The MWS6-DD microwave presence detector provides
automatic control of lighting loads with optional manual
control. The MWS6-DD detects movement using a highly
sensitive microwave detector. This works by emitting low
power microwave signals and measuring the reflections as
the signals bounce off moving objects.
Output Channel 1 comprises a mains voltage relay capable
of simple on/off switching, while Output Channel 2 provides
dimmable control of either DALI or DSI type ballasts.
Functioning as a presence detector, the unit can turn lights
on when a room is occupied and off when the room is
empty. Optional settings allow lights to be turned off in
response to ambient daylight, or to implement a maintained
illuminance (daylight harvesting) system.
The flexibility of having two channels and two switch inputs
allows the following example scenarios:
Dim an outside row of luminaires whilst internal fittings
are switched
Provide absence detection for two separate channels
Maintained illuminance system with manual up/down
controls
All functionality is fully programmable using an IR handset.
Front features
Mounting Bezel
Back features
Retaining Spring
Power Input
& Switched
Output Connector
(Channel 1)
Sensor Lens
which covers...
Microwave Sensor
IR Receiver
Light Level Sensor
Status LEDs
Dimmable
Control Output
Connector
(Channel 2)
Features
Microwave Sensor
Detects movement within the unit’s detection range,
allowing load control in response to changes in occupancy.
IR Receiver
Receives control and programming commands from an
IR (infrared) handset.
Light Level Sensor
Measures the overall light level in the detection area
Status LEDs
The LED flashes Red to indicate the following:
Walk Test LED active
Valid setting received
Power Input & Switched Output Connector (Channel 1)
Used to connect mains power to the unit and to connect a
switched load.
Dimmable Control Output Connector (Channel 2)
Used to connect DSI/DALI controllable ballasts and
transformers for dimmable loads.
Switch Input Connector
Two input terminals can be used to manually override the
dimming levels and override the lights on or off.
when movement is detected
Retaining Spring
Switch Input
Connector
Detection diagram
Area of lower sensitivity Area of high sensitivity
Note. If the range is compromised by the ceiling construction /
material. Add the supplied 20mm spacer ring. See page 4 for
fitting details.
2
Installation
Choosing a Suitable Location
The detector should be sited so that the occupants of the room fall inside the detection pattern shown opposite).
Avoid positioning the unit where direct sunlight may enter the sensor element.
Do not site the sensor within 1m of any lighting, forced air heating or ventilation.
Do not fix the sensor to an unstable or vibrating surface.
Avoid metallic objects directly in front of the sensor head.
Sensor functionality
Detection Mode
The Detection Mode for both output Channels 1 and 2 can be set to behave in Presence or Absence mode:
Presence When movement is detected the load will automatically turn on. When the area is no longer occupied the
load will automatically switch off after an adjustable time period.
Absence The load is manually switched on. When the area is no longer occupied the load will automatically switch
off after the adjustable time period has elapsed.
In either case, sensitivity to movement of the microwave sensor can be adjusted using the Sensitivity parameter.
HINT: To assist in setting the Sensitivity, turn on the Walk Test LED which will flash red when movement is detected.
Switch Level On/Off
Occupancy detection can be made dependant on the ambient light level using the Lux On Level and Lux Off Level
parameters.
Maintained Illuminance (daylight harvesting)
The detector measures the overall light level in the detection area and calculates the correct output for the luminaires, to
achieve a preset lux level (maintained illuminance or daylight harvesting).
Burn-in
Overview
It is a requirement of many fluorescent lamp manufacturers to have the lamps on at maximum output for a period of time
to guarantee lamp life (refer to the manufacturer’s datasheet for details) As this MWS6-DD is able to dim the lamps
using DALI/DSI, the product provides a facility to disable this for a given period of time.
Operation
By setting the “Burn in” parameter, you can select a time during which the lamps are not allowed to deviate from
maximum output. The unit counts the time, and even remembers how long has elapsed in the event of a power failure.
To cancel the burn in function, simply select a time of 0. Note that when the lamps are changed, the burn in time should
be set again.
3
Installation
The MWS6-DD is designed to be mounted using either:
Flush fixing, or
Surface fixing, using the optional Surface Mounting Box (part no. DBB).
Both methods are illustrated below.
Flush Fixing
Warning - be careful
bending springs
when mounting unit.
