Cree XSP Series Installation Instructions Manual

XSP Series
LED Street Light
Includes: XSPR™ Luminaires
When using electrical equipment, basic safety precautions should always be followed including the following:
READ AND FOLLOW ALL SAFETY INSTRUCTIONS
IMPORTANT SAFEGUARDS
1. DANGER- Risk of shock- Disconnect power before installation.
DANGER – Risque de choc – Couper l’alimentation avant l’installation.
2. This luminaire must be installed in accordance with the NEC or your local electrical
code. If you are not familiar with these codes and requirements, consult a qualied
electrician.
Ce produit doit être installé conformément à NEC ou votre code électrique local. Si vous n’êtes pas familier avec ces codes et ces exigences, veuillez contacter un
électricien qualié.
3. If NEMA photo control is installed refer to NEMA Receptacle section for instructions.
4. If mounting bolts are completely removed in the eld they should be hand threaded (prior to use of power tools) to ensure proper engagement of the thread when re­installing. Failure to pre-start threads may result in cross-threading or stripping of the bolts during reinstallation.
SAVE THESE INSTRUCTIONS FOR FUTURE REFERENCE
TO INSTALL:
1 2
Cover Tabs
TORQUE VALUES
Pipe
Size
1.66 in O.D.
2.38 in O.D.
1 of 2
Pipe Position
+5.0 degrees tilt 275 31
+2.5 degrees tilt 275 31
0 degrees (no tilt) 275 31
-2.5 degrees tilt 275 31
-5.0 degrees tilt 275 31
+5.0 degrees tilt 225 25
+2.5 degrees tilt 225 25
0 degrees (no tilt) 225 25
-2.5 degrees tilt 225 25
-5.0 degrees tilt 225 25
Bolt Torque
Required (in-lbs)
Pole
Mounting Bracket
Mounting Bracket
Bolts
Bolt Torque
Required (N-m)
Adjustment Steps
INSTALLATION INSTRUCTIONS
LUMINAIRE INSTALLATION
DO NOT remove splashguard from fixture. If
mounting fixture to 1.25 IP pipe (1.66 O.D.), there is no need to modify the splashguard. If mounting fixture onto 2.0 IP pipe (2.38 O.D.), remove the knockout of the splashguard thru the rear opening of the fixture while the fixture is closed.
To open cover, press tabs in on both sides of the cover and carefully let the cover swing down. Splashguard may dislodge from fixture, but should be repositioned once ready to mount. See
Figure 1.
Slide fixture on to pole through opening on the rear of housing and through splashguard. See
Figure 2.
Adjust leveling of fixture from side to side. To level from front to back, slide pole to different Adjustment Steps in upper housing. Each step changes the angle in 2.5° degree increments.
Once desired position is achieved, tighten mounting bolts to the appropriate torque values specified in TORQUE VALUES table on the back of the sheet. See Figure 2 (use 9/16" socket wrench).
IMPORTANT - DO NOT exceed these
torque levels on the mount bolts. Exceeding recommended torque value resulting in excessive deformation of mounting bracket will cause stripping of mount hardware which could lead to an unsafe mounting condition.
Reference Electrical Connections section for completing electrical connections.
CI379X20R3
LINE OR HOT 1
GREEN
LINE-BLACK
GROUND-GREEN
NEUTRAL-WHITE
DIM (-) GREY
DIM (+) VIOLET
NEUTRAL OR HOT 2
VIOLET
GREY
SUPPLY WIRING
(DIMMING OPTIONAL)
LUMINAIRE
OPTIONAL NEMA CONTENT
TERMINAL
BLOCK
DRV
A
B
C
D
E
F
G
H
I
DRV CRTL
1 2 3 4 5
3 4
DRV
A
B
C
D
E
F
G
H
I
DRV CRTL
1 2 3 4 5
NEMA® RECEPTACLE (OPTIONAL) STEP 1:
Rotational adjustment of the photo control is
tool-less.
Engage/install photo control into NEMA® receptacle on top of the fixture.
Firmly rotate photo-control with its photo­eye approximately in the ‘N’ north direction. Some photo-controls operate best somewhere between NW and NE.
FIELD ADJUSTABLE DIMMING (OPTIONAL)
NOTE: This luminaire may be provided with
field adjustable dimming. Luminaires leave the factory adjusted to the maximum setting specified when ordered. Verify which dimming module, either Figure 3 or 4 is in the luminaire and visit the product specification sheet for lumen and power multipliers for each field adjustable output dim setting.
The Dimming module is located inside the luminaire.
ELECTRICAL CONNECTIONS STEP 1:
Make the following Electrical Connections to the terminal block:
a. For 120/277V connect the black fixture lead to the voltage supply
position of the terminal block (Hot 1 for 208/240V wiring).
b. For 120/277V connect the white fixture lead to the neutral supply
position of the terminal block or (Hot 2 for 208/240V wiring).
c. Connect the green or green/yellow ground lead to the green wire
position of the terminal block.
Dimming capabilities may be accessible through optional Nema receptacle. NOTE: Brown and orange leads on optional NEMA Receptacle are not used and are capped off. No electrical connection is necessary.
d. If Dimming is an option; connect the violet dimming positive lead
to the supply dimming positive lead. If dimming is not being used ensure to cap off the violet lead.
e. If Dimming is an option; connect the grey dimming
to the supply dimming negative lead. If dimming is not being used ensure to cap off the grey lead.
f. If dimming through Nema is an option, install photo control with
dimming capabilities.
Push excess supply wires into pole.
Close cover, making sure that no wires are pinched and latches are fully engaged.
Establish the desired input power multiplier by referring to the product dimming spec sheet and turn the switch to the correlating position. For the half moon shaped dial (Figure 3) the center of the flat side should be turned to the desired setting.
Adjust the Dimming Module, see Figure 3 or 4, to the selected position and close the cover
ensuring no wires are pinched. NOTE: The Utility Option will be limited to the highest setting ordered.
negative lead
© 2018 Cree, Inc. All rights reserved. For informational purposes only. Content is subject to change. See http://lighting.cree.com/warranty for warranty and specifications. Cree® is a registered trademark, and the Cree logo and XSPR™ are trademarks of Cree, Inc.
2 of 2
www.cree.com/lighting
CI379X20R3
Loading...
+ 2 hidden pages