signal in the symbol is described in the SIMPL Windows help file (
Crestron recommends using the latest programming software and that each device
contains the latest firmware to take advantage of the most recently released features.
However, before attempting to upload or upgrade it is necessary to establish
communication. Once communication has been esta bl i shed, files (for example,
programs or firmware) can be transferred to the control system (and/or device).
Finally, program checks can be performed (such as changing the device ID or
creating an IP table) to ensure proper functioning.
Establishing Communication
Use Crestron Toolbox for communicating with the CHV-TSTATEX; refer to the
Crestron Toolbox help file for details. There is a single method of communication:
indirect communication.
Indirect Communication
CEN-RFGW-EX
LAN
Control System
The CHV-TSTATEX connects to the CEN-RFGW-EX (gateway), which connects to
control system via Ethernet.
Establish communications between the PC and the control system as described in the
latest version of the 2-Series Control Systems Reference Guide (Doc. 6256). If
connecting to the MC3, refer to the latest version of the MC3 3-Series Control
System Operations Guide (Doc. 7095).
infiNET EX
Serial,
LAN
or USB
CHV-TSTATEX
PC Running
Crestron Toolbox
Programs and Firmware
Program or firmware files may be distributed from programmers to installers or from
Crestron to dealers. Firmware upgrades are available from the Crestron Web site as
new features are developed after product releases. One has the option to upload
programs via the programming software or to upload and upgrade via the Crestron
Toolbox. For details on uploading and upgrading, re fer to the SIMPL Windows help
file, or the Crestron Toolbox help file.
If a SIMPL Windows program is provided, it can be uploaded to the control system
using SIMPL Windows or Crestron Toolbox.
Check the Crestron website to find the latest firmware. (New users may be required
to register to obtain access to certain areas of the site, including the FTP site.)
infiNET EX™ Thermostat Crestron CHV-TSTATEX
Upgrade CHV-TSTATEX firmware via Crestron Toolbox.
1. Establish communications with the CHV-TSTATEX and display the
“System Info” window.
2. Select Functions | Firmware… to upgrade the CHV-TSTATEX firmware.
NOTE: Since the CHV-TSTATEX might be “asleep”, there may be a delay of one
minute or less before the update starts.
Program Checks
Using Crestron Toolbox, display the network device tree (Tools | Network Device
Tree View) to show all network devices connected to the control system and all
infiNET devices that have been acquired by the CHV-TSTATEX
(CEN-RFGW-EX). Right-click on the CHV-TSTATEX (CEN-RFGW-EX) to
display actions that can be performed on the CHV-TSTATEX (CEN-RFGW-EX).
The following table provides corrective action for possible trouble situations. If
further assistance is required, please contact a Crestron customer service
representative.
CHV-TSTATEX Troubleshooting
TROUBLE POSSIBLE
CAUSE(S)
No display
Device does
not follow
control system
commands.
Heating/Cooling
system is not
operating.
Cannot change
setpoint setting.
System cycles
too quickly.
No power from
system.
Incorrect mounting
to back plate.
Device is not
communicating
with the
CEN-RFGW-EX.
RF ID of device
(or the gateway
ID) is not set to
match the RF ID
of the SIMPL
Windows program.
No power to
thermostat.
The upper or lower
temperature limits
were reached.
Anticipator setting
is too low.
CORRECTIVE ACTION
Check for +24V on 24C connector.
Check circuit breaker powering
furnace or boiler.
Check thermostat wiring.
Check batteries (if running on battery
power).
Check thermostat mounting.
Open Crestron Toolbox and select the
Network Device Tree View. Expand
the tree until the gateway to be
managed is selected.
Right-click the NET ID of the selected
gateway to open the sub-menu and
select Functions | infiNET EX Gateway… If device is not listed,
acquire the device to the infiNET EX
network (refer to ”Basic Thermostat
Setup” which starts on page 17).
Use the Network Device Tree infiNET
EX network in Crestron Toolbox to poll
the infiNET EX network. Verify that the
RF ID for the infiNET EX device is set
to match the RF ID specified in the
SIMPL Windows program.
Check circuit breaker.
Check for +24V on 24C connector.
Check circuit breaker powering
furnace or boiler.
Recheck wiring connections.
Check batteries, replace if necessary.
Heat setpoint range is
38º to 89ºF (3º to 32ºC).
Cool setpoint range is 59º
to 99ºF (15º to 37ºC)
or 38º to 99ºF (3º to 37ºC) if extended
cool mode enabled.
Reprogram anticipator setting (refer to
“Setup Mode Parameters/Functions”
which starts on page 20).
Heat or cool
call occurs but
device does not
indicate a heat
or cool call.
Can not enter
Auto mode.