Surface Fixing
1 2 4
Hole Ø64mm
If the range is compromised by
the ceiling construction /
material. Add the supplied
20mm spacer ring.
1
50mm or 60mm fixing centres
2
Pull out spring tab and rotate
spring arm as shown
3
3
5
4
Wire stripping details
Important
Ensure that the cables are formed as shown
before affixing the cable clamp. The clamp
MUST clamp the outer sheath(s) only.
Bend cores as shown.
Readback function (UNLCDHS handset only)
The UNLCDHS has the ability to read back the settings stored in a device.
To read back individual parameters
Navigate to the parameter and press the ‘R’ (Read) button whilst pointing at the device. The handset will click
when the parameter has been read back, the device will flash its LED, and the value will be shown against the
parameter in the menu.
To read back all of the parameters in a menu
Press and hold the ‘R’ (Read) button for more than 1 second.
The handset will click every time a parameter is received
The device will show multiple flashes of its LED
All of the values will be shown against the parameters in the menu.
The individual parameters may be edited and then saved as a ‘Macro’.
Notes
If a parameter(s) has been missed because of a communication error, the missing value(s) is replaced by dashes.
When reading back, the Channel 1 relay (where fitted) will temporarily be switched off, and will return to it’s normal
state 2 seconds after the read back has been completed.
4
L/OUT
L
N
EBDSPIR-DD SENSOR
SW1/UP
DIM+
DIM-
SW2
DOWN
DIMMING
BALLAST
DIMMING LUMINAIRE
(DSI or DALI)
CIRCUIT PROTECTION
(IF REQUIRED)
LIVE
NEUTRAL
CENTRE BIASED
RETRACTIVE SWITCH
(240V SWITCHING)
Optional for presence,
mandatory for absence detection
Wiring diagrams
Channel 1 (switched output) of the MWS6-DD can either
be used to switch a separate channel of standard, nondimming luminaires, or to isolate the mains supply to
dimming ballasts (saving on the standby current of the
ballasts).
Multiple luminaires may be connected in parallel to
Channel 1 (via the N and L/Out terminals) as long as the
maximum total load is not exceeded.
used to control the light output of luminaires that are fitted
with dimming ballasts/transformers.
The ballasts/transformers can be connected in parallel to
Channel 2 (via the DIM– and DIM+ terminals). Refer to the
specification on page 12 for ballast quantities.
The wiring examples below show common methods of
connecting the output channels for a single detector unit.
Channel 2 (dimmable output) of the MWS6-DD can be
Single channel dimming
Functions: Switches the luminaire with occupancy and maintains illuminance. Dims and switches using optional centre
biased retractive switch (MK K4900 or similar).
Configured to presence detection: Turns on automatically with occupancy. Maintains illuminance. Press and release
down switch to turn off. Press and release up switch to turn back on. Press and hold up switch to dim up, press and hold
down switch to dim down. Turns off after occupancy.
Configured to absence detection: Press and release up switch to turn on. Maintains illuminance. Press and release
down switch to turn off. Press and hold up switch to dim up, press and hold down switch to dim down. Turns off after
occupancy.
Channel mode: Set to “Switch and dim together”.
Switch mode: Set to “2 position switch together”.
