VITP-PD
Ceiling Presence Detector
The VITP-PD presence detector switches are designed to provide automatic control of lighting via the Vitesse Plus marshalling box. They detect movement using a
PIR sensor and turn the load on. When an area is no longer occupied the load will
switch off after an adjustable time out period.
An adjustable internal light sensor provides additional energy saving in lighting
applications. When an area is occupied lighting is only switched on when the level
of natural light is below a preset level.
When the unit is first powered up the PIR sensor will always detect immediately
regardless of whether the room is occupied.
Wire the products simply by connecting to the relevant port of the
Vitesse Plus marshalling box using a Cat5 patch cord. An additional
RJ45 connector is provided to daisy chain sensors together.
The detector should be sited so that the occupants of the room fall
inside the detection pattern shown overleaf, at a recommended
height of 2.8m on the ceiling. Note that the lower the sensor is installed the smaller the detection range will be, subject to the parameters shown on the diagram.
Product Guide
Overview
Wiring & Fixing
Avoid direct sunlight entering the sensor.
Do not site within 1m of forced air heating
or ventilation.
Do not site within 1m of any lighting.
Do not fix to a vibrating surface.
FLUSH FIXING
Warning - be careful bending
springs when mounting unit.
SURFACE FIXING
1 5
50mm or 60mm fixing
Hole Ø64mm
1 2 3
2 3
4
4
6
Pull out spring tab
Installation
1. Connect the unit to the marshalling box.
2. Set the LUX level to maximum and the time to minimum.
3. Apply power, the load should come on immediately.
4. Vacate the room or remain very still and wait for the load to switch off (should take no more than 2 minutes).
5. Check that the load switches on when movement is detected.
6. To set the final LUX level wait until the level of natural daylight is just enough that lighting is required. Starting with the LUX control fully clockwise (at minimum), very slowly turn the control anti-clockwise until the lights come on. Note that when the LUX control is at maximum then the
lights will always come on with occupancy.
7. Set the time required.
Ref %WD156 Issue 3

Detection Pattern
Fault Finding
LOAD DOES NOT COME ON
Check to see if the Vitesse Plus marshalling
box is powered up and the wiring is correct.
If the supply and wiring are good, check the
LUX level setting. Increase the LUX level setting to allow the controller to turn on at higher
ambient natural light level.
If the detection range is smaller than expected,
check the diagram above. Rotating the sensor
slightly may improve the range.
LIGHTS DO NOT GO OFF
Ensure that the area is left unoccupied for
longer than the selected timer setting.
Make sure that the sensor is not adjacent to
circulating air, heaters or lamps.
Specification
LOAD
See datasheet for Vitesse Plus marshalling box
SUPPLY VOLTAGE 12VDC
TIME OUT PERIOD Adjustable 10 seconds to 30 minutes
LIGHT LEVEL Light to dark
FIXING METHOD Flush fixing in 64mm hole
MATERIAL Flame retardant ABS
TYPE Class 2
TEMPERATURE -10°C to 35°C
CONFORMITY EMC-89/336/EEC
LVD-73/23/EEC
Part Numbers
VITP-PD Vitesse Plus ceiling mounted presence detector
DBB Surface mounting box
IMPORTANT NOTICE!
This device should be installed by a
qualified electrician in accordance with
the latest edition of the IEE wiring
regulations.