Steal power
function may be
causing problems
with HVAC
system.
Improper wiring
connections.
Auto mode is
disabled in setup.
Change Power DIP Switch to 24VAC
and ensure you have two AA batteries
installed.
Recheck wiring connections.
Reprogram Auto mode setting (AU) to
“S” (for single setpoint operation) or
“d” (for dual setpoint operation) (refer
to “Setup Mode
Parameters/Functions” which starts
on page 20).
Reference Documents
The latest version of all documents mentioned within the guide can be obtained from
the Crestron Web site (
List of Related Reference Documents
DOCUMENT TITLE
2-Series Control Systems Reference Guide
CEN-RFGW-EX infiNET EX Wireless Gateway
MC3 3-Series Control System
http://www.crestron.com/manuals).
Further Inquiries
If you cannot locate specific information or have questions after reviewing this
guide, please take advantage of Crestron's award winning customer service team by
calling Crestron at 1-888-CRESTRON [1-888- 273- 7 87 6] . For assistance in your
region, please refer to the Crestron Web site (
www.crestron.com) for a listing of
Crestron worldwide offices.
You can also log onto the online help section of the Crestron Web site
www.crestron.com/onlinehelp) to ask questions about Crestron products. First-time
(
users will need to establish a user account to fully benefit from all available features.
Future Updates
As Crestron improves functions, adds new features and extends the capabilities of
the CHV-TSTATEX, additional information may be made available as manual
updates. These updates are solely electronic and serve as intermediary supplements
prior to the release of a complete technical documentation revision.
Check the Crestron Web site periodically for manual update availability and its
relevance. Updates are identified as an “Addendum” in the Download column.
A heat pump extracts available heat from one area and transfers it to another. Even
cold air contains some heat and heat pumps can extract heat from the outside air on a
cold day and transfer it indoors to maintain a comfortable temperature. A heat pump
also works in reverse during the summer, extracting heat from indoors and
transferring it outdoors.
In the heating mode, the efficiency of a heat pump decreases as the outdoor air
temperature decreases.
Heat flows naturally from a warm area to a cooler area and the heat pump takes
advantage of this principle. The heat pump essentially consists of a compressor, an
inside coil and fan and an outside coil and fan. A refrigerant flows inside the coils,
under pressure applied by the compressor.
The refrigerant boils at a very low temperature (as low as -15° F) and becomes a
vapor, just as water becomes a vapor (steam) when boiled. This vapor is sucked into
the compressor where it becomes a high pressure, high temperature vapor.
When heating, the refrigerant is then forced through a coil within part of the heat
pump located indoors. A fan blows cool air over the coil, the vapor cools, turns back
to a liquid, releasing heat that is blown through a duct system to heat the house.
The cycle begins again as the cooled liquid refrigerant is pumped back outside after
releasing it’s heat. On the way, it passes through an expansion valve, lowering the
refrigerant's pressure and temperature again so it can boil more easily in the outdoor
coil.
In its cooling mode, the heat pump system works in reverse, extracting available heat
from indoors and transferring it outside.
Heat pumps are most economical when they can be used year-round for both winter
heating and summer cooling.
The efficiency of a heat pump varies significantly with the outdoor temperature.
While a heat pump may be twice as efficient as a conventional heating system at
50°F. When the outdoor temperature drops to less than 30°F, the heat pump must be
supplemented with an auxiliary heating system such as electric resistance. At
temperatures of 15°F or less the heat pump may shut off and the backup heating
system takes over. This is the heat pump balance point.
In a dual-fuel system, the heat pump is supplemented with a standard furnace, which
takes over when it becomes more efficient than the heat pump at very low
temperatures. The heat pump type setting (HP) of the Heat/Cool Type (HC) setup
parameter will allow aux heat to stage with the heat pump. A dual-fuel type setting
(dF) will not allow both systems to run at the same time.
Used to anticipate the drop or rise in temperature and energize the
appropriate system before reaching the set point. Anticipators affect how
tightly the setpoint temperature is maintained.
Auto Dead Band
Sets the minimum separation in auto mode between heat and cool setpoints
(with dual setpoints) or maximum drift before system latches alternate
mode (with single setpoint).
Balance Point
At low outdoor temperatures, the refrigeration cycle of a heat pump will not
be able to supply the heating requirements without the aid of a
supplementary heat source. At higher outdoor temperatures, it is inefficient
to use supplementary heat.
The heat pump balance point sets the minimum outdoor temperature
required to allow operation of the heat pump. Additionally, for conventional
heat pump system types (Heat/Cool Type setup parameter = HP), the AuxHeat Balance Point sets the maximum outdoor temperature to allow
operation of the auxiliary heat.