5
L/OUT
L
N
EBDSPIR-DD SENSOR
SW1/UP
SW2
DOWN
PLEASE NOTE THAT THE
DIMMING SIGNAL IS USED TO
SWITCH THE DIMMING
LUMINAIRE ON/OFF AND
THEREFORE THE 240V FEED
TO THE LUMINAIRE FITTING
MUST COME FROM THE
PERMANENT LIVE SUPPLY
SWITCH 1 - MOMENTARY
PUSH TO MAKE SWITCH
(240V SWITCHING)
Optional for presence,
mandatory for absence detection
SWITCH 2 - MOMENTARY
PUSH TO MAKE SWITCH
(240V SWITCHING)
Optional for presence,
mandatory for absence detection
DIMMING
BALLAST
DIMMING LUMINAIRE
(DSI or DALI)
LUMINAIRE
(NON-DIMMING)
CIRCUIT PROTECTION
(IF REQUIRED)
LIVE
NEUTRAL
DIM+
DIM-
PLEASE NOTE THAT THE CENTRE BIASED RETRACTIVE
SWITCH WILL PROVIDE CONTROL FOR THE DIMMING
LUMAIRE(S) ONLY. THE NON-DIMMING LUMINAIRE(S) WILL
BE CONTROLLED ONLY BY THE SENSOR
L/OUT
L
N
EBDSPIR-DD SENSOR
SW1/UP
SW2
DOWN
PLEASE NOTE THAT THE
DIMMING SIGNAL IS USED TO
SWITCH THE DIMMING
LUMINAIRE ON/OFF AND
THEREFORE THE 240V FEED
TO THE LUMINAIRE FITTING
MUST COME FROM THE
PERMANENT LIVE SUPPLY
DIMMING
BALLAST
DIMMING LUMINAIRE
(DSI or DALI)
LUMINAIRE
(NON-DIMMING)
CIRCUIT PROTECTION
(IF REQUIRED)
LIVE
NEUTRAL
CENTRE BIASED
RETRACTIVE SWITCH
(240V SWITCHING)
Optional for presence,
mandatory for absence detection
DIM+
DIM-
Two channel, individual switches
Functions: Switches both channels with occupancy. Maintains illuminance, dims and switches the dimming channel
using optional single position retractive switch (switch 2). Switches the switching channel using the optional single
position retractive switch (switch 1).
Configured to presence detection: Turns on automatically with occupancy. Maintains illuminance (dimming channel
only). Press and release switch to toggle output. Press and hold switch to dim up and down (reverses direction with
each press). Turns off after occupancy.
Configured to absence detection: Press and release switch to turn on. Maintains illuminance (dimming channel only).
Press and release switch to turn off. Press and hold switch to dim up and down (reverses direction with each press).
Turns off after occupancy.
Channel mode: Set to “Switch and dim separate”
Switch mode: Set to “1 position switch separate”
Two channel, single switch
Functions: Switches both channels with occupancy. Maintains illuminance, dims and switches the dimming channel
using optional centre biased retractive switch .
Configured to presence detection: Turns on automatically with occupancy. Maintains illuminance (dimming channel
only). Press and release down switch to turn off. Press and release up switch to turn back on. Press and hold up switch
to dim up, press and hold down switch to dim down. Turns off after occupancy. Channel 1 does not operate with switch.
Configured to absence detection: Press and release up switch to turn on. Maintains illuminance (dimming channel
only). Press and release down switch to turn off. Press and hold up switch to dim up, press and hold down switch to dim
down. Turns off after occupancy. Channel 1 does not operate with switch.
Channel mode: Set to “Switch and dim separate”
Switch mode: Set to “2 position switch separate”
6
L/OUT
L
N
EBDSPIR-DD SENSOR
SW1/UP
SW2
DOWN
CIRCUIT PROTECTION
(IF REQUIRED)
LIVE
NEUTRAL
CENTRE BIASED
RETRACTIVE SWITCH
(240V SWITCHING)
Optional for presence,
mandatory for absence detection
LUMINAIRE
(NON-DIMMING)
DIM+
DIM-
Wiring diagrams (cont.)
Single channel switching
Functions: Switches channel 1 only with occupancy, optional override switch. No dimming output.
Configured to presence detection: Turns on automatically with occupancy. Press and release down switch to turn off.
Press and release up switch to turn back on. Turns off after occupancy.
Configured to absence detection: Press and release up switch to turn on. Press and release down switch to turn off.
Turns off after occupancy.
Channel mode: Set to “Switch only”
Switch mode: Set to “2 position switch together”. Note: a single position switch can be used instead to toggle the
output, set to “1 position switch separate”.
Power-up test procedure
When power is applied to the unit, the load will turn on immediately.
Set the timeout to 10 seconds, vacate the room or remain very still and wait for the load to switch off .
Check that the load switches on when movement is detected.
The unit is now ready for programming.
Fault finding
What if the load does not turn ON?
Check that the live supply to the circuit is good.
Check that the load is functioning by bypassing the sensor (e.g. link terminals L and L/ Out on Channel1).
If the detection range is smaller than expected, check the diagram on page 2. Rotating the sensor slightly may
improve the detection range. If still reduced it may be compromised by the ceiling construction / material. Add the
supplied 20mm spacer ring. See page 4 for fitting details.
HINT: The Walk Test LED function can be used to check that the unit is detecting movement in the required area.
What if the load does not turn OFF?
Ensure that the area is left unoccupied for longer than the Time Out Period.
