Microwave Presence/Absence Detector IR & Ceiling Rose
Overview
The VITMR-MWS6-PRM Microwave presence detector provides automatic control of lighting loads. This sensor is supplied pre-wired with a 3m lead and include a ceiling rose for ease of installation.
The VITMR-MWS6-PRM detects movement using a highly sensitive microwave detector. This works by emitting low power microwave signals and measuring the reflections as the signals bounce off moving objects.
The output channel comprises a mains voltage relay capable of simple on/off switching.
Functioning as a presence detector, the unit can turn lights on when a room is occupied and off when the room is empty. Optional settings allow lights to be turned off in response to ambient daylight.
Front features
Mounting Bezel
Sensor Lens
which covers...
Microwave Sensor
IR Receiver
Light Level Sensor
Status LEDs
All functionality is fully programmable using an IR handset.
Features
Microwave Sensor
Detects movement within the unit’s detection range,
allowing load control in response to changes in occupancy.
IR Receiver
Receives control and programming commands from an IR (infrared) handset.
Light Level Sensor
Measures the overall light level in the detection area
Status LEDs The LED flashes Red to indicate the following:
Walk Test LED active
Valid setting received
when movement is detected
Detection diagram
Area of lower sensitivity Area of high sensitivity
Note. If the range is compromised by the ceiling construction / material. Add the supplied 20mm spacer ring. See page 4 for fitting details.
2
Installation
Choosing a Suitable Location
The detector should be sited so that the occupants of the room fall inside the detection pattern shown opposite).
Avoid positioning the unit where direct sunlight may enter the sensor element. Do not site the sensor within 1m of any lighting, forced air heating or ventilation. Do not fix the sensor to an unstable or vibrating surface. Avoid metallic objects directly in front of the sensor head.
Ceiling rose wiring
CIRCUIT PROTECTION
Live
(IF REQUIRED)
Live supply
LUMINAIRE
Earth
Neutral
Permanent Live
Each pole has two screw terminals.
Each terminal accepts 1 x 2.5mm2
Internal detector wiring
Screw fixings to conduit box
VITM-ROSE
Where absence detection or override is required, wire the switch directly to the detector or use the VITM4 series of marshalling boxes
Power-up test procedure
When power is applied to the unit, the load will turn on immediately.
Set the timeout to 10 seconds, vacate the room or remain very still and wait for the load to switch off .
Check that the load switches on when movement is detected.
The unit is now ready for programming.
Sensor functionality
Presence detection
When movement is detected the load will automatically turn on. When the area is no longer occupied the load will
automatically switch off after an adjustable time period.
In either case, sensitivity to movement of the Microwave sensor can be adjusted using the Sensitivity parameter.
HINT: To assist in setting the Sensitivity, turn on the Walk Test LED which will flash red when movement is detected.
Switch Level On/Off
Occupancy detection can be made dependant on the ambient light level using the Lux On Level and Lux Off Level parameters.