Since dual fuel system types only allow operation of one system at a time,
only one balance point is available.
Blower (Fan)
An air-handling device for moving air in a distribution system.
Call
A call is the action taken by the thermostat when it sends a signal to turn on
the heating or cooling system.
Dual Fuel
A heat pump used in conjunction with an existing fossil fueled furnace.
Emergency Heat (Supplementary Electric Heat)
The auxiliary (AUX) or emergency heat provided at temperatures below a
heat pump's balance point. It is usually electrical resistance heat.
Extended Cool
Extends the cool setpoint range to the full auto range of 38 to 99°F.
Forced Air
A type of heating system that uses a blower motor to move air through the
furnace and into the ductwork.
Furnace
Equipment used to convert heating energy, such as fuel, oil, gas or
electricity, to usable heat. It usually contains a heat exchanger, a blower and
the controls to operate the system.
Heat Pump
A unit that both cools and heats. A heat pump system can be either a split
system or a packaged system. A heat pump can be used in conjunction with
a gas/oil/LP furnace (using the furnace instead of electric resistance heat
when temperatures fall below about 35º F).
The total amount of moisture in air. Relative humidity (RH) is the amount
of moisture in air, relative to its total capability based upon its temperature
(dew point). Moisture will condense on surfaces that are below this dew
point.
HVAC
Heating, ventilation and air conditioning.
Interstage Differential
The proportional temperature error (0.5 to 3.0º) to trigger the second stage
(2-stage only), such as the aux heat for a heat pump type system.
Run Fan in Heat Calls
A device setting that activates the fan output during heat (W ) calls . (F or
heat pump or dual fuel system types, this setting activates the fan during
calls for auxiliary heat.
Setpoint
The user selectable temperature you want the system to maintain.
Time Delay (Timer Guards)
Refers to a safety device or circuit that will not allow restart for three
minutes.
1. No merchandise may be returned for credit, exchange or service without prior authorization
from CRESTRON. To obtain warranty service for CRESTRON products, contact an
authorized CRESTRON dealer. Only authorized CRESTRON dealers may contact the factory
and request an RMA (Return Merchandise Authorization) number. Enclose a note specifying
the nature of the problem, name and phone number of contact person, RMA number and
return address.
2. Products may be returned for credit, exchange or service with a CRESTRON Return
Merchandise Authorization (RMA) number. Authorized returns must be shipped freight
prepaid to CRESTRON, 6 Volvo Drive, Rockleigh, N.J. or its authorized subsidiaries, with
RMA number clearly marked on the outside of all cartons. Shipments arriving freight collect
or without an RMA number shall be subject to refusal. CRESTRON reserves the right in its
sole and absolute discretion to charge a 15% restocking fee plus shipping costs on any
products returned with an RMA.
3. Return freight charges following repair of items under warranty shall be paid by CRESTRON,
shipping by standard ground carrier. In the event repairs are found to be non-warranty, return
freight costs shall be paid by the purchaser.
CRESTRON Limited Warranty
CRESTRON ELECTRONICS, Inc. warrants its products to be free from manufacturing defects in mat erial s
and workmanship under normal use for a period of three (3) years from the date of purchase from
CRESTRON, with the following exceptions: disk drives and any other moving or rotating mechanical
parts, pan/tilt heads and power supplies are covered for a period of one (1) year; touch screen display and
overlay components are covered for 90 days; batteries and incandescent lamps are not covered.
This warranty extends to products purchased directly from CRESTRON or an authorized CRESTRON
dealer. Purchasers should inquire of the dealer regard ing the nature and extent of the dealer's warranty, if
any.
CRESTRON shall not be liable to honor the terms of this warranty if the product has been used in any
application other than that for which it was intended or if it has been subjected to misuse, accidental
damage, modification or improper installation procedures. Furthermore, this warranty does not cover any
product that has had the serial number altered, defaced or removed.
This warranty shall be the sole and exclusive remedy to the original purchaser. In no event shall
CRESTRON be liable for incidental or consequential damages of any kind (property or economic damages
inclusive) arising from the sale or use of this equipment. CRESTRON is not liable for any claim made by a
third party or made by the purchaser for a third party.
CRESTRON shall, at its option, repair or replace any product found defective, without charge for parts or
labor. Repaired or replaced equipment and parts supplied under this warranty shall be covered only by the
unexpired portion of the warranty.
Except as expressly set forth in this warranty, CRESTRON makes no other warranties, expressed or
implied, nor authorizes any other party to offer any warranty, including any implied warranties of
merchantability or fitness for a particular purpose. Any implied warranties that may be imposed by law are
limited to the terms of this limited warranty. This warranty statement supersedes all previous warranties.