Make sure that the sensor is not adjacent to vibrating surfaces or objects (e.g. ventilation equipment).
The unit may pick up movement through glass, thin partitions or walls. Reduce the sensitivity.
7
Basic programming
The functionality of the MWS6-DD is controlled by a number of parameters which can be
changed or programmed by any of the following devices:
UHS5 Infrared Handset. See below for programmable functions.
UNLCDHS Infrared Handset (with LCD). See user guide for full programming details.
For most basic programming operations the UHS5 handset can be used and the following procedures
are based on using this device.
Point the handset at the Sensor and send the required programming commands to the unit as shown
below.
Valid commands will be indicated by a red LED flash. See page 1 for details of other LED responses.
Note: other functions on the UHS5 which are not shown below are not applicable to this product.
Number of Shift key presses
Parameter
Name
Default
Value
0 1 2 3 UHS5 Handset Graphics Description
SHIFT 1 SHIFT 2 SHIFT 1 SHIFT 2
SHIFT 1 SHIFT 2
SHIFT 1 SHIFT 2
Button Activation
On / Raise On Raise
Off / Lower Off Lower
Walk test Off On Off
Time Out
(Time
adjustment)
Lux on
level
(Switch
level on)
Light Level 6 (600) 2 (200)
Lux off
level
(Switch
level off)
Load Type DALI 2-DALI
20 mins 1, 10 &
20
minutes
5, 15 &
30
minutes
10
seconds
9 2, 5 & 7 4, 6 & 9
4 (400)
5 (500)
7 (700)
6 (600)
9 (999)
9 2, 5 & 7 4, 6 & 9
2-DALI
7-DSI
on
Turn lights on or to raise lights.
Turn lights off or to lower lights.
When set to On this causes a red LED to flash on
the sensor when it detects movement. Use this
feature to check for adequate sensitivity levels.
Once the detector is turned on, this value sets
how long the lights will stay on once movement
has ceased.
Lux level setting to prevent the luminaires being
switched on if the ambient light level is sufficient
(adjustable between 1 and 9). The luminaires will
always be switched on at level 9.
Sets a target light level to be maintained by the
lighting system.
9 (999) = disabled.
Lux level setting to switch the luminaires off during
occupancy if the ambient light level goes above
the setting (adjustable between 1 and 9). Level 9
will always keep the lights on. This setting can be
used for “window row switching”.
Note: the Lux Off Level value must always be
greater than the Lux On Level value.
Sets the ballast control protocol to be used by the
output channel.
Sensitivity 9 1, 5 & 9 3, 6 & 8
Defaults D
Burn-in 0 0 50 100
Presence /
Presence Presence Absence
Absence
Shift
8
Sensitivity level for detecting movement.
1 = low sensitivity
9 = high sensitivity
Returns the unit to the default settings.
Determines how long the output will be at 100%
so that lamps ‘burn-in’. The ’burn-in’ time is not
affected by power supply interruptions.
Presence mode allows the output to turn on when
movement is detected and off when movement
ceases. Absence mode allows the output to turn
off when movement ceases, but must be manually
turned on first.
Use this button to select the settings in red and
blue signified by the ‘Shift 1’ and ‘Shift 2’ LEDs
Advanced programming
Parameter Name Default Value Range / Options Description
Detector Parameters
Walk Test LED Off On or Off
Time Out
(Time adjustment)
Manual Time Out 10 minutes 0-99 minutes
Sensitivity On 9 1 (min) to 9 (max)
Sensitivity Off 9 1 (min) to 9 (max)
Lux time 0 0 (disabled)
Power Up State On On or Off
Disable Detector N Y or N
On Delay 0 minutes 0-99 minutes
Inhibit 4 seconds 1 to 99 seconds
Factory default
20 minutes 0-99 minutes
1-99 minutes
-
-
When set to On this causes a red LED to flash on the sensor when it detects
movement. Use this feature to check for adequate sensitivity levels.
Once the detector is turned on, this value sets how long the lights will stay on once
movement has ceased. Select 0 for 10 second delay – use for commissioning only.
When a manual operation occurs, either via the switch input or the infrared, it
invokes the timeout period.
Example 1: a detector in presence mode has a detector timeout of 15 minutes and
a manual timeout of 3 minutes. W hen the user leaves the room they press the off
button. The sensor will revert to automatic after 3 minutes, and then walking back
in the room will turn the lights on.
Example 2: using the settings above, the user turns the lights off (say for a
presentation) but stays in the room. Every time a movement is detected, the
manual timeout period is re-triggered, but when it doesn’t pick up for the short
timeout period, the sensor will timeout and revert to automatic. This means the
lights may turn on inadvertently during the presentation, if the occupants are still
for the manual timeout period, so adjust the timing carefully.
Sensitivity level for detecting movement when the detector is already on. *UHS5
sets Sensitivity On and Off to the same value.
Sensitivity level for detecting movement when the detector is off. *UHS5 sets
Sensitivity On and Off to the same value.
If the detector measures the lux level and decides that the output needs switching
on or off as a consequence, the lux time must elapse first. If at any time during the
timed delay the lux change reverses then the process is cancelled. Lux Time
enables absence detection to be implemented with a lux off level set. When the
button is pressed, the lights will go on, regardless of ambient light level. However,
if there is sufficient ambient light, they will turn off again after the Lux Time. Note
that whenever the an external switch is pressed, whether in absence or presence
mode, if the lights were out because of the lux level, they will be immediately
turned on again for at least the Lux Time.
Select No for a 30 second delay on start up. If Yes is selected, there will be no
delay on start up and the detector will always power up detecting.
Disables detection, leaving the relay output permanently off with the dimming
output operational. This mode is used when the unit is for maintained illuminance
only.
The On Delay to allows the first channel to switch on after the second channel. A
typical application for this would be where a detector is controlling lighting and air
conditioning in an area. When the occupant is detected, the lighting will be turned
on immediately, whereas the air conditioning may be turned on after 15 minutes. If
the area is vacated and the detector times out before the delay, then the air
conditioning would never go on. The delay can be set only for channel 1 using the
on delay parameter.
When the detector turns off, a delay is instigated to prevent retriggering. In certain
circumstances this delay may not be enough. T his parameter allows the delay to
be changed.
Restores factory default settings
UHS5 UNLCDHS
*
*
Channel Modes
Switch only - -
Switch and dim
together
Switch and dim
separate
User Modes
Raise
Lower
Override On
Override Off
Cancel
Default -
- -
- -
- -
- -
- -
- -
Usually used for absence detection - in this mode the dimming channel is not used.
The detector will switch and dim the lighting together.
Provides 2 channel operation – Channel 1 is switched via the relay output, and
Channel 2 is dimmed / switched via the dimming output.
Increase light level. Reverts when occupancy cycle complete.
Decrease light level. Reverts when occupancy cycle complete.
If the lights are off, sending the IR command will turn them on immediately and
revert to automatic operation using the manual timeout period.
If the lights are on, sending the IR command will turn them off immediately. After
the manual timeout period (described above), the sensor will revert to automatic.
Cancels the on or off override, returning the detector to normal operation.
9
Advanced programming
Parameter Name Default Value Range / Options Description
Channel 1 –Switching Channel
Detection Mode Presence Presence or
Lux on level
(Switch level on)
Lux off level
(Switch level off)
Channel 2 -Dimming Channel
Detection Mode Presence Presence or
Lux on level
(Switch level on)
Lux off level
(Switch level off)
Light Level
(maintained illuminance)
Load Type DALI DSI
Max Value 100% 0 to 100%
Min Value 0% 0 to 100%
On value 99 0 to 99
Off value 0 0 to 99
Burn-in 0 0 (disabled) or
Fade value 10 0 to 99
Fade mins 0 0 to 99
Speed On 40 Measured in 0.1
Speed Set 5 Measured in 0.1
Set Seconds 120 1 to 999 seconds
9 1 to 9
9 1 to 9
9 1 to 9
9 1 to 9
600 1 to 998 (999
Absence
For a higher resolution
a scale of 101-199 is
available
For a higher resolution
a scale of 101-199 is
available
Absence
For a higher resolution
a scale of 101-199 is
available
For a higher resolution
a scale of 101-199 is
available
disabled)
DALI
DALI On
1 to 999 hours
sec intervals.
sec intervals.
Presence mode allows the output to turn on when movement is detected and off
when movement ceases. Absence mode allows the output to turn off when
movement ceases, but must be manually turned on first.
Sets a minimum light level below which the microwave sensor is enabled, allowing
lights to be turned on by movement.
Note: the Lux Level Off value must always be greater than the Lux Level On value.
Sets a maximum light level above which the microwave sensor is disabled,
preventing lights from being turned on by movement.
Presence mode allows the output to turn on when movement is detected and off
when movement ceases. Absence mode allows the output to turn off when
movement ceases, but must be manually turned on first.
Sets a minimum light level below which the microwave sensor is enabled, allowing
lights to be turned on by movement.
Note: the Lux Level Off value must always be greater than the Lux Level On value.
Sets a maximum light level above which the microwave sensor is disabled,
preventing lights from being turned on by movement.
Sets a target light level to be maintained by the lighting system.
Sets the ballast control protocol to DSI.
Sets the ballast control protocol to DALI.
DALI On provides a permanent voltage to DALI ballasts when DALI has not been
implemented correctly in the ballast. Maximum number of ballasts is 5 unless the
relay is disabled then it is 10.
Maximum dimming output level.
Minimum dimming output level.
Dimming output level when switched on (0-99).
Dimming output level when switched off (0-99). If a non-zero off value is set, then
the output will toggle between this value and completely off depending on the
switch level on and off values. For example, if it is light outside, the fittings will be
off if there is no occupancy. If it is dark outside, they will adopt the preset off value.
This feature is only enabled if ‘Min value’ is set to 99.
Determines how long the output will be at 100% so that lamps ‘burn-in’. The ’burnin’ time is not affected by power supply interruptions.
After occupancy ceases, this dimming output level is loaded for the fade time
(adjustable between 0 and 99).
This is the time period (adjustable between 0 and 99 minutes) that the luminaire
will be held at the fade value before turning off. A value of 0 disables the fade
function.
Determines the dimming response speed after the setup time has finished.
Determines the dimming response speed during the set up time. Measured in 0.1
sec intervals. If set to 0 will disable dimming for “Set seconds” below, used if
fittings are required to warm up before dimming.
Determines how long the dimming response set-up period lasts on power-up or on
setting change. This enables the desired lux level to be achieved rapidly when the
lights come on, or during setup.
UHS5 UNLCDHS
Switch Modes
2 position switch
together
2 position switch
separate
1 position switch
together
1 position switch
separate
10
Default
- -
- -
- -
-
A single centre biased retractive switch will be used to control both channels
together.
A single centre biased retractive switch will be used to control only the dimming
channel.
A single position retractive switch controls both channels together.
Two single position retractive switches, controlling the channels separately.
This page intentionally left blank
11
Technical data
Dimensions See diagrams opposite
Weight 0.15kg
Supply Voltage 230VAC +/- 10%
Frequency 50Hz
Maximum Load Channel 1 (switching):
10A of lighting and/or ventilation
including incandescent, fluorescent,
compact fluorescent, low voltage (by
switching the primary of transformer).
Channel 2 (dimming):
Maximum number of DSI or DALI
ballasts is 10 unless the relay is
disabled then it is 20.
Power consumption On 1100mW, Off 664mW
Dimming output Basic insulation only. Although low
voltage, this is not an SELV output
and should be treated as if mains
potential. Use mains rated wiring.
Terminal Capacity 2.5mm2
Temperature -10ºC to 50ºC
Humidity 5 to 95% non-condensing
Material (casing) Flame retardant ABS and PC/ABS
Type Class 2
Microwave frequency 5.8 GHz
Safety The microwave radiation emitted
by these units is extremely low
power and complies with ANSI
standard “IEEEC95.1-1999
Standard for Safety Levels with
Respect to Human Exposure to
Radio Frequency Electromagnetic
Fields 3kHz 300GHz.”
IP rating IP40
Compliance EMC-2004/108/EC
LVD-2006/95/EC
MWS6-DD
DBB
Part numbers
Part number Description
Detector
Accessories
IMPORTANT NOTICE!
This device should be installed by a qualified electrician in
accordance with the latest edition of the IEE Wiring
Regulations and any applicable Building Regulations.
FM 45789 EMS 534520
Due to our policy of continual product improvement CP Electronics reserves the right to alter the specification of this product without prior notice.
12
MWS6-DD Ceiling microwave presence detector – DALI / DSI dimming
DBB Surface mounting box
UHS5 Programming IR handset
UNLCDHS Universal LCD IR handset